Switching function Normally open (NO)
Output type PNP
Rated operating distance sn40 mm
Installation non-flush
Output polarity DC
Model Number
NBN40-U1K-E2-3G-3D
Features
• Sensor head bidirectional and rotatable
• 40 mm non-flush
•3-wire DC
• 4 LEDs indicator for 360° visibility
• ATEX-approval for zone 2 and zone 22
Accessories
MHW 01
Modular mounting bracket
Assured operating distance s
Actual operating distance sr36 ... 44 mm typ. 40 mm
Reduction factor r
Reduction factor rCu 0.3
Reduction factor r
Reduction factor r
Output type 3-wire
Nominal ratings
Operating voltage UB10 ... 30 V DC
Switching frequency f0 ... 150 Hz
Hysteresis Htyp. 5 %
Reverse polarity protection reverse polarity protected
Short-circuit protection pulsing
Vol tag e d rop Ud≤ 2 V
Vol tag e d rop at I
Vol tage dro p IL = 1 mA, switching element
on U
d
Vol tag e dr op I
on U
d
Vol tag e dr op IL = 20 mA, switching element
on U
d
Vol tag e dr op I
on U
d
Vol tage dro p IL = 100 mA, switching element on U
Vol tage dro p I
ment on U
Operating current I
Off-state current I
Off-state current TU =40 °C, switching ele-
ment off
No-load supply current I
Time delay before availability t
Operating voltage indicator LED, green
Switching state indicator LED, yellow
Functional safety related parameters
MTTFd 1358 a
Mission Time (T
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Connection type screw terminals
Information for connection A maximum of two conductors with the same core cross section
Core cross-section up to 2.5 mm
Minimum core cross-section
Maximum core cross-section
Housing material PA
Sensing face PA
Degree of protection IP68 / IP69K
Mass 225 g
Note Tightening torque: 1.8 Nm (housing)
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and directives
Stan dard conf ormit y
Sta ndar ds
Approvals and certificates
FM approval hazardous (classified) location
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
0.31
Al
0.74
304
0.39
Brass
L
= 10 mA, switching element
L
= 50 mA, switching element
L
d
= 200 mA, switching ele-
L
d
) 20 a
M
0 ... 32.4 mm
a
0.5 ... 2.3 V typ. 0.9 V
0.8 ... 2.2 V typ. 1.4 V
0.9 ... 2.3 V typ. 1.5 V
0.9 ... 2.5 V typ. 1.6 V
1 ... 2.6 V typ. 1.8 V
1.2 ... 2.8 V typ. 2 V
0 ... 200 mA
L
0 ... 0.5 mA typ. 0.01 mA
r
≤ 100 µA
≤ 20 mA
0
80 ms
v
may be mounted on one terminal connection!
tightening torque 1.2 Nm + 10 %
without wire end ferrule 0.5 mm
without wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm
3G; 3D
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Non-incendive
2
2
, with connector sleeves 0.34 mm
2
2
Release date: 2017-05-17 11:37 Date of issue: 2017-05-17 209264_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1
Page 2
Inductive sensorNBN40-U1K-E2-3G-3D
Dimensions
LED ye
40
LED gn
Electrical Connection
LED gn
LED ye
BN
BK
BU
118
M20 x 1.5
6046
5.3
30
40
L+
L-
Release date: 2017-05-17 11:37 Date of issue: 2017-05-17 209264_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Page 3
Inductive sensorNBN40-U1K-E2-3G-3D
Equipment protection level Gc (nA)
Instruction Manual electrical apparatus for hazardous areas
Device category 3G (nA) for use in hazardous areas with gas, vapour and mist
Certificate PF 15CERT3754 X
CE marking
ATEX ma rk in g ¬ II 3G Ex nA IIC T6 Gc
Standards EN 60079-0:2012+A11:2013, EN 60079-15:2010
Ge n e r a l The apparatus has to be operated according to the appropriate data in the data sheet
Installation, commissioning Laws and/or regulations and standards governing the use or intended usage goal must
Maintenance No changes can be made to apparatus, which are operated in hazardous areas.
Special conditions
Maximum operating current I
Maximum operating voltage U
Maximum permissible ambient temperature T
at U
at U
at U
=30 V, IL=200 mA
Bmax
=30 V, IL=100 mA
Bmax
=30 V, IL=50 mA
Bmax
L
Bmax
Umax
Protection from mechanical danger
Protection from UV light
Protection against transients
Electrostatic charge
Lead insertion
Material selection accessories
Plug connector
The Ex-related marking can also be printed on the enclosed label.
Ignition protection category "n"
Use is restricted to the following stated conditions
and in this instruction manual. The data stated in the data sheet are restricted by this
operating instruction! The special conditions must be observed!
be observed. If the Ex-related marking is printed only on the supplied label, then this
must be attached in the immediate vicinity of the sensor. The sticking surface for the
label must be clean and free from grease. The attached label must be legible and indelible, including in the event of possible chemical corrosion. After opening the housing,
you should check that the seal is in the correct position and is clean and intact before
closing the housing again.
Repairs to these apparatus are not possible. After opening the housing, you should
check that the seal is in the correct position and is clean and intact before closing the
housing again.
The maximum permissible load current must be restricted to the values given in the following list. High load currents and load short-circuits are not permitted.
The maximum permissible operating voltage UB max is restricted to the values in the
following list. Tolerances are not permissible.
dependant of the load current I
Information can be taken from the following list.
and the max. operating voltage U
L
Bmax
50 °C (122 °F)
53 °C (127.4 °F)
54 °C (129.2 °F)
The sensor must not be exposed to ANY FORM of mechanical danger.
The sensor and the connection cable must be protected from damaging UV-radiation.
This can be achieved when the sensor is used in internal areas.
Ensure transient protection is provided and that the maximum value of the transient pro-
tection (140% of 85 V) is not exceeded.
When used in group IIC non-permissible electrostatic charges should be avoided on the
plastic housing parts. Avoid electrostatic charges that can cause electrostatic discharge
when installing or operating the device. Information on electrostatic hazards can be
found in the technical specification IEC/TS 60079-32-1.
If cable glands are required for the installation then the following points must be
observed: The cable glands must be certified in accordance with the application.
The temperature range of the cable glands must be selected according to the application. The degree of protection must not be reduced by the cable glands. Seal
the housing. Use a seal that meets the requirements of the application.
When selecting accessories, ensure that the material allows the temperature of the
enclosure to rise to up to 70 °C.
The plug connector must not be withdrawn under voltage. The proximity switch is identified as follows: "WARNING - DO NOT SEPARATE WHEN ENERGIZED". With the plug
connector disconnected, soiling of the internal area must be prevented.(i.e. the area that
is inaccessible when the connector is inserted)
Release date: 2017-05-17 11:37 Date of issue: 2017-05-17 209264_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
3
Page 4
Inductive sensorNBN40-U1K-E2-3G-3D
Equipment protection level Dc (tD)
Note This instruction is only valid for products according to EN 61241-0:2006 and EN 61241-1:2004
Instruction Manual electrical apparatus for hazardous areas
Device category 3D for use in hazardous areas with combustible dust
CE marking
ATEX marking ¬ II 3D Ex tD A22 IP67 T80°C X
Standards EN 61241-0:2006, EN 61241-1:2004
General The apparatus has to be operated according to the appropriate data in the data sheet and in this instruction manual.
Installation, commissioning Laws and/or regulations and standards governing the use or intended usage goal must be observed.
Maintenance No changes can be made to apparatus, which are operated in hazardous areas.
Special conditions
Maximum operating current I
Maximum operating voltage U
Maximum permissible ambient temperature T
at U
at U
at U
Umax
=30 V, IL=200 mA
Bmax
=30 V, IL=100 mA
Bmax
=30 V, IL=50 mA
Bmax
L
Bmax
Protection from mechanical danger
Protection from UV light
Electrostatic charge
Connections for external wire
Lead insertion
Plug connector
Note the ex-marking on the sensor or on the enclosed adhesive label
Protection via housing "tD"
Use is restricted to the following stated conditions
The maximum surface temperature has been determined in accordance with method A without a dust layer on the equipment.
The data stated in the data sheet are restricted by this operating instruction!
The special conditions must be adhered to!
Repairs to these apparatus are not possible.
The maximum permissible load current must be restricted to the values given in the following list.
High load currents and load short-circuits are not permitted.
The maximum permissible operating voltage UBmax must be restricted to the values given in the following list. Tolerances are
not permitted.
dependant of the load current I
Information can be taken from the following list.
and the max. operating voltage U
L
Bmax
50 °C (122 °F)
53 °C (127.4 °F)
54 °C (129.2 °F)
The sensor must not be exposed to ANY FORM of mechanical danger.
The sensor and the connection cable must be protected from damaging UV-radiation. This can be achieved when the sensor is
used in internal areas.
Sliding contact discharges must be avoided.
Terminal connection: Minimum conductor cross-section: 0.5 mm
the conductor must be provided with cable sleeves.
The cable entry must be such, that no tension load or twist is applied to the cable
The protection category must be in accordance with EN 60529 and as stated in the data sheet.
The requirements of EN 61241-0 relating to the cable and lead entries are to be complied with. The special characteristics of
the ignition protection class "tD, method A" of the proximity switch must not be disregarded.
The plug connector must not be withdrawn under voltage. The proximity switch is identified as follows: "WARNING - DO NOT
SEPARATE WHEN ENERGIZED". With the plug connector disconnected, soiling of the internal area must be prevented.(i.e.
the area that is inaccessible when the connector is inserted)
2
, maximum conductor cross-section: 2.5 mm2. The ends of
Release date: 2017-05-17 11:37 Date of issue: 2017-05-17 209264_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
4
Page 5
Inductive sensorNBN40-U1K-E2-3G-3D
Equipment protection level Dc (tc)
Instruction Manual electrical apparatus for hazardous areas
Device category 3D for use in hazardous areas with combustible dust
Certificate PF 15CERT3774 X
CE marking
ATEX ma rk in g ¬ II 3D Ex tc IIIC T80°C Dc
Standards EN 60079-0:2012+A11:2013, EN 60079-31:2014
Ge n e r a l The corresponding datasheets, declarations of conformity, EC-type examination certifi-
Installation, commissioning Laws and/or regulations and standards governing the use or intended usage goal must
Maintenance No changes can be made to apparatus, which are operated in hazardous areas.
Special conditions
Maximum operating current I
Maximum operating voltage U
Maximum permissible ambient temperature T
at U
at U
at U
=30 V, IL=200 mA
Bmax
=30 V, IL=100 mA
Bmax
=30 V, IL=50 mA
Bmax
L
Bmax
Umax
Protection from mechanical danger
Protection from UV light
Electrostatic charge
Lead insertion
Plug connector
The Ex-related marking can also be printed on the enclosed label.
Protection by enclosure "tc" Some of the information in this instruction manual is more
specific than the information provided in the datasheet.
cates, certifications, and control drawings, where applicable (see datasheets), form an
integral part of this document. These documents can be found at www.pepperlfuchs.com. The maximum surface temperature of the device was determined without a
layer of dust on the apparatus. Some of the information in this instruction manual is more
specific than the information provided in the datasheet.
be observed. If the Ex-relevant identification is printed exclusively on the adhesive label
provided, this label must be affixed in the immediate vicinity of the sensor! The background surface to which the adhesivelabel is to be applied must be clean and free from
grease! The applied label must be durable and remain legible, with due consideration of
the possibility of chemical corrosion! After opening the housing, you should check that
the seal is in the correct position and is clean and intact before closing the housing
again.
Repairs to these apparatus are not possible. After opening the housing, you should
check that the seal is in the correct position and is clean and intact before closing the
housing again.
The maximum permissible load current must be restricted to the values given in the following list.
High load currents and load short-circuits are not permitted.
The maximum permissible operating voltage UBmax must be restricted to the values
given in the following list. Tolerances are not permitted.
dependant of the load current I
Information can be taken from the following list.
and the max. operating voltage U
L
Bmax
50 °C (122 °F)
53 °C (127.4 °F)
54 °C (129.2 °F)
The sensor must not be exposed to ANY FORM of mechanical danger.
The sensor and the connection cable must be protected from damaging UV-radiation.
This can be achieved when the sensor is used in internal areas.
Sliding contact discharges must be avoided. Avoid electrostatic charges that can cause
electrostatic discharge when installing or operating the device. Information on electrostatic hazards can be found in the technical specification IEC/TS 60079-32-1. Do not
attach the nameplate provided in areas where electrostatic charge can build up.
If cable glands are required for the installation then the following points must be
observed: The cable glands must be certified in accordance with the application.
The temperature range of the cable glands must be selected according to the application. The degree of protection must not be reduced by the cable glands. Seal
the housing. Use a seal that meets the requirements of the application.
The plug connector must not be withdrawn under voltage. The proximity switch is identified as follows: "WARNING - DO NOT SEPARATE WHEN ENERGIZED". With the plug
connector disconnected, soiling of the internal area must be prevented.(i.e. the area that
is inaccessible when the connector is inserted)