Datasheet MPS Datasheet (Littelfuse)

Page 1
MPS MANUAL
MOTOR PROTECTION SYSTEM
Revision 6-F-022117
Copyright © 2017 by Littelfuse Startco
All rights reserved.
Document Number: PM-1130-EN
Page 2
Factory default password is 1111
New Password
See Section 4.3.6.
Motor Identification
Page 3
Page ii MPS Motor Protection System Rev. 6-F-022117
. Table of Contents
TABLE OF CONTENTS
SECTION PAGE
List of Figures ....................................................................... iv
List of Tables ........................................................................ iv
Disclaimer .............................................................................. v
1 Introduction .......................................................... 1-1
1.1 General .................................................................... 1-1
1.2 MPS Features .......................................................... 1-1
1.2.1 Protection .................................................... 1-1
1.2.2 Control – Starting Methods ........................ 1-1
1.2.3 Metering ...................................................... 1-1
1.2.4 Data Logging .............................................. 1-1
1.2.5 Inputs and Outputs ...................................... 1-1
1.2.6 MPS-OPI Operator Interface ..................... 1-2
1.2.7 MPS-RTD Module ..................................... 1-2
1.2.8 MPS-DIF Differential Module ................... 1-2
1.2.9 Communications Interface ......................... 1-2
1.3 Ordering Information .............................................. 1-2
2 Installation ............................................................. 2-1
2.1 General .................................................................... 2-1
2.2 MPS-CTU Control Unit ......................................... 2-1
2.3 MPS-OPI Operator Interface .................................. 2-1
2.4 MPS-RTD Module ................................................. 2-1
2.5 MPS-DIF Differential Module ............................... 2-1
2.6 Earth-Fault CT’s ..................................................... 2-1
3 System Wiring ....................................................... 3-1
3.1 General .................................................................... 3-1
3.2 Wiring Connections ................................................ 3-1
3.2.1 MPS-CTU Connections ............................. 3-1
3.2.1.1 Supply Voltage .............................. 3-1
3.2.1.2 Current Inputs ................................ 3-1
3.2.1.3 Voltage Inputs ............................... 3-1
3.2.1.3.1 Direct Connection ........ 3-3
3.2.1.3.2 1-PT Connection .......... 3-3
3.2.1.3.3 2-PT Connection .......... 3-3
3.2.1.3.4 3-PT Connection .......... 3-3
3.2.1.4 Digital Inputs ................................. 3-3
3.2.1.4.1 DC Operation ............... 3-4
3.2.1.4.2 AC Operation ............... 3-4
3.2.1.4.3 Combined AC and
DC Operation ............................... 3-4
3.2.1.4.4 Tachometer
Input (HSI) ................................... 3-4
3.2.1.5 Analog Input (AN IN) ................... 3-4
3.2.1.6 Analog Output (AN OUT) ............ 3-4
3.2.1.7 PTC Input ...................................... 3-4
3.2.1.8 IRIG-B Input ................................. 3-4
3.2.1.9 I/O Module Communication ......... 3-4
3.2.1.10 RS-485 Network
Communications ......................................... 3-4
3.2.2 MPS-OPI Connections and
Address Selection ....................................... 3-4
3.2.3 MPS-RTD Connections and
Address Selection ....................................... 3-5
3.2.4 MPS-DIF Connections ............................... 3-5
3.2.4.1 Core Balance ................................. 3-5
TABLE OF CONTENTS
SECTION PAGE
3.2.4.2 MPS Summation ............................ 3-5
3.2.4.3 DIF Summation ............................. 3-5
3.2.5 Dielectric-Strength Testing ........................ 3-5
4 Operation and Setup ............................................ 4-1
4.1 General .................................................................... 4-1
4.2 MPS-CTU ............................................................... 4-1
4.2.1 LED Indication ........................................... 4-1
4.2.2 Reset Switch ................................................ 4-1
4.2.3 Phase-CT Inputs .......................................... 4-1
4.2.4 Earth-Fault-CT Input .................................. 4-2
4.2.5 Voltage Inputs ............................................. 4-2
4.2.6 Motor Data .................................................. 4-2
4.2.7 Output Relay Assignment .......................... 4-2
4.2.8 Digital Inputs 1 to 7 .................................... 4-3
4.2.9 Tachometer Input (HSI) ............................. 4-4
4.2.10 Analog Output ............................................. 4-4
4.2.11 Analog Input ............................................... 4-5
4.2.11.1 Metering only .............................. 4-5
4.2.11.2 Protection ..................................... 4-5
4.2.11.3 Synchronize to ASD .................... 4-5
4.2.11.4 Motor Speed ................................ 4-5
4.2.12 Starter .......................................................... 4-5
4.2.13 Protection .................................................... 4-5
4.2.14 Miscellaneous Configuration ..................... 4-5
4.2.15 Network Communications .......................... 4-5
4.3 MPS-OPI ................................................................. 4-5
4.3.1 General ........................................................ 4-5
4.3.2 Configuring the MPS-CTU for
OPI Operation ............................................. 4-5
4.3.3 Starter Control ............................................. 4-6
4.3.3.1 OPI Control .................................... 4-6
4.3.3.2 Local Control ................................. 4-6
4.3.3.3 Remote Control ............................. 4-6
4.3.4 Metering ...................................................... 4-7
4.3.5 Messages ..................................................... 4-7
4.3.5.1 Trip Reset ....................................... 4-7
4.3.5.2 Status .............................................. 4-7
4.3.5.3 Data Logging ................................. 4-9
4.3.5.4 Statistical Data ............................... 4-9
4.3.5.5 Emergency Thermal Reset ............ 4-9
4.3.6 Password Entry and Programming ............. 4-9
4.4 MPS-RTD ............................................................. 4-10
4.5 MPS-DIF ............................................................... 4-10
4.6 Waveform Capture ............................................... 4-10
5 Protective Functions ......................................... 5-1
5.1 General ............................................................... 5-1
5.2 Overload ............................................................. 5-1
5.2.1 Thermal Model ....................................... 5-1
5.2.2 Locked-Rotor Times ............................... 5-4
5.2.3 Emergency Thermal Reset ...................... 5-4
5.3 Overcurrent ........................................................ 5-4
5.4 Auxiliary Overcurrent ........................................ 5-5
5.5 Reduced Overcurrent ......................................... 5-5
5.6 Jam ..................................................................... 5-5
5.7 Earth Fault .......................................................... 5-5
Page 4
Page iii MPS Motor Protection System Rev. 6-F-022117
. Table of Contents
SECTION PAGE
5.8 Current Unbalance .............................................. 5-5
5.9 Phase Loss—Current .......................................... 5-6
5.10 Phase Reverse—Current ..................................... 5-6
5.11 Undercurrent ....................................................... 5-6
5.12 Overvoltage ........................................................ 5-6
5.13 Voltage Unbalance ............................................. 5-6
5.14 Phase Loss—Voltage ......................................... 5-6
5.15 Phase Reverse—Voltage .................................... 5-6
5.16 Undervoltage ...................................................... 5-7
5.17 Underpower ........................................................ 5-7
5.18 Reversepower ..................................................... 5-7
5.19 Power Factor—Quadrant 4 ................................. 5-7
5.20 Power Factor—Quadrant 3 ................................. 5-7
5.21 Underfrequency .................................................. 5-7
5.22 Overfrequency .................................................... 5-8
5.23 Starts per Hour/Time Between Starts ................. 5-8
5.24 Failure to Accelerate and Underspeed ................ 5-8
5.25 Differential Current Protection ........................... 5-9
5.26 PTC Temperature ............................................... 5-9
5.27 RTD Temperature .............................................. 5-9
5.28 Hot-Motor Compensation ................................ 5-10
5.29 Analog Input ..................................................... 5-10
5.29.1 Protection .............................................. 5-10
5.29.2 Synchronize to ASD ............................. 5-10
5.29.3 Motor Speed .......................................... 5-10
5.29.4 Metering Only ....................................... 5-10
6 Starter Functions .............................................. 6-1
6.1 General ............................................................... 6-1
6.2 Starter Timing Sequences ................................... 6-4
6.3 Full-Voltage Non-Reversing Starter .................. 6-7
6.4 Adjustable-Speed Drive ..................................... 6-7
6.5 Soft-Start Starter ................................................. 6-7
6.6 Full-Voltage Reversing Starter ........................... 6-8
6.7 Two-Speed Starter .............................................. 6-8
6.8 Reactor or Resistor Closed-Transition
Starter ............................................................... 6-10
6.9 Slip-Ring Starter ............................................... 6-10
6.10 Part-Winding and Double-Delta Starters ......... 6-11
6.11 Soft-Start-With-Bypass Starter ........................ 6-12
6.12 Reactor or Resistor Open-Transition Starter .... 6-12
6.13 Two-Winding Starter ........................................ 6-12
6.14 Wye-Delta Open-Transition Starter ................. 6-12
6.15 Autotransformer Closed-Transition Starter ...... 6-13
6.16 Wye-Delta Closed-Transition Starter ............... 6-13
7 Theory of Operation ......................................... 7-1
7.1 Signal-Processing Algorithms ............................ 7-1
7.2 Power Algorithm ................................................ 7-1
7.3 Operator Interface (MPS-OPI) ........................... 7-1
7.4 RTD Module (MPS-RTD) ................................. 7-1
7.5 Differential Module (MPS-DIF) ........................ 7-1
7.6 Firmware Diagnostics ........................................ 7-1
8 Communications ............................................... 8-1
8.1 Personal-Computer Interface .............................. 8-1
8.1.1 Firmware Upgrade .................................. 8-1
8.1.2 SE-Comm-RIS ........................................ 8-1
SECTION PAGE
8.2 Network Interface ............................................... 8-1
8.2.1 RS-485 Communications ........................ 8-1
8.2.2 DeviceNet Communications ................... 8-1
8.2.3 Ethernet Communications ....................... 8-1
8.2.4 Profibus Communications ....................... 8-1
9 Technical Specifications ................................... 9-1
9.1 Control Unit (MPS-CTU) .................................. 9-1
9.2 Operator Interface (MPS-OPI) ........................... 9-3
9.3 RTD Module (MPS-RTD) ................................. 9-3
9.4 Differential Module (MPS-DIF) ........................ 9-4
10 Warranty ........................................................... 9-5
Appendix A MPS-OPI Menu Map ............................ A-1
Appendix B MPS Set-Up Record .............................. B-1
Appendix C MPS Modbus Protocol .......................... C-1
Appendix D MPS A-B DF1 Protocol ......................... D-1
Appendix E Communications Database Table ......... E-1
Appendix F Register Formats .................................... F-1
Appendix G MPS Revision History .......................... G-1
Page 5
Page iv MPS Motor Protection System Rev. 6-F-022117
. Table of Contents
LIST OF FIGURES
FIGURE PAGE
1.1 Motor Protection System Block Diagram ............. 1-3
1.2 MPS Ordering Information .................................... 1-4
2.1 MPS-CTU Outline and Mounting Details ............. 2-2
2.1.1 MPS-CTU-XX-X1 Ring Terminal
Outline and Mounting Details ................................ 2-3
2.2 MPS-OPI Outline and Mounting Details ............... 2-4
2.3 MPS-CTU with OPI Outline and
Mounting Details .................................................... 2-5
2.3.1 MPS-CTU Ring Terminal with OPI Outline and
Mounting Details .................................................... 2-6
2.4 SE-IP65CVR-M Weatherproof Cover Outline .. 2-7
2.5 SE-IP65CVR-M Weatherproof Cover
Installation .......................................................... 2-8
2.6 MPS-RTD Outline and Mounting Details ............. 2-9
2.7 MPS-DIF Outline and Mounting Details ............. 2-10
2.8 EFCT-1 Outline and Mounting Details ............... 2-11
2.9 EFCT-2 Outline and Mounting Details ............... 2-12
2.10 EFCT-26 and SE-CS30-26 Outline and
Mounting Details .................................................. 2-13
2.11 SE-CS30-70 Outline and Mounting Details ........ 2-14
2.12 SE-CS30-4, -5, and -8 Outline and Mounting
Details ................................................................... 2-15
3.1 Residual Phase-CT Connection ............................. 3-1
3.2 Typical MPS Connection Diagram ........................ 3-2
3.3 Direct Connection ................................................... 3-3
3.4 1-PT Connection ..................................................... 3-3
3.5 2-PT Connection ..................................................... 3-3
3.6 3-PT Connection ..................................................... 3-3
3.7 Digital Tachometer Input (HSI) ............................. 3-4
3.8 Address Selection Switch Detail ............................ 3-5
3.9 Two Examples of I/O Module Connections .......... 3-6
3.10 MPS-RTD Connection Diagram ............................ 3-7
3.11 Core Balance Connection ....................................... 3-8
3.12 MPS Summation Connection ................................. 3-8
3.13 DIF Summation Connection .................................. 3-9
4.1 Menu Example ........................................................ 4-1
4.2 Menu Symbols ........................................................ 4-1
4.3 MPS-OPI Interface ................................................. 4-6
5.1 Class-20 Overload Curve ....................................... 5-3
5.2 Asymmetrical-Current Multipliers ......................... 5-5
5.3 Used I2t Bias Curve .............................................. 5-10
6.1 Typical 3-Wire Control .......................................... 6-3
6.2 Typical 2-Wire Control .......................................... 6-4
6.3 Starter Sequence 1 .................................................. 6-4
6.4 Starter Sequence 2 .................................................. 6-4
6.5 Starter Sequence 3 .................................................. 6-5
6.6 Starter Sequence 4 .................................................. 6-5
6.7 Starter Sequence 5 .................................................. 6-6
6.8 Starter Sequence 6 .................................................. 6-6
6.9 Full-Voltage Non-Reversing-Starter
Connection .............................................................. 6-7
6.10 Adjustable-Speed-Drive Connection ..................... 6-7
6.11 Soft-Start-Starter Connection ................................. 6-7
LIST OF FIGURES
FIGURE .............................................. PAGE
6.12 Full-Voltage-Reversing-Starter Connection .......... 6-8
6.13 Two-Speed Two-Winding-Starter Connection ...... 6-8
6.14 Two-Speed Constant- and Variable-Torque-
Starter Connections ................................................. 6-9
6.15 Two-Speed Constant-Horsepower-Starter
Connection ............................................................... 6-9
6.16 Reactor or Resistor-Starter Connection ................ 6-10
6.17 Slip-Ring-Starter Connection ................................ 6-10
6.18 Part-Winding and Double-Delta-Starter
Connections ........................................................... 6-11
6.19 Soft-Start-With-Bypass-Starter Connection ......... 6-12
6.20 Two-Winding-Starter Connection ........................ 6-13
6.21 Wye-Delta Open-Transition-Starter
Connection ............................................................. 6-14
6.22 Autotransformer Closed-Transition-Starter
Connection ............................................................. 6-14
6.23 Wye-Delta Closed-Transition-Starter
Connection ............................................................. 6-15
LIST OF TABLES
TABLE PAGE
3.1 MPS-OPI Address Selection ................................... 3-4
3.2 MPS-RTD Address Selection ................................. 3-5
4.1 Output-Relay Functions .......................................... 4-2
4.2 Digital-Input Functions ........................................... 4-3
4.3 Analog-Output Parameters ...................................... 4-4
4.4 Metering Display ..................................................... 4-8
4.5 Status Messages ....................................................... 4-8
5.1 Trip Time ................................................................. 5-4
5.2 Fault Duration Required for Trip ............................ 5-4
6.1 Start-Source Summary ............................................ 6-1
6.2 Starter Summary ...................................................... 6-3
Page 6
Page v MPS Motor Protection System Rev. 6-F-022117
. Table of Contents
DISCLAIMER
Specifications are subject to change without notice. Littelfuse Startco is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction.
Page 7
Page 1-1 MPS Motor Protection System Rev. 6-F-022117
Introduction
1. INTRODUCTION
1.1 GENERAL
The Littelfuse Startco Motor Protection System (MPS) is a modular system with integrated protection, control, metering, and data-logging functions. The Control Unit (MPS-CTU) is the core module. It can operate as a stand­alone unit or with the Operator Interface (MPS-OPI), RTD Modules (MPS-RTD), and Differential Module (MPS-DIF). The CTU can be programmed using the OPI or the communications network. Programmable inputs and outputs provide a flexible hardware platform and custom software can be easily loaded from a PC to the CTU’s flash memory. The MPS block diagram is shown in Fig. 1.1.
1.2 MPS FEATURES
1.2.1 PROTECTION
• Overload (49, 51)
• Overcurrent (50, 51)
• Earth fault (50G/N, 51G/N)
• Unbalance (voltage and current) (46, 47)
• Phase loss (voltage and current) (46, 47)
• Phase reverse (voltage and current) (46, 47)
• Jam
• Undercurrent (37)
• Failure to accelerate
• Underspeed (14)
• Overvoltage (59)
• Undervoltage (27)
• Underpower (37)
• Reversepower (32)
• Power factor (55)
• Overfrequency (81)
• Underfrequency (81)
• PTC overtemperature (49)
• RTD temperature (38, 49)
• Starts per Hour (66)
• Differential (87)
1.2.2 CONTROL—STARTING METHODS
(1)
• Non-reversing
• Reversing
• Soft start
• Soft start with bypass
• Adjustable-speed drive
• Two speed
• Wye-delta (open or closed transition)
• Reactor (open or closed transition)
• Resistor (open or closed transition)
• Autotransformer
• Part winding
• Slip ring
• Two winding
• Double delta
(1)
Only three CT’s required for all starting methods.
1.2.3 METERING
• Line currents
• Current unbalance
• Positive-sequence current
• Negative-sequence current
• Earth-leakage current
• Differential currents
• Line-to-line voltages
• Line frequency
• Voltage unbalance
• Positive-sequence voltage
• Negative-sequence voltage
• Power
§ Apparent, Reactive, Real, and Power factor
• Energy
§ kWh, kVAh, and kVARh
• Used thermal capacity
• Thermal trend
• Motor speed
• RTD temperatures
• Analog input and output
1.2.4 DATA LOGGING
• Sixty-four records
§ Date and time of event
§ Event type
§ Line currents
§ Current unbalance
§ Earth-leakage current
§ Differential currents
§ Line-to-line voltages
§ Voltage unbalance
§ Thermal capacity
§ Thermal capacity used during starts
§ Start time
§ Analog-input value
§ Frequency
§ Power (P, S, Q, PF)
§ RTD temperatures
§ Trip counters
§ Running hours
§ Waveform Capture
§ 5 seconds of pre-trip waveform data
§ 16 samples per cycle
§ COMTRADE and CSV file generation
1.2.5 INPUTS AND OUTPUTS
• Three ac-current inputs
• Three ac-voltage inputs
• Earth-leakage-current input
• Seven programmable digital (ac/dc) inputs
• 24-Vdc source for digital inputs
• Tachometer (high-speed pulse) input
• 4-20-mA analog input
• 4-20-mA analog output
• PTC thermistor temperature input
Page 8
Page 1-2 MPS Motor Protection System Rev. 6-F-022117
Introduction
• Up to twenty-four RTD inputs
• Five programmable output relays
• Network communications
• IRIG-B time-code input
1.2.6 MPS-OPI OPERATOR INTERFACE
• 4 x 20 vacuum-fluorescent display
• Starter-control keys
• Display-control and programming keys
• LED status indication
• Remote operation up to 1.2 km (4,000’)
• Powered by MPS-CTU
1.2.7 MPS-RTD MODULE
• Eight inputs per module
• Individually selectable RTD types
• RTD Voting
• Solid-state multiplexing
• Up to three modules per system
• Remote operation up to 1.2 km (4,000’)
• Powered by MPS-CTU
1.2.8 MPS-DIF DIFFERENTIAL MODULE
• 3-CT core-balance connection
• 6-CT summation connection
• Remote operation up to 1.2 km (4,000’)
• Powered by MPS-CTU
1.2.9 COMMUNICATIONS INTERFACE
The standard network communication interface is an RS-485 port with Modbus® RTU and A-B® DF1 protocol support. In addition to the standard interface, network communication options include DeviceNet™, Profibus®, Modbus® TCP, and Ethernet/IP.
1.3 ORDERING INFORMATION
See Fig. 1.2 for MPS-CTU, MPS-OPI, MPS-RTD, and MPS-DIF model numbers.
Earth-Fault Current Sensors:
EFCT-1 ......................... Earth-Fault CT,
5-A-primary rating, 82 mm (3.2”) window
EFCT-1FC ..................... Flux Conditioner for EFCT-1,
70 mm (2.7”) window
EFCT-2 ......................... Earth-Fault CT with
Flux Conditioner, 5-A-primary rating, 139 mm (5.5”) window
EFCT-26 ....................... Earth-Fault CT,
5-A-primary rating, 26 mm (1”) window (All EFCT’s include 6 m (19.5’) of 22 AWG (0.33 mm2) shielded cable.)
SE-CS30-4 ............................. Current Sensor,
30-A-primary rating, c/w Flux Conditioner,
95.0 mm (3.7”) window
SE-CS30-5 ............................. Current Sensor,
30-A-primary rating, c/w Flux Conditioner,
130.0 mm (5.1”) window
SE-CS30-8 ............................. Current Sensor
30-A-primary rating, c/w Flux Conditioner,
200.0 mm (7.9”) window
SE-CS30-26 ......................... Current Sensor,
30-A-primary rating,
26 mm (1.0”) window
SE-CS30-70 ......................... Current Sensor,
30-A-primary rating, 70 mm (2.7”) window
Phase CT’s ............................... Protection-Class CT’s,
Contact factory
Accessories:
SE-IP65CVR-M ................... Hinged Transparent OPI
Cover
SE-485-PP ............................ Port-Powered Serial
Converter
SE-485-DIN ......................... Serial Converter,
Industrial, 24 Vdc
Software:
SE-Comm-RIS ..................... PC Communication
Software
(1)
SE-Flash ............................... Firmware Upgrade
Software
(1)
(1)
Available at www.littelfuse.com/relayscontrols.
Page 9
Page 1-3 MPS Motor Protection System Rev. 6-F-022117
Introduction
FIGURE 1.1 Motor Protection System Block Diagram.
Page 10
Page 1-4 MPS Motor Protection System Rev. 6-F-022117
Introduction
FIGURE 1.2 MPS Ordering Information.
Page 11
Page 2-1 MPS Motor Protection System Rev. 6-F-022117
Installation
2. INSTALLATION
2.1 GENERAL
A basic Motor Protection System (MPS) consists of an MPS-CTU and three customer-supplied current transformers (CT's) for measuring phase current. For core-balance earth-fault detection, a 1-A, 5-A, EFCT-1, or EFCT-2 CT is required. For the optional Ring Terminal MPS-CTU, the 1-A connection is not available. The residual phase-CT connection can also be used for earth­fault detection. Voltage inputs do not require potential transformers (PT’s) for system voltages up to 600 Vac. For RTD-temperature measurement, up to three MPS-RTD modules can be connected to the MPS-CTU. For differential protection, an MPS-DIF module can be connected to the MPS-CTU. The MPS-OPI provides an operator interface for the MPS. The MPS power-factor-corrected switch-mode power supply is rated 65 to 265 Vac and 80 to 275 Vdc. All modules can be mounted in any orientation.
2.2 MPS-CTU CONTROL UNIT
The Control Unit is configured for surface mounting. Outline and mounting details for the MPS-CTU are shown in Figs. 2.1 and 2.1.1.
2.3 MPS-OPI OPERATOR INTERFACE
Outline and mounting details for the MPS-OPI are shown in Fig. 2.2. It is certified for use in Class I, Zone 2 and Class I, Division 2 hazardous locations. The Operator Interface is configured for panel mounting or it can be mounted on the MPS-CTU as shown in Fig. 2.3. The Operator Interface can also be mounted on the MPS-CTU ring terminal as shown in Fig. 2.3.1 (surface mount only). If an optional SE-IP65CVR-M is used, follow the included installation instructions. See Figs. 2.4 and 2.5.
2.4 MPS-RTD MODULE
Outline and mounting details for the MPS-RTD are shown in Fig. 2.6. The MPS-RTD will fit inside most motor RTD-termination junction boxes and it is certified for use in Class I, Zone 2 and Class I, Division 2 hazardous locations. The MPS-RTD can be surface or DIN-rail mounted.
2.5 MPS-DIF DIFFERENTIAL MODULE
Outline and mounting details for the MPS-DIF are shown in Fig 2.7. The MPS-DIF can be surface or DIN­rail mounted.
2.6 EARTH-FAULT CT’S
Outline and mounting details for the EFCT-1, EFCT-2, EFCT-26, and SE-CS30 series are shown in Figs. 2.8, 2.9,
2.10, 2.11, and 2.12.
Page 12
Page 2-2 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.1 MPS-CTU Outline and Mounting Details.
Page 13
Page 2-3 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.1.1 MPS-CTU-XX-X1 Ring Terminal Outline and Mounting Details.
Page 14
Page 2-4 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.2 MPS-OPI Outline and Mounting Details.
Page 15
Page 2-5 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.3 MPS-CTU with OPI Outline and Mounting Details.
Page 16
Page 2-6 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.3.1 MPS-CTU Ring Terminal with OPI Outline and Mounting Details.
Page 17
Page 2-7 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.4 SE-IP65CVR-M Weatherproof Cover Outline.
Page 18
Page 2-8 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.5 SE-IP65CVR-M Weatherproof Cover Installation.
Page 19
Page 2-9 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.6 MPS-RTD Outline and Mounting Details.
Page 20
Page 2-10 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.7 MPS-DIF Outline and Mounting Details.
Page 21
Page 2-11 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.8 EFCT-1 Outline and Mounting Details.
Page 22
Page 2-12 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.9 EFCT-2 Outline and Mounting Details.
Page 23
Page 2-13 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.10 EFCT-26 and SE-CS30-26 Outline and Mounting Details.
Page 24
Page 2-14 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.11 SE-CS30-70 Outline and Mounting Details.
Page 25
Page 2-15 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.12 SE-CS30-4, -5, and -8 Outline and Mounting Details.
Page 26
Page 2-16 MPS Motor Protection System Rev. 6-F-022117
Installation
This page intentionally left blank.
Page 27
Page 3-1 MPS Motor Protection System Rev. 6-F-022117
System Wiring
3. SYSTEM WIRING
3.1 GENERAL
A typical connection diagram is shown in Fig. 3.2. The MPS-CTU provides the 24-Vdc supply for the peripheral modules and it communicates with them using an RS-485 interface. The total length of the I/O communication system must be less than 1.2 km (4,000’). I/O communications addressing supports up to three modules of each type; however, the power supply in the MPS-CTU will not support more than three I/O modules. An external 24-Vdc power supply is required if more than three modules are used. The MPS-CTU voltage inputs can be directly connected to a system with line-to-line voltages up to 600 Vac. PT's are required for system voltages higher than 600 Vac. Input resistance of the voltage inputs is
3.4 MΩ.
NOTE: The current and voltage inputs must be phase sequenced A-B-C with correct polarity observed.
START1, START2, and STOP starter-control commands can be issued through the digital inputs, the network interface, or the MPS-OPI. Start, stop, and interlock contacts can be wired to any of the programmable digital inputs. The five programmable output relays can be used for starting control, protection, and interlock functions. Relay 5 is a solid-state, low-level output relay not recommended for starter control. See Section 9 for relay ratings.
NOTE: The default configuration has no assignments for digital inputs and relay outputs.
3.2 WIRING CONNECTIONS
3.2.1 MPS-CTU CONNECTIONS
The MPS-CTU CT-input terminal blocks accept 22 to 10 AWG (0.3 to 4.0 mm2) conductors. The remaining MPS-CTU clamping blocks accept 24 to 12 AWG (0.2 to 2.5 mm2) conductors. Terminal blocks unplug to allow the MPS-CTU to be easily replaced. The MPS-CTU Ring Terminal CT-input terminal block accept a maximum ring width of 8 mm (0.315”). These terminal blocks cannot be unplugged.
3.2.1.1 SUPPLY VOLTAGE
Derive supply voltage from the line side of the motor controller or from an independent source. Connect supply voltage to terminals 1 and 2 (L1 and L2) as shown in Fig. 3.2. In 120-Vac systems, L2 is usually designated as the neutral conductor. For direct-current power supplies, use L1 for the positive terminal and L2 as the negative terminal. Earth terminal 3 ( ). Internal surge-protection devices are connected to terminals 4 (SPG) and 4A (SPGA) to allow dielectric­strength testing. Terminals 4 and 4A must be connected except during dielectric-strength testing. The 24-Vdc I/O module supply (terminals 56 and 60) can support three I/O modules. An external 24-Vdc supply is required if more than three modules are used.
3.2.1.2 CURRENT INPUTS
The MPS-CTU uses 1-A or 5-A CT’s for phase-current measurement. The MPS-CTU Ring Terminal uses 5-A CT’s for phase-current measurement. To maintain specified accuracy, phase CT’s should be protection class and selected with a primary rating between 100 and 300% of motor full-load current (FLA). Current threshold is a function of full-load current and CT-primary rating as defined by the following formula.
The Current Threshold is also used to determine when the motor is in Run mode. Several protective functions are only enabled when in Run mode. See Section 5.1 for a description of Run mode. For synchronous-motor applications, the CT-primary
rating should be selected such that the current threshold is less than the idle current, typically less than 5%. All CT
inputs can withstand a common-mode voltage of 120 Vac so that the MPS-CTU can be connected in series with other CT loads. The connection diagram in Fig. 3.2 shows a typical connection where the MPS-CTU is the only device connected to the phase CT's. The MPS-CTU requires the phase sequence to be A-B-C with correct polarity. The Ip Threshold sets the current level where unbalance protection becomes active. See Section 5.8. A 1-A, 5-A, or sensitive CT is used for core-balance earth-leakage measurement. The MPS-CTU Ring Terminal has no 1-A input. See Fig. 3.1 for the phase-CT residual connection for earth-fault detection.
FIGURE 3.1 Residual Phase-CT Connection.
3.2.1.3 VOLTAGE INPUTS
For all input-voltage connections, the MPS-CTU requires the phase sequence to be A-B-C with correct polarity. If voltage inputs are not used, connect VA, VB, and VC to VN.
NOTE: A voltage input is required for line-frequency metering.
Page 28
Page 3-2 MPS Motor Protection System Rev. 6-F-022117
System Wiring
FIGURE 3.2 Typical MPS Connection Diagram.
Page 29
Page 3-3 MPS Motor Protection System Rev. 6-F-022117
System Wiring
3.2.1.3.1 DIRECT CONNECTION
PT's are not required for system voltages up to 600 Vac
line-to-line. Connect the voltage inputs as shown in Figs. 3.2 and 3.3.
FIGURE 3.3 Direct Connection.
3.2.1.3.2 1-PT CONNECTION
The 1-PT connection is shown in Fig. 3.4. Connect the PT between phase A and phase B. The PT-secondary voltage must be less than 350 Vac.
NOTE: The 1-PT connection does not allow detection of voltage unbalance.
FIGURE 3.4 1-PT Connection.
3.2.1.3.3 2-PT CONNECTION
The 2-PT connection is shown in Fig. 3.5. The PT­secondary voltages must be less than 350 Vac. Connect the PT secondaries in open delta.
FIGURE 3.5 2-PT Connection.
3.2.1.3.4 3-PT CONNECTION
The 3-PT connection is shown in Fig. 3.6. The PT­secondary voltages must be less than 350 Vac. Since the MPS-CTU measures line-to-line voltage, there is no advantage in using a 3-PT connection over a 2-PT connection.
NOTE: This connection relies on PT primary­magnetization current for voltage balance. Do not connect any other secondary loads.
FIGURE 3.6 3-PT Connection.
3.2.1.4 DIGITAL INPUTS
Digital inputs 1 to 8 (terminals 44 to 51) are referenced to COM (terminal 43). These inputs are isolated from all other terminals and operate over a 12 to 120 Vac/Vdc range. Inputs 1 to 7 have programmable functions. See Table 4.2. Input 8 is a high-speed input (HSI) for a tachometer sensor.
Page 30
Page 3-4 MPS Motor Protection System Rev. 6-F-022117
System Wiring
3.2.1.4.1 DC OPERATION
Supply voltage for dc-input operation can be obtained from the 24-Vdc source (terminals 41 and 42), or it can be obtained from an external 12- to 120-Vdc supply. The internal source is current limited at 100 mA and is referenced to the analog output (terminal 40) and the I/O Supply (terminal 56). Connect the “−” terminal of the dc source to COM and connect field inputs between “+” and the digital-input terminals.
3.2.1.4.2 AC OPERATION
Inputs operate over a 12- to 120-Vac range. Connect the ac neutral to COM and connect field inputs between line and the digital inputs.
3.2.1.4.3 COMBINED AC AND DC OPERATION
If both ac and dc inputs are used, connect both the ac­supply common and dc-supply “−” to COM.
3.2.1.4.4 TACHOMETER INPUT (HSI)
A tachometer sensor can be used to provide motor­speed measurement. Connect a logic-output PNP tachometer as shown in Fig. 3.7.
FIGURE 3.7 Digital Tachometer Input (HSI).
3.2.1.5 ANALOG INPUT (AN IN)
The analog input (terminal 52 and 53) is a 4-20-mA current input with a 100-Ω input impedance.
NOTE: The analog input is referenced to an internal supply with 100-kΩ resistors. Maximum common-mode voltage is ± 5 Vdc with respect to MPS-CTU terminal 4.
3.2.1.6 ANALOG OUTPUT (AN OUT)
The analog output is a self-powered current-source output. The current source output is the “+” (terminal 39) and the common is “−” (terminal 40).
NOTE: The analog output (terminal 40) is internally referenced to the 24-Vdc source (terminal 42) and the I/O supply (terminal 56).
3.2.1.7 PTC INPUT
Terminals 54 and 55 are provided for PTC over­temperature protection. See Section 9 for specifications.
3.2.1.8 IRIG-B INPUT
Terminals 61 and 62 are used for an IRIG-B time-code signal. When an IRIG-B signal is detected, the real-time clock (RTC) synchronizes with it. The user must set the MPS date value because the IRIG-B day-of-the-year parameter is not supported. If the time-code generator does not have a local-time adjustment, the IRIG Offset set points can be used to adjust the hour and minute values so that the MPS will read local time.
3.2.1.9 I/O MODULE COMMUNICATION
The I/O module communications interface (terminals 56 through 60) is used to support optional modules. The connector labeled Operator Interface on the MPS-CTU top panel is in parallel with terminals 50 to 56. It is used for direct MPS-OPI mounting. See Section 2.3. I/O module communication is based on the 2-wire multi-drop RS-485 standard. Overall line length must not exceed 1.2 km (4,000’). For line lengths exceeding 10 m (33’), 150-Ω terminations are required at the cable ends. See Fig. 3.9.
3.2.1.10 RS-485 NETWORK COMMUNICATIONS
Terminals 35, 36, and 37 are used for the standard RS-485 interface. See Section 4.2.15.
3.2.2 MPS-OPI CONNECTIONS AND ADDRESS SELECTION
Connect the MPS-OPI to the MPS-CTU using shielded cable (Belden® 3124A or equivalent). The 24-Vdc supply for the MPS-OPI is provided by the MPS-CTU. The cable shield must be connected at both ends so that MPS-OPI transient protection is operational. See Fig. 3.9. The MPS-OPI has two switches to select its network address. See Figs. 2.2 and 3.8. Up to three MPS-OPI modules can be connected to the I/O MODULE bus, and each active OPI must have a unique address. If one OPI is used, address 1 must be used. If two OPI's are used, addresses 1 and 2 must be used. If three OPI's are used, addresses 1, 2, and 3 must be used. Table 3.1 and Fig. 3.8 shows the addressing selection format.
TABLE 3.1 MPS-OPI ADDRESS SELECTION
ADDRESS
SWITCH 1
SWITCH 2
0
(Factory Test)
Open
Open
1
(First OPI)
Closed
Open
2
(Second OPI)
Open
Closed
3
(Third OPI)
Closed
Closed
Page 31
Page 3-5 MPS Motor Protection System Rev. 6-F-022117
System Wiring
FIGURE 3.8 Address Selection Switch Detail.
3.2.3 MPS-RTD CONNECTIONS AND ADDRESS SELECTION
MPS-RTD terminal blocks accept 24 to 12 AWG (0.2 to 2.5 mm2) conductors. Connect the MPS-RTD to the MPS-CTU using the four-conductor shielded cable (Belden 3124A or equivalent) as shown in Fig. 3.9. The MPS-CTU 24-Vdc supply can power up to three MPS-RTD modules. Connect RTD’s to the MPS-RTD as shown in Fig 3.9. When the RTD module is installed in a motor junction box, RTD-lead shielding is not required. Connect the surge-protection (SPG) terminal 20 to
terminal 19 ( ), and earth terminal 19. The MPS-RTD has two switches to select its network address. See Figs. 3.8 and 3.10. Up to three MPS-RTD modules can be connected to the I/O MODULE bus, and each RTD-module address must be unique. If one module is used, address 1 must be used. If two RTD modules are used, addresses 1 and 2 must be used. If three RTD modules are used, addresses 1, 2, and 3 must be used. Table 3.2 shows the addressing selection format.
TABLE 3.2 MPS-RTD ADDRESS SELECTION
ADDRESS
SWITCH 1
SWITCH 2
0
(Offline)
Open
Open
1
(First RTD Module)
Closed
Open
2
(Second RTD Module)
Open
Closed
3
(Third RTD Module)
Closed
Closed
3.2.4 MPS-DIF CONNECTIONS
The MPS-DIF CT-input terminal blocks accept 22 to 10 AWG (0.3 to 4.0 mm2) conductors. The remaining MPS-DIF clamping blocks accept 24 to 12 AWG (0.2 to
2.5 mm2) conductors. Connect the MPS-DIF to the MPS-CTU using four­conductor shielded cable (Belden 3124A or equivalent) as shown in Fig. 3.9. Connect the surge-protection (SPG) terminal 15 to terminal 14 ( ), and earth terminal 14.
3.2.4.1 CORE BALANCE
The core-balance connection is shown in Fig. 3.11. To minimize power-cable and CT-lead length, both the differential CT’s and the MPS-DIF can be located near the motor. The primary rating of the differential CT does not have to match the phase-CT primary rating and is usually selected with a lower ratio resulting in more sensitive differential protection. The core-balance method avoids CT-matching issues and is the preferred connection.
3.2.4.2 MPS SUMMATION
The MPS summation connection uses three phase CT’s and three differential CT’s as shown in Fig. 3.12. Both CT ratio and CT-saturation characteristics must be matched to avoid differential currents under motor starting and running conditions. The MPS-DIF module should be located near the MPS-CTU to minimize CT wire length. It is preferred to use three dedicated phase CT’s and three core-balance differential CT’s as described in Section 3.2.4.1. For the delta connection, the MPS FLA Rating is set equal to the motor’s full-load current multiplied by √3. Power, power factor and energy measurements are not correct for the delta connection.
3.2.4.3 DIF SUMMATION
The DIF summation connection uses six differential CT’s as shown in Fig. 3.13. Both CT-ratio and CT­saturation characteristics must be matched to avoid differential currents under motor starting and running conditions. It is preferred to use three core-balance CT’s as described in Section 3.2.4.1. This six CT connection allows the CT’s and MPS-DIF to be placed near the motor to minimize power-cable and CT-lead length.
3.2.5 DIELECTRIC-STRENGTH TESTING
Dielectric-strength testing should be performed only on CT inputs, PT inputs, output relays, and digital inputs. Unplug all other I/O and remove the SPG connection (terminal 4 to terminal 4A) on the MPS-CTU during dielectric-strength testing.
Page 32
Page 3-6 MPS Motor Protection System Rev. 6-F-022117
System Wiring
FIGURE 3.9 Two Examples of I/O Module Connections.
Page 33
Page 3-7 MPS Motor Protection System Rev. 6-F-022117
System Wiring
FIGURE 3.10 MPS-RTD Connection Diagram.
Page 34
Page 3-8 MPS Motor Protection System Rev. 6-F-022117
System Wiring
FIGURE 3.11 Core Balance Connection.
FIGURE 3.12 MPS Summation Connection.
Page 35
Page 3-9 MPS Motor Protection System Rev. 6-F-022117
System Wiring
FIGURE 3.13 DIF Summation Connection.
Page 36
Page 3-10 MPS Motor Protection System Rev. 6-F-022117
System Wiring
This page intentionally left blank.
Page 37
Page 4-1 MPS Motor Protection System Rev. 6-F-022117
Operation and Setup
4. OPERATION AND SETUP
4.1 GENERAL
The MPS-CTU can operate independently. It can also operate in conjunction with network communications, the MPS-OPI, MPS-RTD and the MPS-DIF. All settings are stored in the MPS-CTU and can be accessed using the OPI or the network communications interface. Use SE-Comm-RIS software and an SE-485PP or SE-485-DIN serial converter to program with a personal computer. In the following sections, menu items and setup parameters are listed in italics and are shown in the format displayed on the OPI. The OPI cannot display subscripts and superscripts. Menu selection is in the following format: Menu 1 | Sub Menu 1 | Sub Menu 2 | Sub Menu 3 |……
Example: For the menu item shown in Fig. 4.1, the notation is Setup | System Ratings | CT Primary
Metering 4
Messages 4
5Setup4
Protection4
vSystem Ratings4
Starter4
6CT Primary→
•
EF-CT-Primary→
•
System Voltage→
•
Input Voltage→
•
•
•
FIGURE 4.1 Menu Example.
Fig. 4.2 shows the symbols that assist in navigating the menu system and how these symbols relate to the arrow keys on the MPS-OPI. See the menu map in Appendix A.
4.2 MPS-CTU
4.2.1 LED INDICATION
The four LED’s on the MPS-CTU indicate POWER (green), TRIP (red), ALARM (yellow), and ERROR (red). The POWER LED is ON when supply voltage is present. The TRIP and ALARM LED’s indicate a trip or alarm condition. The ERROR LED is ON during firmware updates or when there is an MPS-CTU failure.
4.2.2 RESET SWITCH
The reset switch is used to simultaneously reset all trips. Trips cannot be held off by a maintained closure.
4.2.3 PHASE-CT INPUTS
OPI Menu: Setup | System Ratings | CT Primary The setting range for the CT-primary rating is 1 to 5,000 A. To maintain specified accuracy, phase CT’s should be selected with a primary rating between 100 and 300% of motor full-load current. Current unbalance will indicate “−” if the current sequence is B-A-C. If B-A-C sequence is indicated, correct the CT connections so that power measurements will be valid.
NOTE: B-A-C sequence will cause a trip if current phase­reverse protection is enabled.
NOTE: Phase-unbalance and phase-loss testing requires three-phase inputs to the MPS.
FIGURE 4.2 Menu Symbols.
Page 38
Page 4-2 MPS Motor Protection System Rev. 6-F-022117
Operation and Setup
4.2.4 EARTH-FAULT-CT INPUT
OPI Menu: Setup | System Ratings | EF-CT Primary The setting range for the earth-fault-CT-primary rating is 1 to 5,000 A. The CT-primary rating is 5 A for sensitive CT’s—EFCT-1 and EFCT-2.
4.2.5 VOLTAGE INPUTS
OPI Menu: Setup | System Ratings Select the voltage-connection type (1 PT line-line, 2 PT line-line, 3 PT line-neutral/direct) to enable voltage­measuring functions. System Voltage is the system line­to-line voltage. The system voltage range is 120 V to 25 kV. For the 1-PT and 2-PT connections, Input Voltage is the PT-secondary voltage when system voltage is applied. For the 3-PT connection, the Input Voltage is the PT-secondary line-to-line voltage. For the direct connection, set Input Voltage the same as the System Voltage setting. In all cases, line-to-line voltages are displayed. Voltage unbalance will indicate “−” if the voltage sequence is B-A-C. If B-A-C sequence is indicated, correct the PT connections so that power measurements will be valid.
NOTE: The 1-PT connection does not allow detection of voltage unbalance.
NOTE: B-A-C sequence will cause a trip if voltage phase-reverse protection is enabled.
4.2.6 MOTOR DATA
OPI Menu: Setup | System Ratings OPI Menu: Setup | Protection ⏐ Overload
Motor data must be entered for the FLA Rating, Frequency, and Service Factor. If a tachometer is used,
the Sync Speed is required. If the starter selected requires two FLA ratings, FLA Rating 2 must be entered. The Frequency setting determines the sampling rate used by the MPS for current and voltage measurements. If Sync to ASD is selected as the analog-input type, the Frequency setting is not used and the analog output from an adjustable-speed drive determines the sampling rate used by current- and voltage-measuring algorithms. See Section 5.29.2. Locked-rotor current, cold locked-rotor time, and hot locked-rotor time must be entered in the Protection | Overload menu to provide customized overload protection. See Section 5.2.
4.2.7 OUTPUT RELAY ASSIGNMENT
OPI Menu: Setup | Relay Outputs | Relay x Each of the five output relays can be assigned to one of the functions listed in Table 4.1. More than one relay can be assigned the same function. Note that Relay 5 is a solid-state relay with a low current rating and should only be used for interlocks or annunciation. Relay assignments Starter RLYA, Starter RLYB, Starter RLYC, and Starter RLYD operate in conjunction with
MPS starting functions to control the motor-starter contactor(s). See Section 6. Contactor status can be monitored using auxiliary contacts and the digital inputs. See Section 4.2.8 and Figs. 6.9 to 6.23.
TABLE 4.1 OUTPUT-RELAY FUNCTIONS
FUNCTION
ASSIGNMENT OR ACTION
Starter RLYA
Relay is assigned to the Starter Relay A function.
Starter RLYB
Relay is assigned to the Starter Relay B function.
Starter RLYC
Relay is assigned to the Starter Relay C function.
Starter RLYD
Relay is assigned to the Starter Relay D function.
Trip1
Relay operates when a trip occurs in a protective function assigned Trip1, Trip1&2, Trip1&3, or Trip1,2,&3. Fail-safe or non-fail­safe mode selection is active.
Trip1 Pulse
(1)
Trip1 energizes the relay for the time duration specified by the RY Pulse Time set point.
Trip2
Relay operates when a trip occurs in a protective function assigned Trip2, Trip1&2, Trip2&3, or Trip1,2,&3. Fail-safe or non-fail­safe mode selection is active.
Trip3
Relay operates when a trip occurs in a protective function assigned Trip3, Trip1&3, Trip2&3, or Trip1,2,&3. Fail-safe or non-fail­safe mode selection is active.
Alarm1
Relay operates when an alarm occurs in a protective function assigned Alarm1, Alarm1&2, Alarm1&3, or Alarm1,2,&3. Fail­safe or non-fail-safe mode selection is active.
Alarm2
Relay operates when an alarm occurs in a protective function assigned Alarm2, Alarm1&2, Alarm2&3, or Alarm1,2,&3. Fail­safe or non-fail-safe mode selection is active.
Alarm3
Relay operates when an alarm occurs in a protective function assigned Alarm3, Alarm1&3, Alarm2&3, or Alarm1,2,&3. Fail­safe or non-fail-safe mode selection is active.
Local
Relay energized when Local starter control is selected.
Interlock
Relay is energized when all digital-input interlocks are completed.
Current
Relay is energized when current is detected.
Run Mode
Relay is energized when motor is running. (Current <125% for Run-Mode Delay)
Sequence Complete
Relay is energized when the starter Start Time has elapsed.
Start Inhibit
Relay is energized when in an I2t or starts-per-hour inhibit condition.
Watchdog
Relay is energized when the supply voltage is applied and the MPS is operating properly.
Reduced OC
Relay is energized when in maintenance mode (ROC = On).
None
(2)
No Assignment (Default).
(1)
Assign this function to only one relay. Non-fail-
safe operation only.
(2)
Relay outputs must be assigned. Default is None.
Page 39
Page 4-3 MPS Motor Protection System Rev. 6-F-022117
Operation and Setup
When a trip occurs, all assigned starter-control relays (Starter RLYA to Starter RLYD) are de-energized and relays assigned the Trip1, Trip2, or Trip3 function operate. The trip signal may originate from a protective function, from a digital input assigned the Trip1 function, or from a communications network command. See Sections 4.2.8 and 6. Relays assigned to trip or alarm functions operate in fail-safe or non-fail-safe mode. Set the mode using the Setup ⏐ Relay Outputs ⏐ Relay x ⏐ Mode menu. Except for overload trips, which can be selected to auto-reset, trips must be reset with an MPS-OPI, a digital input, or a network command. A trip cannot be reset when the trip condition is present. When a protective function issues an alarm, relays assigned to the corresponding Alarm1, Alarm2, or Alarm3 function operate. Alarms auto-reset when the alarm condition is corrected. Relays assigned the Interlock function energize when all digital inputs assigned the Interlock function are valid (voltage detected at digital input).
4.2.8 DIGITAL INPUTS 1 TO 7
OPI Menu: Setup | Digital Inputs | Digital Input x |
Input x Function
OPI Menu: Setup | Digital Inputs | Digital Input x | In x Start Bypass OPI Menu: Setup | Digital Inputs | Digital Input x | In x Bypass Delay OPI Menu: Setup | Digital Inputs | Digital Input x | In x Trip Delay
Each digital input can be assigned to one of the functions listed in Table 4.2. More than one digital input can be assigned the same function. Start inputs are not active when Protection Only is selected as the starter type. The STOP function is always active. In Protection Only mode, STOP initiates a Trip1 signal. Each digital input assigned the Trip1 function has Start
Bypass, Bypass Delay, and Trip Delay set points. When Start Bypass is enabled, the Trip1 function is bypassed
during a start for the duration specified by Bypass Delay. Since start detection is based on motor current, this feature can be used in the Protection Only mode. After the Bypass Delay, the Trip1 function is enabled and a trip occurs if the digital-input voltage is removed for the time specified by the Trip Delay. If Start Bypass is disabled, Bypass Delay is not used and the Trip1 function is always enabled. The bypass feature can be used in pump-control applications to allow time for a pressure switch to close. Reset inputs are “one-shot” resets that require a transition from open to closed. Maintaining a reset switch closure does not inhibit trips.
TABLE 4.2 DIGITAL-INPUT FUNCTIONS
FUNCTION
STATE
(1)
Start1
1 = Start1 (Momentary)
Start2
1 = Start2 (Momentary)
Local Select -
1 = Per CONTROL SELECT Setting 0 = Local Control
Local Select +
0 = Local Control
(2)
1 = Per CONTROL SELECT Setting
Local Start1
(2)
1 = Start1 (Momentary)
Local Start2
(2)
1 = Start2 (Momentary)
2-Wire Start1
1 = Start1 (Maintained) 0 = Stop
2-Wire Start2
1 = Start2 (Maintained) 0 = Stop
Stop
1 = Start Allowed 0 = Stop
RLYA Status
1 = Contactor Closed 0 = Contactor Open
RLYB Status
1 = Contactor Closed 0 = Contactor Open
RLYC Status
1 = Contactor Closed 0 = Contactor Open
RLYD Status
1 = Contactor Closed 0 = Contactor Open
Interlock
1 = Start Allowed (If all interlocks are valid.) 0 = Start Not Allowed
Trip1
1 = No Trip1 0 = Trip1 (Delays Selectable)
Reset
1 = Reset Trips
FLA2 Select
(3)
1 = Select FLA2 0 = Select FLA1
Limit1 Stop
1 = Start1 Allowed 0 = Start1 Stop
Limit2 Stop
1 = Start2 Allowed 0 = Start2 Stop
Reduced OC
1 = Reduced OC Set Point Not Operational 0 = Reduced OC Set Point Operational
None
No Assignment (Default)
(1)
1 = Input voltage applied, 0 = Input voltage not
applied.
(2)
Interlocks bypassed in LOCAL.
(3)
Applies only to Protection Only mode.
LOCAL is selected using the OPI, the digital input, or by network communications. The Local Select source is responsible for de-selecting. For example if both the digital input and the network communications select LOCAL, both must also de-select LOCAL. The Local
Select – and Local Select + selections allow the digital input to select LOCAL control. Both positive and negative logic versions allow implementation of various “Hand-Off-Auto” control schemes. See Section 6 for CONTROL SELECT operation.
In applications where MPS starter functions are not used, FLA2 Select can be used to switch between FLA1 and FLA2. This applies only to Protection Only mode. The selected FLA is displayed in the Metering ⏐ System State menu.
Page 40
Page 4-4 MPS Motor Protection System Rev. 6-F-022117
Operation and Setup
Limit1 Stop and Limit2 Stop are limit-switch inputs typically used with reversing starters. Limit1 Stop is a stop input associated with Start1 and Limit2 Stop is a stop input associated with Start2. The Reduced OC selection operates in conjunction with the reduced overcurrent set point which must be enabled. See Section 5.5. When Reduced OC is selected and no digital input voltage is applied, the reduced overcurrent set point is operational. When digital input voltage is applied, the reduced overcurrent set point is not operational. The following rules apply when multiple inputs are assigned the same function:
• Start1, Start2, Local Start1, and Local Start2:
Momentary voltage on any input will initiate a start. (MPS must be in LOCAL for Local Start1 and Local Start2 operation.)
• Stop: Voltage must be present on all inputs to allow
an MPS-controlled start.
• Interlock: Voltage must be present on all inputs to
allow an MPS-controlled start and to energize an interlock output relay. Digital inputs programmed as Interlock are bypassed in LOCAL. Interlocks must remain valid while the motor is running.
• RLYA, RLYB, RLYC, and RLYD Status: Voltage
applied to any input programmed for a contactor status results in contactor-closed status.
• Reset: Voltage applied to any input will reset trips.
• 2-Wire Start1 and 2-Wire Start2: Voltage on any
input will initiate a start. All inputs must be open for a stop.
• FLA2 Select: Voltage on one or more inputs assigned
to FLA2 Select will select FLA2.
4.2.9 TACHOMETER INPUT (HSI)
OPI Menu: Setup | System Ratings | Sync Speed OPI Menu: Setup | Digital Inputs | Tachometer
This input is provided for connection to a 24-Vdc proximity sensor for speed measurement. Set the number of pulses per revolution and enable the High-Speed Input in the Tachometer menu. Pulse-frequency range is 10 Hz to 10 kHz. These two settings are required for RPM readings. If Failure to Accelerate protection is used, set the motor’s synchronous speed in the Sync Speed menu. To fully utilize a speed-setting range from 10 to 100%, a full­speed frequency of at least 100 Hz is required. The MPS averages 16 pulse periods to determine speed.
4.2.10 ANALOG OUTPUT
OPI Menu: Setup | Analog Output | Output Parameter A 25-mA programmable current output is provided on
the CTU. Analog-output parameters are shown in Table 4.3. Factory calibration is 4-20 mA. If calibration is required, use the Analog Output menus. Zero Calibration:
• Select Zero in the Output Parameter menu.
• Measure the output current and adjust the Zero
Calibrate setting for the desired output. The calibration number for 4 mA will be in the range of 100 to 110.
Full-Scale Calibration:
• Select Full Scale in the Output Parameter menu.
• Measure the output current and adjust the
FS Calibrate setting for the desired output. The calibration number for 20 mA will be in the range of
540 to 550. Calibration numbers are not changed when factory defaults are loaded.
TABLE 4.3 ANALOG-OUTPUT PARAMETERS
PARAMETER
FULL SCALE
COMMENTS
Phase Current
PH-CT-Primary Rating
Maximum of 3 Phases
Earth Leakage
EFCT-Primary Rating
Differential Current
DF-CT-Primary Rating
Maximum of 3 Currents
Used I2t Capacity
100% I2t
Stator Temperature
(1)
200°C (392°F)
Maximum of Stator RTD’s
Bearing Temperature
(1)
200°C (392°F)
Maximum of Bearing RTD’s
Load Temperature
(1)
200°C (392°F)
Maximum of Load RTD’s
Ambient Temperature
(1)
200°C (392°F)
Maximum of Ambient RTD’s
Voltage
System Voltage
Maximum Line-to-Line Voltage
Unbalance (I)
1.0 per unit or 100%
I2/I1
Power Factor
1.0
Absolute Value
Real Power
CT Primary × System Voltage × √3
Absolute Value
Reactive Power
CT Primary × System Voltage × √3
Absolute Value
Apparent Power
CT Primary × System Voltage × √3
Absolute Value
Zero
Not Applicable
Used for Zero Calibration
Full Scale
Not Applicable
Used for Full-Scale Calibration
Speed
Synchronous Speed
(1)
Output range is 0 to 200°C (32°F to 392°F). The output defaults to the calibrated zero output for an
open or shorted RTD sensor.
Page 41
Page 4-5 MPS Motor Protection System Rev. 6-F-022117
Operation and Setup
4.2.11 ANALOG INPUT
OPI Menu: Setup | 4-20 Analog In | Input Function The analog input function is selectable as Metering
Only, Protection, Sync to ASD, or Motor Speed.
4.2.11.1 METERING ONLY
OPI Menu: Setup | 4-20 Analog In ⏐ Metering Only
When Metering Only is selected, an analog input does not affect MPS operation, but its value can be observed in the Metering menu and with a communications network.
4.2.11.2 PROTECTION
OPI Menu: Setup | 4-20 Analog In ⏐ Protection
The Protection analog input has high- and low-level trip and alarm set points. A high-level trip or alarm occurs when the 4-20-mA input exceeds the high-level trip or alarm set point. A low-level trip or alarm occurs when the 4-20-mA input is lower than the low-level trip or alarm set point.
4.2.11.3 SYNCHRONIZE TO ASD
OPI Menu: Setup | 4-20 Analog In ⏐ Sync to ASD
When Sync to ASD is selected the MPS uses the 4-20 mA input to set the internal sampling rate for current and voltage inputs. Select drive-frequency values corresponding to 4 and 20 mA.
4.2.11.4 MOTOR SPEED
OPI Menu: Setup | 4-20 Analog In ⏐ Motor Speed This selection overrides the selections for the high-
speed tachometer input – failure-to-accelerate protection and speed metering use the analog input as the source of speed information.
4.2.12 STARTER
OPI Menu: Setup | Starter As a default, Starter Type is set to Protection Only. When a starter type is selected, output relays must be assigned for contactor control. See Section 4.2.7. Digital inputs must be assigned if contactor-status feedback is required. See Section 4.2.8. See Section 6 for starter information.
4.2.13 PROTECTION
OPI Menu: Setup | Protection OPI Menu: Setup | System Ratings | Run Mode Delay See Section 5 for protective function details. As a minimum, locked-rotor current and time must be set for overload protection. Some protective functions are active after the Run- Mode Delay.
4.2.14 MISCELLANEOUS CONFIGURATION
OPI Menu: Setup | System Config System Name Appears on many of the display
screens and can be set by the user. (18-character alphanumeric field)
Password Used to change the 4-character
alphanumeric password.
Clock Setting Used to set the date, 24-hour clock,
and IRIG set points. Daylight savings time is not supported.
Password Timeout Used to set the password time-out
delay. Delay is measured from last key press.
Maintenance Used to:
• Clear event records, trip counters, energy values, and run hours
• Load defaults
• View firmware version and
serial numbers
• Unlock local control if communication is lost
• Update Firmware
4.2.15 NETWORK COMMUNICATIONS
OPI Menu: Setup ⏐ Hardware ⏐ Network Comms
The standard interface on the MPS is an RS-485 network. Modbus® RTU and A-B® DF1 protocols are supported. The protocol, network ID (address), error checking, and baud rate are selectable. See Appendices C, D, E, and F. If equipped with an optional network interface, refer to the appropriate optional communications-interface manual.
4.3 MPS-OPI
4.3.1 GENERAL
See Fig. 4.3. The Operator Interface (OPI) is used to perform motor-control functions, display meter readings, and program the MPS-CTU. Set points are not resident in the OPI. Control voltage for the MPS-OPI (24 Vdc) is supplied by the CTU and communications with the CTU is through an RS-485 link. This allows the MPS-OPI to be mounted up to 1.2 km (4,000’) from the CTU. Up to three OPI’s can be used with each CTU.
4.3.2 CONFIGURING THE MPS-CTU FOR OPI OPERATION
OPI Menu: Setup | Hardware | OPI Display
Select the number of OPI's in the Number of OPI's menu. The MPS-CTU supports up to three OPI’s. In multiple-OPI systems, all OPI's display the same information and the CTU will process key presses from all OPI's. If an OPI is not used, set number of OPI's to 1 (default). A loss-of-communication trip can be enabled in the
OPI-Loss Trip menu. Display intensity can be set in the Intensity menu.
To extend the life of the vacuum-florescent display, a screen saver is provided and enabled using the Screen Saver menu. The screen saver activation time is defined by the Setup | System Config | Password Timeout setting.
Page 42
Page 4-6 MPS Motor Protection System Rev. 6-F-022117
Operation and Setup
4.3.3 STARTER CONTROL
OPI Menu: Setup | Starter | Starter Type OPI Menu: Setup | Hardware | OPI Display | OPI Ctrl Select A starter type other than Protection Only must be selected for starter functions to become operational. The OPI has a CONTROL SELECT key and three yellow LED’s (labeled REMOTE, OPI, and LOCAL) to select and indicate the start sources that the MPS will respond to. Each of the start sources can be enabled or disabled in the OPI Ctrl Select menu, and the CONTROL SELECT key allows the operator to choose from among the enabled start sources. The factory default has all sources enabled and REMOTE selected. Regardless of the control setting, all stop sources are always enabled.
4.3.3.1 OPI CONTROL
If only the OPI LED is on, the MPS is under OPI control and start keys on the OPI are the only start source the MPS will respond to. If the OPI has been enabled as a start source for remote control, the OPI LED will also be on when remote control is selected. In this case, the MPS will also respond to the other sources enabled in remote control (Remote Group).
4.3.3.2 LOCAL CONTROL
OPI Menu: Setup | Digital Inputs | Digital Input x | Input x Function When the LOCAL LED is on, the MPS is under local control and digital inputs programmed as Local Start 1 or
Local Start 2 are the only start sources the MPS will respond to.
NOTE: The I2t Start Inhibit function and digital inputs programmed as Interlock are bypassed in local control.
Local control can also be selected with a network command or by a digital input programmed for Local Select—both have priority over the CONTROL SELECT key. If either or both methods force the MPS into local control and then release local control, the MPS will return to the previous control setting. Each local-control source must release local control to allow the MPS to return to the previous control setting.
4.3.3.3 REMOTE CONTROL
OPI Menu: Setup | Starter | Remote Group When the REMOTE LED is on, MPS start control is from the start sources enabled in the Remote Group menu. Start source selections are Digital Inputs, OPI, and Network. If Digital Inputs is enabled, digital inputs programmed for Start1, Start2, 2-Wire Start1, and 2-Wire Start2 are enabled. If OPI is enabled, the start keys on the OPI are enabled and if Network is enabled, start commands from the network are enabled.
NOTE: The OPI STOP key and digital STOP inputs always cause a stop.
FIGURE 4.3 MPS-OPI Interface.
Page 43
Page 4-7 MPS Motor Protection System Rev. 6-F-022117
Operation and Setup
4.3.4 METERING
OPI Menu: Metering
OPI Menu: Setup | Hardware | OPI Display | Meter
Summary
When Metering is selected in the main menu, press the right-arrow key to access a list of metering displays. Use the up- and down-arrow keys to scroll through the display list. Pressing the right-arrow key displays the selected metering information. See the MPS-OPI menu map in Appendix A. RESET is a “hot key” that is active in all meter displays. Pressing RESET causes a jump to the Trip and Alarm display to allow trips to be viewed and reset. Press RESET again to reset a trip. Pressing ESC or the left-arrow key causes a return to the Metering display. Many displays include per unit (pu) values where
1.0 pu is equal to 100%. Ia, Ib, Ic, I1, and I2 are in per unit of full-load current. Ig is in per unit of earth-fault-CT­primary rating. Vab, Vbc, and Vca are in per unit of System Voltage. The unbalance display indicates minus (-) if current inputs are not sequenced A-B-C. The IEEE convention is used for power displays: +Watts, +Vars, -PF (Lag) Importing Watts,
Importing Vars
+Watts, -Vars, +PF (Lead) Importing Watts,
Exporting Vars
-Watts, -Vars, -PF (Lag) Exporting Watts, Exporting Vars
-Watts, +Vars, +PF (Lead) Exporting Watts, Importing Vars
The operating range for energy values is ±2E±1024, however the maximum OPI display range is ±2E±34. The Setup | Hardware | OPI Display | Meter Summary menu is used to configure the type of metering display selected by the Metering | Summary menu. In order to view the maximum amount of data, no menu title is displayed. Display selections for the Summary menu are:
• IDR Current-based metering (I), digital
inputs (D), and relay outputs (R): Average current, current unbalance, earth leakage, used I2t, digital input and relay output status.
I: xxxx A Iu: x.xx Ig:xxxx A I2t:xx% Di: 1..7: xxxxxxx Ry: 1..5: xxxxx
This selection is the default for the summary display.
• IVP Current-based metering (I), voltage (V),
unbalance, and power (P):
Average current, current unbalance, earth leakage, used I2t, average voltage, voltage unbalance, power and power factor.
I: xxxx A Iu: x.xx Ig:xxxx A I2t: xx% V: xx.xx kV Vu: x.xx P: xx.x kW PF: x.xx
This selection is applicable for an MPS using voltage inputs.
• IVPA Current-based metering (I), voltage
(V), power (P), and analog I/O (A):
Average current, average voltage, earth leakage, used I2t, power, power factor, and analog currents.
I: xxxx A V: xx.xx kV Ig:xxxx A I2t:xx% P: xx.x kW PF: x.xx
Ai:xxx% Ao: xxx% This selection is applicable when the MPS analog output is used in a process control loop. The analog input and output values provide indication of control­system operation.
For each metering display, Table 4.4 shows the information that can be displayed.
4.3.5 MESSAGES
OPI Menu: Messages Selecting this menu item allows trip and alarm messages, status messages, event records, and statistical data to be viewed and resets to be performed.
4.3.5.1 TRIP RESET
OPI Menu: Messages | Trip and Alarm Up to fifteen trip and alarm messages can be displayed in a scrollable-list format. Trip messages must be individually selected and reset when the OPI RESET key is used. All trips are simultaneously reset by digital­input reset, with the MPS-CTU RESET key or with a communications-network command. Alarms are non­latching and are displayed only for the time that the alarm condition exists. RESET is a “hot key“ to the Trip and Alarm display, except during set-point entry. In the Trip and Alarm display, press ESC or the left-arrow key to return to the display shown when RESET was pressed.
4.3.5.2 STATUS
OPI Menu: Messages | Status Messages This menu is used to display status messages. Status messages are shown in Table 4.5.
Page 44
Page 4-8 MPS Motor Protection System Rev. 6-F-022117
Operation and Setup
TABLE 4.4 METERING DISPLAY
METERING MENU
INFORMATION DISPLAY
(1)
Summary
Displays values as per the Meter Summary menu. IDR, IVP, or IVPA.
Current
Ia, Ib, Ic in A and per unit of Ip.
Unbalance (I)
I1, I2, in per unit of Ip, I2/I1 in per unit.
Earth Leakage
Ig in A and per unit of Ie.
Thermal Capacity
Used I2t in percent. Trend I2t in percent. Displays reset time when tripped on I2t. Displays time to trip if in overload. Displays time to I2t Inhibit removal. Displays time to Starts-Per-Hour Inhibit removal. Displays number of available starts.
Voltage
Vab, Vbc, Vca in kV and per unit of Vp.
Unbalance (V)
V1, V2, in per unit of Vp, V2/V1 in per unit.
Unbalance (I)
I1, I2, in per unit of FLA, I2/I1 in per unit.
Differential (A)
DIFa, DIFb, DIFc in A and per unit of Id.
Power
P in kW, Q in kVA, S in kVAR, PF.
Energy
kWh, kVAh, kVARh.
Frequency
Vab voltage in per unit of Vp and frequency in Hz.
RTD Temperatures
Summary shows maximum and minimum temperatures for stator, bearing, and load RTD’s in degrees C. Module and input numbers, name, function, temperature in degrees C for each enabled RTD.
I/O Status
Analog input in mA, digital inputs and relay outputs in binary.
System State
Date and Time, Motor Mode (Stopped, Start, Run) Displays starter state when starter is enabled. Displays active FLA when in protection-only mode. Displays RPM if tachometer input is enabled. Displays Reduced Overcurrent mode (ROC: ON, ROC: OFF) Displays ETR mode.
Comm State
Displays DF1 state as online or timed out. Displays Modbus state as online or timed out. Displays Anybus module error and status. Displays DeviceNet errors and status.
(1)
All but Summary, RTD, and System State metering displays show System Name.
TABLE 4.5 STATUS MESSAGES
MESSAGES
DESCRIPTION
INx Interlock Open
The interlock assigned to digital input x is open, preventing a start.
INx Stop Open
The stop switch assigned to digital input x is open, preventing a start.
INx Limit1 Open
The Limit1 switch assigned to digital input x is open, preventing a Start1.
INx Limit2 Open
The Limit2 switch assigned to digital input x is open, preventing a Start2.
I2t Start Inhibit
The Used I2t has exceeded the I2t Inhibit level. A start is prevented if I2t Start Inhibit is enabled.
Sph Start Inhibit
The number of starts per hour has been exceeded. A start is prevented if a starts-per hour trip or alarm is enabled.
t° Disabled by ETR
Indicates that the MPS is in ETR mode. Does not prevent a start.
Backspin Timer On
When a stop is issued and the backspin timer is enabled, a start is prevented until the backspin timer times out. This message is displayed when the backspin timer is on.
Page 45
Page 4-9 MPS Motor Protection System Rev. 6-F-022117
Operation and Setup
4.3.5.3 DATA LOGGING
OPI Menu: Messages | Event Records Trip-record data, start-record data, and Emergency Thermal Resets (ETR) are logged. Trip-record data includes the time of trip, cause of trip, and pre-trip
(1)
data. ETR records contain a snapshot of the data prior to an ETR. Trip or ETR records include:
• Time Stamp YY/MM/DD HH:MM:SS
• Vab, Vbc, Vca, Ia, Ib, Ic, and 3I0 at time of trip or ETR
• Unbalance (I2/I1, V2/V1) at time of trip or ETR
• P, Q, S, and PF at time of trip or ETR
(1)
• Used I2t at time of trip or ETR
• PTC/RTD temperature data if applicable
• Differential module data if applicable
Start records
(2)
are triggered by motor current and
include:
• Time Stamp YY/MM/DD HH:MM:SS
• Maximum values of Ia, Ib, Ic, and 3I0 during the start
• Maximum value of I2/I
(4)
, V2/V1 during the start
• Minimum values of Vab, Vbc, Vca during the start
• Maximum differential currents during the start if
applicable
• I2t used during the start
(3)
• Start duration
• PTC/RTD temperature data if applicable
Record Type .............................. Trip/Start/ETR
Number of Records .................... 64 (First In First Out)
(1)
Recorded values for power quantities (P, Q, S, PF)
are averages of measurements over the previous 16 cycles.
(2)
Values updated at 0.5-s intervals during a start.
Record logged when the Run mode is entered.
(3)
Starting I2t can be used to determine the I2t Lockout
Level. See Section 5.2.
(4)
Measurements enabled 0.5 s after start current is
detected.
4.3.5.4 STATISTICAL DATA
OPI Menu: Messages | Statistics OPI Menu: Setup | System Config | Maintenance
The MPS records the following statistical data:
• Running hours.
• Counters for all trips.
Statistical data can be cleared in the Maintenance menu.
4.3.5.5 EMERGENCY THERMAL RESET
OPI Menu: Messages | Emerg I2t Reset The Emerg I
2
t Reset menu is used to reset the thermal
memory. See Section 5.2.3.
4.3.6 PASSWORD ENTRY AND PROGRAMMING
OPI Menu: Setup | System Config | Password Timeout
NOTE: Factory default password is 1111.
All set points are locked from changes until the four­character password is entered. If set-point access is locked, the user is prompted to enter the password. Once entered, set-point access is allowed and remains enabled until a key has not been pressed for the time defined by the Password Timeout set point.
EXAMPLE: Prior to password entry:
When ENTER is pressed, the Password Entry display is shown:
Use the left- and right-arrow keys to select the position of the flashing cursor. Use the up- and down-arrow keys to select password characters. Press ENTER. When the correct password is entered, a flashing cursor is displayed, the set-point range and units are shown, and set points can be changed.
Use the up- and down-arrow keys to change a set­point update-field character, and use the left- and right­arrow keys to move between characters. Press ENTER to update the set point, or press ESC to exit the display without changing the set point. A set point is set to the minimum or maximum value of its range if an out-of­range value is entered. Press ESC to exit the set-point­update screen.
Page 46
Page 4-10 MPS Motor Protection System Rev. 6-F-022117
Operation and Setup
The sequence for set-point characters depends upon the set-point type. The character sequence for numeric set points is:
. . . 0 1 2 3 4 5 6 7 8 9 . 0 1 2 3 . . . . .
The character sequence for string set points is:
. . . [0…9] [A…Z] [a…z] SP - . / [0…9] [A…Z] . . . . .
Characters forming a series are shown in brackets and “SP” represents the space character. For set points requiring selection from a list, the up and down arrow keys are used to scroll through the items. In the same manner as menu items, selections are displayed using one of the three cursor symbols (½«²) preceding the item. Pressing ENTER selects the item
and that item is indicated by the “∗” symbol to its right.
EXAMPLE:
4.4 MPS-RTD
OPI Menu: Setup | Hardware | RTD Modules OPI Menu: Setup | Protection | RTD Temperature The MPS-RTD module extends MPS protective functions to include multiple-RTD temperature monitoring. It has eight inputs that can be individually configured for RTD type, trip and alarm settings, name, and function. The RTD types are 10-Ω copper, 100-Ω nickel, 120-Ω nickel, and 100-Ω platinum. Functions are stator, bearing, load, and ambient. Control voltage for the MPS-RTD (24 Vdc) is supplied by the MPS-CTU and communication is through an RS-485 link. This allows the MPS-RTD to be mounted up to 1.2 km (4,000’) from the MPS-CTU. To enable RTD protection, the total number of modules must be selected in the Total Modules menu and Temperature Trip Action or Alarm Action must be enabled. If RTD protection is disabled, metering information is still provided. Up to three modules can be used. In the RTD Modules menu, the action to be taken by the MPS-CTU in response to loss of communication is selected. When the hardware has been configured, temperature set points and sensor-failure action selections in the RTD Temperature menu are used for RTD temperature protection. See Section 5.27.
4.5 MPS-DIF
OPI Menu: Setup | Hardware | DIF Module OPI Menu: Setup | Protection | Differential The MPS-DIF Differential Module extends MPS protective functions to include phase-differential monitoring. It has three differential-CT inputs that can be used in a three-CT core-balance connection, a six­differential-CT connection, or a six-CT connection that includes phase-CT MPS inputs. The core-balance, three­CT connection is recommended. Control voltage for the MPS-DIF (24 Vdc) is supplied by the MPS-CTU and communication is through an RS-485 link. This allows the MPS-DIF to be mounted up to 1.2 km (4,000’) from the MPS-CTU, and the link can be shared by other MPS I/O modules. Enable the module and loss-of-communications protection in the Hardware | Dif Module menu, and choose protection settings in the Protection | Differential menu. See Section 5.25.
4.6 WAVEFORM CAPTURE
The MPS continuously samples seven channels of data consisting of the three-phase currents, three-phase voltages, and the earth leakage current. The sample rate is fixed at 16 samples/cycle and sample data (Trace Data) for each channel are stored in a 4800 sample memory. This provides a record depth of 300 cycles, or 5 seconds of pre-trip data at 60 Hz. When a trip occurs, Trace Data capture is halted and a date and time stamp is added. Trace Data values are retrieved using SE-Comm-RIS which generates an industry-standard COMTRADE and CSV file. See Appendix E for data mapping definitions and conversion formulas. The Setup | System Config | Trace Auto-Start menu is used to set the Trace Data start mode after a trip has occurred. When enabled, Trace Data capture automatically starts when reset is pressed. When disabled, Trace Data capture requires a manual re-start using the Messages | Re-Start Trace. This allows the MPS to be reset and the trip data to be analyzed at a later time. Trace Data start can also be activated using Command 13 via the communications interface. Trace Data are stored in volatile memory and are lost if the MPS loses supply voltage. Regardless of the Trace Auto-Start setting, waveform capture starts automatically on power-up if there are no previous trips.
Page 47
Page 5-1 MPS Motor Protection System Rev. 6-F-022117
Protective Functions
5. PROTECTIVE FUNCTIONS
5.1 GENERAL
The MPS measures true RMS, peak, and fundamental­frequency values of current and voltage. Fundamental­frequency values (magnitude and phase angle) are obtained using Discrete-Fourier Transform (DFT) filtering that rejects dc and harmonics. The type of measurement used for a protective function is indicated in each section. Unless otherwise indicated, protective functions have a programmable definite-time characteristic. Each protective function can be assigned a trip action that defines the output contact(s) used. Except for overload protection, which has auto-reset available, MPS trips are latched. Trips are logged.
Trip-action selections are:
• Disable
• Trip1
(1)
• Trip2
(2)
• Trip3
(2)
• Trip1 and Trip2
• Trip1 and Trip3
• Trip1 and Trip2 and Trip3
• Trip2 and Trip3
(1)
Initiates a starter stop. See Section 6.
(2)
Does not initiate a starter stop. See Section 6.
Most protection functions can be assigned an alarm action. Alarms auto-reset and are not logged.
Alarm-action selections are:
• Disable
• Alarm1
• Alarm2
• Alarm3
• Alarm1 and Alarm2
• Alarm1 and Alarm3
• Alarm1 and Alarm2 and Alarm3
• Alarm2 and Alarm3
To operate output contacts, trip and alarm actions must be assigned to output relays using the Setup | Relay Outputs
menu. See Section 4.2.7.
NOTE: When starter functions are used, only set points with a Trip Action that includes Trip1 will cause the starter to stop when a trip occurs.
When enabled, Jam, Power-Factor, Undercurrent, and Underpower protection are not active during a start and are active in the Run mode. The Run mode is initiated when motor current is between 1.5 x (CT-Primary Rating/FLA) and 125% FLA for the duration of the setting in the Setup ⏐ System Ratings ⏐ Run Mode Delay menu.
Run Mode Delay is adjustable from five to 120 seconds. Run-mode status is displayed in the Metering | System State menu. One of three states are indicated: Motor:Start, Motor:Run, or Motor:Off. The motor status line also indicates one of two states for the Reduced Overcurrent (ROC) feature: ROC:OFF or ROC:ON. See Section 5.5.
NOTE: See Appendix B for default set-point values. Per-unit notation (pu) is used. 1 pu = 100%.
5.2 OVERLOAD
At a minimum, for customized thermal-overload protection, motor data, must be entered for Full-Load Current, Service Factor, Locked-Rotor Current, Cold Locked-Rotor Time, and Hot Locked-Rotor Time.
5.2.1 THERMAL MODEL
OPI Menu: Setup | Protection | Overload OPI Menu: Setup | System Ratings A NEMA- or K-factor-based thermal-model algorithm can be selected. The NEMA-based algorithm uses the square of the maximum RMS phase current as the thermal-model input:
2
2
rmsmax
II =
I in per unit of FLA
The K-factor-based algorithm uses a thermal-model input based on true positive- and negative-sequence component values:
A conservative value for k is:
k =
230
I
L
2
Where:
IL=
locked rotor current
full load current
The thermal time constant (τ) used by the thermal model to provide starting and running I2t protection is:
unitperinfactorservicesf
ondssecintimerotorlockedcoldT
:Where
I
sf
ln
T
C
2
L
2
C
=
=
⎟
⎟ ⎠
⎞
⎜
⎜ ⎝
⎛
−−=τ1
When the motor is stopped, the thermal model uses a time constant that is user selectable as a multiple (Cooling Factor) of the thermal time constant (τ).
Page 48
Page 5-2 MPS Motor Protection System Rev. 6-F-022117
Protective Functions
The cold-curve time-to-trip (t) for current above FLA × sf is:
τ×
⎟
⎟ ⎠
⎞
⎜
⎜ ⎝
⎛
−−=
2
2
1
I
sf
lnt
The MPS provides indication of thermal trend and used thermal capacity. Thermal trend is the value that used thermal capacity is tending toward and it is a function of the square of motor current. For currents greater than or
equal to FLA × sf, time-to-trip is displayed in Metering | Thermal Capacity. The thermal trend value (Trend I2t) is:
%100
2
2
2
×
⎟
⎟ ⎠
⎞
⎜
⎜ ⎝
⎛
=
sf
I
tITrend
For currents less than FLA × sf, the thermal trend value is:
ondssecintimerotorlockedhotT
Where
T
TT
sf
I
tITrend
H
C
HC
=
×
⎟
⎟ ⎠
⎞
⎜
⎜ ⎝
⎛
−
×
⎟
⎟ ⎠
⎞
⎜
⎜ ⎝
⎛
=
:
%10 0
2
2
2
The curve shown in Fig. 5.1 is a Class-20 thermal­protection curve (20-s trip @ 600% FLA) with a service factor of 1.15. FLA multiplied by service factor is the current at which used thermal capacity begins to trend towards a trip. Time-to-trip approaches infinity when I = FLA × sf. Service factor has little influence on time-to­trip when motor current is greater than 300% FLA. MPS thermal-overload protection is dynamic. Time to trip at any overload current depends on the value of Used I2t ⎯ as Used I2t increases, time to trip decreases. This is illustrated in Fig. 5.1 by the protection curves labelled 25% Used I2t, 50% Used I2t, and 75% Used I2t. Programming software SE-Comm-RIS has a plot function to display and export MPS protection curves. An overload alarm occurs when Used I2t reaches the I2t Alarm Level set point. An overload trip occurs when Used I2t reaches 100%. When an overload trip occurs, reset is not allowed until Used I2t falls below the I2t Inhibit Level set point. The time-to-reset in minutes is:
t = -
τ
× Cooling Factor × ln(I2t Inhibit Level) / 60
Time-to-reset is displayed in the Metering ⏐ Thermal
Capacity menu. The thermal model has three reset modes; Normal, Auto, and Multiple Motor Seq. The thermal­overload reset mode is set using the Setup ⏐ Protection ⏐
Overload ⏐ I2t Reset Type menu.
In the Normal mode, a thermal-overload trip reset is not allowed until Used I2t falls below the I2t Inhibit Level setting. A reset input is required to reset the trip. Normal is the default reset mode.
In the Auto mode, a thermal-overload trip is automatically reset when Used I2t falls below the I2t Inhibit Level setting.
NOTE: If the starter circuit is configured for 2-wire control, the motor can start without warning when Auto mode is selected. A warning label may be required.
In the Multiple Motor Seq. mode, Used I2t decreases exponentially with a fixed two-second time constant when there is no motor current. This mode is used in applications where one overload relay is used to protect several motors operating in sequence with only one motor running at any one time. A two-second stop is required between starts so that Used I2t decreases sufficiently to allow the next motor to start. It is assumed that each motor is allowed to cool between starts. Motor life may be decreased if this feature is used in single-motor applications. When an overload trip occurs, the trip is latched but can be reset two seconds after the trip. When I2t Start Inhibit is enabled, the I2t Inhibit Level set point can be used to prevent a start with insufficient I2t available. When Used I2t is above the I2t Inhibit Level set point and motor current is not detected, Alarm1 is issued, starter functions Start1 and Start2 are disabled, and the relay assigned to Start Inhibit is energized. The time until a start is permitted is displayed in Metering | Thermal
Capacity, and I2t Inhibit Alarm is displayed in the Trip and Alarm message window. When Used I2t falls below the I2t Inhibit Level set point, the relay assigned to Start Inhibit is
de-energized, the inhibit alarm is cancelled, and starter functions Start1 and Start2 are enabled. Trips require a manual reset. I2t Start Inhibit is removed when current is detected. This applies in both Starter and Protection-only modes. The Start-Inhibit relay is shared with the Starts-Per­Hour function. See Section 5.23. If the motor is equipped with RTD sensors, the thermal model can compensate for high ambient temperature and loss of ventilation. See Section 5.27. I2t used during each start is recorded in Messages ⏐ Event Records. This information can be used to determine the I2t Inhibit Level set point to ensure sufficient I2t is available to complete a start, and to minimize thermal­overload-reset time.
FLA Rating ........................... 1.00 to 5,000.00 A
Service Factor ....................... 1.00 to 1.25
Locked-Rotor Current ........... 1.50 to 10.00 x FLA
Hot Locked-Rotor Time ....... 0.10 to 100.00 s
Cold Locked-Rotor Time ...... 0.10 to 100.00 s
Cooling Factor ...................... 0.10 to 10.00
Model Type: ......................... NEMA, K-Factor
I2t Reset Type ........................ Normal, Auto,
Multiple Motor Sequence
K-Factor ................................ 1.00 to 10.00
I2t Alarm ............................... 0.50 to 1.00 pu
I2t Inhibit Level 0.10 to 0.90 pu
Page 49
Page 5-3 MPS Motor Protection System Rev. 6-F-022117
Protective Functions
I2t Start Inhibit ...................... Enable/Disable
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
Measurement Method ........... DFT or RMS
FIGURE 5.1 Class-20 Overload Curve.
Page 50
Page 5-4 MPS Motor Protection System Rev. 6-F-022117
Protective Functions
5.2.2 LOCKED-ROTOR TIMES
In all cases, values for TH and TC should be obtained from the motor manufacturer. The following information is provided to assist in selecting values for TH and TC only if manufacturer data is not available. Heater-style overload elements are available as Class 10, Class 20, or Class 30. Class 20 is recommended for general applications, Class 10 is used for motors with short locked-rotor time capability, and Class 30 is used in high-inertia applications to allow additional accelerating time where motors are within Class-30 performance requirements. These overloads can be replicated by setting TC = 10, 20, or 30 s; TH = 0.1 s; and Locked-Rotor Current = 6.00 x FLA. An induction motor built to the NEMA MG 1 standard is capable of:
• two starts in succession (coasting to rest between
starts) with the motor initially at ambient temperature (cold start)
• one start with the motor initially at a temperature not
exceeding its rated-load operating temperature (hot start).
Since the connected load has a direct influence on motor heating during a start, NEMA MG 1 defines the load torque and the load inertia (Wk2) for these starts as a function of the motor’s rated power and synchronous speed. To satisfy the cold-start requirement, a start must not use more than 50% thermal capacity. To satisfy the hot-start requirement, used thermal capacity at steady state must be less than 50%. If the thermal model in the MPS has the correct value of TC and if Used I2t increases by 50% during a start, the load is equal to the NEMA-defined load and two starts from cold will be permitted. If Used I2t increases by more than 50% during a start, the load is greater than the NEMA-defined load and two starts from cold should not be permitted — a delay is required between starts. The appropriate delay can be obtained by enabling I2t Start Inhibit and setting the I2t Inhibit Level equal to 100% minus the I2t used during a start (a slightly lower level is recommended to allow for supply and load variations). If Used I2t increases by less than 50% during a start, the load is less than the NEMA-defined load and two starts from cold will be permitted. The magnitude of TH relative to TC determines if a hot start will be permitted if I2t Start Inhibit is enabled and the I2t Inhibit Level is set as described above. If Used I2t increases by 50% or less during a start, a hot start will be permitted if TH is equal to or greater than 50% of TC. Increasing TH above 50% of TC is not recommended unless specific information is available with respect to TH.
5.2.3 EMERGENCY THERMAL RESET
OPI Menu: Messages | Emerg I2t Reset | Reset I2t Memory Emergency Thermal Reset (ETR) sets Used I2t to 0%, resets starts-per-hour variables, and disables PTC and RTD temperature trips. Program access (password) is required. Disabled-temperature protection is indicated by t° Disabled by ETR in the Status Messages display. If PTC or RTD temperature protection is not enabled, t° Disabled by ETR will not be displayed. Stator RTD or PTC trips are reset when ETR is performed regardless of measured temperatures. Temperature protection must be re-enabled in the Messages | Emerg I2t Reset | Reenable Temp menu, or by cycling supply voltage. Temperature alarms and sensor verification remain enabled during ETR.
NOTE: Temperature protection is not automatically re­enabled after an Emergency Thermal Reset.
5.3 OVERCURRENT
OPI Menu: Setup | Protection | Overcurrent Overcurrent protection is based on the largest fundamental-frequency component (DFT) of the three phase currents. An alarm-level setting is not provided. When enabled, overcurrent protection is active at all times. It is not bypassed during a start.
Trip Level ............................. 1.00 to 15.00 x CT-Primary
Rating (Ip)
Trip Delay (TD) .................... 0.00 to 10.00 s
(See Tables 5.1 and 5.2)
Protection .............................. Enable/Disable Trip1, 2, 3
Measurement Method ........... DFT
TABLE 5.1 TRIP TIME
FAULT LEVEL
(multiples of trip-
level setting)
(1)
TRIP RELAYS
(ms)
(± 10 ms)
STARTER
RELAYS (ms)
(± 15 ms)
2
5 10 18
TD + 35 TD + 30 TD + 27 TD + 26
TD + 45 TD + 40 TD + 37 TD + 36
(1)
For overcurrent faults less than 18 x Ip.
For earth faults less than 1 x Ie.
TABLE 5.2 FAULT DURATION REQUIRED FOR TRIP
FAULT LEVEL
(multiples of trip-
FAULT DURATION
(ms)
level setting)
(1)
TD ≤ 20 ms
TD > 20 ms
2
5 10 18
10
5 2 1
TD – 10 TD – 15 TD – 18 TD – 19
(1)
For overcurrent faults less than 18 x Ip.
For earth faults less than 1 x Ie.
Page 51
Page 5-5 MPS Motor Protection System Rev. 6-F-022117
Protective Functions
The asymmetrical-current multipliers for RMS and DFT measuring methods are shown in Fig. 5.2. X/R is the ratio of system reactance to system resistance. Typical X/R values are 6.6 for a low-voltage system, 15 for a medium-voltage system, and can be as high as 25 for a high-voltage system. As shown by the graph, the DFT filters the dc component so that the overcurrent setting can be set closer to the symmetrical fault value.
FIGURE 5.2 Asymmetrical-Current Multipliers.
5.4 AUXILIARY OVERCURRENT
OPI Menu: Setup | Protection | Aux Overcurrent Auxiliary overcurrent is the same as overcurrent protection. This function is intended to be used when backup protection for the overcurrent function is required.
Trip Level ............................. 1.00 to 15.00 x CT-Primary
Rating (Ip)
Trip Delay ............................. 0.00 to 10.00 s
(See Tables 5.1 and 5.2)
Protection .............................. Enable/Disable Trip1, 2, 3
Measurement Method ........... DFT
5.5 REDUCED OVERCURRENT OPI Menu: Setup | Protection | Reduced OC Reduced overcurrent is used to reduce the overcurrent set point when performing maintenance while a motor is running. This mode of operation can be used to meet
NEC 240.87 Arc Energy Reduction (B) (3) Energy­reducing maintenance switching with local status indicator.
Reduced overcurrent is controlled by a digital input assigned to Reduced OC. When the digital input is not applied, this set point is operational and when the digital input is applied, this set point is not operational. When reduced overcurrent is selected, ROC:ON is displayed in the Metering | System State menu and a relay assigned to Reduced OC will be energized. The Protection selection must include Trip1, Trip2, or Trip3. If Disable is selected, Reduced OC mode is disabled.
Trip Level ............................. 1.00 to 15.00 x CT-Primary
Rating (Ip)
Trip Delay ............................. Fixed at 0.00 (Instantaneous)
See Tables 5.1 and 5.2
Protection .............................. Enable/Disable Trip1, 2, 3
Measurement Method ........... DFT
5.6 JAM OPI Menu: Setup | Protection | Jam A trip or alarm occurs if a jam condition is detected. Jam protection is active when the motor is in the Run mode, allowing protection to be set below motor-starting current.
Trip Level ............................. 1.00 to 10.00 x FLA
Trip Delay ............................. 1.00 to 100.00 s
Alarm Level .......................... 1.00 to 10.00 x FLA
Alarm Delay ......................... 1.00 to 100.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
Measurement Method ........... DFT
5.7 EARTH FAULT
OPI Menu: Setup | Protection | Earth Fault Earth-fault protection is based on the fundamental­frequency component of zero-sequence current.
Trip Level ............................. 0.05 to 1.00 x EF-CT-
Primary Rating (Ie)
Trip Delay ............................. 0.00 to 100.00 s
(See Tables 5.1 and 5.2)
Alarm Level .......................... 0.05 to 1.00 x Ie
Alarm Delay ......................... 0.00 to 100.00 s
Protection ............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
Measurement Method ........... DFT
5.8 CURRENT UNBALANCE
OPI Menu: Setup | Protection | Unbalance (I) OPI Menu: Setup | System Config | Ip Threshold Positive-sequence current (I1) and negative-sequence current (I2) are used to determine current unbalance (I2/I1). The unbalance display range is 0.00 to 1.00 where 1.00 is 100% unbalance—a single-phase condition. Negative unbalance will be indicated if current inputs are connected B-A-C. Severe unbalance may be indicated if phase-CT polarity is incorrect. Lightly loaded systems, especially with synchronous motors, may cause false current unbalance trips. The IP Threshold sets the current level where unbalance protection becomes active. The IP Threshold is based on the maximum of the three-phase currents. For example, if the CT-primary rating (Ip) is 100 A, and Ip Threshold is set to 0.25, current unbalance protection will be active above 25 A.
Page 52
Page 5-6 MPS Motor Protection System Rev. 6-F-022117
Protective Functions
Trip Level ............................. 0.05 to 1.00
Trip Delay ............................. 1.00 to 100.00 s
Alarm Level .......................... 0.05 to 1.00
Alarm Delay ......................... 1.00 to 100.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
IP Threshold .......................... 0.10 to 0.50 x CT-primary
rating (IP)
Measurement Method ........... DFT
5.9 PHASE LOSS—CURRENT
OPI Menu: Setup | Protection | Phase Loss (I) Phase loss is a severe form of unbalance. When phase loss occurs, negative-sequence current (I2) is equal to positive-sequence current (I1) and current unbalance is 100% or 1.00 pu. The phase-loss algorithm considers I2/I1 from 0.90 to 1.00 to be a phase loss. This occurs when one phase is open resulting in two current vectors at 180°. Set the phase-loss-trip delay lower than the unbalance trip delay to avoid an unbalance trip in the event of a phase loss.
NOTE: An open CT will result in I2/I1=0.5 because the phase angle between the other two phases remain at 120°. This is not considered a phase loss.
Trip Delay ............................. 1.00 to 100.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Measurement Method ........... DFT
5.10 PHASE REVERSE—CURRENT
OPI Menu: Setup | Protection | Phase Rev (I) If the current phase sequence is B-A-C, the magnitude of negative-sequence current will be larger than the magnitude of positive-sequence current.
Trip and Alarm Delay
(1)
....... 1.00 to 100.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
Measurement Method ........... DFT
(1)
Single set point applies to Trip and Alarm.
5.11 UNDERCURRENT
OPI Menu: Setup | Protection | Undercurrent Undercurrent protection is loss-of-load protection and is active when the motor is in the Run mode. A trip or alarm is initiated if current remains below the set point for the programmed delay.
Trip Level ............................. 0.10 to 1.00 x FLA
Trip Delay ............................. 1.00 to 100.00 s
Alarm Level .......................... 0.10 to 1.00 x FLA
Alarm Delay ......................... 1.00 to 100.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
Measurement Method ........... DFT
5.12 OVERVOLTAGE
OPI Menu: Setup | Protection | Overvoltage A trip or alarm occurs if the maximum line-to-line voltage exceeds the set point.
Trip Level ............................. 1.00 to 1.40 x System
Voltage Rating (Vp)
Trip Delay ............................. 1.00 to 500.00 s
Alarm Level .......................... 1.00 to 1.40 x Vp
Alarm Delay ......................... 1.00 to 500.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
Measurement Method ........... DFT
5.13 VOLTAGE UNBALANCE
OPI Menu: Setup | Protection | Unbalance (V) Positive-sequence voltage (V1) and negative-sequence voltage (V2) are used to determine voltage unbalance (V2/V1). The unbalance display range is 0.00 to 1.00 where 1.00 is 100% unbalance—a single-phase condition. A negative unbalance will be indicated if voltage inputs are connected B-A-C.
Trip Level ............................. 0.05 to 1.00
Trip Delay ............................. 1.00 to 100.00 s
Alarm Level .......................... 0.05 to 1.00
Alarm Delay ......................... 1.00 to 100.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
Measurement Method ........... DFT
5.14 PHASE LOSS—VOLTAGE
OPI Menu: Setup | Protection | Phase Loss (V) Phase loss is a severe form of unbalance. When phase loss occurs, negative-sequence voltage (V2) is equal to positive-sequence voltage (V1) and voltage unbalance is 100% or 1.00 pu. The phase-loss algorithm considers V2/V1 from 0.90 to 1.00 to be a phase loss. Set the phase­loss trip delay lower than the unbalance trip delay to avoid an unbalance trip in the event of a phase loss.
Trip Delay ............................. 1.00 to 100.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Measurement Method ........... DFT
5.15 PHASE REVERSE—VOLTAGE
OPI Menu: Setup | Protection | Phase Rev (V) If the voltage phase sequence is B-A-C, the magnitude of the negative-sequence voltage will be larger than the magnitude of the positive-sequence voltage.
Trip and Alarm Delay
(1)
....... 1.00 to 100.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
Measurement Method ........... DFT
(1)
Single set point applies to Trip and Alarm.
Page 53
Page 5-7 MPS Motor Protection System Rev. 6-F-022117
Protective Functions
5.16 UNDERVOLTAGE
OPI Menu: Setup | Protection | Undervoltage A trip or alarm occurs if the minimum line-to-line voltage is less than the set point.
Trip Level ............................. 0.50 to 1.00 x System
Voltage Rating (Vp)
Trip Delay ............................. 1.00 to 500.00 s
Alarm Level .......................... 0.50 to 1.00 x Vp
Alarm Delay ......................... 1.00 to 500.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
Measurement Method ........... DFT
5.17 UNDERPOWER
OPI Menu: Setup | Protection | Underpower Apparent power (S) is defined by S = P + jQ. A trip or
alarm is initiated when the real power (P) magnitude remains below the set point for the programmed delay. Protection is enabled when the motor is in the Run mode. See Section 7.2. The Underpower setting is in per unit of rated power where 1.00 pu is defined as the System Voltage x FLA Rating x √3. The absolute value of power is used.
Trip Level ............................. 0.10 to 1.00
Trip Delay ............................. 0.50 to 500.00 s
Alarm Level .......................... 0.10 to 1.00
Alarm Delay ......................... 0.50 to 500.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
5.18 REVERSEPOWER
OPI Menu: Setup | Protection | Reversepower Apparent power (S) is defined by S = P + jQ. A trip or
alarm is initiated when the real reverse power (P) magnitude (negative power) is higher than the set point for the programmed delay. See Section 7.2. The Reversepower setting is in per unit of rated power where 1.00 pu is defined as the System Voltage x FLA Rating x √3. The magnitude of the negative power is used and protection is only active when negative power is detected.
Trip Level ............................. 0.10 to 1.00
Trip Delay ............................. 0.50 to 500.00 s
Alarm Level .......................... 0.10 to 1.00
Alarm Delay ......................... 0.50 to 500.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
5.19 POWER FACTOR—QUADRANT 4
OPI Menu: Setup | Protection | PF Quandrant4 OPI Menu: Setup | System Config | Ip Threshold A trip or alarm occurs if the absolute value of power factor in quadrant 4 is less than the set point. In quadrant 4, both Watts and Vars are positive (Importing). Power-factor protection is active when the motor is in the Run mode. Run mode is defined in Section 5.1. The Ip Threshold sets the point where power-factor protection becomes active.
Trip Level ............................. 0.50 to 1.00
Trip Delay ............................. 0.20 to 500.00 s
Alarm Level .......................... 0.50 to 1.00
Alarm Delay ......................... 0.20 to 500.00 s
IP Threshold .......................... 0.10 to 0.50 x CT-primary
rating (IP)
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
5.20 POWER FACTOR—QUADRANT 3
OPI Menu: Setup | Protection | PF Quandrant3 OPI Menu: Setup | System Config | Ip Threshold A trip or alarm occurs if the absolute value of power factor in quadrant 3 is less than the set point. In quadrant 3, Watts are negative (Exporting) and Vars are positive (Importing). Power-factor protection is active when the motor is in the Run mode. Run mode is defined in Section 5.1. The Ip Threshold sets the point where power-factor protection becomes active.
Trip Level ............................. 0.50 to 1.00
Trip Delay ............................. 0.20 to 500.00 s
Alarm Level .......................... 0.50 to 1.00
Alarm Delay ......................... 0.20 to 500.00 s
IP Threshold .......................... 0.10 to 0.50 x CT-primary
rating (IP)
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
5.21 UNDERFREQUENCY
OPI Menu: Setup | Protection | Underfrequency A trip or alarm occurs when the frequency of the input voltage (VA) is below the set point. Underfrequency protection is inhibited when the input voltage is less than 50% of rated input (Vp).
Trip Level ............................. 30.00 to 80.00 Hz
Trip Delay ............................. 0.50 to 500.00 s
Alarm Level .......................... 30.00 to 80.00 Hz
Alarm Delay ......................... 0.5 to 500.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
Page 54
Page 5-8 MPS Motor Protection System Rev. 6-F-022117
Protective Functions
5.22 OVERFREQUENCY
OPI Menu: Setup | Protection | Overfrequency A trip or alarm occurs when the frequency of the input voltage (VA) is above the set point. Overfrequency protection is inhibited when the input voltage is less than 50% of rated input (Vp).
Trip Level ............................. 30.00 to 80.00 Hz
Trip Delay ............................. 0.50 to 500.00 s
Alarm Level .......................... 30.00 to 80.00 Hz
Alarm Delay ......................... 0.50 to 500.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
5.23 STARTS PER HOUR / TIME BETWEEN STARTS
OPI Menu: Setup | Protection | Starts Per Hour Starts-Per-Hour and Time-Between-Starts are useful limits in a protective relay that incorrectly responds to current below FLA. If the relay’s thermal model accurately tracks a motor’s used thermal capacity under all conditions, Starts-Per-Hour and Time-Between-Starts are features that provide no additional protection. The MPS does not require these features to provide protection, but they are included to satisfy protection strategies designed for protective relays without dynamic thermal modeling. The Starts-Per-Hour feature ensures that the programmed number of starts per hour is not exceeded and the Time-Between-Starts feature ensures that the programmed time has elapsed between starts. The available number of starts and time between starts is also a function of the thermal model’s Used I2t value. Consequently, the allowed number of starts may be less than the starts-per-hour value and the time between starts may be longer than the set-point value. The number of starts and time between starts is checked when the motor is stopped. A Starts/Hour Trip or Starts/Hour Alarm is issued if a start will exceed the # Starts Per Hour setting or if the time since the previous start is less than the Time Between setting. When a Starts/Hour Trip or Starts/Hour Alarm is issued, the output relay assigned to Start Inhibit is energized. The Start Inhibit relay is non-latching and can be used as a start permissive. A Starts/Hour Trip will remain latched until a reset is issued. The Start Inhibit relay is shared with the thermal model’s I2t Inhibit feature. If motor current is detected regardless of the alarm or trip condition, the Starts/Hour Alarm is removed, and Starts/Hour Trip can be reset. The starts-per-hour algorithm remains active but any trips or alarms are suppressed until the motor is stopped. The status of Starts-Per-Hour and Time-Between-Starts is displayed in the Metering | Thermal Capacity menu. If there are no trips or alarms, the number of available starts (Sph Available) is displayed and if a trip or alarm is present, the inhibit time (Sph Inhibit) is displayed. Since
the Metering | Thermal Capacity menu is also used to display the thermal model status, messages are prioritized as follows:
• I2t Reset Time
(1)
• I2t Trip Time
(1)
• I2t Inhibit Time
(1)
• Starts Per Hour Inhibit Time
(3)
• Starts Available
(2) (3)
An Emergency Thermal Reset (ETR) can be used to initialize all thermal and starts-per-hour variables and to reset a starts-per-hour trip. See Section 5.2.3.
Time Between Starts ......... 0.00 to 500.00 Minutes
Starts Per Hour
(2)
............... 1 to 10
Protection .......................... Enable/Disable Trip 1, 2, 3
Enable/Disable Alarm 1, 2, 3
(1)
Calculated from thermal model data.
(2)
The display range for the number of available starts is
-9 to +10.
(3)
Initialized when supply voltage is cycled.
5.24 FAILURE TO ACCELERATE AND UNDERSPEED
OPI Menu: Setup | Protection | Underspeed OPI Menu: Setup | 4-20 Analog In | Input Function OPI Menu: Setup | Digital Inputs | Tachometer Failure-to-accelerate and underspeed protection are available if the MPS has a tachometer signal. The tachometer signal can originate from the High Speed Input (HSI) or the analog input. If the analog input is set to Motor Speed, it is used as the input to the algorithm, otherwise the digital tachometer (HSI) is used. The failure-to-accelerate algorithm is activated whenever a start is detected. Start detection is based on motor current. Set points 1 to 3 (for both speed and time) are sequentially checked to confirm acceleration. Motor at Full Speed (refer to Type T28, Bit 2 in Appendix F) will be set when the measured tachometer speed exceeds the Speed 3 threshold setting and the Underspeed protection feature is enabled. If the Speed 3 threshold is not reached within Time 3, the MPS will trip on failure-to-accelerate. While running, the tachometer signal is continuously measured and a trip occurs if the speed falls below the Speed 3 setting. Time 1 must be set less than or equal to Time 2 and Time 2 must be set less than or equal to Time 3. To enable display of the speed in the Metering | System
State menu, select Enable in the Setup ⏐ Digital Input ⏐ Tachometer ⏐ Enable/Disable menu, when the HSI input
is used.
Speed 1 ................................. 1.00 to 100% Sync Speed
Time 1 ................................... 1.00 to 1000.00 s
Speed 2 ................................. 1.00 to 100% Sync Speed
Time 2 ................................... 1.00 to 1000.00 s
Speed 3 ................................. 1.00 to 100% Sync Speed
Time 3 ................................... 1.00 to 1000.00 s
Protection .............................. Enable/Disable Trip1, 2, 3
Page 55
Page 5-9 MPS Motor Protection System Rev. 6-F-022117
Protective Functions
5.25 DIFFERENTIAL CURRENT PROTECTION
OPI Menu: Setup | Protection | Differential OPI Menu: Setup | Hardware | DIF Module OPI Menu: Setup | System Ratings | DF-CT Primary The MPS-DIF provides three-phase differential protection. It is intended to be used specifically for motor protection and not intended for feeder or transformer differential protection. Enable the module and communications-loss protection using the Setup ⏐ Hardware ⏐ DIF Module menu. The module uses I/O module communications and both trip and alarm actions are available in the event of communications loss. Set DF-CT Primary equal to the differential-CT-primary rating. For the MPS summation connection, PH-CT Primary and DF-CT Primary must be equal. Trip and alarm settings are based on multiples of the DF-CT Primary rating (Id).
Trip Level ............................. 0.10 to 15.00 x I
d
Trip Delay ............................. 0.00 to 10.00 s
Alarm Level .......................... 0.10 to 15.00 x Id
Alarm Delay ......................... 0.00 to 10.00 s
Protection .............................. Enable/Disable Trip1,2,3
Enable/Disable Alarm1,2,3
Measurement Method ........... DFT c/w CT saturation
compensation.
5.26 PTC TEMPERATURE
OPI Menu: Setup | Protection | PTC Temperature A positive-temperature-coefficient (PTC) thermistor input is provided on the MPS-CTU. The total resistance of series-connected PTC thermistors must be less than 1,500 Ω at 20°C (68°F). A trip or alarm will occur when
series resistance exceeds 2,900 Ω. NOTE: During Emergency Thermal Reset, a PTC trip is
reset and PTC-temperature protection is disabled. See Section 5.2.3.
Protection .............................. Enable/Disable Trip1, 2, 3
Enable/Disable Alarm1, 2, 3
5.27 RTD TEMPERATURE
OPI Menu: Setup | Protection | RTD Temperature OPI Menu: Setup | Hardware | RTD Module Up to three RTD modules can be connected to the
MPS-CTU. Select the number of modules in the Setup | Hardware | RTD Modules menu. Each module can
monitor eight RTD’s for a total of twenty-four RTD’s. RTD type, function, and trip and alarm set points are programmable for each RTD. When an RTD type is selected, trip and alarm functions are determined by Temperature Trip and Alarm settings. During Emergency Thermal Reset, an RTD trip is reset and RTD-temperature protection is disabled. See Section 5.2.3. RTD failure detection is provided. The actions for an RTD failure are selectable as Trip1, 2, or 3 and as Alarm1, 2, or 3. The selections apply to all RTD's.
The MPS supports three MPS-RTD modules with each module supporting eight RTDs. Each RTD can be assigned to one of eight function groups; Stator, Bearing,
Load, Ambient, Stator Voting, Bearing Voting, Load Voting, and Ambient Voting. The specific assignment is set using the Setup | Protection | RTD Temperature | Module x | Function menu. Regardless of the assigned
function, individual RTD trip and alarm setpoints remain active. When an RTD is assigned to a voting group, it participates in the voting logic. Within a voting group, two RTDs must indicate a temperature above their trip setpoint in order to cause a trip. The first two RTDs that indicate a high temperature will generate a trip. Subsequent trips resulting from other RTDs in the group are not locked out. Trips must be individually reset and all trips must be reset to allow a start. Failed sensors do not participate in the RTD voting logic. For example if six sensors are set to Stator Voting and two sensors fail, only four participate in RTD voting. When RTD voting is used, it is assumed that continuity of service is of high importance. In this case it is recommended to set the sensor-failure action to alarm only or to set the trip action to a value different than the Temperature Trip Action. If only one RTD is assigned to a group, or if only one RTD is active because of sensor failures, RTD protection is the same as the corresponding non-voting function. RTD voting is not available for alarm setpoints. RTD voting is contained within the specific function group and within the RTD module. An RTD in one module does not participate in the voting logic of another module.
Name ..................................... 18 Character, Alphanumeric
Type ...................................... Disable, Pt100, Ni100,
Ni120, Cu10
Function ................................ Stator, Bearing, Load,
Ambient,Stator Voting, Bearing Voting, Load Voting, Ambient Voting
Trip Range ............................ 40.00 to 200.00°C (104°F to
392°F)
Alarm Range ......................... 40.00 to 200.00°C (104°F to
392°F)
Display Range ...................... -40.00 to 200.00°C (-40°F to
392°F)
Error Codes ........................... -100 = No Sensor
-90 = Open Sensor
-80 = Shorted Sensor
-70 = No Data/Module Error (Codes accessed via network
communications)
Page 56
Page 5-10 MPS Motor Protection System Rev. 6-F-022117
Protective Functions
5.28 HOT-MOTOR COMPENSATION
OPI Menu: Setup | Protection | RTD Temperature
If hot-motor compensation (HMC) is enabled, the maximum stator-RTD temperature is used to bias the thermal model by increasing Used I2t when the RTD temperature is greater than the thermal-model temperature.
Two set points are used to define the compensation. See Fig. 5.3. HMC Minimum Bias is the stator temperature where compensation begins at 0% I2t. HMC Maximum Bias is the stator temperature where compensation ends at 100% I2t. Although the bias calculation is based on 0% and 100% I2t values, the Used I2t adjustment is limited to 90% I2t. An actual overload condition is required to cause a trip at 100% I2t.
FIGURE 5.3 Used I2t Bias Curve.
HMC Minimum Bias ............ 40.00 to 200.00°C (104°F to
392°F)
HMC Maximum Bias ........... 40.00 to 200.00°C (104°F to
392°F)
Protection .............................. Enable/Disable
NOTE: Hot-motor compensation will not be active unless the HMC High set point is at least 10°C above the HMC Low set point.
5.29 ANALOG INPUT
OPI Menu: Setup | Analog Input | 4–20 Input Type The analog input function is selectable as Metering Only, Protection, Sync to ASD, or Motor Speed.
5.29.1 PROTECTION
OPI Menu: Setup | 4-20 Analog In | Protection The protection input has high-level and low-level trip and alarm set points. A high-level trip or alarm occurs when the 4-20-mA input exceeds the high-level trip or alarm set point, and a low-level trip or alarm occurs when the 4-20-mA input is lower than the low-level trip or alarm set point. Trip action is fixed at Trip1 and alarm action is fixed at Alarm1.
High Level Trip .................... 0.10 to 20.00 mA
Low Level Trip ..................... 0.10 to 20.00 mA
Trip Delay ............................. 0.01 to 100.00 s
High Level Alarm ................. 0.10 to 20.00 mA
Low Level Alarm ................. 0.10 to 20.00 mA
Alarm Delay ......................... 0.01 to 100.00 s
5.29.2 SYNCHRONIZE TO ASD
OPI Menu: Setup | 4-20 Analog In | Sync to ASD When Sync to ASD is selected, the MPS uses the 4-20-mA input to set the internal sampling rate for current and voltage inputs so that protection and metering functions use accurate RMS and DFT values from 10.00 to 70.00 Hz.
4-mA Frequency (lower) ...... 0.00 to 70.00 Hz
20-mA Frequency (upper) .... 0.00 to 70.00 Hz
Frequency Range .................. 10.00 to 70.00 Hz
5.29.3 MOTOR SPEED
OPI Menu: Setup | 4-20 Analog In | Motor Speed When the analog-input type is selected as Motor Speed, the 4-20-mA analog input is used as the speed input. This selection overrides the selections for the high-speed tachometer input and failure-to-accelerate protection uses the analog input as the source of speed information.
4-mA Speed .......................... 0.00 to 100% Sync Speed
20-mA Speed ........................ 0.00 to 100% Sync Speed
5.29.4 METERING ONLY
When the analog-input type is selected as Metering Only, an analog input does not affect MPS operation, but
its value can be observed in the Metering menu and with a communications network.
Page 57
Page 6-1 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
6. STARTER FUNCTIONS
OPI Menu: Setup | Starter
6.1 GENERAL
All common starter types are supported. From the OPI Starter Type menu, select one of seventeen starter types or select Protection Only. Starter types requiring two FLA settings are indicated by the “x” symbol in the OPI display. When Protection Only is selected, all starter functions except STOP are disabled and all OPI control-select LED’s will be off. Any STOP signal will initiate a Trip1 when the MPS is in Protection Only.
NOTE: When Protection Only is selected, STOP will not function if Trip1 is not assigned to a relay output.
When Protection Only is selected, the OPI STOP and RUN LED’s are controlled by motor current. When motor current is below the minimum Current Threshold defined in Section 3.2.1.2, the STOP LED is on and RUN LED is off. When motor current is above the minimum Current Threshold, the STOP LED is off and RUN LED is on. When a starter type is selected, the STOP and RUN LED’s are under starter control and not based on motor current. When a starter type is selected, starter control can be performed with the digital inputs, OPI, or network communications. See Section 4.3.3 for details on selecting start sources. Three control modes are available and selected using the OPI CONTROL SELECT key. In addition, a digital input can be used to select LOCAL. Each control mode has specific start sources that can be programmed as shown in Table 6.1. REMOTE control can be configured to operate with start sources from the digital input, OPI and the network. OPI Control uses the OPI start keys as the start sources. LOCAL control uses the Local Start1 or Local Start2 start sources or the OPI. In LOCAL mode, OPI control can be enabled or disabled. Control selection is indicated by the REMOTE, OPI, and LOCAL LED’s on the OPI. The digital inputs allow concurrent operation of three start-control methods; 3-wire start/stop, 2-wire start/stop, and 3-wire local start/stop. Three-wire control requires two digital inputs, one programmed for Start1 or Start2 (N.O. momentary start switch) and one programmed for Stop (N.C. momentary stop switch) as shown in Fig. 6.1. Two-wire control uses one input, programmed as 2-Wire Start1 or 2-Wire Start2, for start/stop control and can be used where a single contact provides start/stop operation. See Fig. 6.2. If a start was activated by a 2-wire start input, any other STOP will initiate a latching Trip1. In all other cases, STOP does not cause a trip.
Digital inputs programmed for Limit1 Stop and Limit2
Stop are used to provide stop control for Start1 and Start2. This is typically used in reversing starter
applications. The forward-direction limit switch is connected to the Limit1 Stop input and the reverse­direction limit switch is connected to the Limit2 Stop input. With this control method, a Start1 requires limit switch 1 to be closed and limit switch 2 is ignored. In a similar manner, Start2 requires, limit switch 2 to be closed while limit switch 1 is ignored.
NOTE: When starter functions are used, protective functions with the trip action set to Trip1 will cause the starter to stop when a trip occurs. Reset is required.
Table 6.1 indicates the available start sources.
TABLE 6.1 START-SOURCE SUMMARY
(1)
CONTROL
(7)
SELECTION
START SOURCE
REMOTE
(2)
DIGITAL
INPUTS
(3)
Start1 Input (3-wire control) Start2 Input (3-wire control)
2-W Start1 (2-wire control)
(4)
2-W Start2 (2-wire control)
(4)
OPI
(3)
START1 Key START2 Key
NETWORK
(3)
Start1 Command Start2 Command
OPI
OPI START1 Key OPI START2 Key
LOCAL
(5) (6)
DIGITAL
INPUTS
Local Start1 (3-wire) Local Start2 (3-wire)
OPI
(8)
START1 Key START2 Key
(1)
All STOP sources are always enabled.
(2)
Factory default has all sources enabled and REMOTE
selected.
(3)
Can be enabled or disabled using the Setup | Starters |
Remote Group menu.
(4)
STOP causes a latching trip.
(5)
LOCAL can also be selected by a network command
or by a digital input programmed for Local Select. Each Local Select source must de-select local control for the MPS to return to the previous control setting.
(6)
I2t Start Inhibit, Starts per Hour alarms and Interlocks
are bypassed.
(7)
At least one Control Selection must be enabled even
when Protection Only is selected.
(8)
Can be enabled or disabled using the Setup | Starters
| Local Group menu.
Up to four timers (Stage 1 to 3 Delay, and Start Time) control the start sequence. These timers control Starter RLYA, Starter RLYB, Starter RLYC, and Starter RLYD as shown in the timing diagrams in Section 6.2. These functions can be assigned to any output relay. Digital
Page 58
Page 6-2 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
inputs can be programmed to monitor contactor status. Contactor status corresponding to Starter RLYA, Starter RLYB, Starter RLYC, and Starter RLYD outputs are designated as RLYA Status, RLYB Status, RLYC Status, and RLYD Status. The MPS will issue a Trip1 and indicate Relay Status Trip if the status contact does not follow within 500 ms of the command to operate the respective relay output. In addition, a transition must not occur prior to its intended time. When the starting sequence is complete, contactor status is checked every 500 ms and a Relay Status Trip will occur if the status changes.
NOTE: Relay Status is not checked when the starter is in the stopped state.
The Start Time set point is the maximum start time allowed. The starting process will terminate and generate a Trip1 unless current is between 1.5 x (CT-Primary Rating / FLA) and 125% FLA when the Start Time timer times out. In reduced-voltage-starting applications, the MPS can use time-based or current-based transfer from the starting to the running connection. The transfer type is selected as
Time Transfer or Current Transfer using the Transfer Type menu.
When Current Transfer is selected, the start-connection delay (Stage 1 Delay or Stage 2 Delay, see Table 6.2 and Figs 6.5, 6.6, 6.7, and 6.8) defines the minimum starting­connection time. The transfer to the run connection occurs when the start-connection delay has expired and current is below the Transfer Current. When current is above the Transfer Current, the transfer will be delayed up to the maximum time defined by the Start Time. If current is below 1.5 x (CT-Primary Rating / FLA) when the start-connection delay expires or if the Start Time is exceeded, the MPS will issue a Trip1 and indicate Starter Trip. When Time Transfer is selected, the start-connection delay set point (Stage 1 Delay or Stage 2 Delay) is used to determine the transfer time. Transfer to the run connection occurs after the start-connection delay has expired. In both current- and time-transfer modes, the MPS will issue a Trip1 and indicate Starter Trip if load current is above 125% FLA or below 1.5 x (CT-Primary Rating / FLA) when the Start Time expires. The Start Time set point must be long enough to allow the starting sequence to complete and for the motor current to drop below 125% FLA. Table 6.2 summarizes starter types and shows which starter set points are active. The backspin timer is available when a delay is required between starts. The backspin timer is enabled in the BkSpin En/Disable menu, and the delay time is set in the Backspin Delay menu. The backspin timer is
activated by a STOP or when supply voltage is cycled on the MPS. While the backspin timer is on, the Backspin Timer On message is displayed in the Status Message menu and starts are not allowed. The connection diagrams, Figs. 6.9 to 6.23, show typical control circuits with 120-Vac contactor coils and the 24-Vdc source on the MPS-CTU used for status contacts. Other supply voltages can be used within the limits of the digital-input and relay-contact ratings. The use of status contacts is optional.
NOTE: Stop and start control, electrical interlocks, and mechanical interlocks are not shown in connection diagrams.
NOTE: Connection diagrams show typical output relay assignments that must be set using the Setup ⏐ Relay Outputs ⏐ Relay x ⏐ Relay x Function menu.
NOTE: To cancel a long backspin time, enter new backspin parameters and restart the MPS using the Setup | System Config | Maintenance | Restart MPS-CTU menu or cycle supply voltage.
Page 59
Page 6-3 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
TABLE 6.2 STARTER SUMMARY
STARTER TYPE
SEQ.
NO.
TIMERS USED
(1)
START-
CONNECTION
TIMER
NUMBER
(1)
ACTIVE FLA SETPOINTS
(2)
RELAYS AND CONTACTOR STATUS
(3)
FLA
FLA 2
RLYA
RLYB
RLYC
RLYD
Full-Voltage Non-Reversing
1 4 x x
Adjustable-Speed Drive
1 4 x x
Soft-Start
1 4 x x
Full-Voltage Reversing
2 4 x x x
Two-Speed Two-Winding
2 4 x x x x
Reactor or Resistor Closed­Transition
(4)
3
1,4 1 x x x
Slip-Ring
(4)
3
1,4 1 x x x Part-Winding
(4)
3
1,4 1 x x x x
Double-Delta
(4)
3
1,4 1 x x x x
Soft-Start-with-Bypass
(4)
3
1,4 1 x x x
Reactor or Resistor Open­Transition
(4)
4
1,4 1 x x x
Two-Winding
(4)
4
1,4 1 x x x x Wye-Delta Open-Transition
(4)
5
1,2,3,4
2
x x x x x
Autotransformer Closed­Transition
(4)
5
1,2,3,4
2 x x x x
Wye-Delta Closed-Transition
(4)
6
1,2,4 2 x x x x x
x
(1)
TIMERS 1: Stage 1 Delay 2: Stage 2 Delay 3: Stage 3 Delay 4: Start Time
(4)
Current transfer capability when enabled
(2)
FLA SETPOINTS
FLA: Full-Load Current FLA2: Full-Load Current 2
(3)
RELAYS AND CONTACTOR STATUS
Starter RLYA, Starter RLYB, Starter RLYC, and
Starter RLYD are not automatically assigned. The
user must assign these functions to individual relays.
Status is assignable to any digital input.
FIGURE 6.1 Typical 3-Wire Control.
Page 60
Page 6-4 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
FIGURE 6.2 Typical 2-Wire Control.
6.2 STARTER TIMING SEQUENCES
The MPS uses one of six timing sequences to implement the various starter types. These time-based starter sequences are shown in Figs. 6.3 to 6.8.
FIGURE 6.3 Starter Sequence 1.
FIGURE 6.4 Starter Sequence 2.
Page 61
Page 6-5 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
FIGURE 6.5 Starter Sequence 3.
FIGURE 6.6 Starter Sequence 4.
Page 62
Page 6-6 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
FIGURE 6.7 Starter Sequence 5.
FIGURE 6.8 Starter Sequence 6.
Page 63
Page 6-7 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
6.3 FULL-VOLTAGE NON-REVERSING STARTER
Sequence: Fig. 6.3 Connection: Fig. 6.9 Current Transfer: Not available
START1 or START2 is the start command and Starter RLYA is used as the output to control the contactor.
FIGURE 6.9 Full-Voltage Non-Reversing-Starter Connection.
6.4 ADJUSTABLE-SPEED DRIVE
Sequence: Fig. 6.3 Connection: Fig. 6.10 Current Transfer: Not available
The MPS-CTU provides the start input to an adjustable-speed drive (ASD). START1 or START2 is the start command and Starter RLYA is used as the output to control the ASD. The MPS-CTU has a 4-20 mA input that should be used to synchronize its sampling rate to the ASD output frequency so that all protection and metering values are valid for an ASD output frequency from 10 to 70 Hz. In ASD applications, voltage and current inputs must be derived from the load side of the ASD, and undervoltage protection must be disabled.
FIGURE 6.10 Adjustable-Speed-Drive Connection.
6.5 SOFT-START STARTER
Sequence: Fig. 6.3 Connection: Fig. 6.11 Current Transfer: Not available
The MPS-CTU provides the start input to a solid-state starter. START1 or START2 is the start command and Starter RLYA is used as the output to control the starter.
FIGURE 6.11 Soft-Start-Starter Connection.
Page 64
Page 6-8 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
6.6 FULL-VOLTAGE REVERSING STARTER
Sequence: Fig. 6.4 Connection: Fig. 6.12 Current Transfer: Not available
The full-voltage reversing starter uses START1 to activate Starter RLYA for forward control and START2 to activate Starter RLYB for reverse control. RLYA Status is the status corresponding to Starter RLYA and RLYB Status is the status corresponding to Starter RLYB. For OPI and 3-wire start/stop control, a direction change requires a STOP command prior to a START1 or START2 command. For 2-wire control a STOP command is not required. Fig. 6.12 shows the use of forward and reverse limit switches. When Start1 is issued, K1 is energized. If a STOP is issued or LSF opens, K1 is de-energized. Provided LSR is closed, Start2 will energize K2 to allow operation in the reverse direction.
NOTE: Phase CT’s should be located upstream of the contactors.
FIGURE 6.12 Full-Voltage-Reversing-Starter Connection.
6.7 TWO-SPEED STARTER
Sequence: Fig. 6.4 Connection: Fig. 6.13, 6.14, and 6.15 Current Transfer: Not available
The two-speed starter uses START1 to activate Starter
RLYA for high-speed control and START2 to activate Starter RLYB for low-speed control. RLYA Status is the
status corresponding to Starter RLYA and RLYB Status is the status corresponding to Starter RLYB. A speed change requires a STOP command prior to a START1 or START2 command. This starter can be used on motors with two separate windings (Fig. 6.13) or on motors with reconnectable windings (Figs. 6.14 and 6.15). This starter requires two FLA settings. Use FLA Rating for the high-speed connection and FLA Rating 2 for the low-speed connection.
FIGURE 6.13 Two-Speed Two-Winding-Starter Connection.
Page 65
Page 6-9 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
FIGURE 6.14 Two-Speed Constant- and Variable-Torque-Starter Connections.
FIGURE 6.15 Two-Speed Constant-Horsepower-Starter Connection.
Page 66
Page 6-10 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
6.8 REACTOR OR RESISTOR CLOSED-TRANSITION
STARTER
Sequence: Fig. 6.5 Connection: Fig. 6.16 Current Transfer: Available
This starter uses a reactor or resistor to provide reduced-voltage starting and the reactor or resistor contactor (K1) remains closed during running. START1 or START2 initiates the starting sequence by activating Starter RLYA. Starter RLYB activates after the Stage1 Delay.
FIGURE 6.16 Reactor or Resistor-Starter Connection.
6.9 SLIP-RING STARTER
Sequence: Fig. 6.5 Connection: Fig. 6.17 Current Transfer: Available
The slip-ring starter is a single-stage wound-rotor starter with a single contactor (K2) controlling the rotor resistor bank. START1 or START2 initiates the starting sequence by activating Starter RLYA. Starter RLYB activates after the Stage1 Delay.
FIGURE 6.17 Slip-Ring-Starter Connection.
Page 67
Page 6-11 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
6.10 PART-WINDING AND DOUBLE-DELTA STARTERS
Sequence: Fig. 6.5 Connection: Fig. 6.18 Current Transfer: Available
The part-winding starter is used on motors with two stator windings and the double-delta starter has a delta winding that is parallel connected during running.
START1 or START2 initiates the starting sequence by activating Starter RLYA. Starter RLYB activates after the Stage1 Delay. Both starters require two FLA settings. FLA Rating 2 is the full-load current for the starting connection and FLA Rating is the full-load current for the running connection.
FIGURE 6.18 Part-Winding and Double-Delta-Starter Connections.
Page 68
Page 6-12 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
6.11 SOFT-START-WITH-BYPASS STARTER
Sequence: Fig. 6.5 Connection: Fig. 6.19 Current Transfer: Available
START1 or START2 initiates the starting sequence by activating Starter RLYA. Starter RLYB activates after the Stage1 Delay to close the bypass contactor. Although RLYA Status can be selected as a digital input, it is not usually available for this starter.
For a soft-start where the bypass function is included, a bypass signal from the soft-start can be used as an input to the MPS. There are two solutions:
1) This option coordinates the MPS Starter RLYB signal with the soft-start and ensures the status input does not validate prior to the intended time. Assign an MPS output relay with the Starter RLYB function as per Fig. 6.19. Connect this output-relay contact in series with the bypass contact from the soft-start (K1a) and connect this signal to a digital input programmed as RLYB Status. Set the Stage 1 Delay longer than the soft-start bypass time.
2) This option uses a digital input programmed as Trip1 in conjunction with the MPS trip-bypass feature. Connect the bypass signal from the soft­start to a digital input assigned as Trip1. Enable Trip Bypass and set the Bypass Delay longer than the start time of the soft-start. Note that this feature is based on current and during a stop requires the input to remain valid until current is not detected. If the soft-start has a ramp-down feature, set the INx Trip Delay greater than the ramp-down time to prevent a trip when the soft­start stops. See Section 4.2.8.
6.12 REACTOR OR RESISTOR OPEN-TRANSITION STARTER
Sequence: Fig. 6.6 Connection: Fig. 6.16 Current Transfer: Available
START1 or START2 activates Starter RLYA for the duration of the Stage1 Delay. After Starter RLYA de­activates for the Stage2 Delay, Starter RLYB activates.
6.13 TWO-WINDING STARTER
Sequence: Fig. 6.6 Connection: Fig. 6.20 Current Transfer: Available
This starter is an open-transition starter for two­winding motors that run with only one winding energized.
START1 or START2 activates Starter RLYA for the time specified by the Stage1 Delay. After Starter RLYA de-activates for the Stage2 Delay, Starter RLYB activates. This starter requires two full-load current set points. FLA Rating 2 is the full-load current for the starting connection (Starter RLYA) and FLA Rating is the full-load current for the running connection (Starter RLYB).
6.14 WYE-DELTA OPEN-TRANSITION STARTER
Sequence: Fig. 6.7 Connection: Fig. 6.21 Current Transfer: Available
START1 or START2 initiates the sequence. Starter
RLYC activates to close the neutral contactor (K3). Starter RLYB activates the wye contactor (K2) after the Stage1 Delay. Starter RLYC de-activates to open the
neutral contactor after the Stage2 Delay and Starter RLYA activates to close the delta contactor (K1) after the Stage3 Delay. Stage-1 and Stage-3 delays are contactor-transfer times and should be set in the range of 0.1 to 0.5 seconds. Locate CT’s on the line side of the starter. This starter uses two full-load current settings. Set FLA Rating to the delta full-load current and FLA Rating 2 to the wye full-load current.
FIGURE 6.19 Soft-Start-With-Bypass-Starter Connection.
Page 69
Page 6-13 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
FIGURE 6.20 Two-Winding-Starter Connection.
6.15 AUTOTRANSFORMER CLOSED-TRANSITION STARTER
Sequence: Fig. 6.7 Connection: Fig. 6.22 Current Transfer: Available
START1 or START2 initiates the sequence. Starter RLYC activates to close the neutral contactor (K3) on the autotransformer. Starter RLYB activates to close the main autotransformer contactor (K2) after the Stage1 Delay. Starter RLYC de-activates to open the autotransformer neutral contactor after the Stage2 Delay, and Starter RLYA activates to close the main motor contactor (K1) after the Stage3 Delay. Stage-1 and Stage-3 delays are contactor-transfer times and should be set in the range of
0.1 to 0.5 seconds.
6.16 WYE-DELTA CLOSED-TRANSITION STARTER
Sequence: Fig. 6.8 Connection: Fig. 6.23 Current Transfer: Available
START1 or START2 initiates the start sequence.
Starter RLYC activates to close the neutral contactor (K3). Starter RLYB activates to close the wye contactor (K2)
after the Stage1 Delay. Starter RLYD activates to close the resistor contactor (K4) after the Stage2 Delay. This is followed by de-activation of Starter RLYC, activation of Starter RLYA to close the main motor contactor (K1), and de-activation of Starter RLYD, all displaced by the Stage1 Delay. Locate CT’s on the line side of the starter. Set FLA Rating to the delta full-load current and FLA Rating 2 to the wye full-load current. Stage-1 delay is a contactor­transfer time and should be set in the range of 0.1 to 0.5 seconds.
Page 70
Page 6-14 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
FIGURE 6.21 Wye-Delta Open-Transition-Starter Connection.
FIGURE 6.22 Autotransformer Closed-Transition-Starter Connection.
Page 71
Page 6-15 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
FIGURE 6.23 Wye-Delta Closed-Transition-Starter Connection.
Page 72
Page 6-16 MPS Motor Protection System Rev. 6-F-022117
Starter Functions
This page intentionally left blank.
Page 73
Page 7-1 MPS Motor Protection System Rev. 6-F-022117
Theory of Operation
7. THEORY OF OPERATION
7.1 SIGNAL-PROCESSING ALGORITHMS
The sampling frequency of the MPS is variable. It can be set for 50-Hz, 60-Hz, or variable-frequency applications. The MPS obtains sixteen samples per cycle of each current and voltage signal. For an adjustable­speed drive (ASD) application, a speed or frequency output from the ASD can be connected to the 4-20-mA input to synchronize the sampling rate to the ASD output frequency. This maintains accurate measurements of power and sequential components. The sampling rate is sixteen samples per cycle of the fundamental frequency. A Discrete-Fourier-Transform (DFT) algorithm is used to obtain the magnitude and phase angles of the fundamental-frequency components of the current and voltage waveforms. These values provide true positive- and negative-sequence components. True RMS values of line currents are calculated for use by the thermal-model algorithm. RMS values include up to the 8th harmonic. All calculated values are updated at the sampling frequency to achieve a fast response to fault conditions. RMS values of the fundamental components of current and voltage are displayed. The MPS uses the input voltage VA for frequency measurement. The input voltage must be above 30 Vac and a sixteen-cycle interval is used to determine frequency. Frequency protection is inhibited when system voltage is less than 50% of the System Voltage setting.
7.2 POWER ALGORITHM
Apparent power (S) is calculated by:
jQPS +=
Real power (P) is determined from the in-phase components of I and V, and reactive power (Q) is determined from the quadrature components of I with respect to V. Power factor is the magnitude of the ratio of P to S. The one-PT connection assumes balanced voltages for power calculations. Power calculations for the other connections are valid for both balanced and unbalanced conditions. In all cases, power calculations use the two­wattmeter method and assume 3-wire loads. The IEEE convention is used for power displays: +Watts, +Vars, -PF (Lag) Importing Watts,
Importing Vars
+Watts, -Vars, +PF (Lead) Importing Watts,
Exporting Vars
-Watts, -Vars, -PF (Lag) Exporting Watts, Exporting Vars
-Watts, +Vars, +PF (Lead) Exporting Watts, Importing Vars
7.3 OPERATOR INTERFACE (MPS-OPI)
The OPI is a terminal device used to communicate with the MPS-CTU. All set points, operating parameters, and menus are stored in the MPS-CTU. The OPI contains a microprocessor used to communicate with the MPS-CTU, read key presses, and perform display functions. On multiple-OPI systems, all OPI’s display the same information. Key presses on any OPI will be processed by the MPS-CTU.
7.4 RTD MODULE (MPS-RTD)
The RTD module contains a microprocessor, A/D converter, and analog multiplexers used to measure up to eight RTD’s. The RTD-measuring circuit is isolated from the I/O Module network. All eight RTD’s are scanned every three seconds. RTD linearization, open/short detection, and lead compensation are performed by the RTD module. RTD temperature is sent to the MPS-CTU where temperature monitoring occurs.
7.5 DIFFERENTIAL MODULE (MPS-DIF)
The differential module obtains 32 samples per cycle of the differential current. A Discrete-Fourier-Transform (DFT) algorithm is used to obtain the magnitude of the three differential currents. Frequency of operation is set by the MPS-CTU unit and allows differential protection to be used in variable-frequency drive applications. The DFT values are sent to the MPS-CTU where differential protection is performed.
7.6 FIRMWARE DIAGNOSTICS
Starting with firmware 2.01, diagnostic error handling has been added. In the event of an internal fault, a diagnostic error code is generated and can be viewed with the OPI. The last error code can be viewed by selecting Setup ç System Config ç Maintenance ç Firmware Version. The diagnostic code is a two or three digit hexadecimal number.
02 to FF: Processor Fault 100: Protection-Algorithm Fault 200: Relay-Control Algorithm Fault 300: Starter-Control Fault 400: Menu-Display Fault 500: OPI-Key-Handler Fault 600: Real-Time Clock Fault 700: Communication-Handler Fault 800: RTD Temperature-Handler Fault 900: A/D Communication-Interface Fault
The last diagnostic error code is saved in non-volatile memory. The diagnostic code is overwritten by any new codes but can also be manually set to zero. To clear the error code, press RESET while in the Firmware Version menu.
Page 74
Page 7-2 MPS Motor Protection System Rev. 6-F-022117
Theory of Operation
When upgrading an MPS that did not previously support the diagnostic error code, the initial value of the diagnostic code is not valid and should be cleared. A diagnostic error generates a Trip1 and increments the trip counter; however, a trip record is not generated.
Page 75
Page 8-1 MPS Motor Protection System Rev. 6-F-022117
Personal Computer Interface
8. COMMUNICATIONS
8.1 PERSONAL-COMPUTER INTERFACE
8.1.1 FIRMWARE UPGRADE
The MPS-CTU control program is stored in flash memory. Field updates can be made through the I/O module communications connection. The following are required:
• A WindowsÒ PC with the SE-Flash program installed
• A file containing the MPS-CTU control program (.s19
file)
• An RS-232/RS-485 converter that operates at 57,600
bit/s. Use the Littelfuse Startco SE-485-PP or
SE-485-DIN. SE-Flash is available at www.littelfuse.com/ relayscontrols.
8.1.2 SE-COMM-RIS
SE-Comm-RIS is a Windows-based program used to access MPS functions with a personal computer (PC) via the RS-485 network interface or Modbus® TCP
(1)
. Use SE­Comm-MPS to program an MPS either by changing individual set points or by downloading set-point files. Existing MPS set points can be transferred to the PC. Metered values can be viewed simultaneously and the MPS can be controlled with the computer. SE-Comm-RIS extends the event-record storage capability of the MPS by allowing the user to transfer data to PC memory at a programmable interval. Protection curve plotting capability is included. SE-Comm-RIS is available at www.littelfuse.com/relayscontrols.
(1)
Requires Ethernet option and firmware 2.50 or higher.
8.2 NETWORK INTERFACE
Each MPS-CTU is equipped with an RS-485 interface and can be optionally equipped with a DeviceNet, Ethernet, or Profibus interface. Communications interfaces are mutually exclusive; only one can be used at a time. For detailed information see Appendices in this manual and applicable communications manuals.
8.2.1 RS-485 COMMUNICATIONS
SE-485 communications support Modbus® RTU and Allen Bradley® DF1 half-duplex protocols. All set points and meter values are accessible. Commands are provided to perform trips, resets, and starter control.
Modbus® RTU function codes supported:
• Read Holding Registers (Code 3)
• Read Input Registers (Code 4)
• Write Single Register (Code 6)
• Write Multiple Registers (Code 16)
• Command Instruction (Code 5)
DF1 Commands Supported
• Unprotected Read (CMD = 01)
• Unprotected Write (CMD = 08)
• Typed Read (CMD = 0F, FNC = 68)
• Typed Write (CMD = 0F, FNC = 67)
• Typed Logical Read (CMD = 0F, FNC = A2)
• Typed Logical Write (CMD = 0F, FNC = AA)
8.2.2 DEVICENET COMMUNICATIONS
DeviceNet™ communications support Explicit Messaging and Polled I/O. All set points and meter values are accessible using Explicit Messaging. The Polled I/O connection supports the following ODVA input assemblies:
• Basic Overload (50)
• Extended Overload (51)
• Basic Motor Starter (52)
• Extended Motor Starter 1 (53)
• Extended Motor Starter 2 (53)
In addition to the ODVA assemblies, a user-configurable fixed block of 64 bytes is available. The Polled I/O connection supports the following ODVA Output assemblies:
• Basic Overload (2)
• Basic Motor Starter (3)
• Extended Contactor
• Extended Motor Starter
An Electronic Data Sheet (EDS) file is provided for use with DeviceNet configuration tools such as RSNetWorx and DeltaV.
8.2.3 ETHERNET COMMUNICATIONS
The MPS supports Modbus® TCP and Ethernet/IP using the Anybus-S module from HMS Fieldbus Systems AB. Data from the MPS consists of a 64-byte assembly representing user-defined register data. A command structure is provided to write set-point and MPS commands. Starting with firmware 2.50, Modbus® TCP provides access to all MPS registers and supports SE-Comm-RIS.
8.2.4 PROFIBUS COMMUNICATIONS
The MPS supports Profibus-DP using the Anybus-S module. Data from the MPS consists of a 64-byte assembly representing user-defined register data. A command structure is provided to write set-point and MPS commands.
Page 76
Page 8-2 MPS Motor Protection System Rev. 6-F-022117
Technical Specifications
This page intentionally left blank.
Page 77
Page 9-1 MPS Motor Protection System Rev. 6-F-022117
Technical Specifications
9. TECHNICAL SPECIFICATIONS
9.1 CONTROL UNIT (MPS-CTU)
Supply ....................................... 25 VA, 120 to 240 Vac
(+10, -45%),
40 to 400 Hz, power factor corrected; 25 W, 110 to 250 Vdc (+10, -25%)
Power-Up Time ......................... 800 ms at 120 Vac
Ride-Through Time .................. 100 ms minimum
24-Vdc Source
(1)
....................... 100 mA maximum
AC Measurements:
Methods ............................... True RMS and DFT,
Positive- and negative-
sequence components of the fundamental
Sample Rate ........................ 16 samples/cycle
Frequency:
Fixed .................................... 50, 60 Hz
Variable ............................... 10 to 70 Hz, sync via
4-20 mA signal from ASD
Phase-Current Inputs:
(2)
Range ................................... 18 x CT-Primary Rating
(Ip)
Accuracy:
(3)
I < Ip .................................. 1% Ip
I > Ip .................................. 1% Reading
Burden ................................. < 0.01 W
Unbalance Accuracy ........... 0.01 pu
Common-Mode Voltage ...... 120 Vac maximum
Thermal Withstand:
Continuous ........................ 5 x IP
1-Second ........................... 80 x IP
Earth-Leakage Input:
Range ................................... 1.5 x Earth-Fault-CT-
Primary Rating (Ie)
Accuracy
(3)
.......................... 1% Ie
Burden ................................. < 0.01 W (1- and 5-A
inputs), 10 W for EFCT
Common-Mode Voltage ...... 120 Vac maximum
Thermal Withstand:
Continuous ........................ 5 x Ie
1-Second ........................... 80 x Ie
Phase-Voltage Inputs:
(4, 5)
Nominal Input ..................... 30 to 600 Vac line-to-line
Input Resistance .................. 3.4 MW
Range ................................... 1.4 x PT-Primary Rating
(Vp)
Voltage-Input Fuse .............. 0.3 A, Class CC
Littelfuse KLKR.300 Voltage-Input Wire
(9)
........... 18 AWG to 14 AWG
(0.82 to 2.08 mm2), 600 V Accuracy:
(3)
V < Vp ............................... 1% Vp
V > Vp ............................... 1% Reading
Unbalance Accuracy ........... 0.01 pu
Frequency Metering:
Range ................................... 5 to 100 Hz,
Uses VA input,
Sine wave assumed
Accuracy ............................. 0.05 Hz
PTC-Thermistor Input:
(1)
Cold Resistance ................... 1500 W maximum at 20°C
(68°F)
Trip Level ............................ 2,800 W ± 100 W
Sensor Current ..................... 2 mA maximum
4-20 mA Analog Input:
Input Burden ........................ 100 W
Common-Mode Voltage
(6)
............................ ± 5 Vdc
4-20 mA Analog Output:
(1)
Load ..................................... 500 W maximum
Range ................................... 0 to 25 mA
Update Time ....................... 500 ms
Tachometer Input:
(7)
Type ..................................... Active pickup, 24-V logic
output, sourcing, PNP output TURCK Bi1.5-EG08­AP6X-V1131 or
equivalent
Pulses Per Revolution ......... 1 to 120
Pulse Frequency .................. 10 Hz to 10 kHz
Accuracy ............................. 1%
Timing Accuracies:
(8)
Set Points ............................. -10%, + 0%
(minimum 25 to 45 ms)
Overload .............................. Greater of 2% or
+ 200 ms (minimum 25 to
45 ms)
Page 78
Page 9-2 MPS Motor Protection System Rev. 6-F-022117
Technical Specifications
Starter-Control Stop Time:
Digital Input ........................ 30 to 80 ms
OPI ...................................... 70 to 200 ms
Network ............................... 30 to 80 ms
Relay Contacts (Relays 1 and 2):
Configuration ...................... N.O. (Form A)
CSA/UL Contact Rating ..... 8 A resistive 250 Vac, 5 A
resistive 30 Vdc Supplemental Contact Ratings: Break:
dc ................................... 200 W resistive,
ac .................................... 3,040 VA resistive,
1,000 VA inductive
(PF = 0.4) Subject to maximums of 8 Aac and 5 Adc, 250 V (ac or dc).
Relay Contacts (Relays 3 and 4):
Configuration ...................... N.O. and N.C. (Form C)
CSA/UL Contact Rating ..... 8 A resistive 250 Vac,
8 A resistive 30 Vdc Supplemental Contact Ratings:
Make/Carry ....................... 30 A, 0.2 s
Rating Code ...................... B300
Break:
dc ................................... 50 W resistive, 150 Vdc
ac .................................... 2,500 VA resistive,
360 VA inductive
(PF = 0.4) Subject to maximums of 8 A and 250 V (ac or dc).
Solid-State Output (Relay 5):
Configuration ...................... N.O. (Form A)
Rating .................................. 100 mA, 250 V (ac or dc)
On Resistance ...................... 30 W maximum
Digital Inputs:
(1)
Range ................................... 24 to 130 V (ac or dc),
5 mA
Guaranteed On .................... 12 Vdc at 3 mA,
20 Vac at 3 mA
Guaranteed Off .................... 3 Vdc at 2 mA,
2.5 Vac at 0.3 mA IRIG-B:
Format ................................. Amplitude Modulated
IRIG-B122
Amplitude ............................ 1 to 10 Vpp
Impedance ........................... 10 kW
Ratio .................................... 3:1 to 6:1
I/O Module Interface (OPI, RTD and DIF): Module Supply
(1)
................ 24 Vdc, 400 mA maximum
Configuration ...................... RS-485, 2-wire multi-drop
Bus Length .......................... 1.2 km (4,000’) maximum
Cable ................................... Belden 3124A or
equivalent
Standard Network Communications:
Configuration ...................... RS-485, 2-wire multi-drop
Baud Rate ............................ 1.2, 2.4, 4.8, 9.6, 19.2
kbit/s
Protocols .............................. Modbus RTU and
A-B DF1
Isolation ............................... 120 Vac
Bus Length .......................... 1.2 km (4,000’) maximum
Real-Time Clock and Non-Volatile RAM:
Power-Off Retention ........... 7 Years at 20°C (68°F)
Battery Shelf Life ................ > 50 Years at 20°C (68°F)
Tightening Torque:
Ordering Option .................... MPS-CTU-XX-00
All Terminals .................. 0.6 N•m (5.31 lbf•in) maximum
Ordering Option .................... MPS-CTU-XX-01
CT Input Terminals ......... 0.79 N•m (7.0 lbf•in) maximum
All Other Terminals ........ 0.6 N•m (5.31 lbf•in) maximum
Dimensions:
Height ................................... 121 mm (4.8”)
Width .................................... 190 mm (7.5”)
Depth .................................... 127 mm (5.0”)
Shipping Weight ....................... 2.0 kg (4.4 lb)
PWB Conformal Coating .......... MIL-1-46058 qualified
UL QMJU2 recognized Environment:
Operating Temperature ......... -40 to 60°C (-40 to 140°F)
Storage Temperature ............. -55 to 80°C (-67 to 176°F)
Humidity ............................. 85% Non-Condensing
Surge Withstand ........................ ANSI/IEEE C37.90.1-1989
(Oscillatory and Fast
Transient)
Certification .............................. CSA, Canada and USA
UL Recognized
(10)
Australia
To: CSA C22.2 No. 14 Industrial Control Equipment
UL 60947-4-1 Low-voltage switchgear and control gear - Part 4-1: Contactors and motor-starters ­Electromechanical Contactors and motor-starters. UL 1053 Ground Fault Sensing and Relaying Equipment Australia, Regulatory Compliance Mark (RCM)
Page 79
Page 9-3 MPS Motor Protection System Rev. 6-F-022117
Technical Specifications
9.2 OPERATOR INTERFACE (MPS-OPI)
Supply
(1)
.................................... 24 Vdc Nominal (20 to 30
Vdc), 80 mA
Display Type ............................. 4 x 20 Alphanumeric
Vacuum Fluorescent Interconnection Cable:
Type ..................................... Beldenâ 3124A or
equivalent
Maximum Length ................ 1.2 km (4,000’)
Supplied length .................... 4 m (13’)
Tightening Torque .................... 0.6 N•m (5.31 lbf•in)
maximum
Dimensions:
Height .................................... 98 mm (3.9”)
Width ..................................... 192 mm (7.6”)
Depth ..................................... 113 mm (4.5”)
Shipping Weight ....................... 0.6 kg (1.3 lb)
PWB Conformal Coating .......... MIL-1-46058 qualified
UL QMJU2 recognized
Environment:
Operating Temperature ....... -40 to 60°C (-40 to 140°F)
Storage Temperature ........... -55 to 80°C (-67 to 160°F)
Humidity ............................. 85% Non-Condensing
Surge Withstand ........................ ANSI/IEEE C37.90.1-
1989 (Oscillatory and Fast
Transient)
Certification .............................. CSA, Canada and USA
UL Recognized
(10)
Australia
Hazardous-Location ............ Class I Zone 2 Ex nA II
T6
Class I, Division 2,
Groups A, B, C, D To: CSA C22.2 No. 14 Industrial Control Equipment CSA C22.2 No. 213-M1987 – Non-Incendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations
UL 60947-4-1 Low-voltage switchgear and control gear - Part 4-1: Contactors and motor-starters - Electromechanical Contactors and motor-starters. UL 1053 Ground Fault Sensing and Relaying Equipment
Australia, Regulatory Compliance Mark (RCM)
9.3 RTD MODULE (MPS-RTD)
Supply
(1)
.................................... 16 to 32 Vdc, 90 mA
Configuration ............................ 8 inputs, 3-wire RTD
RTD Types ................................ Pt100, Ni100, Ni120,
Cu10
Measurement Range .................. -40 to 200°C (-40 to
392°F), with open and short detection
Sensor Current .......................... 2 mA
Lead Compensation .................. 20 W maximum
Accuracy:
Pt100, Ni100, Ni120 RTD .... 1°C
Cu10 RTD ........................... 3°C
Interconnection Cable:
Type ..................................... Beldenâ 3124A or
equivalent
Maximum Length ................ 1.2 km (4,000’)
Supplied length .................... 4 m (13’)
Tightening Torque .................... 0.6 N•m (5.31 lbf•in)
maximum
Dimensions:
Height .................................... 87 mm (3.4”)
Width ..................................... 113 mm (4.4”)
Depth ..................................... 53 mm (2.1”)
Shipping Weight ....................... 0.4 kg (0.9 lb)
PWB Conformal Coating .......... MIL-1-46058 qualified
UL QMJU2 recognized Environment:
Operating Temperature ....... -40 to 60°C
(-40 to 140°F)
Storage Temperature ........... -55 to 80°C
(-67 to 160°F)
Humidity ............................. 85% Non-Condensing
Surge Withstand ........................ ANSI/IEEE C37.90.1-1989
(Oscillatory and Fast
Transient)
Page 80
Page 9-4 MPS Motor Protection System Rev. 6-F-022117
Technical Specifications
Certification .............................. CSA, Canada and USA
UL Recognized
(10)
Australia
Hazardous-Location ........... Class I Zone 2 Ex nA II
T6 Class I, Division 2,
Groups A, B, C, D To: CSA C22.2 No. 14 Industrial Control Equipment
UL 60947-4-1 Low-voltage switchgear and control gear - Part 4-1: Contactors and motor-starters ­Electromechanical Contactors and motor-starters. UL 1053 Ground Fault Sensing and Relaying
Equipment CSA E60079-15: 02 Electrical Apparatus for Explosive Gas Atmospheres CSA C22.2 No. 213-M1987 – Non-Incendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations UL 60079-15 Electrical Apparatus for Explosive Gas Atmospheres Australia, Regulatory Compliance Mark (RCM)
9.4 DIFFERENTIAL MODULE (MPS-DIF)
Supply
(1)
.................................... 16 to 32 Vdc, 90 mA
CT Inputs: Thermal Withstand:
Continuous ........................ 5 x CT Primary Rating (Id)
1-Second ........................... 80 x Id
Burden ................................. 0.01 W
Terminal-Block Ratings:
CT Inputs ............................. 25 A, 500 Vac
10 AWG (4.0 mm2)
Tightening Torque ............... 0.6 N•m (5.31 lbf•in)
maximum
Differential-Current Measurement:
Metering Range ................... 15 x Id
Protection Range ................. 80 x I
d
Metering Accuracy:
I < Id .................................. 2% Id
I > Id .................................. 2% Reading
Timing Accuracy ................. 5%, minimum trip time,
Range is set point +20 ms to set point +150 ms, median 81 ms
Interconnection Cable:
Type ..................................... Belden® 3124A or
equivalent
Maximum Length ................ 1.2 km (4,000’
Supplied length .................... 4 m (13’)
Dimensions:
Height .................................... 87 mm (3.4”)
Width ..................................... 113 mm (4.4”)
Depth ..................................... 53 mm (2.1”)
Shipping Weight ....................... 0.4 kg (0.9 lb)
PWB Conformal Coating .......... MIL-1-46058 qualified
UL-QMJU2 recognized Environment:
Operating Temperature ......... -40 to 60°C (-40 to 140°F)
Storage Temperature ............. -55 to 80°C (-67 to 176°F)
Humidity ............................. 85% Non-Condensing
Surge Withstand ........................ ANSI/IEEE C37.90.1-
1989 (Oscillatory and Fast
Transient)
NOTES:
(1)
The I/O module supply (terminal 56), PTC (terminal
54), AN OUT (terminal 40), and 24-Vdc source (terminal 42) are referenced to the same common.
(2)
Current Threshold (%) is defined in Section 3.2.1.2.
Power readings are not displayed for currents below this threshold. To maintain specified accuracy, phase CT's should be selected with a primary rating between 100 and 300% of motor full-load current.
(3)
Transformer accuracy not included.
(4)
Voltage unbalance is not displayed for positive-
sequence voltage levels below 20% of system voltage setting.
(5)
Direct connection for system-voltages up to 600 Vac
line-to-line. UL certification requires the voltage­input fault current to be limited to 5 kA. Use Class CC fuses, 3/10 A, Littelfuse KLKR.300. A self­adhesive label stating this limitation is provided.
(6)
Common-mode voltage relative to CTU terminal 3.
(7)
Referenced to COM.
(8)
Also see Tables 5.1 and 5.2.
(9)
When direct connection is used.
(10)
A 600Y/347 or 480Y/277 system is required when the MPS direct-voltage connection is used.
(11)
UL has evaluated the MPS for use with 60°/ 75° C
conductors.
Page 81
Page 9-5 MPS Motor Protection System Rev. 6-F-022117
Technical Specifications
10. WARRANTY
The MPS Motor Protection System is warranted to be
free from defects in material and workmanship for a period ten years from the date of purchase. Littelfuse Startco will (at Littelfuse Startco’s option) repair, replace, or refund the original purchase price of an MPS-CTU, MPS-OPI, MPS-RTD, or MPS-DIF that is determined by Littelfuse Startco to be defective if it is returned to the Littelfuse Startco factory, freight prepaid, within the warranty period. This warranty does not apply to repairs required as a result of misuse, negligence, an accident, improper installation, tampering or insufficient care. Littelfuse Startco does not warrant products repaired or modified by non-Littelfuse Startco personnel.
Page 82
Page 9-6 MPS Motor Protection System Rev. 6-F-022117
Technical Specifications
This page intentionally left blank.
Page 83
Page A-1 MPS Motor Protection System Rev. 6-F-022117
Appendix A, MPS-OPI Menu Map
APPENDIX A
MPS-OPI MENU MAP
Page 84
Page A-2 MPS Motor Protection System Rev. 6-F-022117
Appendix A, MPS-OPI Menu Map
Page 85
Page A-3 MPS Motor Protection System Rev. 6-F-022117
Appendix A, MPS-OPI Menu Map
Page 86
Page A-4 MPS Motor Protection System Rev. 6-F-022117
Appendix A, MPS-OPI Menu Map
Page 87
Page A-5 MPS Motor Protection System Rev. 6-F-022117
Appendix A, MPS-OPI Menu Map
Page 88
Page A-6 MPS Motor Protection System Rev. 6-F-022117
Appendix A, MPS-OPI Menu Map
Page 89
Page B-1 MPS Motor Protection System Rev. 6-F-022117
Appendix B, MPS Set-Up Record
APPENDIX B
MPS SET-UP RECORD
Motor: _____________________________ MPS S/N: __________________________ Date: _____________________
Firmware Revision:___________________________
PART I: SYSTEM AND MOTOR PARAMETERS
PARAMETER AND SETTINGS
MIN
DEFAULT
MAX
UNIT
PROGRAM SELECTION
System Ratings
PH-CT Primary (Ip)
1
100.00
5,000
A
EF-CT Primary (Ie)
1
5.00
5,000
A
DF-CT Primary (Id)
1
100.00
5,000
A
System Voltage
0.12
0.60
25
kV
Input Voltage
0.06
0.12
0.6
kV
Input Voltage Connection
None
q None q 1PT
q 2PT q 3PT/Direct
Full-Load Current
1
100.00
5,000
A
Frequency
60 Hz
q 50
q 60
Synchronous Speed
10
1,800.00
10k
rpm
Service Factor
1
1.00
1.25
pu
FLA Rating 2
1
100.00
5,000
A
Run-Mode Delay
5
10.00
120
s
Digital Inputs
See Table 4.2 Input Function Definition
Input 1: Function
Not Used
Start Bypass
Disable
q Enable
q Disable
Bypass Delay
0.5
5.00
100
s
Trip Delay
0.01
0.10
100
s
Input 2: Function
Not Used
Start Bypass
Disable
q Enable
q Disable
Bypass Delay
0.5
5.00
100
s
Trip Delay
0.01
0.10
100
s
Input 3: Function
Not Used
Start Bypass
Disable
q Enable
q Disable
Bypass Delay
0.5
5.00
100
s
Trip Delay
0.01
0.10
100
s
Input 4: Function
Not Used
Start Bypass
Disable
q Enable
q Disable
Bypass Delay
0.5
5.00
100
s
Trip Delay
0.01
0.10
100
s
Input 5: Function
Not Used
Start Bypass
Disable
q Enable
q Disable
Bypass Delay
0.5
5.00
100
s
Trip Delay
0.01
0.10
100
s
Input 6: Function
Not Used
Start Bypass
Disable
q Enable
q Disable
Bypass Delay
0.5
5.00
100
s
Trip Delay
0.01
0.10
100
s
Input 7: Function
Not Used
Start Bypass
Disable
q Enable
q Disable
Bypass Delay
0.5
5.00
100
s
Trip Delay
0.01
0.10
100
s
Page 90
Page B-2 MPS Motor Protection System Rev. 6-F-022117
Appendix B, MPS Set-Up Record
PARAMETER AND SETTINGS
MIN
DEFAULT
MAX
UNIT
PROGRAM SELECTION
Tachometer
Disable
q Enable
q Disable
Pulses per Revolution
1
60.00
100
Relay Outputs
See Table 4.1 Output Function Definition
Relay 1: Function
None
Mode
Fail-Safe
q Fail-Safe
q Non-Fail-Safe
Relay 2: Function
None
Mode
Fail-Safe
q Fail-Safe
q Non-Fail-Safe
Relay 3: Function
None
Mode
Fail-Safe
q Fail-Safe
q Non-Fail-Safe
Relay 4: Function
None
Mode
Fail-Safe
q Fail-Safe
q Non-Fail-Safe
Relay 5: Function
None
Mode
Fail-Safe
q Fail-Safe
q Non-Fail-Safe
RY Pulse Time
0.05
0.25
10 s
Analog Input
4-20 Input Type
Metering
Only
q Metering Only q Protection
q Sync. to ASD q Motor Speed
Protection:
High-Level Trip
0.1
16.00
20
mA
Low-Level Trip
0.1
7.00
20
mA
Trip Delay
0.01
5.00
100
s
High-Level Alarm
0.1
14.00
20
mA
Low-Level Alarm
0.1
9.00
20
mA
Alarm Delay
0.01
1.00
100
s
Sync to ASD Set Points:
4-mA Frequency
0
10.00
70
Hz
20-mA Frequency
0
60.00
70
Hz
Motor Speed Set Points:
4-mA Percent Speed
0
10.00
100
%
20-mA Percent Speed
0
100.00
100
%
Analog Output
Output Parameter
Phase
Current
See Table 4.3 Analog Output Parameter Definition
Zero Calibrate
Factory Calibrated
Full-Scale Calibrate
Factory Calibrated
OPI Display
OPI-Loss Trip
Trip1
q Disable q Trip2
q Trip1 q Trip3
Number of OPI’s
1
q 1 q 2
q 3
Intensity
100 %
q 25 q 50
q 75 q 100
Screen Saver
Enable
q Enable
q Disable
OPI Control Select
Remote Select
Enable
q Enable
q Disable
OPI Select
Enable
q Enable
q Disable
Local Select
Enable
q Enable
q Disable
RTD Modules
Total Modules
0
q 0 q 1
q 2 q 3
RTD-Module-Error Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Page 91
Page B-3 MPS Motor Protection System Rev. 6-F-022117
Appendix B, MPS Set-Up Record
PARAMETER AND SETTINGS
MIN
DEFAULT
MAX
UNIT
PROGRAM SELECTION
RTD-Module-Error Alarm
Action
Disable
q Disable q Alarm2
q Alarm1 q Alarm3
Temperature Trip Action
Trip1
q Disable q Trip2
q Trip1 q Trip3
Temperature Alarm Action
Alarm1
q Disable q Alarm2
q Alarm1 q Alarm3
DIF Module
Enable/Disable
Disable
q Enable
q Disable
DIF-Module-Error Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
DIF-Module-Error Alarm
Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Network Communications
Network Type
Modbus
q None q Allen-Bradley q Modbus
q DeviceNet q Anybus q Modbus TCP
Network ID
0
254
255
Baud Rate
SCI 9600
q SCI 1200 q SCI 2400 q SCI 4800 q SCI 9600 q SCI 19200
(1)
q DN125 q DN250 q DN500
Error Checking
Not
Selected
q Not Selected q CRC
q BCC
Ethernet IP
192.168.
000.001
Ethernet Mask
255.255.
255.000
Default Gateway
0.0.0.0
Network-Error Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Network-Error Alarm Action
Disable
q Disable q Alarm2
q Alarm1 q Alarm3
DeviceNet Producing Assembly
0x36
q None q 0x33 q 0x35 q 0x64 q 0x66
q 0x32 q 0x34 q 0x36 q 0x65 q 0x67
DeviceNet Consuming Assembly
None
q None q 0x03 q 0x05
q 0x02 q 0x04
System Name
Startco MPS
Change Password
1111
Password Timeout
1
10.00
60
min.
Ip Threshold (IP is Phase-CT-Primary Rating)
0.10
0.10
0.50
x Ip
Firmware Revision
See Protection | System Config | Maintenance | Firmware Version
Trace Auto-Start
Disable
q Enable
q Disable
(1)
Error rate is 1 byte/120 kB. For high reliability, use SCI9600.
Page 92
Page B-4 MPS Motor Protection System Rev. 6-F-022117
Appendix B, MPS Set-Up Record
PART II: STARTER PARAMETERS
SET POINT
MIN
DEFAULT
MAX
UNIT
PROGRAM SELECTION
Starter Type (see Table 6.2)
Protection Only
Start Time
0.1
20.00
500 s
Stage 1 Delay
0.1
20.00
500 s
Stage 2 Delay
0.1
20.00
500 s
Stage 3 Delay
0.1
20.00
500 s
Backspin Timer
Disable
q Enable
q Disable
Backspin Delay
0.1
5.00
3,600
s
Remote Group
Digital Inputs
Enable
q Enable
q Disable
Network
Enable
q Enable
q Disable
OPI
Enable
q Enable
q Disable
Transfer
Type
Time
q Time
q Current
Level
1.0
1.25
3.0
x FLA
PART III: PROTECTION SET POINTS
FUNCTION & SET POINT
MIN
DEFAULT
MAX
UNIT
PROGRAM SELECTION
Overload
Trip Action
Trip1
q Disable q Trip2
q Trip1 q Trip3
Model Type
NEMA
q NEMA
q K-Factor
K-Factor
1
6.00
10 Locked-Rotor Current
1.5
6.00
10
x FLA
Locked-Rotor Time Cold
0.10
10.00
100
s
Locked-Rotor Time Hot
0.10
5.00
100
s
Cooling Factor
0.10
2.00
10 I2t Start Inhibit
Disable
q Enable
q Disable
I2t Inhibit Level (Per Unit Based on 100% I2t)
0.10
0.30
.90
pu
I2t Alarm Action
Alarm1
q Disable q Alarm2
q Alarm1 q Alarm3
I2t Overload Alarm Level
0.50
1.00 1 pu
Reset Type
Normal
q Normal
q Auto
q Multiple Motor Sequence
Overcurrent
Trip Action
Trip1
q Disable q Trip2
q Trip1 q Trip3
Trip Level (Ip is Phase-CT-Primary Rating)
1
10.00
15
x Ip
Trip Delay
0
0.05
10 s Auxiliary Overcurrent
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Trip Level (Ip is Phase-CT-Primary Rating)
1
10.00
15
x Ip
Trip Delay
0
0.05
10 s
Page 93
Page B-5 MPS Motor Protection System Rev. 6-F-022117
Appendix B, MPS Set-Up Record
FUNCTION & SET POINT
MIN
DEFAULT
MAX
UNIT
PROGRAM SELECTION
Reduced Overcurrent
Trip Action
Trip1
q Disable q Trip2
q Trip1 q Trip3
Trip Level (Ip is Phase-CT-Primary Rating)
1
2.00
15
x Ip
Earth Fault
Trip Action
Trip1
q Disable q Trip2
q Trip1 q Trip3
Trip Level (Ie is EF-CT-Primary Rating)
0.05
0.40 1 x Ie
Trip Delay
0
0.25
100
s
Alarm Action
Alarm1
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level (Ie is EF-CT-Primary Rating)
0.05
0.20 1 x Ie
Alarm Delay
0
1.00
100
s
Jam
Trip Action
Trip1
q Disable q Trip2
q Trip1 q Trip3
Trip Level
1
6.00
10
x FLA
Trip Delay
1
5.00
100
s
Alarm Action
Alarm1
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level
1
3.00
10
x FLA
Alarm Delay
1
5.00
100
s
Unbalance (I)
Trip Action
Trip1
q Disable q Trip2
q Trip1 q Trip3
Trip Level (Per Unit Based on I2/I1)
0.05
0.25 1 pu
Trip Delay
1
15.00
100
s
Alarm Action
Alarm1
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level
0.05
0.10 1 pu
Alarm Delay
1
10.00
100
s
Phase Loss (I)
Trip Action
Trip1
q Disable q Trip2
q Trip1 q Trip3
Phase Loss Delay
1
5.00
100
s
Phase Reverse (I)
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Alarm Action
Alarm1
q Disable q Alarm2
q Alarm1 q Alarm3
Trip and Alarm Delay
1
2.00
100
s
Page 94
Page B-6 MPS Motor Protection System Rev. 6-F-022117
Appendix B, MPS Set-Up Record
FUNCTION & SET POINT
MIN
DEFAULT
MAX
UNIT
PROGRAM SELECTION
Unbalance (V)
Trip Action
Trip1
q Disable q Trip2
q Trip1 q Trip3
Trip Level (Per Unit Based on V2/V1)
0.05
0.10 1 pu
Trip Delay
1
15.00
100
s
Alarm Action
Alarm1
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level
0.05
0.05 1 pu
Alarm Delay
1
10.00
100
s
Phase Loss (V)
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Phase Loss Delay
1
5.00
100
s
Phase Reverse (V)
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Alarm Action
Alarm1
q Disable q Alarm2
q Alarm1 q Alarm3
Phase Reverse Trip and Alarm Delay
1
2.00
100
s
Undercurrent
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Trip Level
0.1
0.50
1
x FLA
Trip Delay
1
10.00
100
s
Alarm Action
Disable
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level
0.1
0.80
1
x FLA
Alarm Delay
1
20.00
100
s
Differential
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Trip Level (Id is DF-CT-Primary Current)
0.1
1.00
15
x Id
Trip Delay
0
0.10
10
s
Alarm Action
Disable
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level (Id is DF-CT-Primary Current)
0.1
0.50
15
x Id
Alarm Delay
0
0.10
10
s
PF Quadrant 4
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Trip Level
0.5
0.80 1
Trip Delay
0.1
5.00
500
s
Alarm Action
Disable
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level
0.5
0.90 1
Alarm Delay
0.1
5.00
500
s
Page 95
Page B-7 MPS Motor Protection System Rev. 6-F-022117
Appendix B, MPS Set-Up Record
FUNCTION & SET POINT
MIN
DEFAULT
MAX
UNIT
PROGRAM SELECTION
PF Quadrant 3
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Trip Level
0.5
0.80 1
Trip Delay
0.1
5.00
500
s
Alarm Action
Disable
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level
0.5
0.90 1
Alarm Delay
0.1
5.00
500
s
Underpower
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Trip Level (Per Unit of Rated Power)
0.1
0.80 1 pu
Trip Delay
0.5
5.00
500
s
Alarm Action
Disable
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level (Per Unit of Rated Power)
0.1
0.80 1 pu
Alarm Delay
0.5
1.00
500
s
Reversepower
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Trip Level (Per Unit of Rated Power)
0.1
0.20 1 pu
Trip Delay
0.5
5.00
500
s
Alarm Action
Disable
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level (Per Unit of Rated Power)
0.1
0.20 1 pu
Alarm Delay
0.5
1.00
500
s
Underfrequency
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Trip Level
30
45
80
Hz
Trip Delay
0.5 5 500
s
Alarm Action
Disable
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level
30
48
80
Hz
Alarm Delay
0.5 1 500
s
Overfrequency
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Trip Level
30
65
80
Hz
Trip Delay
0.5 5 500
s
Alarm Action
Disable
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level
30
62
80
Hz
Alarm Delay
0.5 1 500
s
Page 96
Page B-8 MPS Motor Protection System Rev. 6-F-022117
Appendix B, MPS Set-Up Record
FUNCTION & SET POINT
MIN
DEFAULT
MAX
UNIT
PROGRAM SELECTION
PTC Temperature
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Alarm Action
Disable
q Disable q Alarm2
q Alarm1 q Alarm3
RTD-Sensor-Error Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
RTD-Sensor-Error Alarm
Action
Alarm1
q Disable q Alarm2
q Alarm1 q Alarm3
Hot-Motor Compensation (HMC)
Disable
q Enable
q Disable
HMC High
40
150.00
200
°C
HMC Low
40
40.00
200
°C
Acceleration Failure— Underspeed
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Speed 1 (Percent Sync Speed)
1
30.00
100
% SS
Time 1
1
5.00
1,000
s
Speed 2
1
60.00
100
% SS
Time 2
1
10.00
1,000
s
Speed 3
1
90.00
100
% SS
Time 3
1
15.00
1,000
s
Overvoltage
Trip Action
Trip1
q Disable q Trip2
q Trip1 q Trip3
Trip Level (Vp is system voltage)
1
1.20
1.4
x Vp
Trip Delay
1
5.00
500
s
Alarm Action
Alarm1
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level (Vp is system voltage)
1
1.10
1.4
x Vp
Alarm Delay
1
5.00
500
s
Undervoltage
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Trip Level (Vp is system voltage)
0.5
0.70 1 x Vp
Trip Delay
1
5.00
500
s
Alarm Action
Disable
q Disable q Alarm2
q Alarm1 q Alarm3
Alarm Level (Vp is system voltage)
0.5
0.80 1 x Vp
Alarm Delay
1
5.00
500
s
Starts/Hour
Trip Action
Disable
q Disable q Trip2
q Trip1 q Trip3
Alarm Action
q Disable q Alarm2
q Alarm1 q Alarm3
Number of Starts/Hour
1 5 10
Time Between Starts
0
0.00
500
min
Page 97
Page B-9 MPS Motor Protection System Rev. 6-F-022117
Appendix B, MPS Set-Up Record
FUNCTION & SET POINT
MIN
DEFAULT
MAX
UNIT
PROGRAM SELECTION
RTD TEMPERATURE
Requires RTD Module(s)
RTD M1 #1:
Name
RTD Module 1 #1
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
RTD M1 #2:
Name
RTD Module 1 #2
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
RTD M1 #3:
Name
RTD Module 1 #3
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
RTD M1 #4:
Name
RTD Module 1 #4
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
Page 98
Page B-10 MPS Motor Protection System Rev. 6-F-022117
Appendix B, MPS Set-Up Record
FUNCTION & SET POINT
MIN
DEFAULT
MAX
UNIT
PROGRAM SELECTION
RTD M1 #5:
Name
RTD Module 1 #5
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
RTD M1 #6:
Name
RTD Module 1 #6
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
RTD M1 #7:
Name
RTD Module 1 #7
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
RTD M1 #8:
Name
RTD Module 1 #8
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
Page 99
Page B-11 MPS Motor Protection System Rev. 6-F-022117
Appendix B, MPS Set-Up Record
FUNCTION & SET POINT
MIN
DEFAULT
MAX
UNIT
PROGRAM SELECTION
RTD M2 #1:
Name
RTD Module 2 #1
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
RTD M2 #2:
Name
RTD Module 2 #2
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
RTD M2 #3:
Name
RTD Module 2 #3
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
RTD M2 #4:
Name
RTD Module 2 #4
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
Page 100
Page B-12 MPS Motor Protection System Rev. 6-F-022117
Appendix B, MPS Set-Up Record
FUNCTION & SET POINT
MIN
DEFAULT
MAX
UNIT
PROGRAM SELECTION
RTD M2 #5:
Name
RTD Module 2 #5
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
RTD M2 #6:
Name
RTD Module 2 #6
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
RTD M2 #7:
Name
RTD Module 2 #7
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
RTD M2 #8:
Name
RTD Module 2 #8
Type
Disable
q Disable q Pt100 Ω q Ni100 Ω
q Ni120 Ω q Cu10 Ω
Function
Stator
q Stator q Bearing q Stator Voting q Bearing Voting
q Load q Ambient q Load Voting q Ambient Voting
Trip
40
130.00
200
°C
Alarm
40
110.00
200
°C
Loading...