Datasheet LXR1801-6, LXR1740-6M1, LXR1240-6M1, LXR-1601-6, LXN2880-6 Datasheet (POWER-ONE)

...
Page 1
1
www.power-one.com
Edition 5/7.2001
• Electrically and mechanically rugged DIN-rail front end
• Outputs individually controlled with 150% output peak power
Input range 85...264 V AC with PFC 1 or 2 isolated, regulated outputs up to 96 V 3 kV AC I/O electric strength test voltage
X Series 375 and 500 Watt AC-DC Converters
LGA
Selection chart for front ends
Output 1 Output 2 Input voltage Rated power Type Options
1
U
o nomIo nom
U
o nomIo nom
U
i min
U
i max
T
A
= 60°C
[V DC] [A] [V DC ] [A]
P
o tot
[W]
24.7 15 - - 375 LXR 1601-6 R
24.7 20 - - 500 LXN-1601-6 D1D5 37 9.9 - - 85264 VAC 375 LXR 1701-6 S
37 13.2 - -
(14440 Hz)
3
500 LXN 1701-6 M2
49.4 7.5 - - 90350 VDC 375 LXR-1801-6 F, F1
49.4 10 - - 500 LXN-1801-6 K2
24.7 10 24.7 10 500 LXN-2660-6
49.4 5 49.4 5 500 LXN 2880-6
Selection chart for Battery chargers
2
Output Input voltage Rated power Type Options
1
U
o nom
I
o nom
U
i min
U
i max
T
A
= 60°C
[V DC] [A]
P
o tot
[W]
25.7...29.3 12.6 85264 VAC 345 LXR 1240-6 M1 F, F1
25.7...29.3 16.9
(14440 Hz)
3
460 LXN 1240-6 M1 K2
51.4...58.6 6.3 90350 VDC 345 LXR 1740-6 M1
51.4...58.6 8.4 460 LXN 1740-6 M1
1
For lead times and minimum order quantities contact Power-One.
2
For availability contact Power-One.
3
Input frequency range certified for 14...440 Hz. For continuous operating frequency <40 Hz and >100 Hz contact
factory.
Page 2
2
www.power-one.com
Edition 5/7.2001
X Series 375 and 500 Watt AC-DC Converters
Input
Input voltage world wide mains, single phase 85...264 V AC
for derating information see application note 90...350 V DC Input frequency wide frequency range 16 2/3...440 Hz Power factor active PFC up to 0.99 Inrush current virtually no inrush current
Output
Efficiency
U
i nom
,
I
o nom
up to 89 %
Output voltage setting accuracy
U
i nom
,
I
o nom
±1.3%
U
o nom
Output voltage noise IEC/EN 61204 typ. 50 mV Output voltage ripple sinusoidal output ripple at twice the line frequency 1.2 V
pp
Line and cross regulation
U
i min
...
U
i max
typ. 50 mV
Load regulation 0...100%
I
o nom
,
U
i nom
–1.6%
U
o nom
Minimum load not required Current limitation rectangular U/I characteristic 101...112%
I
o nom
Short term peak power 1 s, electronically controlled 150%
I
o nom
Operation in parallel enabled by droop current share Hold-up time
I
o nom
,
U
o
decreases to 80 % of
U
o nom
typ. 15 ms
Control
Status indication LED output(s) OK
Protection
Input reverse polarity bridge rectifier Input fuse not user accessible 10 A, fast blow Input undervoltage lockout typ. 80%
U
i min
Input overvoltage lockout typ. 105%
U
i max
Input transient voltage depending resistor (VDR) Output(s) no-load, overload and short circuit proof Output overvoltage second control loop, each output, 24/48 V 30/60 V SELV Overtemperature reduced output power if thermally overloaded
Safety
Approvals in progress EN 60950, UL 1950, CSA22.2 No. 950, UL 508 listed Electric strength test voltage class I, I/case 2 kV AC
class I, I/O 3 kV AC
class I, O/case 1 kV AC
class I, O/O 0.35 kV AC Pollution degree AC-in / DC-in 3/2 Degree of protection IP 20
Page 3
3
www.power-one.com
Edition 5/7.2001
DIN Rail Mountable X Series
EMC
Electrostatic discharge IEC/EN 61000-4-2, level 4, contact/air (8/15 kV) criterion A Electromagnetic field IEC/EN 61000-4-3, level 3 (10 V/m) criterion A Electr. fast transients/bursts IEC/EN 61000-4-4, level 4, capacitive/direct (4/2 kV) criterion A Surge IEC/EN 61000-4-5, level 3, in and out, line to line (2 kV) criterion B
level >3, input, line to case (3.5 kV) criterion B
level 2, output, line to case (1 kV) criterion A Conducted disturbances IEC/EN 61000-4-6, level 3 (10 V) criterion A Electromagnetic emissions CISPR 22/EN 55022, conducted class B
Environmental
Operating ambient temperature
U
i nom
,
I
o nom
, convection cooled –40...60°C
Operating case temperature
TCU
i nom
,
I
o nom
–40...87°C Storage temperature non operational –40...100°C Damp heat IEC/EN 60068-2-3, 93%, 40 °C 56 days Shock and vibration unit wall mounted with brackets Shock IEC/EN 60068-2-27, 11 ms 50 g
n
Bump IEC/EN 60068-2-29, 11 ms 25 g
n
Vibration, sinusoidal IEC/EN 60068-2-6, 10...60/60...2000 Hz 0.35 mm/5 g
n
Vibration, random IEC/EN 60068-2-64, 20...500 Hz 0.05 g2/Hz MTBF MIL-HDBK-217E, GB, 40°C 400'000 h
Options
Input and output undervoltage monitoring D1...D5 Output voltage adjustment 10 V...110% of
U
o nom
R Remote on/off S Multi option choice (D1...D5, R, S) via Sub-D connector M1...M2 Built-in second input fuse in the neutral F No fuse fittet (for operation from high DC) F1 System connectors with screw terminals K2
Page 4
4
www.power-one.com
Edition 5/7.2001
Mechanical data
Tolerances ±0.3 mm (0.012") unless otherwise indicated.
European Projection
X Series 375 and 500 Watt AC-DC Converters
106.6 (4.2"
)
113.6 (4.47"
)
5
(
0.59"
)
204 (8.03"
)
()
194 (7.64"
)
()
9
(
1.93"
)
S09127
196 (7.71"
)
()
Wall mountin
g
brackets
(accessor
y)
Measuring point fo
r
case temperature
C
C
A
A
29.4 (1.16"
)
3
(
1.69"
)
31 (1.22")
Option
M
Page 5
5
www.power-one.com
Edition 5/7.2001
1
3
2
S10066
1
35
7
10
12
S90048
2
4
6
8
11
9
Accessories
Mounting brackets for vertical chassis/wall mounting Protective covers over input and output terminals
DIN Rail Mountable X Series
Terminal allocation output side
Pin Des. Single output Double output
1 Earth to load Earth to load 2 + Output pos. Output 1 pos. 3 + Output pos. Output 1 pos. 4 Output neg. Output 1 neg. 5 Output neg. Output 1 neg. 6 + Output pos. Output 2 pos. 7 + Output pos. Output 2 pos. 8 Output neg. Output 2 neg.
9 Output neg. Output 2 neg. 10 Aux1 Options Options 11 Aux2 Options Options 12 Earth to load Earth to load
Terminal allocation input side
Pin Des. Determination
1 Protective earth
2NInput neutral 3PIn
Loading...