Operating Voltage (47-440Hz) [Vrms]48-66048-66048-66048-66048-660
Transient Overvoltage [Vpk]12001200120012001200
Maximum Off-State Leakage Current @ Rated Voltage [mArms]1.01.01.01.01.0
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec]500500500500500
Maximum Load Current [Arms] (6)(3)25507590125
Minimum Load Current [mArms]150150150150150
Maximum 1 Cycle Surge Current (50/60Hz) [Apk]239/250597/625954/10001145/12001670/1750
Maximum On-State Voltage Drop @ Rated Current [Vrms]1.151.151.151.151.15
Thermal Resistance Junction to Case (Rjc) [°C/W]0.80.450.30.270.22
Maximum 1/2 Cycle I² t for Fusing (50/60Hz) [A² sec]285/2591779/16214555/41506560/597613950/12709
Minimum Power Factor (at Maximum Load) (7)0.50.50.50.5 0.5
INPUT SPECIFICATIONS
(5)
DescriptionDC Control
125A90A75A50A25ADescription
Control Voltage Range 4-32 VDC
Minimum Turn-On Voltage (7)4.0 VDC
Must Turn-Off Voltage1 .0 VDC
Maximum Reverse voltage-32 VDC
Minimum Input Current 7 mADC
Maximum Input Current 12 mADC
Nominal Input Impedance Current Regulated
Maximum Turn-On Time [msec] (8)1/2 Cycle
Maximum Turn-Off Time [msec] 1/2 Cycle
Maximum Capacitance, Input/Output8 pF
Ambient Operating Temperature Range -40 to 80 °C
Ambient Storage Temperature Range-40 to 125 °C
Weight (typical)2.6 oz (74.9 g)
Housing Material94 V-0
Baseplate MaterialAluminum
Input Terminal Screw Torque Range (in-lb/Nm)13-15 /1.5-1.7
Load Terminal Screw Torque Range (in-lb/Nm)18-20 / 2.0-2.2
SSR Mounting Screw Torque Range (in-lb/Nm)18-20 / 2.0-2.2
Input/Load Terminal Screw Torque Range (in-lb/Nm)
(3)w/”K” option 8-10 / 0.9-1.13
Input/Output Terminal Screw Thread Size#6-32 UNC / #8-32 UNC
Humidity per IEC60068-2-7893% non-condensing
LED Input Status Indicatorw/”G” option (green)
MTBF (Mean Time Between Failures) at 40°C ambient temperature (9)
11,641,553 hours (1,328 years)
MTBF (Mean Time Between Failures) at 60°C ambient temperature (9)
Designed in accordance with the requirements of IEC 62314
IEC 61000-4-2 : Electrostatic Discharge – Level 3
IEC 61000-4-4 : Electrically Fast Transients – Level 3
IEC 61000-4-5 : Electrical Surges – Level 3
IEC 600068-2-6: Vibration 0.33mm and 0.75mm Amplitude over 10-55 Hz
IEC 600068-2-27: Shock Resistance 15g/11ms
E116949 (25, 50, 75 and 90A)
E116950 (125A)LR81689 10143 UG
ACCESORIES
Protective Cover & Hardware Kits
Recommended Accessories
Protective Cover
Part number: KS101
Clear plastic cover compatible with all new
S1 designs. Safety covers provide added
protection from electric shock when
installing or checking equipment.
Hardware Kit
Part number: HK4
Bag with 2 square brass accessories and 2
screw 8-32 x 5/8 for output. Used to mount
TMR1 lug terminals.
CoverHardware
Kit
KS101HK1
HK4
Heat Sink
Part No.
HS501DR
HS301 / HS301DR
HS251
HS202 / HS202DR
HS201 / HS201DR
HS172
HS151 / HS151DR
HS122 / HS122DR
HS103 / HS103DR
HS101
HS073
HS072
HS053
HS033
HS023
Thermal Resistance
[ºC/W]
5.0
3.0
2.5
2.0
2.0
1.7
1.5
1.2
1.0
1.0
0.7
0.7
0.5
0.36
0.25
Lug Terminal Thermal Pad
TRM1
TRM6
HSP-1
HSP-2
GENERAL NOTES
(1)
Single pair (up to 25A) Double pair* (50A model only). *Caution: User must connect to both pairs
(2) Option “K” is designed and tested for use with printed circuit boards or ring/fork terminals having a thickness between 0.031 and 0.093 inches (0.79 to 2.36 mm), and loads rated up to 50 Amps.
For higher load currents, the “K” standoff temperature must not exceed 105°C. For additional application assistance please contact Crydom Technical Support.
(3)
O
utput will self trigger between 900-1200Vpk, Min. power factor 0.7 or higher, not suitable for capacitive loads.
(4) Instantaneous turn-on version is not recomended for capacitive loads. Use zero turn-on only.
(5)
All parameters at 25°C unless otherwise specified.
(6) Heat sinking required, see derating curves.
(7) Increase minimum voltage by 1V for operations from -20 to -40°C.
(8) Turn-on time for Instantaneous turn-on versions is 0.02 msec.
(9)
All parameters at 50% power rating and 100% duty cycle (contact Crydom tech support for detailed report).
(10)
Load can be wired to either SSR output terminal 1 or 2.
• The product’s side panels may be hot, allow the product to cool
before touching
• Follow proper mounting instructions including torque values
• Do not allow liquids or foreign objects to enter this product
Failure to follow these instructions can result in serious
injury, or equipment damage.
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Disconnect all power before installing or working with this
equipment
• Verify all connections and replace all covers before turning on
power
Failure to follow these instructions will result in death or
serious injury
Sensata Technologies, Inc. (“Sensata”) data sheets are solely intended to assist designers (“Buyers”) who are developing systems that
incorporate Sensata products (also referred to herein as “components”). Buyer understands and agrees that Buyer remains responsible
for using its independent analysis, evaluation and judgment in designing Buyer’s systems and products. Sensata data sheets have
been created using standard laboratory conditions and engineering practices. Sensata has not conducted any testing other than that
specifically described in the published documentation for a particular data sheet. Sensata may make corrections, enhancements,
improvements and other changes to its data sheets or components without notice.
Buyers are authorized to use Sensata data sheets with the Sensata component(s) identified in each particular data sheet. HOWEVER, NO
OTHER LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE TO ANY OTHER SENSATA INTELLECTUAL PROPERTY RIGHT, AND
NO LICENSE TO ANY THIRD PARTY TECHNOLOGY OR INTELLECTUAL PROPERTY RIGHT, IS GRANTED HEREIN. SENSATA DATA SHEETS
ARE PROVIDED “AS IS”. SENSATA MAKES NO WARRANTIES OR REPRESENTATIONS WITH REGARD TO THE DATA SHEETS OR USE
OF THE DATA SHEETS, EXPRESS, IMPLIED OR STATUTORY, INCLUDING ACCURACY OR COMPLETENESS. SENSATA DISCLAIMS
ANY WARRANTY OF TITLE AND ANY IMPLIED WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, QUIET
ENJOYMENT, QUIET POSSESSION, AND NON-INFRINGEMENT OF ANY THIRD PARTY INTELLECTUAL PROPERTY RIGHTS WITH REGARD
TO SENSATA DATA SHEETS OR USE THEREOF.
All products are sold subject to Sensata’s terms and conditions of sale supplied at www.sensata.com SENSATA ASSUMES NO LIABILITY
FOR APPLICATIONS ASSISTANCE OR THE DESIGN OF BUYERS’ PRODUCTS. BUYER ACKNOWLEDGES AND AGREES THAT IT IS SOLELY
RESPONSIBLE FOR COMPLIANCE WITH ALL LEGAL, REGULATORY AND SAFETY-RELATED REQUIREMENTS CONCERNING ITS PRODUCTS,
AND ANY USE OF SENSATA COMPONENTS IN ITS APPLICATIONS, NOTWITHSTANDING ANY APPLICATIONS-RELATED INFORMATION
OR SUPPORT THAT MAY BE PROVIDED BY SENSATA.
Mailing Address: Sensata Technologies, Inc., 529 Pleasant Street, Attleboro, MA 02703, USA.