12 digital inputs (4 inputs available as analog inputs)•
6 relay outputs•
LCD display•
Operating buttons•
Screw terminals•
Timer•
Can be expanded using easy expansion units•
Notes concerning the product group
Backup of real−time clock (only for appropriate devices)
Backup time (hours)
1
Page 2
Operating time (years)
General
EN 55011, EN 55022,
Standards
IEC/EN 61000−4, IEC
60068−2−6, IEC
60068−2−27
Dimensions (W × H × D)mm107.5 × 90 × 58 (6 PE)
Weightkg0,3
Top−hat rail IEC/EN 60715,
Mounting
35 mm or screw fixing using
fixing brackets
ZB4−101−GF1 (accessories)
Terminal capacities
Solidmm20.24 (AWG 22 – 12)
Flexible with ferrulemm20.22.5 (AWG 22 – 12)
Standard screwdrivermm3.5 × 0.8
Max. tightening torqueNm0,6
Input current
Input current 115/230 V ACmANormally 140
Voltage dips (IEC/EN 61131−2)ms10
Heat dissipationWNormally 3.5
Digital inputs 24 V DC
Number12
Inputs can be used as analog inputs4 (I7, I8, I11, I12)
Status indicationLCD−display (if present)
Potential isolation
From power supplyNo
Between digital inputsNo
From the outputsYes
Rated operational voltageU
On 0 signalU
On 1 signalU
e
e
e
V DC24
V DC< 5 (I1 – I12, R1 – R12)
V DC
> 15.0 (I1 – I6, I9, I10), > 8.0
(I7, I8, I11, I12)
Input current on 1 signal
I1 to I6mA3.3 (at 24 V DC)
I7, I8mA2.2 (at 24 V DC)
I9, I10mA3.3 (at 24 V DC)
I11, I12mA2.2 (at 24 V DC)
Delay time from 0 to 1
Debounce ONms20
Debounce OFFmsNormally 0.25 (I1 – I12)
Delay time from 1 to 0
Debounce ONms20
Cable length (unscreened)m100
Frequency counter
Quantity2 (I3, I4)
Counter frequencykHz< 1
Pulse shapeSquare
Pulse pause ratio1:1
Rapid counter inputs
Number2 (I1, I2)
Counter frequencykHz< 1
Pulse shapeSquare
Pulse pause ratio1:1
Analog inputs
Quantity4 (I7, I8, I11, I12)
4
Page 5
Potential isolation
From power supplyNo
From the digital inputsNo
From the outputsYes
From the PC interface, memory card
NET network, EASY−Link
No
Input typeDC voltage
Signal rangeV DC0 – 10
Resolution, analogV0,01
Resolution, digitalV0,01
Resolution, digitalBit10 (value 0 – 1023)
Input impedancek11,2
Accuracy of actual value
Two EASY devices%± 3
Within a single device%± 2, ± 0.12 V
Debounce ON: 20;
Conversion time, analog/digitalms
Debounce OFF: every cycle
time
Input currentmA< 1
Cable length screenedm< 30
Relay outputs
Number6
Outputs in groups of1
Parallel switching of outputs for
increased output
Protection of an output relay
Not permissible
Miniature circuit−breaker B16
or fuse 8 A (slow)
Potential isolation
From power supplyYes
From the inputsYes
From the PC interface, memory card
NET network, EASY−Link
No
Safe isolationV AC300
Basic insulationV AC600
Lifespan, mechanicalOperations× 10610
Contacts
Conventional thermal current (10 A
UL)
Recommended for load: 12 V
AC/DC
A8
mA> 500
5
Page 6
Short−circuit−proof cos = 1,
characteristic B16 at 600 A
A16
Short−circuit−proof cos = 0.5 to 0.7,
characteristic B16 at 900 A
Rated impulse withstand voltage
U
of contact coil
imp
Rated operational voltageU
Rated insulation voltageU
Safe isolation to EN 50178 between
coil and contact
Safe isolation to EN 50178 between
2 contacts
e
i
A16
kV6
V AC250
V AC250
V AC300
V AC300
Making capacity
AC−15, 250 V AC, 3 A (600 Ops./h)Operations300000
DC−13 L/R 150 ms 24 V DC, 1 A
(500 Ops./h)
Operations200000
Breaking capacity
AC−15, 250 V AC, 3 A (600 Ops./h)Operations300000
DC−13 L/R 150 ms 24 V DC, 1 A
(500 Ops./h)
Operations200000
Filament bulb load
1000 W at 230/240 V ACOperations25000
500 W at 115/120 V ACOperations25000
Fluorescent lamp load
Fluorescent lamp load 10 × 58 W at
230/240 V AC
With upstream electrical deviceOperations25000
UncompensatedOperations25000
Fluorescent lamp load 1 × 58 W at
230/240 V AC, conventional,
Operations25000
compensated
Switching frequency
Mechanical operations× 10610
Switching frequencyHz10
Resistive load/lamp loadHz2
Inductive loadHz0,5
UL/CSA
Uninterrupted current at 240 V ACA10
Uninterrupted current at 24 V DCA8
AC
Control Circuit Rating CodesB 300 Light Pilot Duty