Air dischargekV8
Contact dischargekV6
Electromagnetic fields (IEC/EN
61000−4−3, RFI)
Radio interference suppression (EN
55011)
V/m10
EN 55011 Class B, EN
55022 Class B
Burst pulses (IEC/EN 61000−4−4,
level 3)
Supply cableskV2
Signal lineskV2
High−energy pulses (surge) (IEC/EN
61000−4−5)
High−energy pulses (surge) (IEC/EN
61000−4−5, level 2)
Immunity to line−conducted
interference to (IEC/EN 61000−4−6)
kV
kV
2 (supply cables,
symmetrical, EASY...AC)
0.5 (supply cables,
symmetrical, EASY...DC)
V10
Insulation resistance
Clearance in air and creepage
distances
EN 50178, UL 508, CSA
C22.2, no. 142
Insulation resistanceEN 50178
Backup/accuracy of the real−time clock
Accuracy of the real−time clockNormally ± 5 (± 0.5 hyear)
Repetition accuracy of timing relays
Accuracy of timing relays (of values)%± 1
Resolution
Range “S”ms10
Range “M:S”s1
Range “H:M”min1
Retentive memory
Write cycles of the retentive memory1000000 (106)
Power supply
Rated operational voltageU
e
V24 V AC
Admissible rangeV AC20,4 – 26,4
FrequencyHz5060 (± 5%)
Input current
3
Page 4
At 24 V AC 50/60 HzmA300
Voltage dips (IEC/EN 61131−2)ms20
Power loss
At 24 V ACVA7
Digital inputs 24 V DC
Number12
Inputs can be used as analog inputsI7, I8, I11, I12
Status indicationLCD−display (if present)
Potential isolation
From power supplyNo
Between digital inputsNo
From the outputsYes
Rated operational voltageU
e
V24 V AC
Rated voltage L (sinusoidal)
On 0 signalV AC0 – 6
(I7, I8, I11, I12) > 7 AC, > 9.5
On 1 signalU
e
V
DC (I1 − I6, I9, I10) 14 – 26.4
AC
Rated frequencyHz50 – 60
Input current on 1 signal
I1 to I6mA4 (at 24 V AC, 50 Hz)
I7, I8mA
2 (at 24 V AC, 50 Hz) 2 (at
24 V DC)
I9, I10mA4 (at 24 V AC, 50 Hz)
I11, I12mA
2 (at 24 V AC, 50 Hz) 2 (at
24 V DC)
Delay time (0 – 1/1 – 0) I1 − I12
Debounce ON 50/60 Hzms8066
Debounce OFF 50/60 Hzms2016
Max. admissible cable length (per
input)
Maximum cable length between
stripped ends
m40
I9, I10mNormally 40
Analog inputs
Quantity4 (I7, I8, I11, I12)
Potential isolation
From power supplyNo
From the digital inputsNo
From the outputsYes
4
Page 5
From the PC interface, memory card
NET network, EASY−Link
No
Input typeDC voltage
Signal rangeV DC0 – 10
Resolution, analogV0,01
Resolution, digitalV0,01
Resolution, digitalBit10 (value 0 – 1023)
Input impedancek11,2
Accuracy of actual value
Two EASY devices%± 3
Within a single device%± 2, ± 0.12 V
Debounce ON: 20;
Conversion time, analog/digitalms
Debounce OFF: every cycle
time
Input currentmA< 1
Cable length screenedm< 30
Relay outputs
Number6
Outputs in groups of1
Parallel switching of outputs for
increased output
Protection of an output relay
Not permissible
Miniature circuit−breaker B16
or fuse 8 A (slow)
Potential isolation
From power supplyYes
From the inputsYes
From the PC interface, memory card
NET network, EASY−Link
No
Safe isolationV AC300
Basic insulationV AC600
Lifespan, mechanicalOperations× 10610
Contacts
Conventional thermal current (10 A
UL)
Recommended for load: 12 V
AC/DC
A8
mA> 500
Short−circuit−proof cos = 1,
characteristic B16 at 600 A
Short−circuit−proof cos = 0.5 to 0.7,
characteristic B16 at 900 A
A16
A16
Rated impulse withstand voltagekV6
5
Page 6
U
of contact coil
imp
Rated operational voltageU
Rated insulation voltageU
Safe isolation to EN 50178 between
coil and contact
e
i
V AC250
V AC250
V AC300
Safe isolation to EN 50178 between
2 contacts
V AC300
Making capacity
AC−15, 250 V AC, 3 A (600 Ops./h)Operations300000
DC−13 L/R 150 ms 24 V DC, 1 A
(500 Ops./h)
Operations200000
Breaking capacity
AC−15, 250 V AC, 3 A (600 Ops./h)Operations300000
DC−13 L/R 150 ms 24 V DC, 1 A
(500 Ops./h)
Operations200000
Filament bulb load
1000 W at 230/240 V ACOperations25000
500 W at 115/120 V ACOperations25000
Fluorescent lamp load
Fluorescent lamp load 10 × 58 W at
230/240 V AC
With upstream electrical deviceOperations25000
UncompensatedOperations25000
Fluorescent lamp load 1 × 58 W at
230/240 V AC, conventional,
Operations25000
compensated
Switching frequency
Mechanical operations× 10610
Switching frequencyHz10
Resistive load/lamp loadHz2
Inductive loadHz0,5
UL/CSA
Uninterrupted current at 240 V ACA10
Uninterrupted current at 24 V DCA8
AC
Control Circuit Rating Codes
(utilization category)
B 300 Light Pilot Duty
Max. rated operational voltageV AC300
Max. thermal uninterrupted current
= 1 at B 300
A5
VA3600360
6
Page 7
Max. make/break capacity 1 at B
300
DC
Control Circuit Rating Codes
(utilization category)
R 300 Light Pilot Duty
Max. rated operational voltageV DC300
Max. thermal uninterrupted current
at R 300
A1
Max. make/break capacity at R 300VA2828
Notes
Dimensions
Notes
For additional Technical Data EASY5... and EASY7... AWB2528−1508GB,