Datasheet EASY512-DC-TC Datasheet (MOELLER)

Page 1
Type: EASY512−DC−TC Article No.: 274111
Ordering information
Power supply V DC 24 V DC
Description
8 digital inputs (2 inputs available as analog inputs) 4 transistor outputs LCD display Operating buttons Screw terminals Timer
Notes concerning the product group
Backup of real−time clock (only for appropriate devices)
1
Page 2
Operating time (years)
General
EN 55011, EN 55022,
Standards
IEC/EN 61000−4, IEC 60068−2−6, IEC
60068−2−27 Dimensions (W × H × D) mm 71.5 × 90 × 58 (4 PE) Weight kg 0,2
Top−hat rail IEC/EN 60715, Mounting
35 mm or screw fixing using
fixing brackets
ZB4−101−GF1 (accessories)
Terminal capacities
Solid mm Flexible with ferrule mm
2
0.24 (AWG 22 – 12)
2
0.22.5 (AWG 22 – 12) Standard screwdriver mm 3.5 × 0.8 Max. tightening torque Nm 0,6
Climatic environmental conditions
−25 to 55, cold as per IEC Operating ambient temperature °C
60068−2−1, heat as per IEC 60068−2−2
Condensation
Take appropriate measures
to prevent condensation LCD display (clearly legible) °C 055 Storage °C −40/+70 Relative humidity, non−condensing
(IEC/EN 60068−2−30)
% 5 – 95
Air pressure (operation) hPa 795 – 1080 Corrosion resistance
IEC/EN 60068−2−42
IEC/EN 60068−2−43
4 days
SO
2
4 days
H2S
cm3/m
cm3/m
3
10
3
1
Ambient conditions, mechanical
Pollution degree 2 Degree of protection (IEC/EN
60529)
IP 20
Vibrations (IEC/EN 60068−2−6) Constant amplitude 0.15 mm Hz 10 – 57 Constant acceleration 2 g Hz 57 – 150 Mechanical shock resistance
Impacts 18
(IEC/EN 60068−2−27)
2
Page 3
semi−sinusoidal 15 g/11 ms
Drop to IEC/EN 60068−2−31
Free fall, packaged (IEC/EN 60068−2−32)
Drop
height
mm 50
m 1
Mounting position horizontal/vertical
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN 61000−4−2, Level 3, ESD)
Air discharge kV 8 Contact discharge kV 6 Electromagnetic fields (IEC/EN
61000−4−3, RFI) Radio interference suppression (EN
55011)
V/m 10
EN 55011 Class B, EN
55022 Class B Burst pulses (IEC/EN 61000−4−4,
level 3) Supply cables kV 2 Signal lines kV 2 High−energy pulses (surge)
(IEC/EN 61000−4−5) High−energy pulses (surge)
(IEC/EN 61000−4−5, level 2)
kV
kV
2 (supply cables,
symmetrical, EASY...AC)
0.5 (supply cables,
symmetrical, EASY...DC) Immunity to line−conducted
interference to (IEC/EN
V 10
61000−4−6)
Insulation resistance
Clearance in air and creepage distances
EN 50178, UL 508, CSA
C22.2, no. 142 Insulation resistance EN 50178
Backup/accuracy of the real−time clock
Accuracy of the real−time clock typ. ± 5 (± 0.5 hannually)
Repetition accuracy of timing relays
Accuracy of timing relays (of values)
% ± 1
Resolution Range “S” ms 10 Range “M:S” s 1 Range “H:M” min 1
Retentive memory
Write cycles of the retentive memory
3
1000000 (106)
Page 4
Power supply
Rated operational voltage U
e
V 24 DC (−15/+20%) Admissible range V DC 20,4 – 28,8 Residual ripple % 5 Input current Input current 115/230 V AC mA Normally 80 Voltage dips (IEC/EN 61131−2) ms 10 Heat dissipation W Normally 2
Digital inputs 24 V DC
Number 8 Inputs can be used as analog
inputs
2 (I7, I8)
Status indication LCD−display (if present) Potential isolation From power supply No Between digital inputs No From the outputs Yes Rated operational voltage U On 0 signal U On 1 signal U
e
e
e
V DC 24 V DC < 5 (I1 – I8)
V DC > 15 (I1 – I6), > 8 (I7, I8) Input current on 1 signal I1 to I6 mA 3.3 (at 24 V DC) I7, I8 mA 2.2 (at 24 V DC) Delay time from 0 to 1 Debounce ON ms 20 Debounce OFF ms Normally 0.25 (I1 – I8) Delay time from 1 to 0 Debounce ON ms 20 Cable length (unscreened) m 100 Frequency counter Quantity 2 (I3, I4) Counter frequency kHz < 1 Pulse shape Square Pulse pause ratio 1:1 Rapid counter inputs Number 2 (I1, I2) Counter frequency kHz < 1 Pulse shape Square Pulse pause ratio 1:1
4
Page 5
Analog inputs
Quantity 2 (I7, I8) Potential isolation From power supply No From the digital inputs No From the outputs Yes From the PC interface, memory
card NET network, EASY−Link
No
Input type DC voltage Signal range V DC 0 – 10 Resolution, analog V 0,01 Resolution, digital V 0,01 Resolution, digital Bit 10 (value 1 – 1023) Input impedance k 11,2 Accuracy of actual value Two EASY devices % ± 3 Within a single device % ± 2, ± 0.12 V
Debounce ON: 20;
Conversion time, analog/digital ms
Debounce OFF: every cycle
time Input current mA < 1 Cable length screened m < 30
Transistor outputs
Number 4 Rated operational voltage U Admissible range U
e
e
V DC 24
V DC 20,4 – 28,8 Residual ripple % 5 Supply current On 0 signal Normallymax. mA 916 On 1 signal Normallymax. mA 1222
Yes (Attention: A short−circuit will occur if
Protection against polarity reversal
voltage is applied to the outputs on account of
reverse polarity.) Potential isolation From power supply Yes Potential isolation Yes Rated operational current on 1
signal DC
I
e
A Max. 0.5
5
Page 6
Lamp load without R
v
Residual current on 0 signal per channel
Max. output voltage
W 5
mA < 0,1
On 0 signal with external load < 10 M
V 2,5
On 1 signal with Ie = 0.5 A V U = Ue −1 V
Yes, thermal (analysis via Short−circuit protection
diagnostics input I16, I15;
R15, R16) Short−circuit tripping current for R
10 m
a
A 0.7 Ie 2 per output
Total short−circuit current A 8 Peak short−circuit current A 16 Thermal cutout Yes Max. operating frequency with
constant resistive load RL < 100 k (depending on number of active
Ops./h 40000
channels and their load) Parallel connection of outputs With resistive load, inductive load
with external suppressor circuit,
Group 1: Q1 to Q4 combination within a group
Number of outputs max. 4
2 (Caution! Outputs must be Max. total current
actuated simultaneously and
for the same length of time.) Output status indication LCD−display (if present) Inductive load Without external suppressor circuit
T
0.95 = 1 ms, R = 48 , L = 16 mH
Utilization factor g 0,25 Duty factor % DF 100 Max. switching frequency f = 0.5 Hz
(max. DF = 50 %) DC−13,
T0.95 = 72 ms, R = 48 , L = 1.15 H
Operations 1500
Utilization factor g 0,25 Duty factor % DF 100 Max. switching frequency f = 0.5 Hz
(max. DF = 50 %)
T
0.95 = 15 ms, R = 48 , L = 0.24 H
Operations 1500
Utilization factor g 0,25
6
Page 7
Duty factor % DF 100 Max. switching frequency f = 0.5 Hz
(max. DF = 50 %)
Operations 1500
With external suppressor circuit Utilization factor g 1 Duty factor % DF 100 Max. switching frequency, max.
duty factor
Operations
Depending on the
suppressor circuit
Analog outputs
Potential isolation From power supply No From the digital inputs No Signal range V DC 0 – 10
Debounce ON: 20; Conversion time, analog/digital ms
Debounce OFF: every cycle
time
Notes Dimensions
Notes
For additional Technical Data EASY5... and EASY7... AWB2528−1508GB,
EASY8... AWB2528−1423D
Notes
For inductive loading, without external suppression of the transistor outputs, the following applies:
T
= time in ms, until 95 % of the steady−state current is achieved. T
0.95
0.95
3 × T
= 3 × L/R.
0.65
Data transfer rate in the NET network: bus lengths of 40 m and over only attainable with cables with additional cross−section and connection adapter.
Dimensions
7
Page 8
Moeller GmbH, Hein−Moeller−Str. 7−11, D−53115 Bonn E−Mail: catalog@moeller.net, Internet: www.moeller.net, http://catalog.moeller.net Copyright 2006 by Moeller GmbH. Subject to modifications. HPL−C2006GB−INT V2.3
8
Loading...