Datasheet E2K-F Datasheet (OMRON)

Flat Proximity Sensor
E2K-F
Saves Installation Space with a Thickness of Only 10 mm
Flat, Built-in Amplifier Models offer excellent space efficiency and provide a 10-mm sensing distance.
Detects both metallic and nonmetallic objects (water, oil, glass, plastic, etc.).
Be sure to read Safety Precautions on page 3.
Ordering Information
Appearance Sensing distance Output configuration
Flat Unshielded
10 mm
4 to 10 mm
DC 3-wire
NPN
Model/Operation mode
NO NC
E2K-F10MC1 E2K-F10MC2
E2K-F10MC1-A E2K-F10MC2-A
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
1
Ratings and Specifications
)
)
Item Model E2K-F10MC@-A E2K-F10MC@
Sensing distance 4 to 10 mm (adjustable with 12-turn adjuster) 10 mm r10%
Set distance 0 to 7.5 mm *
Differential travel 15% max. of sensing distance
Detectable object Conductors and dielectrics
Standard sensing object Grounded metal plate: 50 u 50 u 1 mm
Response frequency 100 Hz
Power supply voltage (operating voltage range)
Current consumption 10 mA max. at 24 VDC
Control output
Load current NPN open collector, 100 mA max. (at 30 VDC)
Residual voltage 1.5 V max. (Load current: 100 mA, Cable length: 2 m)
Indicators Detection indicator (red)
Operation mode (with sensing object approaching)
Protection circuits Reverse polarity protection, Surge suppressor
Ambient temperature range Operating/Storage: 10 to 55qC (with no icing or condensation)
Ambient humidity range Operating/Storage: 35% to 95% Operating/Storage: 35% to 95%
Temperature influence r15% max. of sensing distance at 23qC in the temperature range of 10 to 55qC
Voltage influence r2.5% max. of sensing distance at rated voltage at rated voltage r10%
Insulation resistance 50 M: min. (at 500 VDC) between current-carrying parts and case
Dielectric strength 500 VAC, 50/60 Hz for 1 min between current-carrying parts and case
Vibration resistance Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Shock resistance Destruction: 500 m/s2 3 times each in X, Y, and Z directions
Degree of protection IP64 (IEC) IP66 (IEC)
Connection method Pre-wired Models (Standard cable length: 2 m)
Weight (packed state) Approx. 35 g
Materials
Case
Sensing surface
Accessories Instruction manual
* The value for the E2K-F10MC@-A is when it is adjusted to 10 mm.
12 to 24 VDC (10 to 30 VDC), ripple (p-p): 10% max.
NO (Refer to the timing charts under I/O Circuit Diagrams on page 3 for details.)
Heat-resistant ABS
E2K-F
Engineering Data (Typical)
Sensing Area (Grounded Metal Plate) Influence of Sensing Object Size and
Material
201612840−4−8
10
9
8
Distance (mm)
7
6
5
4
3
2
1
100
Grounded metal plate (t = 1)
Non-grounded metal plate (t = 10)
Glass (t = 10)
Side length of sensing object (mm
Phenol (t = 10)
80706050403020
12
11
10
9
Distance X (mm)
8
7
6
5
4
3
2
1
12−16−20
Sensing Head
Left and
right
Distance Y (mm
12
11
Y
X
201612840−4−8
10
9
Distance X (mm)
8
7
6
5
4
3
2
1
12−16−20
Sensing Head
Up and
down
Y
X
Distance Y
(mm)
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
2
I/O Circuit Diagrams
V
Present
Not present
Timing chart
Sensing object
Output transistor (load)
Detection indicator (red)
E2K-F
NO Models NC Models
ON
OFF
ON
OFF
Output circuit
100 Ω
Proximity
Sensor
main
circuit
* Load current: 100 mA max.
Brown
Black
Output
Blue
+V
Load
*
0
Safety Precautions
Refer to Warranty and Limitations of Liability.
WARNING
This product is not designed or rated for ensuring safety of persons either directly or indirectly. Do not use it for such purposes.
Precautions for Correct Use
Do not use this product under ambient conditions that exceed the ratings.
Design
Sensing Object Material
The E2K-F can detect almost any type of object. The sensing distance of the E2K-F, however, will vary with the electrical characteristics of the object, such as the conductance and inductance of the object, and the water content and capacity of the object. The maximum sensing distance of the E2K-F will be obtained if the object is made of grounded metal. There are objects that cannot be detected indirectly. Therefore, be sure to test the E2K-F in a trial operation with the objects before using the E2K-F in actual applications.
Influence of Surrounding Metal
Separate the E2K-F from surrounding metal as shown below.
Mutual Interference
When mounting more than one E2K-F face-to-face or side-by-side, separate them as shown below.
40 mm
50 mm
Close mounting possible Face-to-face mounting
50 mm
Effects of a High-frequency Electromagnetic Field
The E2K-F may malfunction if there is an ultrasonic washer, high­frequency generator, transceiver, portable telephone, or inverter nearby. For major measures, refer to Noise of Warranty and Limitations of Liability for Photoelectric Sensors.
Wiring
The characteristics of the E2K-F will not change if the cable is extended. Extending the cable, however, will result in a voltage drop, so do not extend the length past 200 m.
Metal object
45 mm60 mm
Metal object
http://www.ia.omron.com/
Metal object
30 mm
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
3
E2K-F
Dimensions (Unit: mm)
E2K-F
Two, 3.5 dia.
2
,
344250
Sensitivity adjuster *1
Detection indicator (red)
55
10.1
*1. Only the E2K-F10MC@-A has a sensitivity adjuster. *2. 2.9-dia. vinyl-insulated round cable
(Conductor cross section: 0.14 mm Insulator diameter: 0.9 mm), Standard length: 2 m.
20 5
Mounting Hole Dimensions
Two, M3 or 3.5 dia.
*2
42±0.2
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
4
Operating Procedures: Proximity Sensors
E2K-F
Sensitivity Adjustment
After the Sensor is mounted, adjust the detecting sensitivity using the (12-turn) sensitivity adjuster in the way shown below.
Status of the indicator when the liquid level is aligned with the setting position
Not lit
Lit
Note: While adjusting the sensitivity, do not put your hand on the Sensor and make sure that the cable is properly secured. Failure to observe these points may affect
the detection level.
Sensitivity adjuster Adjustment procedure
1
Turn the sensitivity adjuster counter-clockwise using a screwdriver until the indicator lights.
2
1
Turn the sensitivity adjuster clockwise using a screwdriver until the indicator turns OFF. Then, turn the sensitivity adjuster counter-clockwise until the indicator lights again.
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
5
Proximity Sensors Technical Guide
General Precautions
For precautions on individual products, refer to the Safety Precautions in individual product information.
WARNING
These products cannot be used in safety devices for presses or other safety devices used to protect human life. These products are designed for use in applications for sensing workpieces and workers that do not affect safety.
Precautions for Safe Use
To ensure safety, always observe the following precautions.
Wiring Considerations
Item Typical examples
Power Supply Voltage
Do not use a voltage that exceeds the operat­ing voltage range. Applying a voltage that is higher than the operating voltage range, or us­ing an AC power supply (100 VAC or higher) for a Sensor that requires a DC power supply may cause explosion or burning.
Load short-circuiting
Do not short-circuit the load. Explosion or burning may result.
The load short-circuit protection function op­erates when the power supply is connected with the correct polarity and the power is within the rated voltage range.
DC 3-Wire NPN Output Sensors DC 2-Wire Sensors
Brown
Sensor
Blue
DC 3-Wire NPN Output Sensors DC 2-Wire Sensors
Brown
Sensor
Blue
Black
Black
Load
Load
(Load short circuit)
Load
Brown
Sensor
Blue
Even with the load short-circuit protection function, protection will not be provided when a load short circuit occurs if the power supply polarity is not correct.
Load
(Load short circuit)
+
Brown
Sensor
+
Blue
Incorrect Wiring
Be sure that the power supply polarity and oth­er wiring is correct. Incorrect wiring may cause explosion or burning.
Connection without a Load
If the power supply is connected directly with­out a load, the internal elements may explode or burn. Be sure to insert a load when connect­ing the power supply.
DC 3-Wire NPN Output Sensors
Load
Brown
Sensor
Black
Blue
+
DC 2-Wire Sensors
Even with the load short-circuit protection
function, protection will not be provided if both the power supply polarity is incorrect and no load is connected.
Brown
Sensor
Blue
+
Operating Environment
Do not use the Sensor in an environment where there are explosive or combustible gases.
Brown
Sensor
Black
AC 2-Wire Sensors
Brown
Sensor
Blue
Load
+
Blue
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
C-1
Proximity Sensors Technical Guide
S
r
r
Precautions for Correct Use
The following conditions must be considered to understand the conditions of the application and location as well as the relation to control equipment.
Model Selection
Item Points of consideration
Check the relation between the sensing object and the Proximity Sensor.
pecific condi-
tions of object
Direction of ob­ject movement
Peripheral metalSensing distance
Sensing object and operating condition of Proximity Sensor
Electrical conditions
Environ­mental conditions
Sensing object
Sensing distance
Surrounding
metals
Proximity Sensor
Verify the electrical conditions of the control system to be used and the electrical performance of the Proximity Sensor.
Output
Sensor
Proximity
Switching element
The environmental tolerance of the Proximity Sensor is better than that of other types of Sensors. However, investigate carefully before using a Proximity Sensor under harsh temperatures or in special atmospheres.
Temperature and humidity
Atmosphere Water, oil, iron
Vibration and shock
Load
Highest or lowest values, existence of direct sunlight, etc.
powder, or other special chemicals
Size, duration Need for strength,
When deciding the mounting method, take into consideration not only restrictions due to mechanical devices, but also ease of main­tenance and inspection, and interference between Sensors.
Material, size, shape, existence of plating, etc.
Sensing (set) distance, shape of Sensor (rectangular, cylindrical, through­beam, grooved), influence of peripheral metal (Shielded Sensors, Non­shielded Sensors), response speed (response frequency), influence of temperature, influence of voltage, etc.
DC (voltage fluctuation, current ca­pacity value) AC (voltage fluctuation, frequency, etc.) Need for S3D2 Controller
Resistive load - Non-contact control system Inductive load - Relay, solenoid, etc.
Lamp load
Open/close frequency
Temperature influence, high-temperature use, low temperature use, need for shade, etc.
N
e
r
o
d
e
f
a
t
r
o
e
c
n
e
n
r
o
d
e
f
r
p
r
t
s
f
o
o
mounting method
Power
supply
Power supply
Load
Transit interval, speed, existence of vibration, etc.
Steady-state current, inrush current
Operating, reset voltage (current)
Steady-state current, inrush current
Water Resistance
Do not use the Sensor in water, rain, or outdoors.
Ambient Conditions To maintain reliability of operation, do not use the Sensor outside the specified temperature range or outdoors. Even though the Proximity Sensor has a water-resistant structure, it must be covered to pre­vent direct contact with water or water-soluble cutting oil. Do not use the Sensor in atmospheres with chem-
s
e
r
e
r
w
t
a
is
-
ical vapors, in particular, strong alkalis or acids (nitric
a
t
s
i
s
e
il
o
r
lo
p
x
e
e
r
u
t
c
u
,
e
c
n
acid, chromic acid, or hot concentrated sulfuric acid).
n
o
i
s
-
Explosive Atmospheres Do not use the Sensor in atmospheres where there is a danger of explosion. Use an Explosion­proof Sensor.
Material, distance to Sensor, orien­tation, etc.
Fluctuation in tran­sit point, allowable error, etc.
Selecting the power supply type
DC DC + S3D2 Controlle
{
AC
Selecting the power supply type
DC DC + S3D2 Controlle
{
AC
Control output
Maximum current
(voltage) Leakage current Residual load voltage
Mounting conditions
Influence of external electromag­netic fields
Other con­siderations
* mT (millitesla) is a unit for expressing magnetic flux density. One tesla is the equivalent of 10,000 gauss.
The influence within a DC magnetic field is 20 mT* max. Do not use the Sensor at a level higher than 20 mT.
Sudden changes in the DC magnetic field may cause malfunction. Do not use the Sensor for applications that involve turning a
DC electromagnet ON and OFF.
Do not place a transceiver near the Sensor or its wiring. Doing so may cause malfunction.
Cost feasibility: Price/delivery time Life: Power-ON time/frequency of use
http://www.ia.omron.com/
Wiring method, existence of in­ductance surges
Connection
Wires Wire type, length, oil-resistant cable, shielded cable, robot cable, etc.
Conduits, ducts, pre-wired, terminal wiring, ease of main­tenance and inspection
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
Mounting procedure
Installation location
Existence of mounting brackets, direct mounting, secured with bolts or screws
Ease of maintenance and inspection, mounting space
C-2
Design
Sensing Object Material
The sensing distance varies greatly depending on the material of the sensing object. Study the engineering data for the influence of sensing object material and size and select a distance with sufficient leeway.
In general, if the sensing object is a non­magnetic metal (for example, aluminum), the sensing distance decreases.
Example: E2-X10D@
14
12
10
8
6
Sensing distance X (mm)
4
2
05
Side length (one side) of sensing object: d (mm)
t=1mm
X
d
Aluminum
10 15 20 25 30 35 40 45 50 55
Steel
(SPCC)
Stainless steel
Brass
Copper
Size of Sensing Object
In general, if the object is smaller than the standard sensing object, the sensing distance decreases.
Design the setup for an object size that is the same or greater than the standard sensing object size from the graphs showing the sensing object size and sensing distance.
When the size of the standard sensing object is the same or less than the size of the standard sensing object, select a sensing distance with sufficient leeway.
Sensing distance X (mm)
Sensing distance becomes short
Side length (one side) of sensing object: d (mm)
Standard
Stability
sensing object
Proximity Sensors Technical Guide
Thickness of Sensing Object
The thickness of ferrous metals (iron, nickel, etc.) must be 1 mm or greater.
When the coating thickness is
0.01 mm or less, a sensing distance equivalent to a magnetic body can be obtained. When the coating is extremely thin and is not conductive, such as a vacuum deposited film, detection is not possible.
Influence of Plating
If the sensing object is plated, the sensing distance will change (see the table below).
Effect of Plating (Typical) (Reference values: Percent of non-plated sensing distance)
Thickness and base material of plating
No plating 100 100
Zn 5 to 15 μm 90 to 120 95 to 105
Cd 5 to 15 μm 100 to 110 95 to 105
Ag 5 to 15 μm 60 to 90 85 to 100
Cu 10 to 20 μm 70 to 95 95 to 105
Cu 5 to 15 μm - 95 to 105
Cu (5 to 10 μm) + Ni (10 to 20 μm) 70 to 95 -
Cu (5 to 10 μm) + Ni (10 μm) + Cr (0.3 μm)
Mutual Interference
Mutual interference refers to a state where a Sensor is affected by magnetism (or static capacitance) from an adjacent Sensor and the output is unstable.
One means of avoiding interference when mounting Proximity Sensors close together is to alternate Sensors with different frequencies. The model tables indicate whether different frequencies are available. Please refer to the tables.
When Proximity Sensors with the same frequency are mounted together in a line or face-to-face, they must be separated by a minimum distance. For details, refer to Mutual Interference in the Safety Precautions for individual Sensors.
Sensing object shape: Square
10
8
6
4
Sensing distance X (mm)
2
0 0.01 0.1 1 10
Thickness of sensing object: t (mm)
Aluminum
Steel Brass
75 to 95 -
d=30mm
Reset Operate
Steel
http://www.ia.omron.com/
Power Reset Time
A Sensor is ready for detection within 100 ms after turning ON the power. If the load and Sensor are connected to separate power supplies, design the system so that the Sensor power turns ON first.
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
C-3
Proximity Sensors Technical Guide
Turning OFF the Power
An output pulse may be generated when the power is turned OFF, so design the system so that the load or load line power turns OFF first.
Influence of Surrounding Metal
The existence of a metal object other than the sensing object near the sensing surface of the Proximity Sensor will affect detection perfor­mance, increase the apparent operating distance, degrade tempera­ture characteristics, and cause reset failures. For details, refer to the influence of surrounding metal table in Safety Precautions for individ- ual Sensors. The values in the table are for the nuts provided with the Sensors. Changing the nut material will change the influence of the surrounding metal.
Power Transformers
Be sure to use an insulated transformer for a DC power supply. Do not use an auto-transformer (single-coil transformer).
Precautions for AC 2-Wire/DC 2-Wire Sensors
Surge Protection
Although the Proximity Sensor has a surge absorption circuit, if there is a device (motor, welder, etc.) that causes large surges near the Proximity Sensor, insert a surge absorber near the source of the surges.
Influence of Leakage Current
Even when the Proximity Sensor is OFF, a small amount of current runs through the circuit as leakage current. For this reason, a small current may remain in the load (residual voltage in the load) and cause load reset failures. Verify that this voltage is lower than the load reset voltage (the leakage current is less than the load reset current) before using the Sensor.
Using an Electronic Device as the Load for an AC 2-Wire Sensor
When using an electronic device, such as a Timer, some types of devices use AC half-wave rectification. When a Proximity Sensor is connected to a device using AC half-wave rectification, only AC half­wave power will be supplied to the Sensor. This will cause the Sensor operation to be unstable. Also, do not use a Proximity Sensor to turn the power supply ON and OFF for electronic devices that use DC half­wave rectification. In such a case, use a relay to turn the power supply ON and OFF, and check the system for operating stability after connecting it.
Examples of Timers that Use AC Half-wave Rectification Timers: H3Y, H3YN, H3RN, H3CA-8, RD2P, and H3CR (-A, -A8, -AP,
-F, -G)
Countermeasures for Leakage Current (Examples)
AC 2-Wire Sensors
Connect a bleeder resistor to bypass the leakage current flowing in the load so that the current flowing through the load is less than the load reset current.
When using an AC 2-Wire Sensor, connect a bleeder resistor so that the Proximity Sensor current is at least 10 mA, and the residual load voltage when the Proximity Sensor is OFF is less than the load reset voltage.
Load
AC power supply
Bleeder resistor R
Calculate the bleeder resistance and allowable power using the following equation.
Vs
R
P : Watts of bleeder resistance (the actual number of watts
I : Load current (mA)
It is recommend that leeway be included in the actual values used. For 100 VAC, use 10 kΩ or less and 3 W (5 W) or higher, and for 200 VAC, use 20 kΩ or less and 10 W (20 W) or higher. If the effects of heat generation are a problem, use the number of watts in parentheses ( ) or higher.
(kΩ)P >
10 - I R
used should be several times this number)
Vs
2
voltage Vs
(mW)
DC 2-Wire Sensors
Connect a bleeder resistor to bypass the leakage current flowing in the load, and design the load current so that (leakage current) × (load input impedance) < reset voltage.
Load
Bleeder resistor R
Calculate the bleeder resistance and allowable power using the following equation.
R
It is recommend that leeway be included in the actual values used. For 12 VDC, use 15 kΩ or less and 450 mW or higher, and for 24 VDC, use 30 kΩ or less and 0.1 W or higher.
Vs
i
R - iOFFR R
P : Watts of bleeder resistance (the actual number of watts
R : Leakage current of Proximity Sensor (mA)
i
OFF : Load reset current (mA)
i
(kΩ) P >
used should be several times this number)
Vs
2
(mW)
Vs
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
C-4
Proximity Sensors Technical Guide
Loads with Large Inrush Current
Loads, such as lamps or motors, that cause a large inrush current* will weaken or damage the switching element. In this situation, use a relay.
*E2K, TL-N@Y: 1 A or higher
Mounting
Mounting the Sensor
When mounting a Sensor, do not tap it with a hammer or otherwise subject it to excessive shock. This will weaken water resistance and may damage the Sensor. If the Sensor is being secured with bolts, observe the allowable tightening torque. Some models require the use of toothed washers. For details, refer to the mounting precautions in Precautions for Correct Use in individual product information.
Mounting/Removing Using DIN Track
(Example for E2CY)
<Mounting>
(1)Insert the front of the Sensor into the special Mounting Bracket
(included) or DIN Track.
(2)Press the rear of the Sensor into the special Mounting Bracket or
DIN Track.
Rear
Front
<Removing>
While pressing the Amplifier Unit in the direction of (3), lift the fiber plug in the direction of (4) for easy removal without a screwdriver.
(4)
DIN Track
(3)
Set Distance
The sensing distance may vary due to fluctuations in temperature and voltage. When mounting the Sensor, it is recommend that installation be based on the set distance.
(2)
(1)
DIN Track (or Mounting Bracket)
When mounting the side of the Sensor using the special Mounting Bracket, first secure the Amplifier Unit to the special Mounting Bracket, and then mount the special Mounting Bracket with M3 screws and flat washers with a diameter of 6 mm maximum.
Flat washers (6 dia. max.)
Mounting track (yellow)
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
C-5
Wiring Considerations
AND/OR Connections for Proximity Sensors
Model
DC 2-Wire
Type of
connection
AND (series connection)
OR (parallel connection)
Connection Description
+
-
+
-
+
-
+
Load
Load
Load
Proximity Sensors Technical Guide
Keep the number of connected Sensors (N) within the range of the following equation. V
S - N × VR ≥ Operating load voltage
N : Number of Sensors that can be connected
R: Residual output voltage of Proximity Sensor
Vs
Vs
V
S
V
S: Power voltage
V
It is possible, however, that the indicators may not light correctly and error pulses (of approximately 1 ms) may be generated because the rated power supply voltage and current are not supplied to individual Proximity Sensors. Verify that this is not a problem before operation.
Keep the number of connected Sensors (N) within the range of the following equation. N × i Load reset current
N: Number of Sensors that can be connected i: Leakage current of Proximity Sensor
Example: When an MY (24-VDC) Relay is used as the load, the maximum number of Sensors that can be connected is 4.
<TL-NY, TL-MY, E2K-@MY@, TL-T@Y> The above Proximity Sensors cannot be used in a sereis connection. If need­ed, connect through relays.
Load
X
Load
V
2
X
1
X
2
L
VS≥ 100V
AND (series connection)
X
1
AC 2-wire
(A)
(B)
Load
OR (parallel connection)
(A)
Note: When AND/OR connections are used with Proximity Sensors, the effects of erroneous pulses or leakage current may prevent use. Verify that there are no
problems before use.
(B)
1
X
Load
X2
X1
X2
<E2E-X@Y> For the above Proximity Sensors, the voltage VL that can be applied to the load when ON is V
V
S
both 100 VAC and 200 VAC. The load will not operate unless V This must be verified before use. When using two or more Sensors in series with an AND circuit, the limit is three Sensors. (Be careful of the VS value in the diagram at left.)
V
S
In general it is not possible to use two or more Proximity Sensors in parallel with an OR circuit.
A parallel connection can be used if A and B will not be operated simulta­neously and there is no need to hold the load. The leakage current, however, will be n times the value for each Sensor and reset failures will frequently oc­cur. ("n" is the number of Proximity Sensors.)
If A and B will be operated simultaneously and the load is held, a parallel con­nection is not possible. If A and B operate simultaneously and the load is held, the voltages of both A and B will fall to about 10 V when A turns ON, and the load current will flow through A causing random operation. When the sensing object approaches B, the voltage of both terminals of B is too low at 10 V and the switching element of B will not operate. When A turns OFF again, the voltages of both A and B
AC power supply
voltage Vs
rise to the power supply voltage and B is finally able to turn ON.
During this period, there are times when A and B both turn OFF (approximately 10 ms) and the loads are momentarily restored. In cases where the load is to be held in this way, use a relay as shown in the diagram at left.
L = VS - (Output residual voltage × Number of Sensors), for
L is higher than the load operating voltage.
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
C-6
Proximity Sensors Technical Guide
Model
DC 3-wire
Note: When AND/OR connections are used with Proximity Sensors, the effects of erroneous pulses or leakage current may prevent use. Verify that there are no
problems before use.
Extending Cable Length
The cable of a Built-in Amplifier Sensor can be extended to a maximum length of 200 m with each of the standard cables (excluding some models). For Separate Amplifier Sensors (E2C-EDA, E2C, E2J, E2CY), refer to the specific precautions for individual products.
Bending the Cable
If you need to bend the cable, we recommend a bend radius that is at least 3 times the outer diameter of the cable (with the exception of
Type of
connection
AND (series connection)
OR (parallel connection)
(A)
(B)
Connection Description
Keep the number of connected Sensors (N) within the range of the following equation. iL + (N - 1) × i Upper limit of Proximity Sensor control output
S - N × VR ≥ Operating load voltage
V
N : Number of Sensors that can be con-
nected
R: Residual output voltage of Sensor
V V
S: Power supply voltage
i : Current consumption of Sensor iL: Load current
Note: When an AND circuit is connected, the operation of Proximity Sensor B
causes power to be supplied to Proximity Sensor A, and thus erroneous pulses (approximately 1 ms) may be generated in A when the power is turned ON. For this reason, take care when the load has a high response speed because malfunction may result.
For Sensors with a current output, a minimum of three OR connections is pos­sible. Whether or not four or more connections is possible depends on the model.
+
+
+
­+
-
-
-
OUT
OUT
OUT
OUT
i
iL
Load
i
Load
Vs
Vs
Example of Connection with S3D2 Sensor Controller
DC 2-Wire Sensors
Using the S3D2 Sensor Controller
Operation can be reversed with the signal input switch on the S3D2.
Example: A maximum of two Sensors can be used when an MY (24-VDC) Relay is used for the load.
Blue 0 V
Brown OUT
coaxial and shielded cables).
9
11810712
Cable Tensile Strength
In general, do not subject the cable to a tension greater than that indicated in the following table.
Cable diameter Tensile strength
Less than 4 mm 30 N max.
4 mm min. 50 N max.
Note: Do not subject a shielded cable or coaxial cable to tension.
Separating High-voltage Lines
Using Metal Conduits If a power line is to be located near the Proximity Sensor cable, use a separate metal conduit to prevent malfunction or damage. (Same for DC models.)
52416
S3D2
Connecting to a Relay Load
Brown
X
Blue
Note: DC 2-Wire Sensors have a residual voltage of 3 V. Check the operating
voltage of the relay before use. The residual voltage of the E2E-XD-M1J-T is 5 V.
24 VDC
DC 3-Wire Sensors
Operation can be reversed with the signal input switch on the S3D2.
Blue 0 V Black OUT Brown +12 V
S3D2
11810712
52416
3
9
3
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
C-7
Operating Environment
Water Resistance
Do not use the Sensor in water, rain, or outdoors.
Ambient Conditions
Do not use the Sensor in the following environments. Doing so may cause malfunction or failure of the Sensor.
1. To maintain operational reliability and service life, use the Sensor only within the specified temperature range and do not use it outdoors.
2. The Sensor has a water resistant structure, however, attaching a cover to prevent direct contact with water will help improve reliability and prolong product life.
3. Avoid using the Sensor where there are chemical vapors, especially strong alkalis or acids (nitric acid, chromic acid, or hot concentrated sulfuric acid).
Maintenance and inspection
Periodic Inspection
To ensure long-term stable operation of the Proximity Sensor, inspect for the following on a regular basis. Conduct these inspections also for control devices.
1. Shifting, loosening, or deformation of the sensing object and Proximity Sensor mounting
2. Loosening, bad contact, or wire breakage in the wiring and connections
3. Adherence or accumulation of metal powder
4. Abnormal operating temperature or ambient conditions
5. Abnormal indicator flashing (on setting indicator types)
Proximity Sensors Technical Guide
Disassembly and Repair
Do not under any circumstances attempt to disassemble or repair the product.
Quick Failure Check
You can conveniently check for failures by connecting the E39-VA Handy Checker to check the operation of the Sensor.
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
C-8
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specifi ed) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the product.
At the customer's request, OMRON will provide applicable third party certifi cation documents identifying ratings and limitations of use that apply to the products. This information by itself is not suffi cient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifi cations and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when signifi cant construction changes are made.
However, some specifi cations of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fi x or establish key specifi cations for your application on your request. Please consult with your OMRON representative at any time to confi rm actual specifi cations of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
ERRORS AND OMISSIONS
The information in this catalog has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
COPYRIGHT AND COPY PERMISSION
This catalog shall not be copied for sales or promotions without permission. This catalog is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or reproducing this
catalog in any manner, for any other purpose. If copying or transmitting this catalog to another, please copy or transmit it in its entirety.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
In the interest of product improvement, specifications are subject to change without notice.
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
2007.12
Loading...