Datasheet E1YM400VS10 Specification

Page 1
Voltage monitoring in 3- and 1-phase mains
Monitoring relays - ENYA series
Multifunction
Monitoring of phase failure
Monitoring of phase sequence selectable
Connection of neutral wire optional
Width 17.5 mm
Installation design
Technical data
E1YM400VS10
1. Functions
Voltage monitoring in 3-phase and 1-phase mains with adjustable thresholdes, adjustable tripping delay, monitoring of phase sequence and phase failure and the following functions which are selected by means of rotary switch: UNDER Undervoltage monitoring UNDER+SEQ Undervoltage monitoring and monitoring of phase sequence WIN Monitoring the window between Min and Max WIN+SEQ Monitoring the window between Min and Max and monitoring of phase sequence
2. Time ranges
Adjustment range Start-up suppression time: ­Tripping delay: 0.1s 10s
3. Indicators
Red LED ON/OFF: indication of failure of the corresponding threshold Red LED flashes: indication of tripping delay of the orresponding threshold Yellow LED ON/OFF: indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40 Mounted on DIN-rail TS 35 according to EN 60715 Mounting position: any Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 Tightening torque: max. 1Nm Terminals capacity: 1 x 0.5 to 2.5mm² with/without multicore cable end 1 x 4mm² without multicore cable end 2 x 0.5 bis 1.5mm² with/without multicore cable end 2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage: (= measured voltage) Terminals: (N)-L1-L2-L3 Rated voltage UN: see table ordering information or printing on the unit Tolerance: -30% to +30% of U Rated consumption: 8VA (1W) Rated frequency: a.c. 48 bis 63Hz Duty cycle: 100% Reset time: 500ms Hold-up time: ­Drop out voltage: >20% of supply voltage Overvoltage category: III (in accordance with IEC 60664-1) Rated surge voltage: 4kV
N
6. Output circuit
1 potential free change over contact Rated voltage: 250V a.c. Switching capacity: 1250VA (5A / 250V) Fusing: 5A fast acting Mechanical life: 20 x 106 operations Electrical life: 2 x 105 operations at 1000VA resistive load Switching capacity: max. 6/min at 1000VA resistive load (in accordance with IEC 60947-5-1) Overvoltage category: III (in accordance with IEC 60664-1) Rated surge voltage: 4kV
7. Measuring circuit
Measuring variable: 3(N)~, sinus, 48 to 63Hz Measuring input: (= supply voltage) Terminals: (N)-L1-L2-L3 Overload capacity: determined by tolerance specified for supply voltage Input resistance: ­Swiching treshold US: Max: 80%...130% of U Min: 70%...120% of U Overvoltage category: III (in accordance with IEC 60664-1) Rated surge voltage: 4kV
8. Accuracy
Base accuracy: ≤5% of nominal value Adjustment accuracy: ≤5% of maximum scale value Repetition accuracy: ≤2%
Voltage influence: -
Temperature influence: ≤0,05% /
9. Ambient conditions
Ambient temperature: -25 to +55°C Storage temperature: -25 to +70°C Transport temperature: -25 to +70°C Relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) Pollution degree: 2 (in accordance with IEC 60664-1)
10. Weight
Single packing: 72g Packing of 10pcs: 670g per Package
N
N
°C
www.tele-online.com
Page 2
E1YM400VS10
LED Seq
LED U
Delay
Functions
For all functions the LED‘s Min and Max are ashing alternating (the
relay is fallen off), when the minimum value for the measured voltage was chosen to be greater than the maximum value. If a failure already exists when the device is activated, the output relay remains in off-position and the LED for the corresponding threshold is illuminated. The device includes seperately every phase voltage (L-N) and monitors it according to the selected function (UNDER or WINDOW).
Undervoltage monitoring (UNDER, UNDER+SEQ)
When the measured voltage (one of the phase voltages) falls below the value adjusted at the Min-regulator, the set interval of the tripping delay
(Delay) begins (red LED Min ashes). After the interval has expired
(red LED Min illuminated), the output relay R switches into off-position (yellow LED not illuminated). The output relay R switches into on­position again (yellow LED illuminated), when the measured voltage (all phase voltages) exceeds the value adjusted at the Max-regulator.
Phase sequence monitoring (SEQ)
Phase sequence monitoring is selectable for all functions. In single phase circuit, the phase sequence monitoring must be disconnected. If a change in phase sequence is detected (red LED SEQ illuminated), the output relay R switches into off-position after the set interval of tripping delay (Delay) has expired (yellow LED not illuminated).
Neutral wire break
The device monitors every phase (L1, L2 and L3) against the neutral wire N. A shift of neutral point occurs by an asymmetrical phase load if the neutral wire breaks in the power line. If one of the phase voltages exceeds the value adjusted at the trip point, the set interval of tripping
delay (Delay) begins (red LED Min or Max ashes). After the interval has
expired (red LED Min or Max illuminated), the output relay switches into off-position (yellow LED not illuminated).
Windowfunction (WIN, WIN+SEQ)
The output relay R switches into on-position (yellow LED illuminated), when the measured voltage (all phase voltages) exceeds the value adjusted at the Min-regulator. When the measured voltage (one of the phase voltages) exceeds the value adjusted at the Max-regulator, the
set interval of tripping delay (Delay) begins (red LED Max ashes).
After the interval has expired (red LED Max illuminated) the output relay R switches into off-position (yellow LED not illuminated). The output relay switches into on-position again (yellow LED illuminated) when the measured voltage falls below the value adjusted at the Max-regulator (red LED Max not illuminated). When the measured voltage (one of the phase voltage) falls below the value adjusted at the Min-regulator, the
set interval of tripping delay (Delay) begins again (red LED Min ashes).
After the interval has expired (red LED Min illuminated), the output relay R switches into off-positon (yellow LED not illuminated).
www.tele-online.com
Page 3
E1YM400VS10
60mm
87mm
44mm 5mm
45mm
L1
L2
15
16 18
R
N L3
16 18
15
L1 L2 L3 N
3N~
L1
L2
15
16 18
R
N L3
16 18
15
L
N
1~
Connections
Dimensions
Ordering information
Type Rated voltage U
E1YM400VS10 3(N)~400/230V
RELEASE 2012/05
Subject to alterations and errors
N
Swiching treshold US:
Max: 80%...130% of U Min: 70%...120% of U