Datasheet DWB01, PWB01 Datasheet (YZ)

Page 1
Monitoring Relays 3-Phase Load Guard Types DWB01, PWB01
DWB01 PWB01
• TRMS load guard relays for three phase alanced applications
b
• Measuring if the power factor is within set limits
• Measuring ranges: 5A, 10A, MI current transformers
• Power ON delay 1 to 30 s knob adjustable
• Separately adjustable upper/lower level on absolute
scale
• Programmable latching or inhibit at set level
• Automatic and manual start and stop of the system
Output: 8 A SPDT relay N.D. or N.E. selectable
•
• For mounting on DIN-rail in accordance with DIN/EN
50 022 (DWB01) or plug-in module (PWB01)
• 45 mm Euronorm housing (DWB01) or 36 mm plug-in
module (PWB01)
• LED indication for relay, alarm and power supply ON
Product Description
DWB01 and PWB01 are precise TRMS power factor monitoring relays for 3­phase balanced systems. They can be used for moni­toring the actual load of asynchronous motors and other symmetrical loads, where the power factor is almost proportional to the load. The relay measures the power factor (cos the ratio between the active and the apparent power of a motor.
ϕ), that is
Start/stop input allows to use a manual switch to start and stop the motor, without the need of an auxiliary device. The advantage of using the latch function is that the relay can be kept energized even after the end of the alarm condition. Inhibit func­tion can be used to avoid relay operation when not desired (maintenance, tran­sients). The LED's indicate the state of the alarm and the output relay.
Ordering key
Housing Function Type Item number Output Power Supply Range
DWB 01 C M48 10A
Type Selection
Mounting Output Supply: Supply: Supply: Supply:
DIN-rail Plug-in
SPDT SPDT
208 to 240 VAC 380 to 415 VAC 380 to 480 VAC 600 to 690 VAC
DWB 01 C M23 10A PWB 01 C M23 10A
PWB 01 C M48 10A
DWB 01 C M48 10A DWB01 C M69 10A
Input Specifications
Input
V
oltage
(Own power supply):
3 - phase DWB01: L1, L2, L3
1- phase DWB01CM23: L1, L2 (connect pins L2, L3)
ent: DWB01: 5A, 10A: I1, I2
Curr
PWB01:
M23: 208 to 240 VAC ± 15% DWB01CM48: 380 to 480 VAC ± 15% PWB01CM48: 380 to 415 VAC ± 15% DWB01CM69: 600 to 690 VAC ± 15%
PWB01CM23:
PWB01:
5, 6, 7
5, 6 (connect pins 6, 7) 208 to 240 VAC ± 15%
MI...: U1, U2 5A, 10A: MI...:
11, 10 9, 8
Measuring ranges Upper level Lower level
Power factor (cos ϕ) 0.1 to 0.99
AACrms Max. curr.
Direct input: 0.5 to 5A 30A
Standar TADK2 50 A/5 A 5 to 50 A 60 A TAD2 150 A/5 A 15 to 150 A 180 A T T TACO200 6000 A/5 A 600 to 6000 A 7200 A
MI CT ranges MI 100 MI 500
d CT (examples)
AD6 400 A/5 A 40 to 400 A AD12 1000 A/5 A
1 to 10A 50A
100 to 1000 A 1200 A
10 to 100 A 50 to 500 A
0.1 to 0.99
(30 s)
480 A
325 AAC 1000 AAC
1
Page 2
WB01, PWB01
D
Input Specifications (cont.)
Note:
The input voltage cannot raise over 300 VAC with respect to ground (PWB01 only)
Contact input
DWB01 Terminals Z1, U1 PWB01 Terminals 2, 9 Disabled > 10 kΩ Enabled < 500 Ω Pulse width > 500 ms
Hysteresis PF approx 0.1
Power ON delay 1 to 30 s ± 0.5 s Reaction time (input signal variation from
Alarm ON delay < 200 ms Alarm OFF delay < 200 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C Delay ON alarm ± 10% on set value ± 50 ms Repeatability ± 0.5% on full-scale
Indication for
Power supply ON LED, green Alarm ON LED, red (flashing 2 Hz
Output relay ON LED, yellow
Environment
ee of protection IP 20
Degr Pollution degr Operating temperature
@ Max. voltage, 50 Hz -20 to 60°C, R.H. < 95% @ Max. voltage, 60 Hz -20 to 50°C, R.H. < 95%
Storage temperature -30 to 80°C, R.H. < 95%
Housing dimensions
DIN-rail version 45 x 80 x 99.5 mm Plug-in version 36 x 80 x 94 mm
W
eight
ew ter
Scr
Tightening torque Max. 0.5 Nm
ovals
Appr CE-Marking Y EMC Electromagnetic Compatibility
Immunity According to EN 61000-6-2 Emissions
ee
minals
-20% to +20% or from
+20% to -20% of set value)
during delay time)
3 (DWB01), 2 (PWB01)
Appr
ox. 250 g
acc. to IEC 60947
UL, CSA
es
ding to EN 61000-6-3
Accor
Output Specifications
Output SPDT relay Rated insulation voltage 250 VAC Contact ratings (AgSnO
Resistive loads AC 1 8 A @ 250 VAC
Small inductive loads AC 15 2.5 A @ 250 VAC
Mechanical life ≥ 30 x 106operations Electrical life ≥ 10
Operating frequency ≤ 7200 operations/h
ielectric strength
D
Dielectric voltage ≥ 2 kVAC (RMS) Rated impulse withstand volt. 4 kV (1.2/50 µs)
)µ
2
DC 12 5 A @ 24 VDC
DC 13 2.5 A @ 24 VDC
5
operations
(at 8 A, 250 V, cos ϕ = 1)
ccording to EN 60947-1
A
Supply SpecificationsGeneral Specifications
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038) Through terminals:
Dielectric voltage None
Dielectric voltage supply to output 4 kV
Rated operational power
Supplied by L1 and L2
DWB01: L1, L2, L3 PWB01: 5, 6, 7
M23 177 to 276 VAC 45 to 65 Hz DWB01CM48 323 to 552 VAC45 to 65 Hz PWB01CM48 323 to 477 VAC 45 to 65 Hz DWB01CM69 510 to 793 VAC 45 to 65 Hz
M23: 9 VA @ 230 VAC, 50 Hz M48: 13 VA @ 400 VAC, 50 Hz M69: 21 VA @ 600 VAC, 50 Hz
Mode of Operation
DWB01 and PWB01 can be used for monitoring the actu­al load of asynchronous motors. The relay measures the absolute value for the power factor of the system PF= Active Power/Apparent Pow­er that is for balanced sys­tem with sinus waveforms the cosine of the angle between motor current and motor voltage (cos As cos
ϕ varies with the load of the motor, underload and overload can be indirectly detected by DWB01 and PWB01. The relation between the load and cos the type of motor
ϕ).
ϕ depends on
. As a
guideline to ensure correct working conditions for a motor, the upper level could be set above the cos marking on the motor, and the lower level under this val ue. It is anyway recommend­ed to make the adjustment in connection with a practical test. The relay has an adjustable power ON delay in order to avoid overload detection during motor star
Example 1
Latching mode, relay NE In this application DWB01 or PWB01 ar external current metering transformer, type MI..., (con­nected between U1 & U2) as
e connected to an
ϕ
-
t.
2
Page 3
WB01, PWB01
L2 L3L1
15
16 18 cos j cos j
U1
U2
Z1
I2I1
675
1
43 cos j cos j
9
8
2
1011
D
Mode of Operation (cont.)
utomatic reactivation of the
ell as to a 3-phase asyn-
w chronous motor. The relay
nergizes as soon as the
e power supply is applied. After the power ON delay, the unit starts measuring cos ϕ. If cos ϕ is within the set­points the relay is energized. As soon as the power factor
rops below the lower set-
d
oint or exceeds the upper
p
etpoint the output relay
s releases and the red LED turns on after the set time has expired. To restart the cos
ϕ measurement, connect Z1 and U1 (2 and 9) or inter­rupt the power supply for at least 1 s.
Example 2
Non-latching mode, relay NE DWB01 and PWB01 react as described in the previous example 1 except for the
a
elay as soon as cos ϕ i
r
ack within the two set-
b points. When the measured cos
ϕ exceeds the set upper level, the red LED starts flashing. The output relay releases after the set time period. When the measured
os
c
rops below the set
ϕ d
lower level, the red LED
tarts flashing, and the out-
s put relay releases after the set time period. When the output relay releases there will be no LED indication.
Example 3 1-Phase load monitoring
DWB01CM2310A and PWB01CM2310A can be used for monitoring the pow­er factor of a 1-Phase load with 208 to 240 V AC mains voltage. In this case the pow-
r supply has to be connect-
e
d between L1, L2 (or 5, 6),
e
s
2 and L3 (or 6 and 7) have
L to be connected.
Example 4
Start/stop mode, relay NE In this application DWB01 or PWB01 are directly connect-
d to a 3-phase asyn-
e
hronous motor. The relay
c
nergizes as soon as the
e power supply is applied and the start/stop contact is closed. After the power ON delay, the unit starts measur­ing cos
ϕ. If cos ϕ is within the setpoints the relay ener­gizes. As soon as the power factor drops below the lower setpoint or exceeds the upper setpoint the output relay releases and the red LED turns ON after the set time has expired. When the
tart/stop contact is opened
s
he relay de-energizes imme-
t
iately. To restart the system
d just connect the start/stop contact.
Note 1: to use the start/stop function the output relay has
o command a contactor
t
onnected in series to the
c
oad (see last two wiring dia-
l grams).
Note 2: in case of current below the minimum level the alarm is conventionally ON.
Note 3: (3-phase voltage): connect the 3-phase power supply to the terminals L1, L2 and L3 (DWB01) - 5, 6 and 7 (PWB01) taking care of the sequence.
Function/Range/Level/Time Setting
Select the desired function setting the DIP-switches 1 to 4 as shown on the right. To access the DIP-switches open the plastic cover using a screwdriver as shown on the right. If DIP switch 3 is set to ON (start/stop) the position of DIP-switch 4 does not affect
oducts working mode.
the pr
Centre knobs: Setting of upper and lower level of cos
ϕ 0.1 to 0.99.
DWB01
Contact input
PWB01
Contact input
Lower left knob: Setting of delay on absolute scale: 0.1 to 30 s.
Lower right knob: Setting of power ON delay on absolute scale: 1 to 30 s.
Input current range (terminals I1, I2 or 10, 11)
ON: 10A OFF: 5A/MI input
Relay status
ON: Relay de-energized in normal condition OFF: Relay energized in normal condition
Working mode
ON: Contact input for start/stop functions OFF: Contact input for latch/inhibit functions
Contact input (SW4 does not affect the working mode if SW3 is ON)
ON: Latch function enable
Inhibit function enable
OFF:
Notes
1.
DIP-switch 3 set ON enables the start/stop function that is managed by the closing­opening of the contact input.
2.DIP-switch 3 set OFF enables the input contact for the latch/inhibit functions: the selection between these is allows by the DIP switch 4.
The following table shows how the input con tact manages the mode of operation:
Contact input working mode
OPEN
ACTIVE
LA
TCH
CLOSED
NOT ACTIVE
INHIBIT ACTIVE NOT ACTIVE START/STOP START STOP
-
3
Page 4
WB01, PWB01
L2 L3L1
N
L
m
15
16 18
U1
U2
Z1
I2I1
cos j cos j
675
N
L
m
1
43
9
8
2
1011
cos j cos j
L2 L3L1
L1
L2
L3
m
15
16 18
Grey
U1
U2
Z1
I2I1
cos j cos j
675
L1
L2
L3
m
1
43
Grey
9
8
2
1011
cos j cos j
L
2L3L1
L1
L2
L
3
m
1
5
1
618
U1
U2
Z
1
I2I1
cos j cos j
I1
675
L
1
L2
L3
m
1
43
9
8
2
1011
cos j c
os j
I1
L2 L3L1
L1
L2
L3
m
1
5
16 18
I1
cos j cos j
U1
U2
Z1
I2I1
675
L
1
L2
L3
m
1
43
I1
c
os j
cos j
9
8
2
1
011
D
Wiring Diagrams
DWB01 - Direct connection PWB01 - Direct connection
L
atch/Inhibit
Contact
DWB01 - Standard CT PWB01 - Standard CT
L
atch/Inhibit
Contact
L
atch/Inhibit
Contact
Latch/Inhibit
C
ontact
DWB01 - MI CT PWB01 - MI CT
Latch/Inhibit
Contact
PWB01CM2310A - Direct connection - 1-Phase LoadDWB01CM2310A - Direct connection - 1-Phase Load
Latch/Inhibit
Contact
Latch/Inhibit
Contact
Latch/Inhibit
Contact
4
Page 5
T T T
L
2L3L1
m
15
1
618
L
1
L2
L3
c
os j
cos j
U1
U
2
Z
1
I
2I1
I
1
N
675
m
1
43
L
1
L2
L3
c
os j
c
os j
9
8
2
1
011
I
1
N
WB01, PWB01
T T
D
Wiring Diagrams (cont.)
With the start/stop function enabled, it’s necessary to use the following wiring diagrams (which are two examples among many others). It is possible for both 3-phase loads and 1-phase loads, either through direct connection or external current metering transformer.
WB01 - Direct connection - Manual start and stop (NE relay)
D
WB01 - Direct connection - Manual start and stop (NE relay)
P
Start/stop
C
ontact
Operation Diagrams
Latch function - NE relay
Power supply
Latch contact (Closed = latch not active)
Upper Level
Hysteresys
Lower Level
Relay ON
Hysteresys
Power
ON
Power
ON
Start/stop
C
ontact
Inhibit function - ND relay
Power supply
Inhibit contact (Closed = inhibit active)
Upper Level
Hysteresys
esys
Lower Level
Relay ON
Hyster
Power
ON
Start and stop function - NE relay
Power supply
t/Stop contact
Star (Closed = Star
Upper Level
Lower Level
Relay ON
t; Open = Stop)
Hysteresys
Hyster
esys
Power
ON
Power
ON
5
Page 6
WB01, PWB01
45
80
83.5
9
9.5
63
28.5
36
80
94
2
8.5
63
90
D
Dimensions
Plug-inDIN-rail
6
Loading...