(No Earth connection is required)
– Universal AC i nput voltage and full power up to 55°C
– Power will not de-rate for the entire input voltage range
– Efficiency > 82.0% @ 115Vac & 230Vac
– NEC Class 2 / Limi ted Power S ource ( LPS) certified
– Overvoltage / Over current / O ver Tem perature P rotections
Safety Standards
CB Certif ied for worldwide us e
Model Number: DRC-12V10W1A☐
Unit Weight: 0.06 kg
Dimensions (L x W x D): 91 x 18 x 55.6mm
General Descriptio n
The DRC-12V10W1A☐ i s par t of the Chrome DIN Rail Po wer S upp ly seri es, whi c h is d esi gned for use i n c omp act c abi net s f or hom e
automations and the food and beverage industry. Delta’s Chrome DIN Rail Power Supply series offers double isolated input. This
means that no Earth connection is required thus resulting i n lo w leak ag e c ur r en t. This product provides a universal input voltage range
of 90-264Vac, and a wide temperature range of -25°C to 71°C. The Chrome series is certified to safety standard according to
IEC/EN/UL 60950-1 Inform ati on Tec hnol ogy E quipm ent ( ITE) and UL 5 08 Ind ust rial Cont rol Eq uipm ent ( ICE) . The s eri es is al so ful ly
com pli ant w it h RoH S Dir ecti v e 20 11/ 65/ EU for envi ro nm ent al pro t ecti on. NEC Cl as s 2 and Li mi ted P ower S ou rce ( LP S) app ro val s ar e
available for this product.
Model Inf or m a t io n
Chrome DIN Rail Power Suppl y
Model NumberInput Voltage RangeOutput
DRC-12V10W1A☐
Model Numbering
90-264Vac (125-375Vdc) 12Vdc0.83A
V
oltageOutput Current
DRC –24V
DIN RailProduct Series
C – Isolation Class II
Power Supply
All paramet ers ar e speci fied at 25°C ambient unless oth erwis e indicat ed.
www.DeltaPSU.com (August 2016, Rev. 01)
Output VoltageOutput Power
(10W series)
Single PhaseNo PFCZ – Black Plastic Case
G – Grey Plast ic Case
Page 2
TECHNI CAL DATASHEET
Chrome DIN Rail Power
Supply
12V 9.96W 1
Phase (Class II & NEC Class 2)
/ DRC-12V10W1A
2
AWG 26-12
Specifications
Input Ratings / Characteristics
Nominal Input Voltage100-240Vac
Input Voltage Range90-264Vac
Nominal Input Frequency50-60Hz
Input Frequency Range47-63Hz
Nominal DC Input Voltage* 125-375Vdc
Input Current< 0.30A @ 115Vac, < 0.20A @ 230Vac
Efficiency at 100% Load> 82.0% @ 115Vac & 230Vac
Max Inrush Current (Cold Start)< 15A @ 115Vac, < 30A @ 230Vac
Leakage Current< 0.25mA @ 240Vac
*DC input voltage is not included in the UL approval. Additional testing might be necessary.
Output Ratings / Char acter istics
Nominal Output Voltage12Vdc
Output Voltage Tolerance± 2% (initial set point tolerance from factory)
Out put Curren t 0.83A
Output Power9.96W
Line Regulation< 1% typ . (@ 90-264Vac, 100% load)
Load Regulation< 2% typ . (@ 90-264Vac, 100% load)
Residual Ripple / PARD (20MHz)< 50mVpp / 150mVpp
Rise Time
Start-up Time< 3,000ms @ nominal input (100% load)
Hold-up Time> 10ms @ 115Vac,
Dynamic Response (Overshoot & Undershoot O/P Voltage)± 5% @ 10-100% load
Start-up with Capacitive Loads3,000µF Max
Mechanical
Case CoverPlastic
Dimensions (L x W x D)91 x 18 x 55.6 mm
Unit Weight0.06 kg
IndicatorGreen LED (DC OK)
Cooling SystemConvection
TerminalInput M4 x 2 Pins (Rated 300V/16A)
Output M4 x 2 Pins (Rated 300V/16A)
WireInput / Outp ut
Mounting Rail
< 100ms @ nominal input (100% load)
> 30ms @ 230Vac (100% load
Standard TS35 DIN Rail in accordance with EN 60715
)
□
All paramet ers ar e speci fied at 25°C ambient unless oth erwis e indicat ed.
www.DeltaPSU.com (August 2016, Rev. 01)
Page 3
TECHNI CAL DATASHEET
Chrome DIN Rail Power
Supply
12V 9.96W 1
Phase (Class II & NEC Class 2)
/ DRC-12V10W1A
3
(Auto-Rec over y when the fault i s remov ed)
□
Environment
Surrounding Air TemperatureOperating -25°C to +71°C
Storage -25°C to +85°C
Power De-rating
Operating Humidity 5 to 95% RH (Non-Condensing)
Operating Altitude 0 to 2,00 0 M eters
Shock Test (Operating) IEC 60068-2-27, Half Sine Wave: 4G for a duration of
Vibration (Operating) IEC 60068-2-6, Sine Wave: 10-500Hz @ 19.6m/S² (2G
Pollution Degree 2
Protections
Overvoltage< 17.4V, SELV Output, Latch-off Mode
Overload / Overcurrent> 105% of rated load current, Hiccup Mode,
Over Tem perature> 75°C Surrounding Air Temperature @ 100% load,
Short CircuitHiccup Mode, N on-Latching
> 55°C de-rate power by 2.5% / °C
22ms, 3 shocks for each 3 directions, 9 times in total
peak); 10 min per cycle, 60 min for all X, Y, Z directions
Non-Latching (Auto-Recovery when the fault is
removed)
Latch-off Mode
Degree of ProtectionIP20
Protection Against ShockClass II (No PE* connection is required)
*PE: Primary Earth
Reliability Data
MTBF > 500,000 hrs. as per Telcor dia SR-332
I/P: 100Vac, O/P: 100% load, Ta: 35°C
Expected Cap Life Time10 years (115Vac & 230Vac, 50% load @ 40°C)
All paramet ers ar e speci fied at 25°C ambient unless oth erwis e indicat ed.
www.DeltaPSU.com (August 2016, Rev. 01)
Page 4
TECHNI CAL DATASHEET
Chrome DIN Rail Power
Supply
12V 9.96W 1
Phase (Class II & NEC Class 2)
/ DRC-12V10W1A
4
□
Safety Standards / Directives
Electrical Safety
Indust r ial Co ntrol Equipm ent UL/cUL li sted t o UL 508 and CSA C22.2 No. 107.1-01
Class 2 Power Supply UL/cUL recognized to UL 60950-1, CS A C 22.2
CE In conformance with EMC Directive 2014/30/EU and
Mat erial and Parts RoHS Directive 2011/65/EU Compliant
Galvanic IsolationInput to Output 3.0KVac
EMC
EMC / Emissions CISPR 2 2, EN 55022, FCC Title 47: Class B
Immunity to EN 55024
Electrostatic Discharge IEC 61000-4-2 Level 3 C r iter ia A1)
Radiated Field IEC 61000-4-3 Level 2 C riteria A1)
Electrical Fast Transient / Burst IEC 61000-4-4 Level 3 C r iter ia A1)
Surge IEC 61000-4-5 Level 3 C r iter ia A1)
Conducted IEC 61000-4-6 Level 2 C riteria A1)
Power Frequency Magnetic Fields IEC 61000-4-8 Criteria A1)
Voltage Dips IEC 61000-4-11 > 95% di p; 0.5 cycl e ( 10ms )
TUV Bauart to EN 60950-1, UL/cUL r ecognized to
UL 60950-1 and CSA C22.2 No. 60950-1, CB sch eme
to IEC 60950-1, Lim ited Power Source (LPS)
No. 60950-1
Low Voltage Directive 2014/35/EU
Air D ischarge: 8kV
Contact Discharge: 4kV
80MHz-1GHz, 3V/M with 1kHz tone / 80% modulation
1kV
2)
Common Mode
Dif feren tial Mode
150kHz-80MHz, 3Vrms
1A/Meter
: 2kV
3)
: 1kV
Voltage Fluctuation and Flicker IEC/EN 61000-3-3
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
All paramet ers ar e speci fied at 25°C ambient unless oth erwis e indicat ed.
www.DeltaPSU.com (August 2016, Rev. 01)
Page 5
TECHNI CAL DATASHEET
Chrome DIN Rail Power
Supply
12V 9.96W 1
Phase (Class II & NEC Class 2)
/ DRC-12V10W1A
5
Block Diagram
□
Device Descripti on
1) Input terminal block connector
2) Output terminal block connector
3) DC OK control LED (G reen)
4) Universal mounting system
All paramet ers ar e speci fied at 25°C ambient unless oth erwis e indicat ed.
www.DeltaPSU.com (August 2016, Rev. 01)
Page 6
TECHNI CAL DATASHEET
Chrome DIN Rail Power
Supply
12V 9.96W 1
Phase (Class II & NEC Class 2)
/ DRC-12V10W1A
6
Note
be damaged, when the power supply is
°C, the
Protection. When activated, the output
off mode and
Depending on the surrounding air
Fig. 1 De-rating for Vertical Mounting Orientation
Dimensions
L x W x D: 91 x 18 x 55.6 mm
□
Engineering Data
De-rating
> 55°C de-rat e power by 2.5% / °C
1. Power supply components may degrade, or
continuously used outside the shaded region,
ref er to the graph shown in Fig. 1.
2. If the output capacity is not reduced when the
surrounding air temperature >55
device may run into Over Temperature
voltage will go into latchrecover able by AC p ower recycle.
3. In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance of 25mm with adjacent units
while the device is in operation.
4.
tem per at ure a nd o utp ut l oad d eli ver ed b y the
power supply, the dev ice c an be very hot !
5. If th e devic e has t o be mounted in any other
orientation, please do not hesitate to contact
info@deltapsu.com for more details.
All paramet ers ar e speci fied at 25°C ambient unless oth erwis e indicat ed.
www.DeltaPSU.com (August 2016, Rev. 01)
Page 7
TECHNI CAL DATASHEET
Chrome DIN Rail Power
Supply
12V 9.96W 1
Phase (Class II & NEC Class 2)
/ DRC-12V10W1A
7
No output power de-rati ng acr oss the ent ire
Dismounting
Fig. 2.1 Mounting
Fig. 2.2 Dismounting
Output De-rating VS. Input Voltage
□
input voltage range
Assembly & Installation
The power supply unit (PSU) can be mounted on 35mm DIN rails in accordance with EN60715. The device should be installed with
input terminal block at the bottom.
Each device is delivered ready to install.
Mounting
Snap on the DIN rail as shown in Fig. 2.1:
1. Tilt the unit upwards and insert it onto the DIN rail.
2. Push downwards until stopped.
3. Press against the bottom fron t side for locking.
4. Shake the unit slightly to ensure that it is secured.
To uninstall, pull or slide down the latch with screw driver as
shown in Fig. 2.2. Then slide the power supply unit (PSU) in
the opposite direction, release the latch and pull out the power
supply unit (PSU) from the rail.
All paramet ers ar e speci fied at 25°C ambient unless oth erwis e indicat ed.
www.DeltaPSU.com (August 2016, Rev. 01)
Page 8
TECHNI CAL DATASHEET
Chrome DIN Rail Power
Supply
12V 9.96W 1
Phase (Class II & NEC Class 2)
/ DRC-12V10W1A
8
– ALWAYS switch mains of input power OFF before connecting and disconnecting the input
Note that the enclosure of the device can become very hot depending on the surrounding
zardous voltages may be present for up to 5 minutes after the input mains voltage is
and must be installed in a cabinet or room
Safety Instructions
□
voltage to the unit. If mains are not turned OFF, there is risk of explosion / severe damage.
– To guarantee sufficient convection cooling, keep a distance of 50mm above and
below the device as well as a lateral distance of 25mm to other units.
–
air temperature and load of the power supply. Risk of burns!
– DO NOT insert any obj ects into t he unit.
– Ha
disconnected. Do not touch the unit during this time.
– The p ower supplies unit shoul d be ins tall ed in mi nimum IP54 r ated encl osur e.
– The power supplies are built in units
(condensation free environment and indoor location) that is relatively free of conductive
contaminants.
Functions
■Graph illustrating the Start-up Time, Rise Time, and Hold-up Ti me
Start-up Time
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its set value.
Hold-up Time
Hold up time is the time when the AC input collapses and output voltage r etains regulation f or a cer tain peri od of time. The time
required for the output to reach 90% of its set value, after the input voltage is removed.
All paramet ers ar e speci fied at 25°C ambient unless oth erwis e indicat ed.
www.DeltaPSU.com (August 2016, Rev. 01)
Page 9
TECHNI CAL DATASHEET
Chrome DIN Rail Power
Supply
12V 9.96W 1
Phase (Class II & NEC Class 2)
/ DRC-12V10W1A
9
□
Inrush Current
Inrush current is the peak, instantaneous, input current measured
and, occurs when the input voltage is first applied. For AC input
voltages, the maximum peak value of inrush current will occur
during the first half cycle of the applied AC voltage. This peak
value decreases exponentially during subsequent cycles of AC
voltage.
Dynamic Response
The power supply output voltage will remains within ±5% of its
steady state value, when subjected to a dynamic load from 10 to
100% of its rated current.
Overload & Overcurrent Protections
The power supply’s Overload (OLP) and Over current (OCP)
Protections will be activated when output current ra pidl y ex ceed s
105% of I
supply has reached its maximum power limit, the protection is
activated and the power supply will go into “Hiccup mode” (AutoReco ver y ) . T h e po wer sup pl y wi ll r eco v er o nc e th e f a ul t co nd i tion
of the OLP and OCP is removed and I
specifications.
Over Temperature Protection
As mentioned above, the power supply also has Over
Tem per atu re Pr ot ect io n (OT P). I n th e even t of a hig her o pera ti ng
condition at 100% load, the power supply will run into OTP when
the operating temperature is beyond what is recommended in the
de-rating graph. When activated, the output voltage will go into
latch-off mode until the component temperature cools down and
the AC power is recycled.
(Max load). In such occurrence, once the power
O
is back within the
O
Overvoltage Pr otection
The p ower s upply’ s overv olta ge circ uit wil l be acti vated when its
intern al f eed b a ck ci r c ui t f ai l s. Th e ou t pu t v ol t ag e s h al l n ot ex c eed
its specifications defined on Page 3 under “Protections”.
Short Circuit Prot ec tion
The power supply’s output OLP/OCP function also provides
pro tecti on agains t short circuit s. When a short circuit is applied,
the output current will operate in “Hiccup mode”, as shown in the
illustration in the OLP/OCP section on this page. The power
supply will return to normal operation after the short circuit is
removed.
All paramet ers ar e speci fied at 25°C ambient unless oth erwis e indicat ed.
www.DeltaPSU.com (August 2016, Rev. 01)
Page 10
TECHNI CAL DATASHEET
Chrome DIN Rail Power
Supply
12V 9.96W 1
Phase (Class II & NEC Class 2)
/ DRC-12V10W1A
10
Others
Delta RoHS Compliant
Restriction of the usage of hazardous substances
The European directive 2011/65/EU limits the maximum impurity level of homogeneous materials such as lead,
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and
electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substances in
elec trical a nd elec tro nic equ ipment”.
This product conforms to this standard.
□
All paramet ers ar e speci fied at 25°C ambient unless oth erwis e indicat ed.
www.DeltaPSU.com (August 2016, Rev. 01)