Datasheet DK 0606 G Specification

Page 1
with terminals 5-pole per pole 6 x 1,5 mm² r / f, 4 x 2,5 mm² r / f, 4 x 4 mm² r / f, 4 x 6 mm² r / f, 2 x 10 mm² r / f cable entries via k nockouts, order AKM separately (see cable entry systems LES) cable junction box for encapsulating for ground installation without live loads or in risk of condensation formation and ingress of liquids usable for heating cable / heating tape up to max. 70 °C surface temperature with sealing compound and sealing plug In case of re-installation or testing the sealing compound can be removed easily durability of sealing compound to processing ≥ 12 months at a storage temperature of 5 - 50 °C external brackets for wall fixing included colour: grey, RAL 7035
degree of protection IP 68
submersion up to 20 meter, 168 hours
rated insulation voltage Ui = 690 V a.c./d.c.
rated current: 40 A
material PC-GFS (polycarbonate)
width 130 mm
height 130 mm
depth 77 mm
weight 1,26 kg
tightening torque for terminal 1.5 Nm
in accordance with EN 60670-1
DIN VDE V 0606-22-100
Drawings
Dimension drawing
"Waterproof", for encapsulating
WP 0606 G
1.5-6 mm², Cu 3~
Page 1 of 3
Gust av Hensel GmbH & Co. KG * Gustav -Hens el-Str. 6 * 57368 Lennes tadt * Germany * T elefon: +49 (0)2723/609-0 * F ax: +49 (0)2723/60052 * Date: M arch 28. 2022
Page 2
Detail mass
Box walls
Operating and ambient conditions
Application area Suitable for for outdoor installation (harsh environment and/or
outdoor). For application in ambient conditions with formation of condensation and ingress of water as well as for installation in the ground without traffic loads in accordance with DIN VDE V 0606­22-100. Submersion up to 20 meter, 168 hours, IP 68.
Resistant to occasional cleaning procedures (direct jet) Resistant to occasional cleaning procedures (direct jet)with high-
pressure cleaner without additives, water temperature: max. 80° C
Ambient temperature Average value over 24 hours + 55 °C
Maximum value + 70 °C Minimum value - 25 °C
Relative humidity 100 %
Burning behaviour Glow wire test IEC 60695-2-11: 960 °C
UL Subject 94: V-0 flame-retardant self-extinguishing
"Waterproof", for encapsulating
WP 0606 G
1.5-6 mm², Cu 3~
Page 2 of 3
Gust av Hensel GmbH & Co. KG * Gustav -Hens el-Str. 6 * 57368 Lennes tadt * Germany * T elefon: +49 (0)2723/609-0 * F ax: +49 (0)2723/60052 * Date: M arch 28. 2022
Page 3
Degree of protection against mechanical load IK09 (10 Joule)
Toxic behaviour halogen-free
silicone-free isocyanate-free
"Waterproof", for encapsulating
WP 0606 G
1.5-6 mm², Cu 3~
Page 3 of 3
Gust av Hensel GmbH & Co. KG * Gustav -Hens el-Str. 6 * 57368 Lennes tadt * Germany * T elefon: +49 (0)2723/609-0 * F ax: +49 (0)2723/60052 * Date: M arch 28. 2022
Loading...