Datasheet DK 0202 G Specification

Page 1
terminal with 2 clamping units per pole 5-pole per pole 8 x 0,75 mm² f, 6 x 1,5 mm² r / f, 4 x 2,5 mm² r / f, 2 x 4 mm² r / f cable entries via knockouts, order AKM separately (see cable entry systems LES) "weatherproof" resistant to weather influences (UV due to solar radiation, protected against rainwater, temperature resistant, impact resistant, etc.) saltwater-proof "offshore applications" lid fasteners sealable without access ories retaining strap and external brackets for wall fixing included colour: grey, RAL 7035
rated insulation voltage Ui = 690 V a.c./d.c.
rated current: 20 A
material PC-GFS (polycarbonate)
degree of protection IP 66 / IP 67 / IP 69
IP 67, temporary submersion IP 69, water pressure max. 100 bar, water temperature max. 80 °C, distance ≥ 0.15 m
width 93 mm
height 93 mm
depth 62 mm
weight 0,141 kg
tightening torque for terminal 0.5 Nm
in accordance with IEC 60670-22
in accordance with DNV GL - Certificate No: TAE00000EE
Drawings
Dimension drawing
”Weatherproof“ for outdoor installation
KF 0202 G
0.75-2.5 mm², Cu 3~
Page 1 of 3
Gust av Hens el Gm bH & C o. KG * Gustav-H ensel-St r. 6 * 57368 Lennes tadt * Germany * T elefon: +49 (0)2723/609-0 * F ax: +49 (0)2723/60052 * D ate: M arch 28. 2022
Page 2
Detail mass
Box walls
Operating and ambient conditions
Application area Suitable for for outdoor installation (harsh environment and/or
outdoor). To reduce the formation and accumulation of condensed water see technical information.
Resistant to occasional cleaning procedures (direct jet) Resistance to occasional cleaning procedures (direct jet) with high-
pressure cleaner without cleaning additives, water pressure: max 100 bar, water temperature: max 80 °C, distance ≥ 0.15 m, in accordance with DIN EN 60529:2014-09 (IEC 60529:2013) = IP 69. Only with cable entries HENSEL AKM or ASS.
Ambient temperature Average value over 24 hours + 55 °C
Maximum value + 70 °C Minimum value - 25 °C
Relative humidity 50% at 40° C
short-time 100% at 25° C
Fire protection in the event of internal faults Demands placed on electrical devices from standards and laws
Minimum requirements
”Weatherproof“ for outdoor installation
KF 0202 G
0.75-2.5 mm², Cu 3~
Page 2 of 3
Gust av Hens el Gm bH & C o. KG * Gustav-H ensel-St r. 6 * 57368 Lennes tadt * Germany * T elefon: +49 (0)2723/609-0 * F ax: +49 (0)2723/60052 * D ate: M arch 28. 2022
Page 3
- Glow wire test in accordance with IEC 60695-2-11:
- 650°C for boxes and cable glands
- 850°C for parts of insulating material necessary to retain current carrying parts in position
Burning behaviour Glow wire test IEC 60695-2-11: 960 °C
UL Subject 94: V-0 flame-retardant self-extinguishing
Degree of protection against mechanical load IK09 (10 Joule)
Toxic behaviour halogen-free
silicone-free "halogen-free" in accordance with the examination of the cables and insulated wires - corrosiveness of fumes - as per IEC 60754-2
Note: For material properties see technical data.