CRD5150 Single Element, 3-Wire
CRD5150 3 Element, 3-Wire
CRD5170 3 Element, 4-Wire
ASCII Simplified Programming Commands
A simplified data structure is used with only 6 commands
required for full control of the transducer. Commands are :
Read Transducer Name, Read Configuration, Set
Configuration, Read Measurements, Read Energy Totalizer
and Clear Energy Totalizer. For illustration, the following
commands are used to read data from a CRD5170 3
Phase, 4 Wire Transducer with a device address of 00.
Command Transducer to Read Data: #00A<cr>
Transducers Response: >+[% FS Voltage
L1-N
]+[% FS
CurrentL1]+[% FS Voltage
L2-N
]+[% FS CurrentL2]+[% FS
Voltage
L3-N
]+[% FS CurrentL3,][+/- % FS Power][+/-% FS
VARS][+/-Power Factor][Frequency]<cr>
Command Transducer to Read Energy Totalizer:
#00W<cr>
Transducer Responds: 01[+/-KWHr]
{\[+/-KVHr][check
sum]<cr>
Note: This is for illustration purposes only, request a copy
of the programming data sheets from CR Magnetics.
SPECIFICATIONS
OUTLINE DRAWING
Basic Accuracy: .......................0.5%
Calibration: ..............................True RMS Sensing
Thermal Drift: ..........................500 PPM/°C
Operating Temperature: ..........0°C to +60°C
Installation Category: ..............CAT II
Pollution Degree: ....................2
Insulation Voltage: ..................2500 VDC
Altitude: ..................................2000 meter max
Frequency Range: .................20 Hz - 5 KHz
MTBF: ....................................Greater than 100K hours
Cleaning: ................................Water-dampened cloth
Supply Voltage: ......................24 VDC ±10%
Torque Specifications: ............3.0 inch lbs (0.4Nm)
Output Load:.............................-20 mA DC - 0 to 300 Ω
0-5 VDC - 2K Ω or Greater
Response Time: ......................250 ms. max. 0-90% FS
Relative Humidity: ..............80% for temperatures up to
31°C and decreasing linearly to 50% at 40°C
Output Resolution: ................................................16 bit
Transducer fanout on common bus: .................64 max.
Baud Rate 2: ..............
1200, 2400, 4800, 9600,19.7K .bps
A/D Conversion Type: .................4th order Delta Sigma
Device Address 2: ...........................................00 to FF
Data Format: ........................................................ASCII
Supply Current:..................Typical 30mA Max 30mA
Weight:..................................................................0.5 lbs.