Datasheet CRD5100 Datasheet (CR Magnetics)

Page 1
Data Stream
CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
Another HUNTINGTON ELECTRIC Company
11
B
PART NUMBERS
CRD5110
150 to 300 VAC
1 to 25 AAC Input Range
CRD5150
Two Element - .26” Window
150 to 300 VAC
1 to 25 AAC Input Range
CRD5170
Three Element - .26” Window
150 to 300 VAC
1 to 25 AAC Input Range
Sensing
Voltage, True RMS Current, True RMS Active Power, bi-directional Active Energy, bi-directional Reactive Power, bi-directional Reactive Energy, bi-directional Power Factor Frequency
Applications
Sub-Metering Motor Loads Uninterruptible Power Systems Remote Monitoring Load Shedding Energy Management
Features
35mm DIN Rail or Panel Mount Available with 0 - 5 VDC or 4 - 20 mA DC outputs 24 VDC powered Use with external current transformers Highest precision available Connection diagram printed on case
Regulatory Agencies
CRD5110
- - 1 Element, AC Multifunction RS485 Digital Transducer
CRD5150 - - 3 Phase, 3-Wire AC Multifunction RS485 Digital Transducer CRD5170 - - 3 Element, 4-Wire AC Multifunction RS485 Digital Transducer
Data Stream RS485 Digital Transducer
DIN RAIL / PANEL MOUNT
150 - 0-150 VAC 300 - 0-300 VAC
other ranges available
1 - 0-1 AAC
5 - 0-5 AAC 15 - 0-15 AAC 25 - 0-25 AAC
other ranges available
The CRD5100 Series Data Stream Digital Transducers are designed for complete monitoring of electrical power systems. The digital technolo­gy is used to measure voltage, current, power frequency and energy in single and three phase designs. The data is streamed over an RS485 IEEE bus which enables multiple transducers to communicate thru a sin­gle master connection. These advanced sensors are ideal for entire plant or zone monitoring. Also, the communication alagorithm can be pre-ordered with ASCII based control or modified MODBUS based control.
Note: Add an M at the end
for MODBUS
Page 2
CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
Another HUNTINGTON ELECTRIC Company
12
Data Stream
B
RS485 Digital Transducer
0.26 (6.5) Dia. 1 hole for single element 2 holes for two element 3 holes for three element
CRD5110 Single Element, 2-Wire
LINE
N
L3
L1
L2
CRD5150 Single Element, 3-Wire
CRD5150 3 Element, 3-Wire
CRD5170 3 Element, 4-Wire
ASCII Simplified Programming Commands
A simplified data structure is used with only 6 commands required for full control of the transducer. Commands are : Read Transducer Name, Read Configuration, Set Configuration, Read Measurements, Read Energy Totalizer and Clear Energy Totalizer. For illustration, the following commands are used to read data from a CRD5170 3 Phase, 4 Wire Transducer with a device address of 00.
Command Transducer to Read Data: #00A<cr> Transducers Response: >+[% FS Voltage
L1-N
]+[% FS
CurrentL1]+[% FS Voltage
L2-N
]+[% FS CurrentL2]+[% FS
Voltage
L3-N
]+[% FS CurrentL3,][+/- % FS Power][+/-% FS
VARS][+/-Power Factor][Frequency]<cr>
Command Transducer to Read Energy Totalizer:
#00W<cr> Transducer Responds: 01[+/-KWHr]
{\[+/-KVHr][check
sum]<cr>
Note: This is for illustration purposes only, request a copy of the programming data sheets from CR Magnetics.
SPECIFICATIONS
OUTLINE DRAWING
Basic Accuracy: .......................0.5%
Calibration: ..............................True RMS Sensing
Thermal Drift: ..........................500 PPM/°C
Operating Temperature: ..........0°C to +60°C
Installation Category: ..............CAT II
Pollution Degree: ....................2
Insulation Voltage: ..................2500 VDC
Altitude: ..................................2000 meter max
Frequency Range: .................20 Hz - 5 KHz
MTBF: ....................................Greater than 100K hours
Cleaning: ................................Water-dampened cloth
Supply Voltage: ......................24 VDC ±10%
Torque Specifications: ............3.0 inch lbs (0.4Nm)
Output Load:.............................-20 mA DC - 0 to 300
0-5 VDC - 2K or Greater
Response Time: ......................250 ms. max. 0-90% FS
Relative Humidity: ..............80% for temperatures up to
31°C and decreasing linearly to 50% at 40°C
Output Resolution: ................................................16 bit
Transducer fanout on common bus: .................64 max.
Baud Rate 2: ..............
1200, 2400, 4800, 9600,19.7K .bps
A/D Conversion Type: .................4th order Delta Sigma
Device Address 2: ...........................................00 to FF
Data Format: ........................................................ASCII
Supply Current:..................Typical 30mA Max 30mA
Weight:..................................................................0.5 lbs.
Connection Diagram
N
L1
L2
LINE
LOAD
LINE
LOAD
N
L1
L2
L3
N
L1
LINE
LOAD
LINE
L2
L1
L3
LOAD
DIA.
0.14 (3.5)
1.06 (26.8)
2.874 (73)
0.20 (5.1)
3.268 (83)
2.99 (76)
1.42 (36)
SUPPLY
485
1.06 (26.8)
LINE
LN
1 2 3 4
LINE
9 8 7 6 5
L3L1L2
1 2 3 4
LOAD
L2L1N
9 8 7 6 5
1 2 3 4
1 2 3 4
1 2 3 4
LOAD
9 8 7 6 5
1 2 3 4
LOAD
+
9
485
-
8 7 6
+
-
5
SUPPLY
9 8 7 6 5
9 8 7 6 5