Datasheet BLCEN-4M12MT-4AI-TC Datasheet (Turck)

Page 1
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 Analog Inputs for Thermocouple Elements BLCEN-4M12MT-4AI-TC
Type designation BLCEN-4M12MT-4AI-TC
Ident-No. 6811467
Fieldbus transmission rate 10/100 Mbps Adjustment transmission rate Automatic detection Fieldbus connection technology 2 × M12, 4-pole, D-coded Fieldbus address range 1…92
0 (192.168.1.254) 93 (BootP) 94 (DHCP) 95 (PGM) 96 (PGM-DHCP) *Recommended for PROFINET
97…98 (manufacturer specific) Fieldbus addressing 2 decimally coded rotary switches Protocol detection automatic Web server Integrated Service interface Ethernet Vendor ID 48 Product type 12 Product code 11467
On-machine Compact fieldbus I/O block
EtherNet/IP™, Modbus® TCP, or
PROFINET slave
Integrated Ethernet Switch
10 Mbps / 100 Mbps supported
Two 4-pole M12, D-coded, connectors
for fieldbus connection
2 rotary switches for node address
IP67, IP69K
M12 I/O connectors
LEDs indicating status and diagnostics
Electronics galvanically separated from
the field level via optocouplers
4 analog inputs for Thermo Couples
Types B, C, E, G, J, K, N, R, S or T (se-
lectable per channel)
Cold-junction compensation via a
Pt1000 in special connector
FLC/ARGEE programmable
Field Logic Controller (FLC)
Supported from firmware version 3.3.2.0 Released from ARGEE version 2.0.17.0
Modbus TCP
Addressing Static IP, BOOTP, DHCP Supported function codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23 Number of TCP connections 6 Input Data Size max. 6 register Input register start address 0 (0x0000 hex)
EtherNet/IP™
Addressing acc. to EtherNet/IP™ specification Device Level Ring (DLR) supported Class 1 connections 6 Input Data Size 7 INT Output Data Size 1 INT
PROFINET
Addressing DCP Conformance class B (RT) MinCycleTime 1 ms Diagnostics acc. to PROFINET alarm handling Topology detection supported Automatic addressing supported Media Redundancy Protocol (MRP) supported Input Data Size max. 8 BYTE
Edition • Rev. B • 2019-01-21T18:31:55+01:00
1 / 5 TURCK Inc.
Page 2
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 Analog Inputs for Thermocouple Elements BLCEN-4M12MT-4AI-TC
Analog inputs from 4AI-TC
Operating modes Types B, C, E, G, J, K, N, R, S, T Resolution 16 bit Repeatability < 0.05 % Temperature coefficient < 300 ppm / ºC of full scale
Vibration test according to IEC 61131-2 Extended vibration resistance
- up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery Shock test according to IEC 61131-2 Electromagnetic compatibility according to IEC 61131-2 Approvals and certificates CE, cULus
Dimensions (W x L x H) 71 x 113 x 32.5mm Operating temperature -40...+70 ºC Storage temperature -40...+85 ºC Relative humidity 15 to 95% (non-condensing) Protection class IP67
IP69K MTTF 132 years acc. to SN 29500 (Ed. 99) 20 °C Housing material Glass-filled nylon, nickel plated brass connectors Housing color Black Window material Lexan Material screw Nickel-plated brass Material label Polyester with polycarbonate overlay Ground label material Nickel plated brass Weight 390 ± 20 g Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque
Edition • Rev. B • 2019-01-21T18:31:55+01:00
2 / 5 TURCK Inc.
Page 3
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 Analog Inputs for Thermocouple Elements BLCEN-4M12MT-4AI-TC
Pinning and wiring diagram
Ethernet
Fieldbus cable (IP67 example): RSSD RSSD 441-2M ID number
U-02482 or RSSD-RSSD-441-2M/S2174 ID number 6914218
Pin Assignment (M12, D-code)
Thermocouple Inputs
TC compensating connector BL67-WAS5-THERMO ident-no.
6827197
Auxiliary Power
Extension cable (example): RKC 4.4T-2-RSC 4.4T ident-no.
U5264 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208
Pin Assignment
Wiring Diagram
Pin Assignment
Edition • Rev. B • 2019-01-21T18:31:55+01:00
3 / 5 TURCK Inc.
Page 4
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 Analog Inputs for Thermocouple Elements BLCEN-4M12MT-4AI-TC
Station LED status
LED Color Status Description
IOs OFF No power
RED ON Low power or station error
RED FLASHING (1 Hz) I/O module configuration error
RED FLASHING (4 Hz) No I/O module bus communication
GREEN ON Station ok
GREEN FLASHING Force mode active
BUS OFF Power Off
GREEN ON Connected to Master
GREEN FLASHING Ready
GREEN FLASHING 3x (1Hz) ARGEE Running
RED ON Error
RED FLASHING WINK
YELLOW ON DHCP/BOOTP Search
LNK/ACT
GREEN ON Link
GREEN FLASHING Traffic
YELLOW ON 100 Mbit Linked
I/O LED status
LED Color Status Description
D * OFF No diagnostics active
RED ON Station error/ module bus communication failure
RED FLASHING (0.5Hz) Diagnostics active
AI channel
0 / 1
* D LED also indicates gateway diagnostics
AI channel
2 / 3
OFF No Link
Not connected
Edition • Rev. B • 2019-01-21T18:31:55+01:00
4 / 5 TURCK Inc.
Page 5
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 Analog Inputs for Thermocouple Elements BLCEN-4M12MT-4AI-TC
Process Data Mapping of Each Protocol
EtherNet/IP™ I/O & Diagnostics Data Mapping
INPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
1
2
3
Slot 1 (ref. Byte
8)
Legend:
AI Analog Input MR Measurement Value Range Error
CFG Configuration Error OC Open Circuit
COM Communication Failure S1 Slot 1
DIA Diagnostics Active VI low VI Voltage
FCE Force Mode Active VO low VO Voltage
Modbus® TCP Register Mapping
Inputs (RO)
Status (RO) 0x0004 - FCE - - CFG COM VI low - VO low - - - - - - DIA
Diag. (RO) 0x0005 - - - - - - - - - - - - - - - S1 DIA
I/O Diag. (RO)
PROFINET® Process Data
Inputs
0 AI 10 LSBAI 1
1 AI 10 MSB
2 AI 11 LSBAI 1
3 AI 11 MSB
4 AI 12 LSBAI 1
5 AI 12 MSB
6 AI 13 LSBAI 1
7 AI 13 MSB
8 Module number reporting diagnostic dataDiagnostics
9 Replace Sta-
tion
10 - - - - - - Open Circuit
11 - - - - - - Open Circuit
12 - - - - - - Open Circuit
13 - - - - - - Open Circuit
- Diagnostics
Active
- - - - -
AI 1
0
AI 1
1
AI 1
2
AI 1
3
Range Error
AI 1
0
Range Error
AI 1
1
Range Error
AI 1
2
Range Error
AI 1
3
REG Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0x0000 AI 1
0x0001 AI 1
0x0002 AI 1
0x0003 AI 1
0xA000 - - - - - CJAI 11OCAI
0xA001 - - - - - CJAI 13OCAI
0
1
2
3
MRAI
- - - - - CJAI 10OCAI
1
1
1
1
MRAI
- - - - - CJAI 12OCAI
1
1
3
3
MRAI
1
1
0
0
MRAI
1
1
2
2
BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 AI 10 LSB
1 AI 10 MSB
2 AI 11 LSB
3 AI 11 MSB
4 AI 12 LSB
5 AI 12 MSB
6 AI 13 LSB
7 AI 13 MSB
Edition • Rev. B • 2019-01-21T18:31:55+01:00
5 / 5 TURCK Inc.
Loading...