Datasheet BLCDP-4M12MT-4DO-2A-P Datasheet (Turck)

Page 1
BL compact™ fieldbus station for PROFIBUS-DP 4 Digital PNP Outputs BLCDP-4M12MT-4DO-2A-P
Type designation BLCDP-4M12MT-4DO-2A-P
Ident-No. 6811191
Fieldbus transmission rate 9.6 kbps …12 Mbps Adjustment transmission rate Automatic detection Fieldbus connection technology 2 × M12, 5-pole, reverse keyed Fieldbus address range 0...99 Fieldbus addressing 2 decimally coded rotary switches Service interface RS232 interface
On-machine Compact fieldbus I/O block
PROFIBUS-DP slave
9.6 kbps … 12 Mbps
Two 5-pole M12, reverse-keyed, connec-
tors for fieldbus connection
2 rotary switches for node address
IP67, IP69K
M12 I/O connectors
LEDs indicating status and diagnostics
Electronics galvanically separated from
the field level via optocouplers
4 digital PNP outputs, 24 VDC
Max. 2A per output (4A total)
Digital outputs
Output type PNP Type of output diagnostics Channel diagnostics Output voltage 24 VDC Output current per channel 2 A Output delay 3 ms Load type resistive, inductive, lamp load Load resistance, resistive Load resistance, inductive < 1.2 H Lamp load < 10 W Switching frequency, resistive < 200 Hz Switching frequency, inductive < 2 Hz Switching frequency, lamp load < 20 Hz Short-circuit protection yes
Vibration test according to IEC 61131-2 Extended vibration resistance
- up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery Shock test according to IEC 61131-2 Electromagnetic compatibility according to IEC 61131-2 Approvals and certificates CE, cULus
Dimensions (W x L x H) 71 x 113 x 32.5mm Operating temperature -40...+70 ºC Storage temperature -40...+85 ºC Relative humidity 15 to 95% (non-condensing) Protection class IP67
Housing material Glass-filled nylon, nickel plated brass connectors Housing color Black Window material Lexan Material screw Nickel-plated brass Material label Polyester with polycarbonate overlay Ground label material Nickel plated brass Weight 390 ± 20 g Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque
> 12 ò
IP69K
Edition • Rev. A • 2019-01-21T17:06:06+01:00
1 / 4 TURCK Inc.
Page 2
BL compact™ fieldbus station for PROFIBUS-DP 4 Digital PNP Outputs BLCDP-4M12MT-4DO-2A-P
Pinning and wiring diagram
PROFIBUS-DP
Fieldbus cable (example): RSSW RKSW 455-2M ident-no. U0350
or RSSW-RKSW455-2M ident-no. 6602222
Pin Assignment (M12, B-Code)
Digital Outputs
Extension cable (example): RK 4T-2-RS 4T ident-no. U2151-3 or
RKC4T-2-RSC4T/TEL ident-no. 6625204
Auxiliary Power
Extension cable (example): RKC 4.4T-2-RSC 4.4T ident-no.
U5264 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208
Pin Assignment
Wiring Diagram
Pin Assignment
Edition • Rev. A • 2019-01-21T17:06:06+01:00
2 / 4 TURCK Inc.
Page 3
BL compact™ fieldbus station for PROFIBUS-DP 4 Digital PNP Outputs BLCDP-4M12MT-4DO-2A-P
Station LED status
LED Color Status Description
IOs OFF No power
RED ON Low power or station error
RED FLASHING (1 Hz) I/O module configuration error
RED FLASHING (4 Hz) No I/O module bus communication
GREEN ON Station ok
GREEN FLASHING Force mode active
BUS
GREEN ON Field bus communication active
GREEN FLASHING (1 Hz) No field bus communication active, device status OK
RED ON Bus error at the gateway; no data exchange
RED FLASHING Faulty PROFIBUS-DP address
BUS
GREEN ON Field bus communication active
GREEN FLASHING (1 Hz) No field bus communication active, device status OK
RED ON Bus error at the gateway; no data exchange
RED FLASHING Faulty PROFIBUS-DP address
OFF No field bus communication
OFF No field bus communication
Edition • Rev. A • 2019-01-21T17:06:06+01:00
3 / 4 TURCK Inc.
Page 4
BL compact™ fieldbus station for PROFIBUS-DP 4 Digital PNP Outputs BLCDP-4M12MT-4DO-2A-P
I/O Data Map
OUTPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 - - - - DO 1
3
1 - - - - - - - -
DO 1
2
DO 1
1
DO 1
0
Edition • Rev. A • 2019-01-21T17:06:06+01:00
4 / 4 TURCK Inc.
Loading...