Datasheet BLCDN-6M12L-4AI-VI-2AO-V Datasheet (Turck)

Page 1
BL compact™ fieldbus station for DeviceNet™ 4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Voltage BLCDN-6M12L-4AI-VI-2AO-V
On-machine Compact fieldbus I/O block
DeviceNet™ slave
125 / 250 / 500 kbps
Two 5-pole M12 connectors for fieldbus
connection
2 rotary switches for node address
IP67, IP69K
M12 I/O connectors
LEDs indicating status and diagnostics
Electronics galvanically separated from
the field level via optocouplers
4 analog inputs for current or voltage
0/4…20 mA or -10/0…+10 VDC (se-
Type designation BLCDN-6M12L-4AI-VI-2AO-V
Ident-No. 6811001
Fieldbus transmission rate 125/250/500 kbps Adjustment transmission rate Automatic detection Fieldbus connection technology 2 × M12, 5-pole Fieldbus address range 0...63
64…80 (programmable MACID)
81…99 (manufacturer specific) Fieldbus addressing 2 decimally coded rotary switches Service interface RS232 interface Vendor ID 48 Product type 12 Product code 11001
lectable per channel)
2 analog voltage outputs
-10/0…+10 VDC
Analog inputs from 4AI-VI
Operating modes 0/4 … 20 mA or -10/0 … 10 VDC Resolution 16 bit Repeatability < 0.05 % Temperature coefficient < 300 ppm / ºC of full scale
Analog outputs
Operating modes 0/4 … 20 mA
Vibration test according to IEC 61131-2 Extended vibration resistance
- up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery Shock test according to IEC 61131-2 Electromagnetic compatibility according to IEC 61131-2 Approvals and certificates CE, cULus
Dimensions (W x L x H) 71 x 168 x 32.5mm Operating temperature -40...+70 ºC Storage temperature -40...+85 ºC Relative humidity 15 to 95% (non-condensing) Protection class IP67
IP69K Housing material Glass-filled nylon, nickel plated brass connectors Housing color Black Window material Lexan Material screw Nickel-plated brass Material label Polyester with polycarbonate overlay Ground label material Nickel plated brass Weight 540 ± 20 g Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque
Edition • Rev. B • 2019-01-21T16:25:28+01:00
1 / 5 TURCK Inc.
Page 2
BL compact™ fieldbus station for DeviceNet™ 4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Voltage BLCDN-6M12L-4AI-VI-2AO-V
Pinning and wiring diagram
DeviceNet™
Fieldbus cable (example): RSC RKC 572-2M ident-no. U0323 or
RSC-RKC572-2M ident-no. 6603629
Pin Assignment
Slot 1: Analog Inputs
Extension cable (example): RK 4.5T-2-RS 4.5T/S653 ident-no.
U2187-09 or RKC4.5T-2-RSC4.5T/TEL ident-no. 6625212
Pin Assignment
2-wire Technology (Current)
2-wire Technology (Voltage)
3-wire Technology
Edition • Rev. B • 2019-01-21T16:25:28+01:00
2 / 5 TURCK Inc.
4-wire Technology
4-wire Technology (External Power)
Page 3
BL compact™ fieldbus station for DeviceNet™ 4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Voltage BLCDN-6M12L-4AI-VI-2AO-V
Slot 2: Analog Outputs
Extension cable (example): RK 4.5T-2-RS 4.5T/S653 ident-no.
U2187-09 or RKC4.5T-2-RSC4.5T/TEL ident-no. 6625212
Pin Assignment
Edition • Rev. B • 2019-01-21T16:25:28+01:00
3 / 5 TURCK Inc.
Page 4
BL compact™ fieldbus station for DeviceNet™ 4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Voltage BLCDN-6M12L-4AI-VI-2AO-V
Station LED status
LED Color Status Description
IOs OFF No power
RED ON Low power or station error
RED FLASHING (1 Hz) I/O module configuration error
RED FLASHING (4 Hz) No I/O module bus communication
GREEN ON Station ok
GREEN FLASHING Force mode active
MNS
GREEN ON Connection established
GREEN FLASHING (1 Hz) No connection established, device OK
RED ON Duplicate MAC-ID
RED FLASHING Connection time out
IO
I/O LED status slot 1
LED Color Status Description
D1 * OFF No diagnostics active
AI channels OFF Not active
10...1
3
* D1 LED also indicates gateway diagnostics
I/O LED status slot 2
LED Color Status Description
D2 * OFF No diagnostics active
AO channels
0 / 1
* D2 LED also indicates gateway diagnostics
GREEN ON I/O active
GREEN FLASHING (1 Hz) One or more I/O in Idle State
RED ON One or more I/O error
RED FLASHING One or more I/O in Faulted State
RED ON Station error/ module bus communication failure
RED FLASHING (0.5Hz) Diagnostics active (Slot 1)
GREEN ON Active
GREEN FLASHING (0.5 Hz) Underflow in measuring range
GREEN FLASHING (4 Hz) Overflow in measuring range
RED ON Station error/ module bus communication failure
RED FLASHING (0.5Hz) Diagnostics active (Slot 2)
OFF No connection
Not connected
Edition • Rev. B • 2019-01-21T16:25:28+01:00
4 / 5 TURCK Inc.
Page 5
BL compact™ fieldbus station for DeviceNet™ 4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Voltage BLCDN-6M12L-4AI-VI-2AO-V
I/O & Diagnostic Data Map
INPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
1
2
3
Slot 1 (ref. Byte
8)
OUTPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
1
0 AI 10 LSBAI 1
1 AI 10 MSB
2 AI 11 LSBAI 1
3 AI 11 MSB
4 AI 12 LSBAI 1
5 AI 12 MSB
6 AI 13 LSBAI 1
7 AI 13 MSB
8 Module number reporting diagnostic dataDiagnostics
9 Replace Sta-
tion
- Diagnostics
Active
- - - - -
10 - - - - - - Open Circuit
AI 1
0
11 - - - - - - Open Circuit
AI 1
1
12 - - - - - - Open Circuit
AI 1
2
13 - - - - - - Open Circuit
AI 1
3
0 AO 20 LSBAO 2
1 AO 20 MSB
2 AO 21 LSBAO 2
3 AO 21 MSB
Range Error
AI 1
Range Error
AI 1
Range Error
AI 1
Range Error
AI 1
0
1
2
3
Edition • Rev. B • 2019-01-21T16:25:28+01:00
5 / 5 TURCK Inc.