Datasheet BLCCO-4M12S-4DI-P Datasheet (Turck)

Page 1
BL compact™ fieldbus station for CANopen 4 Digital PNP Inputs BLCCO-4M12S-4DI-P
Type designation BLCCO-4M12S-4DI-P
Ident-No. 6811312
Fieldbus transmission rate 10 kbps …1 Mbps Adjustment transmission rate Automatic detection Fieldbus connection technology 2 × M12, 5-pole Fieldbus address range 1...99 Fieldbus addressing 2 decimally coded rotary switches Service interface RS232 interface
On-machine Compact fieldbus I/O block
CANopen slave
10, 20, 50, 125, 250, 500, 800, or 1000
kbps
Two 5-pole M12 connectors for fieldbus
connection
2 rotary switches for node address
IP67, IP69K
M12 I/O connectors
LEDs indicating status and diagnostics
Electronics galvanically separated from
the field level via optocouplers
4 digital PNP inputs, 24 VDC
Digital inputs
Input type PNP Type of input diagnostics Group diagnostics Low level signal voltage < 4.5 VDC High level signal voltage 7 ... 30 VDC Low level signal current < 1.5 mA High level signal current 2.1 ... 3.7 mA Input delay 0.25 ms
Vibration test according to IEC 61131-2 Extended vibration resistance
- up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery Shock test according to IEC 61131-2 Electromagnetic compatibility according to IEC 61131-2 Approvals and certificates CE, cULus
Dimensions (W x L x H) 71 x 93 x 32.5mm Operating temperature -40...+70 ºC Storage temperature -40...+85 ºC Relative humidity 15 to 95% (non-condensing) Protection class IP67
IP69K Housing material Glass-filled nylon, nickel plated brass connectors Housing color Black Window material Lexan Material screw Nickel-plated brass Material label Polyester with polycarbonate overlay Ground label material Nickel plated brass Weight 320 ± 20 g Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque
Edition • Rev. A • 2019-01-21T18:09:37+01:00
1 / 4 TURCK Inc.
Page 2
BL compact™ fieldbus station for CANopen 4 Digital PNP Inputs BLCCO-4M12S-4DI-P
Pinning and wiring diagram
CANopen
Fieldbus cable (example): RSC RKC 572-2M ident-no. U0323 or
RSC-RKC572-2M ident-no. 6603629
Pin Assignment
Digital inputs
Extension cable (example): RK 4T-2-RS 4T ident-no. U2151-3 or
RKC4T-2-RSC4T/TEL ident-no. 6625204
Pin Assignment
Wiring Diagram
Edition • Rev. A • 2019-01-21T18:09:37+01:00
2 / 4 TURCK Inc.
Page 3
BL compact™ fieldbus station for CANopen 4 Digital PNP Inputs BLCCO-4M12S-4DI-P
Station LED status
LED Color Status Description
IOs OFF No power
RED ON Low power or station error
RED FLASHING (1 Hz) I/O module configuration error
RED FLASHING (4 Hz) No I/O module bus communication
GREEN ON Station ok
GREEN FLASHING Force mode active
- OFF No communication error ERR
RED ON CAN bus communication error
BUS
ERR & BUS RED (ERR) & GREEN
I/O LED status
LED Color Status Description
D * OFF No diagnostics active
DI channels OFF Status of channel x = „0“ (OFF)
0...3
* D LED also indicates gateway diagnostics
GREEN ON NMT-slave state is „Operational”
ORANGE ON NMT-slave state is „Pre-Operational“
RED ON NMT-slave state is „Stopped“
FLASHING (4 Hz) Searching for the baud rate
(BUS)
RED ON Station error/ module bus communication failure
RED FLASHING (0.5Hz) Diagnostics active
GREEN ON Status of channel x = „1“ (ON)
Edition • Rev. A • 2019-01-21T18:09:37+01:00
3 / 4 TURCK Inc.
Page 4
BL compact™ fieldbus station for CANopen 4 Digital PNP Inputs BLCCO-4M12S-4DI-P
I/O Data Map
INPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 - - - - DI 1
3
1 - - - - - - - -
DI 1
2
DI 1
1
DI 1
0
Edition • Rev. A • 2019-01-21T18:09:37+01:00
4 / 4 TURCK Inc.