Datasheet ADM1033 Datasheet (Analog Devices)

Page 1
Thermal Monitor and

FEATURES

1 local and 1 remote temperature channel ±1.5°C accuracy on local and remote channels Automatic series resistance cancellation on remote Temperature channels > 1 kΩ Fast (up to 64 measurements per second) SMBus 2.0, 1.1, and 1.0 compliant SMBus address input/LOCATION input to UDID Programmable over-/undertemperature limits Programmable fault queue SMBusALERT Fail-safe overtemperature comparator output Fan speed (RPM) controller
output
ADM1033

FUNCTIONAL BLOCK DIAGRAM

MANUAL FAN
SPEED CONTROL
REGISTERS
TEMPERATURE-TO-
FAN-SPEED
LOOK-UP TABLE
Fan Speed (RPM) Controller
ADM1033
Look-up table for temperature-to-fan-speed control Linear and discrete options for look-up table FAN _FA ULT THERM REF input, used as reference for
3 V to 5.5 V supply Small 16-lead QSOP package

APPLICATIONS

Desktop and notebook PCs Embedded systems Telecommunications equipment LCD projectors
V
CC 6
SMBUS
ADDRESS
SERIAL BUS
INTERFACE
ADDRESS
POINTER
REGISTER
STATUS
REGISTER
output
input, used to time
ALERT
THERM
MASK
REGISTERS
PROCHOT
assertions
THERM (PROCHOT
FAULT
QUEUE
)
16
SCL
15
SDA
8
FAN_FAULT
3
ALERT Comp
14
SMBusALERT
7
THERM
SRC
BLOCK
SENSOR
FAN SPEED
CONTROLLER
TACH SIGNAL
CONDITIONING
MULTIPLEXER
1
DRIVE
2
TACH
4
NC
8
REF
LOCATION
Rev. 0
Information furnished by Analog Devices is believed to be accurate and reliable. However, no responsibility is assumed by Analog Devices for its use, nor for any infringements of patents or other rights of third parties that may result from its use. Specifications subject to change without notice. No license is granted by implication or otherwise under any patent or patent rights of Analog Devices. Trademarks and registered trademarks are the property of their respective owners.
13
9
D–
10
D+
NC
11
12
NC
TEMPERATURE
NC = NO CONNECT
BAND GAP
ANALOG
FAN RESPONSE
SPEED
COUNTER
REFERENCE
FAN
ADC
BAND GAP
5
GND
COMPARATOR
VALUE AND REGISTERS
HYSTERESIS
REGISTERS
OFFSET
REGISTERS
CONVERSION
RATE REGISTER
CONFIGURATION
REGISTERS
Figure 1.
LIMIT
LIMIT
FAULT
QUEUE
THERM PERCENT
TIMER
04937-0-001
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A. Tel: 781.329.4700
www.analog.com
Fax: 781.326.8703 © 2004 Analog Devices, Inc. All rights reserved.
Page 2
ADM1033
TABLE OF CONTENTS
General Description ......................................................................... 3
Specifications..................................................................................... 4
Absolute Maximum Ratings............................................................ 6
Thermal Characteristics .............................................................. 6
ESD Caution.................................................................................. 6
Pin Configuration and Function Descriptions............................. 7
Typical Performance Characteristics ............................................. 8
Functional Description.................................................................. 10
Internal Registers........................................................................ 10
Serial Bus Interface..................................................................... 10
LOCATION Input...................................................................... 10
SMBus 2.0 ARP-Capable Mode................................................ 10
SMBus 2.0 Fixed-and-Discoverable Mode.............................. 12
SMBus 2.0 Read and Write Operations ................................... 12
Register Addresses for Single/Block Byte Modes................... 14
Write Operations ........................................................................14
Read Operations ......................................................................... 15
SMBus Timeout.......................................................................... 15
Packet Error Checking (PEC)................................................... 15
Alert Response Address (ARA)................................................ 15
Temperature Measurement System.............................................. 16
Internal Temperature Measurement........................................ 16
Handling
Interrupt Masking Register....................................................... 22
FAN_FAU LT
Fault Queue................................................................................. 23
Conversion Rate Register.......................................................... 23
THERM
THERM
Fan Drive Signal ......................................................................... 25
Synchronous Speed Control ..................................................... 25
Fan Inputs.................................................................................... 26
Fan Speed Measurement ........................................................... 26
Fan Speed Measurement Registers........................................... 27
Reading Fan Speed..................................................................... 27
Calculating Fan Speed ............................................................... 27
Alarm Speed................................................................................ 27
Look-Up Table: Modes of Operation....................................... 28
Look-Up Table ............................................................................ 28
Setting Up the Look-Up Table in Linear Mode...................... 29
Selecting which Temperature Channel Controls a Fan......... 29
Look-Up Table Hysteresis ......................................................... 29
Programming the
....................................................................................................... 30
SMBusALERT
Output ................................................................. 23
I/O Timer and Limits ................................................ 23
% Limit Register ......................................................... 24
Interrupts......................................... 22
THERM
Limit for Temperature Channels
Remote Temperature Measurement.........................................16
Additional Functions ................................................................. 18
Layout Considerations................................................................... 19
Limits, Status Registers, and Interrupts .......................................20
8-Bit Limits.................................................................................. 20
Out-of-Limit Comparisons....................................................... 20
Analog Monitoring Cycle Time................................................ 20
Status Registers ........................................................................... 20
ALERT
Interrupt Behavior........................................................ 21
Rev. 0 | Page 2 of 40
XOR Tree Test Mode.................................................................. 30
Lock Bit........................................................................................ 30
SW Reset...................................................................................... 30
Outline Dimensions....................................................................... 39
Ordering Guide .......................................................................... 39
REVISION HISTORY
8/04—Revision 0: Initial Version
Page 3
ADM1033

GENERAL DESCRIPTION

The ADM1033 is a remote and local temperature sensor and fan controller. Its remote channel accurately monitors the temperature of a remote thermal diode, which can be a discrete 2N3904/6 or located on a microprocessor die. The device can monitor its own ambient temperature as well.
The ADM1033 is also used to monitor and control the speed of a cooling fan. The user can program a target fan speed, or use the look-up table to input a temperature-to-fan speed profile. The look-up table can be configured to run the fan at discrete
speeds (discrete mode) or to ramp the fan speed with tempera­ture (linear mode).
The ADM1033 communicates over a 2-wire SMBus 2.0 inter­face. An 8-level LOCATION input allows the user to choose between SMBus 1.1 and SMBus 2.0.
The
THERM
THERM reference input for the
output indicates error conditions. In addition, the
ALERT
I/O signals overtemperature as an output and times
assertions as an input. Pin 8 can be configured as a
THERM
(
PROCHOT
) input.
Rev. 0 | Page 3 of 40
Page 4
ADM1033

SPECIFICATIONS

TA = T
Table 1.
Parameter Min Typ Max Units Test Conditions/Comments
POWER SUPPLY
TEMPERATURE-TO-DIGITAL CONVERTER
OPEN-DRAIN DIGITAL OUTPUTS (ALERT, THERM, FAN_FAULT DRIVE)
DIGITAL INPUT LEAKAGE CURRENT (TACH)
DIGITAL INPUT LOGIC LEVELS (TACH)
OPEN-DRAIN SERIAL DATA BUS OUTPUT (SDA)
SERIAL BUS DIGITAL INPUTS (SCL, SDA)
ANALOG INPUTS (LOCATION, REF)
to T
MIN
Supply Voltage, V
Supply Current, I
, VCC = V
MAX
CC
3 mA Interface inactive, ADC active
CC
to V
MIN
2
3.0 3.3 3.6 V
, unless otherwise noted.1
MAX
900 µA Standby mode
Undervoltage Lockout Threshold 2.5 V
Power-On Reset Threshold 1 2.4 V
Internal Sensor Accuracy ±1 ±2 °C 20°C ≤ TA ≤ 60°C
4
+2 °C
40°C ≤ T
≤ +100°C
A
Resolution 0.03125 °C
External Diode Sensor Accuracy ±0.5 ±1 °C
±1 °C
3
+2 °C
40°C ≤ T
40°C ≤ T
40°C ≤ T
≤ +100°C; TA = +40°C
D
≤ +100°C; +20°C ≤ TA ≤ +60°C
D
≤ +100°C; 40°C ≤ TA ≤ +100°C
D
Resolution 0.03125 °C
Remote Sensor Source Current 85 µA High level
34 µΑ Mid level
5 µΑ Low level
Series Resistance Cancellation 1000
Power Supply Sensitivity ±1 %/V
Conversion Time (Local Temperature) 11 ms Averaging enabled
Conversion Time (Remote Temperature) 32 ms Averaging enabled
Total Conversion Time 43 ms Averaging enabled
Output Low Voltage, VOL 0.4 V
High Level Output Leakage Current, IOH 0.1 1 µA V
Input High Current, IIH
1
µA VIN = VCC
I
= −6.0 mA; VCC = +3 V
OUT
= VCC; VCC = 3 V
OUT
Input Low Current, IIL 1 µA VIN = 0
Input Capacitance, CIN 7 pF
Input High Voltage, VIH 2.0 5.5 V
Input Low Voltage, VIL
0.3
+0.8 V
Hysteresis 500 mV p-p
Output Low Voltage, VOL 0.4 V
High Level Output Leakage Current, IOH 0.1 1 µA V
I
= −6.0 mA; VCC = +3 V
OUT
= VCC
OUT
Input High Voltage, VIH 2.1 V
Input Low Voltage, VIL 0.8 V
Hysteresis 500 mV
Input Resistance 80 125 160 kΩ
Rev. 0 | Page 4 of 40
Page 5
ADM1033
A
Parameter Min Typ Max Units Test Conditions/Comments
TACHOMETER ACCURACY
Fan Speed Measurement Accuracy ±4 %
AGTL + INPUT (THERM) Input High Level 0.75 × REF V Input Low Level 0.4 V SERIAL BUS TIMING3 See Figure 2
Clock Frequency, f
400 kHz
SCLK
Glitch Immunity, tSW 50 ns
Bus Free Time, t
Start Setup Time, t
Start Hold Time, t
Stop Condition Setup Time, t
SCL Low Time, t
SCL High Time, t
1.3 µs
BUF
0.6 µs
SU:STA
0.6 µs
HD:STA
0.6 µs
SU:STO
1.3 µs
LOW
0.6 µs
HIGH
SCL, SDA Rise Time, tr 1000 ns
SCL, SDA Fall Time, tf 300 ns
Data Setup Time, t
Detect Clock Low Timeout, t
100 ns
SU:DAT
25 35 ms See Note 4
TIMEOUT
1
Typicals are at TA = 25°C and represent most likely parametric norm. Standby current typ is measured with VCC = 3.3 V. Timing specifications are tested at logic levels of
= 0.8 V for a falling edge and VIH = 2.1 V for a rising edge.
V
IL
2
Operation at 5.5 V is guaranteed by design, not production tested.
3
Guaranteed by design, not production tested.
4
SMBus timeout disabled by default. See the SMBus Timeout section for more information.
SCL
SD
t
t
BUF
PS
HD:STA
t
LOW
t
R
t
HD:DAT
t
F
t
HIGH
t
SU:DAT
S
Figure 2. Serial Bus Timing Diagram
t
SU:STA
t
HD:STA
t
SU:STO
P
04937-0-003
Rev. 0 | Page 5 of 40
Page 6
ADM1033

ABSOLUTE MAXIMUM RATINGS

Table 2.
Parameter Value
Positive Supply Voltage (VCC)
Voltage on Any Input or Output Pin except FAN_FAULT and LOCATION
Voltage on FAN_FAULT1 Voltage on LOCATION VCC + 0.3V Input Current at Any Pin ±20 mA Maximum Junction Temperature (TJmax) 150°C Storage Temperature Range
Lead Temperature, Soldering (10 sec) 300°C IR Reflow Peak Temperature 220°C ESD Rating—All Pins 1500 V
0.3 V to +6.5 V
0.3 V to +6.5 V
V
CC
65°C to +150°C
1
During power-up, the voltage on
FAN_FAULT
should not be higher than VCC.

ESD CAUTION

ESD (electrostatic discharge) sensitive device. Electrostatic charges as high as 4000 V readily accumulates on the human body and test equipment and can discharge without detection. Although this product features proprietary ESD protection circuitry, permanent damage may occur on devices subjected to high energy electrostatic discharges. Therefore, proper ESD precautions are recommended to avoid performance degradation or loss of functionality.
Stresses above those listed under Absolute Maximum Ratings may cause permanent damage to the device. This is a stress rating only; functional operation of the device at these or any other conditions above those indicated in the operational section of this specification is not implied. Exposure to absolute maximum rating conditions for extended periods may affect device reliability.

THERMAL CHARACTERISTICS

16-Lead QSOP Package:
= 150°C/W, θJC = 39°C/W
θ
JA
Rev. 0 | Page 6 of 40
Page 7
ADM1033

PIN CONFIGURATION AND FUNCTION DESCRIPTIONS

1
DRIVE
2
TACH
NC
GND
V
THERM
3
ADM1033
TOP VIEW
4
(Not to Scale)
5
6
CC
7
8
NC = NO CONNECT
ALERT Comp
FAN_FAULT/REF D–
16
SCL
15
SDA
14
SMBusALERT
13
LOCATION
12
NC
11
NC
10
D+
9
04937-0-002
Figure 3. Pin Configuration
Table 3. Pin Function Descriptions
Pin No. Mnemonic Description
1 DRIVE DRIVE Pin Drives the Fan. Open-drain output. Requires a pull-up resistor. 2 TACH Fan Speed Measurement Input. Connects to the fan’s TACH output to measure the fan speed. 3
ALERT Comp Open-Drain Active Low Output. Asserts low whenever a measurement goes outside its programmed limits,
if not masked. Automatically goes high again when the measured parameter falls back within its limits. 4 NC No Connect. 5 GND Ground for Analog and Digital Circuitry. 6 VCC Power. Can be powered by 3.3 V standby power, if monitoring in low power states is required. 7
8
9
THERM Can be configured as an overtemperature interrupt output, or as an input to monitor PROCHOT output of
an INTEL CPU. A timer measures assertion times on the
THERM pin (either input or output).
FAN_FAULT/REF FAN_FAULT: Open-Drain Output. Asserts low whenever the fan stalls.
THERM input.
D
REF: Analog Input Reference for
Cathode Connection for the Thermal Diode or Diode-Connected Transistor. 10 D+ Anode Connection for the Thermal Diode or Diode-Connected Transistor.
11 NC No Connect. 12 NC No Connect. 13 LOCATION
8-Level Analog Input. Used to determine the correct SMBus version and the SMBus address (in fixed-and-
discoverable mode), and to set the LLL bits in the UDID (in ARP-capable mode). 14
SMBusALERT Open-Drain Output. Alerts the system in the case of out-of-limit events such as overtemperature. Can be
reset only with software. 15 SDA
Serial Bus Bidirectional Data. Connects to the SMBus master’s data line. Requires a pull-up resistor, if one is
not provided elsewhere in the system. 16 SCL
Serial SMBus Clock Input. Connects to the SMBus master’s clock line. Requires a pull-up resistor, if one is
not provided elsewhere in the system.
Rev. 0 | Page 7 of 40
Page 8
ADM1033

TYPICAL PERFORMANCE CHARACTERISTICS

40
20
0
–20
–40
–60
TEMPERATURE ERROR (°C)
–80
D+ TO GND
D+ TO V
CC
20
15
10
5
0
TEMPERATURE ERROR (°C)
–5
EXT 100mV p-p EXT 250mV p-p
–100
0 10203040 5060 708090100
LEAKAGE RESISTANCE (M)
Figure 4. Temperature Error vs. PCB Track Resistance, DXP to GND and V
0
–10
–20
–30
–40
–50
–60
TEMPERATURE ERROR (°C)
–70
–80
0426810
DEV 32 (°C)
CAPACITANCE (nF)
DEV 33 (°C)
DEV 31 (°C)
12
Figure 5. Remote Temperature Error vs. D+, D− Capacitance
100
90 80 70 60 50 40 30 20
TEMPERATURE ERROR (°C)
10
0
–10
12 3 4 65
SERIES RESISTANCE IN D+/D– LINES (k)
DEV 33
DEV 31
DEV 32
Figure 6. Remote Temperature Error vs. Series Resistance on D+ and D−
04937-0-004
CC
04937-0-005
04937-0-006
–10
01M2M3M4M 65M
04937-0-007
M
Figure 7. Remote Temperature Error vs. Power Supply Noise Frequency
50
45 40 35
30
25
20 15
TEMPERATURE ERROR (°C)
10
5
00
01M2M 4M3M 5M 6M
NOISE FREQUENCY (Hz)
100mV
20mV
50mV
04937-0-008
Figure 8. Remote Temperature Error vs. Common-Mode Noise Frequency
Coupled on D+ and D−
4.0
3.5
3.0
2.5
2.0
1.5
1.0
TEMPERATURE ERROR (°C)
0.5
0
01M 3M2M 5M4M 6M
NOISE FREQUENCY
20mV
10mV
04937-0-009
Figure 9. Remote Temperature Error vs. Differential-Mode Noise Frequency
Coupled on D+ and D−
Rev. 0 | Page 8 of 40
Page 9
ADM1033
2
1
0
–1
–2
–3
–4
TEMPERATURE ERROR (°C)
–5
–6
–7
S1 S2 S3 S4 S5
–60 –40 –20 0 80 100 12040 6020 140
V1 V2 V3 V4 V5
DIODE TEMPERATURE (
MEAN
°
HIGH 4 SIGMA
LOW 4 SIGMA
C)
Figure 10. Remote Temperature Error vs. Actual Diode Temperature
2
1
0
–1
–2
–3
ERROR (°C)
–4
–5
–6
–7
S1 S2 S3 S4 S5
–50 0 10050 150
V1 V2 V3 V4 V5
TEMPERATURE (°C)
HIGH 4 SIGMA
MEAN
LOW 4 SIGMA
Figure 11. Local Temperature Error vs. Actual Temperature
430
04937-0-010
04937-0-011
0.7
0.6
0.5
0.4
0.3
0.2
STANDBY SUPPLY CURRENT
0.1
0
024531
SUPPLY VOLTAGE (V)
Figure 13. Standby Supply Current vs. Supply Voltage
1200
1000
800
(µA)
600
CC
I
400
DEV 33
200
0
0.01 0.1 1 10010
DEV 31
DEV 32
CONVERSION RATE (Hz)
Figure 14. Supply Current vs. Conversion Rate
1.55
04937-0-013
6
04937-0-014
420
410
400
(µA)
CC
I
390
380
370
360
1 10 1000100
Figure 12. Standby Supply Current vs. SCLK Frequency
FSCL (kHz)
DEV 31
DEV 33
DEV 32
04937-0-012
1.50
1.45
1.40
1.35
SUPPLY CURRENT
1.30
1.25 –60 –40 –20 0 10040 60 8020
TEMPERATURE (°C)
Figure 15. Supply Current vs. ADM1033 Temperature
04937-0-015
Rev. 0 | Page 9 of 40
Page 10
ADM1033
0
0

FUNCTIONAL DESCRIPTION

The ADM1033 is a local and remote temperature monitor and fan controller used in a variety of applications, including microprocessor-based systems. The device accurately monitors remote and ambient temperature and uses that information to quietly control the speed of a cooling fan. Whenever the fan stalls, the device asserts a
The ADM1033 has a assertions on the
THERM
FAN_FAU LT
THERM
I/O. As an input, this measures
pin. As an output, it asserts a low
signal to indicate when the measured temperature exceeds the programmed
THERM
temperature limits. The ADM1033
communicates over an SMBus 2.0 interface. Its LOCATION input determines which version of SMBus to use, as well as the SMBus address (in fixed-and-discoverable mode), and the LOCATION bits in the UDID (in ARP-capable mode).

INTERNAL REGISTERS

Table 4 gives a brief description of the ADM1033’s principal internal registers. For more detailed information on the function of each register, refer to .

SERIAL BUS INTERFACE

The ADM1033 communicates with the master via the 2-wire SMBus 2.0 interface. It supports two SMBus 2.0 versions, determined by the value of the LOCATION input resistors.
The first version is fully ARP-capable. This means that it supports address resolution protocol (ARP), allowing the master to dynamically address the device on power-up. It responds to ARP commands such as “Prepare to ARP.”
The second SMBus version, fixed-and-discoverable, is backward-compatible with SMBus 1.0 and 1.1. In this mode, the ADM1033 powers up with a fixed address, which is determined by the state of the LOCATION pin on power-up. Note: when using the ADM1033, addresses 0xC2 and 0xCA should not be used by any other device on the bus.

LOCATION INPUT

The LOCATION input is a resistor divider input. It has multiple functions and can specify the following: the SMBus version (in fixed-and-discoverable or ARP-capable modes); the SMBus address (in fixed-and-discoverable mode); and the LLL bits (in UDID in ARP-capable mode).
The voltage of this 8-level input is set by a potential divider. The voltage on LOCATION is sampled on power-up and digitized by the on-chip ADC to determine the LOCATION input value. Because the LOCATION input is sampled only at power-up, changes made while power is applied have no effect.
output.
V
CC
R1
R2
GND
Figure 16. Bootstrapping the LOCATION Input
PIN 13
ADM1033
LOCATION
04937-0-016

SMBus 2.0 ARP-CAPABLE MODE

In ARP-capable mode, the ADM1033 supports such features as address resolution protocol (ARP) and unique device identifier (UDID). The UDID is a 128-bit message that describes the ADM1033’s capabilities to the master. The UDID also includes a vendor-specific ID for functionally equivalent devices.
V
CC
LOCATION = 111
LOCATION = 11
LOCATION = 101
LOCATION = 10
ADDRESS = 53h
ADDRESS = 52h
ADDRESS = 51h
ADDRESS = 50h
Figure 17. Setting Up Multiple ADM1033 Addresses
ARP
1.5k
ARP
1k
ARP
1k
ARP
1k
FD
1k
FD
1k
FD
1.5k
FD
GND
In SMBus 2.0 mode, this vendor-specific ID is generated by an on-chip random number generator. This should enable two adjacent ADM1033s in the same system to power-up with a different vendor-specific ID, allowing the master to identify the two separate ADM1033s and assign a different address to each. The state of the LOCATION input on power-up is also reflected in the UDID. This is useful when there are more than one ADM1033 in the system, so the master knows which one it is communicating with. The UDID values are listed in Table 6.
The SMBus 2.0 master issues both general and directed ARP commands. A general command is directed at all ARP devices. A directed command is targeted at a single device, once an address has been established. The PEC byte must be used for ARP commands (refer to Packet Error Checking (PEC)). The ADM1033 responds to the following commands:
Prepare to ARP (general)
Reset device (general and directed)
Get UDID (general and directed)
Assign address (general)
ADM1033 NO. 1
ADM1033 NO. 2
ADM1033 NO. 3
ADM1033 NO. 4
ADM1033 NO. 5
ADM1033 NO. 6
ADM1033 NO. 7
ADM1033 NO. 8
04937-0-017
Rev. 0 | Page 10 of 40
Page 11
ADM1033
Table 4. Internal Register Descriptions
Register Description
Configuration Provides control and configuration of various functions on the device. Conversion Rate Determines the number of measurements per second completed by the ADM1033. Address Pointer
Status Provides the status of each limit comparison. Interrupt Mask Value and Limit Stores the results of temperature and fan speed measurements, along with their limit values. Offset
THERM Limit and Hysteresis Look-Up Table Used to program the look-up table for the fan-speed-to-temperature profile.
THERM % Ontime and THERM % Limit
Table 5. Resistor Ratios for Setting LOCATION Bits
Ideal Ratio R2/(R1 + R2) R1 (kΩ) R2 (kΩ) Actual R2/(R1 + R2) Error (%) SMBus Mode SMBus Address UDID LLL
N/A 0 O/C 1 0 ARP1 N/A 111
0.8125 18 82 0.82 +0.75 ARP1 N/A 110
0.6875 22 47 0.6812 −0.63 ARP1 N/A 101
0.5625 12 15 0.5556 −0.69 ARP1 N/A 100
0.4375 15 12 0.4444 +0.69 FD1 0x53 N/A
0.3125 47 22 0.3188 +0.63 FD1 0x52 N/A
0.1875 82 18 0.18 −0.75 FD1 0x51 N/A N/A O/C 0 0 0 FD1 0x50 N/A
1
FD denotes fixed-and-discoverable mode, ARP denotes ARP-capable mode.
Contains the address that selects one of the other internal registers. When writing to the ADM1033, the first byte of data is always a register address, which is written to the address pointer register.
Allows the option to mask
Allows the local and remote temperature channel readings to be offset by a twos complement value written to them. These values are automatically added to the temperature values (or subtracted from them if negative). This allows the systems designer to optimize the system, if required, by adding or subtracting up to 15.875°C from a temperature reading.
Contains the temperature value at which THERM is asserted and determines the level of hysteresis.
Reflects the state of the percentage of a time window. The user can program the length of the time window.
ALERTs due to particular out-of-limit conditions.
THERM input and monitors the duration of the assertion time of the signal as a
Table 6. UDID Values
Bit No. Name Function Value
<127:120> Device Capabilities
<1119:112> Version/Revision: UDID version number (Version 1) and silicon revision identification 00001010 <111:96> Vendor ID
<95:80> Device ID Device ID
<79:64> Interface
<63:48> Subsystem Vendor ID Subsystem Vendor ID = 0 (subsystem fields are unsupported)
<47:32> Subsystem Device ID Subsystem Device ID = 0 (subsystem fields are unsupported)
<31:0> Vendor-Specific ID
Describes the ADM1033’s capabilities (for instance, that it supports PEC and uses a random number address device)
Vendor ID number, assigned by the SBS Implementer’s Forum or the PCI SIG
Identifies the protocol layer interfaces supported by the ADM1033. This represents SMBus 2.0 as the Interface version.
A unique number per device. Contains the LOCATION Information (LLL) and a 16-bit random number (x). See Table 5 for information on setting the LLL bits.
11000001
00010001 11010100
00010000 00110011
00000000 00000100
00000000 00000000
00000000 00000000
00000000 00000LLL xxxxxxxx xxxxxxxx
Rev. 0 | Page 11 of 40
Page 12
ADM1033

SMBus 2.0 FIXED-AND-DISCOVERABLE MODE

The ADM1033 supports fixed-and-discoverable mode, which is backward-compatible with SMBus 1.0 and 1.1. Fixed-and­discoverable mode supports all the same functionality as ARP­capable mode, except for assign address—in which case it powers up with a fixed address and is not changed by the assign address call. The fixed address is determined by the state of the LOCATION pin on power-up.

SMBus 2.0 READ AND WRITE OPERATIONS

The master initiates a data transfer by establishing a start condition, defined as a high-to-low transition on the serial data line (SDA) while the serial clock line (SCL) remains high. This indicates that an address/data stream is to follow. All slave peripherals connected to the serial bus respond to the start condition and shift in the next eight bits, which consist of a 7­bit address (MSB first) plus an R/
the direction of the data transfer (whether data is written to or read from the slave device).
1. The peripheral that corresponds to the transmitted address
responds by pulling the data line low during the low period before the 9 acknowledge bit. All other devices on the bus remain idle while the selected device waits for data to be read from or written to it. If the R/
slave device. If the R/
th
clock pulse. This pulse is known as the
W W
bit. The last bit determines
W
bit is a 0, the master writes to the bit is a 1, the master reads from it.
It is not possible to mix read and write in one operation, because the type of operation is determined at the beginning and cannot be changed without starting a new operation.
To write data to one of the device data registers or read data from it, the address pointer register (APR) must be set so that the correct data register is addressed. The first byte of a write operation always contains an address that is stored in the APR. If data is to be written to the device, the write operation contains a second data byte. The second data byte is written to the register selected by the APR.
As shown in Figure 18, the device address is sent over the bus, followed by R/
The first data byte is the address of the designated internal data register, which is stored in the APR. The second data byte is the data to be written to the internal data register.
When reading data from a register there are two possibilities:
If the ADM1033’s APR value is unknown or incorrect, it
must be set to the correct value before data can be read from the desired data register. To do this, perform a write to the ADM1033 as before; but this time send only the data byte containing the register. (See Figure 19.) A read operation is then performed. With the serial bus address and the R/
register. (See Figure 20.)
set to 0. This is followed by two data bytes.
W
bit set to 1, the data byte is read from the data
W
2. Data is sent over the serial bus in sequences of nine clock
pulses—eight bits of data followed by an acknowledge bit from the slave device. Transitions on the data line must occur during the low period of the clock signal and remain stable during the high period, as a low-to-high transition when the clock is high might be interpreted as a stop signal. The number of data bytes that can be transmitted over the serial bus in a single read or write operation is limited only by what the master and slave devices can handle.
3. When all data bytes have been read or written, stop
conditions are established. In write mode, the master pulls the data line high during the tenth clock pulse to assert a stop condition. In read mode, the master device overrides the acknowledge bit by pulling the data line high during the low period before the ninth clock pulse. This is known as no acknowledge. The master takes the data line low during the low period before the tenth clock pulse, then high during the tenth clock pulse to assert a stop condition.
If the APR is known to be already at the desired address,
data can be read from the corresponding data register without first writing to the APR. In this case, Figure 19 can be omitted.
In Figure 18 to Figure 20, the serial bus address is determined by the state of the LOCATION pin on power-up.
Rev. 0 | Page 12 of 40
Page 13
ADM1033
SDA
119
SCL
9
SDA
START BY
MASTER
A6
A5 A4 A3 A2 A1 A0 R/W D7
FRAME 1
SERIAL BUS ADDRESS BYTE
SCL (CONTINUED)
SDA (CONTINUED)
ACK. BY
ADM1033
D7 D6 D5 D4 D3
D6 D5 D4 D3 D2 D1 D0
ADDRESS POINTER REGISTER BYTE
FRAME 2
FRAME 3
DATA BYTE
D2
D1 D0
ACK. BY
ADM1033
ACK. BY
ADM1033
91
STOP BY MASTER
04937-0-021
Figure 18. Writing a Register Address to the Address Pointer Register, then Writing Data to the Selected Register
SCL
SDA
START BY
MASTER
119
A6 A5 A4 A3 A2 A1 A0 R/W D7
ACK. BY
FRAME 1
SERIAL BUS ADDRESS BYTE
ADM1033
Figure 19. Writing to the Address Pointer Register Only (Send Byte)
D6 D5 D4 D3 D2 D1 D0
ADDRESS POINTER REGISTER BYTE
FRAME 2
9
ACK. BY
ADM1033
STOP BY MASTER
04937-0-022
119 9
SCL
R/W
ACK. BY
ADM1033
FRAME 2
DATA BYTE FROM ADM1033
NO ACK. BY
ADM1033
STOP BY MASTER
04937-0-023
START BY
MASTER
A6 A5 A4 A3 A2 A1 A0 D7 D6 D5 D4 D3 D2 D1 D0
FRAME 1
SERIAL BUS ADDRESS BYTE
Figure 20. Reading Data from a Previously Selected Register
Rev. 0 | Page 13 of 40
Page 14
ADM1033

REGISTER ADDRESSES FOR SINGLE/BLOCK BYTE MODES

The ADM1033 supports single-byte and multiple-byte (block) read and write operations. The register address determines whether a single-byte or block operation is run. For a single­byte operation, the MSB of the register address is set to 0; for a multiple-byte operation, it is set to 1. The number of bytes read from the ADM1033 in a multiple-byte operation is set in the #Bytes/Block Read Register at Address 0x00. The number of bytes written to it is specified in the block-write operation. The addresses quoted in the register map and throughout this data sheet assume single-byte operation. For multiple-byte opera­tions, set the MSB of each register address to 1.
The SMBus specifications define protocols for different types of read and write operations. The ADM1033 supports the following SMBus write protocols: send byte, write byte, block write, receive byte, and block read. The following abbreviations are used in the diagrams:
S—START
P—STOP
R—REA D
W—W RI TE
A—AC KNOWLEDGE
—NO ACKNOWLEDGE
A

WRITE OPERATIONS

Send Byte
In this operation, the master device sends a single-command byte to a slave device as follows:
1. The master device asserts a start condition on SDA.
2. The master sends a 7-bit address followed by the write bit
(low).
3. The addressed slave device asserts ACK on SDA.
4. The master sends the register address.
5. The slave asserts ACK on SDA.
6. The master asserts a stop condition on SDA, and the
transaction ends.
SLAVE
S
ADDRESS
Figure 21. Send Byte
The ADM1033 uses the send-byte operation to write a register address to the APR for a subsequent read from the same address. This is illustrated in Figure 21. The user may be required to read data from the register immediately after setting up the address. If so, the master can assert a repeat start condition immediately after the final ACK and carry out a single-byte read without asserting an intermediate stop condition.
REG
W A A P
ADDRESS
04937-0-018
Write Byte
In this operation, the master device sends the register address and one data byte to the slave device as follows:
1. The master asserts a start condition on SDA.
2. The master sends the 7-bit slave address followed by a
write bit (low).
3. The addressed slave device asserts ACK on SDA.
4. The master sends the register address. The MSB of the
command code should equal 0 for a write-byte operation. If the MSB equals 1, a block-write operation takes place.
5. The slave asserts ACK on SDA.
6. The master sends a data byte.
7. The slave asserts ACK on SDA.
8. The master asserts a stop condition on SDA to end the
transaction.
S
ADDRESS
SLAVE
REG
W
A
ADDRESS
Figure 22. Write Byte
A
DATA
A
P
04937-0-019
Block Write
In this operation, the master device writes a block of data to a slave address as follows. A maximum number of 32 bytes can be written.
1. The master asserts a start condition on SDA.
2. The master sends the 7-bit slave address followed by a write
bit (low).
3. The addressed slave device asserts ACK on SDA.
4. The master sends the register address. This register address
sets up the address pointer register and determines if a block write (MSB = 1) or a byte write (MSB = 0) takes place.
5. The slave asserts ACK on SDA.
6. The master sends the byte count.
7. The slave asserts ACK on SDA.
8. The master sends N data bytes.
9. The slave asserts ACK on SDA after each byte.
10. The master asserts a stop condition on SDA to end the
transaction.
S
ADDRESS
SLAVE
REGISTER
A
W
ADDRESS
BYTE
COUNT
A
DATA 1
A
Figure 23. Block Write
DATA 2
A
A DATA N
P
A
04918-0-020
Rev. 0 | Page 14 of 40
Page 15
ADM1033

READ OPERATIONS

Receive Byte
This operation is useful when repeatedly reading a single register. The register address must be set up prior to this, with the MSB at 0 to read a single byte. In this operation, the master device receives a single byte from a slave device as follows:
1. The master device asserts a start condition on SDA.
2. The master sends the 7-bit slave address followed by the
read bit (high).
3. The addressed slave device asserts ACK on SDA.
4. The master receives a data byte.
5. The master sends NO ACK on SDA.
6. The master asserts a stop condition on SDA and the
transaction ends.
In the ADM1033, the receive-byte protocol is used to read a single byte from a register whose address has previously been set by a send-byte or write-byte operation.
SLAVE
S
ADDRESS
Figure 24. Receive Byte
Block Read
In this operation, the master reads a block of data from a slave device. The number of bytes to be read must be set in advance. To d o th is , u se a write-byte operation to the #Bytes/Block Read Register at Address 0x00. The register address determines whether a block-read or a read-byte operation is to be completed (set MSB to 1 to specify a block-read operation). A maximum number of 32 bytes can be read.
1. The master asserts a start condition on SDA.
2. The master sends the 7-bit slave address followed by the
write bit (low).
3. The addressed slave device asserts ACK on SDA.
4. The master sends the register address (MSB = 1).
5. The slave asserts ACK on SDA.
6. The master asserts a repeated start on SDA.
7. The master sends the 7-bit slave address followed by the
read bit (high).
8. The slave asserts ACK on SDA.
9. The slave sends the byte count.
10. The master asserts ACK on SDA.
11. The slave sends N data bytes.
12. The master asserts ACK on SDA after each data byte.
13. The master does not acknowledge after the Nth data byte.
14. The master asserts a stop condition on SDA to end the
transaction.
DATAR A A P
04937-0-024
S
SLAVE
ADDRESS
REGISTER
A
W
ADDRESS
Figure 25. Block Read from RAM
SLAVE
S
A
ADDRESS

SMBus TIMEOUT

The ADM1033 has a programmable SMBus timeout feature. When this is enabled, the SMBus typically times out after 25 ms of no activity. The timeout is disabled by default. It prevents SMBus hangups by releasing the bus after a period of inactivity.
To enable the SDA timeout, set the SDA timeout bit (Bit 5) of Configuration Register 1 (Address 0x01) to 1.
To enable the SCL timeout, set the SCL timeout bit (Bit 4) of Configuration Register 1 (Address 0x01) to 1.

PACKET ERROR CHECKING (PEC)

The ADM1033 supports packet error checking (PEC). This optional feature is triggered by the extra clock for the PEC byte. The PEC byte is calculated using CRC-8. The frame check sequence (FCS) conforms to CRC-8 by the following:
28
1)(
+++= xxxxC
For more information, consult www.SMBus.org.

ALERT RESPONSE ADDRESS (ARA)

ALERT RESPONSE
S
ADDRESS
Figure 26. Alert Response Address
When multiple devices exist on the same bus, the alert response address (ARA) feature allows an interrupting device to identify itself to the host. The
output or as an
ALERT
SMBALERT be connected to a common connected to the master. If a device’s following procedure occurs:
1.
SMBALERT
is pulled low.
2. The master initiates a receive-byte operation and sends the
alert response address (ARA 0001 100). This is a general call address that must not be used as a specific device address.
3. The device with the low
ARA, and the master reads its device address. Once the address is known, it can be interrogated in the usual way.
4. If low
output is detected in more than one device,
ALERT the one with the lowest device address has priority, in accordance with normal SMBus arbitration.
5. Once the ADM1033 has responded to the ARA, it resets its
output. If the error persists, the
ALERT asserted on the next monitoring cycle.
R A A P
output can be used as an interrupt
. One or more
SMBALERT
ALERT
BYTE
A
R
COUNT
DEVICE
ADDRESS
ALERT
A
DATA 1
A DATA N
04937-0-043
outputs can
line, which is
line goes low, the
ALERT
output responds to the
is re-
ALERT
A
P
04918-0-025
Rev. 0 | Page 15 of 40
Page 16
ADM1033

TEMPERATURE MEASUREMENT SYSTEM

INTERNAL TEMPERATURE MEASUREMENT

The ADM1033 contains an on-chip band gap temperature sensor. The on-chip ADC performs conversions on the sensor’s output and outputs the temperature data in 13-bit format. The resolution of the local temperature sensor is 0.03125°C.
Table 7 shows the format of the temperature data MSBs. Table 8 shows the local and remote sensor extended resolution data for the LSBs. To ensure accurate readings, the LSBs should be read first. This locks the current LSBs and MSBs until the MSBs are read. They then start to update again. (Reading only the MSBs does not lock the registers.) Temperature updates to the look-up table take place in parallel, so fan speeds can be updated even if the MSBs are locked.
Table 7. Temperature Data Format for Local and Remote Temperature High Bytes
Temperature (°C) Digital Output
−64 0000 0000
−40 0001 1000
−32 0010 0000
−2 0011 1110
−1 0011 1111 0 0100 0000 1 0100 0001 2 0100 0010 10 0100 1010 20 0101 0100 50 0111 0010 75 1000 1011 100 1010 0100 125 1011 1101 150 1101 0110 191 1111 1111
Table 8. Local and Remote Sensor Extended Resolution
Extended Resolution (°C) Temperature Low Bits
0.0000 00000
0.03125 00001
0.0625 00010
0.125 00100
0.250 01000
0.375 01100
0.500 10000
0.625 10100
0.750 11000
0.875 11100
Te mp e ra t ur e (°C) = (MSB − 64°C) + (LSB × 0.03125)
Example: MSB = 0101 0100 = 84d
LSB = 11100 = 14
Te mp e ra t ur e °C = (84 − 64) + (28 × 0.03125) = 20.875

REMOTE TEMPERATURE MEASUREMENT

The ADM1033 measures the temperature of one external diode sensor or diode-connected transistor, which is connected to Pins 9 and 10. These pins are dedicated temperature input channels. The series resistance cancellation (SRC) feature can automatically cancel out the effect of up to 1 kΩ of resistance in series with the remote thermal diode.
The forward voltage of a diode or diode-connected transistor, operated at a constant current, exhibits a negative temperature coefficient of about −2 mV/°C. Unfortunately, the absolute value of V calibration is required to null this out. Therefore, the technique is unsuitable for mass production.
2N3906
varies from device to device, and individual
BE
ADM1033
D+
D–
Figure 27. Measuring Temperature Using Discrete Transistors
2N3904
ADM1033
D+
D–
04937-0-026
Rev. 0 | Page 16 of 40
Page 17
ADM1033
T
R
N2 × I
IN1×I
D+
REMOTE SENSING
RANSISTO
D–
Figure 28. ADM1033 Signal Conditioning
The ADM1033 operates at three different currents to measure the change in V
.
BE
Figure 28 shows the input signal conditioning used to measure the output of an external temperature sensor. It also shows the external sensor as a substrate transistor, provided for temperature monitoring on some microprocessors. The external sensor works equally well as a discrete transistor.
If a discrete transistor is used, the collector is not grounded and should be linked to the base. If a PNP transistor is used, the base is connected to the D− input and the emitter to the D+ input. If an NPN transistor is used, the emitter is connected to the D− input and the base to the D+ input.
If the sensor is used in a very noisy environment, a capacitor value of up to 1000 pF can be placed between the D+ and D− inputs to filter the noise. However, additional parasitic capaci­tance on the lines between D+, D−, and the thermal diode should also be considered. The total capacitance should never be greater than 1000 pF.
To m e as ur e ea ch Δ V
, the sensor is switched between operat-
BE
ing currents of I, (N1 × I), and (N2 × I). The resulting waveform is passed through a 65 kHz low-pass filter to remove noise, then to a chopper-stabilized amplifier that amplifies and rectifies the waveform. This produces a dc voltage proportional to ∆V
.
BE
These measurements are used to determine the temperature of the thermal diode, while automatically compensating for any series resistance on the D+ and/or D− lines. The temperature is stored in two registers as a 13-bit word.
I
BIAS
LOW-PASS FILTER
f
= 65kHz
C
To further reduce the effects of noise, digital filtering is per­formed by averaging the results of 16 measurement cycles at conversion rates of less than 16 Hz. An external temperature measurement takes nominally 32 ms when averaging is enabled and 6 ms when averaging is disabled.
One LSB of the ADC corresponds to 0.03125°C. The ADM1033 can theoretically measure temperatures from −64°C to +191.96875°C, although −64°C and +191°C are outside its operating range. The extended temperature resolution data format is shown in Table 8. The extended temperature resolution for the local and remote channels is stored in the extended temperature resolution registers (Reg. 0x40 = Local, Reg. 0x42 = Remote).
Table 9. Temperature Measurement Registers
Register Description Default
0x40 Local Temperature, LSBs 0x00 0x41 Local Temperature, MSBs 0x00 0x42 Remote Temperature, LSBs 0x00 0x43 Remote Temperature, MSBs 0x00
High and low temperature limit registers are associated with each temperature measurement channel. The appropriate status bit is set when the high and low limits are exceeded. Exceeding either limit can cause an
Table 10. Temperature Measurement Limit Registers
Register Description Default
0x0B Local High Limit 0x8B (75°C) 0x0C Local Low Limit 0x54 (20°C) 0x0D
0x0E Remote High Limit 0x8B (75°C) 0x0F Remote Low Limit 0x54 (20°C) 0x10
V
DD
V
OUT+
TO ADC V
OUT–
04937-0-027
interrupt.
0x95 (85°C)
0x95 (85°C)
THERM Limit
Local
Remote
SMBALERT
THERM Limit
Rev. 0 | Page 17 of 40
Page 18
ADM1033

ADDITIONAL FUNCTIONS

Several other temperature measurement functions available on the ADM1033 offer the systems designer added flexibility.

Turn-Off Averaging

The ADM1033 performs averaging at conversion rates of less than or equal to eight conversions per second. This means that the value in the measurement register is the average of 16 meas­urements. For faster measurements, set the conversion rate to 16 conversions per second or greater. (Averaging is not carried out at these conversion rates.) Or, to switch off averaging at the slower conversion rates, set Bit 1 (AVG) of Configuration 1 Register (Address 0x01).

Single-Channel ADC Conversions

In normal operating mode, the ADM1033 converts on both the local temperature and remote channels. However, the user can set the ADM1033 to convert on one channel only. To enable single-channel mode, set the round robin bit (Bit 7) in Configuration Register 2 (Address 0x02) to 0. When the round robin bit equals 1, the ADM1033 converts on both temperature channels. In single-channel mode, it converts on one channel only, to be determined by the state of the channel selector bit (Bit 4) of Configuration Register 2 (Address 0x02).
Table 11. Channel Selector
Bit 4 Channel Selector (Configuration 2)
0 Local Channel (default) 1 Remote Channel

Removing Temperature Errors

As CPUs run faster and faster, it becomes more difficult to avoid high frequency clocks when routing the D+ and D− traces around a system board. Even when recommended layout guidelines are followed, temperature errors attributed to noise coupled onto the D+ and D− lines remain. High frequency noise generally gives temperature measurements that are too high by a constant amount. The ADM1033 has local and remote temperature offset registers at Addresses 0x16 and 0x17—one for each channel. By completing a one-time calibration, the user can determine the offset caused by the system board noise and remove it using the offset registers. The registers automatically add a twos complement word to the remote temperature meas­urements, ensuring correct readings in the value registers.
Table 12. Offset Registers
Registration Description Default
0x16 Local Offset 0x00 0x17 Remote Offset 0x00
Table 13. Offset Register Values
Code Offset Value
0 0000 000 0°C (Default) 0 0000 001 0.125°C 0 0000 111 0.875°C 0 0001 111 1.875°C 0 0111 111 7.875°C 0 1111 111 15.875°C 1 0000 000 −16°C 1 1111 000 −0.875°C
Rev. 0 | Page 18 of 40
Page 19
ADM1033
T

LAYOUT CONSIDERATIONS

Digital boards can be electrically noisy environments. Be sure to protect the analog inputs from noise, particularly when measuring the very small voltages from a remote diode sensor. Take the following precautions:
Place the ADM1033 as close as possible to the remote
sensing diode. A distance of 4 inches to 8 inches is adequate, provided that the worst noise sources such as clock generators, data/address buses, and CRTs are avoided.
If the distance to the remote sensor is more than 8 inches,
twisted pair cable is recommended. This works up to about 6 feet to 12 feet.
For very long distances (up to 100 feet), use shielded
twisted pair such as Belden #8451 microphone cable. Connect the twisted pair to D+ and D− and the shield to GND, close to the ADM1033. Leave the remote end of the shield unconnected to avoid ground loops.
Route the D+ and D− tracks close together, in parallel, with
grounded guard tracks on each side. Provide a ground plane under the tracks if possible.
Use wide tracks to minimize inductance and reduce noise
pickup. A minimum of 5 mil track width and spacing is recommended.
Try to minimize the number of copper/solder joints, which
can cause thermocouple effects. Where copper/ solder joints are used, make sure that they are in both the D+ and D− path and at the same temperature. Thermocouple effects should not be a major problem because 1°C corresponds to about 200 µV, and thermocouple voltages are about 3 µV/°C of temperature difference. Unless there are two thermocouples with a big temperature differential between them, thermocouple voltages should be much less than 200 µV.
GND
D+
D–
GND
Figure 29. Arrangement of Signal Tracks
5MIL 5MIL 5MIL 5MIL 5MIL 5MIL 5MIL
04937-0-028
Place a 0.1 µF bypass capacitor close to the ADM1033.
Because the measurement technique uses switched current sources, excessive cable and/or filter capacitance can affect the measurement. When using long cables, the filter capacitor C1 may be reduced or removed. In any case, the total shunt capacitance should never exceed 1000 pF.

Noise Filtering

For temperature sensors operating in noisy environments, common practice is to place a capacitor across the D+ and D− pins to help combat the effects of noise. However, large capacitan­ces affect the accuracy of the temperature measurement, leading to a recommended maximum capacitor value of 1000 pF. While this capacitor reduces the noise, it does not eliminate it, making it difficult to use the sensor in a very noisy environment.
The ADM1033 has a major advantage over other devices when it comes to eliminating the effects of noise on the external sen­sor. The series resistance cancellation feature allows a filter to be constructed between the external temperature sensor and the part. The effect of any filter resistance seen in series with the remote sensor is automatically cancelled from the temperature result.
The construction of a filter allows the ADM1033 and the remote temperature sensor to operate in noisy environments. Figure 30 shows a low-pass R-C-R filter with the following values: R = 100 Ω and C = 1 nF. This filtering reduces both common-mode noise and differential noise.
100
REMOTE
EMPERATURE
SENSOR
Figure 30. Filter Between R emote Sensor and ADM1033
100
1nF
D+
D–
04110-0-009
Rev. 0 | Page 19 of 40
Page 20
ADM1033

LIMITS, STATUS REGISTERS, AND INTERRUPTS

High and low limits are associated with each measurement channel on the ADM1033 and form the basis of system status monitoring. The user can set a status bit for any out-of-limit condition and detect it by polling the device. Alternatively, SMBusALERT microcontroller of an out-of-limit condition.

8-BIT LIMITS

Table 14 and Table 15 list all the 8-bit limits on the ADM1033:
Table 14. Temperature Limit Registers
Register Description Default
0x0B Local High Limit 0x8B (75°C) 0x0C Local Low Limit 0x54 (20°C) 0x0D
0x0E Remote High Limit 0x8B (75°C) 0x0F Remote Low Limit 0x54 (20°C) 0x10
Table 15.
Register Description Default
0x19

OUT-OF-LIMIT COMPARISONS

The ADM1033 measures all parameters in a round-robin format and sets the appropriate status bit for out-of limit conditions. Comparisons are made differently, depending on whether the measured value is compared to a high or low limit.
s can be generated to flag a processor or
THERM Limit
Local
Remote
THERM
THERM % Limit
THERM Limit
Limit Register
0x95 (85°C)
0x95 (85°C)
0xFF
The ADC performs round-robin conversions and takes 11 ms for the local temperature measurement and 32 ms for each remote temperature measurement with averaging enabled.
The total monitoring cycle time for the average temperatures is, therefore, nominally
32 + 11 = 43 ms
Once the conversion time elapses, the round robin starts again. For more information, refer to the Conversion Rate Register section.
Fan TACH measurements take place in parallel and are not synchronized with the temperature measurements.

STATUS REGISTERS

The results of limit comparisons are stored in the status registers. A 1 represents an out-of-limit measurement; a 0 represents an in-limit measurement. The status registers are located at Addresses 0x4F to 0x51.
If the measurement is outside its limits, the corresponding status register bit is set to 1. It remains set at 1 until the measurement falls back within its limits and either the status register is read or an ARA is completed.
To poll the state of the various measurements, read the status registers over the serial bus. If Bit 0 (
Register 3 (Address 0x51) is set, this means the ADM1033 has pulled the
ALERT
output low.
ALERT
low) of Status
High Limit: ≥ Comparison Performed
Low Limit: < Comparison Performed

ANALOG MONITORING CYCLE TIME

The analog monitoring cycle time begins on power-up or, if monitoring has been disabled, by writing a 1 to the monitor/ STBY bit of Configuration Register 1 (Address 0x01). The ADC measures each one of the analog inputs in turn; as each measurement is completed, the result is automatically stored in the appropriate value register. The round-robin monitoring cycle continues, unless it is disabled. To disable the cycle, write a 0 to the monitor/STBY bit (Bit 0) of Configuration Register 1 (Address 0x01).
Rev. 0 | Page 20 of 40
Pin 14 is an notifies the system supervisor of an out-of-limit condition.
Reading the status register clears the status bit, as long as the error condition has been cleared.
Pin 3 is an ever an unmasked measurement goes outside its limit. Unlike SMBusALERT falls back within the programmed limits.
Status register bits are sticky. Whenever a status bit is set due to an out-of-limit condition, it remains set—even after the trigger­ing event has cleared. The only way to clear the status bit is to read the status register (after the triggering event has cleared). Interrupt mask registers (Reg. 0x08, Reg. 0x09, Reg. 0x0A) allow individual interrupt sources to be masked from causing an ALERT limit, its associated status bit is set in the status register.
SMBusALERT
Comp output. This pin asserts low when
ALERT
, it automatically resets once the measurement
. If one of these masked interrupt sources goes out of
output. This pin automatically
Page 21
ADM1033
A
Table 16. Status Register 1 (Reg. 0x4F)
Bit No. Name Description
7 LH
6 LL
5 RH
4 RL
3 RD
2 Unused Reserved. 1 Unused Reserved. 0 Unused Reserved.
1 = Local high temperature limit has been exceeded.
1 = Local low temperature limit has been exceeded.
1= Remote high temperature limit has been exceeded.
1 = Remote low temperature limit has been exceeded.
1 = Remote diode error; indicates an open or short on the D1+/D1− pins.
Table 17. Status Register 2 (Reg. 0x50)
Bit No. Name Description
7 LT
6 RT
5 Unused Reserved. 4 T%
3 TA
2 TS
1 Res Reserved. 0 Res Reserved.
1 = Local been exceeded.
1 = Remote been exceeded.
1 = exceeded.
1 = One of the exceeded; and the has been asserted.
1 = if
THERM temperature limit has
THERM temperature limit has
THERM timer limit has been
THERM limits has been
THERM pin is active. Clears on a read,
THERM is not active.
Table 18. Status Register 3 (Reg. 0x51)
Bit No. Name Description
7 FS 1= Fan has stalled. 6 FA
5 Res Reserved. 4 Res Reserved. 3 Res Reserved. 2 Res Reserved. 1 Res Reserved. 0
ALERT 1= SMBusALERT low, indicates the
1= Fan ALARM speed, indicates fan is running at alarm speed.
ADM1033 has pulled the line low.
THERM output signal
SMBusALERT
ALERT INTERRUPT BEHAVIOR
The ADM1033 generates an conditions. Out-of-limit conditions can also be detected by
polling the status registers. The ADM1033 has two outputs, called
In
SMBusALERT
Comp and
ALERT
mode, the output remains low until the
following combination of conditions occur: the measurement falls back within its programmed limits, and either the status register is read or an ARA is completed.
In
Comp mode, the output automatically resets
ALERT
once the temperature measurement falls back within the programmed limits.
For the
SMBusALERT
output, a status bit is set when a
measurement goes outside its programmed limit. If the corresponding mask bit is not set, the
is pulled low. If the measured value falls back within the limits, the
SMBusALERT
output remains low until the corresponding
status register is read or until an ARA is completed, as long as no other measurement is outside its limits.
On the other hand, the
ALERT
pulled low when a measurement goes outside its programmed limits. Once the measurement falls back within its limits, the
output is automatically pulled back high again,
ALERT assuming no other measurement channel is outside its limits.
The main difference between the two outputs is that the SMBusALERT while the In this data sheet, an and
SMBusALERT
TEMPERATURE
LERT, 70°C
SMBusALERT
ALERT COMP
Figure 31. How
does not reset without software intervention,
Comp output automatically resets itself. Note:
ALERT
ALERT
, unless otherwise stated.
LIMITS
ALERT
Comparator and
to signal out-of-limit
ALERT
ALERT
SMBusALERT
SMBusALERT
.
output
Comp output is automatically
refers to both the
SMBusALERT
Comp
ALERT
CLEARED ON READ
Outputs Work
TIME
04937-0-029
Rev. 0 | Page 21 of 40
Page 22
ADM1033
HANDLING
SMBUSALERT
To prevent tie-ups due to service interrupts, follow these steps:
1. Detect an SMBus assertion.
2. Enter the interrupt handler.
3. Read the status register to identify the interrupt source.
4. Mask the interrupt source by setting the appropriate mask
bit in the interrupt mask registers (Reg. 0x08 to Reg. 0x0A).
5. Take the appropriate action for a given interrupt source.
6. Exit the interrupt handler.
7. Periodically poll the status register. If the interrupt status bit
has cleared, reset the corresponding interrupt mask bit to 0. This causes the
SMBusALERT
behave as shown in Figure 32.
HIGH LIMIT
TEMPERATURE
"STICKY"
STATUS BIT
SMBusALERT
Figure 32. Handling

INTERRUPT MASKING REGISTER

Mask Registers 1, 2, and 3 are located at Addresses 0x08, 0x09, and 0x0A. These registers allow individual interrupt sources to be masked out to prevent the
masking the interrupt source prevents only the being asserted; the appropriate status bit is set as normal.
INTERRUPTS
output and status bits to
CLEARED ON READ
(TEMP BELOW LIMIT)
TEMP BACK IN LIMIT (STATUS BIT STAYS SET)
INTERRUPT MASK BIT SET
ALERT
INTERRUPT MASK BIT
CLEARED
(SMBusALERT REARMED)
SMBusALERT
s
interrupts. Note that
ALERT
from
04937-0-030
Table 19. Mask Register 1 (Reg. 0x08)
Bit No. Name Description
7 LH
1 masks the
ALERT for the local high
temperature.
6 LL
1 masks the
ALERT for the local low
temperature.
5 RH
1 masks the
ALERT for the remote high
temperature.
4 RL
1 masks the
ALERT for the remote low
temperature.
3 RD
1 masks the
ALERT for the remote diode
errors. 2 Res Reserved. 1 Res Reserved. 0 Res Reserved.
Table 20. Mask Register 2 (Reg. 0x09)
Bit No. Name Description
7 Res Reserved. 6 Res Reserved. 5 Res Reserved. 4 T%
1 masks the
ALERT for the THERM timer
limit. 3 TA
1 masks the
ALERT for the THERM limit being exceeded and the signal being asserted.
2 TS
1 masks the
ALERT for a transition on THERM; has no effect on ALERT in ALERT Comp mode.
1 Res Reserved. 0 Res Reserved.
Table 21. Mask Register 3 (Reg. 0x0A)
Bit No. Name Description
7 FS 6 FA
1 masks the 1 masks the
ALERT for fan stalling.
ALERT for fan running at ALARM speed.
5 Res Reserved. 4 Res Reserved. 3 Res Reserved. 2 Res Reserved. 1 Res Reserved. 0 Res Reserved.
THERM output
Rev. 0 | Page 22 of 40
Page 23
ADM1033
FAN_FAULT OUTPUT
The
FAN_FAU LT dual-function pin, defaults to a be reconfigured as an analog input reference for the input. To configure the pin, set the in Configuration Register 4 (Address 0x04) to 1.
output signals when the fan stalls. Pin 8, a
FAN_FAU LT
output. It can also
THERM
FAN_FAU LT
/REF bit (Bit 7)

FAULT QUEUE

The ADM1033 has a programmable fault queue option that lets the user program the number of out-of-limit measurements allowable before generating an
SMBusALERT
affects only temperature measurement channels and is opera­tional only in
SMBusALERT
mode. It performs some simple
filtering, which is particularly useful at the higher conversion rates (16, 32, and 64 conversions per second), where averaging is not carried out.
There is a queue for each of the temperature channels. If L (the value programmed to the fault queue) or more consecutive out­of-limit measurements are made on the same temperature channel, the fault queue fills and the
SMBusALERT
triggers. To fill the fault queue, the user needs L or more consecutive out-of-limit measurements on the local, or L or more consecutive out-of-limit measurements on the remote channel. The fault queue is independent of the state of the bits in the status register.
Table 22. Fault Queue (Address 0x06)
Bits <3:0> Fault Queue
000x 1 001x 2 01xx 3 1xxx 4
To reset the fault queue, do one of the following:
SMBus ARA command
Read Status Register 1
Power-on reset
SMBusALERT
The SMBusALERT
clears, even if the condition that caused the
remains. The
SMBusALERT
fault queue fills up.
. The fault queue
output
is reasserted, if the

CONVERSION RATE REGISTER

The ADM1033 makes up to 64 measurements per second. However, for the sake of reduced power consumption and better noise immunity, users can run the ADM1033 at a slower conversion rate. Averaging does not occur at rates of 16, 32, and 64 conversions per second. Table 23 lists the available rates. The conversion rate register is located at Address 0x05. Note that the current round-robin loop must be completed before the newly programmed conversion rate can take effect.
Table 23. Conversion Rates
Code Conversion Rate
0x00 0.0625 0x01 0.125 0x02 0.25 0x03 0.5 0x04 1 0x05 2 0x06 4 0x07 8 0x08 16 0x09 32 0x0A 64 0x0B to 0xFF Reserved
THERM I/O TIMER AND LIMITS
Pin 7 can be configured as either an input or output. As an output, it is asserted low to signal that the measured tempera­ture has exceeded preprogrammed temperature limits. The output is automatically pulled high again when the temperature falls below the (
THERM teresis is programmable in Register 0x1A. an output by default on power-up.
TEMPERATURE
LIMITS
THERM, 85°C
THERM-HYST,
80°C
− Hysteresis) limit. The value of hys-
THERM
is enabled as
Rev. 0 | Page 23 of 40
THERM
Figure 33.
THERM
Behavior
TIME
04937-0-031
Page 24
ADM1033
Once the
THERM
full speed—that is, as long as the boost disable bit (Bit 1) is not set in Configuration Register 2 (Address 0x02).
limits are exceeded, the fans are boosted to
When
THERM
THERM
is configured as an input only, set the enable
events bits in Configuration Register 4 (Address 0x04)
to allow Pin 7 to operate as an I/O.
To c o nf ig ur e
THERM
as an input, set the
THERM
timer bit
(Bit 2) of Configuration Register 1 (Address 0x01) to 1. (It no longer operates as an output.) The ADM1033 can then detect whenever the
THERM
nected to a trip point temperature sensor or to the
input is asserted low. This can be con-
PROCHOT
output of a CPU. With processor core voltages reducing all the time, the threshold for the ADTL +
PROCHOT
output also
reduces as new processors become available. The default thresh­old on
THERM
(
FAN_FAU LT is done by setting Bit 7 ( Register 4 (Address 0x04) to 1. The processor V connected to this input to provide a reference for the input. The resulting
is the normal CMOS threshold. However, Pin 8
/REF) can be reconfigured as a REF input. This
FAN_FAU LT
/REF) in Configuration
should be
CCP
THERM
THERM
threshold is 0.75 × V
CCP
, the
correct threshold for an AGTL+ signal.
The ADM1033 can also measure assertion times on the THERM
input as a percentage of an on-time window. This
window is programmable in Configuration Register 4 (Address 0x04) using Bits <6:4> (
THERM
% on-time window).
Values of between 0.25 and 8 are programmable. The assertion time, as a percentage of the time window, is stored in the THERM
A
% on-time register (Address 0x4E).
THERM
% (0x19) limit is also associated with this register.
Once the measured percentage exceeds the percentage limit, the
THERM (Address 0x50) is asserted and an as the mask bit is not set. If the limit is set to 0x00, an
% exceeded bit (Bit 4) in Status Register 2
is generated, as long
ALERT
ALERT
is generated on the first assertion. If the limit is set to 0xFF, an
is never generated. This is because 0xFF corresponds to
ALERT the
THERM
input, which is asserted all the time.
To configure the
THERM whenever the local temperature exceeds the local set the enable local
pin to be pulled low as an output
THERM
events bit (Bit 0) of Configuration
THERM
limit,
Register 4 (Address 0x04).
To configure the
THERM whenever the remote temperature exceeds the remote limit, set the enable remote
pin to be pulled low as an output
THERM
THERM
events bit (Bit 1) of
Configuration Register 4 (Address 0x04).
THERM
The
ALERT
% LIMIT REGISTER
THERM
% limit is programmed to Register 0x19. An
is generated if the
THERM
is asserted for longer than
the programmed percentage limit. The limit is programmed as a percentage of the chosen time window.
0x00 = 0%
0xFF = 100%
Therefore, 1 LSB = 0.39%
Example
If a time window of 8 seconds is chosen, and an generated if
THERM
is asserted for more than 1 second,
ALERT
is to be
program the following value to the limit register:
% Limit = 1/8 × 100 = 12.5%
12.5% / 0.39% = 32d = 0x20 = 0010 0000
An
is generated if the
ALERT
THERM
limit is exceeded after
the time window has elapsed, assuming it is not masked.
Table 24.
Code
000 0.25 s 001 0.5 s 010 1 s 011 2 100 4 s 101 8 s 110 8 s 111 8 s
THERM
% On-Time Window
THERM
% On-Time Window
Rev. 0 | Page 24 of 40
Page 25
ADM1033
A

FAN DRIVE SIGNAL

The ADM1033 controls the speed of a cooling fan. Varying the duty cycle (on/off time) of a square wave applied to the fan varies the speed of the fan. The ADM1033 uses a control method called synchronous speed control, in which the PWM drive signal applied to the fan is synchronized with the fan’s TACH signal. See the Synchronous Speed Control section.
The external circuitry required to drive the fan is simple. A single N-channel MOSFET is the only drive device required. The specifications of the MOSFET depend on the maximum
1N4148
< 3 V
GS
04937-0-032
current required by the fan and the gate voltage drive (V for direct interfacing to the drive pin). V
can be greater than
GS
3 V, as long as the pull-up on the gate is tied to 5 V. The MOSFET should also have a low on resistance to ensure that there is no significant voltage drop across the FET. A high on resistance reduces the voltage applied across the fan and, therefore, the maximum operating speed of the fan. Figure 34 shows a scheme for driving a 3-wire fan.
12V
12V
10k
TACH
ADM1033
DRIVE
Figure 34. Interfacing a 3-Wire Fan to the ADM1033 Using an
10k
TACH
4.7k
3.3V
100k
N-Channel MOSFET
12V FAN
Q1 NDT3055L
Figure 34 uses a 10 kΩ pull-up resistor for the TACH signal. This assumes that the TACH signal is an open collector from the fan. In all cases, the fan’s TACH signal must be kept below 5 V maximum to prevent damaging the ADM1033.
If in doubt as to whether a fan has an open collector or totem­pole TACH output, use one of the input signal conditioning circuits shown in the Fan Inputs section.
When designing drive circuits with transistors and FETs, make sure that the drive pins are not required to source current and that they sink less than the maximum current specified.

SYNCHRONOUS SPEED CONTROL

The ADM1033 drives the fan using a control scheme called synchronous speed control. In this scheme, the PWM drive signal applied to the fan is synchronized with the TACH signal. Accurate and repeatable fan speed measurements are the main benefits. The fan is allowed to run reliably at speeds as low as 30 % of the full capability.
The drive signal applied to the fan is synchronized with the TACH signal. The ADM1033 switches on the drive signal and waits for a transition on the TACH signal. When a transition takes place on the TACH signal, the PWM drive is switched off for a period of time called t on again. The t
time is varied in order to vary the fan speed.
OFF
If the fan runs too fast, the t too slow, the t
time is decreased.
OFF
Because the drive signal is synchronized with the TACH signal, the frequency with which the fan is driven depends on the cur­rent speed of the fan and the number of poles in it.
Figure 35 shows how the synchronous speed drive signal works. The ideal TAC H signal is the signal that would be output from the fan, if power were applied 100% of the time. It is representa­tive of the actual speed of the fan. The actual TAC H s i g n a l i s t he signal seen on the TACH output from the fan, if using a scope. In effect, the actual TACH signal is the ideal TACH signal chopped with the drive signal.
. The drive signal is then switched
OFF
time is increased. If the fan runs
OFF
POLE TRANSITION POINTS
IDEAL TACH
t
POLE
DRIVE
t
OFF
CTUAL TACH
DASH = TACH FLOATS HIGH BY PULL-UP RESISTOR SOLID = TRUE TACH WHEN FAN IS POWERED
Figure 35. Drive Signal by Using Synchronous Control
Rev. 0 | Page 25 of 40
04937-0-033
Page 26
ADM1033
K

FAN INPUTS

Pin 2 is the TACH input intended for fan speed measurement. This input is open-drain.
Signal conditioning on the ADM1033 accommodates the slow rise and fall time of typical tachometer outputs. The maximum input signal range is from 0 V to 5 V, even when V 5 V. If these inputs are supplied from fan outputs that exceed 0 V to 5 V, either resistive attenuation of the fan signal or diode clamping must be used to keep the fan inputs within an acceptable range.
Figure 36 to Figure 38 show examples of possible fan input circuits.
5V OR 12V
FAN
is less than
CC
V
CC
The fan inputs have an input resistance of about 160 kΩ to ground. Consider this when calculating resistor values.
With a pull-up voltage of 12 V and pull-up resistor of less than 1 kΩ, suitable values for R1 and R2 would be 100 kΩ and 47 kΩ. This gives a high input voltage of 3.83 V.
12V
<1 k
R1*
TACH
OUTPUT
*SEE TEXT
FAN(0–7)
R2
Figure 38. Fan with Strong TACH Pull-Up to Voltage > V
Output, Attenuated with R1/R2
V
CC
ADM1033
FAN SPEED
COUNTER
to Totem Pole
CC
04937-0-037
PULL-UP
4.7k
*CHOOSE ZD1 VOLTAGE APPROXIMATELY 0.8 × V
TYP
TACH
OUTPUT
V
CC
100k TYP
TACH X
ZD1*
ADM1033
FAN SPEED
COUNTER
DRIVE X
04937-0-035
CC
Figure 36. Fan with TACH Pull-Up to Voltage > 5 V, Clamped with Zener Diode
If the fan output has a resistive pull-up to 12 V (or another voltage greater than 5 V), the fan output can be clamped with a Zener diode, as shown in Figure 36. Select a Zener voltage that is greater than V
but less than 5 V, allowing for the voltage
IH
tolerance of the Zener. A value of between 3 V and 5 V is suitable.
12V
PULL-UP TYP <1 kOR TOTEM POLE
TACH
OUTPUT
R1
10k
FAN(0–7)
ZD1
ZENER*
V
CC
ADM1033
FAN SPEED
COUNTER

FAN SPEED MEASUREMENT

The fan counter does not count the fan TACH output pulses directly. This is because the fan may be spinning at less than 1,000 rpm and it would take several seconds to accumulate a large and accurate count. Instead, the period of the fan revolution is measured by gating an on-chip 81.92 kHz oscillator into the input of a 16-bit counter for one complete revolution of the fan. Therefore, the accumulated count value is actually proportional to the fan tachometer period and inversely proportional to the fan speed.
The number of poles in the fan must be programmed in Configuration Register 3 (Address 0x03). This number must be an even number only, because there cannot be an uneven number of poles in a fan. A TACH period is output for every two poles. Therefore, the number of poles must be known so that the ADM1033 can measure for a full revolution.
Figure 39 shows the fan speed measurement period, assuming that the fan outputs an ideal TACH signal. In reality, the TACH signal output by the fan is chopped by the drive signal. However, because the drive signal and TACH signal are synchronized, there is enough information available for the ADM1033 to measure the fan speed accurately.
*CHOOSE ZD1 VOLTAGE APPROXIMATELY 0.8 × V
CC
Figure 37. Fan with Strong TACH Pull-Up to Voltage > VCC or Totem Pole
Output, Clamped with Zener and Resistor
If the fan has a strong pull-up (less than 1 kΩ to 12 V) or a totem-pole output, then a series resistor can be added to limit the Zener current, as shown in Figure 37.
Or, resistive attenuation can be used, as shown in Figure 38.
R1 and R2 should be chosen such that
PULL-UP
× R2/(R
2 V < V
+ R1 + R2) < 5 V
PULL-UP
04937-0-036
Rev. 0 | Page 26 of 40
CLOC
IDEAL
TACH
FAN
MEASUREMENT
PERIOD
Figure 39. Fan Speed Measurement for a 4-Pole Fan
04937-0-038
Page 27
ADM1033

FAN SPEED MEASUREMENT REGISTERS

The16-bit measurements listed in Table 25 are stored in the TACH value registers.
Table 25. TACH Value Registers
Register Description Default
0x4A TACH Period, LSB 0xFF 0x4B TACH Period, MSB 0xFF

READING FAN SPEED

Reading back the fan speed involves a 2-register read for each measurement. The low byte should be read first. This freezes the high byte until both high and low byte registers have been read, preventing erroneous fan speed measurement readings.
The fan tachometer reading registers report back the number of
12.20 µs period clocks (81.92 kHz oscillator) gated to the fan speed counter for one full rotation of the fan (assuming the correct number of poles is programmed). Because the ADM1033 essentially measures the fan TACH period, the higher the count value, the slower the fan’s actual speed. A 16­bit fan TACH reading of 0xFFFF indicates that the fan has stalled or is running very slowly (<75 rpm).

CALCULATING FAN SPEED

Fan speed in rpm is calculated as follows. This calculation assumes the number of poles programmed in Configuration Register 3 (Address 0x03) is correct for the fan used.
Fan Speed (rpm) = (81920 × 60)/Fan TACH Reading
where the Fan TACH Reading is the 16-bit Fan Tachometer Reading.
Example:
TACH High By te (Reg. 0×28) = 0×7
TACH Low Byte (Reg. 0×29) = 0×FF
What is the fan speed in rpm?

ALARM SPEED

The fan ALARM speed (Bit 6) in Status Register 3 (Address 0x51) is set whenever the fan runs at alarm speed. This occurs if the device is programmed to run the fan at full speed whenever the THERM alarm speed, for example, if the Boost Disable bit (Bit 1) of the Configuration 2 Register (Address 0x02) is not set to 1.

Fan Response Register

The ADM1033 fan speed controller operates by reading the current fan speed, comparing it with the programmed fan speed, and then updating the drive signal applied to the fan. The fan response register determines the rate at which the ADM1033 looks at and updates the drive signal. Different fans have different inertias and respond to a changing drive signal more or less quickly than others. The fan’s response register allows the user to tailor the ADM1033 to a particular fan, to prevent situations like overshoot.
The user selects the number of updates to the drive signal per second. Table 26 lists the available options.
Table 26. Fan Response Codes
Code Update Rate
000 1.25 updates/s 001 2.5 updates/s = default 010 5 updates/s 011 10 updates/s 100 20 updates/s 101 40 updates/s 110 80 updates/s 111 160 updates/s
Table 27. Fan Response Register (Address 0x3C)
Bit Function
<7:3> Unused <2:0> Fan Response
temperature limits are exceeded. The device runs at
Fan TACH Reading = 0×17FF = 6143d
rpm = (f × 60)/Fan TACH Reading
rpm = (81920 × 60)/6143
Fan Speed = 800 rpm
Rev. 0 | Page 27 of 40
Page 28
ADM1033
6
5
4
6
5
4

LOOK-UP TABLE: MODES OF OPERATION

The ADM1033 look-up table has two modes of operation used to determine the behavior of the system:
Manual mode
Look-up table

Manual Mode

In manual mode, the ADM1033 is under software control. The software programs the required fan speed value or target rpm value. The ADM1033 then outputs that fan speed.
Programming Target Fan Speed
In this mode, the user programs the target rpm as a TACH count for N poles or a TACH count for one full rotation of the fan. This assumes that the number of poles is programmed correctly in Configuration 3 Register (Address 0x03).
Follow these steps to program the target fan speed:
1. Place the ADM1033 in manual mode. Set Bit 7 (Table/SW)
of Configuration Register 1 (Address 0x01) = 0.
2. Program the target TACH count (fan speed) using the
following equation:
TACH Count = (f × 60)/R
where:

LOOK-UP TABLE

The ADM1033 allows the user to program a temperature-to­fan-speed profile. There are 24 registers in the look-up table, eight for temperature and 16 for target fan speed (each target fan speed is two registers). In total, there are eight available points.
There are two options when programming the look-up table. It can be programmed to make the fan run at discrete speeds and jump to the new speed once the temperature threshold is crossed. Or, it can linearly ramp the TACH count between the two temperature thresholds.
Figure 40 and Figure 41 show what the look-up table looks like, if all eight points are used on the one curve for both fans.
Figure 40 shows the transfer curve when the fan is programmed to run at discrete speeds. The ADM1033 spins the fan at its new speed once a threshold is crossed.
FAN SPEED
TACH COUNT 8 TACH COUNT 7
TACH COUNT TACH COUNT TACH COUNT
TACH COUNT 3
TACH COUNT 2 TACH COUNT 1
f = clock frequency = 81.92 kHz
R = required rpm value
Example 1: If the desired value is 5,000 rpm, program the following value to the TACH pulse period registers:
TACH Pulse Period = (f × 60)/5000
TACH Pulse Period = 983d = 0x03D7
Example 2: If the desired value is 3,500 rpm, program the following value to the TACH pulse period registers:
TACH Pulse Period = (f × 60)/3500
TACH Pulse Period = 1404d = 0x057C
Table 28. Registers to be Programmed
Fan Description Address Value
Example 1 Look-Up Table LSB 0x2A 0xD7 Example 1 Look-Up Table MSB 0x2B 0x03 Example 2 Look-Up Table LSB 0x2C 0x7C Example 2 Look-Up Table MSB 0x2D 0x05
T1 T2 T3 T4 T5 T6 T7 T8
Figure 40. Programming the Look-Up Table in Discrete RPM Mode
TEMPERATURE
Figure 41 shows the transfer curve if the linear fan speeds option is chosen. At temperature T1, the fan runs at Fan Speed 1. As the temperature increases, the fan speed increases until it reaches Fan Speed 2 at T2.
FAN SPEED
TACH COUNT 8 TACH COUNT 7
TACH COUNT TACH COUNT TACH COUNT
TACH COUNT 3
TACH COUNT 2 TACH COUNT 1
T1 T2 T3 T4 T5 T6 T7 T8
Figure 41. Programming the Look-Up Table in Linear Fan Speeds Mode
TEMPERATURE
04937-0-039
04937-0-040
Rev. 0 | Page 28 of 40
Page 29
ADM1033
TACH COUNT 2 TO 8
FAN SPEED
TACH COUNT 1
T1 T2 T (3 TO 8) = 191 °C
TEMPERATURE
Figure 42. Programming Two Points on the Look-Up Table
Once the temperature exceeds the highest temperature point in the look-up table, the fan speed remains at the highest speed until the temperature drops below the T7 temperature value.
If the temperatures in T1 to T8 are not programmed in succession, the fan speed moves to the next highest pro­grammed temperature as the temperature increases. Similarly, when the temperature decreases, it ignores programmed higher temperatures and jumps to the next lower temperature. There­fore, the temperature-to-fan-speed profile for increasing and decreasing temperature can be different.
When programming the look-up table, the user has the option to use between two and eight points for the fan (eight points only if the same curve is to be used for both fans).
If the user wants to program only the transfer curve and knows the starting temperature, minimum fan speed, maximum temperature, and maximum fan speed, then only four parame­ters are required: T1, T2, FS1, and FS2. The remaining look-up temperature thresholds should remain at their default values of +191°C. FS 3 to FS8 should be programmed with the same value as FS2 to give the flat curve, if required, or, they can be left at the default value of 0.
However, it is normal to program a
THERM
limit as well. Once
this temperature is exceeded and the boost bit is set, the fan runs to full speed. This overrides the table.
Table 29. Look-Up Table Register Addresses
x Temperature, x RPMx, LSB RPMx, MSB
1 0x22 0x2A 0x2B 2 0x23 0x2C 0x2D 3 0x24 0x2E 0x2F 4 0x25 0x30 0x31 5 0x26 0x32 0x33 6 0x27 0x34 0x35 7 0x28 0x36 0x37 8 0x29 0x38 0x39
04918-0-041

SETTING UP THE LOOK-UP TABLE IN LINEAR MODE

When discrete/linear speed (Bit 2) is set to 1 (default), the TACH count decreases linearly and the fan speed increases with temperature. At temperature T increases with temperature to FS
, the fan runs at FSX and speed
X
at temperature T
X+1
X+1
.
Alternatively, the fan can be run at discrete fan speeds. When discrete/linear speed (Bit 2) is set to 0, the fan runs at a new speed once the temperature threshold is exceeded.

SELECTING WHICH TEMPERATURE CHANNEL CONTROLS A FAN

Fan Behavior Register (Address 0x07)
Bits <1:0> = DRIVE Behavior
The ADM1033 can be configured so that either the local temperature or the remote temperature controls the fan. In default, the remote temperature controls the fan.
Table 30. Drive BHVR Bits
Bits Drive x BHVR
00 Local Temperature Controls the Fan 01 Remote Temperature Controls the Fan 10 Remote Temperature Controls the Fan 11 Fan Runs at Full Speed

LOOK-UP TABLE HYSTERESIS

The user can program a hysteresis to be applied to the look-up table. The advantage of this is apparent, if the temperature is cycling around one of the threshold temperatures, particularly when the look-up table is configured in discrete mode. It is not as important in linear mode.
Table 31. Programming the Hysteresis
Code Hysteresis Value
0000 0000 0°C 0000 0001 1°C 0000 0010 2°C 0000 0101 5°C 0000 1000 8°C 0000 1111 15°C
The hysteresis register of the look-up table is at Address 0x3A. A hysteresis value of between 0°C and 15°C can be programmed with a resolution of 1°C and applied to all the temperature thresholds. Table 31 gives sample values for programming.
Rev. 0 | Page 29 of 40
Page 30
ADM1033
PROGRAMMING THE THERM LIMIT FOR TEMPERATURE CHANNELS
THERM temperature channel. Above this temperature, a component such as the CPU or VRM might operate beyond its safe
operating limit. When the temperature exceeds are driven at full speed to provide critical system cooling. The
fans remain running at 100% until the temperature drops below THERM grammed; its default is 5°C. If the boost disable bit (Bit 1) is set in Configuration Register 2, the fans do not run to full speed.
is the absolute maximum temperature allowed on a
THERM
, all fans
− Hysteresis. The hysteresis value can be pro-

XOR TREE TEST MODE

The ADM1033 includes an XOR tree test mode. This mode is useful for in-circuit test equipment at board-level testing. By applying stimulus to the pins included in the XOR test, it is possible to detect opens or shorts on the system board. Figure 43 shows the signals exercised in this mode.
TACH1
ALERT_COMP
THERM
The
THERM
operating temperature of the system. Exceeding any
limit is considered the maximum worst-case
THERM
limit runs all fans at full speed, a condition with very negative acoustic effects. This limit should be set up as a fail-safe and not exceeded under normal system operating conditions. The THERM
Table 32.
Address Description Default
0x0D 0x10
The
temperature limit registers are listed in Table 32.
THERM
THERM
Hysteresis Registers
THERM Limit
Local Remote
THERM Limit
hysteresis register is at Address 0x1A. A value is
0x95 (85°C) 0x95 (85°C)
programmed and applied to both temperature channels—local and remote. A
THERM
hysteresis value of between 0°C and
15°C can be programmed with a resolution of 1°C. See Table 33.
Table 33. Programming
Code Hysteresis Value
0000 0000 0°C 0000 0001 1°C 0000 0010 2°C 0000 0101 5°C 0000 1000 8°C 0000 1111 15°C
THERM
Hysteresis
FAN_FAULT/REF
LOCATION
ALERT
Figure 43. XOR Tree Test
DRIVE1

LOCK BIT

Setting the lock bit (Bit 6) of Configuration Register 1 (Address 0x01) makes all the lockable registers read-only. These registers remain read only until the ADM1033 is powered down and back up again. For more information on which registers are lockable, see Table 33.

SW RESET

Setting the software reset bit (Bit 0) of Configuration Register 1 (Address 0x01) resets all software-resettable bits to their default value. For more information on resetting registers and their default values, see Table 34 to Table 68.
04937-0-042
Rev. 0 | Page 30 of 40
Page 31
ADM1033
Table 34. ADM1033 Registers
Address R/W Description Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0x00/80 R/W #Bytes/Block Read 7 6 5 4 3 2 1 0 0x01/81 R/W Configuration 1 Table/SW Lock SDA SCL
ALERT
TIMER AVG MON
0x02/82 R/W Configuration 2 RR RES RES CS LUT D/L BD Reset 0x03/83 R/W Configuration 3 RES RES RES RES #FP #FP #FP #FP 0x04/84 R/W Configuration 4 FF/REF %T %T %T XOR RES RTM LTM 0x05/85 R/W Conversion Rate RES RES RES RES Conv Conv Conv Conv 0x06/86 R/W Fault Queue RES F1 Off RES RES FQ FQ FQ FQ 0x07/87 R/W Fan Behavior RES RES RES RES RES RES DB DB 0x08/88 R/W Mask 1 LH LL RH RL RD RES RES RES 0x09/89 R/W Mask 2 RES RES RES %T TA TS RES RES 0x0A/8A R/W Mask 3 FS FA RES RES RES RES RES RES 0x0B/8B R/W Local High Limit 7 6 5 4 3 2 1 0 0x0C/8C R/W Local Low Limit 7 6 5 4 3 2 1 0 0x0D/8D R/W
Local
THERM Limit
7 6 5 4 3 2 1 0
0x0E/8E R/W Remote High Limit 7 6 5 4 3 2 1 0 0x0F/8F R/W Remote Low Limit 7 6 5 4 3 2 1 0 0x10/90 R/W
Remote
THERM
7 6 5 4 3 2 1 0
Default
0x20 Y 0x01 Y
0x84 Y 0x44 Y 0x00 Y 0x07 Y 0x01 Y 0x09 Y 0x52 N 0x10 N 0x00 N 0x8B N 0x54 N 0x95 Y
0x8B N 0x54 N 0x95 Y
Limit 0x16/96 R/W Local Offset 7 6 5 4 3 2 1 0 0x17/97 R/W Remote Offset 7 6 5 4 3 2 1 0 0x19/99 R/W
0x1A/9A R/W
THERM % Limit
THERM Hysteresis
7 6 5 4 3 2 1 0 RES RES RES RES Hys Hys Hys Hys
0x22/A2 R/W Look-Up Table T1 7 6 5 4 3 2 1 0 0x23/A3 R/W Look-Up Table T2 7 6 5 4 3 2 1 0 0x24/A4 R/W Look-Up Table T3 7 6 5 4 3 2 1 0 0x25/A5 R/W Look-Up Table T4 7 6 5 4 3 2 1 0 0x26/A6 R/W Look-Up Table T5 7 6 5 4 3 2 1 0 0x27/A7 R/W Look-Up Table T6 7 6 5 4 3 2 1 0 0x28/A8 R/W Look-Up Table T7 7 6 5 4 3 2 1 0 0x29/A9 R/W Look-Up Table T8 7 6 5 4 3 2 1 0 0x2A/AA R/W Look-Up Table, FS1 7 6 5 4 3 2 1 0 0x2B/AB R/W Look-Up Table, FS1 15 14 13 12 11 10 9 8 0x2C/AC R/W Look-Up Table, FS2 7 6 5 4 3 2 1 0 0x2D/AD R/W Look-Up Table, FS2 15 14 13 12 11 10 9 8 0x2E/AE R/W Look-Up Table, FS3 7 6 5 4 3 2 1 0
0x00 Y 0x00 Y 0x00 Y
0x05 N 0xFF Y
0xFF Y 0xFF Y 0xFF Y 0xFF Y 0xFF Y 0xFF Y 0xFF Y 0xFF Y 0xFF Y 0xFF Y 0xFF Y 0xFF Y
0x2F/AF R/W Look-Up Table, FS3 15 14 13 12 11 10 9 8 0xFF Y 0x30/B0 R/W Look-Up Table, FS4 7 6 5 4 3 2 1 0 0xFF Y 0x31/B1 R/W Look-Up Table, FS4 15 14 13 12 11 10 9 8 0xFF Y 0x32/B2 R/W Look-Up Table, FS5 7 6 5 4 3 2 1 0 0xFF Y 0x33/B3 R/W Look-Up Table, FS5 15 14 13 12 11 10 9 8 0xFF Y 0x34/B4 R/W Look-Up Table, FS6 7 6 5 4 3 2 1 0 0xFF Y 0x35/B5 R/W Look-Up Table, FS6 15 14 13 12 11 10 9 8 0xFF Y 0x36/B6 R/W Look-Up Table, FS7 7 6 5 4 3 2 1 0 0xFF Y 0x37/B7 R/W Look-Up Table, FS7 15 14 13 12 11 10 9 8 0xFF Y 0x38/B8 R/W Look-Up Table, FS8 7 6 5 4 3 2 1 0 0xFF Y 0x39/B9 R/W Look-Up Table, FS8 15 14 13 12 11 10 9 8 0xFF Y 0x3A/BA R/W
Look-Up Table
RES RES RES RES HYS HYS HYS HYS 0x00 Y
Hysteresis 0x3C/BC R/W Fan Response RES RES RES RES RES FR FR FR 0x00 Y 0x3D\BD R Device ID 7 6 5 4 3 2 1 0 0x33 N 0x3E\BE R Company ID 7 6 5 4 3 2 1 0 0x41 N
Lockable
Rev. 0 | Page 31 of 40
Page 32
ADM1033
Address R/W Description Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0x3F\BF R Revision Register 7 6 5 4 3 2 1 0 0x02 N 0x40\C0 R Local Temperature 4 3 2 1 0 RES RES RES 0x00 N 0x41\C1 R Local Temperature 12 11 10 9 8 7 6 5 0x00 N 0x42\C2 R
0x43\C3 R
0x4A\CA R TACH Period 7 6 5 4 3 2 1 0 0xFF N 0x4B\CB R TACH Period 15 14 13 12 11 10 9 8 0xFF N 0x4E\CE R THERM % On-Time 7 6 5 4 3 2 1 0 0x00 N 0x4F\CF R Status 1 LH LL RH RL RTH RES RES RES 0x00 N 0x50\D0 R Status 2 LT RT RES %T TA TS RES RES 0x00 N 0x51\D1 R Status 3 FS FA RES RES RES RES RES
Remote Temperature
Remote Temperature
4 3 2 1 0 RES RES RES 0x00 N
12 11 10 9 8 7 6 5 0x00 N
ALERT
Default
0x00 N
Table 35. Register 0x00, # Bytes/Block Read, Power-On Reset = 0x20, Lock = Y, S/W Reset = Y
Bit Name R/W Description
<7:0> # Bytes Block Read R/W Block reads are # bytes/block read long. The maximum is 32 bytes, the SMBus transaction limit.
Table 36. Register 0x01, Configuration Register 1, Power-On Default = 0x01, Lock = Y, SW Reset = Y
Bit Name R/W Description
7 SW Con R/W
6 Lock Bit R/W
5 SDA Timeout R/W 1 = SDA timeout enabled. 0 = SDA timeout disabled. Default = 0. 4 SCL Timeout R/W 1 = SCL timeout enabled. 0 = SDL timeout disabled. Default = 0. 3 Reserved R/W Reserved. 2 1 Averaging Off R/W
0 Monitor/STBY R/W
Enable
THERM Timer
Set to 1 to have look-up table control the fan speed. Set to 0 to put ADM1033 in software/manual control mode. Default = 0.
Set to 1 to prevent the user from writing to the ADM1033 registers. 1 = ADM1033 registers locked. 0 = ADM1033 registers unlocked. Default = 0.
R/W
1 = timer enabled, 0 = timer disabled. Enables Disables averaging at the slower conversion rates (8 Hz and slower). Averaging is automatically
disabled at the higher (16, 32, and 64) conversion rates. Default = Averaging On = 0. Set to 1 to enable monitoring of temperature. Set to 0 to disable temperature monitoring. Power-
On Default = 1.
THERM
as an input. Default = 0.
Table 37. Register 0x02, Configuration Register 2, Power-On Default = 0x84, Lock = Y, SW Reset = Y
Bit Name R/W Description
7 Round Robin R/W
<6:5> Reserved R/W Reserved. 4 Channel Selector R/W 0 = local temperature measurements, 1 = remote temperature measurements. 3 Reserved R/W Reserved. 2 Discrete/Linear RPM R/W
1 Boost Disable R/W
0 SW Reset R/W
Enables round-robin mode. Set to 0 for single-channel mode. (The ADC converts on only one channel, which is determined by the channel selector bits.) Default = Round Robin = 1.
Determines whether the fans run at discrete speeds or whether the fan speed increases with temperature between the two thresholds. Default = 1 = linear.
Set to 1 to prevent fans from being boosted, if either exceeded. Under these conditions, the fans run at the previously calculated speed. Default = 0.
Set this bit to 1 to reset the ADM1033 registers to their default values, excluding the limit registers, offset registers, and look-up table registers. This bit self-clears. Default = 0.
THERM temperature or THERM timer limits are
Table 38. Register 0x03, Configuration Register 3, Power-On Default = 0x44, Lock = Y, SW Reset = Y
Bit Name R/W Description
<7:4> Unused R/W Reserved. <3:0> #Poles Fan R/W
Write the number of poles in the fan to this register. Power-On Default = 4 poles = 100. This value should be an even number only.
Lockable
Rev. 0 | Page 32 of 40
Page 33
ADM1033
Table 39. Register 0x04, Configuration Register 4, Power-On Default = 0x00, Lock = Y, SW Reset = Y
Bit Name R/W Description
7
<6:4>
3 XOR Test R/W Set this bit to 1 to enable the XOR connectivity test. 2 Unused R/W Reserved. 1
0
FAN_FAULT REF
THERM % Time Window
Enable Remote
Enable Local
THERM Events
THERM Events
Table 40. Register 0x05, Conversion Rate Register, Power-On Default = 0x0A, Lock = Y, SW Reset = Y
Bit Name R/W Description
7 Reserved R/W Reserved. Do not write a 1 to this bit. <6:4> Unused R Reserved. <3:0> Conversion Rate R/W
Table 41. Register 0x06, Fault Queue, Power-On Default = 0x01, Lock = Y, SW Reset = Y
Bit Name R/W Description
<7:4> Unused R Reserved. <3:0> Fault Queue Length R/W
R/W
R/W
R/W
R/W
Sets the function for Pin 8. 0 = Default = FAN_FAULT Output (THERM Input is CMOS). 1 = Reference Input for
These bits set the time window over which THERM % is calculated. 000 = 0.25 s
001 = 0.5 s 010 = 1 s 011 = 2 s 100 = 4 s 101 = 8 s 110 = 8 s 111 = 8 s
This bit enables THERM assertions as an output. Functions when the THERM timer is enabled and the remote temperature exceeds its
This bit enables THERM assertions as an output. Functions when the THERM timer is enabled and the local temperature exceeds its
These 4 bits set the conversion rates of the ADM1033. Changing these bits does not update the conversion rate until the start of the next round robin.
0000 = 0.0625 conversions/s 0001 = 0.125 conversions/s 0010 = 0.25 conversions/s 0011 = 0.5 conversions/s 0100 = 1 conversion/s 0101 = 2 conversions/s 0110 = 4 conversions/s 0111 = 8 conversions/s 1000 = 16 conversions/s 1001 = 32 conversions/s 1010 = 64 conversions/s
These 4 bits set the fault queue (the number of out-of-limit measurements made before an
000x = 1 001x = 2 01xx = 3 1xxx = 4
ALERT is generated).
THERM .
THERM limit.
THERM limit.
Rev. 0 | Page 33 of 40
Page 34
ADM1033
Table 42. Register 0x07, Fan BHVR Register, Power-On Default = 0x09, Lock = Y, SW Reset = Y
Bit Name R/W Description
7 Reserved R Reserved. 6 Fan Off R/W
<5:2> Reserved R Reserved. <1:0> DRIVE BHVR R/W
Table 43. Register 0x08, Mask Register 1, Power-On Default = 0x52, Lock = N, SW Reset = Y
Bit Name R/W Description
7 Local Temp High R/W
6 Local Temp Low R/W
5 Remote High R/W
4 Remote Low R
3 Remote Diode Error R
2 Unused R Reserved. 1 Unused R Reserved. 0 Unused R Reserved.
Table 44. Register 0x09, Mask Register 2, Power-On Default = 0x10, Lock = N, SW Reset = Y
Bit Name R/W Description
<7:5> Unused R Unused. 4
3
2
<1:0> Unused R Unused.
THERM %
THERM Assert
THERM_State
R/W
R/W
R/W
Table 45. Register 0x0A, Mask Register 3, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit Name R/W Description
7 Fan Stalled R/W
6 Fan Alarm Speed R/W
5 Reserved R Reserved. Default = 0. 4 Reserved R Reserved. Default = 0. 3 Reserved R Reserved. Default = 0. 2 Reserved R Reserved. Default = 0. 1 Reserved R Reserved. Default = 0. 0 Reserved R Reserved. Default = 0.
When this bit is set to 1, the fan switches off, regardless of programmed target fan speed. Default = 0.
Determine which temperature source controls the DRIVE Output. 00 = local temp controls the DRIVE. 01 = remote temperature controls the DRIVE. 10 = remote temperature controls the DRIVE. 11 = DRIVE at full speed.
A 1 disables the corresponding interrupt status bit from causing the interrupt output to be set. The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from causing the interrupt output to be set. The status bit is not affected. Default = 1.
A 1 disables the corresponding interrupt status bit from causing the interrupt output to be set. The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from causing the interrupt output to be set. The status bit is not affected. Default = 1.
A 1 disables the corresponding interrupt status bit from causing the interrupt output to be set. The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from setting the interrupt output. The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from setting the interrupt output. The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from setting the interrupt output. The status bit is not affected. Default = 0. This bit has no effect for the ALERT Comp output.
A 1 disables the corresponding interrupt status bit from setting the interrupt output. The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from setting the interrupt output. The status bit is not affected. Default = 0.
Rev. 0 | Page 34 of 40
Page 35
ADM1033
Table 46. Register 0x0B, Local High Limit, Power-On Default = 0x8B, Lock = N, SW Reset = N
Bit Name R/W Description
<7:0> Local High Limit R/W
Table 47. Register 0x0C, Local Low Limit, Power-On Default = 0x54, Clock = N, SW Reset = N
Bit Name R/W Description
<7:0> Local Low Limit R/W
Table 48. Register 0x0D, Local
Bit Name R/W Description
<7:0>
Local
THERM Limit
THERM
Limit, Power-On Default = 0x95, Lock = Y, SW Reset = N
R/W
Table 49. Register 0x0E, Remote High Limit, Power-On Default = 0x8B, Lock = N, SW Reset = N
Bit Name R/W Description
<7:0> Remote High Limit R/W
Table 50. Register 0x0F, Remote Low Limit, Power-On Default = 0x54, Lock = N, SW Reset = N
Bit Name R/W Description
<7:0> Remote Low Limit R/W
Table 51. Register 0x10, Remote
Bit Name R/W Description
<7:0>
Remote
THERM Limit
THERM
Limit, Power-On Default = 0x95, Lock = Y, SW Reset = N
R/W
Table 52. Register 0x16, Local Offset Register, Power-On Default = 0x00, Lock = Y, SW Reset = N
Bit Name R/W Description
<7:0> Local Offset R/W
Table 53. Register 0x17, Remote Offset Register, Power-On Default = 0x00, Lock = Y, SW Reset = N
Bit Name R/W Description
<7:0> Remote Offset R/W
Table 54. Register 0x19,
Bit Name R/W Description
<7:0>
THERM Timer on % Limit
THERM
Timer % Limit, Power-On Default = 0xFF, Lock = Y, SW Reset = N
R/W
When the local temperature exceeds this point, the corresponding interrupt status bit is set.
When the local temperature falls below this point, the corresponding interrupt status bit is set.
When the local temperature exceeds this point, the corresponding status bit is set and the
When the remote temperature exceeds this point, the corresponding interrupt status bit is set.
When the remote temperature falls below this point, the corresponding interrupt status bit is set.
When the temperature exceeds this point, the corresponding status bit is set and the THERM output is activated.
Allows a twos complement offset to be automatically added to or subtracted from the local temperature measurement. Resolution = 0.125°C. Maximum offset = 16°C to +15.875°C. Default = 0.
Allows a twos complement offset to be automatically added to or subtracted from the remote temperature measurement. Resolution = 0.125°C. Maximum offset = −16°C to +15.875°C. Default = 0.
If the THERM is asserted for greater than or equal to the THERM timer on % limit of the time window, then the corresponding status bit is set.
THERM output is activated.
Rev. 0 | Page 35 of 40
Page 36
ADM1033
Table 55. Register 0x1A,
Bit Name R/W Description
<7:4> Reserved R Reserved. <3:0>
THERM Hysteresis
THERM
Table 56. Look-Up Table Registers, Lock = Y, SW Reset = Y
Register Address R/W Description Power-On Default
0x22 R/W Look-Up Table, T1 0xFF 0x23 R/W Look-Up Table, T2 0xFF 0x24 R/W Look-Up Table, T3 0xFF 0x25 R/W Look-Up Table, T4 0xFF 0x26 R/W Look-Up Table, T5 0xFF 0x27 R/W Look-Up Table, T6 0xFF 0x28 R/W Look-Up Table, T7 0xFF 0x29 R/W Look-Up Table, T8 0xFF 0x2A R/W Look-Up Table, RPM1, LSB 0xFF 0x2B R/W Look-Up Table, RPM1, MSB 0xFF 0x2C R/W Look-Up Table, RPM2, LSB 0xFF 0x2D R/W Look-Up Table, RPM2, MSB 0xFF 0x2E R/W Look-Up Table, RPM3, LSB 0xFF 0x2F R/W Look-Up Table, RPM3, MSB 0xFF 0x30 R/W Look-Up Table, RPM4, LSB 0xFF 0x31 R/W Look-Up Table, RPM4, MSB 0xFF 0x32 R/W Look-Up Table, RPM5, LSB 0xFF 0x33 R/W Look-Up Table, RPM5, MSB 0xFF 0x34 R/W Look-Up Table, RPM6, LSB 0xFF 0x35 R/W Look-Up Table, RPM6, MSB 0xFF 0x36 R/W Look-Up Table, RPM7, LSB 0xFF 0x37 R/W Look-Up Table, RPM7, MSB 0xFF 0x38 R/W Look-Up Table, RPM8, LSB 0xFF 0x39 R/W Look-Up Table, RPM8, MSB 0xFF
Table 57. Register 0x3A, Look-Up Table Hysteresis, Power-On Default = 0x02, Lock = Y, SW Reset = Y
Bit Name R/W Description
<7:4> Reserved R Reserved. <3:0> Look-Up Table Hysteresis R/W
Table 58. Register 0x3, Fan Response Register, Power-On Default = 0x11, Lock = Y, SW Reset = Y
Bit Name R/W Description
<7:3> Reserved R Reserved. <2:0> Fan Response R/W These bits set the fan’s response in the rpm control mode.
Hysteresis, Power-On Default = 0x05, Lock = Y, SW Reset = N
R/W
An unsigned THERM hysteresis value, LSB = 1°C. Once THERM has been activated on a temperature channel, if the temperature drops below the limit hysteresis, the
These bits determine the hysteresis applied to the temperature thresholds in the look-up table. LSB size = 1°C.
000 = 1.25 updates/s 001 = 2.5 updates/s (default) 010 = 5 updates/s 011 = 10 updates/s 100 = 20 updates/s 101 = 40 updates/s 110 = 80 updates/s 111 = 160 updates/s
THERM is deactivated.
THERM
Rev. 0 | Page 36 of 40
Page 37
ADM1033
Table 59. Register 0x3D, Device ID, Power-On Default = 0x33, Lock = N, SW Reset = N
Bit Name R/W Description
<7:0> Device ID R This read-only value contains the device ID, which is 0x33.
Table 60. Register 0x3E, Company ID, Power-On Default = 0x41, Lock = N, SW Reset = N
Bit Name R/W Description
<7:0> Company ID R This read-only value contains the company ID, which is 0x41.
Table 61. Register 0x3D, Revision Register, Power-On Default = 0x02, Lock = N, SW Reset = N
Bit Name R/W Description
<7:0> Revision ID R This read-only value contains the revision ID.
Table 62. Register 0x40/41, Local Temperature Registers, Power-On Default = 0x02, Lock = N, SW Reset = Y
Bit Name R/W Description
<4:0> Local Temperature LSB R
<12:5> Local Temperature MSB R Contains the MSBs of the last measured local temperature value. Resolution = 1°C.
Table 63. Register 0x42/43, Remote Temperature Registers, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit Name R/W Description
<4:0> Remote Temperature LSB R
<12:5> Remote Temperature MSB R Contains the MSBs of the last measured remote temperature value. Resolution = 1°C.
Table 64. Register 0x4A/4B, TACH Period, Power-On Default = 0xFF, Lock = N, SW Reset = Y
Bit Name R/W Description
<7:0> Fan Period Count, LSB R This register contains the LSBs of the last measured fan revolution count. <15:8> Fan Period Count, MSB R This register contains the MSBs of the last measured fan revolution count.
Table 65. Register 0x4E,
Bit Name R/W Description
<7:0>
THERM % On Time
THERM
% On-Time; Power-On Default = 0x00, Lock = N, SW Reset = Y
R
Table 66. Register 0x4F, Status 1, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit Name R/W Description
7 Local Temp High R A 1 indicates the local high limit has been tripped. 6 Local Temp Low R A 1 indicates the local low limit has been tripped. 5 Remote Temp High R A 1 indicates the remote high limit has been tripped. 4 Remote Temp Low R A 1 indicates the remote low limit has been tripped. 3 Remote Diode Error R
<2:0> Reserved R Reserved.
Contains the LSBs of the last measured local temperature value. Resolution =
0.03125°C.
Contains the LSBs of the last measured remote temperature value. Resolution =
0.03125°C.
This value represents the % on time of THERM activity within the time window set by the configuration bits.
A 1 indicates a short or an open has been detected on the remote temperature channel. This test is completed once on each conversion.
Rev. 0 | Page 37 of 40
Page 38
ADM1033
Table 67. Register 0x50, Status 2, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit Name R/W Description
7 6 5 Reserved R Reserved for future use.
4
3 2 1 Reserved R Reserved.
0 Reserved R Reserved.
THERM
Local Remote
THERM % Exceeded
THERM Asserted THERM_State
THERM
Table 68. Register 0x51, Status Register 3, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit Name R/W Description
7 Fan Stalled R A 1 indicates the fan has stalled. 6 Fan Alarm Speed R
5 Reserved R Reserved. 4 Reserved R Reserved. 3 Reserved R Reserved. 2 Reserved R Reserved. 1 Reserved R Reserved. 0
ALERT Low
R R
R
R R
R
A 1 indicates the local A 1 indicates the remote THERM limit has been tripped.
A 1 indicates the THERM signal has been asserted for longer than the programmed limit. Clear on read. If
A 1 indicates the THERM signal has been asserted low, as an input only. A 1 indicates the THERM pin has been asserted low as an output.
A 1 indicates the fan is running at full speed, due to an ALARM condition (for instance, if the THERM temperature limit is exceeded).
A 1 indicates the ADM1033 has pulled the ALERT output pin low. Allows polling of a single status register to determine if an
THERM limit has been tripped.
THERM % Limit = 0x00 and THERM is asserted, it reasserts immediately.
ALERT condition has occurred in any of the status registers.
Rev. 0 | Page 38 of 40
Page 39
ADM1033

OUTLINE DIMENSIONS

0.193 BSC
0.012
0.008
9
8
0.154 BSC
0.069
0.053
SEATING PLANE
0.236 BSC
0.010
0.006
8° 0°
0.050
0.016
0.065
0.049
0.010
0.004
COPLANARITY
0.004
16
1
PIN 1
0.025 BSC
COMPLIANT TO JEDEC STANDARDS MO-137AB
Figure 44. 16-Lead Shrink Small Outline Package [QSOP]
(RQ-16)
Dimensions shown in inches

ORDERING GUIDE

Model Temperature Range Package Description Package Option
ADM1033ARQ
ADM1033ARQ-REEL ADM1033ARQ-REEL7
ADM1033ARQZ1
ADM1033ARQZ-REEL1
ADM1033ARQZ-REEL71
40°C to +125°C
40°C to +125°C
40°C to +125°C
40°C to +125°C
40°C to +125°C
40°C to +125°C
16-Lead QSOP RQ-16
16-Lead QSOP RQ-16 16-Lead QSOP RQ-16
16-Lead QSOP RQ-16
16-Lead QSOP RQ-16
16-Lead QSOP RQ-16
1
Z = Pb-free part.
Rev. 0 | Page 39 of 40
Page 40
ADM1033
NOTES
© 2004 Analog Devices, Inc. All rights reserved. Trademarks and registered trademarks are the property of their respective owners. D04937–0–8/04(0)
Rev. 0 | Page 40 of 40
Loading...