On-chip VCO tunes from 1.45 GHz to 1.80 GHz
External VCO/VCXO to 2.4 GHz optional
1 differential or 2 single-ended reference inputs
Reference monitoring capability
Automatic revertive and manual reference
switchover/holdover modes
Accepts LVPECL, LVDS, or CMOS references to 250 MHz
Programmable delays in path to PFD
Digital or analog lock detect, selectable
2 pairs of 1.6 GHz LVPECL outputs
Each output pair shares a 1-to-32 divider with coarse
Each output pair shares two cascaded 1-to-32 dividers
with coarse phase delay
Additive output jitter: 275 fs rms
Fine delay adjust (Δt) on each LVDS output
Each LVDS output can be reconfigured as two 250 MHz
CMOS outputs
Automatic synchronization of all outputs on power-up
Manual output synchronization available
Available in a 48-lead LFCSP
APPLICATIONS
Low jitter, low phase noise clock distribution
10/40/100 Gb/sec networking line cards, including SONET,
Synchronous Ethernet, OTU2/3/4
Forward error correction (G.710)
Clocking high speed ADCs, DACs, DDSs, DDCs, DUCs, MxFEs
High performance wireless transceivers
ATE and high performance instrumentation
GENERAL DESCRIPTION
The AD9517-41 provides a multi-output clock distribution
function with subpicosecond jitter performance, along with an
on-chip PLL and VCO. The on-chip VCO tunes from 1.45 GHz
to 1.80 GHz. Optionally, an external VCO/VCXO of up to
2.4 GHz can be used.
The AD9517-4 emphasizes low jitter and phase noise to
maximize data converter performance, and it can benefit other
applications with demanding phase noise and jitter requirements.
Integrated 1.6 GHz VCO
AD9517-4
FUNCTIONAL BLOCK DIAGRAM
PLL
∆t
∆t
∆t
∆t
LF
STATUS
MONITOR
VCO
LVPECL
LVPECL
LVDS/CMOS
LVDS/CMOS
AD9517-4
CP
REF1
REFIN
REF2
SWITCHOVER
AND MONITOR
CLK
DIV/ΦDIV/Φ
DIV/ΦDIV/Φ
SERIAL CONT ROL PORT
DIVIDER
AND MUXs
DIV/Φ
DIV/Φ
AND
DIGITAL LOGIC
Figure 1.
The AD9517-4 features four LVPECL outputs (in two pairs)
and four LVDS outputs (in two pairs). Each LVDS output can
be reconfigured as two CMOS outputs. The LVPECL outputs
operate to 1.6 GHz, the LVDS outputs operate to 800 MHz, and
the CMOS outputs operate to 250 MHz.
For applications that require additional outputs, a crystal reference
input, zero-delay, or EEPROM for automatic configuration at
startup, the AD9520 and AD9522 are available. In addition,
the AD9516 and AD9518 are similar to the AD9517 but have
a different combination of outputs.
Each pair of outputs has dividers that allow both the divide
ratio and coarse delay (or phase) to be set. The range of division
for the LVPECL outputs is 1 to 32. The LVDS/CMOS outputs
allow a range of divisions up to a maximum of 1024.
The AD9517-4 is available in a 48-lead LFCSP and can be
operated from a single 3.3 V supply. An external VCO, which
requires an extended voltage range, can be accommodated
by connecting the charge pump supply (VCP) to 5 V. A separate
LVPECL power supply can be from 2.5 V to 3.3 V (nominal).
The AD9517-4 is specified for operation over the industrial
range of −40°C to +85°C.
1
AD9517 is used throughout the data sheet to refer to all the members of the
AD9517 family. However, when AD9517-4 is used, it refers to that specific
member of the AD9517 family.
OUT0
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
06428-001
Rev. D
Information furnished by Analog Devices is believed to be accurate and reliable. However, no
responsibility is assumed by Analog Devices for its use, nor for any infringements of patents or other
rights of third parties that may result from its use. Specifications subject to change without notice. No
license is granted by implication or otherwise under any patent or patent rights of Analog Devices.
Trademarks and registered trademarks are the property of their respective owners.
Typical is g i v e n for VS = V
Minimum and maximum values are given over full V
POWER SUPPLY REQUIREMENTS
Table 1.
Parameter Min Typ Max Unit Test Conditions/Comments
VS 3.135 3.3 3.465 V 3.3 V ± 5%
V
2.375 VS V Nominally 2.5 V to 3.3 V ± 5%
S_LVPECL
VCP V
RSET Pin Resistor 4.12 kΩ Sets internal biasing currents; connect to ground
CPRSET Pin Resistor 2.7 5.1 10 kΩ Sets internal CP current range, nominally 4.8 mA (CP_lsb = 600 μA);
BYPASS Pin Capacitor 220 nF Bypass for internal LDO regulator; necessary for LDO stability;
PLL CHARACTERISTICS
Table 2.
Parameter Min Typ Max Unit Test Conditions/Comments
VCO (ON-CHIP)
Frequency Range 1450 1800 MHz
VCO Gain (K
Tuning Voltage (VT) 0.5 VCP −
Frequency Pushing (Open Loop) 1 MHz/V
Phase Noise at 100 kHz Offset −109 dBc/Hz f = 1625 MHz
Phase Noise at 1 MHz Offset −128 dBc/Hz f = 1625 MHz
REFERENCE INPUTS
Differential Mode (REFIN,
Input Frequency 0 250 MHz Frequencies below about 1 MHz should be dc-coupled; be careful
Input Sensitivity 250 mV p-p PLL figure of merit (FOM) increases with increasing slew rate
Self-Bias Voltage, REFIN 1.35 1.60 1.75 V Self-bias voltage of REFIN1
Self-Bias Voltage,
Input Resistance, REFIN 4.0 4.8 5.9 kΩ
Input Resistance,
Dual Single-Ended Mode (REF1, REF2) Two single-ended CMOS-compatible inputs
Input Frequency (AC-Coupled) 20 250 MHz Slew rate > 50 V/μs
Input Frequency (DC-Coupled) 0 250 MHz Slew rate > 50 V/μs; CMOS levels
Input Sensitivity (AC-Coupled) 0.8 V p-p Should not exceed VS p-p
Input Logic High 2.0 V
Input Logic Low 0.8 V
Input Current −100 +100 μA
Pulse Width High/Low 1.8 ns This value determines the allowable input duty cycle and is the
Differential mode (can accommodate single-ended input by ac
1.30 1.50 1.60 V
4.4 5.3 6.4 kΩ
Rev. | Page 4 of 80
= 4.12 kΩ; CP
SET
= 5.1 kΩ, unless otherwise noted.
RSET
actual current can be calculated by CP_lsb = 3.06/CPRSET; connect
to ground
connect to ground
See
Figure 15
See
Figure 10
V VCP ≤ VS when using internal VCO; outside of this range,
the CP spurs may increase due to CP up/down mismatch
grounding undriven input)
to match V
(see
(self-bias voltage)
CM
Figure 14); the input sensitivity is sufficient for ac-coupled
LVDS and LVPECL signals
1
Self-bias voltage of
Self-biased
Self-biased
1
1
REFIN
amount of time that a square wave is high/low
Each pin, REFIN/
REFIN
(REF1/REF2)
Page 5
AD9517-4
D
Parameter Min Typ Max Unit Test Conditions/Comments
CHARGE PUMP (CP) CPV is CP pin voltage; VCP is charge pump power supply voltage
ICP Sink/Source Programmable
High Value 4.8 mA With CP
Low Value 0.60 mA
Absolute Accuracy 2.5 % CPV = VCP/2 V
CP
Range 2.7/10 kΩ
RSET
ICP High Impedance Mode Leakage 1 nA
Sink-and-Source Current Matching 2 % 0.5 < CPV < VCP − 0.5 V
ICP vs. CPV 1.5 % 0.5 < CPV < VCP − 0.5 V
ICP vs. Temperature 2 % CPV = VCP/2 V
PRESCALER (PART OF N DIVIDER)
See the
Prescaler Input Frequency
P = 1 FD 300 MHz
P = 2 FD 600 MHz
P = 3 FD 900 MHz
P = 2 DM (2/3) 200 MHz
P = 4 DM (4/5) 1000 MHz
P = 8 DM (8/9) 2400 MHz
P = 16 DM (16/17) 3000 MHz
P = 32 DM (32/33) 3000 MHz
Prescaler Output Frequency 300 MHz A, B counter input frequency (prescaler input frequency divided by P)
Below about 1 MHz, the input should be dc-coupled. Care should be taken to match VCM.
CLOCK OUTPUTS
Table 4.
Parameter Min Typ Max Unit Test Conditions/Comments
LVPECL CLOCK OUTPUTS Termination = 50 Ω to VS − 2 V
OUT0, OUT1, OUT2, OUT3
Output Frequency, Maximum 2950 MHz
Output High Voltage (VOH)
Output Low Voltage (VOL)
Output Differential Voltage (VOD) 550 790 980 mV
LVDS CLOCK OUTPUTS Differential termination 100 Ω at 3.5 mA
OUT4, OUT5, OUT6, OUT7
Output Frequency 800 MHz
Output Differential Voltage (VOD) 247 360 454 mV
Delta VOD 25 mV
Output Offset Voltage (VOS) 1.125 1.24 1.375 V (VOH + VOL)/2 across a differential pair
Delta VOS 25 mV
Short-Circuit Current (ISA, ISB) 14 24 mA Output shorted to GND
Differential input
1
1.6 GHz Distribution only (VCO divider bypassed)
Measured at 2.4 GHz; jitter performance is improved
with slew rates > 1 V/ns
Larger voltage swings may turn on the protection
diodes and may degrade jitter performance
1.3 1.8 V With 200 mV p-p signal applied; dc-coupled
CMR
CLK ac-coupled; CLK
Differential (OUT, OUT
ac-bypassed to RF ground
)
Using direct to output; see Figure 25 for peak-to-peak
differential amplitude
V
S_LVPECL
1.12
V
S_LVPECL
2.03
−
−
V
S_LVPECL
0.98
V
S_LVPECL
1.77
−
−
V
S_LVPECL
0.84
V
S_LVPECL
1.49
V
−
V
−
This is V
− VOL for each leg of a differential pair for
OH
default amplitude setting with driver not toggling; the
peak-to-peak amplitude measured using a differential
probe across the differential pair with the driver toggling
is roughly 2× these values (see Figure 25 for variation
over frequency)
Differential (OUT, OUT
)
The AD9517 outputs toggle at higher frequencies,
but the output amplitude may not meet the V
specification; see Figure 26
− VOL measurement across a differential pair at the
V
OH
default amplitude setting with output driver not
toggling; see Figure 26 for variation over frequency
This is the absolute value of the difference between
when the normal output is high vs. when the
V
OD
complementary output is high
This is the absolute value of the difference between
when the normal output is high vs. when the
V
OS
complementary output is high
OD
Rev. | Page 6 of 80
Page 7
AD9517-4
D
Parameter Min Typ Max Unit Test Conditions/Comments
CMOS CLOCK OUTPUTS
OUT4A, OUT4B, OUT5A, OUT5B,
OUT6A, OUT6B, OUT7A,
OUT7B
Output Frequency 250 MHz See Figure 27
Output Voltage
High (VOH) VS − 0.1 V At 1 mA load
Low (VOL) 0.1 V At 1 mA load
Source Current Exceeding these values can result in damage to the part
Static 20 mA
Dynamic 16 mA
Sink Current Exceeding these values can result in damage to the part
Static 8 mA
Dynamic 16 mA
Single-ended; termination = 10 pF
Rev. | Page 7 of 80
Page 8
AD9517-4
D
TIMING CHARACTERISTICS
Table 5.
Parameter Min Typ Max Unit Test Conditions/Comments
LVPECL Termination = 50 Ω to VS − 2 V; level = 810 mV
Output Rise Time, tRP 70 180 ps 20% to 80%, measured differentially
Output Fall Time, tFP 70 180 ps 80% to 20%, measured differentially
PROPAGATION DELAY, t
High Frequency Clock Distribution Configuration 835 995 1180 ps
Clock Distribution Configuration 773 933 1090 ps
Variation with Temperature 0.8 ps/°C
OUTPUT SKEW, LVPECL OUTPUTS1
LVPECL Outputs That Share the Same Divider 5 15 ps
LVPECL Outputs on Different Dividers 13 40 ps
All LVPECL Outputs Across Multiple Parts 220 ps
LVDS Termination = 100 Ω differential; 3.5 mA
Output Rise Time, tRL 170 350 ps 20% to 80%, measured differentially2
Output Fall Time, tFL 160 350 ps 20% to 80%, measured differentially2
PROPAGATION DELAY, t
For All Divide Values 1.4 1.8 2.1 ns
Variation with Temperature 1.25 ps/°C
OUTPUT SKEW, LVDS OUTPUTS1 Delay off on all outputs
LVDS Outputs That Share the Same Divider 6 62 ps
LVDS Outputs on Different Dividers 25 150 ps
All LVDS Outputs Across Multiple Parts 430 ps
CMOS Termination = open
Output Rise Time, tRC 495 1000 ps 20% to 80%; C
Output Fall Time, tFC 475 985 ps 80% to 20%; C
PROPAGATION DELAY, t
For All Divide Values 1.6 2.1 2.6 ns
Variation with Temperature 2.6 ps/°C
OUTPUT SKEW, CMOS OUTPUTS1 Fine delay off
CMOS Outputs That Share the Same Divider 4 66 ps
All CMOS Outputs on Different Dividers 28 180 ps
All CMOS Outputs Across Multiple Parts 675 ps
Application example based on a typical
setup where the reference source is clean,
so a wider PLL loop bandwidth is used;
reference = 15.36 MHz; R = 1
Application example based on a typical
setup where the reference source is jittery,
so a narrower PLL loop bandwidth is used;
reference = 10.0 MHz; R = 20
CLOCK OUTPUT ABSOLUTE TIME JITTER (CLOCK GENERATION USING EXTERNAL VCXO)
Table 10.
Parameter Min Typ Max Unit Test Conditions/Comments
Distribution section only; does not include PLL
and VCO; uses rising edge of clock signal
Calculated from SNR of ADC method;
DCC not used for even divides
Calculated from SNR of ADC method;
DCC on
Distribution section only; does not include PLL
and VCO; uses rising edge of clock signal
Calculated from SNR of ADC method;
DCC not used for even divides
Distribution section only; does not include PLL
and VCO; uses rising edge of clock signal
Calculated from SNR of ADC method;
DCC not used for even divides
CLOCK OUTPUT ADDITIVE TIME JITTER (VCO DIVIDER USED)
Table 12.
Parameter Min Typ Max Unit Test Conditions/Comments
LVPECL OUTPUT ADDITIVE TIME JITTER
CLK = 2.4 GHz; VCO DIV = 2; LVPECL = 100 MHz;
Divider = 12; Duty-Cycle Correction = Off
LVDS OUTPUT ADDITIVE TIME JITTER
CLK = 2.4 GHz; VCO DIV = 2; LVDS = 100 MHz;
Divider = 12; Duty-Cycle Correction = Off
CMOS OUTPUT ADDITIVE TIME JITTER
CLK = 2.4 GHz; VCO DIV = 2; CMOS = 100 MHz;
Divider = 12; Duty-Cycle Correction = Off
210 fs rms Calculated from SNR of ADC method
285 fs rms Calculated from SNR of ADC method
350 fs rms Calculated from SNR of ADC method
Distribution section only; does not include PLL
and VCO; uses rising edge of clock signal
Distribution section only; does not include PLL
and VCO; uses rising edge of clock signal
Distribution section only; does not include PLL
and VCO; uses rising edge of clock signal
Rev. | Page 12 of 80
Page 13
AD9517-4
D
DELAY BLOCK ADDITIVE TIME JITTER
Table 13.
Parameter Min Typ Max Unit Test Conditions/Comments
DELAY BLOCK ADDITIVE TIME JITTER1 Incremental additive jitter
100 MHz Output
Delay (1600 μA, 0x1C) Fine Adj. 000000b 0.54 ps rms
Delay (1600 μA, 0x1C) Fine Adj. 101111b 0.60 ps rms
Delay (800 μA, 0x1C) Fine Adj. 000000b 0.65 ps rms
Delay (800 μA, 0x1C) Fine Adj. 101111b 0.85 ps rms
Delay (800 μA, 0x4C) Fine Adj. 000000b 0.79 ps rms
Delay (800 μA, 0x4C) Fine Adj. 101111b 1.2 ps rms
Delay (400 μA, 0x4C) Fine Adj. 000000b 1.2 ps rms
Delay (400 μA, 0x4C) Fine Adj. 101111b 2.0 ps rms
Delay (200 μA, 0x1C) Fine Adj. 000000b 1.3 ps rms
Delay (200 μA, 0x1C) Fine Adj. 101111b 2.5 ps rms
Delay (200 μA, 0x4C) Fine Adj. 000000b 1.9 ps rms
Delay (200 μA, 0x4C) Fine Adj. 101111b 3.8 ps rms
1
This value is incremental. That is, it is in addition to the jitter of the LVDS or CMOS output without the delay. To estimate the total jitter, the LVDS or CMOS output jitter
should be added to this value using the root sum of the squares (RSS) method.
SERIAL CONTROL PORT
Table 14.
Parameter Min Typ Max Unit Test Conditions/Comments
CS (INPUT)
CS has an internal 30 kΩ pull-up resistor
Input Logic 1 Voltage 2.0 V
Input Logic 0 Voltage 0.8 V
Input Logic 1 Current 3 μA
Input Logic 0 Current 110 μA
Input Capacitance 2 pF
SCLK (INPUT) SCLK has an internal 30 kΩ pull-down resistor
Input Logic 1 Voltage 2.0 V
Input Logic 0 Voltage 0.8 V
Input Logic 1 Current 110 μA
Input Logic 0 Current 1 μA
Input Capacitance 2 pF
SDIO (WHEN INPUT)
Input Logic 1 Voltage 2.0 V
Input Logic 0 Voltage 0.8 V
Input Logic 1 Current 10 nA
Input Logic 0 Current 20 nA
Input Capacitance 2 pF
SDIO, SDO (OUTPUTS)
Output Logic 1 Voltage 2.7 V
Output Logic 0 Voltage 0.4 V
TIMING
Clock Rate (SCLK, 1/t
Pulse Width High, t
Pulse Width Low, t
) 25 MHz
SCLK
16 ns
HIGH
16 ns
LOW
SDIO to SCLK Setup, tDS 2 ns
SCLK to SDIO Hold, tDH 1.1 ns
SCLK to Valid SDIO and SDO, tDV 8 ns
CS to SCLK Setup and Hold, tS, tH
CS Minimum Pulse Width High, t
PWH
2 ns
3 ns
Rev. | Page 13 of 80
Page 14
AD9517-4
D
PD, SYNC, AND RESET PINS
Table 15.
Parameter Min Typ Max Unit Test Conditions/Comments
INPUT CHARACTERISTICS
Logic 1 Voltage 2.0 V
Logic 0 Voltage 0.8 V
Logic 1 Current 1 μA
Logic 0 Current 110 μA
Capacitance 2 pF
RESET TIMING
Pulse Width Low 50 ns
SYNC TIMING
Pulse Width Low 1.5
High speed
clock cycles
LD, STATUS, AND REFMON PINS
Table 16.
Parameter Min Typ Max Unit Test Conditions/Comments
OUTPUT CHARACTERISTICS
Output Voltage High (VOH) 2.7 V
Output Voltage Low (VOL) 0.4 V
MAXIMUM TOGGLE RATE 100 MHz
ANALOG LOCK DETECT
Capacitance 3 pF
REF1, REF2, AND VCO FREQUENCY STATUS MONITOR
Normal Range 1.02 MHz
Extended Range (REF1 and REF2 Only) 8 kHz
LD PIN COMPARATOR
Trip Point 1.6 V
Hysteresis 260 mV
These pins each have a 30 kΩ internal pull-up
resistor
High speed clock is CLK input signal
When selected as a digital output (CMOS);
there are other modes in which these pins
are not CMOS digital outputs; see Table 54 ,
Register 0x017, Register 0x01A, and
Register 0x01B
Applies when mux is set to any divider or
counter output, or PFD up/down pulse; also
applies in analog lock detect mode; usually
debug mode only; beware that spurs may
couple to output when any of these pins are
toggling
On-chip capacitance; used to calculate RC
time constant for analog lock detect
readback; use a pull-up resistor
Frequency above which the monitor always
indicates the presence of the reference
Frequency above which the monitor always
indicates the presence of the reference
Rev. | Page 14 of 80
Page 15
AD9517-4
D
POWER DISSIPATION
Table 17.
Parameter Min Typ Max Unit Test Conditions/Comments
POWER DELTAS, INDIVIDUAL FUNCTIONS Power delta when a function is enabled/disabled
VCO Divider 30 mW VCO divider bypassed
REFIN (Differential) 20 mW All references off to differential reference enabled
REF1, REF2 (Single-Ended) 4 mW
VCO 70 mW CLK input selected to VCO selected
PLL 75 mW PLL off to PLL on, normal operation; no reference enabled
Channel Divider 30 mW Divider bypassed to divide-by-2 to divide-by-32
LVPECL Channel (Divider Plus Output Driver) 160 mW
LVPECL Driver 90 mW Second LVPECL output turned on, same channel
LVDS Channel (Divider Plus Output Driver) 120 mW
LVDS Driver 50 mW Second LVDS output turned on, same channel
CMOS Channel (Divider Plus Output Driver) 100 mW
CMOS Driver (Second in Pair) 0 mW Static; second CMOS output, same pair, turned on
CMOS Driver (First in Second Pair) 30 mW Static; first output, second pair, turned on
Fine Delay Block 50 mW Delay block off to delay block enabled; maximum current setting
75 185 mW
31 mW
No clock; no programming; default register values;
does not include power dissipated in external resistors
PLL on; internal VCO = 2750 MHz; VCO divider = 2;
all channel dividers on; four LVPECL outputs at 687.5 MHz;
eight CMOS outputs (10 pF load) at 229 MHz; all fine delay on,
maximum current; does not include power dissipated in
external resistors
PLL on; internal VCO = 2800 MHz, VCO divider = 2;
all channel dividers on; four LVPECL outputs at 700 MHz;
four LVDS outputs at 200 MHz; all fine delay on, maximum
current; does not include power dissipated in external resistors
PD pin pulled low; does not include power dissipated in
terminations
All references off to REF1 or REF2 enabled; differential
reference not enabled
No LVPECL output on to one LVPECL output on, independent
of frequency
No LVDS output on to one LVDS output on; see Figure 8 for
dependence on output frequency
Static; no CMOS output on to one CMOS output on; see
Figure 9 for variation over output frequency
Rev. | Page 15 of 80
Page 16
AD9517-4
K
D
TIMING DIAGRAMS
t
CLK
CL
DIFFERENTIAL
80%
20%
t
LVDS
t
PECL
LVDS
t
CMOS
Figure 2. CLK/
DIFFERENTIAL
80%
20%
Figure 3. LVPECL Timing, Differential
CLK
to Clock Output Timing, DIV = 1
LVPECL
t
RP
t
RL
06428-060
Figure 4. LVDS Timing, Differential
SINGL E-ENDE D
80%
CMOS
10pF LOAD
20%
t
FP
06428-061
t
RC
Figure 5. CMOS Timing, Single-Ended, 10 pF Load
t
FL
t
FC
06428-062
06428-063
Rev. | Page 16 of 80
Page 17
AD9517-4
D
ABSOLUTE MAXIMUM RATINGS
Table 18.
Parameter Rating
VS, VS_LVPECL to GND −0.3 V to +3.6 V
VCP to GND −0.3 V to +5.8 V
REFIN, REFIN to GND
REFIN to REFIN
−0.3 V to V
−3.3 V to +3.3 V
+ 0.3 V
S
RSET to GND −0.3 V to VS + 0.3 V
CPRSET to GND −0.3 V to VS + 0.3 V
CLK, CLK to GND
CLK to CLK
SCLK, SDIO, SDO, CS to GND
OUT0, OUT0, OUT1, OUT1, OUT2, OUT2,
OUT3, OUT3
OUT6, OUT6
,OUT4, OUT4, OUT5, OUT5,
, OUT7, OUT7 to GND
SYNC to GND
−0.3 V to V
−1.2 V to +1.2 V
−0.3 V to V
−0.3 V to V
−0.3 V to V
+ 0.3 V
S
+ 0.3 V
S
+ 0.3 V
S
+ 0.3 V
S
REFMON, STATUS, LD to GND −0.3 V to VS + 0.3 V
Junction Temperature1 150°C
Storage Temperature Range −65°C to +150°C
Lead Temperature (10 sec) 300°C
1
See Table 19 for θJA.
Stresses above those listed under Absolute Maximum Ratings
may cause permanent damage to the device. This is a stress
rating only; functional operation of the device at these or any
other conditions above those indicated in the operational
section of this specification is not implied. Exposure to absolute
maximum rating conditions for extended periods may affect
device reliability.
THERMAL RESISTANCE
Table 19.
Package Type1 θ
Unit
JA
48-Lead LFCSP 24.7 °C/W
1
Thermal impedance measurements were taken on a 4-layer board in still air
in accordance with EIA/JESD51-2.
ESD CAUTION
Rev. | Page 17 of 80
Page 18
AD9517-4
D
PIN CONFIGURATION AND FUNCTION DESCRIPTIONS
REFIN (REF 1)
REFIN (REF 2)
CPRSETVSRSETVSOUT0
4847464544434241403938
OUT0
VS_LVPECL
OUT1
OUT1
VS
37
REFMON
REF_SEL
BYPASS
NOTES
1. THE EXTERNAL PADDLE ON T HE BOTTO M OF THE PACKAGE MUST BE
CONNECTED TO GROUND FO R PROPER OPERAT ION.
LD
VCP
CP
STATUS
SYNC
VS
CLK
CLK
1
2
3
4
5
6
7
8
LF
9
10
11
12
PIN 1
INDICATO R
13141516171819
CS
SCLK
Table 20. Pin Function Descriptions
Input/
Pin No.
Output
Pin Type Mnemonic Description
1 O 3.3 V CMOS REFMON
2 O 3.3 V CMOS LD
3 I Power VCP
4 O 3.3 V CMOS CP
5 O 3.3 V CMOS STATUS
6 I 3.3 V CMOS REF_SEL
7 I 3.3 V CMOS
SYNC
8 I Loop filter LF
9 O Loop filter BYPASS
10, 24, 25,
I Power VS
30, 31, 36,
37, 43, 45
11 I
Differential
CLK
clock input
12 I
Differential
Along with CLK, this is the self-biased differential input for the clock distribution
CLK
clock input
13 I 3.3 V CMOS SCLK
14 I 3.3 V CMOS
Serial Control Port Chip Select; Active Low. This pin has an internal 30 kΩ pull-up
CS
36
S
V
35
OUT4 (OUT4A)
34
OUT4 (OUT4B)
33
OUT5 (OUT5A)
32
VS
OUT5 (OUT5B)
31
VS
30
VS
29
OUT7 (OUT7B)
28
OUT7 (OUT7A)
27
OUT6 (OUT6B)
26
OUT6 (OUT6A)
25
V
S
06428-003
AD9517-4
TOP VIEW
(Not to Scale)
SDO
SDIO
RESET
PD
OUT2
2021222324
OUT2
OUT3
OUT3
VS_LVPECL
Figure 6. Pin Configuration
Reference Monitor (Output). This pin has multiple selectable outputs; see Table 54,
Register 0x01B.
Lock Detect (Output). This pin has multiple selectable outputs; see Table 5 4,
Register 0x01A.
Power Supply for Charge Pump (CP); V
≤ VCP ≤ 5.0 V. This pin is usually 3.3 V for
S
most applications; but if a 5 V external VCXO is used, this pin should be 5 V.
Charge Pump (Output). Connects to external loop filter.
Status (Output). This pin has multiple selectable outputs; see Table 54, Register 0x017.
Reference Select. Selects REF1 (low) or REF2 (high). This pin has an internal 30 kΩ
pull-down resistor.
Manual Synchronizations and Manual Holdover. This pin initiates a manual
synchronization and is also used for manual holdover. Active low. This pin has an
internal 30 kΩ pull-up resistor.
Loop Filter (Input). Connects to VCO control voltage node internally. This pin has
31 pF of internal capacitance to ground, which may influence the loop filter design
for large loop bandwidths.
This pin is for bypassing the LDO to ground with a capacitor.
3.3 V Power Pins.
Along with CLK
, this is the self-biased differential input for the clock distribution
section. This pin can be left floating if internal VCO is used.
section. This pin can be left floating if internal VCO is used.
Serial Control Port Data Clock Signal.
resistor.
Rev. | Page 18 of 80
Page 19
AD9517-4
D
Input/
Pin No.
15 O 3.3 V CMOS SDO Serial Control Port. Unidirectional serial data output.
16 I/O 3.3 V CMOS SDIO
17 I 3.3 V CMOS
18 I 3.3 V CMOS
21, 40 I Power VS_LVPECL Extended Voltage 2.5 V to 3.3 V LVPECL Power Pins.
42 O LVPECL OUT0 LVPECL Output; One Side of a Differential LVPECL Output.
41 O LVPECL
39 O LVPECL OUT1 LVPECL Output; One Side of a Differential LVPECL Output.
38 O LVPECL
19 O LVPECL OUT2 LVPECL Output; One Side of a Differential LVPECL Output.
20 O LVPECL
22 O LVPECL OUT3 LVPECL Output; One Side of a Differential LVPECL Output.
23 O LVPECL
35 O
34 O
33 O
32 O
26 O
27 O
28 O
29 O
44 O
46 O
47 I
48 I
EPAD GND GND
Output Pin Type Mnemonic Description
Serial Control Port. Bidirectional serial data input/output and unidirectional serial
data input.
Chip Reset, Active Low. This pin has an internal 30 kΩ pull-up resistor.
Chip Power Down, Active Low. This pin has an internal 30 kΩ pull-up resistor.
LVPECL Output; One Side of a Differential LVPECL Output.
LVPECL Output; One Side of a Differential LVPECL Output.
LVPECL Output; One Side of a Differential LVPECL Output.
LVPECL Output; One Side of a Differential LVPECL Output.
LVDS/CMOS Output; One Side of a Differential LVDS Output
or a Single-Ended CMOS Output.
or a Single-Ended CMOS Output.
LVDS/CMOS Output; One Side of a Differential LVDS Output
or a Single-Ended CMOS Output.
or a Single-Ended CMOS Output.
LVDS/CMOS Output; One Side of a Differential LVDS Output
or a Single-Ended CMOS Output.
or a Single-Ended CMOS Output.
LVDS/CMOS Output; One Side of a Differential LVDS Output
or a Single-Ended CMOS Output.
or a Single-Ended CMOS Output.
Alternatively, this pin is a single-ended input for REF2.
Along with REFIN
Alternatively, this pin is a single-ended input for REF1.
Ground. The external paddle on the bottom of the package must be connected to
ground for proper operation.
LVDS or
CMOS
LVDS or
CMOS
LVDS or
CMOS
LVDS or
CMOS
LVDS or
CMOS
LVDS or
CMOS
LVDS or
CMOS
LVDS or
CMOS
Current set
resistor
Current set
resistor
Reference
input
Reference
input
RESET
PD
OUT0
OUT1
OUT2
OUT3
OUT4 (OUT4A)
(OUT4B) LVDS/CMOS Output; One Side of a Differential LVDS Output
OUT4
OUT5 (OUT5A)
(OUT5B) LVDS/CMOS Output; One Side of a Differential LVDS Output
OUT5
OUT6 (OUT6A)
(OUT6B) LVDS/CMOS Output; One Side of a Differential LVDS Output
OUT6
OUT7 (OUT7A)
(OUT7B) LVDS/CMOS Output; One Side of a Differential LVDS Output
OUT7
RSET Resistor connected here sets internal bias currents. Nominal value = 4.12 kΩ.
CPRSET Resistor connected here sets CP current range. Nominal value = 5.1 kΩ.
(REF2) Along with REFIN, this is the self-biased differential input for the PLL reference.
REFIN
REFIN (REF1)
, this is the self-biased differential input for the PLL reference.
Rev. | Page 19 of 80
Page 20
AD9517-4
D
TYPICAL PERFORMANCE CHARACTERISTICS
240
220
200
180
160
CURRENT (mA)
140
2 CHANNELS—4 LVPE CL
2 CHANNELS—2 LVPE CL
50
45
40
35
(MHz/V)
VCO
K
30
120
100
050010001500200025003000
1 CHANNEL—1 LVPECL
FREQUENCY (MHz)
Figure 7. Current vs. Frequency, Direct to Output, LVPECL Outputs
180
2 CHANNELS—4 LVDS
160
140
120
CURRENT (mA)
100
80
0200400600800
2 CHANNELS—2 LVDS
1 CHANNEL—1 LVDS
FREQUENCY (MHz )
Figure 8. Current vs. Frequency—LVDS Outputs
(Includes Clock Distribution Current Draw)
240
220
200
180
160
140
CURRENT (mA)
120
100
2 CHANNELS—8 CMOS
1 CHANNEL—2 CMOS
80
0220015010050
2 CHANNELS—2 CMOS
1 CHANNEL—1 CMOS
FREQUENCY (MHz )
Figure 9. Current vs. Frequency—CMOS Outputs
25
20
1.451.551. 651.75
06428-007
VCO FREQUENCY ( GHz)
Figure 10. VCO K
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
CURRENT FROM CP P IN (mA)
1.0
0.5
06428-008
PUMP DOWNPUMP UP
0
00.51.01.52.02.53.0
VOLTAGE ON CP PIN (V)
Figure 11. Charge Pump Characteristics at V
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
CURRENT FROM CP P IN (mA)
1.0
0.5
50
06428-009
0
PUMP DOWNPUMP UP
00.5 1.0 1.5 2.03.04.02. 53.55.04.5
VOLTAGE ON CP PIN (V)
Figure 12. Charge Pump Characteristics at V
vs. Frequency
VCO
= 3.3 V
CP
= 5.0 V
CP
06428-200
06428-011
06428-012
Rev. | Page 20 of 80
Page 21
AD9517-4
–
–
D
140
–145
–150
–155
(dBc/Hz)
–160
–165
PFD PHASE NOI SE REFERRED TO PFD INPUT
–170
0.1110010
PFD FREQUENCY (MHz)
Figure 13. PFD Phase Noise Referred to PFD Input vs. PFD Frequency
210
–212
–214
–216
–218
–220
PLL FIGURE OF MERIT (dBc/ Hz)
–222
–224
022.01.51.00. 5
SLEW RATE (V/n s)
Figure 14. PLL Figure of Merit (FOM) vs. Slew Rate at REFIN/
2.1
1.9
1.7
1.5
1.3
VCO TUNING V OLTAGE (V)
1.1
0.9
1.451.551.651.751.501.601.701.80
FREQUENCY (GHz)
Figure 15. VCO Tuning Voltage vs. Frequency
(Note that VCO calibration centers the dc tuning voltage
for the PLL setup that is active during calibration.)
An ideal sine wave can be thought of as having a continuous
and even progression of phase with time from 0° to 360° for
each cycle. Actual signals, however, display a certain amount
of variation from ideal phase progression over time. This
phenomenon is called phase jitter. Although many causes can
contribute to phase jitter, one major cause is random noise,
which is characterized statistically as being Gaussian (normal)
in distribution.
This phase jitter leads to a spreading out of the energy of the
sine wave in the frequency domain, producing a continuous
power spectrum. This power spectrum is usually reported as
a series of values whose units are dBc/Hz at a given offset in
frequency from the sine wave (carrier). The value is a ratio
(expressed in dB) of the power contained within a 1 Hz
bandwidth with respect to the power at the carrier frequency.
For each measurement, the offset from the carrier frequency is
also given.
It is meaningful to integrate the total power contained within
some interval of offset frequencies (for example, 10 kHz to
10 MHz). This is called the integrated phase noise over that
frequency offset interval and can be readily related to the time
jitter due to the phase noise within that offset frequency interval.
Phase noise has a detrimental effect on the performance of
ADCs, DACs, and RF mixers. It lowers the achievable dynamic
range of the converters and mixers, although they are affected
in somewhat different ways.
Time Jitter
Phase noise is a frequency domain phenomenon. In the time
domain, the same effect is exhibited as time jitter. When
observing a sine wave, the time of successive zero crossings
varies. In a square wave, the time jitter is a displacement of the
edges from their ideal (regular) times of occurrence. In both
cases, the variations in timing from the ideal are the time jitter.
Because these variations are random in nature, the time jitter is
specified in units of seconds root mean square (rms) or 1 sigma
of the Gaussian distribution.
Time jitter that occurs on a sampling clock for a DAC or an
ADC decreases the signal-to-noise ratio (SNR) and dynamic
range of the converter. A sampling clock with the lowest possible
jitter provides the highest performance from a given converter.
Additive Phase Noise
Additive phase noise is the amount of phase noise that can be
attributed to the device or subsystem being measured. The
phase noise of any external oscillators or clock sources is
subtracted. This makes it possible to predict the degree to which
the device impacts the total system phase noise when used in
conjunction with the various oscillators and clock sources, each
of which contributes its own phase noise to the total. In many
cases, the phase noise of one element dominates the system
phase noise. When there are multiple contributors to phase
noise, the total is the square root of the sum of squares of the
individual contributors.
Additive Time Jitter
Additive time jitter is the amount of time jitter that can be
attributed to the device or subsystem being measured. The time
jitter of any external oscillators or clock sources is subtracted. This
makes it possible to predict the degree to which the device impacts
the total system time jitter when used in conjunction with the
various oscillators and clock sources, each of which contributes
its own time jitter to the total. In many cases, the time jitter of
the external oscillators and clock sources dominates the system
time jitter.
Rev. | Page 26 of 80
Page 27
AD9517-4
V
D
DETAILED BLOCK DIAGRAM
REFIN ( REF1)
REFIN ( REF2)
BYPASS
CLK
CLK
SYNC
RESET
SCLK
SDIO
SDO
REF1
REF2
REGULATOR ( LDO)
LF
PD
CS
REF_ SELCPRSETVCP
REFERENCE
SWITCHOVER
STATUS
STATUS
LOW DROPOUT
VCO
DIGITAL
LOGIC
SERIAL
CONTROL
PORT
SGNDRSET
DISTRIBUTI ON
REFERENCE
R
DIVIDER
VCO STATUS
P, P + 1
PRESCALER
DIVIDE BY
2, 3, 4, 5, OR 6
01
N DIVIDE R
A/B
COUNTERS
DIVIDE BY
1 TO 32
REFMO N
PROGRAMMABLE
R DELAY
PROGRAMMABLE
N DELAY
DIVIDE BY
1 TO 32
DIVIDE BY
1 TO 32
DIVIDE BY
1 TO 32
LOCK
DETECT
PHASE
FREQUENCY
DETECTOR
PLL
REFERENCE
∆T
∆T
CHARGE
PUMP
LVDS/CMOS
HOLD
LVPECL
LVPECL
LD
CP
STATUS
OUT0
OUT0
OUT1
OUT1
OUT2
OUT2
OUT3
OUT3
OUT4 (OUT4A)
OUT4 (OUT4B)
OUT5 (OUT5A)
OUT5 (OUT5B)
AD9517-4
DIVIDE BY
1 TO 32
DIVIDE BY
Figure 42. Detailed Block Diagram
Rev. | Page 27 of 80
1 TO 32
∆T
∆T
LVDS/CMOS
OUT6 (OUT6A)
OUT6 (OUT6B)
OUT7 (OUT7A)
OUT7 (OUT7B)
6428-002
Page 28
AD9517-4
D
THEORY OF OPERATION
OPERATIONAL CONFIGURATIONS
The AD9517 can be configured in several ways. These
configurations must be set up by loading the control registers
(see Tabl e 52 and Ta bl e 53 through Tabl e 6 2 ). Each section or
function must be individually programmed by setting the
appropriate bits in the corresponding control register or registers.
High Frequency Clock Distribution—CLK or External
VCO > 1600 MHz
The AD9517 power-up default configuration has the PLL
powered off and the routing of the input set so that the
CLK
CLK/
through the VCO divider (divide-by-2/ divide-by-3/divide-by-4/
divide-by-5/divide-by-6). This is a distribution-only mode that
allows for an external input up to 2400 MHz (see ). The
maximum frequency that can be applied to the channel dividers
is 1600 MHz; therefore, higher input frequencies must be
divided down before reaching the channel dividers. This input
routing can also be used for lower input frequencies, but the
minimum divide is 2 before the channel dividers.
When the PLL is enabled, this routing also allows the use of the
PLL with an external VCO or VCXO with a frequency of less than
2400 MHz. In this configuration, the internal VCO is not used
and is powered off. The external VCO/VCXO feeds directly into
the prescaler.
The register settings shown in Table 2 1 are the default values of
these registers at power-up or after a reset operation. If the
contents of the registers are altered by prior programming after
power-up or reset, these registers can also be set intentionally to
these values.
After the appropriate register values are programmed,
Register 0x232 must be set to 0x01 for the values to take effect.
input is connected to the distribution section
Table 3
Table 21. Default Settings of Some PLL Registers
Register Function
0x010[1:0] = 01b PLL asynchronous power-down (PLL off ).
0x1E0[2:0] = 010b Set VCO divider = 4.
0x1E1[0] = 0b Use the VCO divider.
0x1E1[1] = 0b CLK selected as the source.
When using the internal PLL with an external VCO, the PLL
must be turned on.
Table 22. Settings When Using an External VCO
Register Function
0x010[1:0] = 00b PLL normal operation (PLL on).
0x010 to 0x01D
0x1E1[1] = 0b CLK selected as the source
PLL settings. Select and enable a reference
input; set R, N (P, A, B), PFD polarity, and I
according to the intended loop configuration.
CP
An external VCO requires an external loop filter that must be
connected between CP and the tuning pin of the VCO. This
loop filter determines the loop bandwidth and stability of the
PLL. Make sure to select the proper PFD polarity for the VCO
being used.
Table 23. Setting the PFD Polarity
Register Function
PFD polarity positive (higher control voltage
0x010[7] = 0b
0x010[7] = 1b
produces higher frequency).
PFD polarity negative (higher control
voltage produces lower frequency).
,
Rev. | Page 28 of 80
Page 29
AD9517-4
V
D
REFIN (REF 1)
REFIN (REF 2)
BYPASS
CLK
CLK
PD
SYNC
RESET
SCLK
SDIO
SDO
CS
REF1
REF2
LF
REF_ SELCPRSETVCP
REFERENCE
SWITCHOVER
STATUS
STATUS
LOW DROPOUT
REGULATOR (LDO)
VCO
DIGITAL
LOGIC
SERIAL
CONTROL
PORT
SGNDRSET
DISTRI BUTION
REFERENCE
R
DIVIDE R
VCO STATUS
P, P + 1
PRESCALER
DIVIDE BY
2, 3, 4, 5, OR 6
01
N DIVIDER
A/B
COUNTERS
DIVIDE BY
1 TO 32
REFMON
PROGRAMMABLE
R DELAY
PROGRAMMABLE
N DELAY
DIVIDE BY
1 TO 32
DIVIDE BY
1 TO 32
DIVIDE BY
1 TO 32
LOCK
DETECT
PHASE
FREQUENCY
DETECTOR
PLL
REFERENCE
∆T
∆T
CHARGE
PUMP
LVDS/CMOS
HOLD
LVPECL
LVPECL
LD
CP
STATUS
OUT0
OUT0
OUT1
OUT1
OUT2
OUT2
OUT3
OUT3
OUT4 (OUT4A)
OUT4 (OUT4B)
OUT5 (OUT5A)
OUT5 (OUT5B)
AD9517-4
DIVIDE BY
1 TO 32
DIVIDE BY
1 TO 32
Figure 43. High Frequency Clock Distribution or External VCO > 1600 MHz
Rev. | Page 29 of 80
∆T
∆T
LVDS/CMOS
OUT6 (OUT6A)
OUT6 (OUT6B)
OUT7 (OUT7A)
OUT7 (OUT7B)
06428-029
Page 30
AD9517-4
V
D
REFIN ( REF1)
REFIN ( REF2)
BYPASS
CLK
CLK
SYNC
RESET
SCLK
SDIO
SDO
REF1
REF2
LF
PD
CS
REF_ SELCPRSETVCP
REFERENCE
SWITCHOVER
STATUS
STATUS
LOW DROPOUT
REGULATOR ( LDO)
VCO
DIGITAL
LOGIC
SERIAL
CONTROL
PORT
SGNDRSET
DISTRIBUTI ON
REFERENCE
R
DIVIDER
VCO STATUS
P, P + 1
PRESCALER
DIVIDE BY
2, 3, 4, 5, OR 6
01
N DIVIDER
A/B
COUNTERS
DIVIDE BY
1 TO 32
REFMON
PROGRAMMABLE
R DELAY
PROGRAMMABLE
N DELAY
DIVIDE BY
1 TO 32
DIVIDE BY
1 TO 32
DIVIDE BY
1 TO 32
LOCK
DETECT
PHASE
FREQUENCY
DETECTOR
PLL
REFERENCE
∆T
∆T
CHARGE
PUMP
LVDS/CMOS
HOLD
LVPECL
LVPECL
LD
CP
STATUS
OUT0
OUT0
OUT1
OUT1
OUT2
OUT2
OUT3
OUT3
OUT4 (OUT4A)
OUT4 (OUT4B)
OUT5 (OUT5A)
OUT5 (OUT5B)
DIVIDE BY
1 TO 32
AD9517-4
Figure 44. Internal VCO and Clock Distribution
Internal VCO and Clock Distribution
When using the internal VCO and PLL, the VCO divider must
be employed to ensure that the frequency presented to the channel
dividers does not exceed their specified maximum frequency of
1600 MHz (see Tab l e 3 ). The internal PLL uses an external loop
filter to set the loop bandwidth. The external loop filter is also
crucial to the loop stability.
When using the internal VCO, it is necessary to calibrate the
VCO (Register 0x018[0]) to ensure optimal performance.
For internal VCO and clock distribution applications, use the
register settings that are shown in Tab le 2 4.
Rev. | Page 30 of 80
∆T
DIVIDE BY
1 TO 32
LVDS/CMOS
∆T
Table 24. Settings When Using Internal VCO
Register Function
0x010[1:0] = 00b
0x010 to 0x01D
PLL normal operation (PLL on).
PLL settings. Select and enable a reference
input; set R, N (P, A, B), PFD polarity, and I
according to the intended loop configuration.
0x018[0] = 0b,
0x232[0] = 1b
Reset VCO calibration. This is not required
the first time after power-up, but it must be
performed subsequently.
0x1E0[2:0]
Set VCO divider to divide-by-2, divide-by-3,
divide-by-4, divide-by-5, and divide-by-6.
0x1E1[0] = 0b
Use the VCO divider as the source for the
distribution section.
0x1E1[1] = 1b
0x018[0] = 1b,
0x232[0] = 1b
Select VCO as the source.
Initiate VCO calibration.
OUT6 (OUT6A)
OUT6 (OUT6B)
OUT7 (OUT7A)
OUT7 (OUT7B)
06428-030
CP
Page 31
AD9517-4
V
D
REFIN (REF1)
REFIN (REF2)
BYPASS
CLK
CLK
PD
SYNC
RESET
SCLK
SDIO
SDO
CS
REF1
REF2
LF
REF_ SELCPRSETVCP
REFERENCE
SWITCHOVER
STATUS
STATUS
LOW DROPOUT
REGULATOR (LDO)
VCO
DIGITAL
LOGIC
SERIAL
CONTROL
PORT
SGNDRSET
DISTRIBUTI ON
REFERENCE
R
DIVIDER
VCO STATUS
P, P + 1
PRESCALER
DIVIDE BY
2, 3, 4, 5, OR 6
01
N DIVIDER
A/B
COUNTERS
DIVIDE BY
1 TO 32
REFMON
PROGRAMMABLE
R DELAY
PROGRAMMABLE
N DELAY
DIVIDE BY
1 TO 32
DIVIDE BY
1 TO 32
DIVIDE BY
1 TO 32
LOCK
DETECT
PHASE
FREQUENCY
DETECTOR
PLL
REFERENCE
∆T
∆T
CHARGE
PUMP
LVDS/CMOS
HOLD
LVPECL
LVPECL
LD
CP
STATUS
OUT0
OUT0
OUT1
OUT1
OUT2
OUT2
OUT3
OUT3
OUT4 (OUT4A)
OUT4 (OUT4B)
OUT5 (OUT5A)
OUT5 (OUT5B)
OUT6 (OUT6A)
OUT6 (OUT6B)
OUT7 (OUT7A)
OUT7 (OUT7B)
06428-028
AD9517-4
DIVIDE BY
1 TO 32
DIVIDE BY
1 TO 32
∆T
LVDS/CMOS
∆T
Figure 45. Clock Distribution or External VCO < 1600 MHz
Rev. | Page 31 of 80
Page 32
AD9517-4
D
Clock Distribution or External VCO < 1600 MHz
When the external clock source to be distributed or the external
VCO/VCXO is less than 1600 MHz, a configuration that bypasses
the VCO divider can be used. This configuration differs from the
High Frequency Clock Distribution—CLK or External VCO >
1600 MHz section only in that the VCO divider (divide-by-2,
divide-by-3, divide-by-4, divide-by-5, and divide-by-6) is bypassed.
This limits the frequency of the clock source to <1600 MHz (due
to the maximum input frequency allowed at the channel dividers).
Configuration and Register Settings
For clock distribution applications where the external clock is
<1600 MHz, use the register settings that are shown in Table 25 .
Table 25. Settings for Clock Distribution < 1600 MHz
Bypass the VCO divider as source for
distribution section
When using the internal PLL with an external VCO of <1600 MHz,
the PLL must be turned on.
Table 26. Settings for Using Internal PLL with External VCO <
1600 MHz
Register Function
0x1E1[0] = 1b
0x010[1:0] = 00b
Bypass the VCO divider as source for
distribution section
PLL normal operation (PLL on), along
with other appropriate PLL settings in
Register 0x010 to Register 0x01D
An external VCO/VCXO requires an external loop filter that
must be connected between CP and the tuning pin of the
VCO/VCXO. This loop filter determines the loop bandwidth
and stability of the PLL. Make sure to select the proper PFD
polarity for the VCO/VCXO being used.
Table 27. Setting the PFD Polarity
Register Function
0x010[7] = 0b
0x010[7] = 1b
PFD polarity positive (higher control voltage
produces higher frequency)
PFD polarity negative (higher control
voltage produces lower frequency)
After the appropriate register values are programmed,
Register 0x232 must be set to 0x01 for the values to take effect.
Rev. | Page 32 of 80
Page 33
AD9517-4
VCPV
D
Phase-Locked Loop (PLL)
REF_SEL
SGND
RSET
REFMO N
CPRSET
N DIVIDER
DIST
REF
R DIVIDER
A/B
COUNTERS
0
1
REFIN ( REF1)
REFIN ( REF2)
BYPASS
LF
CLK
CLK
REFERENCE
SWITCHOVER
REF1
REF2
LOW DROPOUT
REGULATOR (LDO)
STATUS
VCO
STATUS
P, P + 1
PRESCALER
DIVIDE BY
2, 3, 4, 5, OR 6
01
Figure 46. PLL Functional Blocks
The AD9517 includes an on-chip PLL with an on-chip VCO.
The PLL blocks can be used either with the on-chip VCO to
create a complete phase-locked loop, or with an external VCO
or VCXO. The PLL requires an external loop filter, which
usually consists of a small number of capacitors and resistors.
The configuration and components of the loop filter help to
establish the loop bandwidth and stability of the operating PLL.
The AD9517 PLL is useful for generating clock frequencies
from a supplied reference frequency. This includes conversion
of reference frequencies to much higher frequencies for subsequent
division and distribution. In addition, the PLL can be exploited to
clean up jitter and phase noise on a noisy reference. The exact
choices of PLL parameters and loop dynamics are very application
specific. The flexibility and depth of the AD9517 PLL allow the
part to be tailored to function in many different applications
and signal environments.
Configuration of the PLL
The AD9517 allows flexible configuration of the PLL,
accommodating various reference frequencies, PFD comparison
frequencies, VCO frequencies, internal or external VCO/VCXO,
and loop dynamics. This is accomplished by the various settings
that include the R divider, the N divider, the PFD polarity (only
applicable to external VCO/VCXO), the antibacklash pulse width,
the charge pump current, the selection of internal VCO or
external VCO/VCXO, and the loop bandwidth.
PROGRAMMABLE
R DELAY
PROGRAMMABLE
N DELAY
VCO STATUS
These are managed through programmable register settings
(see Tabl e 52 and Ta bl e 54 ) and by the design of the external
loop filter. Successful PLL operation and satisfactory PLL loop
performance are highly dependent upon proper configuration of
the PLL settings. The design of the external loop filter is crucial
to the proper operation of the PLL. A thorough knowledge of
PLL theory and design is helpful.
ADIsimCLK™ (V1.2 or later) is a free program that can help
with the design and exploration of the capabilities and features
of the AD9517, including the design of the PLL loop filter. It is
available at www.analog.com/clocks.
Phase Frequency Detector (PFD)
The PFD takes inputs from the R counter and N counter and
produces an output proportional to the phase and frequency
difference between them. The PFD includes a programmable
delay element that controls the width of the antibacklash pulse.
This pulse ensures that there is no dead zone in the PFD transfer
function and minimizes phase noise and reference spurs. The
antibacklash pulse width is set by Register 0x017[1:0].
An important limit to keep in mind is the maximum frequency
allowed into the PFD, which in turn determines the correct
antibacklash pulse setting. The antibacklash pulse setting is
specified in the phase/frequency detector parameter of Tabl e 2.
LOCK
DETECT
PHASE
FREQUENCY
DETECTOR
PLL
REF
CHARGE PUMP
HOLD
LD
CP
STATUS
06428-064
Rev. | Page 33 of 80
Page 34
AD9517-4
D
Charge Pump (CP)
The charge pump is controlled by the PFD. The PFD monitors
the phase and frequency relationship between its two inputs,
and tells the CP to pump up or pump down to charge or
discharge the integrating node (part of the loop filter). The
integrated and filtered CP current is transformed into a voltage
that drives the tuning node of the internal VCO through the LF
pin (or the tuning pin of an external VCO) to move the VCO
frequency up or down. The CP can be set (Register 0x010[6:4])
for high impedance (allows holdover operation), for normal
operation (attempts to lock the PLL loop), for pump up, or for
pump down (test modes). The CP current is programmable in
eight steps from (nominally) 600 μA to 4.8 mA. The exact value
of the CP current LSB is set by the CPRSET resistor, which is
nominally 5.1 kΩ. If the value of the resistor connected to the
CP_RSET pin is doubled, the resulting charge pump current range
becomes 300 μA to 2.4 mA.
On-Chip VCO
The AD9517 includes an on-chip VCO covering the frequency
range shown in Tab le 2 . The calibration procedure ensures that
the VCO operating voltage is centered for the desired VCO
frequency. The VCO must be calibrated when the VCO loop
is first set up, as well as any time the nominal VCO frequency
changes. However, once the VCO is calibrated, the VCO has
sufficient operating range to stay locked over temperature and
voltage extremes without needing additional calibration. See the
VCO Calibration section for additional information.
The on-chip VCO is powered by an on-chip, low dropout
(LDO), linear voltage regulator. The LDO provides some
isolation of the VCO from variations in the power supply
voltage level. The BYPASS pin should be connected to ground
by a 220 nF capacitor to ensure stability. This LDO employs the
same technology used in the anyCAP® line of regulators from
Analog Devices, Inc., making it insensitive to the type of
capacitor used. Driving an external load from the BYPASS pin
is not supported.
Note that the reference input signal must be present and the
VCO divider must not be static during VCO calibration.
PLL External Loop Filter
When using the internal VCO, the external loop filter should
be referenced to the BYPASS pin for optimal noise and spurious
performance. An example of an external loop filter for a PLL
that uses the internal VCO is shown in Figure 47. The thirdorder design shown in Figure 47 usually offers best performance.
A loop filter must be calculated for each desired PLL configuration.
The values of the components depend upon the VCO frequency,
the K
, the PFD frequency, the CP current, the desired loop
VCO
bandwidth, and the desired phase margin. The loop filter affects
the phase noise, loop settling time, and loop stability. A basic
knowledge of PLL theory is helpful for understanding loop filter
design. ADIsimCLK can help with the calculation of a loop
filter according to the application requirements.
Rev. | Page 34 of 80
When using an external VCO, the external loop filter should be
referenced to ground. See Figure 48 for an example of an external
loop filter for a PLL using an external VCO.
AD9517-4
VCO
31pF
CHARGE
PUMP
Figure 47. Example of External Loop Filter for a PLL Using the Internal VCO
LF
CP
BYPASS
C
BP
C1C2C3
= 220nF
R2
R1
06428-065
AD9517-4
CLK/CLK
CP
CHARGE
PUMP
Figure 48. Example of External Loop Filter for a PLL Using an External VCO
EXTERNAL
VCO/VCXO
R2
R1
C1C2C3
06428-265
PLL Reference Inputs
The AD9517 features a flexible PLL reference input circuit that
allows either a fully differential input or two separate single-ended
inputs. The input frequency range for the reference inputs is
specified in Tabl e 2. Both the differential and the single-ended
inputs are self-biased, allowing for easy ac coupling of input signals.
The differential input and the single-ended inputs share the two
pins, REFIN and
REFIN
(REF1 and REF2, respectively). The
desired reference input type is selected and controlled by
Register 0x01C (see and ). Tabl e 52Tabl e 54
When the differential reference input is selected, the self-bias
level of the two sides is offset slightly (~100 mV, see Ta b le 2 ) to
prevent chattering of the input buffer when the reference is slow
or missing. This increases the voltage swing that is required of the
driver and overcomes the offset. The differential reference input
can be driven by either ac-coupled LVDS or ac-coupled LVPECL
signals.
The single-ended inputs can be driven by either a dc-coupled
CMOS level signal or an ac-coupled sine-wave or square wave.
Each single-ended input can be independently powered down
when not needed to increase isolation and reduce power. Either
a differential or a single-ended reference must be specifically
enabled. All PLL reference inputs are off by default.
The differential reference input is powered down whenever the
PLL is powered down, or when the differential reference input
is not selected. The single-ended buffers power down when the
PLL is powered down, and when their individual power down
registers are set. When the differential mode is selected, the
single-ended inputs are powered down.
Page 35
AD9517-4
V
D
In differential mode, the reference input pins are internally selfbiased so that they can be ac-coupled via capacitors. It is possible to
dc couple to these inputs. If the differential REFIN is driven by
a single-ended signal, the unused side (
REFIN
) should be
decoupled via a suitable capacitor to a quiet ground. Figure 49
shows the equivalent circuit of REFIN.
S
85kΩ
REF1
V
S
REFIN
REFIN
REF2
10kΩ 12kΩ
150Ω
150Ω
10kΩ 10kΩ
V
S
85kΩ
Figure 49. REFIN Equivalent Circuit
06428-066
Reference Switchover
The AD9517 supports dual single-ended CMOS inputs, as well
as a single differential reference input. In the dual single-ended
reference mode, the AD9517 supports automatic and manual
PLL reference clock switching between REF1 (on Pin REFIN)
and REF2 (on Pin
REFIN
). This feature supports networking
and other applications that require smooth switching of redundant
references. When used in conjunction with the automatic
holdover function, the AD9517 can achieve a worst-case
reference input switchover with an output frequency disturbance as
low as 10 ppm.
When using reference switchover, the single-ended reference
inputs should be dc-coupled CMOS levels and never be allowed
to go to high impedance. If these inputs are allowed to go to high
impedance, noise may cause the buffer to chatter, causing a
false detection of the presence of a reference.
Reference switchover can be performed manually or automatically. Manual switchover is performed either through
Register 0x01C or by using the REF_SEL pin. Manual switchover
requires the presence of a clock on the reference input that is
being switched to, or that the deglitching feature be disabled
(Register 0x01C[7]). The reference switching logic fails if this
condition is not met, and the PLL does not reacquire.
Automatic revertive switchover relies on the REFMON pin to
indicate when REF1 disappears. By programming Register 0x01B =
0xF7 and Register 0x01C = 0x26, the REFMON pin is programmed
to be high when REF1 is invalid, which commands the switch to
REF2. When REF1 is valid again, the REFMON pin goes low, and
the part again locks to REF1. It is also possible to use the STATUS
pin for this function, and REF2 can be used as the preferred
reference.
A switchover deglitch feature ensures that the PLL does not
receive rising edges that are far out of alignment with the newly
selected reference.
Automatic nonrevertive switching is not supported.
Reference Divider R
The reference inputs are routed to the reference divider, R.
R (a 14-bit counter) can be set to any value from 0 to 16383
by writing to Register 0x011 and Register 0x012. (Both R = 0 and
R = 1 give divide-by-1.) The output of the R divider goes to one
of the PFD inputs to be compared to the VCO frequency
divided by the N divider. The frequency applied to the PFD
must not exceed the maximum allowable frequency, which
depends on the antibacklash pulse setting (see Table 2).
The R counter has its own reset. R counter can be reset using
the shared reset bit of the R, A, and B counters. It can also be
reset by a
SYNC
operation.
VCXO/VCO Feedback Divider N—P, A, B, R
The N divider is a combination of a prescaler (P) and two
counters, A and B. The total divider value is
N = (P × B) + A
where the value of P can be 2, 4, 8, 16, or 32.
Prescaler
The prescaler of the AD9517 allows for two modes of operation:
a fixed divide (FD) mode of 1, 2, or 3, and dual modulus (DM)
mode where the prescaler divides by P and (P + 1) {2 and 3,
4 and 5, 8 and 9, 16 and 17, or 32 and 33}. The prescaler modes
of operation are given in Table 54, Register 0x016[2:0]. Not all
modes are available at all frequencies (see Table 2).
When operating the AD9517 in dual modulus mode (P//P + 1),
the equation used to relate input reference frequency to VCO
output frequency is
f
= (f
VCO
/R) × (P × B + A) = f
REF
× N/R
REF
However, when operating the prescaler in an FD mode of 1,
2, or 3, the A counter is not used (A = 0) and the equation
simplifies to
f
= (f
VCO
/R) × (P × B) = f
REF
× N/R
REF
When A = 0, the divide is a fixed divide of P = 2, 4, 8, 16, or 32,
in which case the previous equation also applies.
Rev. | Page 35 of 80
Page 36
AD9517-4
D
By using combinations of the DM and FD modes, the AD9517
can achieve values of N all the way down to N = 1 and up to N =
26,2175. Tabl e 28 shows how a 10 MHz reference input can be
locked to any integer multiple of N.
Note that the same value of N can be derived in different ways,
as illustrated by the case of N = 12. The user can choose a fixed
divide mode of P = 2 with B = 6; use the dual modulus mode of
2/3 with A = 0, B = 6; or use the dual modulus mode of 4/5 with
A = 0, B = 3.
The maximum frequency into the prescaler in 2/3 dual-modulus
mode is limited to 200 MHz. There are only two cases where
this frequency limitation limits the flexibility of that N divider:
N = 7 and N = 11. In these two cases, the maximum frequency
into the prescaler is 300 MHz and is achieved by using the P = 1
FD mode. In all other cases, the user can achieve the desired N
divider value by using the other prescaler modes.
A and B Counters
The B counter must be ≥3 or bypassed, and, unlike the R counter,
A = 0 is actually zero.
When the prescaler is in dual-modulus mode, the A counter
must be less than the B counter.
The maximum input frequency to the A/B counter is reflected
in the maximum prescaler output frequency (~300 MHz) that is
specified in Ta b l e 2. This is the prescaler input frequency (VCO or
CLK) divided by P. For example, a dual modulus mode of P = 8/9
is not allowed if the VCO frequency is greater than 2400 MHz
because the frequency going to the A/B counter is too high.
When the AD9517 B counter is bypassed (B = 1), the A counter
should be set to 0, and the overall resulting divide is equal to the
prescaler setting, P. The possible divide ratios in this mode are
1, 2, 3, 4, 8, 16, and 32. This mode is useful only when an
external VCO/VCXO is used because the frequency range of the
internal VCO requires an overall feedback divider greater than 32.
Although manual reset is not normally required, the A/B counters
have their own reset bit. Alternatively, the A and B counters can be
reset using the shared reset bit of the R, A, and B counters. Note
that these reset bits are not self-clearing.
R, A, and B Counters—
SYNC
Pin Reset
The R, A, and B counters can also be reset simultaneously through
SYNC
the
(see ). The Tabl e 54
pin. This function is controlled by Register 0x019[7:6]
SYNC
pin reset is disabled by default.
R and N Divider Delays
Both the R and N dividers feature a programmable delay cell.
These delays can be enabled to allow adjustment of the phase
relationship between the PLL reference clock and the VCO or
CLK. Each delay is controlled by three bits. The total delay
range is about 1 ns. See Register 0x019 in Tabl e 54 .
Table 28. Using a 10 MHz Reference Input to Generate Different VCO Frequencies
f
REF
(MHz) R P A B N
10 1 1 X 1 1 10 FD P = 1, B = 1 (A and B counters are bypassed).
10 1 2 X 1 2 20 FD P = 2, B = 1 (A and B counters are bypassed).
10 1 1 X 3 3 30 FD A counter is bypassed.
10 1 1 X 4 4 40 FD A counter is bypassed.
10 1 1 X 5 5 50 FD A counter is bypassed.
10 1 2 X 3 6 60 FD A counter is bypassed.
10 1 2 0 3 6 60 DM
10 1 2 1 3 7 70 DM
10 10 32 22 84 2710 2710 DM P = 32, A = 22, B = 84.
f
VCO
(MHz) Mode Comments/Conditions
Maximum frequency into prescaler in P = 2/3 mode is 200 MHz.
If N = 7 or N = 11 is desired for prescaler input frequency of 200 MHz
to 300 MHz, use P = 1, and N = 7 or 11, respectively.
P = 32 is not allowed (A > B not allowed).
P = 16 is also permitted.
Rev. | Page 36 of 80
Page 37
AD9517-4
V
V
CLKC
D
DIGITAL LOCK DETECT (DLD)
By selecting the proper output through the mux on each pin,
the DLD function can be made available at the LD, STATUS,
and REFMON pins. The DLD circuit indicates a lock when the
time difference of the rising edges at the PFD inputs is less than
a specified value (the lock threshold). The loss of a lock is
indicated when the time difference exceeds a specified value
(the unlock threshold). Note that the unlock threshold is wider
than the lock threshold, which allows some phase error in
excess of the lock window to occur without chattering on the
lock indicator.
The lock detect window timing depends on three settings:
the digital lock detect window bit (Register 0x018[4]), the
antibacklash pulse width setting (Register 0x017[1:0], see Tab le 2 ),
and the lock detect counter (Register 0x018[6:5]). A lock is not
indicated until there is a programmable number of consecutive
PFD cycles with a time difference that is less than the lock detect
threshold. The lock detect circuit continues to indicate a lock
until a time difference greater than the unlock threshold occurs
on a single subsequent cycle. For the lock detect to work properly,
the period of the PFD frequency must be greater than the unlock
threshold. The number of consecutive PFD cycles required for
lock is programmable (Register 0x018[6:5]).
Analog Lock Detect (ALD)
The AD9517 provides an ALD function that can be selected for
use at the LD pin. There are two versions of ALD, as follows:
•N-channel open-drain lock detect. This signal requires a
pull-up resistor to the positive supply, VS. The output is
normally high with short, low-going pulses. Lock is indicated
by the minimum duty cycle of the low-going pulses.
•P-channel open-drain lock detect. This signal requires a
pull-down resistor to GND. The output is normally low
with short, high-going pulses. Lock is indicated by the
minimum duty cycle of the high-going pulses.
The analog lock detect function requires an R-C filter to
provide a logic level indicating lock/unlock.
= 3.3
S
AD9517-4
LD
ALD
Figure 50. Example of Analog Lock Detect Filter
Using N-Channel Open-Drain Driver
Current Source Digital Lock Detect (DLD)
During the PLL locking sequence, it is normal for the DLD
signal to toggle a number of times before remaining steady
when the PLL is completely locked and stable. There may be
applications where it is desirable to have DLD asserted only
after the PLL is solidly locked. This is made possible by using
the current source lock detect function. This function is set
R2
V
R1
OUT
C
06428-067
when it is selected as the output from the LD pin control
(Register 0x01A[5:0]).
The current source lock detect provides a current of 110 μA
when DLD is true, and it shorts to ground when DLD is false.
If a capacitor is connected to the LD pin, it charges at a rate that
is determined by the current source during the DLD true time
but is discharged nearly instantly when DLD is false. By monitoring
the voltage at the LD pin (top of the capacitor), it is possible to
get a logic high level only after the DLD has been true for a
sufficiently long time. Any momentary DLD false resets the
charging. By selecting a properly sized capacitor, it is possible to
delay a lock detect indication until the PLL is stably locked and
the lock detect does not chatter.
The voltage on the capacitor can be sensed by an external
comparator connected to the LD pin. However, there is an
internal LD pin comparator that can be read at the REFMON
pin control (Register 0x01B[4:0]) or the STATUS pin control
(Register 0x017[7:2]) as an active high signal. It is also available
as an active low signal (REFMON, Register 0x01B[4:0] and
STATUS, Register 0x017[7:2]). The internal LD pin comparator
trip point and hysteresis are listed in Tab le 1 6.
AD9517-4
110µA
C
V
OUT
CLK
06428-068
)
DLD
LD PIN
COMPARAT OR
Figure 51. Current Source Lock Detect
LD
REFMON
OR
STATUS
External VCXO/VCO Clock Input (CLK/
CLK is a differential input that can be used as an input to drive
the AD9517 clock distribution section. This input can receive
up to 2.4 GHz. The pins are internally self-biased, and the input
signal should be ac-coupled via capacitors.
CLOCK INPUT
STAGE
06428-032
The CLK/
V
S
LK
2.5kΩ2.5kΩ
5kΩ
5kΩ
Figure 52. CLK Equivalent Input Circuit
CLK
input can be used either as a distribution-only
input (with the PLL off ), or as a feedback input for an external
VCO/VCXO using the internal PLL when the internal VCO is
not used. The CLK/
CLK
input can be used for frequencies up
to 2.4 GHz.
Rev. | Page 37 of 80
Page 38
AD9517-4
D
Holdover
The AD9517 PLL has a holdover function. Holdover is
implemented by putting the charge pump into a state of high
impedance. This is useful when the PLL reference clock is lost.
Holdover mode allows the VCO to maintain a relatively
constant frequency even though there is no reference clock.
Without this function, the charge pump is placed into a
constant pump-up or pump-down state, resulting in a massive
VCO frequency shift. Because the charge pump is placed in a
high impedance state, any leakage that occurs at the charge
pump output or the VCO tuning node causes a drift of the VCO
frequency. This can be mitigated by using a loop filter that
contains a large capacitive component because this drift is
limited by the current leakage induced slew rate (I
/C) of the
LEAK
VCO control voltage. For most applications, the frequency
accuracy is sufficient for 3 sec to 5 sec.
Both a manual holdover, using the
SYNC
pin, and an automatic
holdover mode are provided. To use either function, the
holdover function must be enabled (Register 0x01D[0] and
Register 0x01D[2]).
Note that the VCO cannot be calibrated with the holdover
enabled because the holdover resets the N divider during
calibration, which prevents proper calibration. Disable holdover
before issuing a VCO calibration.
Manual Holdover Mode
A manual holdover mode can be enabled that allows the user to
place the charge pump into a high impedance state when the
SYNC
pin is asserted low. This operation is edge sensitive, not
level sensitive. The charge pump enters a high impedance state
immediately. To take the charge pump out of a high impedance
state, take the
SYNC
pin high. The charge pump then leaves
high impedance state synchronously with the next PFD rising
edge from the reference clock. This prevents extraneous charge
pump events from occurring during the time between
SYNC
going high and the next PFD event. This also means that the
charge pump stays in a high impedance state as long as there is
no reference clock present.
The B-counter (in the N divider) is reset synchronously with
the charge pump leaving the high impedance state on the
reference path PFD event. This helps align the edges out of the
R and N dividers for faster settling of the PLL. Because the
prescaler is not reset, this feature works best when the B and R
numbers are close because this results in a smaller phase
difference for the loop to settle out.
When using this mode, set the channel dividers to ignore the
SYNC
pin (at least after an initial
are not set to ignore the
off each time
SYNC
is taken low to put the part into holdover.
SYNC
SYNC
event). If the dividers
pin, the distribution outputs turn
Rev. | Page 38 of 80
Automatic/Internal Holdover Mode
When enabled, this function automatically puts the charge pump
into a high impedance state when the loop loses lock. The
assumption is that the only reason the loop loses lock is due to
the PLL losing the reference clock; therefore, the holdover function
puts the charge pump into a high impedance state to maintain
the VCO frequency as close as possible to the original frequency
before the reference clock disappears. See Figure 53 for a flowchart
of the automatic/internal holdover function operation.
PLL ENABLED
LOOP OUT OF LOCK. DIGITAL LOCK
NO
DETECT SIG NAL GOES LOW WHE N THE
LOOP LE AVES LOCK AS DETERMINED
DLD == LOW
YES
WAS
LD PIN == HIG H
WHEN DLD WENT
LOW?
YES
HIGH IMPEDANCE
CHARGE PUMP
YES
REFERENCE
EDGE AT PFD?
YES
RELEASE
CHARGE PUMP
HIGH IMPEDANCE
YES
DLD == HIGH
Figure 53. Flowchart of Automatic/Internal Holdover Mode
BY THE PHASE DIF FERENCE AT T HE
INPUT OF THE PFD.
NO
ANALOG LO CK DETECT PI N INDICATES
LOCK WAS PREVIOUSLY ACHIEVED.
(0x1D[3] = 1: USE LD PIN VOLTAGE
WITH HOLDOVER.
0x1D[3] = 0: IG NORE LD PIN VOLTAG E,
TREAT L D PIN AS ALWAYS HIG H.)
CHARGE PUMP IS MADE
HIGH IMPEDANCE.
PLL COUNTERS CONTINUE
OPERATING NORMALLY.
NO
CHARGE PUMP REMAINS HIGH
IMPEDANCE UNTIL THE REFERE NCE
HAS RETURNED.
YES
TAKE CHARGE PUMP O UT OF
HIGH IMPEDANCE. PLL CAN
NOW RESETTLE.
NO
WAIT FO R DLD TO GO HIGH. T HIS TAKES
5 TO 255 CYCLES (PROGRAMMING OF
THE DLD DELAY CO UNTER) WITH THE
REFERENCE AND FEEDBACK CLOCKS
INSIDE THE L OCK WINDOW AT THE PF D.
THIS ENSURES THAT THE HOLDOVER
FUNCTION W AITS FO R THE PLL T O SETT LE
AND LOCK BEFORE T HE HOLDOVER
FUNCTION CAN BE RET RIGGERE D.
The holdover function senses the logic level of the LD pin as a
condition to enter holdover. The signal at LD can be from the
DLD, ALD, or current source LD mode. It is possible to disable
the LD comparator (Register 0x01D[3]), which causes the holdover
function to always sense LD as high.
06428-069
Page 39
AD9517-4
D
If DLD is used, it is possible for the DLD signal to chatter some
while the PLL is reacquiring lock. The holdover function may
retrigger, thereby preventing the holdover mode from ever
terminating. Use of the current source lock detect mode is
recommended to avoid this situation (see the Current Source
Digital Lock Detect section).
Once in holdover mode, the charge pump stays in a high
impedance state as long as there is no reference clock present.
As in the external holdover mode, the B counter (in the N
divider) is reset synchronously with the charge pump leaving
the high impedance state on the reference path PFD event. This
helps align the edges out of the R and N dividers for faster
settling of the PLL and to reduce frequency errors during
settling. Because the prescaler is not reset, this feature works
best when the B and R numbers are close because this results in
a smaller phase difference for the loop to settle out.
After leaving holdover, the loop then reacquires lock and the
LD pin must charge (if Register 0x01D[3] = 1) before it can
re-enter holdover (CP high impedance).
The holdover function always responds to the state of the
currently selected reference (Register 0x01C). If the loop loses
lock during a reference switchover (see the Reference Switchover
section), holdover is triggered briefly until the next reference
clock edge at the PFD.
The following registers affect the internal/automatic holdover
function:
•Register 0x018[6:5], lock detect counter. These bits change
the number of consecutive PFD cycles with edges inside the
lock detect window that are required for the DLD indicator
to indicate lock. This impacts the time required before the
LD pin can begin to charge as well as the delay from the end
of a holdover event until the holdover function can be
reengaged.
•Register 0x018[3], disable digital lock detect. This bit must
be set to 0b to enable the DLD circuit. Internal/automatic
holdover does not operate correctly without the DLD function
enabled.
•Register 0x01A[5:0], lock detect pin output select. Set these
bits to 000100b for the current source lock detect mode if
using the LD pin comparator. Load the LD pin with a
capacitor of an appropriate value.
• Register 0x01D[2]=1b; enable the holdover function.
• Register 0x01D[1] = 0b; use internal/automatic holdover
mode.
•Register 0x01D[0] = 1b; enable the holdover function.
(VCO calibration must be complete before this bit is enabled.)
•Connect REFMON pin to REFSEL pin.
Frequency Status Monitors
The AD9517 contains three frequency status monitors that are
used to indicate if the PLL reference (or references in the case of
single-ended mode) and the VCO have fallen below a threshold
frequency. A diagram showing their location in the PLL is shown
in Figure 54. The VCO status frequency monitor is also capable
of monitoring the CLK input if the CLK input is selected as the
input to the N divider.
The PLL reference frequency monitors have two threshold
frequencies: normal and extended (see Tabl e 16 . ). The reference
frequency monitor thresholds are selected in Register 0x01A.
The frequency monitor status can be found in Register 0x01F,
Bits[3:1].
Rev. | Page 39 of 80
Page 40
AD9517-4
V
D
REF1
REF2
REFIN (REF1)
REFIN (REF2)
BYPASS
REGULATOR (LDO)
LF
CLK
CLK
REF_SELCPRSETVCP
REFERENCE
SWITCHOVER
STATUS
STATUS
LOW DROPO UT
VCO
SGNDRSET
DISTRIBUTION
REFERENCE
R
DIVIDER
N DIVIDER
P, P + 1
PRESCALER
DIVIDE BY
2, 3, 4, 5, O R 6
01
A/B
COUNTERS
Figure 54. Reference and VCO Status Monitors
VCO Calibration
The AD9517 on-chip VCO must be calibrated to ensure proper
operation over process and temperature. VCO calibration centers
the dc voltage at the internal VCO input (at the LF pin) for the
selected configuration; this is normally required only during initial
configuration and any time the PLL settings change. VCO calibration is controlled by a calibration controller driven by the R divider
output. The calibration requires that the input reference clock be
present at the REFIN pins, and that the PLL be set up properly to
lock the PLL loop. During the first initialization after a power-up
or a reset of the AD9517, a VCO calibration sequence is initiated
by setting Register 0x018[0] = 1b. This can be done during initial
setup, before executing an update registers (Register 0x232[0] =
1b). Subsequent to initial setup, a VCO calibration sequence is
initiated by resetting Register 0x018[0] = 0b, executing an update
registers operation, setting Register 0x018[0] = 1b, and executing
another update registers operation. A readback bit, Bit 6 in
Register 0x1F, indicates when a VCO calibration is finished
by returning a logic true (that is, 1b).
The sequence of operations for the VCO calibration is as follows:
1. Program the PLL registers to the proper values for the PLL
loop. Note that that automatic holdover mode must be
disabled, and the VCO divider must not be set to “Static.”
2. Ensure that the input reference signal is present.
3. For the initial setting of the registers after a power-up or reset,
initiate VCO calibration by setting Register 0x018[0] = 1b.
Subsequently, whenever a calibration is desired, set
Register 0x018[0] = 0b, update registers; and then set
Register 0x018[0] = 1b, update registers.
4. A sync operation is initiated internally, causing the outputs
to go to a static state determined by normal sync function
operation.
5. The VCO calibrates to the desired setting for the requested
VCO frequency.
6. Internally, the
SYNC
signal is released, allowing outputs to
continue clocking.
Rev. | Page 40 of 80
PROGRAMMABLE
PROGRAMMABLE
VCO STATUS
0
1
REFMON
LD
CP
STATUS
06428-070
R DELAY
N DELAY
LOCK
DETECT
PHASE
FREQUENCY
DETECTOR
PLL
REFERENCE
CHARGE
HOLD
PUMP
7. The PLL loop is closed.
8. The PLL locks.
A sync is executed during the VCO calibration; therefore, the
outputs of the AD9517 are held static during the calibration,
which prevents unwanted frequencies from being produced.
However, at the end of a VCO calibration, the outputs may
resume clocking before the PLL loop is completely settled.
The VCO calibration clock divider is set as shown in Table 54
(Register 0x018[2:1]).
The calibration divider divides the PFD frequency (reference
frequency divided by R) down to the calibration clock. The
calibration occurs at the PFD frequency divided by the
calibration divider setting. Lower VCO calibration clock
frequencies result in longer times for a calibration to be
completed.
The VCO calibration clock frequency is given by
f
CAL_CLOCK
= f
REFIN
/(R × cal_div)
where:
f
is the frequency of the REFIN signal.
REFIN
R is the value of the R divider.
cal_div is the division set for the VCO calibration divider
(Register 0x018[2:1]).
The VCO calibration takes 4400 calibration clock cycles.
Therefore, the VCO calibration time in PLL reference clock
cycles is given by
Time to Calibrate VCO =
4400 × R × cal_div PLL Reference Clock Cycles
Table 29. Example Time to Complete a VCO Calibration
with Different f
f
(MHz) R Divider PFD Time to Calibrate VCO
REFIN
Frequencies
REFIN
100 1 100 MHz 88 μs
10 10 1 MHz 8.8 ms
10 100 100 kHz 88 ms
Page 41
AD9517-4
D
VCO calibration must be manually initiated. This allows for
flexibility in deciding what order to program registers and when
to initiate a calibration, instead of having it happen every time
certain PLL registers have their values change. For example, this
allows for the VCO frequency to be changed by small amounts
without having an automatic calibration occur each time; this
should be done with caution and only when the user knows that
the VCO control voltage is not going to exceed the nominal best
performance limits. For example, a few 100 kHz steps are fine, but
a few MHz might not be. In addition, because the calibration
procedure results in rapid changes in the VCO frequency, the
distribution section is automatically placed in SYNC until the
calibration is finished. Therefore, this temporary loss of outputs
must be expected.
A VCO calibration should be initiated under the following
conditions:
•After changing any of the PLL R, P, B, and A divider
settings, or after a change in the PLL reference clock
frequency. This, in effect, means any time a PLL register
or reference clock is changed such that a different VCO
frequency results.
•Whenever system calibration is desired. The VCO is
designed to operate properly over extremes of temperatures
even when it is first calibrated at the opposite extreme.
However, a VCO calibration can be initiated at any time,
if desired.
CLOCK DISTRIBUTION
A clock channel consists of a pair (or double pair, in the case of
CMOS) of outputs that share a common divider. A clock output
consists of the drivers that connect to the output pins. The clock
outputs have either LVPECL or LVDS/CMOS signal levels at
the pins.
The AD9517 has four clock channels: two channels are LVPECL
(four outputs); two channels are LVDS/CMOS (up to four LVDS
outputs or up to eight CMOS outputs).
Each channel has its own programmable divider that divides
the clock frequency that is applied to its input. The LVPECL
channel dividers can divide by any integer from 2 to 32, or the
divider can be bypassed to achieve a divide by one. Each
LVDS/CMOS channel divider contains two of these divider
blocks in a cascaded configuration. The total division of the
channel is the product of the divide value of the cascaded dividers.
This allows divide values of (1 to 32) × (1 to 32), or up to 1024
(note that this is not all values from 1 to 1024 but only the set
of numbers that are the product of the two dividers).
If the user wishes to use the channel dividers, the VCO divider
must be used after the on-chip VCO. This is because the internal
VCO frequency is above the maximum channel divider input
frequency (1600 MHz). The VCO divider can be set to divide
by 2, 3, 4, 5, or 6. External clock signals connected to the CLK
input also require the VCO divider if the frequency of the signal
is greater than 1600 MHz.
Rev. | Page 41 of 80
The channel dividers allow for a selection of various duty cycles,
depending on the currently set division. That is, for any specific
division, D, the output of the divider can be set to high for
N + 1 input clock cycles and low for M + 1 input clock cycles
(where D = N + M + 2). For example, a divide-by-5 can be high
for one divider input cycle and low for four cycles, or a divideby-5 can be high for three divider input cycles and low for two
cycles. Other combinations are also possible.
The channel dividers include a duty-cycle correction function
that can be disabled. In contrast to the selectable duty cycle
just described, this function can correct a non-50% duty cycle
caused by an odd division. However, this requires that the
division be set by M = N + 1.
In addition, the channel dividers allow a coarse phase offset or
delay to be set. Depending on the division selected, the output
can be delayed by up to 31 input clock cycles. The divider
outputs can also be set to start high or start low.
Internal VCO or External CLK as Clock Source
The clock distribution of the AD9517 has two clock input
sources: an internal VCO or an external clock connected to the
CLK
CLK/
chosen as the source of the clock signal to distribute. When the
internal VCO is selected as the source, the VCO divider must be
used. When CLK is selected as the source, it is not necessary to
use the VCO divider if the CLK frequency is less than the
maximum channel divider input frequency (1600 MHz);
otherwise, the VCO divider must be used to reduce the
frequency to one acceptable by the channel dividers.
shows how the VCO, CLK, and VCO divider are selected.
Register 0x1E1[1:0] selects the channel divider source and
determines whether the VCO divider is used. It is not possible
to select the VCO without using the VCO divider.
Table 30. Selecting VCO or CLK as Source for Channel
Divider, and Whether VCO Divider Is Used
Register 0x1E1
Bit 1 Bit 0
0 0 CLK Used
0 1 CLK Not used
1 0 VCO Used
1 1 Not allowed Not allowed
pins. Either the internal VCO or CLK must be
Tabl e 30
Channel Divider Source VCO Divider
CLK or VCO Direct to LVPECL Outputs
It is possible to connect either the internal VCO or the CLK
(whichever is selected as the input to the VCO divider) directly
to the LVPECL outputs, OUT0 to OUT3. This configuration
can pass frequencies up to the maximum frequency of the VCO
directly to the LVPECL outputs. The LVPECL outputs may not
be able to provide a full voltage swing at the highest frequencies.
Page 42
AD9517-4
D
To connect the LVPECL outputs directly to the internal VCO or
CLK, the VCO divider must be selected as the source to the
distribution section, even if no channel uses it.
Either the internal VCO or the CLK can be selected as the
source for the direct-to-output routing.
Table 31. Settings for Routing VCO Divider Input Directly
to LVPECL Outputs
Register Setting Selection
0x1E1[1:0] = 00b CLK is the source; VCO divider selected
0x1E1[1:0] = 10b VCO is the source; VCO divider selected
0x192[1] = 1b Direct to OUT0 and OUT1 outputs
0x198[1] = 1b Direct to OUT2 and OUT3 outputs
Clock Frequency Division
The total frequency division is a combination of the VCO
divider (when used) and the channel divider. When the VCO
divider is used, the total division from the VCO or CLK to the
output is the product of the VCO divider (2, 3, 4, 5, and 6) and
the division of the channel divider. Tabl e 32 and Ta b le 3 3
indicate how the frequency division for a channel is set. For the
LVPECL outputs, there is only one divider per channel. For the
LVDS/ CMOS outputs, there are two dividers (X.1, X.2)
cascaded per channel.
Table 32. Frequency Division for Divider 0 and Divider 1
CLK
or VCO
Selected
CLK/VCO 2 to 6 1 (bypassed) Yes 1
CLK/VCO 2 to 6 1 (bypassed) No (2 to 6) × (1)
CLK/VCO 2 to 6 2 to 32 No
CLK Not used 1 (bypassed) No 1
CLK Not used 2 to 32 No 2 to 32
VCO
Divider
Channel
Divider
Direct to
Output
Frequency
Division
(2 to 6) ×
(2 to 32)
Table 33. Frequency Division for Divider 2 and Divider 3
CLK
or VCO
Selected
CLK/VCO 2 to 6
CLK/VCO 2 to 6 2 to 32
CLK/VCO 2 to 6 2 to 32 2 to 32
CLK Not used 1 1 1
CLK Not used 2 to 32 1 (2 to 32) × (1)
CLK Not used 2 to 32 2 to 32
VCO
Divider
Channel Divider
X.1 X.2
1
(bypassed) 1 (bypassed)
1
(bypassed)
Frequency
Division
(2 to 6) ×
(1) × (1)
(2 to 6) ×
(2 to 32) × (1)
(2 to 6) ×
(2 to 32) ×
(2to 32)
2 to 32 ×
(2 to 32)
The channel dividers feeding the LVPECL output drivers
contain one 2-to-32 frequency divider. This divider provides for
division by 2 to 32. Division by 1 is accomplished by bypassing
the divider. The dividers also provide for a programmable duty
cycle, with optional duty-cycle correction when the divide ratio
is odd. A phase offset or delay in increments of the input clock
cycle is selectable. The channel dividers operate with a signal at
their inputs up to 1600 MHz. The features and settings of the
dividers are selected by programming the appropriate setup
and control registers (see Tab l e 5 2 through Table 62 ).
VCO Divider
The VCO divider provides frequency division between the
internal VCO or the external CLK input and the clock
distribution channel dividers. The VCO divider can be set
to divide by 2, 3, 4, 5, or 6 (see Tab le 6 0 , Register 0x1E0[2:0]).
Channel Dividers—LVPECL Outputs
Each pair of LVPECL outputs is driven by a channel divider.
There are two channel dividers (0, 1) driving four LVPECL
outputs (OUT0 to OUT3). Tabl e 34 gives the register locations
used for setting the division and other functions of these
dividers. The division is set by the values of M and N. The
divider can be bypassed (equivalent to divide-by-1, divider circuit
is powered down) by setting the bypass bit. The duty-cycle
correction can be enabled or disabled according to the setting of
the DCCOFF bits.
Note that the value stored in the register = # of cycles minus 1.
for Divider 0 and Divider 11
X
N Bypass DCCOFF
Channel Frequency Division (0, 1)
For each channel (where the channel number is x: 0, 1), the
frequency division, D
, is set by the values of M and N
X
(four bits each, representing Decimal 0 to Decimal 15), where
Number of Low Cycles = M + 1
Number of High Cycles = N + 1
The cycles are cycles of the clock signal currently routed to the
input of the channel dividers (VCO divider out or CLK).
When a divider is bypassed, D
Otherwise, D
= (N + 1) + (M + 1) = N + M + 2. This allows
X
= 1.
X
each channel divider to divide by any integer from 2 to 32.
Rev. | Page 42 of 80
Page 43
AD9517-4
D
Duty Cycle and Duty-Cycle Correction (0, 1)
The duty cycle of the clock signal at the output of a channel is a
result of some or all of the following conditions:
• What are the M and N values for the channel?
• Is the DCC enabled?
• Is the VCO divider used?
• What is the CLK input duty cycle? (The internal VCO has
a 50% duty cycle.)
The DCC function is enabled by default for each channel divider.
However, the DCC function can be disabled individually for
each channel divider by setting the DCCOFF bit for that channel.
Certain M and N values for a channel divider result in a non-50%
duty cycle. A non-50% duty cycle can also result with an even
division, if M ≠ N. The duty-cycle correction function
automatically corrects non-50% duty cycles at the channel
divider output to 50% duty cycle. Duty-cycle correction
requires the following channel divider conditions:
• An even division must be set as M = N.
• An odd division must be set as M = N + 1.
When not bypassed or corrected by the DCC function, the duty
cycle of each channel divider output is the numerical value of
(N + 1)/(N + M + 2), expressed as a percentage (%).
The duty cycle at the output of the channel divider for various
configurations is shown in Tabl e 35 to Tab le 3 7.
Table 35. Duty Cycle with VCO Divider; Input Duty Cycle Is 50%
VCO
Divider
Even
Odd = 3
Odd = 5
Even, Odd Even
Even, Odd Odd
DX Output Duty Cycle
N + M + 2 DCCOFF = 1 DCCOFF = 0
1 (divider
bypassed)
1 (divider
bypassed)
1 (divider
bypassed)
50% 50%
33.3% 50%
40% 50%
(N + 1)/
(N + M + 2)
(N + 1)/
(N + M + 2)
50%; requires M = N
50%; requires M = N + 1
Table 36. Duty Cycle with VCO Divider; Input Duty Cycle Is X%
VCO
Divider
Even
Odd = 3
Odd = 5
Even Even
Odd
Odd = 3 Even
Odd = 3 Odd
Odd = 5 Even
Odd = 5 Odd
DX Output Duty Cycle
N + M + 2 DCCOFF = 1 DCCOFF = 0
1 (divider
bypassed)
1 (divider
bypassed)
1 (divider
bypassed)
50% 50%
33.3% (1 + X%)/3
40% (2 + X%)/5
(N + 1)/
(N + M + 2)
(N + 1)/
(N + M + 2)
(N + 1)/
(N + M + 2)
(N + 1)/
(N + M + 2)
(N + 1)/
(N + M + 2)
(N + 1)/
(N + M + 2)
50%,
requires M = N
50%,
requires M = N + 1
50%,
requires M = N
(3N + 4 + X%)/(6N + 9),
requires M = N + 1
50%,
requires M = N
(5N + 7 + X%)/(10N +
15), requires M = N + 1
Table 37. Channel Divider Output Duty Cycle When the
VCO Divider Is Not Used
Input
Clock
Duty
Cycle N + M + 2 DCCOFF = 1 DCCOFF = 0
Any 1
Any Even
50% Odd
X% Odd
DX Output Duty Cycle
1 (divider
bypassed)
(N + 1)/
(M + N + 2)
(N + 1)/
(M + N + 2)
(N + 1)/
(M + N + 2)
Same as input
duty cycle
50%, requires M = N
50%, requires
M = N + 1
(N + 1 + X%)/(2 × N + 3),
requires M = N + 1
The internal VCO has a duty cycle of 50%. Therefore, when the
VCO is connected directly to the output, the duty cycle is 50%.
If the CLK input is routed directly to the output, the duty cycle of
the output is the same as the CLK input.
Rev. | Page 43 of 80
Page 44
AD9517-4
D
Phase Offset or Coarse Time Delay (0, 1)
Each channel divider allows for a phase offset, or a coarse time
delay, to be programmed by setting register bits (see Ta b le 3 8).
These settings determine the number of cycles (successive
rising edges) of the channel divider input frequency by which to
offset, or delay, the rising edge of the output of the divider. This
delay is with respect to a nondelayed output (that is, with a
phase offset of zero). The amount of the delay is set by five bits
loaded into the phase offset (PO) register plus the start high (SH)
bit for each channel divider. When the start high bit is set, the
delay is also affected by the number of low cycles (M) that are
programmed for the divider.
The sync function must be used to make phase offsets effective
(see the Synchronizing the Outputs—Sync Function section).
Table 38. Setting Phase Offset and Division for Divider 0 and
Divider 1
The channel divide-by is set as N = high cycles and M = low cycles.
Case 1
For Φ ≤ 15:
Δt = Φ × T
Δc = Δt/T
X
= Φ
X
Case 2
For Φ ≥ 16:
Δt = (Φ − 16 + M + 1) × T
X
Δc = Δt/TX
By giving each divider a different phase offset, output-to-output
delays can be set in increments of the channel divider input
clock cycle. Figure 55 shows the results of setting such a coarse
offset between outputs.
CHANNEL
DIVIDER INPUT
DIVIDER 0
DIVIDER 1
DIVIDER 2
0123456789101112131415
SH = 0
PO = 0
SH = 0
PO = 1
SH = 0
PO = 2
Tx
E
L
I
D
N
N
A
H
C
I
D
V
1 × Tx
2 × Tx
P
T
U
S
T
U
E
R
O
V
I
D
=
5
0
%
,
T
U
D
Y
=
4
Figure 55. Effect of Coarse Phase Offset (or Delay)
06428-071
Rev. | Page 44 of 80
Channel Dividers—LVDS/CMOS Outputs
Channel Divider 2 and Channel Divider 3 each drive a pair of
LVDS outputs, giving a total of four LVDS outputs (OUT4 to
OUT7). Alternatively, each of these LVDS differential outputs
can be configured individually as a pair (A and B) of CMOS
single-ended outputs, providing for up to eight CMOS outputs.
By default, the B output of each pair is off but can be turned on
as desired.
Channel Divider 2 and Channel Divider 3 each consist of two
cascaded, 2 to 32, frequency dividers. The channel frequency
division is D
X.1
× D
or up to 1024. Divide-by-1 is achieved by
X.2
bypassing one or both of these dividers. Both of the dividers
also have DCC enabled by default, but this function can be
disabled, if desired, by setting the DCCOFF bit of the channel.
A coarse phase offset or delay is also programmable (see the
Phase Offset or Coarse Time Delay (Divider 2 and Divider 3)
section). The channel dividers operate up to 1600 MHz. The
features and settings of the dividers are selected by programming
the appropriate setup and control registers (see Tabl e 5 2 and
Tabl e 53 through Ta b le 6 2).
Note that the value stored in the register = # of cycles minus 1.
Channel Frequency Division (Divider 2 and Divider 3)
The division for each channel divider is set by the bits in the
registers for the individual dividers (X.Y = 2.1, 2.2, 3.1, and 3.2)
Number of Low Cycles = M
Number of High Cycles = N
When both X.1 and X.2 are bypassed, D
When only X.2 is bypassed, D
When both X.1 and X.2 are not bypassed, D
(N
+ M
X.2
+ 2).
X.2
X.Y
= (N
X
X.Y
+ 1
+ 1
X.1
= 1 × 1 = 1.
X
+ M
+ 2) × 1.
X.1
= (N
X
X.1
+ M
+ 2) ×
X.1
By cascading the dividers, channel division up to 1024 can be
obtained. However, not all integer value divisions from 1 to
1024 are obtainable; only the values that are the product of the
separate divisions of the two dividers (D
X.1
× D
X.2
) can be realized.
If only one divider is needed when using Divider 2 and Divider 3,
use the first one (X.1) and bypass the second one (X.2). Do not
bypass X.1 and use X.2.
Page 45
AD9517-4
D
Duty Cycle and Duty-Cycle Correction (Divider 2 and
Divider 3)
The same duty cycle and DCC considerations apply to Divider 2
and Divider 3 as to Divider 0 and Divider 1 (see the Duty Cycle
and Duty-Cycle Correction (0, 1) section); however, with these
channel dividers, the number of possible configurations is even
more complex.
Duty-cycle correction on Divider 2 and Divider 3 requires the
following channel divider conditions:
•An even D
must be set as M
X.Y
X.Y
= N
(low cycles = high
X.Y
cycles).
•An odd D
must be set as M
X.Y
X.Y
= N
+ 1 (the number of
X.Y
low cycles must be one greater than the number of high
cycles).
•If only one divider is bypassed, it must be the second
divider, X.2.
•If only one divider has an even divide-by, it must be the
second divider, X.2.
The possibilities for the duty cycle of the output clock from
Divider 2 and Divider 3 are shown in Tabl e 40 through
Tabl e 44 .
Table 40. Divider 2 and Divider 3 Duty Cycle; VCO Divider
Used; Duty Cycle Correction Off (DCCOFF = 1)
VCO
Divider
D
X.1
N
+ M
+ 2 N
X.1
X.1
X.2
+ M
X.2
X.2
+ 2
Output
Duty Cycle
D
Even 1 1 50%
Odd = 3 1 1 33.3%
Odd = 5 1 1 40%
Even Even, odd 1
Odd Even, odd 1
Even Even, odd Even, odd
Odd Even, odd Even, odd
(N
(N
(N
(N
(N
(N
(N
(N
X.1
X.1
X.1
X.1
X.2
X.2
X.2
X.2
+ 1)/
+ M
+ 1)/
+ M
+ 1)/
+ M
+ 1)/
+ M
X.1
X.1
X.2
X.2
+ 2)
+ 2)
+ 2)
+ 2)
Table 41. Divider 2 and Divider 3 Duty Cycle; VCO Divider
Not Used; Duty Cycle Correction Off (DCCOFF = 1)
Input Clock
Duty Cycle
D
X.1
N
+ M
X.1
+ 2 N
X.1
X.2
+ M
X.2
X.2
+ 2
Output
Duty Cycle
D
50% 1 1 50%
X% 1 1 X%
50% Even, odd 1
X% Even, odd 1
50% Even, odd Even, odd
X% Even, odd Even, odd
(N
(N
(N
(N
(N
(N
(N
(N
X.1
X.1
X.1
X.1
X.2
X.2
X.2
X.2
+ 1)/
+ M
+ 1)/
+ M
+ 1)/
+ M
+ 1)/
+ M
X.1
X.1
X.2
X.2
+ 2)
+ 2)
+ 2)
+ 2)
Table 42. Divider 2 and Divider 3 Duty Cycle; VCO Divider
Used; Duty Cycle Correction Is On (DCCOFF = 0); VCO
Divider Input Duty Cycle = 50%
VCO
Divider
D
X.1
N
+ M
X.1
+ 2 N
X.1
X.2
+ M
X.2
X.2
+ 2
Output
Duty Cycle
D
Even 1 1 50%
Odd 1 1 50%
Even Even (N
Odd Even (N
Even Odd (M
Odd Odd (M
Even Even (N
Odd Even (N
Even Odd (M
Odd Odd (M
Even Odd (M
Odd Odd (M
Table 44. Divider 2 and Divider 3 Duty Cycle; VCO Divider
Not Used; Duty Cycle Correction On (DCCOFF = 0)
Input
Clock
D
D
X.1
X.2
Duty
Cycle N
X.1
+ M
+ 2 N
X.1
X.2
+ M
X.2
Output Duty Cycle
+ 2
50% 1 1 50%
50%
Even
(N
X.1
= M
X.1
1 50%
)
X% 1 1 X% (High)
X%
50%
X%
50%
X%
50%
X%
50%
X%
Even
(N
X.1
Odd
(M
X.1
Odd
(M
X.1
Even
(N
X.1
Even
(N
X.1
Odd
(M
X.1
Odd
(M
X.1
Odd
(M
X.1
Odd
(M
X.1
= M
= N
= N
= M
= M
= N
= N
= N
= N
X.1
X.1
X.1
X.1
X.1
X.1
X.1
X.1
X.1
1 50%
)
1 50%
+ 1)
+ 1)
)
)
+ 1)
+ 1)
+ 1)
+ 1)
1
Even
(N
X.2
Even
(N
X.2
Even
(N
X.2
Even
(N
X.2
Odd
(M
X.2
Odd
(M
X.2
= M
= M
= M
= M
= N
= N
X.2
X.2
X.2
X.2
X.2
X.2
)
)
)
)
+ 1)
+ 1)
(N
X.1
(2N
50%
50%
50%
50%
50%
(2N
3N
X.2
((2N
+ 1 + X%)/
+ 3)
X.1
+ 3N
X.1NX.2
+ 4 + X%)/
+ 3)(2N
X.1
X.2
+
X.1
+ 3))
Phase Offset or Coarse Time Delay (Divider 2 and Divider 3)
Divider 2 and Divider 3 can be set to have a phase offset or
delay. The phase offset is set by a combination of the bits in the
phase offset and start high registers (see Tab l e 4 5 ).
Table 45. Setting Phase Offset and Division for Divider 2 and
Divider 3
Fine Delay (ns) =
Delay Range × Delay Fraction × (1/63) + Offset
Note that only delay fraction values up to 47 decimal (101111b;
0x2F) are supported.
In no case can the fine delay exceed one-half of the output clock
period. If a delay longer than half of the clock period is attempted,
the output stops clocking.
The delay function adds some jitter that is greater than that
specified for the nondelayed output. This means that the delay
function should be used primarily for clocking digital chips,
such as FPGA, ASIC, DUC, and DDC. An output with this
delay enabled may not be suitable for clocking data converters.
The jitter is higher for long full scales because the delay block
uses a ramp and trip points to create the variable delay. A slower
ramp time produces more time jitter.
Synchronizing the Outputs—Sync Function
The AD9517 clock outputs can be synchronized to each other.
Outputs can be individually excluded from synchronization.
Synchronization consists of setting the nonexcluded outputs to
a preset set of static conditions and subsequently releasing these
outputs to continue clocking at the same instant with the preset
conditions applied. This allows for the alignment of the edges of
two or more outputs or for the spacing of edges according to the
coarse phase offset settings for two or more outputs.
⎞
⎟
×
⎟
⎠
Synchronization of the outputs is executed in several ways,
as follows:
By forcing the
•
SYNC
pin low and then releasing it (manual
sync).
•
By setting and then resetting any one of the following three
bits: the soft sync bit (Register 0x230[0]), the soft reset bit
(Register 0x000[2] [mirrored]), and the power-down
distribution reference bit (Register 0x230[1]).
By executing synchronization of the outputs as part of the
•
chip power-up sequence.
By forcing the
•
6
reset).
By forcing the
•
RESET
pin low and then releasing it (chip
PD
pin low and then releasing it (chip power-
down).
Following completion of a VCO calibration. An internal
•
SYNC signal is automatically asserted at the beginning of
a VCO calibration and then released upon its completion.
The most common way to execute the sync function is to use
SYNC
the
This requires a low-going signal on the
pin to do a manual synchronization of the outputs.
SYNC
pin, which is held
low and then released when synchronization is desired. The
timing of the sync operation is shown in (using VCO
divider) and (VCO divider not used). There is an
Figure 58
Figure 57
uncertainty of up to one cycle of the clock at the input to the
channel divider due to the asynchronous nature of the SYNC
signal with respect to the clock edges inside the AD9517. The
SYNC
delay from the
rising edge to the beginning of synchronized
output clocking is between 14 and 15 cycles of clock at the
channel divider input, plus either one cycle of the VCO divider
input (see ), or one cycle of the channel divider input
(see ), depending on whether the VCO divider is used.
Figure 57
Figure 58
Cycles are counted from the rising edge of the signal.
Another common way to execute the sync function is by setting
and resetting the soft sync bit at Register 0x230[0] (see Tabl e 5 3
through Ta ble 62 for details). Both the setting and resetting
of the soft sync bit require an update all registers operation
(Register 0x232[0] = 1) to take effect.
Rev. | Page 47 of 80
Page 48
AD9517-4
S
R
R
R
D
CHANNEL DIVIDE
OUTPUT CLOCKING
INPUT TO VCO DIVIDER
INPUT TO CHANNEL DIVIDER
YNC PIN
OUTPUT OF
CHANNEL DIVIDER
CHANNEL DIVIDER
OUTPUT CLOCKING
INPUT TO CLK
CHANNEL DIVIDER O UTPUT STAT IC
123 456 78910
14 TO 15 CYCLES AT CHANNEL DIVIDER INPUT + 1 CYCLE AT VCO DIVIDER INPUT
Figure 57. SYNC Timing When VCO Divider Is Used—CLK or VCO Is Input
CHANNEL DIVIDER O UTPUT STATIC
CHANNEL DIVIDE
OUTPUT CLOCKING
1
11
1314
12
06428-073
CHANNEL DIVIDE
OUTPUT CLOCKING
1
IINPUT TO CHANNEL DIVI DER
SYNC PIN
OUTPUT OF
CHANNEL DIVIDER
12345678910
14 TO 15 CYCLES AT CHANNEL DIVIDER INPUT + 1 CYCLE AT CLK I NPUT
Figure 58. SYNC Timing When VCO Divider Is Not Used—CLK Input Only
A sync operation brings all outputs that have not been excluded
(by the nosync bit) to a preset condition before allowing the outputs
to begin clocking in synchronicity. The preset condition takes
into account the settings in each of the channel’s start high bit
and its phase offset. These settings govern both the static state
of each output when the sync operation is happening and the
state and relative phase of the outputs when they begin clocking
again upon completion of the sync operation. Between outputs
and after synchronization, this allows for the setting of phase
offsets.
The AD9517 outputs are in pairs, sharing a channel divider per
pair (two pairs of pairs, four outputs, in the case of CMOS). The
synchronization conditions apply to both outputs of a pair.
11
1314
12
Each channel (a divider and its outputs) can be excluded from
any sync operation by setting the nosync bit of the channel.
Channels that are set to ignore SYNC (excluded channels) do
not set their outputs static during a sync operation, and their
outputs are not synchronized with those of the nonexcluded
channels.
Clock Outputs
The AD9517 offers three different output level choices:
LVPECL, LVDS, and CMOS. OUT0 to OUT3 are LVPECL
differential outputs; and OUT4 to OUT7 are LVDS/CMOS
outputs. These outputs can be configured as either LVDS
differential or as pairs of single-ended CMOS outputs.
6428-074
Rev. | Page 48 of 80
Page 49
AD9517-4
V
3
A
3
A
V
D
LVPECL Outputs—OUT0 to OUT3
The LVPECL differential voltage (VOD) is selectable from ~400 mV
to ~960 mV (see Register 0x0F0[3:2] to Register 0x0F5[3:2]).
The LVPECL outputs have dedicated pins for power supply
(VS_LVPECL), allowing a separate power supply to be used.
V
can be from 2.5 V to 3.3 V.
S_LVPECL
The LVPECL output polarity can be set as noninverting or
inverting, which allows for the adjustment of the relative
polarity of outputs within an application without requiring a
board layout change. Each LVPECL output can be powered
down or powered up as needed. Because of the architecture of
the LVPECL output stages, there is the possibility of electrical
overstress and breakdown under certain power-down conditions.
For this reason, the LVPECL outputs have several power-down
modes. This includes a safe power-down mode that continues
to protect the output devices while powered down, although it
consumes somewhat more power than a total power-down. If
the LVPECL output pins are terminated, it is best to select the
safe power-down mode. If the pins are left floating (i.e., not
connected), total power-down mode is fine.
3.3
Figure 60. LVDS Output Simplified Equivalent Circuit with
Each LVDS/CMOS output can be powered-down as needed to
save power. The CMOS output power-down is controlled by the
same bit that controls the LVDS power-down for that output.
This power-down control affects both CMOS Output A and
CMOS Output B. However, when CMOS Output A is powered
up, CMOS Output B can be powered on or off separately.
OUT4 to OUT7 can be configured as either an LVDS
differential output or as a pair of CMOS single-ended outputs.
The LVDS outputs allow for selectable output current from
~1.75 mA to ~7 mA.
The LVDS output polarity can be set as noninverting or
inverting, which allows for the adjustment of the relative
polarity of outputs within an application without requiring a
board layout change. Each LVDS output can be powered down
if not needed to save power.
OUT4 to OUT7 can also be CMOS outputs. Each LVDS output
can be configured to be two CMOS outputs. This provides for
up to eight CMOS outputs: OUT4A, OUT4B, OUT5A, OUT5B,
OUT6A, OUT6B, OUT7A, and OUT7B. When an output is
configured as CMOS, CMOS Output A is automatically turned on.
CMOS Output B can be turned on or off independently. The
relative polarity of the CMOS outputs can also be selected for
any combination of inverting and noninverting (see Ta b le 5 7,
Register 0x140[7:5], Register 0x141[7:5], Register 0x142[7:5],
and Register 0x143[7:5]).
Rev. | Page 49 of 80
06428-035
Figure 61. CMOS Equivalent Output Circuit
RESET MODES
The AD9517 has several ways to force the chip into a reset
condition that restores all registers to their default values and
makes these settings active.
Power-On Reset—Start-Up Conditions When VS Is Applied
A power-on reset (POR) is issued when the VS power supply is
turned on. This initializes the chip to the power-on conditions
that are determined by the default register settings. These are
indicated in the Default Value (Hex) column of Tab le 5 2. At
power-on, the AD9517 also executes a sync operation, which
brings the outputs into phase alignment according to the default
settings.
Asynchronous Reset via the
An asynchronous hard reset is executed by momentarily pulling
RESET
low. A reset restores the chip registers to the default settings.
Soft Reset via Register 0x00[2]
A soft reset is executed by writing Register 0x000[2] and
Register 0x000[5] = 1b. This bit is not self-clearing; it must be
cleared by writing Register 0x000[2] and Register 0x000[5] = 0b to
reset it and complete the soft reset operation. A soft reset restores
the default values to the internal registers. The soft reset bit does
not require an update registers command (Register 0x232) to be
issued.
RESET
Pin
Page 50
AD9517-4
D
POWER-DOWN MODES
Chip Power-Down via PD
The AD9517 can be put into a power-down condition by
pulling the
functions and currents inside the AD9517. The chip remains in
this power-down state until
When the AD9517 wakes up, it returns to the settings programmed
into its registers prior to the power-down, unless the registers
are changed by new programming while the
The
the bias current that is necessary to maintain the LVPECL outputs
in a safe shutdown mode. This is needed to protect the LVPECL
output circuitry from damage that could be caused by certain
termination and load configurations when tristated. Because
this is not a complete power-down, it can be called sleep mode.
When the AD9517 is in a
following state:
•
The PLL is off (asynchronous power-down).
•
The VCO is off.
•
The CLK input buffer is off.
•
All dividers are off.
•
All LVDS/CMOS outputs are off.
•
All LVPECL outputs are in safe off mode.
•
The serial control port is active, and the chip responds to
If the AD9517 clock outputs must be synchronized to each
other, a SYNC is required upon exiting power-down (see the
Synchronizing the Outputs—Sync Function section). A VCO
calibration is not required when exiting power-down.
PLL Power-Down
The PLL section of the AD9517 can be selectively powered down.
There are three PLL operating modes set by Register 0x010[1:0],
as shown in Tab l e 5 4 .
PD
pin low. Power-down turns off most of the
PD
is brought back to logic high.
PD
pin is held low.
PD
power-down shuts down the currents on the chip, except
PD
power-down, the chip is in the
commands.
In asynchronous power-down mode, the device powers down as
soon as the registers are updated.
In synchronous power-down mode, the PLL power-down is
gated by the charge pump to prevent unwanted frequency
jumps. The device goes into power-down on the occurrence of
the next charge pump event after the registers are updated.
Distribution Power-Down
The distribution section can be powered down by writing
Register 0x230[1] = 1b. This turns off the bias to the distribution
section. If the LVPECL power-down mode is normal operation
(00b), it is possible for a low impedance load on that LVPECL
output to draw significant current during this power-down. If
the LVPECL power-down mode is set to 11b, the LVPECL
output is not protected from reverse bias and may be damaged
under certain termination conditions.
Individual Clock Output Power-Down
Any of the clock distribution outputs can be powered down
individually by writing to the appropriate registers. The register
map details the individual power-down settings for each output
(see Tabl e 52 ). The LVDS/CMOS outputs can be powered
down, regardless of their output load configuration.
The LVPECL outputs have multiple power-down modes
(see Tabl e 56 ), which give some flexibility in dealing with the
various output termination conditions. When the mode is set to
10b, the LVPECL output is protected from reverse bias to
2 VBE + 1 V. If the mode is set to 11b, the LVPECL output is
not protected from reverse bias and can be damaged under
certain termination conditions. This setting also affects the
operation when the distribution block is powered down with
Register 0x230[1] = 1b (see the Distribution Power-Down
section).
Individual Circuit Block Power-Down
Other AD9517 circuit blocks (such as CLK, REF1, and REF2)
can be powered down individually. This gives flexibility in
configuring the part for power savings whenever certain chip
functions are not needed.
Rev. | Page 50 of 80
Page 51
AD9517-4
D
SERIAL CONTROL PORT
The AD9517 serial control port is a flexible, synchronous, serial
communications port that allows an easy interface with many
industry-standard microcontrollers and microprocessors. The
AD9517 serial control port is compatible with most synchronous
transfer formats, including both the Motorola SPI® and Intel®
SSR® protocols. The serial control port allows read/write access
to all registers that configure the AD9517. Single or multiple
byte transfers are supported, as well as MSB first or LSB first
transfer formats. The AD9517 serial control port can be
configured for a single bidirectional I/O pin (SDIO only)
or for two unidirectional I/O pins (SDIO/SDO). By default,
the AD9517 is in bidirectional mode, long instruction (long
instruction is the only instruction mode supported).
SERIAL CONTROL PORT PIN DESCRIPTIONS
SCLK (serial clock) is the serial shift clock. This pin is an input.
SCLK is used to synchronize serial control port reads and
writes. Write data bits are registered on the rising edge of this
clock, and read data bits are registered on the falling edge. This
pin is internally pulled down by a 30 kΩ resistor to ground.
SDIO (serial data input/output) is a dual-purpose pin that acts
as either an input only (unidirectional mode) or as both an
input/output (bidirectional mode). The AD9517 defaults to the
bidirectional I/O mode (Register 0x000[0] = 0b).
(serial data out) is used only in the unidirectional I/O mode
SDO
(Register 0x000[0] = 1b) as a separate output pin for reading
back data.
CS
(chip select bar) is an active low control that gates the read
and write cycles. When
CS
is high, SDO and SDIO are in a high
impedance state. This pin is internally pulled up by a 30 kΩ
resistor to VS.
13
SCLK
SDO
SDIO
Figure 62. Serial Control Port
CS
AD9517-4
14
SERIAL
15
CONTRO L
16
PORT
06428-036
GENERAL OPERATION OF SERIAL CONTROL PORT
A write or a read operation to the AD9517 is initiated by pulling
CS
low.
CS
stalled high is supported in modes where three or fewer bytes
of data (plus instruction data) are transferred (see ).
In these modes,
CS
can temporarily return high on any byte
boundary, allowing time for the system controller to process the
next byte.
CS
can go high on byte boundaries only and can go
high during either part (instruction or data) of the transfer.
Table 4 7
Rev. | Page 51 of 80
During this period, the serial control port state machine enters
a wait state until all data is sent. If the system controller decides
to abort the transfer before all of the data is sent, the state machine
must be reset, either by completing the remaining transfers or
CS
by returning
less than eight SCLK cycles). Raising
low for at least one complete SCLK cycle (but
CS
on a nonbyte boundary
terminates the serial transfer and flushes the buffer.
In the streaming mode (see Tab l e 4 7 ), any number of data bytes
can be transferred in a continuous stream. The register address
is automatically incremented or decremented (see the MSB/LSB
First Transfers section).
CS
must be raised at the end of the last
byte to be transferred, thereby ending the stream mode.
Communication Cycle—Instruction Plus Data
There are two parts to a communication cycle with the AD9517.
The first part writes a 16-bit instruction word into the AD9517,
coincident with the first 16 SCLK rising edges. The instruction
word provides the AD9517 serial control port with information
regarding the data transfer, which is the second part of the
communication cycle. The instruction word defines whether
the upcoming data transfer is a read or a write, the number of
bytes in the data transfer, and the starting register address for
the first byte of the data transfer.
Write
If the instruction word is for a write operation, the second part
is the transfer of data into the serial control port buffer of the
AD9517. Data bits are registered on the rising edge of SCLK.
The length of the transfer (1, 2, 3 bytes or streaming mode) is
indicated by two bits ([W1:W0]) in the instruction byte. When
the transfer is 1, 2, or 3 bytes, but not streaming,
CS
can be raised
after each sequence of eight bits to stall the bus (except after the
last byte, where it ends the cycle). When the bus is stalled, the serial
CS
transfer resumes when
is lowered. Raising CS on a nonbyte
boundary resets the serial control port. During a write, streaming
mode does not skip over reserved or blank registers; therefore,
the user must know the bit pattern to write to the reserved
registers to preserve proper operation of the part. Refer to the
control register map (see ) to determine if the default
Tabl e 52
value for reserved registers is nonzero. It does not matter what
data is written to blank registers.
Because data is written into a serial control port buffer area, and
not directly into the actual control registers of the AD9517, an
additional operation is needed to transfer the serial control port
buffer contents to the actual control registers of the AD9517,
thereby causing them to become active. The update registers
operation consists of setting Register 0x232[0] = 1b (this bit is
self-clearing). Any number of bytes of data can be changed before
an update registers operation is executed. The update registers
operation simultaneously actuates all register changes that have
been written to the buffer since any previous update.
Page 52
AD9517-4
D
Read
If the instruction word is for a read operation, the next N × 8
SCLK cycles clock out the data from the address specified in the
instruction word, where N is 1 to 3 as determined by [W1:W0].
If N = 4, the read operation is in streaming mode, continuing
until
is raised. Streaming mode does not skip over reserved
CS
or blank registers. The readback data is valid on the falling
edge of SCLK.
The default mode of the AD9517 serial control port is the
bidirectional mode. In bidirectional mode, both the sent data
and the readback data appear on the SDIO pin. It is also possible to
set the AD9517 to unidirectional mode via the SDO active bit,
Register 0x000[0] = 1b. In unidirectional mode, the readback
data appears on the SDO pin.
A readback request reads the data that is in the serial control
port buffer area, or the data that is in the active registers (see
Figure 63). Readback of the buffer or active registers is controlled
by Register 0x004[0].
The AD9517 supports only the long instruction mode; therefore,
Register 0x000[4:3] must be set to 11b. (This register uses mirrored
bits.) Long instruction mode is the default at power-up or reset.
The AD9517 uses Register Address 0x000 to Register
Address 0x232.
SCLK
SDIO
SDO
CS
SERIAL
CONTROL
PORT
WRITE RE GISTE R 0x232 = 0x01
TO UDATE REG ISTERS
Figure 63. Relationship Between Serial Control Port Buffer Registers and
Active Registers of the AD9517
UPDATE
REGISTERS
BUFFER REGIS TERS
ACTIVE REGISTERS
06428-037
THE INSTRUCTION WORD (16 BITS)
The MSB of the instruction word is R/W, which indicates
whether the instruction is a read or a write. The next two bits,
[W1:W0], indicate the length of the transfer in bytes. The final
13 bits are the address ([A12:A0]) at which to begin the read or
write operation.
For a write, the instruction word is followed by the number of
bytes of data indicated by Bits[W1:W0] (see Ta b l e 4 7 ).
Table 47. Byte Transfer Count
W1 W0 Bytes to Transfer
0 0 1
0 1 2
1 0 3
1 1 Streaming mode
Rev. | Page 52 of 80
The 13 bits found in [A12:A0] select the address within the
register map that is written to or read from during the data
transfer portion of the communications cycle. Only Bits[A9:A0]
are needed to cover the range of the 0x232 registers used by the
AD9517. Bits[A12:A10] must always be set to 0b. For multibyte
transfers, this address is the starting byte address. In MSB first
mode, subsequent bytes decrement the address.
MSB/LSB FIRST TRANSFERS
The AD9517 instruction word and byte data can be MSB first
or LSB first. Any data written to Register 0x000 must be mirrored;
the upper four bits (Bits[7:4]) with the lower four bits (Bits[3:0).
This makes it irrelevant whether LSB first or MSB first is in
effect. As an example of this mirroring, see the default setting
for this register: 0x18, which mirrors Bit 4 and Bit 3. This sets
the long instruction mode (which is the default and the only
mode that is supported).
The default for the AD9517 is MSB first.
When LSB first is set by Register 0x000[1] and Register 0x000[6],
it takes effect immediately because it affects only the operation
of the serial control port and does not require that an update be
executed.
When MSB first mode is active, the instruction and data bytes
must be written from MSB to LSB. Multibyte data transfers in
MSB first format start with an instruction byte that includes the
register address of the most significant data byte. Subsequent
data bytes must follow in order from the high address to the low
address. In MSB first mode, the serial control port internal
address generator decrements for each data byte of the
multibyte transfer cycle.
When LSB first is active, the instruction and data bytes must be
written from LSB to MSB. Multibyte data transfers in LSB first
format start with an instruction byte that includes the register
address of the least significant data byte followed by multiple
data bytes. The internal byte address generator of the serial
control port increments for each byte of the multibyte
transfer cycle.
The AD9517 serial control port register address decrements
from the register address just written toward 0x000 for multibyte
I/O operations if the MSB first mode is active (default). If the LSB
first mode is active, the register address of the serial control port
increments from the address just written toward Address 0x232
for multibyte I/O operations.
Streaming mode always terminates when it hits Address 0x232.
Note that unused addresses are not skipped during multibyte
I/O operations.
Table 48. Streaming Mode (No Addresses Are Skipped)
Write Mode Address Direction Stop Sequence
LSB first Increment 0x230, 0x231, 0x232, stop
MSB first Decrement 0x001, 0x000, 0x232, stop
Page 53
AD9517-4
K
D
Table 49. Serial Control Port, 16-Bit Instruction Word, MSB First
Use the following equation to determine the junction
temperature of the AD9517 on the application PCB:
= T
J
+ (ΨJT × PD)
CASE
T
where:
T
is the junction temperature (°C).
J
is the case temperature (°C) measured by the user at the
T
CASE
top center of the package.
Ψ
is the value from Table 51.
JT
PD is the power dissipation of the device (see Table 17).
Val u es o f θ
design considerations. θ
approximation of T
where T
Val u es o f θ
design considerations when an external heat sink is required.
Val u es o f Ψ
design considerations.
are provided for package comparison and PCB
JA
can be used for a first-order
JA
by the following equation
J
= TA + (θJA × PD)
T
J
is the ambient temperature (°C).
A
are provided for package comparison and PCB
JC
are provided for package comparison and PCB
JB
11.9
11.8
11.6
Rev. | Page 55 of 80
Page 56
AD9517-4
D
CONTROL REGISTERS
CONTROL REGISTER MAP OVERVIEW
Table 52. Control Register Map Overview
Reg.
Addr.
(Hex)
Serial Port Configuration
0x000 Serial port
0x001 Blank
0x002 Reserved
0x003 Part ID Part ID (read only) 0xD3
0x004 Readback
PLL
0x010 PFD and
0x011 R counter 14-bit R divider, Bits[7:0] (LSB) 0x01
0x012 Blank 14-bit R divider, Bits[13:8] (MSB) 0x00
0x013 A counter Blank 6-bit A counter 0x00
0x014 B counter 13-bit B counter, Bits[7:0] (LSB) 0x03
0x015 Blank 13-bit B counter, Bits[12:8] (MSB) 0x00
0x016 PLL Control 1 Set CP pin
0x017 PLL Control 2 STATUS pin control Antibacklash pulse width 0x00
0x018 PLL Control 3 Reserved Lock detect counter Digital lock
0x019 PLL Control 4
0x01A PLL Control 5 Reserved Reference
0x01B PLL Control 6 VCO
0x01C PLL Control 7 Disable
0x01D PLL Control 8 Reserved PLL status
0x01E PLL Control 9 Reserved 0x00
0x01F PLL readback Reserved VCO cal
0x020
to
0x04F
Parameter Bit 7 (MSB) Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 (LSB)
configuration
control
charge pump
SDO
active
PFD
polarity
to V
CP
R, A, B counters
frequency
monitor
switchover
deglitch
LSB first Soft reset Long
Charge pump current Charge pump mode PLL power-down 0x7D
/2
pin reset
Reset R
counter
SYNC
frequency
monitor
threshold
REF2
REFIN
(
frequency
monitor
Select
REF2
finished
)
Reset A and
B counters
REF1 (REFIN)
frequency
monitor
Use
REF_SEL pin
Holdover
active
instruction
Blank Read back
Reset all
counters
detect
window
R path delay N path delay 0x00
register
disable
REF2
selected
Long
instruction
B counter
bypass
Disable
digital lock
detect
LD pin control 0x00
Reserved REF2
LD pin
comparator
enable
VCO
frequency >
threshold
Blank
Soft reset LSB first SDO active 0x18
active
registers
Prescaler P 0x06
VCO calibration divider VCO cal now 0x06
REFMON pin control 0x00
power-on
Holdover
enable
REF2
frequency >
threshold
REF1
power-on
External
holdover
control
REF1
frequency >
threshold
Differential
reference
Holdover
enable
Digital
lock detect
Default
Value
(Hex)
0x00
0x00
0x00
N/A
Rev. | Page 56 of 80
Page 57
AD9517-4
D
Reg.
Addr.
(Hex)
Fine Delay Adjust—OUT4 to OUT7
0x0A0 OUT4 delay
0x0A1 OUT4 delay
0x0A2 OUT4 delay
0x0A3 OUT5 delay
0x0A4 OUT5 delay
0x0A5 OUT5 delay
0x0A6 OUT6 delay
0x0A7 OUT6 delay
0x0A8 OUT6 delay
0x0A9 OUT7 delay
0x0AA OUT7 delay
0x0AB OUT7 delay
0x0AC
to
0x0EF
LVPECL Outputs
0x0F0 OUT0 Blank OUT0
0x0F1 OUT1 Blank OUT1
0x0F2,
0x0F3
0x0F4 OUT2 Blank OUT2
0x0F5 OUT3 Blank OUT3
0x0F6
to
0x13F
LVDS/CMOS Outputs
0x140 OUT4 OUT4 CMOS
0x141 OUT5 OUT5 CMOS
0x142 OUT6 OUT6 CMOS
0x143 OUT7 OUT7 CMOS
0x144
to
0x18F
Parameter Bit 7 (MSB) Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 (LSB)
Parameter Bit 7 (MSB) Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 (LSB)
(PECL)
bypass
(PECL)
bypass
(LVDS/CMOS)
(LVDS/CMOS)
and sync
registers
Divider 0 low cycles Divider 0 high cycles 0x00
Divider 0
nosync
Divider 1 low cycles Divider 1 high cycles 0x00
Divider 1
nosync
Low Cycles Divider 2.1 High Cycles Divider 2.1 0x22
Low Cycles Divider 3.1 High Cycles Divider 3.1 0x22
Divider 0
force high
Divider 1
force high
Divider 2.2
Divider 3.2
Reserved Power
Divider 0
start high
Reserved
Divider 1
start high
Bypass
Divider 2.1
Bypass
Divider 3.1
down
clock input
section
Blank Update all
Divider 2
nosync
Divider 3
nosync
Blank
Power down
VCO clock
interface
Blank
Divider 0 phase offset 0x80
Divider 0
direct to
output
Divider 1 phase offset 0x00
direct to
output
Divider 2
force high
Divider 3
force high
Power
down VCO
and CLK
down sync
Start High
Divider 2.2
Start High
Divider 3.2
Select
VCO or CLK
Power
down
distribution
reference
DCCOFF
Divider 1
DCCOFF
Start High
Divider 2.1
DCCOFF
Start High
Divider 3.1
DCCOFF
Bypass VCO
divider
Soft sync 0x00
registers (self-
clearing bit)
Default
Value
(Hex)
0x00
0x00
0x00
0x00
0x00
0x00
0x00
0x00
Rev. | Page 58 of 80
Page 59
AD9517-4
D
CONTROL REGISTER MAP DESCRIPTIONS
Tabl e 53 through Ta b le 6 2 provide a detailed description of each of the control register functions. The registers are listed by hexadecimal
address. A range of bits (for example, from Bit 5 through Bit 2) is indicated using a colon and brackets, as follows: [5:2].
Table 53. Serial Port Configuration and Part ID
Reg.
Addr
(Hex)
0x000 [7:4] Mirrored, Bits[3:0]
Bit 7 = Bit 0.
Bit 6 = Bit 1.
Bit 5 = Bit 2.
Bit 4 = Bit 3.
3 Long instruction
1 LSB first MSB or LSB data orientation.
0: data-oriented MSB first; addressing decrements (default).
1: data-oriented LSB first; addressing increments.
0 SDO active Selects unidirectional or bidirectional data transfer mode.
0: SDIO pin used for write and read; SDO set to high impedance; bidirectional mode (default).
1: SDO used for read, SDIO used for write; unidirectional mode.
0x003 [7:0] Part ID (read only) Uniquely identifies the dash version (-0 through -4) of the AD9517
AD9517-0: 0x11
AD9517-1: 0x51
AD9517-2: 0x91
AD9517-3: 0x53
AD9517-4: 0xD3
0x004 0 Read back active registers Selects register bank used for a readback.
0: reads back buffer registers (default).
1: reads back active registers.
Bits Name Description
Bits[7:4] should always mirror Bits[3:0] so that it does not matter whether the part
is in MSB or LSB first mode (see Bit 1, Register 0x000). The user should set the bits as follows:
Short/long instruction mode. This part uses long instruction mode only, so this bit should
always be set to 1b.
1: soft reset; restores default values to internal registers. Not self-clearing. Must be cleared to
0b to complete reset operation.
Rev. | Page 59 of 80
Page 60
AD9517-4
D
Table 54. PLL
Reg.
Addr.
(Hex)
0x010 7 PFD polarity Sets the PFD polarity. Negative polarity is for use (if needed) with external VCO/VCXO only. The on-chip VCO requires
0x013 [5:0] 6-bit A counter A counter (part of N divider) (default = 0x00).
0x014 [7:0] 13-bit B counter,
0x015 [4:0] 13-bit B counter,
0x016 7 Set CP pin to VCP/2 Sets the CP pin to one-half of the VCP supply voltage.
6 Reset R counter Resets R counter (R divider).
5 Reset A, B counters Resets A and B counters (part of N divider).
4 Reset all counters Resets R, A, and B counters.
0: normal (default).
1: holds the R, A, and B counters in reset.
3 B counter B counter bypass. This is valid only when operating the prescaler in FD mode.
bypass 0: normal (default).
1: B counter is set to divide-by-1. This allows the prescaler setting to determine the divide for the N divider.
Bits Name Description
positive polarity; Bit 7 = 0b.
3 2 Charge Pump Mode
0 0 High impedance state.
0 1 Force source current (pump up).
1 0 Force sink current (pump down).
1 1 Normal operation (default).
Bits[7:0] (LSB)
Bits[13:8] (MSB)
Bits[7:0] (LSB)
Bits[12:8] (MSB)
0: CP normal operation (default).
0: normal (default).
0: normal (default).
1 0 Mode
0 0 Normal operation.
0 1 Asynchronous power-down (default).
1 0 Normal operation.
1 1 Synchronous power-down.
R divider LSBs—lower eight bits (default = 0x01).
R divider MSBs—upper six bits (default = 0x00).
B counter (part of N divider)—lower eight bits (default = 0x03).
B counter (part of N divider)—upper five bits (default = 0x00).
1: CP pin set to V
1: holds the R counter in reset.
1: holds the A and B counters in reset.
/2.
CP
Rev. | Page 60 of 80
Page 61
AD9517-4
D
Reg.
Addr.
(Hex)
0x016 [2:0] Prescaler P Prescaler: DM = dual modulus and FD = fixed divide.
2 1 0 Mode Prescaler 0 0 0 FD Divide-by-1.
0 0 1 FD Divide-by-2.
0 1 0 DM Divide-by-2 (2/3 mode).
0 1 1 DM Divide-by-4 (4/5 mode).
1 0 0 DM Divide-by-8 (8/9 mode).
1 0 1 DM Divide-by-16 (16/17 mode).
1 1 0 DM Divide-by-32 (32/33 mode) (default).
1 1 1 FD Divide-by-3.
0x017 [7:2] STATUS pin Selects the signal that is connected to the STATUS pin.
control
0 0 0 0 0 0 LVL Ground (dc) (default).
0 0 0 0 0 1 DYN N divider output (after the delay).
0 0 0 0 1 0 DYN R divider output (after the delay).
0 0 0 0 1 1 DYN A divider output.
0 0 0 1 0 0 DYN Prescaler output.
0 0 0 1 0 1 DYN PFD up pulse.
0 0 0 1 1 0 DYN PFD down pulse.
0 X X X X X LVL Ground (dc); for all other cases of 0XXXXXb not specified above.
The selections that follow are the same as REFMON.
1 0 0 0 0 0 LVL Ground (dc).
1 0 0 0 0 1 DYN REF1 clock (differential reference when in differential mode).
1 0 0 0 1 0 DYN REF2 clock (not available in differential mode).
1 0 0 0 1 1 DYN Selected reference to PLL (differential reference when in differential mode).
1 0 0 1 0 0 DYN Unselected reference to PLL (not available in differential mode).
1 0 0 1 0 1 LVL Status of selected reference (status of differential reference); active
1 0 0 1 1 0 LVL Status of unselected reference (not available in differential mode);
1 0 0 1 1 1 LVL Status REF1 frequency (active high).
1 0 1 0 0 0 LVL Status REF2 frequency (active high).
1 0 1 0 0 1 LVL (Status REF1 frequency) AND (status REF2 frequency).
1 0 1 0 1 0 LVL (DLD) AND (status of selected reference) AND (status of VCO).
1 0 1 0 1 1 LVL Status of VCO frequency (active high).
1 0 1 1 0 0 LVL Selected reference (low = REF1, high = REF2).
1 0 1 1 0 1 LVL Digital lock detect (DLD); active high.
1 0 1 1 1 0 LVL Holdover active (active high).
1 0 1 1 1 1 LVL LD pin comparator output (active high).
1 1 0 0 0 0 LVL VS (PLL supply).
1 1 0 0 0 1 DYN REF1 clock
1 1 0 0 1 0 DYN REF2 clock
1 1 0 0 1 1 DYN Selected reference to PLL
1 1 0 1 0 0 DYN Unselected reference to PLL
1 1 0 1 0 1 LVL Status of selected reference (status of differential reference); active low.
1 1 0 1 1 0 LVL Status of unselected reference (not available in differential mode); active low.
1 1 0 1 1 1 LVL Status of REF1 frequency (active low).
1 1 1 0 0 0 LVL Status of REF2 frequency (active low).
1 1 1 0 0 1 LVL
(Status of REF1 frequency) AND (status of REF2 frequency).
(DLD) AND (status of selected reference) AND (status of VCO).
Rev. | Page 61 of 80
(differential reference when in differential mode).
(not available in differential mode).
(differential reference when in differential mode).
(not available when in differential mode).
Page 62
AD9517-4
D
Reg.
Addr.
(Hex)
0x017 [1:0] Antibacklash 1 0 Antibacklash Pulse Width (ns) pulse width 0 0 2.9 (default). This is the recommended setting; it does not normally need to be changed.
0 1 1.3. This setting may be necessary if the PFD frequency > 50 MHz.
1 0 6.0.
1 1 2.9.
0x018 [6:5] Lock detect
0: high range (default).
1: low range.
3 Disable digital Digital lock detect operation.
lock detect 0: normal lock detect operation (default).
1: disables lock detect.
[2:1] VCO cal divider VCO calibration divider. Divider used to generate the VCO calibration clock from the PLL reference clock.
0 0 2. This setting is fine for PFD frequencies < 12.5 MHz. The PFD frequency is f
0 1 4. This setting is fine for PFD frequencies < 25 MHz.
1 0 8. This setting is fine for PFD frequencies < 50 MHz.
1 1 16 (default). This setting is fine for any PFD frequency but also results in the longest VCO calibration time.
0 VCO cal now Bit used to initiate the VCO calibration. This bit must be toggled from 0b to 1b in the active registers. To initiate
[5:3] R path delay R path delay (default = 0x00) (see Table 2).
[2:0] N path delay N path delay (default = 0x00) (see Table 2).
Bits Name Description
counter
window
pin reset
Required consecutive number of PFD cycles with edges inside lock detect window before the DLD indicates a locked
condition.
If the time difference of the rising edges at the inputs to the PFD is less than the lock detect window time, the digital lock
detect flag is set. The flag remains set until the time difference is greater than the loss-of-lock threshold.
2 1 VCO Calibration Clock Divider
calibration, use the following three steps: first, ensure that the input reference signal is present; second, set to 0b (if
not zero already), followed by an update bit (Register 0x232, Bit 0); and third, program to 1b, followed by another update
bit (Register 0x232, Bit 0). Clearing this bit discards the VCO calibration and usually results in the PLL losing lock.
The user must ensure that the holdover enable bits in Register 0x01D = 00b during VCO calibration.
7 6 Action
0 0
Does nothing on
Does nothing on
SYNC
SYNC
(default).
.
/R.
REF
Rev. | Page 62 of 80
Page 63
AD9517-4
D
Reg.
Addr.
(Hex) Bits Name Description
0x01A 6 Reference
frequency monitor
threshold 0: frequency valid if frequency is above the higher frequency threshold (default).
1: frequency valid if frequency is above the lower frequency threshold.
[5:0] LD pin control Selects the signal that is connected to the LD pin.
0 0 0 0 0 0 LVL Digital lock detect (high = lock, low = unlock) (default).
0 0 0 0 0 1 DYN P-channel, open-drain lock detect (analog lock detect).
0 0 0 0 1 0 DYN N-channel, open-drain lock detect (analog lock detect).
0 0 0 0 1 1 HIZ High-Z LD pin.
0 0 0 1 0 0 CUR Current source lock detect (110 μA when DLD is true).
0 X X X X X LVL Ground (dc); for all other cases of 0XXXXXb not specified above.
The selections that follow are the same as REFMON.
1 0 0 0 0 0 LVL Ground (dc).
1 0 0 0 0 1 DYN REF1 clock (differential reference when in differential mode).
1 0 0 0 1 0 DYN REF2 clock (not available in differential mode).
1 0 0 0 1 1 DYN Selected reference to PLL (differential reference when indifferential mode).
1 0 0 1 0 0 DYN Unselected reference to PLL (not available in differential mode).
1 0 0 1 0 1 LVL Status of selected reference (status of differential reference); active high.
1 0 0 1 1 0 LVL Status of unselected reference (not available in differential mode);
1 0 0 1 1 1 LVL Status REF1 frequency (active high).
1 0 1 0 0 0 LVL Status REF2 frequency (active high).
1 0 1 0 0 1 LVL (Status REF1 frequency) AND (status REF2 frequency).
1 0 1 0 1 0 LVL (DLD) AND (status of selected reference) AND (status of VCO).
1 0 1 0 1 1 LVL Status of VCO frequency (active high).
1 0 1 1 0 0 LVL Selected reference (low = REF1, high = REF2).
1 0 1 1 0 1 LVL Digital lock detect (DLD); active high.
1 0 1 1 1 0 LVL Holdover active (active high).
1 0 1 1 1 1 LVL Not available. Do not use.
1 1 0 0 0 0 LVL VS (PLL supply).
1 1 0 0 0 1 DYN REF1 clock
1 1 0 0 1 0 DYN REF2 clock
1 1 0 0 1 1 DYN
1 1 0 1 0 0 DYN Unselected reference to PLL
1 1 0 1 0 1 LVL Status of selected reference (status of differential reference); active
1 1 0 1 1 0 LVL Status of unselected reference (not available in differential mode);
1 1 0 1 1 1 LVL Status of REF1 frequency (active low).
1 1 1 0 0 0 LVL Status of REF2 frequency (active low).
1 1 1 0 0 1 LVL (Status of REF1 frequency) AND (status of REF2 frequency)
1 1 1 0 1 0 LVL (DLD) AND (status of selected reference) AND (status of VCO)
1 1 1 0 1 1 LVL Status of VCO frequency (active low).
1 1 1 1 0 0 LVL Selected reference (low = REF2, high = REF1).
1 1 1 1 0 1 LVL Digital lock detect (DLD); active low.
1 1 1 1 1 0 LVL Holdover active (active low).
1 1 1 1 1 1 LVL Not available. Do not use.
Sets the reference (REF1/REF2) frequency monitor’s detection threshold frequency. This does not affect the VCO
frequency monitor’s detection threshold (see
Level or
Dynamic
5 4 3 2 1 0
Signal Signal at LD Pin
Tab le 16: REF1, REF2, and VCO frequency status monitor parameter).
active high.
(differential reference when in differential mode).
(not available in differential mode).
Selected reference to PLL
mode).
low.
active low.
(differential reference when in differential
(not available when in differential mode).
.
.
Rev. | Page 63 of 80
Page 64
AD9517-4
D
Reg.
Addr.
(Hex) Bits Name Description
0x01B 7 VCO Enables or disables VCO frequency monitor.
frequency monitor 0: disables VCO frequency monitor (default).
1: enables VCO frequency monitor.
6
frequency monitor 0: disables REF2 frequency monitor (default).
1: enables REF2 frequency monitor.
5 REF1 (REFIN)
0: disables REF1 (REFIN) frequency monitor (default).
1: enables REF1 (REFIN) frequency monitor.
[4:0] REFMON Selects the signal that is connected to the REFMON pin.
pin control
0 0 0 0 0 LVL Ground (dc) (default).
0 0 0 0 1 DYN REF1 clock (differential reference when in differential mode).
0 0 0 1 0 DYN REF2 clock (not available in differential mode).
0 0 0 1 1 DYN Selected reference to PLL (differential reference when in differential mode).
0 0 1 0 0 DYN Unselected reference to PLL (not available in differential mode).
0 0 1 0 1 LVL Status of selected reference (status of differential reference); active high.
0 0 1 1 0 LVL Status of unselected reference (not available in differential mode); active high.
0 0 1 1 1 LVL Status REF1 frequency (active high).
0 1 0 0 0 LVL Status REF2 frequency (active high).
0 1 0 0 1 LVL (Status REF1 frequency) AND (status REF2 frequency).
0 1 0 1 0 LVL (DLD) AND (status of selected reference) AND (status of VCO).
0 1 0 1 1 LVL Status of VCO frequency (active high).
0 1 1 0 0 LVL Selected reference (low = REF1, high = REF2).
0 1 1 0 1 LVL Digital lock detect (DLD); active low.
0 1 1 1 0 LVL Holdover active (active high).
0 1 1 1 1 LVL LD pin comparator output (active high).
1 0 0 0 0 LVL VS (PLL supply).
1 0 0 0 1 DYN REF1 clock
1 0 0 1 0 DYN REF2 clock
1 0 0 1 1 DYN Selected reference to PLL
1 0 1 0 0 DYN Unselected reference to PLL
1 0 1 0 1 LVL Status of selected reference (status of differential reference); active low.
1 0 1 1 0 LVL Status of unselected reference (not available in differential mode); active low.
1 0 1 1 1 LVL Status of REF1 frequency (active low).
1 1 0 0 0 LVL Status of REF2 frequency (active low).
1 1 0 0 1 LVL (Status of REF1 frequency) AND (Status of REF2 frequency)
1 1 0 1 0 LVL (DLD) AND (Status of selected reference) AND (Status of VCO)
1 1 0 1 1 LVL Status of VCO frequency (active low).
1 1 1 0 0 LVL Selected reference (low = REF2, high = REF1).
1 1 1 0 1 LVL Digital lock detect (DLD); active low.
1 1 1 1 0 LVL Holdover active (active low).
1 1 1 1 1 LVL LD pin comparator output (active low).
0x01C 7 Disable Disables or enables the switchover deglitch circuit.
switchover 0: enables switchover deglitch circuit (default).
deglitch 1: disables switchover deglitch circuit.
6 Select REF2 If Register 0x01C, Bit 5 = 0b, selects reference for PLL.
0: selects REF1 (default).
1: selects REF2.
5 Use REF_SEL pin Sets method of PLL reference selection.
0: uses Register 0x01C, Bit 6 (default).
1: uses REF_SEL pin.
[4:3] Reserved Reserved (default: 00b).
REFIN
REF2 (
frequency monitor
)
Enables or disables REF2 frequency monitor.
REF1 (REFIN) frequency monitor enable; this is for both REF1 (single-ended) and REFIN (differential) inputs
(as selected by differential reference mode).
Level or
Dynamic
4 3 2 1 0
Signal
Signal at REFMON Pin
(differential reference when in differential mode).
(not available in differential mode).
(differential reference when in differential mode).
(not available in differential mode).
.
.
Rev. | Page 64 of 80
Page 65
AD9517-4
D
Reg.
Addr.
(Hex)
0x01C 2 REF2 power-on This bit turns the REF2 power on.
0: REF2 power off (default).
1: REF2 power on.
1 REF1 power-on This bit turns the REF1 power on.
0: REF1 power off (default).
1: REF1 power on.
0 Differential
0: single-ended reference mode (default).
1: differential reference mode.
0x01D 4 PLL status Disables the PLL status register readback.
registerdisable0: PLL status register enable (default).
1: PLL status register disable.
3 LD pin comparator
0: disables LD pin comparator; internal/automatic holdover controller treats this pin as true (high) (default).
1: enables LD pin comparator.
2 Holdover enable Along with Bit 0, enables the holdover function. Automatic holdover must be disabled during VCO calibration.
0: holdover disabled (default).
1: holdover enabled.
1 External
holdover control 0: automatic holdover mode—holdover controlled by automatic holdover circuit. (default)
0 Holdover enable Along with Bit 2, enables the holdover function. Automatic holdover must be disabled during VCO calibration.
0: holdover disabled (default).
1: holdover enabled.
0x01F 6 VCO cal finished Read-only register: indicates status of the VCO calibration.
0: VCO calibration not finished.
1: VCO calibration finished.
5 Holdover active Read-only register: indicates if the part is in the holdover state (see Figure 53). This is not the same as holdover enabled.
0: not in holdover.
1: holdover state active.
4 REF2 selected Read-only register: indicates which PLL reference is selected as the input to the PLL.
0: REF1 selected (or differential reference if in differential mode).
1: REF2 selected.
3 VCO frequency >
0: VCO frequency is less than the threshold.
1: VCO frequency is greater than the threshold.
2 REF2 frequency >
0: REF2 frequency is less than threshold frequency.
1: REF2 frequency is greater than threshold frequency.
1 REF1 frequency >
0: REF1 frequency is less than threshold frequency.
1: REF1 frequency is greater than threshold frequency.
0 Digital lock detect Read-only register: digital lock detect.
0: PLL is not locked.
1: PLL is locked.
Bits Name Description
reference
enable
threshold
threshold
threshold
Selects the PLL reference mode, differential or single-ended. Single-ended must be selected for the automatic
switchover between REF1 and REF2 to work.
Enables the LD pin voltage comparator. This function is used with the LD pin current source lock detect mode. When
in the internal (automatic) holdover mode, this function enables the use of the voltage on the LD pin to determine if
the PLL was previously in a locked state (see Figure 53). Otherwise, this function can be used with the REFMON and
STATUS pins to monitor the voltage on this pin.
Enables the external hold control through the
1: external holdover mode—holdover controlled by
Read-only register: indicates if the VCO frequency is greater than the threshold (see Table 16: REF1, REF2, and VCO
frequency status monitor).
Read-only register: indicates if the frequency of the signal at REF2 is greater than the threshold frequency set by
Register 0x1A, Bit 6.
Read-only register: indicates if the frequency of the signal at REF2 is greater than the threshold frequency
set by Register 0x01A, Bit 6.
SYNC
pin. (This disables the internal holdover mode.)
SYNC
pin.
Rev. | Page 65 of 80
Page 66
AD9517-4
D
Table 55. Fine Delay Adjust—OUT4 to OUT7
Reg.
Addr.
(Hex)
0x0A0 0 OUT4 delay bypass Bypasses or uses the delay function.
0: uses delay function.
1: bypasses delay function (default).
0x0A1 [5:3] OUT4 ramp capacitors
Selects the number of ramp capacitors used by the delay function. The combination of the
number of the capacitors and the ramp current sets the delay full scale.
5 4 3 Number of Capacitors
Ramp current for the delay function. The combination of the number of capacitors and the ramp
current sets the delay full scale.
2 1 0 Current (μA)
Selects the fraction of the full-scale delay desired (6-bit binary).
A setting of 000000b gives zero delay.
Only delay values up to 47 decimals (101111b; 0x2F) are supported (default = 0x00).
Selects the number of ramp capacitors used by the delay function. The combination of the
number of the capacitors and the ramp current sets the delay full scale.
0x0A9 0 OUT7 delay bypass Bypasses or uses the delay function.
0: uses delay function.
1: bypasses delay function (default).
Ramp current for the delay function. The combination of the number of capacitors and the ramp
current sets the delay full scale.
2 1 0 Current (μA)
Selects the fraction of the full-scale delay desired (6-bit binary).
A setting of 000000b gives zero delay.
Only delay values up to 47 decimals (101111b; 0x2F) are supported (default = 0x00).
Selects the number of ramp capacitors used by the delay function. The combination of the
number of capacitors and the ramp current sets the delay full scale.
5 4 3 Number of Capacitors
Ramp current for the delay function. The combination of the number of capacitors and the ramp
current sets the delay full scale.
2 1 0 Current (μA)
Selects the fraction of the full-scale delay desired (6-bit binary).
A setting of 000000b gives zero delay.
Only delay values up to 47 decimals (101111b; 0x2F) are supported (default = 0x00).
Selects the number of ramp capacitors used by the delay function. The combination of the
number of capacitors and the ramp current sets the delay full scale.
5 4 3 Number of Capacitors
Ramp current for the delay function. The combination of the number of capacitors and the ramp
current sets the delay full scale.
2 1 0 Current Value (μA)
Selects the fraction of the full-scale delay desired (6-bit binary).
A setting of 000000b gives zero delay.
Only delay values up to 47 decimals (101111b; 0x2F) are supported (default = 0x00).
In CMOS mode, Bits[7:5] select the output polarity of each CMOS output.
In LVDS mode, only Bit 5 determines LVDS polarity.
7 6 5 OUT7A (CMOS) OUT7B (CMOS) OUT7 (LVDS)
Rev. | Page 71 of 80
Page 72
AD9517-4
D
Reg.
Addr.
(Hex) Bits Name Description
0x143 [2:1] OUT7 LVDS output current Sets output current level in LVDS mode. This has no effect in CMOS mode.
0 0 1.75 100
0 1 3.5 100 (default)
1 0 5.25 50
1 1 7 50
0 OUT7 power-down Powers down output (LVDS/CMOS).
0: power on (default).
1: power off.
Table 58. LVPECL Channel Dividers
Reg.
Addr.
(Hex)
0x190 [7:4] Divider 0 low cycles
[3:0] Divider 0 high cycles
0x191 7 Divider 0 bypass Bypasses and powers down the divider; routes input to divider output.
0: uses divider.
1: bypasses divider (default).
6 Divider 0 nosync No sync.
0: obeys chip-level SYNC signal (default).
1: ignores chip-level SYNC signal.
5 Divider 0 force high Forces divider output to high. This requires that nosync (Bit 6) also be set.
0: divider output forced to low (default).
1: divider output forced to high.
4 Divider 0 start high Selects clock output to start high or start low.
0: starts low (default).
1: starts high.
[3:0] Divider 0 phase offset Phase offset (default = 0x0).
0x192 1 Divider 0 direct to output Connects OUT0 and OUT1 to Divider 0 or directly to VCO or CLK.
0: OUT0 and OUT1 are connected to Divider 0 (default).
0x197 7 Divider 1 bypass Bypasses and powers down the divider; routes input to divider output.
0: uses divider (default).
1: bypasses divider.
6 Divider 1 nosync No sync.
0: obeys chip-level SYNC signal (default).
1: ignores chip-level SYNC signal.
5 Divider 1 force high Forces divider output to high. This requires that nosync (Bit 6) also be set.
0: divider output forced to low (default).
1: divider output forced to high.
Bits Name Description
2 1 Current (mA) Recommended Termination (Ω)
Number of clock cycles (minus 1) of the divider input during which divider output stays
low. A value of 0x0 means that the divider is low for one input clock cycle (default = 0x0).
Number of clock cycles (minus 1) of the divider input during which divider output stays
high. A value of 0x0 means that the divider is high for one input clock cycle (default = 0x0).
1: If Register 0x1E1[1:0] = 10b, the VCO is routed directly to OUT0 and OUT1.
If Register 0x1E1[1:0] = 00b, the CLK is routed directly to OUT0 and OUT1.
If Register 0x1E1[1:0] = 01b, there is no effect.
Number of clock cycles of the divider input during which divider output stays low.
A value of 0x0 means that the divider is low for one input clock cycle (default = 0x0).
Number of clock cycles (minus 1) of the divider input during which divider output stays
high. A value of 0x0 means that the divider is high for one input clock cycle (default = 0x0).
Rev. | Page 72 of 80
Page 73
AD9517-4
D
Reg.
Addr.
(Hex) Bits Name Description
0x197 4 Divider 1 start high Selects clock output to start high or start low.
0: starts low (default).
1: starts high.
[3:0] Divider 1 phase offset Phase offset (default = 0x0).
0x198 1 Divider 1 direct to output Connects OUT2 and OUT3 to Divider 2 or directly to VCO or CLK.
0: OUT2 and OUT3 are connected to Divider 1 (default).
0x19C 5 Bypass Divider 2.2 Bypasses (and powers down) 2.2 divider logic, routes clock to 2.2 output.
0: does not bypass (default).
1: bypasses.
4 Bypass Divider 2.1 Bypasses (and powers down) 2.1 divider logic, routes clock to 2.1 output.
0: does not bypass (default).
1: bypasses.
3 Divider 2 nosync No sync.
0: obeys chip-level SYNC signal (default).
1: ignores chip-level SYNC signal.
2 Divider 2 force high Forces Divider 2 output high. Requires that nosync also be set.
0: forces low (default).
1: forces high.
1 Start High Divider 2.2 Divider 2.2 start high/low.
0: starts low (default).
1: starts high.
0 Start High Divider 2.1 Divider 2.1 start high/low.
0: starts low (default).
1: starts high.
0x19D 0 Divider 2 DCCOFF Duty-cycle correction function.
0: enables duty-cycle correction (default).
1: disables duty-cycle correction.
0x19E [7:4] Low Cycles Divider 3.1
[3:0] High Cycles Divider 3.1
Bits Name Description
1: If Register 0x1E1[1:0] = 10b, the VCO is routed directly to OUT2 and OUT3.
If Register 0x1E1[1:0] = 00b, the CLK is routed directly to OUT2 and OUT3.
If Register 0x1E1[1:0] = 01b, there is no effect.
Number of clock cycles (minus 1) of 2.1 divider input during which 2.1 output stays low.
A value of 0x0 means that the divider is low for one input clock cycle (default = 0x0).
Number of clock cycles (minus 1) of 2.1 divider input during which 2.1 output stays high.
A value of 0x0 means that the divider is high for one input clock cycle (default = 0x0).
Number of clock cycles (minus 1) of 2.2 divider input during which 2.2 output stays low.
A value of 0x0 means that the divider is low for one input clock cycle (default = 0x0).
Number of clock cycles (minus 1)of 2.2 divider input during which 2.2 output stays high.
A value of 0x0 means that the divider is high for one input clock cycle (default = 0x0).
Number of clock cycles (minus 1) of 3.1 divider input during which 3.1 output stays low.
A value of 0x0 means that the divider is low for one input clock cycle (default = 0x0).
Number of clock cycles (minus 1) of 3.1 divider input during which 3.1 output stays high.
A value of 0x0 means that the divider is high for one input clock cycle (default = 0x0).
Rev. | Page 73 of 80
Page 74
AD9517-4
D
Reg.
Addr.
(Hex) Bits Name Description
0x19F [7:4] Phase Offset Divider 3.2 Refer to LVDS/CMOS channel divider function description (default = 0x0).
[3:0] Phase Offset Divider 3.1 Refer to LVDS/CMOS channel divider function description (default = 0x0).
0x1A0 [7:4] Low Cycles Divider 3.2
[3:0] High Cycles Divider 3.2
0x1A1 5 Bypass Divider 3.2 Bypasses (and powers down) 3.2 divider logic; routes clock to 3.2 output.
0: does not bypass (default).
1: bypasses.
4 Bypass Divider 3.1 Bypasses (and powers down) 3.1 divider logic; routes clock to 3.1 output.
0: does not bypass (default).
1: bypasses.
3 Divider 3 nosync Nosync.
0: obeys chip-level SYNC signal (default).
1: ignores chip-level SYNC signal.
2 Divider 3 force high Forces Divider 3 output high. Requires that nosync also be set.
0: forces low (default).
1: forces high.
1 Start High Divider 3.2 Divider 3.2 start high/low.
0: starts low (default).
1: starts high.
0 Start High Divider 3.1 Divider 3.1 start high/low.
0: starts low (default).
1: starts high.
0x1A2 0 Divider 3 DCCOFF Duty-cycle correction function.
0: enables duty-cycle correction (default).
1: disables duty-cycle correction.
Number of clock cycles (minus 1) of 3.2 divider input during which 3.2 output stays low.
A value of 0x0 means that the divider is low for one input clock cycle (default = 0x0).
Number of clock cycles (minus 1) of 3.2 divider input during which 3.2 output stays high.
A value of 0x0 means that the divider is high for one input clock cycle (default = 0x0).
0x1E1 4 Power down clock input section Powers down the clock input section (including CLK buffer, VCO divider, and CLK tree).
0: normal operation (default).
1: power-down.
3 Power down VCO clock interface Powers down the interface block between VCO and clock distribution.
0: normal operation (default).
1: power-down.
2 Power down VCO and CLK Powers down both VCO and CLK input.
0: normal operation (default).
1: power-down.
1 Select VCO or CLK Selects either the VCO or the CLK as the input to VCO divider.
0: selects external CLK as input to VCO divider (default).
1: selects VCO as input to VCO divider; cannot bypass VCO divider when this is selected.
0 Bypass VCO divider Bypasses or uses the VCO divider.
0: uses VCO divider (default).
1: bypasses VCO divider; cannot select VCO as input when this is selected.
2 1 0 Divide
Output static. Note that setting the VCO divider static should occur only
after VCO calibration.
Output static. Note that setting the VCO divider static should occur only
after VCO calibration.
Output static. Note that setting the VCO divider static should occur only
after VCO calibration.
Table 61. System
Reg.
Addr.
(Hex)
0x230 2 Power down sync Powers down the sync function.
0: normal operation of the sync function (default).
1: powers down sync circuitry.
1 Power down distribution reference Powers down the reference for distribution section.
0: normal operation of the reference for the distribution section (default).
1: powers down the reference for the distribution section.
0 Soft sync
Bits Name Description
The soft sync bit works the same as the SYNC
is reversed. That is, a high level forces selected channels into a predetermined static
state, and a 1-to-0 transition triggers a sync.
0: same as SYNC
1: same as SYNC
pin, except that the polarity of the bit
high (default).
low.
Table 62. Update All Registers
Reg.
Addr
(Hex) Bits Name Description
0x232 0 Update all registers
1 (self-clearing): updates all active registers to the contents of the buffer registers.
This bit must be set to 1b to transfer the contents of the buffer registers into the active
registers. This bit is self-clearing; that is, it does not have to be set back to 0b.
Rev. D | Page 75 of 80
Page 76
AD9517-4
D
APPLICATIONS INFORMATION
FREQUENCY PLANNING USING THE AD9517
The AD9517 is a highly flexible PLL. When choosing the PLL
settings and version of the AD9517, keep in mind the following
guidelines.
The AD9517 has the following four frequency dividers: the
reference (or R) divider, the feedback (or N) divider, the VCO
divider, and the channel divider. When trying to achieve a
particularly difficult frequency divide ratio requiring a large
amount of frequency division, some of the frequency division
can be done by either the VCO divider or the channel divider,
thus allowing a higher phase detector frequency and more
flexibility in choosing the loop bandwidth.
Within the AD9517 family, lower VCO frequencies generally
result in slightly lower jitter. The difference in integrated jitter
(from 12 kHz to 20 MHz offset) for the same output frequency is
usually less than 150 fs over the entire VCO frequency range
(1.45 GHz to 2.95 GHz) of the AD9517 family. If the desired
frequency plan can be achieved with a version of the AD9517
that has a lower VCO frequency, choosing the lower frequency
part results in the lowest phase noise and the lowest jitter.
However, choosing a higher VCO frequency may result in more
flexibility in frequency planning.
Choosing a nominal charge pump current in the middle of the
allowable range as a starting point allows the designer to increase or
decrease the charge pump current, and thus allows the designer
to fine-tune the PLL loop bandwidth in either direction.
ADIsimCLK is a powerful PLL modeling tool that can be
downloaded from www.analog.com. It is a very accurate tool for
determining the optimal loop filter for a given application.
USING THE AD9517 OUTPUTS FOR ADC CLOCK
APPLICATIONS
Any high speed ADC is extremely sensitive to the quality of its
sampling clock. An ADC can be thought of as a sampling mixer,
and any noise, distortion, or timing jitter on the clock is combined
with the desired signal at the analog-to-digital output. Clock
integrity requirements scale with the analog input frequency
and resolution, with higher analog input frequency applications
at ≥14-bit resolution being the most stringent. The theoretical
SNR of an ADC is limited by the ADC resolution and the jitter
on the sampling clock. Considering an ideal ADC of infinite
resolution where the step size and quantization error can be
ignored, the available SNR can be expressed approximately by
SNR
⎛
⎜
×=
log20(dB)
⎜
⎝
⎞
1
⎟
⎟
π
tf
2
J
A
⎠
where:
is the highest analog frequency being digitized.
f
A
is the rms jitter on the sampling clock.
t
J
Figure 70 shows the required sampling clock jitter as a function
of the analog frequency and effective number of bits (ENOB).
110
f
A
(MHz)
SNR = 20log
t
J
=
1
0
0
2
0
0
f
S
4
0
0
f
S
1
p
s
2
p
s
1
0
p
s
100
90
80
70
SNR (dB)
60
50
40
30
101k100
Figure 70. SNR and ENOB vs. Analog Input Frequency
1
2πf
f
S
AtJ
18
16
14
12
ENOB
10
8
6
See the AN-756 Application Note, Sampled Systems and the Effects
of Clock Phase Noise and Jitter; and the AN-501 Application Note,
Aperture Uncertainty and ADC System Performance, at
www.analog.com.
Many high performance ADCs feature differential clock inputs
to simplify the task of providing the required low jitter clock on
a noisy PCB. (Distributing a single-ended clock on a noisy PCB
may result in coupled noise on the sample clock. Differential
distribution has inherent common-mode rejection that can provide
superior clock performance in a noisy environment.) The AD9517
features both LVPECL and LVDS outputs that provide differential
clock outputs, which enable clock solutions that maximize
converter SNR performance. The input requirements of the ADC
(differential or single-ended, logic level, termination) should be
considered when selecting the best clocking/converter solution.
06428-044
Rev. | Page 76 of 80
Page 77
AD9517-4
V
V
V
V
V
D
LVPECL CLOCK DISTRIBUTION
The LVPECL outputs of the AD9517 provide the lowest jitter
clock signals that are available from the AD9517. The LVPECL
outputs (because they are open emitter) require a dc termination
to bias the output transistors. The simplified equivalent circuit in
Figure 59 shows the LVPECL output stage.
In most applications, an LVPECL far-end Thevenin termination
(see Figure 71) or Y-termination (see Figure 72) is recommended.
In each case, the V
V
voltage. If it does not, ac coupling is recommended (see
S_LVPECL
Figure 73). In the case of Figure 73, pull-down resistors of <150 Ω
are not recommended when V
the LVPECL drivers may result. The minimum recommended
pull-down resistor size for V
The resistor network is designed to match the transmission line
impedance (50 Ω) and the switching threshold (V
V
S_LVPECL
LVPECL
Figure 71. DC-Coupled 3.3 V LVPECL Far-End Thevenin Termination
S_LVPECL
LVPECL
Figure 72. DC-Coupled 3.3 V LVPECL Y-Termination
S_LVPECL
LVPECL
200Ω200Ω
Figure 73. AC-Coupled LVPECL with Parallel Transmission Line
of the receiving buffer should match the
S
= 3.3 V; if used, damage to
S_LVEPCL
= 2.5 V is 100 Ω.
S_LVPECL
− 1.3 V).
S
S_DRV
V
S
50Ω
127Ω127Ω
83Ω83Ω
50Ω
50Ω
100Ω
LVPECL
VS = 3.3V
LVPECL
LVPECL
V
S
50Ω
SINGLE-ENDED
(NOT COUPLED)
50Ω
Z0 = 50Ω
Z0 = 50Ω
0.1nF
100Ω DIFFERENTIAL
0.1nF
(COUPLED)
TRANSMISSION LINE
06428-145
06428-147
06428-146
LVPECL Y-termination is an elegant termination scheme that
uses the fewest components and offers both odd- and even-mode
impedance matching. Even-mode impedance matching is an
important consideration for closely coupled transmission lines
at high frequencies. Its main drawback is that it offers limited
flexibility for varying the drive strength of the emitter-follower
LVPECL driver. This can be an important consideration when
driving long trace lengths but is usually not an issue. In the case
shown in Figure 72, where VS_LVPECL = 2.5 V, the 50 Ω
termination resistor that is connected to ground should be
changed to 19 Ω.
Thevenin-equivalent termination uses a resistor network to
provide 50 Ω termination to a dc voltage that is below V
of
OL
the LVPECL driver. In this case, VS_LVPECL on the AD9517
should equal V
of the receiving buffer. Although the resistor
S
combination shown in Figure 72 results in a dc bias point of
VS_LVPECL − 2 V, the actual common-mode voltage is
VS_LVPECL − 1.3 V because additional current flows from the
AD9517 LVPECL driver through the pull-down resistor.
The circuit is identical when VS_LVPECL = 2.5 V, except that the
pull-down resistor is 62.5 Ω and the pull-up resistor is 250 Ω.
LVDS CLOCK DISTRIBUTION
The AD9517 provides four clock outputs (OUT4 to OUT7) that
are selectable as either CMOS or LVDS level outputs. LVDS is a
differential output option that uses a current mode output stage.
The nominal current is 3.5 mA, which yields 350 mV output swing
across a 100 Ω resistor. An output current of 7 mA is also available
in cases where a larger output swing is required. The LVDS
output meets or exceeds all ANSI/TIA/EIA-644 specifications.
A recommended termination circuit for the LVDS outputs is
shown in Figure 74.
S
LVDS
DIFFERENTIAL (COUPLED)
100Ω
100Ω
Figure 74. LVDS Output Termination
See the AN-586 Application Note, LVDS Data Outputs for HighSpeed Analog-to-Digital Converters for more information on LVDS.
S
LVDS
06428-047
Rev. | Page 77 of 80
Page 78
AD9517-4
V
Ω
D
CMOS CLOCK DISTRIBUTION
The AD9517 provides four clock outputs (OUT4 to OUT7)
that are selectable as either CMOS or LVDS level outputs.
When selected as CMOS, each output becomes a pair of CMOS
outputs, each of which can be individually turned on or off and
set as noninverting or inverting. These outputs are 3.3 V CMOS
compatible.
Whenever single-ended CMOS clocking is used, some of the
following general guidelines should be used.
Point-to-point nets should be designed such that a driver has
only one receiver on the net, if possible. This allows for simple
termination schemes and minimizes ringing due to possible
mismatched impedances on the net.
Series termination at the source is generally required to provide
transmission line matching and/or to reduce current transients
at the driver. The value of the resistor is dependent on the board
design and timing requirements (typically 10 Ω to 100 Ω is used).
CMOS outputs are also limited in terms of the capacitive load
or trace length that they can drive. Typically, trace lengths of less
than 3 inches are recommended to preserve signal rise/fall times
and preserve signal integrity.
60.4
(1.0 INCH)
10Ω
CMOSCMOS
Figure 75. Series Termination of CMOS Output
MICROSTRIP
06428-076
Termination at the far end of the PCB trace is a second option.
The CMOS outputs of the AD9517 do not supply enough current
to provide a full voltage swing with a low impedance resistive,
far-end termination, as shown in Figure 76. The far-end
termination network should match the PCB trace impedance and
provide the desired switching point. The reduced signal swing
may still meet receiver input requirements in some applications.
This can be useful when driving long trace lengths on less
critical nets.
S
10Ω
CMOSCMOS
Figure 76. CMOS Output with Far-End Termination
50Ω
100Ω
100Ω
6428-077
Because of the limitations of single-ended CMOS clocking,
consider using differential outputs when driving high speed
signals over long traces. The AD9517 offers both LVPECL and
LVDS outputs that are better suited for driving long traces
where the inherent noise immunity of differential signaling
provides superior performance for clocking converters.
Rev. | Page 78 of 80
Page 79
AD9517-4
D
OUTLINE DIMENSIONS
PIN 1
INDICATOR
1.00
0.85
0.80
SEATING
PLANE
12° MAX
7.10
7.00 SQ
6.90
TOP VIEW
0.60 MAX
6.85
6.75 SQ
6.65
0.80 MAX
0.65 TYP
0.05 MAX
0.02 NOM
COPLANARITY
0.20 REF
*
COMPLIANT TO JEDEC STANDARDS MO-220-VKKD-2
WITH EXCEPTION TO EXPOSED PAD DIMENSION.
0.50
REF
0.08
0.50
0.40
0.30
0.60 MAX
36
25
37
EXPOSED
(BOTTOM VIEW)
24
5.50 REF
Figure 77. 48-Lead Lead Frame Chip Scale Package [LFCSP_VQ]
7 mm × 7 mm Body, Very Thin Quad
CP-48-8
Dimensions shown in millimeters
ORDERING GUIDE
Model1 Temperature Range Package Description Package Option
AD9517-4ABCPZ −40°C to +85°C 48-Lead Lead Frame Chip Scale Package (LFCSP_VQ) CP-48-8
AD9517-4ABCPZ-RL7 −40°C to +85°C 48-Lead Lead Frame Chip Scale Package (LFCSP_VQ) CP-48-8
AD9517-4A/PCBZ Evaluation Board
1
Z = RoHS Compliant Part.
0.30
0.23
0.18
48
PAD
13
FORPROPERCONNECTIONOF
THE EXPOSED PAD, REFER TO
THE PIN CONFIGURATION AND
FUNCTION DESCRIPTIONS
SECTION OF THIS DATA SHEET.