The A-Series hydraulic-magnetic circuit breakers offer
precise operation in a compact size for both general
purpose as well as full amp load applications. Visi
Rocker® and recessed paddle actuators are ideally
suited for clean, front panel designs while the metal
toggle conguration is ideal for harsh environments. The
A-Series is available as a one to six pole conguration,
rated up to 50 amps, 277VAC/80VDC and has a max IC
of 7,500 amps.
specication MIL-PRF-55629 & MIL-STD-202 as follows:
current.
90% of rated current.
days @ +85°C, 85% RH.
RH @ 5% NaCl Solution, 96 hrs).
to +25°C).
Current RatingsStandard current coils: 0.100,
0.250, 0.500, 0.750, 1.00, 2.50, 5.00,
7.50, 10.0, 15.0, 20.0, 25.0, 30.0, 35.0,
40.0, 50.0. Other ratings available
Standard Voltage CoilsDC-6V, 12V; AC-120V, Other ratings
available, consult ordering
Auxiliary Switch RatingSPDT; 10.1 A - 250VAC,
1.0 A-65VDC/0.5 A - 80 VDC,
Insulation ResistanceMinimum: 100 Megohms at 500
Dielectric StrengthUL, CSA - 1500V 60 Hz for one
minute between all electrically
isolated terminals. A-Series
rocker circuit breakers comply
with the 8mm spacing & 3750V
dielectric requirements from
hazardous voltage to operator
accessible surfaces per EN 60950
Resistance, ImpedanceValues from Line to Load Terminal
based on Series Trip Circuit
RESISTANCE PER POLE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
1000
100
10
O
1
H
M
S
0.1
CURRENT
(AMPS)
TOLERANCE
(%)
0.10 - 5.015
5.1 - 20.025
20.1 - 50.035
Endurance10,000 ON-OFF operations @ 6
per minute; with rated Current &
Trip FreeAll A-Series Circuit Breakers will
trip on overload, even when the
actuator is forcibly held in the ON
Trip IndicationThe operating actuator moves
positively to the OFF position
when an overload causes the
circuit breaker to trip. When
mid-trip handle is specied, the
handle moves to the mid position
on electrical trip of the circuit
breaker. When mid-trip handle
with alarm switch is specied,
the handle moves to the mid
position & the alarm switch
actuates when the circuit breaker
Number of Poles1 - 6 Poles (handle) and 1-3 poles
(rocker) at 30 Amps or less.1 and
Internal Circuit Cong.Series, (with or without auxiliary
switch), Shunt and Relay with
current or voltage trip coils, Dual
Coil, Switch Only with or without
WeightApproximately 65 grams/pole.
Standard ColorsHousing - Black; Actuator- See
Designed and tested in accordance with requirements of
0.01
0.001
0.01
0.1
AMPERE RATING
02.
Pulse Tolerance Curves
Rated Current
*Manufacturer reserves the right to change product specication without prior notice.
Inrush Pulse Tolerance
60 Hz 1/2 Cycle
Time Delay Curves
(50 Amps Max.)
Time Delay Curves
(50 Amps Max.)
1
42, 44 & 46
22, 24 & 26
10
Time in
Milliseconds
100
22x
10x
Rated Current
Inrush Pulse Tolerance
10.0
5.0
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
Time Delay Curves
22, 24 & 26
(50 Amps Max.)
20.0
Time in
Milliseconds
ShockWithstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultra-short
curves tested @ 90% of rated
VibrationWithstands 0.060” excursion from
10-55 Hz, and 10 Gs 55-500 Hz, at
rated current per Method 204C,
Test Condition A. Instantaneous
and ultrashort curves tested at
Moisture ResistanceMethod 106D; ten 24-hour cycles
@ + 25°C to +65°C, 80-98% RH.56
Salt SprayMethod 101, Condition A (90-95%
Thermal ShockMethod 107D, Condition A (Five
cycles @ -55°C to +25°C to +85°C
Operating Temperature-40° C to +85° C
Page 3
Tech Specs
Electrical Tables
Table A: Lists UL Recognized & CSA Accepted congurations and performance capabilities as a
Notes:
1 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector.
2 Same as note 1, except that backup fuse is limited to 80 A maximum.
3 2 pole protector required (with one pole per power line) for: 125/250 VAC, 1 pole protector required for : 125 VAC, 1Ø Power System.
4 Satises the requirements of clause 11.2.8.2.5 of CSA STD C22.2 No 100 for the use of supplementary protectors with portable generators.
Page 4
Tech Specs
Electrical Tables
Table B:Lists UL Recognized, CSA Accepted, VDE & TUV Certied congurations & performance capabilities as a
Notes:
1 General Purpose Ratings for UL/CSA Only.
2 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector.
3 Same as note 2, except that backup fuse is limited to 80 A maximum.
4 Satises the requirements of clause 11.2.8.2.5 of CSA STD C22.2 No 100 for the use of supplementary protectors with portable generators.
Table C: Lists UL Recognized, CSA Accepted congurations and performance capabilities as Protectors,
Supplementary for Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500.
UL Classied Small Craft Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as
Marine Supplementary Protectors.
UL1500 (Marine Ignition Protection)
Circuit
Conguration
Rating
Series
125 / 2501
1 Notes:
2 Available with special catalog number only (consult factory).
3 2 pole protector required (with one per power line) for 125 / 250 VAC. 1 pole protector required for 125 VAC 1 phase power system
Voltage
Max
Frequency Phase
1
14
1
32
65
125
25010.02 - 301500TC1, OL1, U1TC1, OL1, U1
DC---
50 / 60
Current
Rating
Full Load
Amps
0.02 - 50
1TC1, OL1, U2TC1, OL1, U2
2
Table D: Lists UL Listed congurations and performance capabilities as Circuit Breakers for use in
Communications Equipment
Short Circuit
Capacity
(Amps)
Without
Backup Fuse
5000
3000
Application Codes
ULCSA
TC1, OL1, U1TC1, OL1, U1
TC1, OL1, U2TC1, OL1, U2
TC1, OL1, U1TC1, OL1, U1
TC1, OL1, U2TC1, OL1, U2
UL489A (Communications Equipment)
Circuit
Conguration
Series80DC
Notes:
1 Parallel Pole Construction
VoltageCurrent RatingInterrupting Capacity (Amps)
Max RatingFrequencyGeneral Purpose Amps without Backup Fuse
0.10 - 50
60 - 90
1
5000
Time Delay Specs
To view all hydraulic-magnetic circuit breaker time delay values, please visit
www.carlingtech.com/sites/default/les/documents/Carling-HM-CB-Time-Delays.pdf
UL 1077Component Recognition Program
UL 508Switches, Industrial Control
UL 1500Protectors, Supplementary for
as Protectors Supplementary
Marine Electrical & Fuel Systems
(Guide PEQZ2, File E75596) Ignition
UL 489ACommunications Equipment
CSA CertiedComponent Supplementary
TUV CertiedEN60934, under License No.
VDE CertiedEN60934, VDE 0642 under File
05.
Protector under Class 3215 30,
File 047848 0 000 CSA
Page 6
Sample
Part Number
A
A
3-B
0-10
-
450
-
1B1-C
Selection
123 4 567 8 9
10
11
Ordering Scheme
Handle - UL 1077 Recognized
06.
1. SERIES
A
2. ACTUATOR
A Handle, one per pole
B Handle, one per multipole unit
S Mid-Trip Handle, one per pole
T Mid-Trip Handle, one per pole & Alarm Switch
1
3. POLES
1 One
2 Two
3 Three
4 Four
5 Five
6 Six
4. CIRCUIT
A 2 Switch Only (No Coil) F 3 Relay Trip (Current)
B Series Trip (Current) G
C Series Trip (Voltage) H
03 DC 50/60Hz, Switch Only
10 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
30 DC, 50/60Hz Instantaneous
Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided un-assembled with multi-pole
units.
B: Handle location as viewed from front of breaker:
2 pole - left pole 3 pole - center pole 4 pole - two handles at center poles
5 pole - three handles at center poles 6 pole - four handles at center poles
S: Handle moves to mid-position only upon electrical trip of the breaker. Available
with circuit codes B, C, D, E, F, G, H and K.
T: Handle moves to mid-position and alarm switch activates only upon electrical
trip of the breaker. Available with circuit codes B & C.
2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available when
tied to a protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps, select Cur
rent Code 630. For 35 - 50 amps, select Current Code 650.
3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 50A amps
maximum.
4 Consult factory for available Dual Coil options, as special catalog number is
required. With Shunt construction, Dual Coils will trip instantaneously on line volt
age. Dual coils require 30VA minimum power to trip and are rated for intermittent
duty only.
5 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A - supplied
with standard half shells. 35-50A - supplied with extended boat (B-Style) half
shells. On multi-pole breakers, one auxiliary switch is supplied, mounted in the
extreme right pole.
6 Separate pole type voltage coils not rated for continuous duty. Available only with
delay codes 10 and 20.
7 Available with Circuit Codes B & D only. VDE Certied to 30 amps. UL Recognized,
CSA Accepted & TUV Certied to 50 amps.
8 VDE Certication available with single pole breakers with DC Delay only. UL Recog
nition and CSA Accepted available in one and two pole breakers.
9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings
over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q.
10 Terminal Code 1: VDE Certication up to 25 amps and UL Recognition and CSA
Certication up to 30 amps, but not recommended over 20 amps.
11 Terminal Codes 3, 5, E and H (Bus Type) with VDE, are supplied with Lock Washers,
and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat
Washers. These breakers are only VDE Certied when the washers are used.
12 Terminal Code L: VDE Certied available up to 12A. UL Recognized & CSA Accepted
available up to 30A.
13 Single pole breakers with Terminal Code P (Printed Circuit Board) are available
up to 30 amps with VDE Certication and 50 amps with UL Recognition and CSA
Accepted, with Circuit Codes A, B and C. Two pole breakers with Terminal Code
P (Printed Circuit Board) are available up to 40 amps with UL Recognition and CSA
Accepted with Circuit Codes A, B and C.
14 Terminal Code Q not available with VDE certication.
15 Single pole only.
31 DC, 50/60Hz Ultra Short
32 DC, 50/60Hz Short
34 DC, 50/60Hz Medium
36 DC, 50/60Hz Long
White A B 1 Black
Black C D 2White
Red F G 3White
Green H J 4White
Blue K L 5White
Yellow M N 6 Black
Gray P Q 7 Black
Orange R S 8 Black
Black (short handle)15 T U 9White
10. MOUNTING / BARRIERS
MOUNTING STYLE BARRIERS
Threaded Insert, 2 per pole
1 6-32 x 0.195 inches no
A 6-32 x 0.195 inches yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multipole only) yes
Front panel Snap-In, 0.75” wide bezel
5 without Handleguard no
6 without Handleguard (multipole only) yes
Front panel Snap-In, 0.96” wide bezel
7 without Handleguard, 1-pole 0.96” wide; no
multipole units have .105” bezel overhang on all sides
8without Handleguard, 1-pole 0.96” wide; yes (multipole only) .105” bezel overhang on all sides
11. AGENCY APPROVAL
C UL Recognized & CSA Accepted
D VDE Certied, UL Recognized & CSA Accepted
E TUV Certied, UL Recognized & CSA Accepted
I UL Recognized STD 1077, UL Recognized 1500
& CSA Accepted
Congure Complete Part Number > Browse Standard Parts >
(ignition protected),
Page 7
Sample
Part Number
AA1-B
0-14
-
450
-
1B1-M
T
Selection
123 4567 891011
12
Ordering Scheme
Handle - UL 489A Listed
1. SERIES
A
2. ACTUATOR
A Handle, one per pole
S Mid-Trip Handle, one per pole
T Mid-Trip Handle, one per pole & Alarm Switch
& 30° bend
8 Screw 10-32 with upturned
lugs & 30° bend
(Bus Type)
9
Screw 10-32
& 30° bend
B
Screw M5 with upturned lugs
F Screw M5 with upturned lugs
& 30° bend
G Screw M5 (Bus Type) & 30° bend
H Screw M5 (Bus Type)
M 7 M6 Threaded Stud
8
P
Printed Circuit Board Terminals
9
Q
Push-In Stud & 30° bend
(Bus Type)
9. ACTUATOR COLOR & LEGEND
Actuator Color ON-OFF Dual Legend Color
White B 1 Black
Black D 2White
Red G 3White
Green J 4White
Blue L 5White
Yellow N 6 Black
Gray Q 7 Black
Orange S 8 Black
Black (short handle) 10 U 9White
10. MOUNTING / BARRIERS
MOUNTING STYLE BARRIERS
Threaded Insert, 2 per pole
1 6-32 x 0.195 inches no
A 6-32 x 0.195 inches yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multipole only) yes
Front panel Snap-In, 0.75” wide bezel
5 without Handleguard no
6 without Handleguard (multipole only) yes
Front panel Snap-In, 0.96” wide bezel
7 without Handleguard, 1-pole 0.96” wide; no
multipole units have .105” bezel overhang on all sides
8without Handleguard, 1-pole 0.96” wide; yes (multipole only) .105” bezel overhang on all sides
9
11. MAXIMUM APPLICATION RATING
M 80 DC
12. AGENCY APPROVAL
T UL489A Listed
K UL489A Listed, VDE Certied
J UL489A Listed, TUV Certied
Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided un-assembled with multi-pole units.
S: Handle moves to mid-position only upon electrical trip of the breaker.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip
of the breaker.
2 On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right
pole.
3 VDE Certied to 30 amps. UL489A Listed to 50 amps.
4 VDE Certication available with single pole breakers only. UL489A Listing available with
one and two pole breakers.
5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30
amps are only available with Terminal Codes 5, 9 G, H, M and Q.
6 Terminal Code 1 (Push-On) available up to 25 amps with VDE Certication and 30
amps with UL489A Listing, but is not recommended over 20 amps.
7 Terminal Codes 3, 5 and H (Bus Type) with VDE, are supplied with Lock Washers, and
Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers.
These breakers are only VDE Certied when the washers are used.
8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to
30 amps with VDE Certication and 50 amps with UL489A Listing.
9 Terminal Code Q not available with VDE certication.10 Single pole only.
Congure Complete Part Number > Browse Standard Parts >
07.
Page 8
A-Series Circuit Breaker - Handle WORLD – Ordering Scheme
Sample
Part Number
A
A
3-B
0-14
-
450
-
1A1-P
Selection
123 4 5 67 89
10
11
Ordering Scheme
1. SERIES
A
2. ACTUATOR
A Handle, one per pole
B Handle, one per multipole unit
S Mid-Trip Handle, one per pole
T Mid-Trip Handle, one per pole & Alarm Switch
3. POLES
1 One
2 Two
4. CIRCUIT
A 2 Switch Only (No Coil) D
B Series Trip (Current) E
C Series Trip (Voltage) H
Voltage Coil
5. AUXILIARY / ALARM SWITCH
0 without Aux Switch
2 S.P.D.T., 0.110 Q.C. Term.
6. FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only
10 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
White A 1 Black
Black C 2White
Red F 3White
Green H 4White
Blue K 5White
Yellow M 6 Black
Gray P 7 Black
Orange R 8 Black
Black (short handle)15 T 9White
10. MOUNTING / BARRIERS
MOUNTING STYLE BARRIERS
Threaded Insert, 2 per pole
1 6-32 x 0.195 inches no
A 6-32 x 0.195 inches yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multipole only) yes
Front panel Snap-In, 0.75” wide bezel
5 without Handleguard no
6 without Handleguard (multipole only) yes
Front panel Snap-In, 0.96” wide bezel
7 without Handleguard, 1-pole 0.96” wide; no
multipole units have .105” bezel overhang on all sides
8without Handleguard, 1-pole 0.96” wide; yes (multipole only) .105” bezel overhang on all sides
11. AGENCY APPROVAL
P TUV Certied, UL Recognized & CSA Accepted
Q UL Recognized STD 1077, UL Recognized 1500
& CSA Accepted
Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole
units.
S: Handle moves to mid-position only upon electrical trip of the breaker. Available
with circuit codes B, C, D, E, and H.
T: Handle moves to mid-position and alarm switch activates only upon electrical
trip of the breaker. Available with circuit codes B & C.
2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available when
tied to a protected pole (Circuit Code B, C, D or H.), For .01 to 30 amps, select
Current Code 630. For 35 - 50 amps, select Current Code 650.
3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps
maximum.
4 Consult factory for available Dual Coil options, as special catalog number is
required. With Shunt construction, Dual Coils will trip instantaneously on line volt
age. Dual coils require 30VA minimum power to trip and are rated for intermittent
duty only.
5 On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme
right pole.
6 Separate pole type voltage coils not rated for continuous duty. Available only with
delay codes 10, 20 & 30.
7 Available with Circuit Codes B & D only. VDE Certied to 30 amps. UL Recognized,
CSA Accepted & TUV Certied to 50 amps.
8 Available up to two poles with AC or DC delays.
9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings
over 30 amps are only available with Terminal Codes 5, 9, G and H.
10 Terminal Code 1: TUV Certication up to 30 amps, but not recommended over 20
amps.
11 Terminal Codes 3, 5 , 7, 9, E, G and H (Bus Type) are supplied with Lock Washers.
These breakers are only TUV Certied when the washers are used.12 Single pole only.
Congure Complete Part Number > Browse Standard Parts >
(ignition protected),
08.
8. TERMINAL
10
1
Push-On 0.250 Tab (Q.C.)
2
Screw 8-32 with upturned
lugs
11
Screw 8-32 (Bus Type)
3
4
Screw 10-32 with upturned
lugs
5 11 Screw 10-32 (Bus Type)
6
Screw 8-32 with upturned
lugs & 30° bend
7 Screw 8-32
& 30° bend
8 Screw 10-32 with upturned
lugs & 30° bend
(Bus Type)
9
Screw 10-32
& 30° bend
B
Screw M5 with upturned lugs
C Screw, M4 with upturned lugs
11
E
Screw M4 (Bus Type)
F Screw M5 with upturned lugs
& 30° bend
G Screw M5 (Bus Type) & 30° bend
H 11 Screw M5 (Bus Type)
M M6 Threaded Stud
R Screw, M4 with upturned lugs
& 30° Bend
11
T
Screw, M4 with upturned lugs
(Bus Type)
Page 9
> 30 AMPS
LOAD
CIRCUIT
CODE
CIRCUIT
[25.40]
Circuit & Terminal Diagrams
inches [millimeters]
Handle
2 TERMINALS
5 TERMINALS
.205
[5.21]
3 TERMINALS
4 TERMINALS
CIRCUIT BREAKER PROFILE
LINE
MAIN TERMINALS
(SEE TABLE A)
LOAD
1.640
[41.66]
NC
NO
C
STANDARD
AUX. SWITCH
TERMINALS
.390
[9.91]
1
.780
[19.81]
2
3
4
.390
[9.91]
NO
NC
C
.520
[13.21]
ALARM
SWITCH
TERMINALS
& STD. AUX.
VDE OR <30
AMPS oR
AGENCY
CODE”P”
CIRCUIT SCHEMATIC
ANSI
SWITCH ONLY (NO COIL)
LINE
LOAD
LINE
NC
NO
LOAD
C
SHUNT TRIP
LINE
SHUNT
LOAD
RELAY TRIP
LINE
1
2
LOAD
RELAY
3
4
RELAY
CODE
A
FG0
CIRCUIT SCHEMATIC
AUX
SWITCH
CODE
ANSI
SERIES TRIP
LINE
BCA
LOAD
SERIES TRIP WITH (3)
AUXILIARY/ALARM SWITCH
1
2
3
4
DUAL COIL; SERIES TRIP CURRENT COIL,
NC
NO
C
STANDARD
AUX. SWITCH
RELAY TRIP VOLTAGE COIL
LINE
VOLTAGE
LOAD
DUAL COIL; SERIES TRIP CURRENT COIL,
RELAY TRIP VOLTAGE COIL
LINE
LOAD
COIL
1
2
3
4
ALARM SWITCH
VOLTAGE
COIL
NO
NC
AUX
CODE
SWITCH
BC0
C
BC
H
K0
1
2
3
4
0DE0
09.
AUXILIARY/ALARM SWITCH TERMINAL DETAIL
.239
[6.07]
NC
NO
LINE
.205
[5.21]
C
LOAD
.677
< 30 AMPS
[17.19]
LINE
LOAD
Notes:
1 Tolerance ±.020 [.51] unless otherwise specied.
2 Alarm Switch available with .110 x .020 Q.C. & Solder Lug Terminals Only.
.406
[10.31]
.344
[8.74]
.050 DIA [ 1.27]
TAB (Q.C.)
.520
[13.21]
2 PLCS
C
NO
NC
1.000
.110
[2.79]
.051 DIA [ 1.29]
.087
[2.20]
.287
[7.29]
TAB (Q.C.)
.250
[6.35]
TAB (Q.C.)
.110
[2.80]
.093
[2.36]
Page 10
[5.59]
Circuit & Terminal Diagrams
inches [millimeters]
Handle
.069
[1.75]
DIA
TAB(Q.C.)
30 AMP
MID
TRIP
HANDLE POSITION VS. AUX/ALARM SWITCH MODE
30
0
ON
30
90
.344
[8.74]
MID TRIP C/B
VOLTAGE COILS
1.936
[49.17]
MID TRIP C/B
ALARM SWITCH MODE
NC
NC
NC
.361
[9.17]
.110
[2.79]
.110 QC
ONLY
HANDLE POSITION
30
OFF
0
C
NO
ON
NO
NO
M6 STUD
30
C
90
MID
TRIP
C
.750
[19.05]
.405
[10.29]
50 AMP
TIGHTENING TORQUE
SPECIFICATIONS
TABLE A
(W/O ALARM SWITCH)
.100
[2.54]
.750
[19.05]
AUX. SWITH CODE
NO
NC
NO
NC
NO
NC
PUSH-IN STUF
50 AMP
TORQUETHREAD SIZE
#6-32 & M3 MOUNTING
HARDWARE
#8-32 & M4 THREAD
TERMINAL SCREW
#10-32 & M5 THREAD
TERMINAL SCREW
7-9 IN-LBS
[0.8-1.0 NM]
12-15 IN-LBS
[1.4-1.7 NM]
15-20 IN-LBS
[1.7-2.3 NM]
TABLE B
TERMINAL DESCRIPTION
MAIN
SHUNT,RELAY
&
DUAL COIL
AUX. SWITCH*
*AVAILABLE ON SERIES TRIP AND SWITCH ONLY CIRCUITS
WHEN CALLED FOR ON MULTI-POLE UNITS, ONLY ONE AUX.
SWITCH IS NORMALLY SUPPLIED, AS SHOWN IN MULTI-POLE
INDENTIFICATION SHEME.
TAB (Q.C.)
SCREW TYPE
TAB (Q.C.)
SCREW #8-32
W/UPTURNED LUGS
1.350
[34.29]
2.207[56.10]
2.095[53.20].093 TAB (Q.C.)
2.189[55.60].110 TAB (Q.C.)
2 PLCS
C
C
C
1.000
[25.40]
CENTERLINE OF PUSH-IN
STUD CONTACT AREA
.154
DIA
[3.91]
DEPTH
BEHIND PANEL
2.000[50.80]
2.032[51.60]
2.364[60.05]
1.970[50.00]SOLDER TYPE
.393
[9.96]
30
.392
[9.97]
REF
1.560
[39.62]
TYP
CIRCUIT
BREAKER
MODE
OFF
STANDARD C/B
HANDLE POSITION
30
OFF
0
ON
AUX. SWITCH MODE
C
NO
NC
HANDLE POSITION
OFF
ON
ELECTRICAL
TRIP
30
30
OFF
0
NC
NC
C
NO
MID
TRIP
C
NO
TERMINAL DIMENSIONAL DETAIL & RATING
.360
[9.14]
.250
[6.35]
UPTURN LUG
#8-32 30 AMP
#10-32 30 AMP
M5 30 AMP
M4 30 AMP
.392
[9.96]
.375
[9.53]
#10-32 50 AMP
PUSH-IN STUD
MATING HOLE
UL-RECOGNIZED MULTI-POLE
SEE TABLE-B
DEPTH BEHIND PANEL
ON
OFF
O
.375
[9.53]
BUS
#8-32 30 AMP
.520
[13.21]
BARRIER FOR
BREAKERS
LINE
(NETZ)
1.560
TYP
[39.62]
.392
[9.96]
+.002
-.000
.161 DIA [ 4.10]
.250
DIA
.093
[6.35]
[.76]
QC SOLDER LUG
30 AMP
[+.05]
[-.00]
LINE
LOAD
2.000
[50.80]
10.
LOAD
1.640
[41.66]
Notes:
1 Tolerance ±.020 [.51] unless otherwise specied.
2 Alarm Switch available with .110 x .020 QC & solder lug terminals only.
.032
[.81]
REF
(LAST)
TYP
.220
TYP
M6 STUD
PUSH-IN
STUD
SCREW TERMINAL
WITH 30 BEND
Page 11
#6-32 [M3] THREAD X.195[4.95]DEEP
1.640
UNLESS OTHERWISE SPECIFIED
Dimensional Specs
inches [millimeters]
Handle
2 PLCS PER POLE
[15.49]
1-POLE
(AA1)
.170
[4.32]
2-POLE
(AA2)
3-POLE
(AA3)
2.265
[57.53]
MAX
.610
.755
[19.18]
MAX
TYPICAL-OPTIONAL
“ON-OFF” LEGEND
.750
[19.05]
1.515
[38.48]
MAX
.750
[19.05]
TYP
.130
[3.30]
SEE NOTE 3
60
.690
[17.50]
MULTI-POLE HANDLE TIE KIT
SHIPPED BULK
.250
[6.35]
SHORT HANDLE
ON
OFF
2-POLE
(AB2)
3-POLE
(AB3)
[41.66]
TYP
2.000
[50.80]
2.032
[51.61]
LINE
1.560
[39.62]
LOAD
TAB (Q.C.) TYPE
SCREW TYPE
2.265
[57.53]
MAX
TYP
1.515
[38.48]
MAX
TAB (Q.C.) TYPE TERMINALS
IN SERIES TRIP CONCUIT
CONFIGURATION SHOWN.
FOR OTHER CONFIGURATIONS
SEE CIRCUIT & TERMINAL
DIAGRAMS
4-POLE
(AA4)
.750
[19.05]
TYP
3.015
[76.05]
MAX
LINE
LOAD
POLE
POLE
1
MULTI-POLE INDENTIFICATION SCHEME
AS VIEWED FROM TERMINAL END OF BREAKER.
Notes:
1 Tolerance ± 0.20 [.51] unless otherwise specied.
2 For agency code P = .150 [3.81].
POLE
2
POLE
3
4-POLE
(AB4)
3.015
[76.58]
MAX
[+.25]
.156 DIA [ 3.96]
2 PLCS TYP
PER POLE
1.660
[42.16]
4
1.050
[26.67]
.750
[19.05]
TYP
PER POLE
AA1, AB2, AB3
AA2, AB4
PANEL CUTOUT DETAIL
TOLERANCE +.005[+.12]
+.010
-.000
.630 DIA [ 16.00]
ONE PER POLE
AA3
AA4
__
[-.00]
11.
Page 12
1.640
1.560
TIE KITSHIPPED BULK
Dimensional Specs
inches [millimeters]
Handle
1 POLE
(AA1)
2 POLE
(AA2)
1.488
[37.80]
2.598
[65.99]
TYP
.744
[18.90]
.125
[3.18]
60
.250
[6.35]
(SHORT HANDLE)
.690
[17.50]
2 POLE
(AB2)
ON
OFF
[41.66]
TYP
[50.80]
[51.61]
1.488
[37.80]
2.000
2.032
[39.62]
TYP
LINE
1.220
[31.00]
TYP
LOAD
.250 TAB (Q.C.) TYPE
SCREW TYPE
2.000
[50.80]
TYP
.010
.770
[19.56]
.012
2.187
[55.55]
TYP
.755
[19.18]
MAX
BREAKER
WIDTH
TAB (Q.C.) TYPE TERMINALS
IN SERIES TRIP CIRCUIT
CONFIGURATION SHOWN.
FOR OTHER CONFIGURATIONS,
SEE CIRCUIT AND TERMINAL
03 DC 50/60Hz, Switch Only
10 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
& 30° bend
8 Screw 10-32 with upturned
lugs & 30° bend
9
Screw 10-32 (Bus Type)
& 30° bend
B
Screw M5 with upturned lugs
9. LEGEND PLATE
0 No legend plate
10. MOUNTING / BARRIERS
MOUNTING STYLE BARRIERS
1 Standard Hex Nut no
A Standard Hex Nut (multipole only) yes
11. AGENCY APPROVAL
C UL Recognized & CSA Accepted
I UL Recognized STD 1077, UL Recognized 1500
& CSA Accepted
Notes:
1 Actuator Code M: Handle location as viewed from front of panel:
2 pole - right pole 3 pole - center pole
2 Switch Only circuits, rated up to 50 amps and 3 poles. Only available when tied to
a protected pole. For .02 to 30 amps, select Current Code 630. For 35 - 50 amps,
select Current Code 650.
3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps
maximum.
4 Consult factory for available Dual Coil options, as special catalog number is
required. With Shunt construction, Dual Coils will trip instantaneously on line volt
age. Dual coils require 30VA minimum power to trip and are rated for intermittent
duty only.
5 Auxiliary Switch available on Series Trip & Switch Only circuits, limited to 30 amps.
On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme
right pole.
6 Voltage coils not rated for continuous duty. Available only with delay codes 10 and
20.
7 Available with Circuit Codes B & D only. VDE Certied to 30 amps. UL Recognized,
CSA Accepted & TUV Certied to 50 amps.
8 UL Recognition and CSA Certication available on one and two pole breakers.
9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings
over 30 amps are only available with Terminal Codes 5, 9, B, F, G, H, M and Q.
10 Terminal Code 1: UL Recognition and CSA Certication up to 30 amps, but not
recommended over 20 amps.
11 Terminal Code L : available up to 30A.
12 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up
to 50 amps, with Circuit Codes A, B and C. Two pole breakers with Terminal Code P(Printed Circuit Board) are available up to 40 amps with Circuit Codes A, B and C.
Congure Complete Part Number > Browse Standard Parts >
9
(Bus Type)
(Bus Type)
C Screw, M4 with upturned lugs
E Screw M4
F Screw M5 with upturned lugs
& 30° bend
G Screw M5 (Bus Type) & 30° bend
H Screw M5 (Bus Type)
L 12 0.250 Q.C./ Solder Lug
M M6 Threaded Stud
P 12 Printed Circuit Board Terminals
Q Push-In Stud
R Screw, M4 with upturned lugs
Two Color Visi-Rocker
C Indicate ON, vertical legend
D Indicate ON, horizontal legend
F Indicate OFF, vertical legend
G Indicate OFF, horizontal legend
H Indicate OFF, no legend
Push-To-Reset, Visi-Rocker
N Indicate OFF, vertical legend
O Indicate OFF, horizontal legend
P Indicate OFF, no legend
Single color
J Vertical legend
K Horizontal legend
L No legend
Push-To-Reset , Single color
R Vertical legend
U Horizontal legend
V No legend
1
ROCKER STYLE DESCRIPTIONS
HORIZONTAL STYLE
INDICATE “ON”
LINE
INDICATE “OFF”
LINE
SINGLE COLOR
CODE “G”, “O”
CODE “k”, “U”
CODE “D”
LINE
VERTICAL STYLE
LINE
INDICATE
COLOR
LOCATION
LINE
LINE
CODE “F”, “N”
CODE “J”, “R”
3. POLES
1 One2 Two3 Three
4. CIRCUIT
A 3 Switch Only (No Coil) G 4 Relay Trip (Voltage)
B Series Trip (Current) H
C Series Trip (Voltage) Voltage Coil
D 4 Shunt Trip (Current) K
E 4 Shunt Trip (Voltage) Voltage Coil
03 DC 50/60Hz, Switch Only
10 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
& 30° bend
8 Screw 10-32 with upturned
lugs & 30° bend
9
Screw 10-32 (Bus Type)
& 30° bend
B
Screw M5 with upturned lugs
11
(Bus Type)
C Screw, M4 with upturned lugs
13
Screw M4 (Bus Type)
E
F Screw M5 with upturned lugs
& 30° bend
G Screw M5 (Bus Type) & 30° bend
H 13 Screw M5 (Bus Type)
L 14 0.250 Q.C./ Solder Lug
M 13 M6 Threaded Stud
P 15 Printed Circuit Board Terminals
Q Push-In Stud
R Screw, M4 with upturned lugs
& 30° Bend
17
S
Push-On 0.110 Tab (Q.C.)
& 30° bend
T Screw, M4 with upturned lugs
9. ACTUATOR COLOR & LEGEND
Actuator or Marking: Marking Color
Visi-Color 12 I-O ON-OFF Dual
White A B 1 Black White
Black C D 2White n/a
Red F G 3White Red
Green H J 4White Green
Blue K L 5White Blue
Yellow M N 6Black Yellow
Gray P Q 7 Black Gray
Orange R S 8 Black Orange
10. MOUNTING / BARRIERS
STANDARD ROCKER BEZEL Threaded Insert, 2 per pole BARRIERS
1 6-32 x 0.195 inches no
A 6-32 X 0.195 inches (multi-pole units only) yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multi-pole units only) yes
ROCKERGUARD & PUSH-TO-RESET BEZEL
Threaded Insert, 2 per pole
3 6-32 x 0.195 inches no
C 6-32 x 0.195 inches (multi-pole units only) yes
4 ISO M3 x 5mm no
D ISO M3 x 5mm (multi-pole units only) yes
FRONT PANEL SNAP-IN BRACKET, 0.744” [18.90mm] wide bezel
8 without Rockerguard (single pole units only) no
H with Rockerguard (single pole units only) no
FRONT PANEL SNAP-IN BRACKET, 0.96” [24.48mm] wide bezel
9 without Rockerguard (single pole units only) no
J with Rockerguard (single pole units only) no
12
Single Color Visi-Rocker
20
11. AGENCY APPROVAL
C UL Recognized & CSA Accepted
D VDE Certied, UL Recognized & CSA Accepted
E TUV Certied, UL Recognized & CSA Accepted
I UL Recognized STD 1077, UL Recognized 1500 (ignition protected),
& CSA Accepted
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all breakers identical except when specifying Auxiliary switch
and/or mixed poles, and have one rocker per breaker.
3 Switch Only circuits, rated up to 50 amps & 3 poles, are available only when tied to a
protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps, select Current Code 630.
For 35 - 50 amps, select Current Code 650.
4 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum.
5 Consult factory for Dual Coil options, as special catalog number is required.
With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils
require 30VA minimum power to trip and are rated for intermittent duty only.
6 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A, are supplied with
standard half shells. 30-50A are supplied with extended boat (B-Style) half shells.
7 On multi-pole breakers, one auxiliary switch is supplied, mounted in the right pole.
8 Separate pole type voltage coils not rated for continuous duty. Available only with
delay codes 10 & 20.
9 Available with Circuit Codes B & D only. VDE Certied to 30 amps. UL Recognized, CSA
Accepted & TUV Certied to 50 amps.
10 Series Trip current ratings: VDE Certication available with single pole breakers with DC
Delay only. UL Recognition & CSA Accepted available in one and two pole breakers.
11 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30
amps are only available with Terminal Codes 5, 9, G, H, M and Q.
12 Terminal Code 1: VDE Certication up to 25 amps and UL Recognition and CSA
Accepted up to 30 amps, but not recommended over 20 amps.
13 Terminal Codes 3, 5 E & H (Bus Type) with VDE, are supplied with Lock Washers;
Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers.
These breakers are only VDE Certied when the washers are used.
14 VDE Cert. available up to 12 amps. UL Rec. & CSA Accepted available up to 30 amps.
15 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to
30 amps with VDE Certication and 50 amps with UL Recognition and CSA Accepted,
with Circuit Codes A, B & C.Two pole breakers with Terminal Code P (Printed Circuit
Board) are available up to 40 amps with UL Recognition and CSA Certication with
Circuit Codes A, B and C.
16 Terminal Code Q not available with VDE.
17 Terminal Code S used on voltage coil circuit constructions only.
18 Color shown is visi and legend with remainder of rocker black.
19 Dual = ON-OFF/I-O legend with actuator. None = no legend on actuator
20 Legend on Push-to-reset bezel/shroud is white with single color actuator codes R, & U.
Legend on Push-to-reset bezel/shroud matches Visi-color of rocker with actuator
codes N & O. Rockerguard available with actuator codes C through L.
Page 17
Sample
Part Number
AF1-B
0-14
-
450
-
131-M
T
Selection
123 4 5 67 89
10 1112
Ordering Scheme
Rocker - UL 489A Listed
17.
1. SERIES
A
2. ACTUATOR
Two Color Visi-Rocker Push-To-Reset, Visi-Rocker
C Indicate ON, vertical legend N Indicate OFF,
D Indicate ON, horizontal legend vertical legend
F Indicate OFF, vertical legend O Indicate OFF, horizontal
G Indicate OFF, horizontal legend legend
Single color Push-To-Reset , Single color
J Vertical legend R Vertical legend
K Horizontal legend U Horizontal legend
F Screw M5 with upturned lugs
G Screw M5 (Bus Type) & 30° bend
H Screw M5 (Bus Type)
M 7 M6 Threaded Stud
P 8 Printed Circuit Board Terminals
Q 9 Push-In Stud
Actuator or Marking: Marking Color
Visi-Color
White B 1 Black White
Black D 2White n/a
Red G 3White Red
Green J 4White Green
Blue L 5White Blue
Yellow N 6Black Yellow
Gray Q 7 Black Gray
Orange S 8 Black Orange
10. MOUNTING / BARRIERS
STANDARD ROCKER BEZEL Threaded Insert, 2 per pole BARRIERS
1 6-32 x 0.195 inches no
A 6-32 X 0.195 inches (multi-pole units only) yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multi-pole units only) yes
ROCKERGUARD & PUSH-TO-RESET BEZEL Threaded Insert, 2 per pole
3 6-32 x 0.195 inches no
C 6-32 x 0.195 inches (multi-pole units only) yes
4 ISO M3 x 5mm no
D ISO M3 x 5mm (multi-pole units only) yes
FRONT PANEL SNAP-IN BRACKET, 0.744” [18.90mm] wide bezel
8 without Rockerguard (single pole units only) no
H with Rockerguard (single pole units only) no
FRONT PANEL SNAP-IN BRACKET, 0.96” [24.48mm] wide bezel
9 without Rockerguard (single pole units only) no
J with Rockerguard (single pole units only) no
10
ON-OFFDual
10
Single Color Visi-Rocker
20
11. MAXIMUM APPLICATION RATING
M 80 DC
12. AGENCY APPROVAL
T UL489A Listed
K UL489A Listed, VDE Certied
J UL489A Listed, TUV Certied
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all breakers identical except when specifying Auxiliary
switch and/or mixed poles, and have one rocker per breaker.
3 Auxiliary Switch breakers with Series Trip circuits: ≤ 30A, are supplied with standard
half shells. 30-50A are supplied with extended boat (B-Style) half shells.
4 VDE Certication available with single pole breakers only. UL489A Listing available
with one and two pole breakers.
5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings
over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q.
6 Terminal Code 1 (Push-On) available up to 25 amps with TUV or VDE Certication
and 30 amps with UL489A Listing, but is not recommended over 20 amps.
7 Terminal Codes 3, 5 and H (Bus Type) with TUV or VDE, are supplied with Lock
Washers, and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock
and Flat Washers. These breakers are only TUV or VDE Certied when the washers
are used.
8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up
to 30 amps with VDE Certication and 50 amps with UL489A Listing.
9 Terminal Code Q not available with VDE certication.
10 Color shown is Visi and Legend with remainder of rocker black. Dual = ON-OFF/I O legend.
11 Legend on Push-to-reset bezel/shroud is white with single color actuator codes R
& U. Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator codes N & O. Rockerguard available with actuator codes C through K
Congure Complete Part Number > Browse Standard Parts >
Page 18
STUD
WITH 30 BEND
CIRCUIT
[5.59]
Circuit & Terminal Diagrams
inches [millimeters]
Rocker
2 TERMINALS
5 TERMINALS
3 TERMINALS
4 TERMINALS
CIRCUIT BREAKER PROFILECIRCUIT SCHEMATIC
ANSI
LINE
MAIN TERMINALS
(SEE TABLE A)
LOAD
1.640
[41.66]
.020
TYP
[.51]
NC
NO
C
[9.91]
1
2
[19.81]
3
4
AUX.
SWITCH
TERMINALS
.205
[5.21]
.390
.780
.390
[9.91]
C
NO
NC
.520
[13.21]
ALARM
SWITCH
TERMINALS
& STD. AUX.
SW. WITH
VDE OR
>30 AMPS
SWITCH ONLY (NO COIL)
LINE
LOAD
SWITCH ONLY (NO COIL)
WITH AUXILIARY SWITCH
LINE
LOAD
LINE
LOAD
LINE
LOAD
RELAY
RELAY
TABLE B
TERMINAL DESCRIPTION
MAIN
SHUNT,RELAY
&
DUAL COIL
AUX. SWITCH*
*AVAILABLE ON SERIES TRIP AND SWITCH ONLY CIRCUITS
WHEN CALLED FOR ON MULTI-POLE UNITS, ONLY ONE AUX.
SWITCH IS NORMALLY SUPPLIED, AS SHOWN IN MULTI-POLE
INDENTIFICATION SHEME.
TAB (Q.C.) TYPE TERMINALS
IN SERIES TRIP CONCUIT
CONFIGURATION SHOWN>
FOR OTHER CONFIGURATIONS
SEE CIRCUIT & TERMINAL
DIAGRAMS
LINE
Rocker
INDICATE “OFF” & SINGLE COLOR
(INDICATE “OFF” SHOWN)
OPTIONAL
“ROCKER GUARD”
LOAD
LINE
.432
[10.97]
CENTER-LINE
OF ROCKER,&
PANEL CUT-OUT
OPTIONAL “PUSH-TO RESET”
ACTUATOR
AF1
LOAD
.945
[24.00]
2.309
[58.65]
1.660
[42.16]
TYP
AC2
[38.48]
AC3
2.265
[57.53]
MAX
1.515
MAX
LOAD
OPTIONAL “ROCKER
GUARD” SHOWN IN
DASHED LINES
.220
[5.59]
TYP
LINE
1.660
[42.16]
TYP
LOAD
.750
[19.05]
TYP
P(1) P(2) P(3)
(SEE NOTE 2)
REAR VIEW OF INDICATE “ON”
SERIES TRIP W/AUX SWITCH
PANEL CUT-OUT
DETAIL
_
+ .005
1.260
[32.00]
_
[+ .13]
.200
[5.08]
LINE
LOAD
+ .005
_[+ .25]
-.000
_[+ .00]
.750
[19.05]
1.660
[42.16]
_
+ .005
.156 DIA[ 3.96]
2 HOLES
LINE
AF2
.055x.205
SLOTTED
HOLE
(ROCKER OFF
ACTUATION)
ROCKER
SHROUDED ON
“OFF” POSITION
SIDE, SHOWN IN
DASHED LINES
[11.81]
[25.65].465
1.010
LOAD
_
[+ .13]
LINE
AF3
P(1) P(2) P(3)
(SEE NOTE 2)
REAR VIEW OF INDICATE “OFF”
SERIES TRIP W/AUX SWITCH
19.
Notes:
1 Dimensions apply to all variations shown. Notice that circuit breaker line & load
terminal orientation on indicate OFF is opposite of indicate ON.
2 For pole orientation with horizontal legend, rotate front view clockwise 90°.
3 Tolerance ± 0.20 [.51] unless otherwise specied.
Page 20
INDICATE “ON”
PANEL CUTOUT DETAIL
Dimensional Specs
inches [millimeters]
Rocker Snap-In Bracket
FRONT PANEL SNAP-IN BRACKET , 0.96”[24.48 mm] wide bezel
AC1
ROCKER ADAPTER
BREAKER WIDTH
[65.99]
.960
[24.38]
MAX
2.598
.410
[10.41]
.320
[8.13]
.125
[3.18]
1.640
[41.66]
2.370
[58.93]
TAB TYPE
2.352
[59.74]
SCREW TYPE
FRONT PANEL SNAP-IN BRACKET , 0.744”[18.90 mm] wide bezel
AC1
2.598
[65.99]
.744
[18.90]
MAX
ROCKER ADAPTER
BREAKER WIDTH
FRONT PANEL SNAP-IN BRACKET , 0.96 ”[24.48 mm] wide bezel
.755
[19.18]
MAX
ROCKER ADAPTER
BREAKER WIDTH
LOAD
2.000
[50.80]
1.560
[39.62]
1.640
[41.66]
1.560
[39.62]
[50.80]
INDICATE “OFF”
.320
[8.13]
.755
[19.18]
MAX
BREAKER WIDTH
LINE
2.000
LOAD
TAB (Q.C.) TYPE TERMINALS
IN SERIES TRIP CONCUIT
CONFIGURATION SHOWN.
FOR OTHER CONFIGURATIONS
SEE CIRCUIT & TERMINAL
DIAGRAMS
2.98
[65.99]
AF1
.483
[12.27]
.125
[3.18]
.320
[8.13]
OPTIONAL”ROCKER GUARD”
SHOWN IN DASHED LINES
.483
[12.27]
.125
[3.18]
20.
LINE
.125
[3.18]
.410
[10.41]
FRONT PANEL SNAP-IN BRACKET , 0.744 ”[18.90 mm] wide bezel
LOAD
LINE
Notes:
1 Dimensions apply to all variations shown. Notice that circuit breaker line & load terminal
2 For pole orientation with horizontal legend, rotate front view clockwise 90°.
Orientation on indicate “OFF” is opposite of indicate “ON”
3 Recommended panel thickness: .04 0 [1.02] to .100 [2.54]
4 Tolerance ±.020 [.51] unless otherwise specied.
Two Color Visi-Rocker
1 Indicate OFF, vertical legend
2 Indicate OFF, horizontal legend
Single color
3 Vertical legend
4 Horizontal legend
Push-To-Reset, Visi-Rocker
5 Indicate OFF, vertical legend
6 Indicate OFF, horizontal legend
Push-To-Reset , Single color
7 Vertical legend
8 Horizontal legend
3. POLES
1 One2 Two3 Three
4. CIRCUIT
A 3 Switch Only (No Coil) G 4 Relay Trip (Voltage)
B Series Trip (Current) H
C Series Trip (Voltage) Voltage Coil
D 4 Shunt Trip (Current) K
E 4 Shunt Trip (Voltage) Voltage Coil
F 4 Relay Trip (Current)
03 DC 50/60Hz, Switch Only
10 6 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 6 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
30 DC, 50/60Hz Instantaneous
& 30° bend
8 Screw 10-32 with upturned
lugs & 30° bend
9
Screw 10-32 (Bus Type)
& 30° bend
B
Screw M5 with upturned lugs
11
(Bus Type)
C Screw, M4 with upturned lugs
13
Screw M4 (Bus Type)
E
F Screw M5 with upturned lugs
& 30° bend
G Screw M5 (Bus Type) & 30° bend
H 13 Screw M5 (Bus Type)
L 14 0.250 Q.C./ Solder Lug
M 13 M6 Threaded Stud
P 15 Printed Circuit Board Terminals
Q Push-In Stud
R Screw, M4 with upturned lugs
& 30° Bend
16
S
Push-On 0.110 Tab (Q.C.)
& 30° bend
T Screw, M4 with upturned lugs
9. ACTUATOR COLOR & LEGEND
Actuator or Marking: Marking Color
Visi-Color
White B 1 Black White
Black D 2White n/a
Red G 3White Red
Green J 4White Green
Blue L 5White Blue
Yellow N 6Black Yellow
Gray Q 7 Black Gray
Orange S 8 Black Orange
10. MOUNTING / BARRIERS
STANDARD ROCKER BEZEL Threaded Insert, 2 per pole BARRIERS
FLAT ROCKER ACTUATOR
1 6-32 x 0.195 inches no
A 6-32 X 0.195 inches (multi-pole units only) yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multi-pole units only) yes
RECESSED OFF SIDE ROCKER ACTUATOR
5 6-32 x 0.195 inches no
E 6-32 x 0.195 inches (multi-pole units only)yes
6 ISO M3 x 5mm no
F ISO M3 x 5mm (multi-pole units only) yes
PUSH-TO-RESET BEZEL,Threaded Insert, 2 per pole
3 6-32 x 0.195 inches no
C 6-32 x 0.195 inches (multi-pole units only) yes
4 ISO M3 x 5mm no
D ISO M3 x 5mm (multi-pole units only) yes
17
ON-OFFDual
17
Single Color Visi-Rocker
18
19
11. AGENCY APPROVAL
C UL Recognized & CSA Accepted
E TUV Certied, UL Recognized & CSA Accepted
I UL Recognized STD 1077, UL Recognized 1500
& CSA Accepted
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all breakers identical except when specifying Auxiliary
switch and/or mixed poles, and have one rocker per breaker.
3 Switch Only circuits, rated up to 50 amps & 3 poles. Only available when tied to a
protected pole. For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select
Current Code 650.
4 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum.
5 Consult factory for Dual Coil options, as special catalog number is required. With
Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils
require 30VA minimum power to trip and are rated for intermittent duty only.
6 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A, are supplied
with standard half shells. 30-50A are supplied with extended boat (B-Style) half shells.
7 On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right
pole.
8 Separate pole type voltage coils not rated for continuous duty. Available only with
delay codes 10 & 20.
9 Available with Circuit Codes B & D only. UL Recognized, CSA Accepted & TUV Certied
to 50 amps.
10 UL Recognition, CSA Acceptance & TUV Certication available in one and two pole
breakers.
11 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over
30 amps are only available with Terminal Codes 5, 9, G, H, M and Q.
12 Terminal Code 1: Available up to 30 amps, but not recommended over 20 amps.
13 Terminal Codes 3, 5 E & H (Bus Type) with TUV, are supplied with Lock Washers;
Terminal Code M (M6 Threaded Stud) with TUV is supplied with Lock and Flat Washers.
These breakers are only TUV Certied when the washers are used.
14 TUV Cert. available up to 12 amps. UL Rec. & CSA Accepted available up to 30 amps.
15 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to
50 amps with UL Recognition, CSA Accepted & TUV Certication, with Circuit Codes
A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board) are avail
able up to 40 amps with UL Recognition and CSA Accepted with Circuit Codes A, B & C.
16 Terminal Code S used on voltage coil circuit constructions only.
17 Color shown is visi & legend with remainder of rocker black, Dual = ON-OFF/I-O legend.
18 Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 &
8. Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator
codes 5 & 6.
19 Recessed “off-side” available with actuator codes 1, 2, 3 & 4. Legends on rocker are
available in ink stamping only.
(ignition protected),
Page 23
Sample
Part Number
A11-B
0-14
-
630
-
231-M
T
Selection
123 4 5 67 89
10 1112
Ordering Scheme
ROCKER STYLE DESCRIPTIONS
HORIZONTAL
VERTICAL
Flat Rocker - UL 489A Listed
1. SERIES
A
2. ACTUATOR
Two Color Visi-Rocker
1 Indicate OFF, vertical legend
2 Indicate OFF, horizontal legend
Single color
3 Vertical legend
4 Horizontal legend
Push-To-Reset, Visi-Rocker
5 Indicate OFF, vertical legend
6 Indicate OFF, horizontal legend
Push-To-Reset , Single color
7 Vertical legend
8 Horizontal legend
Actuator or Marking: Marking Color
Visi-Color
White B 1 Black White
Black D 2White n/a
Red G 3White Red
Green J 4White Green
Blue L 5White Blue
Yellow N 6Black Yellow
Gray Q 7 Black Gray
Orange S 8 Black Orange
10. MOUNTING / BARRIERS
STANDARD ROCKER BEZEL BARRIERSThreaded Insert, 2 per pole
FLAT ROCKER ACTUATOR
1 6-32 x 0.195 inches no
A 6-32 X 0.195 inches (multi-pole units only) yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multi-pole units only) yes
RECESSED OFF SIDE ROCKER ACTUATOR
5 6-32 x 0.195 inches no
E 6-32 x 0.195 inches (multi-pole units only) yes
6 ISO M3 x 5mm no
F ISO M3 x 5mm (multi-pole units only) yes
PUSH-TO-RESET BEZEL,Threaded Insert, 2 per pole
3 6-32 x 0.195 inches no
C 6-32 x 0.195 inches (multi-pole units only) yes
4 ISO M3 x 5mm no
D ISO M3 x 5mm (multi-pole units only) yes
11
ON-OFFDual
11
Single Color Visi-Rocker
12
11. MAXIMUM APPLICATION RATING
M 80 DC
12.AGENCY APPROVAL
T UL489A Listed
J UL489A Listed, TUV Certied
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all breakers identical except when specifying Auxiliary
switch and/or mixed poles, and have one rocker per breaker.
3 Auxiliary Switch breakers with Series Trip circuits: ≤ 30A, are supplied with
standard half shells. 30-50A are supplied with extended boat (B-Style) half shells.
4 VDE Certication available with single pole breakers only. UL489A Listing avail
able with one and two pole breakers.
5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings
over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q.
6 Terminal Code 1 (Push-On) available up to 25 amps with TUV or VDE Certication
and 30 amps with UL489A Listing, but is not recommended over 20 amps.
7 Terminal Codes 3, 5 and H (Bus Type) with TUV or VDE, are supplied with Lock
Washers, and Terminal Code M (M6 Threaded Stud) with VDE is supplied with
Lock and Flat Washers. These breakers are only TUV or VDE Certied when the
washers are used.
8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available
up to 30 amps with VDE Certication and 50 amps with UL489A Listing.
9 Terminal Code Q not available with VDE certication.
10 Color shown is Visi and Legend with remainder of rocker black. Dual = ON-OFF/I O legend.
11 Legend on Push-to-reset bezel/shroud is white with single color actuator codes
R & U.
12 Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actua tor codes N & O. Rockerguard available with actuator codes C through K
Congure Complete Part Number > Browse Standard Parts >
8. TERMINAL
2
Screw 8-32 with upturned
lugs
3 7 Screw 8-32 (Bus Type)
4
Screw 10-32 with upturned
lugs
5 7 Screw 10-32 (Bus Type)
6
Screw 8-32 with upturned
lugs & 30° bend
23.
8 Screw 10-32 with upturned
lugs & 30° bend
11
9
Screw 10-32 (Bus Type)
& 30° bend
B
Screw M5 with upturned lugs
F Screw M5 with upturned lugs
G Screw M5 (Bus Type) & 30° bend
H Screw M5 (Bus Type)
M 7 M6 Threaded Stud
P 8 Printed Circuit Board Terminals
Q 9 Push-In Stud
Page 24
INDICATE “OFF” & SINGLE COLOR
ROCKER
Dimensional Specs
inches [millimeters]
(INDICATE “OFF” SHOWN)
2.402
[61.01]
SCREW TYPE
2.370
[60.20]
TAB TYPE
1.640
[41.66]
.755
[19.18]
MAX
BREAKER WIDTH
A11
LOAD
2.000
[50.80]
1.560
[39.62]
LINE
Flat Rocker
.370
[9.40]
REF
1.245
[31.62]
.208
[5.27]
#6-32 [M3] THREAD
X.195[4.95]DEEP
2 PLCS
1.010
[25.65]
1.660
[42.16]
2.309
[58.65]
TAB (Q.C.) TYPE TERMINALS
IN SERIES TRIP CONCUIT
CONFIGURATION SHOWN.
FOR OTHER CONFIGURATIONS
SEE CIRCUIT & TERMINAL
DIAGRAMS
A12
1.660
[42.16]
TYP
.750
[19.05]
TYP
1.515
[38.48]
MAX
A13
LOAD
LINE
.220
[5.59]
TYP
1.660
[42.16]
.120
[3.05]
CENTER-LINEOF ROCKER
&PANEL CUT-OUT
PANEL CUT-OUT
DETAIL
_
+ .005
1.260
[32.00]
_
[+ .13]
.200
[5.08]
LOAD
LINE
.397
[10.08]
+ .005
_[+ .25]
-.000
_[+ .00]
.750
[19.05]
1.660
[42.16]
_
+ .005
.156 DIA[ 3.96]
2 HOLES
1.245
[31.62]
.745
[18.92]
MAX
ROCKER ADAPTER
BRACKET WIDTH
_
[+ .13]
SIDE VIEW OF BREAKER IN THE
“ON” POSITION
PUSH-TO-RESET
ACTUATOR
A51
LOAD
.515
[13.08]
2.309
[58.65]
24.
P(1) P(2) P(3)
2.265
[57.53]
MAX
Notes:
1 For pole orientation with horizontal legend, rotate front view clockwise 90°.
2 Tolerance ± 0.20 [.51] unless otherwise specied.
(SEE NOTE 2)
REAR VIEW OF INDICATE “OFF”
SERIES TRIP W/AUX SWITCH
CIRCUIT CONFIGURATION
.055x.205
SLOTTED HOLE
(ROCKER OFF ACTUATION)
ACTUATOR SIDE VIEW
(SURFACE CONTOURS)
FLAT ROCKER
LINE
ROCKER SHROUDED ON “OFF”
POSITION SIDE, SHOWN IN
DASHED LINES
RECESSED OFF SIDE
1.010
[25.65]
Page 25
Sample
Part Number
AY1-B
0-14
-
630
-
231-M
T
Selection
123 4 5 67 89
10 1112
Ordering Scheme
Recessed Paddle
1. SERIES
A
2. ACTUATOR
Y Single Color Recessed Paddle Actuator with Vertical Legends
3. POLES
1 One2 Two3 Three
1
2
4. CIRCUIT
A Switch-Only (No Coil) F Relay Trip (Current)
B Series Trip (Current) G Relay Trip (Voltage)
C Series Trip (Voltage) H Dual Coil with Shunt Trip Voltage Coil
D Shunt Trip (Current) K Dual Coil with Shunt Trip Current Coil
E Shunt Trip (Voltage)
5. AUXILIARY SWITCH
0 without Aux Switch
1 S.P.D.T. with 0.093 Q.C. Terminals
2 S.P.D.T. with 0.110 Q.C. Terminals
3 S.P.D.T. with 0.139 Solder Lug Terminals
5 S.P.D.T. with 0.093 Q.C. Terminals (Gold Contacts)
6 S.P.S.T.-N.O. with 0.139 Solder Lug Terminals
7 S.P.S.T.-N.O. with 0.110 Q.C. Terminals (Gold Contacts)
8 S.P.S.T.-N.O. with 0.187 Q.C. Terminals
9 S.P.D.T. with 0.187 Q.C. Terminals
6. FREQUENCY & DELAY
3 DC, 50/60 Hz Switch Only
10 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 50/60 Hz Instantaneous
21 50/60 Hz Ultra Short
22 50/60 Hz Short
& 30° bend
8 Screw 10-32 with upturned
lugs & 30° bend
9
Screw 10-32 (Bus Type)
& 30° bend
(Bus Type)
9. ACTUATOR COLOR & LEGEND
Actuator Color I-O ON-OFF Dual Legend Color
White A B 1 Black
Black C D 2White
Red F G 3White
Green H J 4White
Blue K L 5White
Yellow M N 6 Black
Gray P Q 7 Black
Orange R S 8 Black
B
Screw M5 with upturned lugs
C Screw, M4 with upturned lugs
F Screw M5 with upturned lugs
G Screw M5 (Bus Type) & 30° bend
H Screw M5 (Bus Type)
M M6 Threaded Stud
P Printed Circuit Board Terminals
Q Push-In Stud
R Screw, M4 with upturned lugs
& 30° Bend
S Screw, M5 with upturned lugs
T Screw, M4 with upturned lugs
5
10. MOUNTING / BARRIERS
BARRIERS
1 6-32 x 0.195 inches no
A 6-32 X 0.195 inches (multi-pole units only) yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multi-pole units only) yes
11. MAXIMUM APPLICATION RATING
A 65 VDC
C 120/240 VAC (Available only on 2 or 3-Pole units)
K 120 VAC
M 80 DC
12.AGENCY APPROVAL
A Without Approvals
C UL Recognized and CSA Accepted
T UL 489A
Notes:
1 A l l s t an d ar d c a ta l og nu m be rs ar e s u p pl ie d w i t h V e r ti c al Le ge n ds . F o r H or i zo n ta l
or other non-standard legends, choose “X” and order as a special catalog
number.
2 For rating (T) 2 & 3 Pole not available.
3 Frequency and Time Delay ratings of (03, 20, 21, 22, 24, 26, 42, 44, 46) not
available with approval T.
4 Voltage Coil Ratings starting with (J, K, or L) not available with approval T.
5 “ O FF an d/ o r “ O ” L e ge n ds a r e o n B r a c k et an d a re on ly vi si b le w h e n th e P a dd l e
Actuator is in the off position.
6 Maximum Application Ratings (C & K) not available with approval T.7 Not all approvals are available in all constructions. Consult factory for details.
Congure Complete Part Number > Browse Standard Parts >
Click on a region of the map below to nd your local representatives and distributors
or visit www.carlingtech.com/ndarep.
CANADA
USA
MEXICO
SOUTH
AMERICA
EUROPE
AFRICA
MIDDLE
EAST
ASIA-PACIFIC
OCEANIA
27.
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and
electronic switches and assemblies, circuit breakers, electronic controls, power
distribution units, and multiplexed power distribution systems. With six ISO9001 and
IATF16949 registered manufacturing facilities and technical sales ofces worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than
manufacture electrical components, they engineer powerful solutions! To learn more
about Carling please visit www.carlingtech.com/company-prole.
To view all of Carling’s environmental, quality, health & safety certications please visit