Datasheet AB2-B1-11-430-BJB-C, AB2-B1-11-450-BJB-C Specification

Page 1
NOW PART OF
A-Series
Hydraulic-Magnetic Circuit Breaker
PRODUCT WEBPAGE
request sample, congure part
Typical Applications
Marine ∙ Telecom
Renewable Energy ∙ Generators
∙ Welders Military
Compact and Versatile Design
The A-Series hydraulic-magnetic circuit breakers offer precise operation in a compact size for both general purpose as well as full amp load applications. Visi Rocker® and recessed paddle actuators are ideally suited for clean, front panel designs while the metal toggle conguration is ideal for harsh environments. The A-Series is available as a one to six pole conguration, rated up to 50 amps, 277VAC/80VDC and has a max IC of 7,500 amps.
1-6 80 7500A
Poles VDC Max Max ICVAC Max
50
Amps Max
Industrial Automation Commercial Food
277
Medical Equipment
www.carlingtech.com 860.793.9281 sales@carlingtech.com
Page 2
RESISTANCE, IMPEDANCE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
Multiple of
60 Hz 1/2 Cycle
Multiple of
Rated Current
Multiple of
Time in Milliseconds
Inrush Pulse Tolerance
50 Hz 1/2 Cycle
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
Time Delay Curves
22, 24 & 26
(50 Amps Max.)
Tech Specs
Electrical
Maximum Voltage
277VAC 50/60 Hz, 80VDC
- consult ordering scheme.
scheme.
0.1A - 125VAC (with gold contacts)
VDC
and VDE 0805.
Breaker.
Mechanical
Voltage.
position.
is electrically tripped
Physical
2 poles at 31 Amps thru 50 Amps.
auxiliary switch.
(Approximately 2.32 ounces/pole)
Ordering Scheme.
Environmental
specication MIL-PRF-55629 & MIL-STD-202 as follows:
current.
90% of rated current.
days @ +85°C, 85% RH.
RH @ 5% NaCl Solution, 96 hrs).
to +25°C).
Current Ratings Standard current coils: 0.100,
0.250, 0.500, 0.750, 1.00, 2.50, 5.00,
7.50, 10.0, 15.0, 20.0, 25.0, 30.0, 35.0,
40.0, 50.0. Other ratings available
Standard Voltage Coils DC-6V, 12V; AC-120V, Other ratings
available, consult ordering
Auxiliary Switch Rating SPDT; 10.1 A - 250VAC,
1.0 A-65VDC/0.5 A - 80 VDC,
Insulation Resistance Minimum: 100 Megohms at 500
Dielectric Strength UL, CSA - 1500V 60 Hz for one
minute between all electrically isolated terminals. A-Series rocker circuit breakers comply with the 8mm spacing & 3750V dielectric requirements from hazardous voltage to operator accessible surfaces per EN 60950
Resistance, Impedance Values from Line to Load Terminal
based on Series Trip Circuit
RESISTANCE PER POLE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
1000
100
10
O
1
H M
S
0.1
CURRENT
(AMPS)
TOLERANCE
(%)
0.10 - 5.0 15
5.1 - 20.0 25
20.1 - 50.0 35
Endurance 10,000 ON-OFF operations @ 6
per minute; with rated Current &
Trip Free All A-Series Circuit Breakers will
trip on overload, even when the actuator is forcibly held in the ON
Trip Indication The operating actuator moves
positively to the OFF position when an overload causes the circuit breaker to trip. When mid-trip handle is specied, the handle moves to the mid position on electrical trip of the circuit breaker. When mid-trip handle with alarm switch is specied, the handle moves to the mid position & the alarm switch actuates when the circuit breaker
Number of Poles 1 - 6 Poles (handle) and 1-3 poles
(rocker) at 30 Amps or less.1 and
Internal Circuit Cong. Series, (with or without auxiliary
switch), Shunt and Relay with current or voltage trip coils, Dual Coil, Switch Only with or without
Weight Approximately 65 grams/pole.
Standard Colors Housing - Black; Actuator- See
Designed and tested in accordance with requirements of
0.01
0.001
0.01
0.1
AMPERE RATING
02.
Pulse Tolerance Curves
Rated Current
*Manufacturer reserves the right to change product specication without prior notice.
Inrush Pulse Tolerance
60 Hz 1/2 Cycle
Time Delay Curves
(50 Amps Max.)
Time Delay Curves
(50 Amps Max.)
1
42, 44 & 46
22, 24 & 26
10
Time in Milliseconds
100
22x
10x
Rated Current
Inrush Pulse Tolerance
10.0
5.0
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
Time Delay Curves
22, 24 & 26
(50 Amps Max.)
20.0
Time in Milliseconds
Shock Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per Method 213, Test Condition “I”. Instantaneous and ultra-short curves tested @ 90% of rated
Vibration Withstands 0.060” excursion from
10-55 Hz, and 10 Gs 55-500 Hz, at rated current per Method 204C, Test Condition A. Instantaneous and ultrashort curves tested at
Moisture Resistance Method 106D; ten 24-hour cycles
@ + 25°C to +65°C, 80-98% RH.56
Salt Spray Method 101, Condition A (90-95%
Thermal Shock Method 107D, Condition A (Five
cycles @ -55°C to +25°C to +85°C
Operating Temperature -40° C to +85° C
Page 3
Tech Specs
Electrical Tables
Table A: Lists UL Recognized & CSA Accepted congurations and performance capabilities as a
Component Supplementary Protector.
Component Supplementary Protectors
Circuit
Conguration
Series
Dual Coil
Shunt
Relay
Switch Only
Voltage Current Rating Short Circuit Capacity
Max
Rating
125 / 250 50 / 60 1 30.02 - 30 --- --- 3000 TC1, 2, OL1, U2 TC1, 2, OL1, U2 Rocker 125 / 250 50 / 60 1 30.02 - 50 --- --- 3000 TC1, 2, OL1, U2 TC1, 2, OL1, U2 Handle
125 / 250 50 / 60 1 30.02 - 30 --- --- 3000 TC1, 2, OL1, U1 TC1, 2, OL1, U1 Rocker 125 / 250 50 / 60 1 30.02 - 50 --- --- 3000 TC1, 2, OL1, U2 TC1, 2, OL1, U2
125 / 250 50 / 60 1 0.02 - 30 --- --- 3000 TC1, 2, OL1, U1 TC1, 2, OL1, U1
125 / 250 50 / 60 1 30.02 - 30 --- --- 3000 TC1, 2, OL1, U1 TC1, 2, OL1, U1
Frequency Phase
32 DC --- 0.02 - 15 --- --- 5000 TC1, OL1, U2 TC1, OL1, U2
65 DC --- 31 - 50 --- --- 7500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
80 DC ---
125 50 / 60 1 0.02 - 30 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Rocker 125 50 / 60 1 1 - 50 --- --- 2000 TC1, OL1, U2 TC1, OL1, U2 125 50 / 60 1
250 50 / 60
277 50 / 60 1 0.02 - 30 --- 5000
32 DC --- 0.02 - 50 --- --- 5000 TC1, OL1, U2 TC1, OL1, U2
65 DC --- 0.02 - 50 --- --- 7500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
80 DC ---
125 50 / 60 1
125 50 / 60 1 40.02 - 30 --- --- 1000 TC1, OL1, U2 TC3, OL1, U3
250 50 / 60
277 50 / 60 1 0.02 - 30 --- 5000
80 DC --- 0.02 - 30 --- --- 7500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
250 50 / 60
277 50 / 60 1 0.02 - 30 --- 5000
80 DC --- 0.02 - 30 --- --- 7500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
250 50 / 60
277 50 / 60 1 0.02 - 30 --- 5000
65 DC --- 0.02 - 50 --­80 DC --- 0.02 - 30 ---
250 50 / 60
277 50 / 60 1 0.02 - 30 31 - 50
Full Load
Amps
0.02 - 30 --- --- 7500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
4
1 - 50 --- --- 1000 TC1, OL1, U2 TC3, OL1, U3
0.02 - 30 --- --- 1500 TC1, 2, OL0, U2 TC1, 2, OL0, U2 Single Pole
1
0.02 - 30 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Two Pole
4
1
1 - 50 --- --- 1000 TC1, OL1, U2 TC3, OL1, U3
0.02 - 30 --- 5000
3
31 - 50 --- 2000
0.02 - 30 --- --- 7500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
0.02 - 30 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Rocker 1 - 50 --- --- 2000 TC1, OL1, U2 TC1, OL1, U2
1 0.02 - 30 --- --- 1500 TC1, OL0, U2 TC1, OL0, U2 Single Pole 1 0.02 - 30 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Two Pole 1 --- 31 - 50 --- 3000 TC1, 2, OL0, U1 TC1, 2, OL0, U1
4
1
1 - 50 --- --- 1000 TC1, OL1, U2 TC3, OL1, U3
0.02 - 30 --- 5000
3
31 - 50 --- 2000
1 0.02 - 30 --- --- 3000 TC1, 2, OL1, U1 TC1, 2, OL1, U1
3 0.02 - 30 --- 5000
1 0.02 - 30 --- --- 3000 TC1, 2, OL1, U1 TC1, 2, OL1, U1
3 0.02 - 30
1 --- 31 - 50
3 0.02 - 50 ---
General Purpose
Amps
--- 31 - 50 --- 7500 TC1, 2, OL0, U1 TC1, 2, OL0, U1
--- --- 3000 TC1, 2, OL0, U1 TC1, 2, OL0, U1
--- 31 - 50 --- 7500 TC1, 2, OL0, U1 TC1, 2, OL0, U1
Backup Fuse
--- 5000
UL / CSA
With
2
1 1
2
1 1
2
1
2
1
(Amps)
Without
Backup Fuse
--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
--- TC1, 2, OL1, U1 TC1, 2, OL1, U1
--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
not applicable
Application Codes
UL CSA
Notes
03.
Notes: 1 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector. 2 Same as note 1, except that backup fuse is limited to 80 A maximum. 3 2 pole protector required (with one pole per power line) for: 125/250 VAC, 1 pole protector required for : 125 VAC, 1Ø Power System.
4 Satises the requirements of clause 11.2.8.2.5 of CSA STD C22.2 No 100 for the use of supplementary protectors with portable generators.
Page 4
Tech Specs
Electrical Tables
Table B: Lists UL Recognized, CSA Accepted, VDE & TUV Certied congurations & performance capabilities as a
Component Supplementary Protector.
Component Supplementary Protectors
Voltage Current Rating Short Circuit Capacity (Amps)
Circuit
Conguration
Series
Dual Coil
Shunt
Notes: 1 General Purpose Ratings for UL/CSA Only. 2 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector. 3 Same as note 2, except that backup fuse is limited to 80 A maximum.
4 Satises the requirements of clause 11.2.8.2.5 of CSA STD C22.2 No 100 for the use of supplementary protectors with portable generators.
Max
Frequency Phase
Rating
65 DC --- 0.10 - 50
80 DC ---
1
250 50 / 60
80 DC --- 0.10 - 30
250 50 / 60
80 DC ---
250 50 / 60
1 0.10 - 30 TC1, OL1, U2 TC1, OL1, U2
4
1
3
1
3
1 3000 5000
3
General
Full Load
Purpose
Amps
Amps
0.10 - 30 31 - 50 31 - 50 TC1, 2, OL0, U1 TC1, 2, OL0, U1
0.10 - 30 31 - 32 TC1, 2, OL1, U1 TC1, 2, OL1, U1 Rocker: 2 Pole 31 - 50 31 - 50 TC1, 2, OL0, U1 TC1, 2, OL0, U1 Rocker: 1 Pole
0.10 - 30 --­31 - 50 31 - 50 --- --- TC1, 2, OL0, U1 TC1, 2, OL0, U1 31 - 32
1 - 50 1000 --- --- TC1, OL1, U2 TC3, OL1, U3
0.10 - 30 5000 31 - 50 2000
0.10 - 30
30 - 50 31 - 50 --- --- TC1, 2, OL0, U1 TC1, 2, OL0, U1
0.10 - 30 31 - 50 2000
0.10 - 30 ---
30 - 50 31 - 50 --- --- TC1, 2, OL0, U1 TC1, 2, OL0, U1
0.10 - 30
31 - 50 2000
---
---
---
---
---
---
UL / CSA VDE TUV
With
Backup
Fuse
--- 7500
---
3
2
---
3
5000
2
---
3
5000
2
Without
(Inc) with
Backup
Backup
Fuse
Fuse
3000 1500 3000
3000 1500
3000
6000 1500
--- 3000 1500 3000
7500
3000 1500
3000 5000
3000 1500
---
7500
3000 1500
3000 1500
---
(Icn)
without
Backup
Fuse
--- --- 5000 3000 TC1, 2, OL1, U1 TC1, 2, OL1, U1
--- --- TC1, 2, OL1, C1 TC1, 2, OL1, C1
--- --- TC1, 2, OL1, C1 TC1, 2, OL1, C1
(Inc)
with
Backup
Fuse
5000
3000
3000
3000
3000
(Icn)
without
Backup
Fuse
1500
1500
1500
Application Codes
UL CSA
TC1, 2, OL1, U1 TC1, 2, OL1, U1
TC1, 2, OL1, U1 TC1, 2, OL1, U1 Rocker: 1-3 Poles
TC1, 2, OL1, U1 TC1, 2, OL1, U1
TC1, 2, OL1, U1 TC1, 2, OL1, U1
TC1, 2, OL1, C1 TC1, 2, OL1, C1 TC1, 2, OL1, C1 TC1, 2, OL1, C1 TC1, 2, OL1, U1 TC1, 2, OL1, U1 TC1, 2, OL1, U1 TC1, 2, OL1, U1
TC1, 2, OL1, C1 TC1, 2, OL1, C1
TC1, 2, OL1, U1 TC1, 2, OL1, U1 Handle: 1 Pole TC1, 2, OL1, U1 TC1, 2, OL1, U1 TC1, 2, OL1, U1 TC1, 2, OL1, U1
TC1, 2, OL1, C1 TC1, 2, OL1, C1
Notes
World Market
Breaker TUV only
Handle: 1 Pole
Rocker: 1-3 Poles
Rocker: 2 Pole
Rocker: 1-3 Poles
Rocker: 1-3 Poles
Rocker: 1-3 Poles
04.
Page 5
Tech Specs
Agency Approvals
(Guide CCN/QVNU2, File E75596)
(Guide CCN/NRNT2, File E148683)
Protection
(Guide CCN/DITT, File E189195)
Standard C22.2 No. 235
R72103448
No. 10537
Electrical Tables
Table C: Lists UL Recognized, CSA Accepted congurations and performance capabilities as Protectors,
Supplementary for Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classied Small Craft Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
UL1500 (Marine Ignition Protection)
Circuit
Conguration
Rating
Series
125 / 250 1
1 Notes: 2 Available with special catalog number only (consult factory). 3 2 pole protector required (with one per power line) for 125 / 250 VAC. 1 pole protector required for 125 VAC 1 phase power system
Voltage
Max
Frequency Phase
1
14
1
32
65
125
250 1 0.02 - 30 1500 TC1, OL1, U1 TC1, OL1, U1
DC ---
50 / 60
Current
Rating
Full Load
Amps
0.02 - 50
1 TC1, OL1, U2 TC1, OL1, U2
2
Table D: Lists UL Listed congurations and performance capabilities as Circuit Breakers for use in
Communications Equipment
Short Circuit
Capacity
(Amps)
Without
Backup Fuse
5000
3000
Application Codes
UL CSA
TC1, OL1, U1 TC1, OL1, U1
TC1, OL1, U2 TC1, OL1, U2
TC1, OL1, U1 TC1, OL1, U1
TC1, OL1, U2 TC1, OL1, U2
UL489A (Communications Equipment)
Circuit
Conguration
Series 80 DC
Notes: 1 Parallel Pole Construction
Voltage Current Rating Interrupting Capacity (Amps)
Max Rating Frequency General Purpose Amps without Backup Fuse
0.10 - 50 60 - 90
1
5000
Time Delay Specs
To view all hydraulic-magnetic circuit breaker time delay values, please visit www.carlingtech.com/sites/default/les/documents/Carling-HM-CB-Time-Delays.pdf
UL 1077 Component Recognition Program
UL 508 Switches, Industrial Control
UL 1500 Protectors, Supplementary for
as Protectors Supplementary
Marine Electrical & Fuel Systems (Guide PEQZ2, File E75596) Ignition
UL 489A Communications Equipment
CSA Certied Component Supplementary
TUV Certied EN60934, under License No.
VDE Certied EN60934, VDE 0642 under File
05.
Protector under Class 3215 30, File 047848 0 000 CSA
Page 6
Sample
Part Number
A
A
3-B
0-10
-
450
-
1B1-C
Selection
123 4 567 8 9
10
11
Ordering Scheme
Handle - UL 1077 Recognized
06.
1. SERIES
A
2. ACTUATOR
A Handle, one per pole B Handle, one per multipole unit S Mid-Trip Handle, one per pole T Mid-Trip Handle, one per pole & Alarm Switch
1
3. POLES
1 One 2 Two
3 Three 4 Four
5 Five 6 Six
4. CIRCUIT
A 2 Switch Only (No Coil) F 3 Relay Trip (Current) B Series Trip (Current) G C Series Trip (Voltage) H
3
D
Shunt Trip (Current) Voltage Coil
3
E
Shunt Trip (Voltage) K
Voltage Coil
5. AUXILIARY / ALARM SWITCH
0 without Aux Switch 7 S.P.S.T., 0.110 Q.C. Term. 1 S.P.D.T., 0.093 Q.C. Term. (Gold Contacts) 2 S.P.D.T., 0.110 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term. 5 S.P.S.T., 0.093 Q.C. Term. 9 S.P.D.T., 0.187 Q.C. Term.
(Gold Contacts)
3
Relay Trip (Voltage)
3,4
Dual Coil with Shunt Trip
3,4
Dual Coil with Relay Trip
5
6. FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only 10 DC Instantaneous 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 20 50/60Hz Instantaneous 21 50/60Hz Ultra Short 22 50/60Hz Short 24 50/60Hz Medium 26 50/60Hz Long 30 DC, 50/60Hz Instantaneous
Notes: 1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided un-assembled with multi-pole units. B: Handle location as viewed from front of breaker: 2 pole - left pole 3 pole - center pole 4 pole - two handles at center poles 5 pole - three handles at center poles 6 pole - four handles at center poles S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit codes B, C, D, E, F, G, H and K. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. Available with circuit codes B & C. 2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available when tied to a protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps, select Cur rent Code 630. For 35 - 50 amps, select Current Code 650. 3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 50A amps maximum. 4 Consult factory for available Dual Coil options, as special catalog number is required. With Shunt construction, Dual Coils will trip instantaneously on line volt age. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only. 5 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A - supplied with standard half shells. 35-50A - supplied with extended boat (B-Style) half shells. On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole. 6 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes 10 and 20. 7 Available with Circuit Codes B & D only. VDE Certied to 30 amps. UL Recognized, CSA Accepted & TUV Certied to 50 amps. 8 VDE Certication available with single pole breakers with DC Delay only. UL Recog nition and CSA Accepted available in one and two pole breakers. 9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q. 10 Terminal Code 1: VDE Certication up to 25 amps and UL Recognition and CSA Certication up to 30 amps, but not recommended over 20 amps. 11 Terminal Codes 3, 5, E and H (Bus Type) with VDE, are supplied with Lock Washers, and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only VDE Certied when the washers are used. 12 Terminal Code L: VDE Certied available up to 12A. UL Recognized & CSA Accepted available up to 30A. 13 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certication and 50 amps with UL Recognition and CSA Accepted, with Circuit Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board) are available up to 40 amps with UL Recognition and CSA Accepted with Circuit Codes A, B and C. 14 Terminal Code Q not available with VDE certication. 15 Single pole only.
31 DC, 50/60Hz Ultra Short 32 DC, 50/60Hz Short 34 DC, 50/60Hz Medium 36 DC, 50/60Hz Long
7
42
50/60Hz Short, High-inrush
7
44
50/60Hz Medium,
High-inrush
7
46
50/60Hz Long, High-inrush
7
52
DC, Short, High-inrush
7
54
DC, Medium, High-inrush
7
56
DC, Long, High-inrush
7. CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 095 0.095 210 0.100 215 0.150 220 0.200
OR VOLTAGE COIL (NORMAL RATED VOLTAGE) 6
A06 6 DC A12 12 DC A18 18 DC A24 24 DC
8. TERMINAL
10
1
Push-On 0.250 Tab (Q.C.)
2
Screw 8-32 with upturned
lugs
11
Screw 8-32 (Bus Type)
3 4
Screw 10-32 with upturned
lugs
5 11 Screw 10-32 (Bus Type) 6
Screw 8-32 with upturned
lugs & 30° bend
7 Screw 8-32
& 30° bend 8 Screw 10-32 with upturned lugs & 30° bend
9
Screw 10-32 (Bus Type)
& 30° bend
225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750
A32 32 DC A48 48 DC A65 65 DC J06 6 AC
9
(Bus Type)
420 2.000 522 2.250 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500
J12 12 AC J18 18 AC J24 24 AC J48 48 AC
B
Screw M5 with upturned lugs
C Screw, M4 with upturned lugs E 11 Screw M4 (Bus Type) F Screw M5 with upturned lugs
& 30° bend
G Screw M5 (Bus Type) & 30° bend H 11 Screw M5 (Bus Type)
12
L
0.250 Q.C./ Solder Lug
M 11 M6 Threaded Stud
13
P
Printed Circuit Board Terminals
14
Q
Push-In Stud
R Screw, M4 with upturned lugs & 30° Bend
13
S
Push-On 0.110 Tab (Q.C.)
T 11 Screw, M4 with upturned lugs
611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 8 35.000 640 8 40.000 645 8 45.000 650 8 50.000
J65 65 AC K20 120 AC L40 240 AC
9. ACTUATOR COLOR & LEGEND
Actuator Color I-O ON-OFF Dual Legend
White A B 1 Black Black C D 2 White Red F G 3 White Green H J 4 White Blue K L 5 White Yellow M N 6 Black Gray P Q 7 Black Orange R S 8 Black Black (short handle)15 T U 9 White
10. MOUNTING / BARRIERS
MOUNTING STYLE BARRIERS
Threaded Insert, 2 per pole 1 6-32 x 0.195 inches no A 6-32 x 0.195 inches yes 2 ISO M3 x 5mm no B ISO M3 x 5mm (multipole only) yes Front panel Snap-In, 0.75” wide bezel 5 without Handleguard no 6 without Handleguard (multipole only) yes Front panel Snap-In, 0.96” wide bezel 7 without Handleguard, 1-pole 0.96” wide; no
multipole units have .105” bezel overhang on all sides 8 without Handleguard, 1-pole 0.96” wide; yes (multipole only) .105” bezel overhang on all sides
11. AGENCY APPROVAL
C UL Recognized & CSA Accepted D VDE Certied, UL Recognized & CSA Accepted E TUV Certied, UL Recognized & CSA Accepted I UL Recognized STD 1077, UL Recognized 1500
& CSA Accepted
Congure Complete Part Number > Browse Standard Parts >
(ignition protected),
Page 7
Sample
Part Number
AA1-B
0-14
-
450
-
1B1-M
T
Selection
123 4567 891011
12
Ordering Scheme
Handle - UL 489A Listed
1. SERIES
A
2. ACTUATOR
A Handle, one per pole S Mid-Trip Handle, one per pole T Mid-Trip Handle, one per pole & Alarm Switch
3. POLES
1 One 2 Two
1
2
3 Three 4 Four
4. CIRCUIT
B Series Trip (Current)
5 AUXILIARY/ALARM SWITCH
0 without Aux Switch 7 S.P.S.T., 0.110 Q.C. Term. 1 S.P.D.T., 0.093 Q.C. Term. (Gold Contacts) 2 S.P.D.T., 0.110 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term. 5 S.P.S.T., 0.093 Q.C. Term. 9 S.P.D.T., 0.187 Q.C. Term.
(Gold Contacts)
2
6. FREQUENCY & DELAY
3
52
11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long
DC, Short, High-inrush
3
54
DC, Medium, High-inrush
3
56
DC, Long, High-inrush
7. CURRENT RATING (AMPERES)
CODE AMPERES
210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800
285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000
455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500
613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 3 35.000 640 3 40.000 645 3 45.000 650 3 50.000
8. TERMINAL
6
Push-On 0.250 Tab (Q.C.)
1 2
Screw 8-32 with upturned
lugs
7
Screw 8-32 (Bus Type)
3 4
Screw 10-32 with upturned
lugs
5 7 Screw 10-32 (Bus Type) 6
Screw 8-32 with upturned
lugs & 30° bend
7 Screw 8-32
& 30° bend 8 Screw 10-32 with upturned lugs & 30° bend
(Bus Type)
9
Screw 10-32
& 30° bend
B
Screw M5 with upturned lugs
F Screw M5 with upturned lugs
& 30° bend
G Screw M5 (Bus Type) & 30° bend H Screw M5 (Bus Type) M 7 M6 Threaded Stud
8
P
Printed Circuit Board Terminals
9
Q
Push-In Stud & 30° bend
(Bus Type)
9. ACTUATOR COLOR & LEGEND
Actuator Color ON-OFF Dual Legend Color
White B 1 Black Black D 2 White Red G 3 White Green J 4 White Blue L 5 White Yellow N 6 Black Gray Q 7 Black Orange S 8 Black Black (short handle) 10 U 9 White
10. MOUNTING / BARRIERS
MOUNTING STYLE BARRIERS
Threaded Insert, 2 per pole 1 6-32 x 0.195 inches no A 6-32 x 0.195 inches yes 2 ISO M3 x 5mm no B ISO M3 x 5mm (multipole only) yes Front panel Snap-In, 0.75” wide bezel 5 without Handleguard no 6 without Handleguard (multipole only) yes Front panel Snap-In, 0.96” wide bezel 7 without Handleguard, 1-pole 0.96” wide; no
multipole units have .105” bezel overhang on all sides 8 without Handleguard, 1-pole 0.96” wide; yes (multipole only) .105” bezel overhang on all sides
9
11. MAXIMUM APPLICATION RATING
M 80 DC
12. AGENCY APPROVAL
T UL489A Listed K UL489A Listed, VDE Certied J UL489A Listed, TUV Certied
Notes: 1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided un-assembled with multi-pole units. S: Handle moves to mid-position only upon electrical trip of the breaker. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. 2 On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole. 3 VDE Certied to 30 amps. UL489A Listed to 50 amps. 4 VDE Certication available with single pole breakers only. UL489A Listing available with one and two pole breakers. 5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9 G, H, M and Q. 6 Terminal Code 1 (Push-On) available up to 25 amps with VDE Certication and 30 amps with UL489A Listing, but is not recommended over 20 amps. 7 Terminal Codes 3, 5 and H (Bus Type) with VDE, are supplied with Lock Washers, and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only VDE Certied when the washers are used. 8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certication and 50 amps with UL489A Listing. 9 Terminal Code Q not available with VDE certication. 10 Single pole only.
Congure Complete Part Number > Browse Standard Parts >
07.
Page 8
A-Series Circuit Breaker - Handle WORLD – Ordering Scheme
Sample
Part Number
A
A
3-B
0-14
-
450
-
1A1-P
Selection
123 4 5 67 89
10
11
Ordering Scheme
1. SERIES
A
2. ACTUATOR
A Handle, one per pole B Handle, one per multipole unit S Mid-Trip Handle, one per pole T Mid-Trip Handle, one per pole & Alarm Switch
3. POLES
1 One 2 Two
4. CIRCUIT
A 2 Switch Only (No Coil) D B Series Trip (Current) E C Series Trip (Voltage) H
Voltage Coil
5. AUXILIARY / ALARM SWITCH
0 without Aux Switch 2 S.P.D.T., 0.110 Q.C. Term.
6. FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only 10 DC Instantaneous 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 20 50/60Hz Instantaneous 21 50/60Hz Ultra Short 22 50/60Hz Short 24 50/60Hz Medium 26 50/60Hz Long
7. CURRENT RATING (AMPERES)
CODE AMPERES
210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800
OR VOLTAGE COIL (NORMAL RATED VOLTAGE) 6
A06 6 DC A12 12 DC A18 18 DC A24 24 DC
1
3 Three 4 Four
285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000
A32 32 DC A48 48 DC A65 65 DC J06 6 AC
5 Five 6 Six
3
Shunt Trip (Current)
3
Shunt Trip (Voltage)
3,4
Dual Coil with Shunt Trip
5
30 DC, 50/60Hz Instantaneous 31 DC, 50/60Hz Ultra Short 32 DC, 50/60Hz Short 34 DC, 50/60Hz Medium 36 DC, 50/60Hz Long
7
42
50/60Hz Short, High-inrush
7
44
50/60Hz Medium, High-inrush
7
46
50/60Hz Long, High-inrush
7
52
DC, Short, High-inrush
7
54
DC, Medium, High-inrush
7
56
DC, Long, High-inrush
455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500
J12 12 AC J18 18 AC J24 24 AC J48 48 AC
613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 8 35.000 640 8 40.000 645 8 45.000 650 8 50.000
J65 65 AC K20 120 AC L40 240 AC
Handle - World
9 ACTUATOR COLOR & LEGEND
Actuator Color I-O Dual Legend Color
White A 1 Black Black C 2 White Red F 3 White Green H 4 White Blue K 5 White Yellow M 6 Black Gray P 7 Black Orange R 8 Black Black (short handle)15 T 9 White
10. MOUNTING / BARRIERS
MOUNTING STYLE BARRIERS Threaded Insert, 2 per pole
1 6-32 x 0.195 inches no A 6-32 x 0.195 inches yes 2 ISO M3 x 5mm no B ISO M3 x 5mm (multipole only) yes Front panel Snap-In, 0.75” wide bezel 5 without Handleguard no 6 without Handleguard (multipole only) yes Front panel Snap-In, 0.96” wide bezel 7 without Handleguard, 1-pole 0.96” wide; no
multipole units have .105” bezel overhang on all sides 8 without Handleguard, 1-pole 0.96” wide; yes (multipole only) .105” bezel overhang on all sides
11. AGENCY APPROVAL
P TUV Certied, UL Recognized & CSA Accepted Q UL Recognized STD 1077, UL Recognized 1500
& CSA Accepted
Notes: 1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units. S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit codes B, C, D, E, and H. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. Available with circuit codes B & C. 2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available when tied to a protected pole (Circuit Code B, C, D or H.), For .01 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. 3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum. 4 Consult factory for available Dual Coil options, as special catalog number is required. With Shunt construction, Dual Coils will trip instantaneously on line volt age. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only. 5 On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole. 6 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes 10, 20 & 30. 7 Available with Circuit Codes B & D only. VDE Certied to 30 amps. UL Recognized, CSA Accepted & TUV Certied to 50 amps. 8 Available up to two poles with AC or DC delays. 9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G and H. 10 Terminal Code 1: TUV Certication up to 30 amps, but not recommended over 20 amps. 11 Terminal Codes 3, 5 , 7, 9, E, G and H (Bus Type) are supplied with Lock Washers. These breakers are only TUV Certied when the washers are used. 12 Single pole only.
Congure Complete Part Number > Browse Standard Parts >
(ignition protected),
08.
8. TERMINAL
10
1
Push-On 0.250 Tab (Q.C.)
2
Screw 8-32 with upturned
lugs
11
Screw 8-32 (Bus Type)
3 4
Screw 10-32 with upturned
lugs
5 11 Screw 10-32 (Bus Type) 6
Screw 8-32 with upturned
lugs & 30° bend
7 Screw 8-32
& 30° bend 8 Screw 10-32 with upturned lugs & 30° bend
(Bus Type)
9
Screw 10-32
& 30° bend
B
Screw M5 with upturned lugs
C Screw, M4 with upturned lugs
11
E
Screw M4 (Bus Type)
F Screw M5 with upturned lugs
& 30° bend
G Screw M5 (Bus Type) & 30° bend H 11 Screw M5 (Bus Type) M M6 Threaded Stud R Screw, M4 with upturned lugs
& 30° Bend
11
T
Screw, M4 with upturned lugs
(Bus Type)
Page 9
> 30 AMPS
LOAD
CIRCUIT
CODE
CIRCUIT
[25.40]
Circuit & Terminal Diagrams
inches [millimeters]
Handle
2 TERMINALS
5 TERMINALS
.205
[5.21]
3 TERMINALS
4 TERMINALS
CIRCUIT BREAKER PROFILE
LINE
MAIN TERMINALS (SEE TABLE A)
LOAD
1.640
[41.66]
NC NO
C
STANDARD AUX. SWITCH TERMINALS
.390
[9.91]
1
.780
[19.81]
2
3
4
.390
[9.91]
NO NC
C
.520
[13.21]
ALARM SWITCH TERMINALS & STD. AUX. VDE OR <30 AMPS oR AGENCY CODE”P”
CIRCUIT SCHEMATIC
ANSI
SWITCH ONLY (NO COIL)
LINE
LOAD
LINE
NC
NO
LOAD
C
SHUNT TRIP
LINE
SHUNT
LOAD
RELAY TRIP
LINE
1
2
LOAD
RELAY
3
4
RELAY
CODE
A
FG 0
CIRCUIT SCHEMATIC
AUX
SWITCH
CODE
ANSI
SERIES TRIP
LINE
BCA
LOAD
SERIES TRIP WITH (3)
AUXILIARY/ALARM SWITCH
1
2 3
4
DUAL COIL; SERIES TRIP CURRENT COIL,
NC
NO
C
STANDARD
AUX. SWITCH
RELAY TRIP VOLTAGE COIL
LINE
VOLTAGE
LOAD
DUAL COIL; SERIES TRIP CURRENT COIL,
RELAY TRIP VOLTAGE COIL
LINE
LOAD
COIL
1
2
3
4
ALARM SWITCH
VOLTAGE COIL
NO
NC
AUX
CODE
SWITCH
BC 0
C
BC
H
K 0
1
2 3
4
0DE 0
09.
AUXILIARY/ALARM SWITCH TERMINAL DETAIL
.239
[6.07]
NC NO
LINE
.205
[5.21]
C
LOAD
.677
< 30 AMPS
[17.19]
LINE
LOAD
Notes: 1 Tolerance ±.020 [.51] unless otherwise specied. 2 Alarm Switch available with .110 x .020 Q.C. & Solder Lug Terminals Only.
.406
[10.31]
.344
[8.74]
.050 DIA [ 1.27]
TAB (Q.C.)
.520
[13.21]
2 PLCS C NO NC
1.000
.110
[2.79]
.051 DIA [ 1.29]
.087
[2.20]
.287
[7.29]
TAB (Q.C.)
.250
[6.35]
TAB (Q.C.)
.110
[2.80]
.093
[2.36]
Page 10
[5.59]
Circuit & Terminal Diagrams
inches [millimeters]
Handle
.069
[1.75]
DIA
TAB(Q.C.)
30 AMP
MID TRIP
HANDLE POSITION VS. AUX/ALARM SWITCH MODE
30
0
ON
30
90
.344
[8.74]
MID TRIP C/B
VOLTAGE COILS
1.936
[49.17]
MID TRIP C/B
ALARM SWITCH MODE
NC
NC
NC
.361
[9.17]
.110
[2.79]
.110 QC
ONLY
HANDLE POSITION
30
OFF
0
C
NO
ON
NO
NO
M6 STUD
30
C
90
MID TRIP
C
.750
[19.05]
.405
[10.29]
50 AMP
TIGHTENING TORQUE
SPECIFICATIONS
TABLE A
(W/O ALARM SWITCH)
.100
[2.54]
.750
[19.05]
AUX. SWITH CODE
NO
NC
NO
NC
NO
NC
PUSH-IN STUF
50 AMP
TORQUETHREAD SIZE
#6-32 & M3 MOUNTING HARDWARE
#8-32 & M4 THREAD TERMINAL SCREW
#10-32 & M5 THREAD TERMINAL SCREW
7-9 IN-LBS
[0.8-1.0 NM] 12-15 IN-LBS
[1.4-1.7 NM]
15-20 IN-LBS
[1.7-2.3 NM]
TABLE B
TERMINAL DESCRIPTION
MAIN
SHUNT,RELAY
&
DUAL COIL
AUX. SWITCH*
*AVAILABLE ON SERIES TRIP AND SWITCH ONLY CIRCUITS WHEN CALLED FOR ON MULTI-POLE UNITS, ONLY ONE AUX. SWITCH IS NORMALLY SUPPLIED, AS SHOWN IN MULTI-POLE INDENTIFICATION SHEME.
TAB (Q.C.) SCREW TYPE
TAB (Q.C.)
SCREW #8-32 W/UPTURNED LUGS
1.350
[34.29]
2.207[56.10]
2.095[53.20].093 TAB (Q.C.)
2.189[55.60].110 TAB (Q.C.)
2 PLCS
C
C
C
1.000
[25.40]
CENTERLINE OF PUSH-IN
STUD CONTACT AREA
.154
DIA
[3.91]
DEPTH
BEHIND PANEL
2.000[50.80]
2.032[51.60]
2.364[60.05]
1.970[50.00]SOLDER TYPE
.393
[9.96]
30
.392
[9.97]
REF
1.560
[39.62]
TYP
CIRCUIT
BREAKER
MODE
OFF
STANDARD C/B
HANDLE POSITION
30
OFF
0
ON
AUX. SWITCH MODE
C
NO
NC
HANDLE POSITION
OFF
ON
ELECTRICAL
TRIP
30
30
OFF
0
NC
NC
C
NO
MID TRIP
C
NO
TERMINAL DIMENSIONAL DETAIL & RATING
.360
[9.14]
.250
[6.35]
UPTURN LUG
#8-32 30 AMP
#10-32 30 AMP
M5 30 AMP M4 30 AMP
.392
[9.96]
.375
[9.53]
#10-32 50 AMP
PUSH-IN STUD MATING HOLE
UL-RECOGNIZED MULTI-POLE
SEE TABLE-B
DEPTH BEHIND PANEL
ON
OFF
O
.375
[9.53]
BUS
#8-32 30 AMP
.520
[13.21]
BARRIER FOR
BREAKERS
LINE
(NETZ)
1.560
TYP
[39.62]
.392
[9.96]
+.002
-.000
.161 DIA [ 4.10]
.250
DIA
.093
[6.35]
[.76]
QC SOLDER LUG
30 AMP
[+.05] [-.00]
LINE
LOAD
2.000
[50.80]
10.
LOAD
1.640
[41.66]
Notes: 1 Tolerance ±.020 [.51] unless otherwise specied. 2 Alarm Switch available with .110 x .020 QC & solder lug terminals only.
.032 [.81]
REF
(LAST)
TYP
.220
TYP
M6 STUD
PUSH-IN
STUD
SCREW TERMINAL
WITH 30 BEND
Page 11
#6-32 [M3] THREAD X.195[4.95]DEEP
1.640
UNLESS OTHERWISE SPECIFIED
Dimensional Specs
inches [millimeters]
Handle
2 PLCS PER POLE
[15.49]
1-POLE
(AA1)
.170
[4.32]
2-POLE
(AA2)
3-POLE
(AA3)
2.265
[57.53]
MAX
.610
.755
[19.18]
MAX
TYPICAL-OPTIONAL
“ON-OFF” LEGEND
.750
[19.05]
1.515
[38.48]
MAX
.750
[19.05]
TYP
.130
[3.30]
SEE NOTE 3
60
.690
[17.50]
MULTI-POLE HANDLE TIE KIT SHIPPED BULK
.250
[6.35]
SHORT HANDLE
ON
OFF
2-POLE
(AB2)
3-POLE
(AB3)
[41.66]
TYP
2.000
[50.80]
2.032
[51.61]
LINE
1.560
[39.62]
LOAD
TAB (Q.C.) TYPE SCREW TYPE
2.265
[57.53]
MAX
TYP
1.515
[38.48]
MAX
TAB (Q.C.) TYPE TERMINALS IN SERIES TRIP CONCUIT CONFIGURATION SHOWN. FOR OTHER CONFIGURATIONS SEE CIRCUIT & TERMINAL DIAGRAMS
4-POLE
(AA4)
.750
[19.05]
TYP
3.015
[76.05]
MAX
LINE
LOAD
POLE
POLE
1
MULTI-POLE INDENTIFICATION SCHEME AS VIEWED FROM TERMINAL END OF BREAKER.
Notes: 1 Tolerance ± 0.20 [.51] unless otherwise specied. 2 For agency code P = .150 [3.81].
POLE
2
POLE
3
4-POLE
(AB4)
3.015
[76.58]
MAX
[+.25]
.156 DIA [ 3.96]
2 PLCS TYP
PER POLE
1.660
[42.16]
4
1.050
[26.67]
.750
[19.05]
TYP
PER POLE
AA1, AB2, AB3
AA2, AB4
PANEL CUTOUT DETAIL
TOLERANCE +.005[+.12]
+.010
-.000
.630 DIA [ 16.00]
ONE PER POLE
AA3
AA4
_ _
[-.00]
11.
Page 12
1.640
1.560
TIE KITSHIPPED BULK
Dimensional Specs
inches [millimeters]
Handle
1 POLE
(AA1)
2 POLE
(AA2)
1.488
[37.80]
2.598
[65.99]
TYP
.744
[18.90]
.125
[3.18]
60
.250
[6.35]
(SHORT HANDLE)
.690
[17.50]
2 POLE
(AB2)
ON
OFF
[41.66]
TYP
[50.80]
[51.61]
1.488
[37.80]
2.000
2.032
[39.62]
TYP
LINE
1.220
[31.00]
TYP
LOAD
.250 TAB (Q.C.) TYPE
SCREW TYPE
2.000
[50.80]
TYP
.010
.770
[19.56]
.012
2.187
[55.55]
TYP
.755
[19.18]
MAX
BREAKER
WIDTH
TAB (Q.C.) TYPE TERMINALS IN SERIES TRIP CIRCUIT CONFIGURATION SHOWN. FOR OTHER CONFIGURATIONS, SEE CIRCUIT AND TERMINAL
[.25]
[.30]
DIAGRAMS.
1.530
[38.86]
.010
3.030
[76.96]
.010
2.280
.010
[57.91]
[.25]
[.25]
[.25]
3 POLE
(AA3)
2.232
[56.69]
4 POLE
(AA4)
2.976
[75.59]
MULTI-POLE HANDLE
Notes: 1 Recommended panel thickness: .040 [1.02] to .100 [2.54]. 2 Tolerance ±.020 [.51] unless otherwise specied.
3 POLE
(AB3)
4 POLE
(AB4)
2.323
[56.69]
[75.59]
AA1
AA2, AB2
AA3, AB3
AA4, AB4
PANEL CUTOUT DETAIL
2.976
12.
Page 13
4 POLE
1.640
SHIPPED BULK
.755
Dimensional Specs
inches [millimeters]
Handle
1 POLE
(AA1)
2 POLE
(AA2)
1.700
[43.18]
2.598
[65.99]
TYP
.960
[24.38]
60
.250
[6.35]
(SHORT HANDLE)
.690
[17.50]
2 POLE
(AB2)
ON
OFF
[41.66]
TYP
[50.80]
2.032
[51.61]
1.700
[43.18]
2.000
1.560
[39.62]
TYP
LINE
1.220
[31.00]
TYP
LOAD
.250 TAB (Q.C.) TYPE
SCREW TYPE
.770
[19.56]
[55.55]
.010
2.187 TYP
2.000
[50.80]
TYP
[.25]
.012
[19.18]
MAX
BREAKER
WIDTH
TAB (Q.C.) TYPE TERMINALS IN SERIES TRIP CIRCUIT CONFIGURATION SHOWN. FOR OTHER CONFIGURATIONS, SEE CIRCUIT AND TERMINAL DIAGRAMS.
.010
3.030
[.25]
[76.96]
.010
2.280
[.25]
[57.91]
.010
1.530
[.25]
[38.86]
[.30]
3 POLE
(AA3)
2.450
[62.23]
(AA4)
3.190
[81.03]
MULTI-POLE HANDLE TIE KIT
Notes: 1 Recommended panel thickness: .040 [1.02] to .100 [2.54]. 2 Tolerance ±.020 [.51] unless otherwise specied.
3 POLE
(AB3)
4 POLE (AB4)
2.450
[62.23]
3.190
[81.03]
AA1
AA2, AB2
AA3, AB3
AA4, AB4
PANEL CUTOUT DETAIL
13.
Page 14
A-Series Circuit Breaker - Sealed Toggle UL Recognized – Ordering SchemeA-Series Circuit Breaker - Handle WORLD – Ordering Scheme
Sample
Part Number
A
M
1-B
0-10
-
450
-
101-C
Selection
123 4 5 67 89
10
11
Ordering Scheme
1. SERIES
A
2. ACTUATOR
M Sealed Toggle, one per unit
3. POLES
1 One 2 Two 3 Three
4. CIRCUIT
A 2 Switch Only (No Coil) F 3 Relay Trip (Current) B Series Trip (Current) G C Series Trip (Voltage) H
3
D
Shunt Trip (Current) Voltage Coil
3
E
Shunt Trip (Voltage) K
Voltage Coil
5. AUXILIARY / ALARM SWITCH
0 without Aux Switch 7 S.P.S.T., 0.110 Q.C. Term. 1 S.P.D.T., 0.093 Q.C. Term. (Gold Contacts) 2 S.P.D.T., 0.110 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term. 5 S.P.S.T., 0.093 Q.C. Term. 9 S.P.D.T., 0.187 Q.C. Term.
(Gold Contacts)
6. FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only 10 DC Instantaneous 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 20 50/60Hz Instantaneous 21 50/60Hz Ultra Short 22 50/60Hz Short 24 50/60Hz Medium 26 50/60Hz Long
7. CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 095 0.095 210 0.100 215 0.150 220 0.200 225 0.250
OR VOLTAGE COIL (NORMAL RATED VOLTAGE) 6
A06 6 DC A12 12 DC A18 18 DC A24 24 DC
1
230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250
A32 32 DC A48 48 DC A65 65 DC J06 6 AC
3
Relay Trip (Voltage)
3,4
Dual Coil with Shunt Trip
3,4
Dual Coil with Relay Trip
5
30 DC, 50/60Hz Instantaneous 31 DC, 50/60Hz Ultra Short 32 DC, 50/60Hz Short 34 DC, 50/60Hz Medium 36 DC, 50/60Hz Long
7
42
50/60Hz Short, High-inrush
7
44
50/60Hz Medium, High-inrush
7
46
50/60Hz Long, High-inrush
7
52
DC, Short, High-inrush
7
54
DC, Medium, High-inrush
7
56
DC, Long, High-inrush
425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500
J12 12 AC J18 18 AC J24 24 AC J48 48 AC
612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 8 35.000 640 8 40.000 645 8 45.000 650 8 50.000
J65 65 AC K20 120 AC L40 240 AC
Sealed Toggle
8. TERMINAL
10
1
Push-On 0.250 Tab (Q.C.)
2
Screw 8-32 with upturned
lugs
3 Screw 8-32 4
Screw 10-32 with upturned
lugs
5 Screw 10-32 (Bus Type) 6
Screw 8-32 with upturned
lugs & 30° bend
7 Screw 8-32
& 30° bend 8 Screw 10-32 with upturned lugs & 30° bend
9
Screw 10-32 (Bus Type)
& 30° bend
B
Screw M5 with upturned lugs
9. LEGEND PLATE
0 No legend plate
10. MOUNTING / BARRIERS
MOUNTING STYLE BARRIERS
1 Standard Hex Nut no A Standard Hex Nut (multipole only) yes
11. AGENCY APPROVAL
C UL Recognized & CSA Accepted I UL Recognized STD 1077, UL Recognized 1500
& CSA Accepted
Notes: 1 Actuator Code M: Handle location as viewed from front of panel: 2 pole - right pole 3 pole - center pole 2 Switch Only circuits, rated up to 50 amps and 3 poles. Only available when tied to
a protected pole. For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. 3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum. 4 Consult factory for available Dual Coil options, as special catalog number is required. With Shunt construction, Dual Coils will trip instantaneously on line volt age. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only. 5 Auxiliary Switch available on Series Trip & Switch Only circuits, limited to 30 amps. On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole. 6 Voltage coils not rated for continuous duty. Available only with delay codes 10 and
20. 7 Available with Circuit Codes B & D only. VDE Certied to 30 amps. UL Recognized, CSA Accepted & TUV Certied to 50 amps. 8 UL Recognition and CSA Certication available on one and two pole breakers. 9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, B, F, G, H, M and Q. 10 Terminal Code 1: UL Recognition and CSA Certication up to 30 amps, but not recommended over 20 amps.
11 Terminal Code L : available up to 30A. 12 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up
to 50 amps, with Circuit Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board) are available up to 40 amps with Circuit Codes A, B and C.
Congure Complete Part Number > Browse Standard Parts >
9
(Bus Type)
(Bus Type)
C Screw, M4 with upturned lugs E Screw M4 F Screw M5 with upturned lugs
& 30° bend
G Screw M5 (Bus Type) & 30° bend H Screw M5 (Bus Type) L 12 0.250 Q.C./ Solder Lug M M6 Threaded Stud P 12 Printed Circuit Board Terminals Q Push-In Stud R Screw, M4 with upturned lugs
& 30° Bend
17
S
Push-On 0.110 Tab (Q.C.)
& 30° bend T Screw, M4 with upturned lugs
(Bus Type)
(ignition protected),
14.
Page 15
Dimensional Specs
inches [millimeters]
Sealed Toggle
15.
Notes: 1 Tolerance ±.020 [.51] unless otherwise specied.
Page 16
Sample
Part Number
A
F
1-B
0-24
-
630
-
231-D
Selection
123 4 5 67 89
10
11
Ordering Scheme
Rocker UL 1077 Recognized
16.
1. SERIES
A
2. ACTUATOR
Two Color Visi-Rocker C Indicate ON, vertical legend D Indicate ON, horizontal legend F Indicate OFF, vertical legend G Indicate OFF, horizontal legend H Indicate OFF, no legend Push-To-Reset, Visi-Rocker N Indicate OFF, vertical legend O Indicate OFF, horizontal legend P Indicate OFF, no legend Single color J Vertical legend K Horizontal legend L No legend Push-To-Reset , Single color R Vertical legend U Horizontal legend V No legend
1
ROCKER STYLE DESCRIPTIONS
HORIZONTAL STYLE
INDICATE “ON”
LINE
INDICATE “OFF”
LINE
SINGLE COLOR
CODE “G”, “O”
CODE “k”, “U”
CODE “D”
LINE
VERTICAL STYLE
LINE
INDICATE COLOR LOCATION
LINE
LINE
CODE “F”, “N”
CODE “J”, “R”
3. POLES
1 One 2 Two 3 Three
4. CIRCUIT
A 3 Switch Only (No Coil) G 4 Relay Trip (Voltage) B Series Trip (Current) H C Series Trip (Voltage) Voltage Coil D 4 Shunt Trip (Current) K E 4 Shunt Trip (Voltage) Voltage Coil
5. AUXILIARY / ALARM SWITCH
0 without Aux Switch 7 S.P.S.T., 0.110 Q.C. Term. 1 S.P.D.T., 0.093 Q.C. Term. (Gold Contacts) 2 S.P.D.T., 0.110 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term. 5 S.P.S.T., 0.093 Q.C. Term. 9 S.P.D.T., 0.187 Q.C. Term.
(Gold Contacts)
4,5
Dual Coil with Shunt Trip
4,5
Dual Coil with Relay Trip
5
6. FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only 10 DC Instantaneous 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 20 50/60Hz Instantaneous 21 50/60Hz Ultra Short 22 50/60Hz Short 24 50/60Hz Medium 26 50/60Hz Long
30 DC, 50/60Hz Instantaneous 31 DC, 50/60Hz Ultra Short 32 DC, 50/60Hz Short 34 DC, 50/60Hz Medium 36 DC, 50/60Hz Long 42 9 50/60Hz Short, High-inrush 44 9 50/60Hz Medium, High-inrush 46 9 50/60Hz Long, High-inrush 52 9 DC, Short, High-inrush 54 9 DC, Medium, High-inrush 56 9 DC, Long, High-inrush
7. CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 095 0.095 210 0.100 215 0.150 220 0.200
OR VOLTAGE COIL (NORMAL RATED VOLTAGE) 8
A06 6 DC A12 12 DC A18 18 DC A24 24 DC
Congure Complete Part Number > Browse Standard Parts >
225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750
A32 32 DC A48 48 DC A65 65 DC J06 6 AC
420 2.000 522 2.250 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500
J12 12 AC J18 18 AC J24 24 AC J48 48 AC
611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 8 35.000 640 8 40.000 645 8 45.000 650 8 50.000
J65 65 AC K20 120 AC L40 240 AC
CODE “C”
8. TERMINAL
12
1
Push-On 0.250 Tab (Q.C.)
2
Screw 8-32 with upturned
lugs
13
Screw 8-32 (Bus Type)
3 4
Screw 10-32 with upturned
lugs
5 13 Screw 10-32 (Bus Type) 6
Screw 8-32 with upturned
lugs & 30° bend
7 Screw 8-32
& 30° bend 8 Screw 10-32 with upturned lugs & 30° bend
9
Screw 10-32 (Bus Type)
& 30° bend
B
Screw M5 with upturned lugs
11
(Bus Type)
C Screw, M4 with upturned lugs
13
Screw M4 (Bus Type)
E F Screw M5 with upturned lugs
& 30° bend
G Screw M5 (Bus Type) & 30° bend H 13 Screw M5 (Bus Type) L 14 0.250 Q.C./ Solder Lug M 13 M6 Threaded Stud P 15 Printed Circuit Board Terminals Q Push-In Stud R Screw, M4 with upturned lugs
& 30° Bend
17
S
Push-On 0.110 Tab (Q.C.)
& 30° bend
T Screw, M4 with upturned lugs
9. ACTUATOR COLOR & LEGEND
Actuator or Marking: Marking Color Visi-Color 12 I-O ON-OFF Dual White A B 1 Black White
Black C D 2 White n/a Red F G 3 White Red Green H J 4 White Green Blue K L 5 White Blue
Yellow M N 6 Black Yellow
Gray P Q 7 Black Gray Orange R S 8 Black Orange
10. MOUNTING / BARRIERS
STANDARD ROCKER BEZEL Threaded Insert, 2 per pole BARRIERS 1 6-32 x 0.195 inches no A 6-32 X 0.195 inches (multi-pole units only) yes 2 ISO M3 x 5mm no B ISO M3 x 5mm (multi-pole units only) yes ROCKERGUARD & PUSH-TO-RESET BEZEL Threaded Insert, 2 per pole 3 6-32 x 0.195 inches no C 6-32 x 0.195 inches (multi-pole units only) yes 4 ISO M3 x 5mm no D ISO M3 x 5mm (multi-pole units only) yes FRONT PANEL SNAP-IN BRACKET, 0.744” [18.90mm] wide bezel 8 without Rockerguard (single pole units only) no H with Rockerguard (single pole units only) no FRONT PANEL SNAP-IN BRACKET, 0.96” [24.48mm] wide bezel 9 without Rockerguard (single pole units only) no J with Rockerguard (single pole units only) no
12
Single Color Visi-Rocker
20
11. AGENCY APPROVAL
C UL Recognized & CSA Accepted D VDE Certied, UL Recognized & CSA Accepted E TUV Certied, UL Recognized & CSA Accepted I UL Recognized STD 1077, UL Recognized 1500 (ignition protected),
& CSA Accepted
Notes: 1 Push-To-Reset actuators have OFF portion of rocker shrouded. 2 Multi-pole breakers have all breakers identical except when specifying Auxiliary switch
and/or mixed poles, and have one rocker per breaker. 3 Switch Only circuits, rated up to 50 amps & 3 poles, are available only when tied to a protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. 4 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum. 5 Consult factory for Dual Coil options, as special catalog number is required. With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only. 6 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A, are supplied with standard half shells. 30-50A are supplied with extended boat (B-Style) half shells. 7 On multi-pole breakers, one auxiliary switch is supplied, mounted in the right pole. 8 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes 10 & 20. 9 Available with Circuit Codes B & D only. VDE Certied to 30 amps. UL Recognized, CSA Accepted & TUV Certied to 50 amps. 10 Series Trip current ratings: VDE Certication available with single pole breakers with DC Delay only. UL Recognition & CSA Accepted available in one and two pole breakers. 11 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q. 12 Terminal Code 1: VDE Certication up to 25 amps and UL Recognition and CSA Accepted up to 30 amps, but not recommended over 20 amps. 13 Terminal Codes 3, 5 E & H (Bus Type) with VDE, are supplied with Lock Washers; Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only VDE Certied when the washers are used. 14 VDE Cert. available up to 12 amps. UL Rec. & CSA Accepted available up to 30 amps. 15 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certication and 50 amps with UL Recognition and CSA Accepted, with Circuit Codes A, B & C.Two pole breakers with Terminal Code P (Printed Circuit Board) are available up to 40 amps with UL Recognition and CSA Certication with Circuit Codes A, B and C. 16 Terminal Code Q not available with VDE. 17 Terminal Code S used on voltage coil circuit constructions only. 18 Color shown is visi and legend with remainder of rocker black. 19 Dual = ON-OFF/I-O legend with actuator. None = no legend on actuator 20 Legend on Push-to-reset bezel/shroud is white with single color actuator codes R, & U. Legend on Push-to-reset bezel/shroud matches Visi-color of rocker with actuator codes N & O. Rockerguard available with actuator codes C through L.
Page 17
Sample
Part Number
AF1-B
0-14
-
450
-
131-M
T
Selection
123 4 5 67 89
10 1112
Ordering Scheme
Rocker - UL 489A Listed
17.
1. SERIES
A
2. ACTUATOR
Two Color Visi-Rocker Push-To-Reset, Visi-Rocker C Indicate ON, vertical legend N Indicate OFF, D Indicate ON, horizontal legend vertical legend F Indicate OFF, vertical legend O Indicate OFF, horizontal G Indicate OFF, horizontal legend legend Single color Push-To-Reset , Single color J Vertical legend R Vertical legend K Horizontal legend U Horizontal legend
INDICATE “ON”
LINE
STYLE
VERTICAL
INDICATE COLOR LOCATION
STYLE
HORIZONTAL
3. POLES
1 One 2 Two 3 Three
1
ROCKER STYLE DESCRIPTIONS
INDICATE “OFF”
CODE “C”
CODE “D”
LINE
2
CODE “F”, “N”
LINE
CODE “G”, “O” CODE “K”, “U”
LINE
SINGLE COLOR
CODE “J”, “R”
LINE
LINE
4. CIRCUIT
B Series Trip (Current)
5. AUXILIARY / ALARM SWITCH
0 without Aux Switch 7 S.P.S.T., 0.110 Q.C. Term. 1 S.P.D.T., 0.093 Q.C. Term. (Gold Contacts) 2 S.P.D.T., 0.110 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term. 5 S.P.S.T., 0.093 Q.C. Term. 9 S.P.D.T., 0.187 Q.C. Term.
(Gold Contacts)
2
6. FREQUENCY & DELAY
11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long
52 DC, Short, High-inrush 54 DC, Medium, High-inrush 56 DC, Long, High-inrush
7. CURRENT RATING (AMPERES)
CODE AMPERES
210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800
8. TERMINAL
6
1
Push-On 0.250 Tab
2
Screw 8-32 with upturned
lugs
3 7 Screw 8-32 (Bus Type) 4
Screw 10-32 with upturned
lugs
5 7 Screw 10-32 (Bus Type) 6
Screw 8-32 with upturned
lugs & 30° bend 7 Screw 8-32 (Bus Type) & 30° bend
285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000
5
(Q.C.)
455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500
8 Screw 10-32 with upturned
lugs & 30° bend
9
Screw 10-32 (Bus Type)
& 30° bend
B
Screw M5 with upturned lugs
F Screw M5 with upturned lugs G Screw M5 (Bus Type) & 30° bend H Screw M5 (Bus Type) M 7 M6 Threaded Stud P 8 Printed Circuit Board Terminals Q 9 Push-In Stud
613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 6354 35.000 6404 40.000 6454 45.000 6504 50.000
9. ACTUATOR COLOR & LEGEND
Actuator or Marking: Marking Color Visi-Color White B 1 Black White
Black D 2 White n/a Red G 3 White Red Green J 4 White Green Blue L 5 White Blue
Yellow N 6 Black Yellow
Gray Q 7 Black Gray Orange S 8 Black Orange
10. MOUNTING / BARRIERS
STANDARD ROCKER BEZEL Threaded Insert, 2 per pole BARRIERS 1 6-32 x 0.195 inches no A 6-32 X 0.195 inches (multi-pole units only) yes 2 ISO M3 x 5mm no B ISO M3 x 5mm (multi-pole units only) yes ROCKERGUARD & PUSH-TO-RESET BEZEL Threaded Insert, 2 per pole 3 6-32 x 0.195 inches no C 6-32 x 0.195 inches (multi-pole units only) yes 4 ISO M3 x 5mm no D ISO M3 x 5mm (multi-pole units only) yes FRONT PANEL SNAP-IN BRACKET, 0.744” [18.90mm] wide bezel 8 without Rockerguard (single pole units only) no H with Rockerguard (single pole units only) no FRONT PANEL SNAP-IN BRACKET, 0.96” [24.48mm] wide bezel 9 without Rockerguard (single pole units only) no J with Rockerguard (single pole units only) no
10
ON-OFF Dual
10
Single Color Visi-Rocker
20
11. MAXIMUM APPLICATION RATING
M 80 DC
12. AGENCY APPROVAL
T UL489A Listed K UL489A Listed, VDE Certied J UL489A Listed, TUV Certied
Notes: 1 Push-To-Reset actuators have OFF portion of rocker shrouded. 2 Multi-pole breakers have all breakers identical except when specifying Auxiliary
switch and/or mixed poles, and have one rocker per breaker. 3 Auxiliary Switch breakers with Series Trip circuits: ≤ 30A, are supplied with standard half shells. 30-50A are supplied with extended boat (B-Style) half shells. 4 VDE Certication available with single pole breakers only. UL489A Listing available with one and two pole breakers. 5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q. 6 Terminal Code 1 (Push-On) available up to 25 amps with TUV or VDE Certication and 30 amps with UL489A Listing, but is not recommended over 20 amps. 7 Terminal Codes 3, 5 and H (Bus Type) with TUV or VDE, are supplied with Lock Washers, and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only TUV or VDE Certied when the washers are used. 8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certication and 50 amps with UL489A Listing. 9 Terminal Code Q not available with VDE certication. 10 Color shown is Visi and Legend with remainder of rocker black. Dual = ON-OFF/I­ O legend. 11 Legend on Push-to-reset bezel/shroud is white with single color actuator codes R & U. Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator codes N & O. Rockerguard available with actuator codes C through K
Congure Complete Part Number > Browse Standard Parts >
Page 18
STUD
WITH 30 BEND
CIRCUIT
[5.59]
Circuit & Terminal Diagrams
inches [millimeters]
Rocker
2 TERMINALS
5 TERMINALS
3 TERMINALS
4 TERMINALS
CIRCUIT BREAKER PROFILE CIRCUIT SCHEMATIC
ANSI
LINE
MAIN TERMINALS (SEE TABLE A)
LOAD
1.640
[41.66]
.020
TYP
[.51]
NC
NO
C
[9.91]
1
2
[19.81]
3
4
AUX. SWITCH TERMINALS
.205
[5.21]
.390
.780
.390
[9.91]
C NO
NC
.520
[13.21]
ALARM SWITCH TERMINALS & STD. AUX. SW. WITH VDE OR >30 AMPS
SWITCH ONLY (NO COIL)
LINE
LOAD
SWITCH ONLY (NO COIL) WITH AUXILIARY SWITCH
LINE
LOAD
LINE
LOAD
LINE
LOAD RELAY
RELAY
TABLE B
TERMINAL DESCRIPTION
MAIN
SHUNT,RELAY
&
DUAL COIL
AUX. SWITCH*
*AVAILABLE ON SERIES TRIP AND SWITCH ONLY CIRCUITS WHEN CALLED FOR ON MULTI-POLE UNITS, ONLY ONE AUX. SWITCH IS NORMALLY SUPPLIED, AS SHOWN IN MULTI-POLE INDENTIFICATION SHEME.
TAB (Q.C.)
SCREW TYPE TAB (Q.C.)
SCREW #8-32 W/UPTURNED LUGS
.093 TAB (Q.C.) .110 TAB (Q.C.) SOLDER TYPE
DEPTH
BEHIND PANEL
2.370[60.20]
2.402[61.01]
2.577[65.46]
2.734[69.44]
2.465[62.61]
2.559[65.00]
2.340[59.44]
C
NO
NC
SHUNT TRIP
SHUNT
RELAY TRIP
1
2
3
4
(NETZ)
(LAST)
LINE
(NETZ)
LOAD
(LAST)
LINE
(NETZ)
(NEBENSCHLUSS)
I >
LOAD
(LAST)
RELAY
(RELAIS)
I >
RELAY
(RELAIS)
IEC
LINE
LOAD
3
4
(4)
SHUNT
LINE
(RELAIS)
LOAD
(LAST)
CIRCUIT SCHEMATIC
LINE
LOAD
LINE
(NETZ)
I >
LOAD
(LAST)
LINE
(NETZ)
I > U >
LOAD
(LAST)
IEC
(NETZ) (3)
I >
(LAST)
(4)
C
NO
VOLTAGE
COIL
AUX
CODE
CODE
SWITCH
CIRCUIT
BC0
(3)
1
B
2
C
3 4
NC
H
0
K
0
AUX
CODE
A 0
C
A
NO
NC
(3)
D
0
E
(3)
1
F G
2
ANSI
CODE
SWITCH
LINE
1 2 3 4
LOAD
DUAL COIL; SERIES TRIP CURRENT COIL,
LINE
LOAD
0
SERIES TRIP
LINE
LOAD
SERIES TRIPSWITH
AUXILIARY SWITCH
C
NO
NC
SHUNT TRIP VOLTAGE COIL
VOLTAGE
COIL
.520
[13.21]
LINE
2.000
[50.80]
LOAD
BARRIER FOR
UL-RECOGNIZED MULTI-POLE
BREAKERS
18.
SEE TABLE-B
DEPTH BEHIND PANEL
.370
[9.40]
REF
.032 [.81]
TYP
[39.62]
1.640
REF
[41.66]
Notes: 1 Tolerance ±.020 [.51] unless otherwise specied. 2 Schematic shown represents current trip circuit. 3 Circuits shown for >30 amps / VDE.
.220
TYP
1.560
LINE
(NETZ)
TYP
LOAD
(LAST)
M6 STUD
1.936
[49.17]
PUSH-IN
1.350
[34.29]
.393
[9.96]
30
2 PLCS
SCREW TERMINAL
REF
1.560
[39.62]
TYP
Page 19
INDICATE “ON”
CIRCUIT CONFIGURATION
CIRCUIT CONFIGURATION
Dimensional Specs
inches [millimeters]
#6-32 [M3] THREAD X.195[4.95]DEEP 2 PLCS
1.660
[42.16]
.745
[18.92]
ROCKER ADAPTER
BRACKET WIDTH
AC1
LINE
2.156
[54.76]
.208
[5.27]
.945
[24.00]
1.245
[31.62]
1.245
[31.62]
.370
[9.40]
REF
.420
[10.67]
.120
[3.05]
.432
[10.97]
1.640
[41.66]
2.370
[60.20]
TAB TYPE
2.402
[61.20]
SCREW TYPE
.755
MAX
[19.18]
BREAKER
WIDTH
1.560
2.000
[39.62]
[50.80]
LOAD
TAB (Q.C.) TYPE TERMINALS IN SERIES TRIP CONCUIT CONFIGURATION SHOWN> FOR OTHER CONFIGURATIONS SEE CIRCUIT & TERMINAL DIAGRAMS
LINE
Rocker
INDICATE “OFF” & SINGLE COLOR
(INDICATE “OFF” SHOWN)
OPTIONAL “ROCKER GUARD”
LOAD
LINE
.432
[10.97]
CENTER-LINE OF ROCKER,& PANEL CUT-OUT
OPTIONAL “PUSH-TO RESET” ACTUATOR
AF1
LOAD
.945
[24.00]
2.309
[58.65]
1.660
[42.16]
TYP
AC2
[38.48]
AC3
2.265
[57.53]
MAX
1.515
MAX
LOAD
OPTIONAL “ROCKER GUARD” SHOWN IN DASHED LINES
.220
[5.59]
TYP
LINE
1.660
[42.16]
TYP
LOAD
.750
[19.05]
TYP
P(1) P(2) P(3)
(SEE NOTE 2)
REAR VIEW OF INDICATE “ON” SERIES TRIP W/AUX SWITCH
PANEL CUT-OUT
DETAIL
_
+ .005
1.260
[32.00]
_
[+ .13]
.200
[5.08]
LINE
LOAD
+ .005
_[+ .25]
-.000 _[+ .00]
.750
[19.05]
1.660
[42.16]
_
+ .005
.156 DIA[ 3.96] 2 HOLES
LINE
AF2
.055x.205 SLOTTED HOLE (ROCKER OFF ACTUATION)
ROCKER SHROUDED ON “OFF” POSITION SIDE, SHOWN IN DASHED LINES
[11.81]
[25.65].465
1.010
LOAD
_
[+ .13]
LINE
AF3
P(1) P(2) P(3)
(SEE NOTE 2)
REAR VIEW OF INDICATE “OFF” SERIES TRIP W/AUX SWITCH
19.
Notes: 1 Dimensions apply to all variations shown. Notice that circuit breaker line & load
terminal orientation on indicate OFF is opposite of indicate ON.
2 For pole orientation with horizontal legend, rotate front view clockwise 90°. 3 Tolerance ± 0.20 [.51] unless otherwise specied.
Page 20
INDICATE “ON”
PANEL CUTOUT DETAIL
Dimensional Specs
inches [millimeters]
Rocker Snap-In Bracket
FRONT PANEL SNAP-IN BRACKET , 0.96”[24.48 mm] wide bezel
AC1
ROCKER ADAPTER
BREAKER WIDTH
[65.99]
.960
[24.38]
MAX
2.598
.410
[10.41]
.320
[8.13]
.125
[3.18]
1.640
[41.66]
2.370
[58.93]
TAB TYPE
2.352
[59.74]
SCREW TYPE
FRONT PANEL SNAP-IN BRACKET , 0.744”[18.90 mm] wide bezel
AC1
2.598
[65.99]
.744
[18.90]
MAX
ROCKER ADAPTER
BREAKER WIDTH
FRONT PANEL SNAP-IN BRACKET , 0.96 ”[24.48 mm] wide bezel
.755
[19.18]
MAX
ROCKER ADAPTER
BREAKER WIDTH
LOAD
2.000
[50.80]
1.560
[39.62]
1.640
[41.66]
1.560
[39.62]
[50.80]
INDICATE “OFF”
.320
[8.13]
.755
[19.18]
MAX
BREAKER WIDTH
LINE
2.000
LOAD
TAB (Q.C.) TYPE TERMINALS IN SERIES TRIP CONCUIT CONFIGURATION SHOWN. FOR OTHER CONFIGURATIONS SEE CIRCUIT & TERMINAL DIAGRAMS
2.98
[65.99]
AF1
.483
[12.27]
.125
[3.18]
.320
[8.13]
OPTIONAL”ROCKER GUARD”
SHOWN IN DASHED LINES
.483
[12.27]
.125
[3.18]
20.
LINE
.125
[3.18]
.410
[10.41]
FRONT PANEL SNAP-IN BRACKET , 0.744 ”[18.90 mm] wide bezel
LOAD
LINE
Notes: 1 Dimensions apply to all variations shown. Notice that circuit breaker line & load terminal 2 For pole orientation with horizontal legend, rotate front view clockwise 90°.
Orientation on indicate “OFF” is opposite of indicate “ON” 3 Recommended panel thickness: .04 0 [1.02] to .100 [2.54] 4 Tolerance ±.020 [.51] unless otherwise specied.
.960
[24.38]
ROCKER ADAPTER
BREAKER WIDTH
2.598
[65.99]
.744
[18.90]
MAX
ROCKER ADAPTER
BREAKER WIDTH
.320
MAX
OPTIONAL “ROCKER GUARD”
SHOWN IN DASHED LINES
[8.13]
AF1
_
+ .010
.770
[19.56]
_
[+ .25]
_
+ .012
2.187
[55.55]
_
[+ .30]
Page 21
A-SERIES ROCKER
WITH AUX. SWITCH
PC Terminal Diagrams
inches [millimeters]
.125
[3.17]
TYP
.145
[3.68]
3 PL
.475
[12.07]
.370
[9.40]
REF
.120
[3.05]
2.309
[58.65]
1.245
[31.62]
[53.90]
.1640
[41.66]
.520
[13.21]
2.122
.375
[9.53]
TYP
[3.68]
.221
[5.61]
.145
3 PL
[39.57]
1.558
2.000
[50.80]
LOAD
NC
NO
C
.050 DIA[ 1.27]
(2 PL)
.050 DIA[ 1.27]
(2 PL)
2.122
[53.90]
.745
[18.92]
MAX
.096
[2.44]
(2 PL)
.096
[2.44]
(2 PL)
.544
[13.82]
.745
[18.92]
MAX
.590 DIA
[ 14.99]
1.010
[25.65]
.420
[10.67]
A-SERIES HANDLE
.693
[17.50]
OFF
ON
.060 DIA[ 1.52]
14 THRU HOLES
.0427
[1.19]
FIBER
[53.90]
1.640
[41.66]
.130
[3.30]
2.122
.096
[2.44]
(2 PL)
2.122
[53.90]
.030
[.762]
.632
[16.05]
2 PL
[3.17]
.221
[5.61]
+.003
.030
[.762]
TYP
[16.05]
_
+.003
TYP
.125
TYP
.375
[9.53]
[39.57]
.632
TYP
1.558
2.000
[50.80]
.544
[13.82]
.050
[1.27]
LINE
.755
[19.18]
MAX BREAKER
WIDTH
LOAD
LINE
.755
[19.18]
MAX BREAKER
WIDTH
.060 DIA[ 1.52]
17 THRU HOLES
21.
1.528
[38.81]
P.C. FOOT PRINT
Notes: 1 Drawing illustrates A-Series with VDE certication. 2 Tolerance ± 0.20 [.51] unless otherwise specied
.100
[2.54]
TYP
.295
[7.49]
.295
[7.49]
1.528
[38.81]
P.C. FOOT PRINT
.100
[2.54]
TYP
Page 22
Sample
Part Number
A
1
1-B
0-24
-
630
-
231-E
Selection
123 4 5 67 89
10
11
Ordering Scheme
ROCKER STYLE DESCRIPTIONS
Flat Rocker - UL 1077 Recognized
1. SERIES
A
2. ACTUATOR
Two Color Visi-Rocker 1 Indicate OFF, vertical legend 2 Indicate OFF, horizontal legend Single color 3 Vertical legend 4 Horizontal legend Push-To-Reset, Visi-Rocker 5 Indicate OFF, vertical legend 6 Indicate OFF, horizontal legend Push-To-Reset , Single color 7 Vertical legend 8 Horizontal legend
3. POLES
1 One 2 Two 3 Three
4. CIRCUIT
A 3 Switch Only (No Coil) G 4 Relay Trip (Voltage) B Series Trip (Current) H C Series Trip (Voltage) Voltage Coil D 4 Shunt Trip (Current) K E 4 Shunt Trip (Voltage) Voltage Coil F 4 Relay Trip (Current)
5. AUXILIARY / ALARM SWITCH
0 without Aux Switch 7 S.P.S.T., 0.110 Q.C. Term. 1 S.P.D.T., 0.093 Q.C. Term. (Gold Contacts) 2 S.P.D.T., 0.110 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term. 5 S.P.S.T., 0.093 Q.C. Term. 9 S.P.D.T., 0.187 Q.C. Term.
(Gold Contacts)
6. FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only 10 6 DC Instantaneous 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 20 6 50/60Hz Instantaneous 21 50/60Hz Ultra Short 22 50/60Hz Short 24 50/60Hz Medium 26 50/60Hz Long 30 DC, 50/60Hz Instantaneous
7. CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 095 0.095 210 0.100 215 0.150
22.
220 0.200
OR VOLTAGE COIL (NORMAL RATED VOLTAGE) 8
A06 6 DC A12 12 DC A18 18 DC A24 24 DC
Congure Complete Part Number > Browse Standard Parts >
1
2
225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750
A32 32 DC A48 48 DC A65 65 DC J06 6 AC
INDICATE”OFF”
CODE “1” , “5”
STYLE
VERTICAL
INDICATE COLOR
LINE
LOCATION
CODE “2” , “6”
STYLE
HORIZONTAL
LINE LINE
4,5
Dual Coil with Shunt Trip
4,5
Dual Coil with Relay Trip
6,7
31 DC, 50/60Hz Ultra Short 32 DC, 50/60Hz Short 34 DC, 50/60Hz Medium 36 DC, 50/60Hz Long 42 9 50/60Hz Short, High-inrush 44 9 50/60Hz Medium,
High-inrush
46 9 50/60Hz Long, High-inrush 52 9 DC, Short, High-inrush 54 9 DC, Medium, High-inrush 56 DC, Long, High-inrush
420 2.000 522 2.250 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500
J12 12 AC J18 18 AC J24 24 AC J48 48 AC
SINGLE COLOR
CODE “3” , “7”
LINE
CODE “4” , “8”
611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 8 35.000 640 8 40.000 645 8 45.000 650 8 50.000
J65 65 AC K20 120 AC L40 240 AC
8. TERMINAL
12
1
Push-On 0.250 Tab (Q.C.)
2
Screw 8-32 with upturned
lugs
13
Screw 8-32 (Bus Type)
3 4
Screw 10-32 with upturned
lugs
5 13 Screw 10-32 (Bus Type) 6
Screw 8-32 with upturned
lugs & 30° bend
7 Screw 8-32
& 30° bend 8 Screw 10-32 with upturned lugs & 30° bend
9
Screw 10-32 (Bus Type)
& 30° bend
B
Screw M5 with upturned lugs
11
(Bus Type)
C Screw, M4 with upturned lugs
13
Screw M4 (Bus Type)
E F Screw M5 with upturned lugs
& 30° bend
G Screw M5 (Bus Type) & 30° bend H 13 Screw M5 (Bus Type) L 14 0.250 Q.C./ Solder Lug M 13 M6 Threaded Stud P 15 Printed Circuit Board Terminals Q Push-In Stud R Screw, M4 with upturned lugs
& 30° Bend
16
S
Push-On 0.110 Tab (Q.C.)
& 30° bend
T Screw, M4 with upturned lugs
9. ACTUATOR COLOR & LEGEND
Actuator or Marking: Marking Color Visi-Color White B 1 Black White
Black D 2 White n/a Red G 3 White Red Green J 4 White Green Blue L 5 White Blue
Yellow N 6 Black Yellow
Gray Q 7 Black Gray Orange S 8 Black Orange
10. MOUNTING / BARRIERS
STANDARD ROCKER BEZEL Threaded Insert, 2 per pole BARRIERS FLAT ROCKER ACTUATOR 1 6-32 x 0.195 inches no A 6-32 X 0.195 inches (multi-pole units only) yes 2 ISO M3 x 5mm no B ISO M3 x 5mm (multi-pole units only) yes RECESSED OFF SIDE ROCKER ACTUATOR 5 6-32 x 0.195 inches no E 6-32 x 0.195 inches (multi-pole units only)yes 6 ISO M3 x 5mm no F ISO M3 x 5mm (multi-pole units only) yes PUSH-TO-RESET BEZEL,Threaded Insert, 2 per pole 3 6-32 x 0.195 inches no C 6-32 x 0.195 inches (multi-pole units only) yes 4 ISO M3 x 5mm no D ISO M3 x 5mm (multi-pole units only) yes
17
ON-OFF Dual
17
Single Color Visi-Rocker
18
19
11. AGENCY APPROVAL
C UL Recognized & CSA Accepted E TUV Certied, UL Recognized & CSA Accepted I UL Recognized STD 1077, UL Recognized 1500
& CSA Accepted
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded. 2 Multi-pole breakers have all breakers identical except when specifying Auxiliary
switch and/or mixed poles, and have one rocker per breaker. 3 Switch Only circuits, rated up to 50 amps & 3 poles. Only available when tied to a protected pole. For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. 4 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum. 5 Consult factory for Dual Coil options, as special catalog number is required. With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only. 6 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A, are supplied with standard half shells. 30-50A are supplied with extended boat (B-Style) half shells. 7 On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole. 8 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes 10 & 20. 9 Available with Circuit Codes B & D only. UL Recognized, CSA Accepted & TUV Certied to 50 amps. 10 UL Recognition, CSA Acceptance & TUV Certication available in one and two pole breakers. 11 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q.
12 Terminal Code 1: Available up to 30 amps, but not recommended over 20 amps. 13 Terminal Codes 3, 5 E & H (Bus Type) with TUV, are supplied with Lock Washers;
Terminal Code M (M6 Threaded Stud) with TUV is supplied with Lock and Flat Washers. These breakers are only TUV Certied when the washers are used. 14 TUV Cert. available up to 12 amps. UL Rec. & CSA Accepted available up to 30 amps. 15 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 50 amps with UL Recognition, CSA Accepted & TUV Certication, with Circuit Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board) are avail able up to 40 amps with UL Recognition and CSA Accepted with Circuit Codes A, B & C. 16 Terminal Code S used on voltage coil circuit constructions only. 17 Color shown is visi & legend with remainder of rocker black, Dual = ON-OFF/I-O legend. 18 Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 &
8. Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator codes 5 & 6. 19 Recessed “off-side” available with actuator codes 1, 2, 3 & 4. Legends on rocker are available in ink stamping only.
(ignition protected),
Page 23
Sample
Part Number
A11-B
0-14
-
630
-
231-M
T
Selection
123 4 5 67 89
10 1112
Ordering Scheme
ROCKER STYLE DESCRIPTIONS
HORIZONTAL
VERTICAL
Flat Rocker - UL 489A Listed
1. SERIES
A
2. ACTUATOR
Two Color Visi-Rocker 1 Indicate OFF, vertical legend 2 Indicate OFF, horizontal legend Single color 3 Vertical legend 4 Horizontal legend Push-To-Reset, Visi-Rocker 5 Indicate OFF, vertical legend 6 Indicate OFF, horizontal legend Push-To-Reset , Single color 7 Vertical legend 8 Horizontal legend
3. POLES
1 One 2 Two 3 Three
1
INDICATE”OFF”
CODE “1” , “5”
STYLE
INDICATE COLOR
LINE
LOCATION
CODE “2” , “6”
STYLE
LINE LINE
2
SINGLE COLOR
CODE “3” , “7”
LINE
CODE “4” , “8”
4. CIRCUIT
B Series Trip (Current)
5. AUXILIARY / ALARM SWITCH
0 without Aux Switch 7 S.P.S.T., 0.110 Q.C. Term. 1 S.P.D.T., 0.093 Q.C. Term. (Gold Contacts) 2 S.P.D.T., 0.110 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term. 9 S.P.D.T., 0.187 Q.C. Term.
3
6. FREQUENCY & DELAY
11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long
52 DC, Short, High-inrush 54 DC, Medium, High-inrush 56 DC, Long, High-inrush
7. CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 095 0.095 210 0.100 215 0.150 220 0.200
225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750
420 2.000 522 2.250 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500
611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 6354 35.000 6404 40.000 6454 45.000 6504 50.000
9. ACTUATOR COLOR & LEGEND
Actuator or Marking: Marking Color Visi-Color White B 1 Black White
Black D 2 White n/a Red G 3 White Red Green J 4 White Green Blue L 5 White Blue
Yellow N 6 Black Yellow
Gray Q 7 Black Gray Orange S 8 Black Orange
10. MOUNTING / BARRIERS
STANDARD ROCKER BEZEL BARRIERS Threaded Insert, 2 per pole FLAT ROCKER ACTUATOR 1 6-32 x 0.195 inches no A 6-32 X 0.195 inches (multi-pole units only) yes 2 ISO M3 x 5mm no B ISO M3 x 5mm (multi-pole units only) yes RECESSED OFF SIDE ROCKER ACTUATOR 5 6-32 x 0.195 inches no E 6-32 x 0.195 inches (multi-pole units only) yes 6 ISO M3 x 5mm no F ISO M3 x 5mm (multi-pole units only) yes PUSH-TO-RESET BEZEL,Threaded Insert, 2 per pole 3 6-32 x 0.195 inches no C 6-32 x 0.195 inches (multi-pole units only) yes 4 ISO M3 x 5mm no D ISO M3 x 5mm (multi-pole units only) yes
11
ON-OFF Dual
11
Single Color Visi-Rocker
12
11. MAXIMUM APPLICATION RATING
M 80 DC
12.AGENCY APPROVAL
T UL489A Listed J UL489A Listed, TUV Certied
Notes: 1 Push-To-Reset actuators have OFF portion of rocker shrouded. 2 Multi-pole breakers have all breakers identical except when specifying Auxiliary
switch and/or mixed poles, and have one rocker per breaker. 3 Auxiliary Switch breakers with Series Trip circuits: ≤ 30A, are supplied with standard half shells. 30-50A are supplied with extended boat (B-Style) half shells. 4 VDE Certication available with single pole breakers only. UL489A Listing avail able with one and two pole breakers. 5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q. 6 Terminal Code 1 (Push-On) available up to 25 amps with TUV or VDE Certication and 30 amps with UL489A Listing, but is not recommended over 20 amps. 7 Terminal Codes 3, 5 and H (Bus Type) with TUV or VDE, are supplied with Lock Washers, and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only TUV or VDE Certied when the washers are used. 8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certication and 50 amps with UL489A Listing. 9 Terminal Code Q not available with VDE certication. 10 Color shown is Visi and Legend with remainder of rocker black. Dual = ON-OFF/I­ O legend. 11 Legend on Push-to-reset bezel/shroud is white with single color actuator codes R & U. 12 Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actua tor codes N & O. Rockerguard available with actuator codes C through K
Congure Complete Part Number > Browse Standard Parts >
8. TERMINAL
2
Screw 8-32 with upturned
lugs
3 7 Screw 8-32 (Bus Type) 4
Screw 10-32 with upturned
lugs
5 7 Screw 10-32 (Bus Type) 6
Screw 8-32 with upturned
lugs & 30° bend
23.
8 Screw 10-32 with upturned
lugs & 30° bend
11
9
Screw 10-32 (Bus Type)
& 30° bend
B
Screw M5 with upturned lugs
F Screw M5 with upturned lugs G Screw M5 (Bus Type) & 30° bend H Screw M5 (Bus Type) M 7 M6 Threaded Stud P 8 Printed Circuit Board Terminals Q 9 Push-In Stud
Page 24
INDICATE “OFF” & SINGLE COLOR
ROCKER
Dimensional Specs
inches [millimeters]
(INDICATE “OFF” SHOWN)
2.402
[61.01]
SCREW TYPE
2.370
[60.20]
TAB TYPE
1.640
[41.66]
.755
[19.18]
MAX
BREAKER WIDTH
A11
LOAD
2.000
[50.80]
1.560
[39.62]
LINE
Flat Rocker
.370
[9.40]
REF
1.245
[31.62]
.208
[5.27]
#6-32 [M3] THREAD X.195[4.95]DEEP 2 PLCS
1.010
[25.65]
1.660
[42.16]
2.309
[58.65]
TAB (Q.C.) TYPE TERMINALS IN SERIES TRIP CONCUIT CONFIGURATION SHOWN. FOR OTHER CONFIGURATIONS SEE CIRCUIT & TERMINAL DIAGRAMS
A12
1.660
[42.16]
TYP
.750
[19.05]
TYP
1.515
[38.48]
MAX
A13
LOAD
LINE
.220
[5.59]
TYP
1.660
[42.16]
.120
[3.05]
CENTER-LINEOF ROCKER &PANEL CUT-OUT
PANEL CUT-OUT
DETAIL
_
+ .005
1.260
[32.00]
_
[+ .13]
.200
[5.08]
LOAD
LINE
.397
[10.08]
+ .005
_[+ .25]
-.000 _[+ .00]
.750
[19.05]
1.660
[42.16]
_
+ .005
.156 DIA[ 3.96] 2 HOLES
1.245
[31.62]
.745
[18.92]
MAX
ROCKER ADAPTER
BRACKET WIDTH
_
[+ .13]
SIDE VIEW OF BREAKER IN THE
“ON” POSITION
PUSH-TO-RESET
ACTUATOR
A51
LOAD
.515
[13.08]
2.309
[58.65]
24.
P(1) P(2) P(3)
2.265
[57.53]
MAX
Notes: 1 For pole orientation with horizontal legend, rotate front view clockwise 90°. 2 Tolerance ± 0.20 [.51] unless otherwise specied.
(SEE NOTE 2)
REAR VIEW OF INDICATE “OFF” SERIES TRIP W/AUX SWITCH CIRCUIT CONFIGURATION
.055x.205
SLOTTED HOLE
(ROCKER OFF ACTUATION)
ACTUATOR SIDE VIEW
(SURFACE CONTOURS)
FLAT ROCKER
LINE
ROCKER SHROUDED ON “OFF” POSITION SIDE, SHOWN IN DASHED LINES
RECESSED OFF SIDE
1.010
[25.65]
Page 25
Sample
Part Number
AY1-B
0-14
-
630
-
231-M
T
Selection
123 4 5 67 89
10 1112
Ordering Scheme
Recessed Paddle
1. SERIES
A
2. ACTUATOR
Y Single Color Recessed Paddle Actuator with Vertical Legends
3. POLES
1 One 2 Two 3 Three
1
2
4. CIRCUIT
A Switch-Only (No Coil) F Relay Trip (Current) B Series Trip (Current) G Relay Trip (Voltage) C Series Trip (Voltage) H Dual Coil with Shunt Trip Voltage Coil D Shunt Trip (Current) K Dual Coil with Shunt Trip Current Coil E Shunt Trip (Voltage)
5. AUXILIARY SWITCH
0 without Aux Switch 1 S.P.D.T. with 0.093 Q.C. Terminals 2 S.P.D.T. with 0.110 Q.C. Terminals 3 S.P.D.T. with 0.139 Solder Lug Terminals 5 S.P.D.T. with 0.093 Q.C. Terminals (Gold Contacts) 6 S.P.S.T.-N.O. with 0.139 Solder Lug Terminals 7 S.P.S.T.-N.O. with 0.110 Q.C. Terminals (Gold Contacts) 8 S.P.S.T.-N.O. with 0.187 Q.C. Terminals 9 S.P.D.T. with 0.187 Q.C. Terminals
6. FREQUENCY & DELAY
3 DC, 50/60 Hz Switch Only 10 DC Instantaneous 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 20 50/60 Hz Instantaneous 21 50/60 Hz Ultra Short 22 50/60 Hz Short
7. CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 095 0.095 210 0.100 215 0.150 220 0.200
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)
A06 6 DC A12 12 DC A18 18 DC A24 24 DC
225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750
A32 32 DC A48 48 DC A65 65 DC J06 6 AC
3
24 50/60 Hz Medium 26 50/60 Hz Long 42 50/60 Hz Short High-inrush 44 50/60 Hz Medium High-inrush 46 50/60 Hz Long High-inrush 52 DC, Short, High-inrush 54 DC, Medium, High-inrush 56 DC, Long, High-inrush
4
420 2.000 522 2.250 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500
J12 12 AC J18 18 AC J24 24 AC J48 48 AC
611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 35.000 640 40.000 645 45.000 650 50.000
J65 65 AC K20 120 AC L40 240 AC
8. TERMINAL
1 Push-On 0.250 Tab (Q.C.) 2
Screw 8-32 with upturned
lugs
3 7 Screw 8-32 (Bus Type) 4
Screw 10-32 with upturned
lugs
5 7 Screw 10-32 (Bus Type) 6
Screw 8-32 with upturned
lugs & 30° bend
7 Screw 8-32
& 30° bend 8 Screw 10-32 with upturned lugs & 30° bend
9
Screw 10-32 (Bus Type)
& 30° bend
(Bus Type)
9. ACTUATOR COLOR & LEGEND
Actuator Color I-O ON-OFF Dual Legend Color
White A B 1 Black Black C D 2 White Red F G 3 White Green H J 4 White Blue K L 5 White Yellow M N 6 Black Gray P Q 7 Black Orange R S 8 Black
B
Screw M5 with upturned lugs
C Screw, M4 with upturned lugs F Screw M5 with upturned lugs G Screw M5 (Bus Type) & 30° bend H Screw M5 (Bus Type) M M6 Threaded Stud P Printed Circuit Board Terminals Q Push-In Stud R Screw, M4 with upturned lugs
& 30° Bend
S Screw, M5 with upturned lugs T Screw, M4 with upturned lugs
5
10. MOUNTING / BARRIERS
BARRIERS
1 6-32 x 0.195 inches no A 6-32 X 0.195 inches (multi-pole units only) yes 2 ISO M3 x 5mm no B ISO M3 x 5mm (multi-pole units only) yes
11. MAXIMUM APPLICATION RATING
A 65 VDC C 120/240 VAC (Available only on 2 or 3-Pole units) K 120 VAC M 80 DC
12.AGENCY APPROVAL
A Without Approvals C UL Recognized and CSA Accepted T UL 489A
Notes: 1 A l l s t an d ar d c a ta l og nu m be rs ar e s u p pl ie d w i t h V e r ti c al Le ge n ds . F o r H or i zo n ta l
or other non-standard legends, choose “X” and order as a special catalog number.
2 For rating (T) 2 & 3 Pole not available. 3 Frequency and Time Delay ratings of (03, 20, 21, 22, 24, 26, 42, 44, 46) not
available with approval T. 4 Voltage Coil Ratings starting with (J, K, or L) not available with approval T. 5 “ O FF an d/ o r “ O ” L e ge n ds a r e o n B r a c k et an d a re on ly vi si b le w h e n th e P a dd l e Actuator is in the off position. 6 Maximum Application Ratings (C & K) not available with approval T. 7 Not all approvals are available in all constructions. Consult factory for details.
Congure Complete Part Number > Browse Standard Parts >
7
6
25.
Page 26
Dimensional Specs
inches [millimeters]
Recessed Paddle
#6-32 [M3] THREAD
X .105 [4.95] DEEP
2 PLCS
BREAKER SHOWN IN
THE OFF POSITION
.745
[18.92]
.755
.750
[19.05]
[19.18]
MAX
LOAD
LINE
TYP
.243
1.240
[31.50]
.380
[9.65]
[6.17]
2.010
[51.05]
2.378
[60.40]
TAB TYPE
2.410
[61.21]
SCREW TYPE
BREAKER SHOWN IN
THE OFF POSITION
1.560
[39.62]
2.000
[50.80]
2.10
[5.33]
1.660
[42.16]
MAX
.750
[19.05]
TYP
1.515
[38.48]
MAX
2.265
[57.53]
MAX
Notes: 1 Tolerance ± 0.20 [.51] unless otherwise specied
1.260 + .005
-
[32.00+ .12]
-
.848
[21.54]
[5.08]
.200
2.888
[73.36]
PANEL CUT-OUT
DETAIL
.156 + .005
[3.96 + .12]
2 HOLES
[42.16]
-
-
1.660
.750
[
19.05
+ .010
-.000 + .25
- .00
]
26.
Page 27
Authorized Sales Representatives and Distributors
Click on a region of the map below to nd your local representatives and distributors or visit www.carlingtech.com/ndarep.
CANADA
USA
MEXICO
SOUTH
AMERICA
EUROPE
AFRICA
MIDDLE
EAST
ASIA-PACIFIC
OCEANIA
27.
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power distribution systems. With six ISO9001 and IATF16949 registered manufacturing facilities and technical sales ofces worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than
manufacture electrical components, they engineer powerful solutions! To learn more about Carling please visit www.carlingtech.com/company-prole.
To view all of Carling’s environmental, quality, health & safety certications please visit
www.carlingtech.com/environmental-certications.
© Carling Technologies, Inc. Carling, Visi-Rocker are registered trademarks of Carling Technologies, Inc. in the U.S. and other countries.