Datasheet 116121009 Specification

Page 1
Low voltage - Energy and cabling
H07BQ-F
Structure and electrical, physical, mechanical requirements:
Halogen free: IEC 60754-1 No corrosive gases: IEC 60754-2 Oil resistant:
Approval IMQ: certificate CA01.00651 Low Voltage Directive: 2014/35/EU RoHS Directive: 2011/65/EU
EN 50525-2-21
reaction to fire
CPR COMPLIANT
REGULATION 305/2011/EU
Standard: EN 50575:2014+A1:2016 Class: E Classification: EN 13501-6 Flame propagation: EN 60332-1-2 Notified Body: 0051 - IMQ
ca
2017
www.latrivenetacavi.com
review n° 012 date 06/05/20
Page 2
Description
Use and installation method
•
Conductor: class 5, flexible, plain copper wire
•
Insulation: EPR rubber compound, quality EI6
•
Filler (optional): LS0H rubber, penetrating between the cores
•
Sheath: LS0H TMPU polyurethane
•
Colour: orange
LS0H = Low Smoke Zero Halogen
Functional characteristics
•
Rated voltage Uo/U: 450/750 V (max 480/820 V a.c.) 560/1120 V (max 620/1240 V d.c.)
•
Max. operating temperature: 90°C
•
Min. operating temperature: -60°C (without mechanical shocks)
•
Max. short circuit temperature: 250°C
Special features
Good resistance to mechanical stress and abrasion. Good flexibility and behaviour at low temperatures. Good resistance to UV (ISO 4892-2). Absence of halogens. Sea water resistant.
Reference Guide EN 50565: They can be used both indoors and outdoors, in dry, damp or wet conditions. Suitable for heavy-duty uses and to power industrial and farm machinery. For connections undergoing moderate mechanical stresses, such as those in power tools (drills, circular saws, electrical home appliances) and heaters, as long as they do not touch hot parts and are not exposed to heat radiation. Avoid skin contact if they are used at high operating temperatures. Suitable to be used for fixed installations on temporary building fronts and workmen’s shelter at work sites. Suitable up to 1000 V A.C. for fixed installations and duly shielded (in ducts and equipment). Not suitable for underground laying, even if shielded.
Reference Construction Products Regulation 305/2011 EU and Standard EN 50575: The cable is suitable for the supply of electricity in buildings and other civil engineering works.
Installation conditions
•
Minimum installation temperature: -40°C
•
Recommended minimum bending radius: 6 times the cable diameter for mobile use, 4 times for static use
•
Recommended maximum tensile stress: 15 N/mm² of the cross-section of the copper for mobile use, 50 N/mm² for static use.
Colours of the cores
TWO-CORE THREE-CORE FOUR-CORE FIVE-CORE
or
or
or
Marking
LTC IEMMEQU ◄HAR► H07BQ-F [form.] Eca [order number] [year] Made in Italy [metric]
review n° 012 date 06/05/20
Page 3
Two-core
Formation
2
n° x mm
2 x 1 1,3 0,6 0,9 9,0 19,5 75 19
2 x 1,5 1,5 0,8 1,0 9,8 13,3 90 26
2 x 2,5 2,0 0,9 1,1 11,6 7,98 130 36
2 x 4 2,5 1,0 1,2 13,7 4,95 185 49
2 x 6 3,0 1,0 1,3 15,1 3,30 235 63
2 x 10 4,0 1,2 2,0 19,9 1,91 390 86
2 x 16 5,0 1,2 2,1 22,8 1,21 550 115
N.B. Permissible current rating values are according to:
- two-phase circuit for two-core cables
Approx.
conductor
Ø
mm mm mm mm /km kg/km A
Average insulation thickness
Average
sheath
thickness
Max.
external
Ø
Max.
electrical
resistance
at 20°C
Approx.
cable
weight
Three-core
Formation
(*)
n° x mm
Approx.
conductor
Ø
2
mm mm mm mm /km kg/km A
Average insulation thickness
Average
sheath
thickness
Max.
external
Ø
Max.
electrical
resistance
at 20°C
Approx.
cable
weight
Free laying
at 30°
Free laying
at 30°
3G1 1,3 0,6 0,9 9,5 19,5 90 17
3G1,5 1,5 0,8 1,0 10,4 13,3 110 23
3G2,5 2,0 0,9 1,1 12,4 7,98 160 32
3G4 2,5 1,0 1,2 14,5 4,95 220 42
3G6 3,0 1,0 1,4 16,3 3,30 305 54
3G10 4,0 1,2 2,1 21,4 1,91 500 75
3G16 5,0 1,2 2,3 24,7 1,21 720 100
(*) also available without the green/yellow N.B. Permissible current rating values are according to:
- three-phase circuit for three-core cables
review n° 012 date 06/05/20
Page 4
Four-core
Formation
(*)
2
n° x mm
4G1 1,3 0,6 0,9 10,7 19,5 115 17
4G1,5 1,5 0,8 1,1 11,6 13,3 140 23
4G2,5 2,0 0,9 1,2 13,8 7,98 195 32
4G4 2,5 1,0 1,3 16,2 4,95 280 42
4G6 3,0 1,0 1,5 18,1 3,30 385 54
4G10 4,0 1,2 2,2 23,6 1,91 630 75
4G16 5,0 1,2 2,3 27,0 1,21 900 100
(*) also available without the green/yellow N.B. Permissible current rating values are according to:
- three-phase circuit for three-core cables
Approx.
conductor
Ø
mm mm mm mm /km kg/km A
Average insulation thickness
Average
sheath
thickness
Max.
external
Ø
Max.
electrical
resistance
at 20°C
Approx.
cable
weight
Five-core
Formation
(*)
n° x mm
Approx.
conductor
Ø
2
mm mm mm mm /km kg/km A
Average insulation thickness
Average
sheath
thickness
Max.
external
Ø
Max.
electrical
resistance
at 20°C
Approx.
cable
weight
Free laying
at 30°
Free laying
at 30°
5G1 1,3 0,8 1,0 11,9 19,5 145 17
5G1,5 1,5 0,8 1,1 12,7 13,3 170 23
5G2,5 2,0 0,9 1,3 15,3 7,98 240 32
5G4 2,5 1,0 1,4 17,9 4,95 350 42
5G6 3,0 1,0 1,6 20,0 3,30 475 54
5G10 4,0 1,2 2,3 25,9 1,91 775 75
5G16 5,0 1,2 2,5 30,0 1,21 1110 100
(*) also available without the green/yellow N.B. Permissible current rating values are according to:
- three-phase circuit for three-core cables
review n° 012 date 06/05/20