DATASENSOR S5 Instruction Manual

CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
S5 SERIES
INSTRUCTION MANUAL
CONTROLS
OUTPUT LED
The red LED indicates the output status.
STABILITY LED (S5-5-x)
TRIMMER (S5-x-B3/C30/C35/C60/D14/E1/F8/F12)
The trimmer can be used to adjust sensitivity; the operating distance increases turning the trimmer clockwise.
WARNING: The trimmer rotation is limited to 270° by a mechanical stop. Do not apply excessive torque when adjusting (max 40 Nmm).
POWER ON LED (S5-x-G8/G12)
The red LED indicates that the sensor is operating.
CONNECTIONS
S5-5-x (4 wires) S5-5-G8/G12 (4 wires)
BROWN
WHITE BLACK
BLUE
BLACK 1
BLUE
BROWN
BLACK BLUE
1 4
1
10 … 30 Vdc
+
2
TEST +
4
TEST -
3
0 V
15 … 264 Vac 48 … 62 Hz
2
1
+
4
3
10 … 30 Vdc
PNP LOAD 150mA 0 V
BROWN
1
2
4
NPN
LIGHT DARK MODE MODE
WHITE
BLACK
BLUE WHITE
BLACK
10 … 30 Vdc
150mA
S5-1-x S5-1-G8
BLACK 1
2
BLUE
3
WHITE
BROWN
BLACK
BLUE
1
+
4
3
M12 CONNECTOR
+
+
2
+
150mA
4
PNP
15 … 264 Vac 48 … 62 Hz
LOAD 100mA max.
S5-5-x (3 wires)
10 … 30 Vdc
NPN LOAD 150mA
0 V
2 3
DIMENSIONS
AC AXIAL VERSION
23.5
22
M O D E L S
with trimmer
without trimmer
52
X1
75
L
RADIAL VERSION
23.5
22
OUTPUT
M O D E L S
mod. F/G
mod. B
L
19.5 20.5 16.5
8
L
3
M12
CONNECTOR
3 32
16.5
X1
TRIMMER
M18x1
4
8
18.8
55
11.9
M18x1
TRIMMER
4
8
OUTPUT LED POWER ON LED POWER ON LED
3.2
42 65
4.5
L
STABILITY LED
9.5
other models
DC AXIAL VERSION
STABILITY LED OUTPUT LED
16.6
5
16.6
M12
FIBRE OPTIC VERSION
STABILITY LED
16.6
L X1 X2
2222
without trimmer
55 32
3
23.5
M O D E L S
with trimmer
(except mod. B)
23.5
4.5
65 42
3
OUTPUT LED
4.5
mod. B
68 42
6
16.6
3
CONNECTOR
13 37.4
M12
11.9
L
X1X2
TRIMMER
M18x1
4
8
70.4
TRIMMER
4
8
16.6
18.8
16.6
M12
11.9
16.6
M18x1
mm
TECHNICAL DATA
Power supply: 10 … 30 Vdc limit values 15 … 264 Vac (48 … 62 Hz) limit values Ripple: 2 Vpp max. ­Current consumption (output current excluded): Output: NPN/PNP selectable; 30 Vdc max.
Output current: 150 mA max. Output saturation voltage: 2.5 V max. / 1.2 V max. mod. L2
Rated insulation voltage: - 250 Vac (test 1500 Vac 1 minutes) Output leakage: Response time: 1 ms max.
Switching frequency: 500 Hz max.
Indicators: OUTPUT LED (RED) / STABILITY LED (GREEN) / POWER ON LED (RED) mod. G8/G12 Setting: sensitivity trimmer mod. B3/C30/C35/C60/D14/E1/F8/F12 Operating temperature: -25 … 55 °C Storage temperature: -25 … 70 °C Electric shock protection: Class 2 Class 1 Operating distance (minimum):
Emission type: INFRARED (880 nm) / RED (660 nm) mod. B3/D14/E1 Ambient light rejection: according to EN 60947-5-2 Vibration: 0.5 mm amplitude, 10 … 55 Hz frequency, for every axis (EN60068-2-6) Shock resistance: 11 ms (30 G) 6 shock for every axis (EN60068-2-27) LIGHT/DARK selection: by inverting the power supply wires (4 wires versions) Housing: ABS UL 94V-O Connector: Polycarbonate ABS UL 94V-O Lenses: PMMA plastic Protection class: IP67 Connections: Weight: 100 g. max. cable versions / 25 g. max. connector versions
AXIAL VERSION RADIAL VERSION AXIAL VERSION RADIAL VERSION
(short-circuit protection at 200 mA)
2 ms max. mod. F8/F12/G8/G12
250 Hz max. mod. F8/F12/G8/G12
A4: 0.1 … 4 m on R2 B3: 0.1 … 3 m on R2
C10: 1 … 10 cm C35: 1 … 35 cm
C60: 1… 60 cm D14: 10 … 20 mm D15: 10 … 20 mm
F12/G12: 0 … 12 m
L2: 2 … 15 mm
T1: 0.1 … 0.8 m on R2
E1 (OF-18): 22 mm E1 (OF-19): 85 mm
S5-5-x S5-1-x
30 mA max.
SCR + bridge rectifier – 264 Vac
50μA at 30 Vdc
6 ms max. mod. L2
175 Hz max. mod. L2
A4: 0.1 … 4 m on R2 B3: 0.1 … 3 m on R2
C10: 1 … 10 cm C35: 1 … 35 cm
C60: 1… 60 cm
D15: 10 … 20 mm
2 m cable 5 mm / M12 4-pole connector
10 mA max.
100 mA max.
1mA max. at 264 Vac
20 ms max.
25 Hz max.
A2: 0.1 … 2 m on R2
C8: 1 … 8 cm
C30: 1 … 30 cm D14: 10 … 20 mm D15: 10 … 20 mm
F8/G8: 0 … 8 m
SETTING
The following procedures are valid for LIGHT mode operation. Alignment S5-x-A2/A4/B3/T1
Position the sensor and reflector on opposite sides. Find the points where the red LED (OUT) is switched ON and OFF in both vertical and horizontal positions, and fix the sensor in the centre between these points. B/T models: Turn the sensitivity trimmer to maximum; if necessary reduce sensitivity in order to detect very small or transparent targets. In order to improve alignment, repeat the procedure detailed above whilst progressively reducing the sensitivity.
Alignment S5-x-F8/G8/F12/G12/E1 (E/R fibres) Position the sensors on opposite sides. Turn the sensitivity trimmer to maximum. Find the points where the red LED (OUT) is switched ON and OFF in both vertical and horizontal positions, and fix the sensor in the centre between these points. Optimum operation is obtained when both LEDs switch ON.
6.2
If necessary, reduce sensitivity using the trimmer, in order to detect very small targets. In order to improve alignment, repeat the procedure detailed above whilst progressively reducing the sensitivity.
Alignment S5-x-C30/C35/C60/D14/E1 (proximity fibres) Position the sensor and turn the sensitivity trimmer at minimum: the green LED is ON and the red LED is OFF. Place the target opposite the sensor. Turn the sensitivity trimmer clockwise until the red LED turns ON (Target detected state, pos.A). Remove the target, the red LED turns OFF. Turn the trimmer clockwise until the red LED turns ON (Background detected state, pos.B). The trimmer reaches maximum if the background is not detected. Turn the trimmer to the intermediate position C, between the two positions A and B. The green LED must be ON.
Alignment S5-x-C8/C10/D15/L2 The operating distance range of these sensors is factory preset: please consider this feature when positioning.
A
C
B
MAX
MIN
TEST FUNCTION (S5-x-G8/G12)
The TEST+ and TEST- inputs can be used to inhibit the emitter and verify that the system is correctly operating. The receiver output should switch when the test is activated while the beam is uninterrupted. The inputs activating voltage range is 10 … 30 Vdc, whilst respecting the polarity.
DECLARATION OF CONFORMITY
We DATASENSOR S.p.A. declare under our sole responsibility that these products are conform to the 2004/108/CE, 2006/95/CE Directives and successive amendments.
WARRANTY DATASENSOR S.p.A. warrants its products to be free from defects. DATASENSOR S.p.A. will repair or replace, free of charge, any product found to be defective during the warranty period of 36 months from the manufacturing date. This warranty does not cover damage or liability deriving from the improper application of DATASENSOR products.
DATASENSOR S.p.A. Via Lavino 265 40050 Monte S. Pietro - Bologna - Italy Tel: +39 051 6765611 Fax: +39 051 6759324 http://www.datasensor.com e-mail: info@datasensor.co m
DATASENSOR S.p.A. cares for the environment: 100% recycled paper. DATASENSOR S.p.A. reserves the right to make modifications and improvements without prior notification.
826000176 Rev.F
Loading...