DataSafe HX Series, 12HX205, 12HX300, 12HX330, 12HX400 Installation, Operation And Maintenance Instructions

...
DATASAFE® HX TOP TERMINATED BATTERIES
DataSafe® HX Top Terminated Batteries
6 and 12 Volt
®
HX
Battery Installation, Operation and Maintenance Instructions
Available exclusively from EnerSys®, the world leader in stored power solutions.
Important
Please read this manual immediately upon receipt of battery before unpacking and installing. Failure to comply with these instructions will render any warranties null and void. The term battery within this literature pertains to (1) 12 Volt battery consisting of (6) individual cells or (1) 6 Volt battery consisting of (3) individual cells.
Care for Your Safety
Dispose at registered waste handling facility
Battery must be recycled
Handling
DataSafe® HX batteries are supplied in a fully charged state and must be unpacked carefully to avoid very high short-circuit currents between terminals of opposite polarity. Use care when handling and moving batteries. Appropriate lifting equipment must be used.
Other safety precautions that need to be taken
No smoking, no naked flames, no sparks
Clean all acid splash in eyes or on skin with plenty of clean water.
Then seek medical help. Acid on clothing is to be washed with water.
Receiving the Shipment
Carefully examine the battery shipment upon arrival for any signs of transit damage and that it agrees with the materials list or packing slip. Be very careful not to inadvertently discard any accessories contained in the packing material.
Batteries contain sulfuric acid in glass fiber separators.
Use rubber gloves when handling broken or damaged containers in case of acid leakage.
Storage
Store D
ataSafe® HX batteries in a dry, clean and preferably cool location.
Since the batteries are supplied charged, storage time is limited. In order to easily charge the batteries after prolonged storage, it is advised not to store it more than:

6 months at ambient temperature no warmer than 77°F (25°C)

4 months at 86°F (30°C)

2 months at 104°F (40°C)
Give the battery a freshening charge before the end of the recommended storage interval.
A refreshing charge shall be performed at 2.26 Volts per cell (VPC) at 77°F (25°C) for 96 hours or until the charge current does not vary for a 3 hour period.
The necessity of a charge can also be determined by measuring the open circuit voltage of a stored battery.
Charging is advised if the voltage drops below 2.07 VPC.
Maximum total storage prior to installation is 2 years from date of shipment from the factory to the customer. Freshening charges are required before the end of the storage time period or more frequently, as noted above.
Failure to observe these conditions may result in greatly reduced capacity and service life.
FAILURE TO CHARGE AS NOTED VOIDS THE BATTERY’S WARRANTY.
www.enersys.com
Protect eyes from electrolyte
Keep flames away
In case of accidental overcharge, a flammable gas can escape from the safety vent.
Discharge any possible static electricity from clothes by touching an earth connected part.
Danger
Risk of explosion or fire. Avoid any short circuit. Metallic parts under voltage on the battery, do not place tools or items on top of the battery.
Installation
Install in clean, dry area. DataSafe HX batteries release minimal amounts of gas during normal operation (gas recombination efficiency 97%). The batteries can be installed near the main equipment. Batteries must be installed in accordance with federal, state and local law regulations and the manufacturer’s instructions.

Temperature
Avoid placing batteries in areas of high temperature or in direct sunlight. The batteries will give their best performance and service life when operating at a temperature between 68°F (20°C) and 77°F (25°C), however they are capable of operating in a temperature range of -22°F (-30°C) to 122°F (50°C). Please reference the charging float voltage section for more information regarding float voltage adjustments for temperature variations. Reasonable precautions should be taken to prevent continuous operation below -22°F (-30°C) or above 122°F (50°C).

Ventilation
Under normal conditions gas release is very low and natural ventilation is sufficient for cooling purposes and inadvertent overcharge, enabling DataSafe HX batteries to be used safely in offices and with main equipment.
However, care must be taken to ensure adequate ventilation when placed in cabinets. Batteries must not be placed in sealed cabinets.

Stowing
For proper installation, EnerSys® battery racks and cabinets are recommended.
For rack installations, reference Assembly Instructions for DataSafe HX and HX Front Terminal UBC Battery Racks (US-HXRACK-IM).
For cabinet installations, reference DataSafe HX Battery Cabinet Systems Range Summary (US-HXCAB-RS).
If provided, intercell connector covers should be installed after completing the intercell connections.
Attention: Unless otherwise noted, battery racks and cabinets should not be transported with rigid intercell connectors in place.

Torque
The maximum torque load of intercell connector bolts (M6) is 6.8 to 10 N•m (60 to 88 in-lbs). A loose connector can cause problems in charger adjustment, erratic battery performance, possible damage to the battery and/or personal injury.
Read instructions
Do not charge in sealed container
Tools
Use tools with insulated handles.
Do not place or drop metal objects on the battery.
Remove rings, wristwatches and any other articles of clothing with metal parts that may come into contact with the battery terminals.
Electrolyte is corrosive
Publication No: US-HX-IOM-004 - September 2012