Datalogic Vlase UV User Manual

USER’S MANUAL
> VLASE
TM
UV
Datalogic S.r.l. Via S. Vitalino 13 40012 – Calderara di Reno Italy
VlaseTM UV User’s Manual Ed.: 05/2017
Helpful links at www.datalogic. c om: Contact Us, Terms and Conditions, Support. © 2014 - 2017 Datalogic S.p.A. and/or its affiliates  ALL RIGHTS RESERVED.  Without
limiting the rights under copyright, no part of this documentation may be reproduced, stored in or introduced into a retrieval system, or transmitted in any form or by any means, or for any purpose, without the express written permission of Datalogic S.p.A. and/or its affiliates. Datalogic and the Datalogic logo are registered trademarks of Datalogic S.p.A. in many countries, including the U.S.A. and the E.U.
Vlase, Arex, Eox, Violino, Lighter Suite are trademarks of Datalogic S.p.A. and/or affiliates. All other trademarks and brands are property of their respective owners.
Datalogic reserves the right to make modifications and improvements without prior notification.
Datalogic shall not be liable for technical or editorial errors or omissions contained herein, nor for incidental or consequential damages resulting from the use of this material.
821002863 rev. C
iii

SYMBOLS

Symbols used in this m anual along with their meaning are show n below. Symbols and signs are repeated within the chapters and/or sections and have the following meaning:
Generic Warning:
This symbol indicates the need to read the manual carefully or the necessity of an important maneuver or maintenance operation
.
Electricity Warning:
This symbol indicates d angerous voltage associated with t he laser product, or powerful enough to constitute an electrical risk. This symbol may also appear on the marking system at the risk area
.
Laser Warning:
This symbol indicates the danger of exposure t o visible or invisible las er radiatio n. This symbol may also appear on the marking system at the risk area
.
Fire Warning:
This symbol indicates the d anger of a fire w hen proce ssing flam mable m aterials. Because th ere is a danger of fire, it is indispensable to follow the instructions provided by the manufacturer when commissioning the marking system
.
Notice:
Notes, usage tips, or additional information.
Note:
Carefully read the user’s manual before using the marking system.
iv

REVISION INDEX

Revision Date Number of added or edited pages
821002860 10-03-2015 Release
821002861 rev.A 15-01-2016 General Review
821002862 rev.B 29-04-2016 Appendix C
821002863 rev.C 22-05-2017 ii, Appendix F
NOTE:
We sometimes update the documentation after original publication. Therefore, you should also review the documentation at www.datalogic.com for updates.

FOREWORD

Information included in this manual is intended for a qualified installer able to integrate the marking system into a system, complying with all the protection features required by international rules and local legislations. Refer to the Appendices for further infor m ation.
Following manual refers to an VLASETM 3PWX-TLS2 system in Class 4 configuration.
In addition to being profess ionally trained in their role, pers onnel assigned to work on the m arking system must be informed and m ade acquainted with the risk s inherent to invisible and visib le laser radiation. The operator is required to caref ully read the section of the m anual concerning safet y instructions as well as the sections related to matters falling under her/his responsibility.
The workers assigned to the marking system can be identified as:
OPERATOR
responsible for loading elements to be processed, visually checking the work cycle, removing the finished product and cleaning the marking system.
MAINTENANCE WORKER
responsible for the electrical, mechanical and optical maintenance and adjustment of the marking system.
WARNING!
Datalogic shall not be held responsible for any non-conforming use of the marking system of its
manufacture
.
NOTE:
BEFORE INSTALLING AND USING THE MARKING SYSTEM, READ CAREFULLY THE APPENDICES.
vi

OVERVIEW

We are honoured b y your c hoice of a Data logic produc t, spec ificall y a new product belonging to the VlaseTM product fam ilies, which aim to satisf y new market evolutions, and especially the integrat ion industrial laser sources.

OPERATION OF A LASER SYSTEM WITH GALVANOMETRIC SCANNING

The laser generates a train of high-energy pulses of invisible radiation. In order to obtain a mor e accur ate focus, t he laser beam is f irst enlarged using an optica l expans ion s ystem and then deflected by a scanning system consisting of two mirrors mounted on galvanometric motors. These mirrors deflect the beam in a controlled beam along the X and Y axes; processing of the product surface occurs by coordinating the movement of the two motors with the turning on/off of the laser beam. The deflected laser beam is focused by an F-Theta objective before it hits the surface of the product. Generally speaking, the marking is carried out within the focus of the beam.

MARKING SOFTWARE

The marking software Lighter is preinstalled on the system.
NOTE:
Consult Lighter software user’s manual for a proper use of the same.
NOTE:
Consult the proper Appendix to upgrade the preinstalled software if necessary.
The VlaseTM laser marking system features a control unit whose size is compatible with the standard 19” 2,5U in varnished steel, a nd a resonator whose compact dimensions make it eas y to integrate into a s ystem that comprises safet y devices required by applicab le regulations, the management of m arking signals and the customer’s complementary modules, if any.
All laser marking system connections are found on the rear of the rack: power supply, safety, electrical signals, communication ports, patch cord to the scanner head, while the front features key and enable command devices, status LED in addition to a USB connector for the communication with the internal embedded controller.
TM
Vlase Switched” configuration. The mechanical and electric al characteristic s satisf y standardization and connect ivity needs of the ind ustrial field, such as the new 19” rack and different solutions for laser system control.
The new marking system control platform allows for an easy integration in industrial environments and complies with the sta ndard of the other Dat alogic mark ing systems, with the sam e philosophy im plemented in Arex
Based on the optical la yout of the Datalo gic Violino improvements in term s of performances thanks to the new laser diode current and temper ature controllers, developed by the Data logic labor atories, which short warm -up time and im prove the s tabilit y of emitted las er power. The operating temperature range has been extended to 5°- 40°C for its use in industrial environments.
belongs to the fam ily of DP SS (D iode Pum p Soli d Stat e) las er so urces in the “e nd pum ped” a nd “ Q-
TM
.
TM
laser sour ce, the VlaseTM fam ily guarantees sign ificant
WARNING!
Marking system installation in secure environment is responsibility of the system integrator!
vii
Figure 1: Control rack and resonator with scan head.
Main features:
100 to 240 V AC @ 50-6 0 H z Power Supply
Operating Temperature Range extended to 40°C
Fully integrated marking and system control
Integrated PC embedded and marking software for stand-alone operation
Ease of integration in industrial en vironments and m aximum control compatib ility with other m arking
platforms (Arex
Integrated photocell and encoder connectors for Marking ON Fly (MOF) applications
Unattended control of the system by LAN network or serial communication (RS232 protocol)
Stable Marking process and high a beam quality (M
Compact Design: 19” 2,5U rack
High peak power and shor t pulse dur at io n (<10ns)
Available cable lengths: 3m standard, other length available on request
Simplified access to Laser Diode Module for fiber installation and Laser Diode Module maintenance
Dedicated software tool for laser parameter setting and diagnostics
TM
/EoxTM)
2
<1.3)

IMPORTANT WARNINGS

Access to the interna l part s of the marking system is allo wed o nly to authorized pe r sonnel, du ly qualified and trained with regards to risks of optical and electrical nature. Datalogic declines a ny and all responsib ility for work carr ied out on live parts b y untrained or unauthor ized personnel.
WARNING!
It is forbidden to change the intended use for which the system was designed and developed. Datalogic declines any responsi bility and liability for irregular and im proper use of the laser system
which it manufactures.
WARNING!
These marking system actuation is demanded to the system integrator.
viii

TABLE OF CONTENTS

SYMBOLS III REVISION INDEX IV FOREWORD V OVERVIEW VI
OPERATION OF A LASER SYSTEM WITH GALVANOMETRIC SCANNING vi MARKING SOFTWARE vi IMPORTANT WARNINGS vii
TABLE OF CONTENTS VIII 1 CONTENTS OF THE PACKAGING 10
1.1 UNPACKING 10
1.2 MAIN HARDWARE 11
1.3 CABLES AND OTHER COMPONENTS 11
1.4 TRANSPORT 12
1.5 ON MOISTURE CONDENSATION 12
1.6 FIXING AND POSITIONING 13
1.7 INSTALLATION ENVIRONMENT 15
1.8 FUME / DUST EXTRACTOR 16
1.9 FAN INSTALLATION 16
2 TECHNICAL SPECIFICATIONS 17
2.1 TECHNICAL CHARACTERISTICS 17
2.2 DESCRIPTION OF THE MODULES 19
2.2.1 RESONATOR 19
2.2.2 CONTROL RACK 20
2.3 MARKING AREA SPEC IF I C AT I ON 21
2.4 EXTERNAL CONNECTORS SPECIFICATIONS 23
2.4.1 INTERLOCK CONNECTOR 23
2.4.2 INTERLOCK OUT CONNECTOR 25
2.4.3 COMMAND BOX CONNECTOR (LASER CONTROL) 26
2.4.4 AXES CONNECTOR (I/O CONTROL) 31
2.4.5 RS232 CONNECTOR (COM2) 32
2.4.6 ENCODER CONNECTOR 33
2.4.7 PHOTOCELL CONNECTOR 33
2.5 INPUT/OUTPUT SIGNAL SPECIFICATIONS 34
2.6 CONNECTION EXAMPLES 35
3 INSTALLATION AND SET UP 36
3.1 CONNECTIONS 36
3.1.1 CONNECTING COMMAND BOX CABLE 36
3.1.2 CONNECTING INTERLOCK CABLE 37
3.1.3 CONNECTING INTERLOCK OUT CONNECTOR 37
3.1.4 CONNECTING THE OPTICAL FIBER TO THE CONTROL RACK 38
3.1.5 CONNECTING THE OPTICAL FIBER ON THE RESONATOR 41
3.1.6 CONNECTING RADIOFREQUENCY CABLE 43
3.1.7 CONNECTING MDR CABLE 44
3.1.8 CONNECTING RESONATOR CABLE 45
3.1.9 CONNECTING FAN CABLE 46
3.1.10 CONNECTING POWER SUPPLY CABLE 47
3.1.11 GROUND CONNECTION 47
3.1.12 CONNECTING RESONATOR POWER SUPPLY CABLE 48
3.1.13 LOCAL MODE CONNECTION 49
3.1.14 REMOTE MODE CONNECTION 50
3.1.15 F-THETA LENS PROTECTION CAP REMOVAL 51
4 USE AND OPERATION 52
4.1 TURNING ON SEQUENCE 52
ix
4.1.1 ADVICE ON USING THE SYSTEM 55
4.2 LOCAL MODE OPERATIONS 56
4.3 REMOTE MODE OPERATIONS 56
4.4 OPERATING IN LOCAL MODE 58
4.4.1 HOW TO CREATE AND EDIT YOUR FIRST GRAPHIC DOCUMENT 59
4.4.2 HOW TO TEST AND ENGRAVE YOUR DOCUMENT 62
4.4.3 HOW TO USE EXTERNAL SIGNALS TO ENGRAVE YOUR DOCUMENT 64
4.5 THERMALIZATION AND SUPPRESSION OF GIANT PULSES 66
5 CUSTOMIZE THE SYSTEM’S SOFTWARE 68
5.1 CHANGE O.S. LANGUAGE AND KEYBOARD LAYOUT 68
5.2 CHANGE LAN CONFIGURATION AND IP ADDRESS 71
5.3 CHANGE VIDEO SETTING 74
5.4 REMOTE DESKTOP CONNECTION 76
6 ACCESSORIES 78
6.1 CONTROL BOX 78
6.2 MARKING ON FLY KIT 79
6.3 CABLE KIT LENGTH PLUS 79
6.4 RACK HANDLES 80
7 TECHNICAL SUPPORT 81
7.1 SEALS 81
7.2 MAINTENANCE 82
7.2.1 F-THETA SCAN LENS CLEANING PROCEDURE 82
7.2.2 AIR FILTER CLEANING PROCEDURE 83
7.3 PRODUCT SUPPORT AND CUSTOMER SERVICE 84
APPENDIX A: LABELS IDENTIFICATION 85
POSITIONING OF EXTERNAL LABELS 87
APPENDIX B: STANDARDS 89
LASER STANDARDS 89 CE COMPLIANCE 89 FCC COMPLIANCE 89
APPENDIX C: SAFETY CONSIDER ATION ACCORDING TO EN ISO 13489-1:2008 90
PERFORMANCE LEVEL (PL) 90
APPLICATION EXAMPLE 90
SAFETY FUNCTIONS OF VLASE
APPENDIX D: NOTE ABOUT LASER 95
LASER SAFET Y 95
LASER RADIATIO N 96 ABSORPTION OF LASER RADIATION 97 CLASSIFICATION AND DANGER LEVEL 97 RADIATION VIEWING CONDITIONS 98 DIRECT VIEWING OF THE LASER BEAM 98 DIRECT VIEWING OF THE BEAM AFTER MIRROR REFLECTION 98 DIRECT VIEWING OF THE BEAM OUTPUT BY AN OPTICAL FIBER 98 DIRECT VIEWING OF THE BEAM AFTER FOCUSING 98 SCATTERED VIEWING OF THE BEAM AFTER FOCUSING 98 N.O.H.D. DETERMINATION AND O.D. OF PROTECTION GOGGLES 99 EYES AND SKIN RISKS 101 GENERAL SAFETY REGULATIONS 101 COLLATERAL RISKS 101
TM
94
APPENDIX E: SOFTWARE UPGRADE 103 APPENDIX F: RECOVER THE SYSTEM USING USB RECOVERY DISK 106 APPENDIX G: MECHANICAL DRAWINGS 112 FIGURES 114
10

1 CONTENTS OF THE PACKAGING

1.1 UNPACKING

When unpacking the marking system from the shipping carton you should:
Remove the documentation from the top of the marking system
Remove the box containing the accessories
Carefully remove the marking system from the packaging using both hands
VLASETM UV
Figure 2: Unpacking.
Before installing or operating the marking system, you should:
Inspect the shipping container for damage
Inspect the marking system for signs of damage
Confirm that the shipping carton contains all items on the shipping inventory list including any
accessories
Retain all packaging m aterials until the marking syste m has been inspect ed for complete ness and damage , and you have checked the operating performance. If anything is missing or defective, see chapter 7 for contact details.
CONTENTS OF THE PACKING
11
Interlock cable
Safety Key
USB Stick
Cable gland
Rack adapters
Sample Test
User Manual
Test Report

1.2 MAIN HARDWARE

Control rack Resonator F-Theta (except 3PWX-T0SV)

1.3 CABLES AND OTHE R CO MP O NE NTS

RF cable Resonator cable Optical fiber cable USB cable
Power supply cables Scan Head cable Command Box cable
Command Box Gold connector (*) Interlock connector gold (*) Interlock OUT connector
* If this connector is used, the marking system works in DANGEROUS condition (MUTING DEVICE).
VLASETM UV
12

1.4 TRANSPORT

The marking system needs to be moved in order to proceed to its positioning and wiring. The marking system can’t be lifted up and moved by a single person.
WARNING!
To avoid damaging or breaking the optical fiber, n ever subject it a bending radi us below the limits specified in the technical specification table.
Figure 3: Transport.
WARNING!
VlaseTM is a delicate optical laser marking system, avoid damaging it with shock and vibrations.
WARNING!
Be extremely careful to not damage the fiber optic cable between resonator and rack.

1.5 ON MOISTURE CONDENSATION

If the marking s ystem is brought directl y from a cold to a warm loc ation, moisture may condens e inside or outside the marking system. This moisture condensation may cause a malfunction of the marking system.
If moisture condensation occurs
Turn off the marking system and wait about 1 hour for the moisture to evaporate.
Note on moisture condensation
Moisture may condens e when you bring the m arking system from a cold place int o a warm place (or vice versa) or when you use the marking system in a humid place as shown below.
How to avoid moisture condensation
When you bring the mark ing system from a cold place into a war m place, put it in a plastic bag and s eal it tightly. Remove the bag when the air temperature inside the plastic bag has reached the ambient temperature (after about 1 hour).
CONTENTS OF THE PACKING
13

1.6 FIXING AND POSITIONING

The marking system must be positioned in a safely manner and the precautions listed below must be followed.
Figure 4: Positioning rack.
Figure 5: Vertical positioning (need additional fixing).
WARNING!
DO NOT fix the marking system in manner not shown in figure.
VLASETM UV
14
The marking system can be f itted inside a special rac k cabinet equippe d with special suppor t shoulders and handles, available on reques t. The figure below shows the mounting points for mounting in rack:
Figure 6: Fixing points on rack handles (cabinet assembly).
The resonator mus t be secured to a special base (not supplied by Datalogic ) using the four M6 threaded holes.
The resonator, just lik e the control r ack , mus t be safety posit ioned and secur ed o n a spec ial surf ace, par allel to the ground and absolutely vibration-free. The resonator can be secured both horizontally and vertically.
NOTE:
In order to prevent mar king distortions, install a vibrom eter on the base of the piece to be mark ed and check for the absence of vibrations during the marking process.
NOTE:
It is recommended to install the resonator on a micrometer positioning Z-axis system!
Figure 7: Resonator fixing points
WARNING!
It is very important to s ecure the laser system before you start m arking the piece since improper securing or positioning may cause serious damage.
Do not secure the marking system in a way other than the one described in the figure.
CONTENTS OF THE PACKING
15

1.7 INS TALLATION ENVIRONMENT

The control rack must be installed in a s uitable environment in order to al low proper air flow passage and correct housing of the cables.
TM
Vlase the system. Install must not slow or stop the flow of air cooling. Moreover, do not install a heat source near. Clean air f ilter w hen it is d ir ty. If the air f ilter is dirt y, the air-flow might bec ome not sufficient to ensure correct cooling and might stop marking operation. Clean or exchange air filter periodically.
is an air cooled marking system: an ade quate air flow is n ecessary to guar antee correct cool ing of
Figure 8: Rack installation environmen t.
WARNING!
DO NOT place heavy objects on top of rack!
In order to have the marking system operating in safety mode (see Appendices for more details) we recommended to ins tall the mark ing system as shown in figure below in order to limit laser ou tput area. To obtain a good marking quality, and not to decrease life time, we recommended a ventilation or vacuum system in a protection box to limit dust due to marking phase.
Figure 9: Safety mode example.
VLASETM UV
16

1.8 FUME / DUST EXTRACTO R

During marking proc ess, dust and/or gas may be produc ed. It is important to use adequa te fume extractor and/or air filtration.
WARNING!
Marking PVC (or oth er plastic m aterial) can c ause the release of chlor ine gas witc h can be harmful to the laser operator and t o the marking system itself. Always use adequate fume extractor dur ing PVC and plastic marking.

1.9 FAN INSTALLATION

The fan supplied with the d ev ice must be accurately positi one d an d f ix ed on th e res onat or s o that i t can work properly. The fan must be as sembled so that the air flow is aimed at the unit containing the crystal (gold-coloured section on the resonator).
Figure 10: Fan installation.
TECHNICAL SPECIFICATIONS
17

2 TECHNICAL SPECIFICATIONS

NOTE:
BEFORE INSTALLING AND USING THE LASER, RE AD CAREFULLY THE APPENDICES.
WARNING!
VlaseTM is a CLAS S 4 LASER PRODUCT and it is the responsibility of the OEM/system integrator to provide the safety completeness to be ready-to-use.

2.1 TECHNICAL CHARACTERISTICS

CONTROL RACK MECHANICAL CHARACTERISTICS
RESONATOR WITH SCANNER HEAD MECHANICAL CHARACTERISTICS
(*) Without F-Theta. (**) Vary from models.
Weight 15 Kg
Height 122 mm
Width 430 mm Depth 480 mm
Weight (*) 11 Kg
Height 168 mm
Width 181 mm
Depth (**) 686 mm
NOTE:
Refer to Datalogic’s website for detailed drawings.
18
Storage temperature
-10° to 60°C (14° to 140°F)
Package Drop Test
60 cm
Environmental temperature
5°C to 40°C (41° to 104°F)
Humidity
< 90% without condensation
Altitude
< 2000 m
Pollution Degree
Overvoltage Categor y
Input Voltage
100 to 240 V AC @ 50-60 Hz
Max Power
600W
LASER MARKER SOURCE (specification @ 25°C)
Laser Type
Class 4 DPSSL (Diode Pumped Solid State Laser)
Average Power at reference Rep Rate (30kHz)1
Pulse energy (max)
mJ
0.10 (7ns)
Peak power (max)
kW
14
Central emission wavelength
nm
355
Repetition Rate2
kHz
20 ÷ 80
Laser aiming beam Class 2 <1mW @ 630-670nm
Forced Air
Resonator Fan = L10 @ 40°C : 70000h
OTHER
Optical Fiber Minimum Bending Radius
Available Cables Length
m
3 standard, other available
Marking Speed
mm/s
Up to 3000 mm/s
3
MOF (Marking on the fly)
YES [constant speed or encoder]
Line speed – Productivity
4
Up to 75 m/min – 3 Pcs/s
Communication
RS232, Ethernet (TCP/IP 10, 100 Mbit), digital I/O
STORAGE AND TRASPORTATION CONDITIONS
Shock and vibrations MIL 810E “CAT 1 Basic Transportation”
WARNING!
This product includes precision optical parts; avoid vibration and shocks: marking quality may deteriorate.
ENVIRONMENTAL OPERATING CONDITIONS
ELECTRICAL POWER SUPPLY
VLASETM UV
Input Current 6 max
PERFORMANCES
W 3.0
Cooling
Noise dB(A) < 70 at 1 meter
mm 200 (fixed installation)
Rack Fans = L10 @ 40°C : 60000h
Char Marking Speed
char/s Up to 340 char/s
Marking Control and Software EMC Embedded Control and Lighter Suite
1
Without F-Theta
2
Without Power derating
3
h char=1mm in roman s Level100% f=30kHz F-Theta160L on TESA label
4
Single line string, Roman-s font
TECHNICAL SPECIFICATIONS
19

2.2 DESCRIPTION OF THE MODULES

2.2.1 RESONATOR

A description of the main parts of the resonator unit is provided here below:
1) Scan Head signals connector
2) USB port type B 6) RF connector
3) Fan connector 7) Cooling fan
4) Rack-Resonator connector 8) Optic fiber inlet
5) Resonator power supply connection
Figure 11: Resonator view.
VLASETM UV
20

2.2.2 CONTROL RACK

A description of the c ontrol rack is provided her e below for th e purpose of obtaining the right inform ation for proper installation of the marking system.
1) Status LED 11) MDR connector
2) Enable 12) Resonator signals connector
3) Key 13) Optic fiber outlet
4) USB port 14) RF connector
5) VGA port 15) Command Box connector
6) LAN port 16) I/O connector (axis control)
7) RS232 port 17) Photocell connector
8) 3x USB ports 18) Encoder connector
9) Interlock connector 19) Earth ground
10) Interlock OUT connector 20) Mains power supply connection
Figure 12: Control rack front view.
TECHNICAL SPECIFICATIONS
21
ƒ
ƒ

2.3 MARKING AREA SPECIFICATION

Datalogic provides a wide range of F-Theta sc an lenses to be attached to the scannin g head to focus the laser beam in flat Marking Field, in order to achieve high-resolution marking results.
These F-Theta scan lenses are available t o best-match the object (i.e.: logo; string; 2D m atrix; etc.) to be marked and fit the s tandard Datalogic Scanning Head; f urther solutions about differ ent models of F-Theta scan lenses and scanning heads will be considered upon request.
The table below lists the standard F-Theta scan lenses currently availabl e:
F-Theta Scan Lens diameter: M85
F-Theta Scan Lens
Working Distance mm 135 ± 3 197 ± 3 Fixing Distanc e mm 159 ± 4 187 ± 4 Marking Area mm
2
= 103L Telecentric
60 x 60
= 160L
110 x 110
NOTE:
Definition of Marking Area: square marking field measured on black anodized aluminium plate.
WARNING!
This product was d esigned to use only certain conf igurations of F-Theta lens and mark ing field. If your needs are not satisfied by current available F-Theta lens configurations please contact Datalogic for a solution. T he use of other F-T heta lenses or operation o utside the specif ied marking field for a certain F-Theta l ens configuration can lea d to damage of F-Theta lens, scanning head or laser source. Such damage is not covered by warranty!
WARNING!
For each F-T heta lens configurat ion Datalogic recommends the use of certain ad apter. This adapter ensures that residual back ref lections cause d by F-T heta lens do not dam age optics of the scanni ng head. The removal of such adapter or its incorrect use (for example incomplete thread ing, use of another F-Theta lens adapt er, etc.) can lead to dam age of the F-Theta lens, scannin g head or las er source. Such damage is not covered by warranty!
22
NOTE:
Working Distance is defin ed as the distance between the center of the marking area (defined in the focal plane) and the last mechanical edge of the F-Theta Scan Lens. Refer to the following figure.
WD: Working Distance MA: Marking Area AB: Aiming beam FD: Fixing Distance
VLASETM UV
Figure 13: Marking area
TECHNICAL SPECIFICATIONS
23

2.4 EXTERNAL CONNECTORS SPECIFICATIONS

2.4.1 INTERLOCK CONNECTOR

Interlock disables the Class 4 laser source inside the marking system. Interlock internal circuit is designed to comply with the single fault conditio n.
PANEL CONNECTOR Type SWITCHCRAFT TB Series male Tini Q-G (Mini XLR) panel mount connector, 4 positions.
Figure 14: Male panel plug cod. TB4M (front view).
PIN SIGNAL TYPE DESCRIPTION FUNCTIONAL DIAGRAM
1 VCC_INT_IN_A OUTPUT
2 INTERLOCK_A INPUT
3 GND_INT_IN_B GND
4 INTERLOCK _B INPUT
PIN 1- PIN 2 PIN 3- PIN 4
CONTACT OPEN CONTACT OPEN NOT POSSIBLE SAFE CONTACT CLOSED CONTACT OPEN NOT POSSIBLE DANGEROUS CONTACT OPEN CONTACT CLOSED NOT POSSIBLE DANGEROUS CONTACT CLOSED CONTACT CLOSED POSSIBLE DANGEROUS
24V DC reference for
INTERLOCK_A signal
INTERLOCK_A signal
Ground reference for INTERLOCK_B signal
INTERLOCK_B signal
MARKING FUNCTIONALITY
CONDITION
WARNING!
In order to NO T D AM AG E the i nterlock circuitr y, we recommended us ing “dry circuit” (zero vo ltage) switches or relay circuitry.
VLASETM UV
24
PLUG CONNECTOR
Connector type SWITCHCRAFT TA Series Tini Q-G (Mini XLR) female cable mount connectors, 4 positions.
Figure 15: Female cable mount connector cod. TY4F (solder view).
WARNING!
If the interlock gold connec tor is used, the marking s ystem is in DANGEROUS condition ( MUTING DEVICE).
NOTE:
To restore the mark ing system it is necess ary to repeat the “ Turning on sequenc e” without shutting down the system. See chapter 4.1 for more details.
TECHNICAL SPECIFICATIONS
25

2.4.2 INTERLOCK OUT CONNECTOR

The interlock-out allows to monitoring of the operation of the interlock connector.
PANEL CONNECTOR
Panel socket BINDER, 4 positions female, 719 series.
Figure 16: Female panel socket cod. 09-9766-30-04 (front view).
PIN SIGNAL TYPE DESCRIPTION
1 INT_OUT_A_COLLECTOR COLLECTOR 2 INT_OUT_A_EMITTER EMITTER 3 INT_OUT_B_COLLECTOR COLLECTOR 4 INT_OUT_B_EMITTER EMITTER
Type NPN BJT transistor V
300 V
max
I
60 mA
max
Vsaturation < 1,5 V
Interlock OUT signal A
(INT_OUT_A)
Interlock OUT signal B (INT_OUT_B)
INT_OUT_A INT_OUT_B CONDITION
Closed Closed SAFE Closed Open DANGEROUS Open Closed DANGEROUS Open Open DANGEROUS
Leakage current < 400 nA
NOTE:
The response time is 10 ms from the output’s switching.
PLUG CONNECTOR
Binder male cable mount connectors, 719 series, 4 positions.
+
Figure 17: Male cable mount connector cod. 09-9767-00-04 (front view).
26

2.4.3 COMMAND BOX CONNECTOR (LASER CONTROL)

Panel socket Sub-D, 25 positions, female.
Figure 18: Female panel socket Sub-D 25 (front view).
PIN SIGNAL TYPE (***) DESCRIPTION
VLASETM UV
1 12V_ENABLE_B
2 EXT_ENABLE_B Digital Input
3 RESERVED Digital Output DO NOT CONNECT 4 EXT_12V
5 EXT_12V
6 EXT_12V
7 12V_ENABLE_A
8 EXT_ENABLE_A Digital Input
9 BUSY (*) Digital Output
CONNECTOR
10
PRESENCE
11 START MARKING (*) Digital Input
12 EXT_KEY Digital Input
13 STOP MARKING (*) Digital Input
Output power supply
Output power supply
Output power supply
Output power supply
Output power supply
Digital Input
12V DC power supply available for EXT_ENABLE_B (max 250mA)
Secondary external ENABLE signal (see par. 2.4.3.1)
- HIGH level: contact closed
- LOW level or disconnected: contact opened
Auxiliary 12V DC power supply available for drive input logical HIGH (max 250mA)
Auxiliary 12V Dc power supply available for drive input logical HIGH (max 250mA)
Auxiliary 12V DC power supply available for drive input logical HIGH (max 250mA)
12V DC power supply available for EXT_ENABLE_A (max 250mA)
Primary external ENABLE signal (see paragraph 2.4.3.1)
- HIGH level: contact closed;
- LOW level or disconnected: contact opened
This signal is used to know if the current spooler is executing (marking in progress) (see paragraph 2.4.3.4)
- ON during marking process
This signal is used to check the presence of the command box connector (see paragraph 2.6)
- HIGH level: normal operation;
- LOW level or disconnected: laser source faulty
This signal is used to start to the marking process when a document or a sequence is running in AUTO MODE (**) or WORK MODE (**): (see paragraph 2.4.3.4)
- HIGH level pulsed signal start the marking process
External KEY signal (see paragraph 2.4.3.2)
- HIGH level: contact closed;
- LOW level or disconnected: contact opened
This signal is used to stop the marking process (see paragraph 2.4.3.4)
- HIGH level pulsed signal stop the marking process
TECHNICAL SPECIFICATIONS
27
14 RESERVED Digital Input 15 RESERVED Digital Input DO NOT CONNECT 16 RESERVED Digital Input DO NOT CONNECT
17 END Digital Output
18 POWER_ON Digital Output
19 GND Ground
20 SYSTEM_ALARM Digital Output
21 GND Ground Ground reference
22 ENABLE_OUT Digital Output
23 SW_READY (*) Digital Output
24 GND Ground Ground reference
DO NOT CONNECT
This signal is used to know if the marking process is finished (see paragraph 2.4.3.4):
- ON at the end of marking process
This signal is used to know if the system is already warmed up: (see 2.4.3.3)
- ON when the laser is in STAND_BY or READY state
Ground reference This signal is used to know if the system is in booting
up state or in error state: (see paragraph 2.4.3.3)
- ON during BOOTING UP
- ON in case of system error
This signal is used to know if the system is ready to emit laser radiation: (see paragraph 2.4.3.3)
- ON when the system is in READY state
This signal is used to know if a document, sequence or script is loaded and ready to be executed:
- ON when a document or a sequence is running in AUTO MODE (**) or WORK MODE (**) (SW_READY COMPATIBILITY (**) = true)
- ON when a document or a sequence is running in AUTO MODE (**) and laser in READY state (SW_READY COMPATIBILITY (**) = false)
- ON when a script is running n AUTO MODE (**) and “IoPort.setReady (true)” function is used
25 GND Ground
(*) refers to Lighter user’s manual “Setting I/O parameters” paragraph to set the signal properties (**) refers to Lighter user’s manual (***) refer to 2.5
Ground reference
NOTE:
Connection example in paragraph 2.6.
28
2.4.3.1 ENABLE SIGNAL’S SCHEME (COMMAND BOX CONNECTOR)
VLASETM UV
Figure 19: ENABLE signal’s scheme.
TECHNICAL SPECIFICATIONS
29
2.4.3.2 KEY SIGNAL’S SCHEME (COMMAND BOX CONNECTOR)
Figure 20: KEY signal’s scheme
2.4.3.3 LASER CONTROL SIGNALS TIMING
Figure 21: Timing control signals
30
2.4.3.4 TIMING MARKING PROCESS SIGNALS
The following diagram illustrates the possible timings and settings of these signals:
VLASETM UV
Figure 22: Timing signals
The time intervals in the diagram can all be programmed with a resolution of 1 ms
Start Time For setting the minimum acceptable time for the START_MARKING signal
T
1
Start Delay For delaying the start of marking process
T
2
Busy Advance BUSY signal corresponding to marking progress
T
3
T
Stop Time The minimum time for STOP_MARKING signal to stop the marking process
4
Busy Delay For delaying the Laser END signal with respect to laser emission
T
5
End Time For setting the Laser End activation time
T
6
(*) Refer to Lighter user’s manual “Setting I/O parameters” to set the signal’s properties.
(*).
Loading...
+ 86 hidden pages