Datalogic QL300, QL500 User Manual

5
5
QL300 / QL500
Quick Link ID-NET™ Connectors
DESCRIPTION
The QL series ID-NET™ connectors provide a fast and efficient way to cable an ID-NET™ network using standard cables. The QL300/500s are typically Master ID-NET™ connectors designed to be used with the QL100/150/200s ID-NET™ Slave connectors.
The QL500 is an active connection module which can be used in Standalone or ID-NET™ Master Multidata, or Master Synchronized layouts. It provides separate ports for Power Supply, External Trigger, Digital I/O and Communication. Host communication is provided through the integrated Ethernet module which connects internally to the reader's Main serial interface. Reader Aux RS232 serial interface is also provided. ID-NET™ network and power supply signals are sent out to the next connected device by means of a dedicated port, however there is no network input connector and therefore it cannot be used as an ID-NET™ Slave.
The QL series are compatible with the following readers:
DS2100N DS4800 Matrix 400™
DS2400N Matrix 200™
QL300
QL500
CONNECTIONS
ID-NET Out
M12 5P Female (A-coded)
Pin Function
1 Shield 2 Vdc 3 GND 4 ID+ 5 ID-
QL300 only (ID-NET In)
M12 5P Male (A-coded)
Pin Function
1 Shield 2 nc 3 GND 4 ID+ 5 ID-
QL500 only (Ethernet)
RJ45 8P Female
Pin Function
1 TX+ 2 TX­3 RX+ 6 RX-
4, 5, 7, 8 nc
OVERALL DIMENSIONS
129
[4.56]
42
[1.49]
42
[1.49]
45
[1.59]
129
[4.56]
45
[1.59]
QL300
QL500
56
56
[1.98]
[1.98]
76
76
[2.67]
[2.67]
P8 P1
mm
in
mm
in
27
27
[0.95]
[0.95]
Power
M12 3P Male (B-coded)
Pin Function
1 Earth 2 Vdc 3 GND
Trigger
M12 4P Female (A-coded)
Pin Function
1 +V 2 nc 3 -V 4 I1+
MOUNTING
There are two self-threading screws provided for mounting the QLs to various wooden or plastic surfaces. Mounting to other surfaces such as concrete walls or metallic panels requires user­supplied parts (screws, screw anchors, nuts, etc). Keep in mind that the connected reader must have its Chassis grounded to Earth, see paragraph "Grounding".
QLs can also be mounted to a Bosch Frame using the BA200 mounting accessory.
The distance between mounting bushings is given in the overall dimension diagram for each QL.
IP65 protection is provided when the cables (or QLs) are properly mated.
NOTE
GROUNDING
There are two general rules to follow regarding network grounding:
1) The network Shield must only be connected to Earth ground at one point (the Master).
When using isolated power supplies, Earth grounding can be accomplished through the CAB-PW-EXT accessory cable and the BA400 or QL300/500 Power connector.
QL300
CAB-PW-EXT
Power Supply
Earth ground connection
2) All reader Chassis must be connected to Earth ground.
All the readers in the network must have their Chassis connected to Earth ground either by: mounting to
conductive metal brackets or frames which are connected to Earth ground; or through the CBX or SC4000; or through the QL bushing.
In the case of grounding through the CBX or SC4000, connect the Earth signal to a good earth ground and set the internal Chassis jumper to Earth.
In the case of grounding through the QL bushing, connect a flying lead from the mounting bushing to an Earth ground. The mounting bushing is internally connected to the reader Chassis.
Power
Reader
13
1
25P D-Sub Female
142
Pin Function Pin Function
1,
shell,
both bushings
2 TXM 14 nc 3 RXM 15 nc 4 5 6 I2A 18 I1A 7 GND 19 GND 8 O1+ 20 RXA
9 nc 21 TXA 10 I2B 22 O1­11 O2+ 23 ID+ 12 O2- 24 ID­13 Vdc 25 GND
Reader Chassis
RTSM * CTSM *
16 nc 17 nc
* pins 4 and 5 are nc for QL500.
I/O Port
15P HD D-Sub Female
10
15
1
6
11
Pin Function Pin Function
1 O1+ 9 I2A 2 TXA 10 O2­3 RXA 11 I2B 4 5 6 O1- 14 SGND 7 Vdc 15 8 O2+
RXM * CTSM *
12 13 GND
TXM *
RTSM *
* pins 4, 5, 12 and 15 are nc for QL500.
Do not connect GND and SGND to different (external) ground references. GND and SGND are internally connected through filtering circuitry which can be permanently damaged if subjected to voltage drops over
CAUTION
0.8 Vdc.
ACCESSORIES
Description Part Number Connection Cables
CAB-PW-EXT M12 POWER EXTENSION CABLE
CBL-1480-01 THIN M12/5P MALE/FEMALE 1M
CBL-1480-02 THIN M12/5P MALE/FEMALE 2M
Terminators
CBL-1490 TERM. RESIST. THIN M12/5P/MALE
CBL-1496 TERM. RESIST. THIN M12/5P/FEMALE
Field Mountable Connectors
FMC400 M12 3P F. CONN. POWER
Mounting
BA200 Bosch Adaptors 93ACC1822
The FMC accessory connectors can be used to make custom External Power and Service cables in case the standard cables don't satisfy the application requirements.
93A051381 Power
970101021
970101022
ID-NET Out/In
970101069 ID-NET Out
970101082 ID-NET In
93ACC1884 Power
TECHNICAL SPECIFICATIONS
A
A
ELECTRICAL FEATURES QL300 QL500
Supply Voltage 10 to 30 Vdc
(see Voltage Drop below) Consumption - 210 mA - 70 mA Maximum Distributed Current
4 A
Allowed
see related reading device manual for consumption
Inputs see relative reader Reference Manual Outputs see relative reader Reference Manual
PHYSICAL FEATURES
Mechanical Dimensions 129 x 76 x 27 mm
(5.1 x 3 x 1.1 in.)
Weight 312 g.
(11 oz.)
309
(10.9 oz.)
ENVIRONMENTAL FEATURES
Operating Temperature Storage Temperature
0° to 50 C (+32° to 122 °F)
-20° to 70 C (-4° to 158 °F) Humidity max. 90% non condensing Vibration Resistance 14 mm @ 2 to 10 Hz EN 60068-2-6
2 hours on each axis
1.5 mm @ 13 to 55 Hz 2 g @ 70 to 200 Hz
Shock Resistance 30 g; 11 ms; EN 60068-2-27 3 shocks on each axis Protection Class EN 60529
(when IP protection caps or
IP65
IP cables and reading
device are correctly
connected)
IP40
The features given are typical at a 25 C ambient temperature (if not otherwise indicated).
VOLTAGE DROP AND MAX DISTRIBUTED CURRENT CALCULATIONS
For correct network management, the maximum number of readers which can propagate power through the QLs must be calculated so that max distributed current is not exceeded and so voltage drop doesn't affect reader functioning. This is done according to the following formula:
Voltage Drop = (Max Reader Current x Number of readers) x
(Resistance per Meter per wire* x Cable length in Meters)
* the resistance calculation must include both wires (Vdc and GND).
Example:
An ID-NET™ network is composed of 4 DS2100N readers. Three 2 meter ThinNet cables are used to connect the readers, which have Cable Resistance = 0.058 Ohms per meter per wire. The network power is 24 Vdc.
(0.2083 A x 4 readers) x [(0.058 x 2) x 6 meters] = 0.58 Vdc voltage drop
24 Vdc - 0.58 = 23.42 Vdc at reader number 4 (worst case)
Integrate a sufficient number of QL200s to resupply network power.
821001640
TYPICAL LAYOUTS
Host
Point to Point - Matrix 200™ with QL500 (Ethernet to Host)
1
The reader must first be configured for Ethernet communication. This is done by connecting to the
reader through the RS232 Aux port available on the QL500 I/O Port and running the software configuration program.
QL300
Power
CAB-PW-EXT
CBL-1496
ID-NET
Terminator
Main Interface
ID-NET™ Synchronized Network - Matrix 400™ Master with QL300
Power
ID-NET™
CBL-1480-xx
Master
PS
+ Matrix 400™ Slaves with QL150
CAB-PW-EXT
1
QL500
Ethernet
QL150
I/O
Matrix 200™
PS
CAB-AUX03 CAB-AUX03
QL150
Slave Nodes
The ID-NET network must be terminated inserting an ID-NET terminator into the QL300 (Master) and into the last QL in the network.
Host
CBL-1480-xx
CBL-1490
ID-NET
Terminator
TRIGGER
In order to allow direct trigger cabling between the photocell and the QL300/500 using standard M12 A-coded one-to-one cables, the trigger signal has been internally wired to manage PNP type photocells. The external trigger therefore must be connected as shown in the diagram
below.
Power 1
READER
VCC
~
+-
~
The electrical features of both inputs and outputs are given in the relative reader Reference Manual.
13 Vdc
7
GND
I1B
19
18 I1
13
7
19
Reader
Vdc
23
QL300/500
GND
1 +V
3
-V
nc
2
4 I1+18
Trigger
EXTERNAL TRIGGER
V
Ground
Sig nal
Power
QL500 1
CAB-PW-EXT
Ethernet Interface
CBL-1480-xx
Power
Master
PS
QL200 2
Host
Slave Nodes
CBL-1480-xx
The ID-NET network must be terminated inserting an ID-NET terminator into the last QL in the network. ID-NET on the QL500 is internally terminated.
QL100 ID-NET™
ID-NET™ Synchronized Network - DS4800 Master with QL500
+ DS4800 Slaves with QL200 and QL100
1
The reader must first be configured for Ethernet communication. This is done by connecting to the
reader through the RS232 Aux port available on the QL500 I/O Port and running the software configuration program.
2
The above diagram is an example showing layout connections and is not intended to represent power
limits, which instead, depend on each specific application. See "Voltage Drop and Max Distributed Current Calculations".
Slave
CBL-1496
Terminator
PS
Power
QL300
Slave
ID-NET
PS PS
CBL-1480-xx
ID-NET™
The ID-NET network must be terminated inserting an ID-NET terminator into the QL300 (Master) and into the last QL300 in the network.
UX Port
QL300
Power
Master
CBL-1480-xx
QL300
ID-NET™ Multidata Network - DS4800 Master with QL300
+ Mixed Reader Slaves with QL300s
COMPLIANCE
FCC Compliance
Modifications or changes to this equipment without the expressed written approval of Datalogic could void the authority to use the equipment.
This device complies with PART 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference which may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
CE Compliance Warning:
This is a Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
Power Supply This product is intended to be installed by Qualified Personnel only.
This accessory device is intended to be supplied by a UL Listed or CSA Certified Power Unit with «Class 2» or LPS power source.
CBL-1490
ID-NET
Terminator
Power
CBL-1490
ID-NET
Terminator
Host