Datakom DKG-225 User Manual

DKG-225 User Manual Firmware V-01
AUTOMATIC MAINS
FAILURE UNIT
WITH INTERNAL
CHARGER
DKG-225, is a low cost AMF controller for 12V-DC gensets, featuring an internal battery charger. Internal fuel and crank relays are rated at 40Amps@12V-DC and do not require external relays.
Thus a typical transfer panel will simply consist on one DKG-225 and two contactors, reducing material cost, panel size and production time.
The unit supports also current transformer connections allowing detailed power measurements from both mains and genset sides. The standard unit supports 1A and 5A secondary CTs. A special version supports low cost and small 0.1A secondary CTs allowing more compact panel design.
Thanks to the DKG-225, automatization of small gensets has become easy and cost effective.
In AUTO position, the unit monitors 3 phases of the mains, runs and stops the genset automatically and performs load transfer. When the engine is running, it monitors internal protections and alarm inputs.
The 1Amp @12V-DC rated battery charger is sufficient for the float charging of the engine start battery.
Timers, threshold levels, input and output configurations are digitally programmable. Programs are modified through front panel pushbuttons and do not require an additional unit.
The fault conditions are considered in 2 categories as Warnings and Alarms. Measured values have separate programmable limits for warning and alarm conditions.
Automatic mains monitoring
Automatic load transfer
Automatic starting and stopping
Automatic stopping in fault condition
Gas engine support
Test mode available
Emergency backup mode
3 phase mains voltage inputs
3 phase genset voltage inputs
3 phase mains/genset CT inputs
2 configurable analog sender inputs
3 configurable digital inputs
Detailed AC measurements and protections
Internal battery charging rectifier
40 Amp rated Fuel and Crank outputs
Front panel adjustable parameters
Stop, preheat and choke output capability
Survives cranking voltage dropouts
Compact dimensions, panel mounted
Mains Volts: L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1 Genset Volts: L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1 Load Currents: L1, L2, L3 Load total kW, kVA, kVAr, cosΦ Genset Frequency Battery Voltage Oil pressure Coolant temperature Engine run Hours Service Counters
MEASUREMENTS
FEATURES
DESCRIPTION
DKG-225 User Manual Firmware V-01
- 2 -
Any unauthorized use or copying of the contents or any part of this document is prohibited.
This document describes minimum requirements and necessary steps for the successful installation of the DKG-225 family units.
Follow carefully advices given in the document. These are often good practices for the installation which reduce future issues.
For all technical queries please contact Datakom at below e-mail address:
datakom@datakom.com.tr
If additional information to this manual is required, please contact the manufacturer directly at below e­mail address:
datakom@datakom.com.tr
Please provide following information in order to get answers to any question:
- Device model name (see the back panel of the unit),
- Complete serial number (see the back panel of the unit),
- Firmware version (read from the display screen),
- Measuring-circuit voltage and power supply voltage,
- Precise description of the query.
REVISION
DATE
WRITTEN
DESCRIPTION
01
08.11.2016
MH
First edition
CAUTION: Potential risk of injury or death.
WARNING: Potential risk of malfunction or material damage.
ATTENTION: Useful hints for the understanding of device operation.
TERMINOLOGY
QUERRIES
REVISION HISTORY
ABOUT THIS DOCUMENT
COPYRIGHT NOTICE
DKG-225 User Manual Firmware V-01
- 3 -
Screw Type Bracket
Stock Code=J10P01 (1 unit)
Spring Type Bracket
Stock Code=K16P01 (1 unit)
Watertight Gasket, Stock Code= K96P01
SPARE PARTS
DKG-225 User Manual Firmware V-01
- 4 -
Electrical equipment should be installed only by qualified specialist. No
responsibility is assured by the manufacturer or any of its subsidiaries for any consequences resulting from the non-compliance to these instructions.
Check the unit for cracks and damages due to transportation. Do not install
damaged equipment.
Do not open the unit. There are no serviceable parts inside. Fuses must be connected to phase voltage inputs, in close proximity of the
unit.
Fuses must be of fast type (FF) with a maximum rating of 6A.
Disconnect all power before working on equipment.
When the unit is connected to the network do not touch terminals.
Short circuit terminals of unused current transformers.
Any electrical parameter applied to the device must be in the range
specified in the user manual. Although the unit is designed with a wide safety margin, over-range parameters may reduce lifetime, alter operational precision or even damage the unit.
Do not try to clean the device with solvent or the like. Only clean with a
dump cloth.
Verify correct terminal connections before applying power. Only for FRONT panel mounting.
Current Transformers must be used for current measurement. No direct connection allowed.
WARNING: Use of fuses of higher rating than allowed may result in serious hazards.
SAFETY NOTICE Failure to follow below instructions will result in death or serious injury
DKG-225 User Manual Firmware V-01
- 5 -
1. INSTALLATION INSTRUCTIONS
2. MOUNTING
2.1 DIMENSIONS
2.2 SEALING, GASKET
2.3 ELECTRICAL INSTALLATION
3. TERMINAL DESCRIPTIONS
3.1. BATTERY VOLTAGE INPUT / OUTPUT
3.2. AC VOLTAGE INPUTS
3.3. AC CURRENT INPUTS
3.4. DIGITAL INPUTS
3.5. ANALOG SENDER INPUTS
3.6. CHARGE INPUT TERMINAL
3.7. MAINS CONTACTOR OUTPUT
3.8. GENERATOR CONTACTOR OUTPUT
3.9. DIGITAL OUTPUTS
4. CONNECTION DIAGRAM
5. TERMINAL DESCRIPTION
6. TECHNICAL SPECIFICATIONS
7. DESCRIPTION OF CONTROLS
7.1. FRONT PANEL FUNCTIONALITY
7.2. PUSHBUTTON FUNCTIONS
7.3. DISPLAY SCREEN ORGANIZATION
7.4. MEASURED PARAMETERS
7.5. LED INDICATORS
8. OPERATION OF THE UNIT
8.1. QUICK START GUIDE
8.2. STOP MODE
8.3. MANUAL RUN MODE
8.4. AUTO MODEN
9. PROTECTIONS AND ALARMS
9.1. SERVICE REQUEST ALARM
9.2. ALARMS
10. PROGRAMMING
11. CRANK CUTTING
TABLE OF CONTENTS
DKG-225 User Manual Firmware V-01
- 6 -
12. SOFTWARE FEATURES
12.1. REMOTE START OPERATION
12.2. MAINS SIMULATION
12.3. DELAYED MAINS SIMULATION, BATTERY CHARGING
12.4. SERVICE REQUEST DISPLAY
12.5. ENGINE HOUR METER
12.6. SOFTWARE VERSION DISPLAY
12.7. GAS ENGINE FUEL SOLENOID CONTROL
12.8. SINGLE PHASE OPERATION
13. DECLARATION OF CONFORMITY
14. MAINTENANCE
15. DISPOSAL OF THE UNIT
16. ROHS COMPLIANCE
17. TROUBLESHOOTING
TABLE OF CONTENTS (continued)
DKG-225 User Manual Firmware V-01
- 7 -
Before installation:
Read the user manual carefully, determine the correct connection diagram. Remove all connectors and mounting brackets from the unit, then pass the unit through the
mounting opening.
Put mounting brackets and tighten. Do not tighten too much, this can brake the enclosure. Make electrical connections with plugs removed from sockets, then place plugs to their sockets. Be sure that adequate cooling is provided. Be sure that the temperature of the environment will not exceed the maximum operating
temperature in any case.
Below conditions may damage the device:
Incorrect connections. Incorrect battery voltage. Reverse battery voltage Voltage at measuring terminals beyond specified range. Voltage applied to digital inputs over specified range. Current at measuring terminals beyond specified range. Overload or short circuit at relay outputs Excessive vibration, direct installation on vibrating parts.
Below conditions may cause abnormal operation:
Battery voltage below minimum acceptable level. Frequency out of specified limits Missing earthing
Current Transformers must be used for current measurement. No direct connection allowed.
1. INSTALLATION INSTRUCTIONS
DKG-225 User Manual Firmware V-01
- 8 -
Dimensions: 133x107x46mm (5.25”x4.2”x1.9”) Panel cutout: 117x87mm minimum (4.6”x3.43”) Weight: 200g (0.45 lb)
87m
m
117mm
WALL
40mmmin 60mm
Mount the unit on a flat, vertical surface. Before mounting, remove the mounting brackets and connectors from the unit, then pass the unit through the mounting opening.
Place and tighten mounting brackets.
The unit is designed for panel mounting. The user should not be able to access parts of the unit other than the front panel.
2.1. DIMENSIONS
2. MOUNTING
DKG-225 User Manual Firmware V-01
- 9 -
The module will come with one of below bracket types:
Screw type bracket
Spring type bracket
Screw type bracket installation
Spring type bracket installation
Do not tighten too much, this may break the unit.
DKG-225 User Manual Firmware V-01
- 10 -
The rubber gasket provides a watertight means of mounting the module to the genset panel. Together with the gasket, IEC 60529-IP65 protection can be reached from the front panel. A short definition of IP protection levels is given below.
1st Digit Description of Protection Level
0 Not protected 1 Protected against solid foreign objects of 50 mm diameter and greater 2 Protected against solid foreign objects of 12,5 mm diameter and greater 3 Protected against solid foreign objects of 2,5 mm diameter and greater 4 Protected against solid foreign objects of 1,0 mm diameter and greater 5 Protected from the amount of dust that would interfere with normal operation
6 Dust tight
2nd Digit Description of Protection Level
0 Not protected 1 Protected against vertically falling water drops 2 Protected against vertically falling water drops when enclosure is tilted up to 15 ° 3 Protected against water sprayed at an angle up to 60 ° on either side of the vertical 4 Protected against water splashed against the component from any direction
5 Protected against water projected in jets from any direction
6 Protected against water projected in powerful jets from any direction 7 Protected against temporary immersion in water 8 Protected against continuous immersion in water, or as specified by the user
2.2. SEALING, GASKET
Module
Gasket
Panel
DKG-225 User Manual Firmware V-01
- 11 -
Although the unit is protected against electromagnetic disturbance, excessive disturbance can affect the operation, measurement precision and data communication quality.
ALWAYS remove plug connectors when inserting wires with a screwdriver. Fuses must be connected to phase voltage inputs, in close proximity of the
unit.
Fuses must be of fast type (FF) with a maximum rating of 6A. Use cables of appropriate temperature range. Use adequate cable section, at least 0.75mm2 (AWG18).  Follow national rules for electrical installation. Current transformers must have 5A output. The current transformer cable length should not exceed 1.5 meters. If
longer cable is used, increase the cable section proportionally.
Current Transformers must be used for current measurement. No direct connection allowed.
For the correct operation, engine body must be grounded. Otherwise faulty voltage and frequency measurements may occur.
Do not install the unit close to high electromagnetic noise emitting devices like contactors, high current busbars, switchmode power supplies and the like.
2.3. ELECTRICAL INSTALLATION
DKG-225 User Manual Firmware V-01
- 12 -
Battery terminals are both internal battery charger outputs and battery supply inputs. When AC mains supply is available, the unit charges the battery. When mains voltages fail, the unit
continues operation through the engine battery.
Charger output voltage:
13.7VDC
Charger output current
1.0 ADC
Operating voltage range:
8 - 16VDC
Cranking dropouts:
Survives 0VDC during 100ms. The voltage before surge should be 9VDC minimum
Max. Operating current:
200mA @ 12VDC. (All features active, outputs open)
Typical operating current:
100mA @ 12VDC. (All features passive, digital outputs open)
Measurement range:
0 - 36VDC
Display resolution:
0.1VDC
Accuracy:
1.0% + 1 digit @ 12VDC
Measurement method:
True RMS
Input voltage range:
14 to 300 VAC (phase-neutral)
Min voltage for frequency detect:
14 VAC (Ph-N)
Measurement range:
0 to 330VAC ph-N (0 to 570VAC ph-ph)
Common mode offset:
Max 100V between neutral and battery negative
Input impedance:
4.5M-ohms
Display resolution:
1VDC
Accuracy:
1.0% + 1 digit @ 230VAC ph-N (±3VAC ph-N)
1.0% + 1 digit @ 400VAC ph-ph (±5VAC ph-ph)
Frequency range:
DC to 100 Hz
Frequency display resolution:
0.1 Hz
Frequency accuracy:
0.2% + 1 digit (±0.2 Hz @ 50Hz)
Be sure that battery connection is not reversed. Reverse connection will damage the unit.
3.1. BATTERY VOLTAGE INPUT / OUTPUT
3. TERMINAL DESCRIPTIONS
3.2. AC VOLTAGE INPUTS
DKG-225 User Manual Firmware V-01
- 13 -
Measurement method:
True RMS
CT secondary rating:
5A
Measurement range:
5/5 to 500/5A minimum
Input impedance:
15 mili-ohms
Burden:
0.375W
Maximum continuous current:
6A
Measurement range:
0.1 to 7.5A
Common mode offset:
Max 5VAC between BAT- and any CT terminal.
Display resolution:
1A, 0.1A (3 digits)
Accuracy:
1.0% + 1 digit @ 5A (± 0.6A @ 5/50A)
SELECTING THE CT RATING AND CABLE SECTION:
The load on a CT should be kept minimum in order to minimize phase shift effect of the current transformer. Phase shift in a CT will cause erroneous power and power factor readings, although amp readings are correct.
Datakom advises CT rating to be selected following this table for the best measurement accuracy.
SELECTING THE CT ACCURACY CLASS:
The CT accuracy class should be selected in accordance with the required measurement precision. The accuracy class of the Datakom controller is 1.0%. Thus 1.0% class CTs are advised for the best result.
Current Transformers must be used for current
measurement. No direct connection allowed.
No common terminals or grounding allowed.
3.3. AC CURRENT INPUTS
DKG-225 User Manual Firmware V-01
- 14 -
CONNECTING CTs:
Be sure of connecting each CT to the related phase input with the correct polarity. Mixing CTs between phases will cause faulty power and pf readings.
Many combinations of incorrect CTs connections are possible, so check both order of CTs and their polarity. Reactive power measurement is affected by incorrect CTs connection in similar way as active power measurement.
CORRECT CT CONNECTIONS
Let’s suppose that the genset is loaded with 10 kW on each phase. The load Power Factor (PF) is 1. Measured values are as follows:
kW
kVAr
kVA
pf
Phase L1
10.0
0.0
10
1.00
Phase L2
10.0
0.0
10
1.00
Phase L3
10.0
0.0
10
1.00
Total
30.0
0.0
30
1.00