Datakom DK-45 User Manual

DK-45 User Manual V1.0 (22.09.2016)
COMPRESSOR
CONTROLLER
The DK-45 is a high-tech product providing control and protection of screw or piston type air compressors driven by electric motors.
The controller incorporates all functions needed in a compressor control panel. Thus no additional modules are necessary resulting in lower panel cost.
The “early start” function analyzes the air consumption
trend and runs the compressor so that the pressure never falls below the low limit.
The controller is directly supplied from the 230/400V utility network. It provides fail contact and sensor supplies internally, removing the need for a supply transformer in the panel.
Utility mains voltages and frequency can be read on the controller. It offers low/high voltage and phase order protections.
The 2.9” wide, 128x64 pixels graphical screen displays
values in bigger size and with graphic support. The logic level Modbus RTU communication port of the
controller allows computer connection providing monitoring and program parameter adjusting.
Optically isolated digital inputs feature noise filtering allowing fault-free operation in electrically noisy environments.
The controller provides 5 relay outputs rated at 5 Amps.
The controller configuration may be done through the front panel or using the free PC software. The PC software is available for free download at manufacturer’s website.
It is possible to monitor and record the controller using the free RAINBOW+ software.
● Graphical LCD screen: 128x64 pixels, 2.9”
● Automatic operation from output pressure
● Voltage protection relay function
● Phase order protection relay function
● Analog speed control output
Multiple compressor support
● Flexible motor hours calculation algorithm
● Early start function preventing pressure drop
● Dryer control function
● History records
● 5 independent service counters
● Supports various topologies
● Displays utility mains voltages
● No external transformer needed
● Star / Delta start-up
● Load solenoid control
5 programmable relay outputs
Optically isolated, programmable digital inputs
2 pressure sensor inputs
2 temperature sensor inputs
● Adjustable sensor characteristics
● Logic level serial port
MODBUS-RTU communications
Password protected front panel programming
● Low panel depth, easy installation
● Wide operating temperature range
Sealed front panel (IP65 with gasket)
DESCRIPTION
FEATURES
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 2 -
Any unauthorized use or copying of the contents or any part of this document is prohibited. This applies in particular to trademarks, model denominations, part numbers and drawings.
This document describes minimum requirements and necessary steps for the successful installation of the DK-45 family controllers.
Follow carefully advices given in the document. These are often good practices for the installation of compressor controllers which reduce future issues.
For all technical queries please contact Datakom at below e-mail address:
technical.support@datakom.com.tr
If additional information to this manual is required, please contact the manufacturer directly at below e­mail address:
technical.support@datakom.com.tr
Please provide following information in order to get answers to any question:
- Device model name (see the back panel of the controller),
- Complete serial number (see the back panel of the controller),
- Firmware version (read from the display screen),
- Measuring-circuit voltage and power supply voltage,
- Precise description of the query.
REVISION
DATE
AUTHOR
DESCRIPTION
01
19.06.2015
MH
First edition, firmware version 1.0
CAUTION: Potential risk of injury or death.
WARNING: Potential risk of malfunction or material damage.
ATTENTION: Useful hints for the understanding of device operation.
REVISION HISTORY
TERMINOLOGY
QUERRIES
ABOUT THIS DOCUMENT
COPYRIGHT NOTICE
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 3 -
Electrical equipment should be installed only by qualified
specialist. No responsibility is assured by the manufacturer or any of its subsidiaries for any consequences resulting from the non-compliance to these instructions.
Check the controller for cracks and damages due to
transportation. Do not install damaged equipment.
Do not open the controller. There are no serviceable parts inside. Fuses must be connected to the power supply and phase voltage
inputs, in close proximity of the controller.
Fuses must be of fast type (FF) with a maximum rating of 6A.
Disconnect all power before working on equipment.
When the controller is connected to the network do not touch
terminals.
Short circuit terminals of unused current transformers.
Any electrical parameter applied to the device must be in the
range specified in the user manual. Although the controller is designed with a wide safety margin, over-range parameters may reduce lifetime, alter operational precision or even damage the controller.
Do not try to clean the device with solvent or the like. Only clean
with a dump cloth.
Verify correct terminal connections before applying power. Only for front panel mounting.
SAFETY NOTICE Failure to follow below instructions will result in death or serious injury
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 4 -
1. INSTALLATION INSTRUCTIONS
1.1. FRONT AND REAR PANELS
1.2. MECHANICAL INSTALLATION
1.3. ELECTRICAL INSTALLATION
1.4. CONNECTION DIAGRAM
2. PUSHBUTTON FUNCTIONS
3. SCREEN SCROLLING
4. MODES OF OPERATION
5. ALARMS AND WARNINGS
5.1. SERVICE ALARM OPTIONS
5.2. LIST OF FAULT CODES
6. OTHER FEATURES
6.1. RESETTING SERVICE COUNTERS
6.2. MODIFYING MOTOR RUN HOURS
6.3. SELECTION OF MOTOR HOURS COUNTING METHOD
6.4. CONNECTION TOPOLOGIES
6.5. PREVENTING PRESSURE LOSS
6.6. ALARM HISTORY
6.7. DRYER FUNCTION
6.8. VARIABLE UNLOAD TIMER
6.9. PID CONTROL AND ANALOG OUTPUT (PWM)
6.10. MOTOR PTC INPUT
7. MULTI-COMPRESSOR OPERATION
8. DIGITAL INPUTS
9. RELAY OUTPUTS
10. PROGRAMMING
10.1. ENTERING THE PROGRAMMING MODE
10.2. LIST OF PARAMETERS
11. MODBUS COMMUNICATIONS
11.1. DESCRIPTION
11.2. MODBUS REGISTER LIST
11.3. ALARMS, WARNINGS, SERVICE REQUESTS
12. DECLARATION OF CONFORMITY
13. TECHNICAL SPECIFICATIONS
TABLE OF CONTENTS
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 5 -
Before installation:
Read the user manual carefully, determine the correct connection diagram. Remove all connectors and mounting brackets from the controller, then pass the controller
through the mounting opening.
Put mounting brackets and tighten. Do not tighten too much, this can brake the enclosure. Make electrical connections with plugs removed from sockets, then place plugs to their sockets. Take into consideration that supply inputs are isolated from measurement inputs. Be sure that adequate cooling is provided. Be sure that the temperature of the environment will not exceed the maximum operating
temperature in any case.
Below conditions may damage the device:
Incorrect connections. Incorrect power supply voltage. Voltage at measuring terminals beyond specified range. Overload or short circuit at relay outputs Connecting or removing data terminals when the controller is powered-up. High voltage applied to communication ports. Ground potential differences at non-isolated communication ports. Excessive vibration, direct installation on vibrating parts.
Below conditions may cause abnormal operation:
Power supply voltage below minimum acceptable level. Power supply frequency out of specified limits
1.1 INSTALLATION INSTRUCTIONS
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 6 -
WALL
40mmmin 60mm
Panel Cutout Dimensions Required Panel Depth
1.1. FRONT AND REAR PANELS
1.2. MECHANICAL INSTALLATION
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 7 -
Although the controller is protected against electromagnetic disturbance, excessive disturbance can affect the operation, measurement precision and data communication quality.
ALWAYS remove plug connectors when inserting wires with a screwdriver. Fuses must be connected to the power supply and phase voltage inputs, in
close proximity of the controller.
Fuses must be of fast type (FF) with a maximum rating of 6A. Use cables of appropriate temperature range. Use adequate cable section, at least 0.75mm2 (AWG18).  Follow national rules for electrical installation. Connect only the provided serial port adapter to the serial communication
port.
Do not install the controller close to high electromagnetic noise emitting devices like contactors, high current busbars, switchmode power supplies and the like.
1.3. ELECTRICAL INSTALLATION
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 8 -
1.4. CONNECTION DIAGRAM
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 9 -
Three pushbuttons on the front panel allow access to programming and measuring screens.
BUTTON
DESCRIPTION
FUNCTION
MENU
Displays the next parameter. Reset alarms. PROGRAMMING: Save the adjusted parameter.
RUN
Reset alarms and run the compressor. PROGRAMMING: Increase parameter value.
STOP
Reset alarms and stop the compressor. PROGRAMMING: Decrease parameter value.
2. PUSHBUTTON FUNCTIONS
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 10 -
When the controller powers-on, the top part of the display will show (P1) the first pressure sensor (or first pressure switch). The pressure unit may be displayed as PSI or Bar following program parameter setting.
The upper visual bar fills up in relation with the current pressure level. The right end of the bar is always set to the maximum displayable pressure, which is E.03 High Pressure
Alarm Limit. The left end of the bar is set to the minimum displayable pressure level.
The (start) icon on the bar indicates the E05. Starting Pressure, the (stop) icon indicates the E04. Stop Pressure and the icon indicates the E.03 High Pressure Alarm Limit.
The bottom part of the display shows (T1) the first temperature sensor. The temperature unit may be °C (degrees celcius) or °F (degrees Fahrenheit) following program parameter setting.
The lower visual bar fills up in relation with the current temperature. The right end of the bar is always set to the maximum displayable pressure, which is E.08 High
Temperature Alarm Limit. The left end of the bar is set to the minimum displayable temperature. The icon indicates the E.08 High Temperature Alarm Limit.
If a relay output is set as the Fan Relay (see chapter 9), when this relay is active a fan icon will appear at the bottom right corner of the display screen.
Through parameter setting in the programming menu, (P2) second pressure value or the differential pressure P2-P1 (DP), (T2) second temperature sensor or the differential temperature T1-T2 (DT) may be displayed in a second pressure/temperature screen.
All measurement screens are scrolled by depressing the MENU pushbutton.
First Pressure/Temperature Screen
Second Pressure/Temperature Screen
3. SCREEN SCROLLING
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 11 -
Phase-to-Neutral voltage screen
Phase-to-Phase voltage screen
Run Hours Screen
Service Timers Screen
This screen shows remaining time to services A,B, C, D and E in hours. Service timers operate on a decremental basis. Service bars are emptied with relation to timer values.
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 12 -
Information Screen
If the E.47 Motor Control PWM Signal is enabled, then instead of start/stop pressures, this screen will show the E.48 Motor Control PWM Set Pressure (DRVR SET PRS) parameter.
Alarm history Screen
Alarm history will be described in detail in chapter 6.6. Above screens or values shown in screens may not be displayed depending on program parameter
setup.
Display of some values are selected with program parameters. Display screens may differ following compressor manufacturers.
When an alarm occurs, the display will show the alarm code and alarm symbol.
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 13 -
Below is the description of some abbreviations displayed on the screen:
ABBREVIATION
DESCRIPTION
P1
First pressure sensor value or first pressure switch position
P2
Second pressure sensor value or second pressure switch position
DP
P2-P1 differential pressure (Delta pressure)
T1
First temperature sensor value
T2
Second temperature sensor value
DT
T1-T2 differential temperature (Delta temperature)
L-1
Voltage between phase L1 and neutral
L-2
Voltage between phase L2 and neutral
L-3
Voltage between phase L3 and neutral
L12
Voltage between phases L1 and L2
L23
Voltage between phases L2 and L3
L31
Voltage between phases L3 and L1
FRQ
Frequency
RUN H.
Total motor run hours (On-load + off-load)
LOAD H.
On-load motor run hours
LD/RUN
(On-load) / (Total) motor hours ratio
STRTS/h
Maximum number of starts per hour
DRVR SET PRS
Motor control PWM signal set pressure
STRT PRES
Compressor’s starting pressure
STOP PRES
Compressor’s stop pressure
MASTR DEV. ADR
Master device address (multi-compressor operation)
NUM OF DEVICES
Number of devices (multi-compressor operation)
SOFTWARE VER.
Device firmware version
msec
milisecond
sec
second)
min
minute
h (hour)
hour
V
Volt
Hz
Hertz
%
percent
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 14 -
Below is the description of some icons displayed on the screen:
ICON
DESCRIPTION
OFF, disabled, not-OK
Remote Start
Reset, cancel, disable
Enabled, adjusted, action complete, OK
Enter / change password
Motor PTC
Pressure-2 in Separator filter
Waiting the pressure in separator filter to drop Remote Start / Stop
Waiting input signal
Max Slaves
Auto restart register, PORO
Dryer function
Insufficient pressure (run the compressor)
Sufficient pressure (stop the compressor)
Remaining hours to service
Run hour counters
Programming
Remote Stop
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 15 -
Selecting the mode of operation:
When powered-up, the device turns-on all lights during 3 seconds for verification. Then it goes into STOP mode and the STOP led turns on.
The compressor may be run with the REMOTE START signal ( icon displayed during 5 seconds) or by depressing the RUN pushbutton.
If the E.27 Safety Timer is not expired, then the RUN led will flash until the expiration of the timer. Then the motor will run is the output pressure is below E.05 Start Pressure.
The compressor is usually stopped with REMOTE STOP signal ( icon is displayed during 5 seconds) or by depressing the STOP pushbutton.
Stop procedure:
STOP led starts flashing. If the compressor is under load, the load relay will release and the motor continues to run during E.27
Safety Delay Timer or E.25 Unload Timer (whichever is longer). During this period the RUN mode may be resumed by depressing the RUN pushbutton.
If the STOP pushbutton is depressed again during off-load running, then the compressor will stop immediately.
The STOP led will continue to flash until the complete stop.
4. MODES OF OPERATION
If an alarm occurs the compressor will stop immediately and the screen will display the alarm code and related icon. Please see chapter_5 for the complete list of alarm codes.
If the compressor is running off-load and the STOP pushbutton is depressed, it will continue to run until the expiration of the E.25 Unload Timer. By depressing again the STOP pushbutton the compressor may be stopped immediately.
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 16 -
Start-up procedure:
If utility mains voltages and frequency is between set limits and the phase order is correct, the the LINE led will turn on. The compressor can run only when the LINE led is on. Otherwise it cannot be run by any means.
The RUN mode is selected by depressing the RUN pushbutton or by setting the REMOTE START signal (if enabled). At this stage the compressor will run only when the output pressure falls below the E.05 Start Pressure (or when the pressure switch closes).
Before the compressor runs, the STAR relay will be activated. After the expiration of E.15 Delay Between Relays Timer the MAIN relay will be active. Thus the motor will start-up in STAR configuration.
After the expiration of E.22 Star Timer the STAR relay will release. After the expiration of E.23 Star Delta Timer the DELTA relay will be active.
After the expiration of E.24 Time Before Load, the LOAD relay will become active and the compressor starts producing compressed air.
Unloading and reloading of the compressor:
When the output pressure reaches E.04 Stop Pressure limit (or the pressure switch opens) the load relay will release and the motor will run off-load during E.25 Unload Timer. If the pressure falls below the
E.05 Start Pressure before expiration of the timer, then the LOAD relay will be activated again.
Stopping and restarting following output pressure:
If the output pressure stays over the E.05 Start Pressure during E.25 Unload Timer, then the DELTA relay relases. After E.15 Delay Between Relays the MAIN relay releases and the compressor stops.
In this position the RUN led is flashing. The maximum number of start cycles that the compressor is allowed to perform in 1 hour is defined by the
F.01 Max Starts per Hour program parameter. If the maximum number of starts is reached, then following stop cycles will be skipped until the expiration
of 1 hour period.
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 17 -
Abnormal conditions of a compressor are divided into 3 categories, being WARNINGS, ALARMS and SERVICE REQUESTS. Warnings are the lowest priority fault conditions and result only in visual warnings. Alarms are highest level fault conditions and cause the compressor to stop immediately, the alarm relay to operate (if enabled) and the controller give visual warning.
When a fault condition occurs, the related fault code and icon will appear on the screen. If the fault condition is an alarm, then the ALARM led will turn on. If the fault is a service request then the SERVICE led turns on.
Warnings may be cancelled by depressing the MENU pushbutton. Alarms cannot be cancelled with pushbuttons. The alarm signal must also be removed. However the depression of the MENU
pushbutton will cause the large alarm icon to disappear and the alarm goes to the upper right corner of the screen.
5. ALARMS AND WARNINGS
When the MENU pushbutton is depressed, the display will rever to the “measurements” screen.
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 18 -
Following the selection of the program parameter F.02 Stop Service Request, the expiration of a service timer may simply cause a visual warning and the activation of the alarm relay, or it may also cause below behaviour:
TIME TO SERVICE
ACTION TAKEN
> 100 hours
No warning occurs
100 hours
Service request warning is given and the service led turns on. The compressor continues normal operation.
0 hours
The compressor stops. Service request warning is given and the service led turns on. The compressor may be run again by depressing the RUN
pushbutton.
-100 hours
The compressor stops. Service request warning is given and the service led turns on. The compressor may be run again by depressing the RUN
pushbutton.
Between -120 and -200 hours, every 20 hours
The compressor stops. Service request warning is given and the service led turns on. The compressor may be run again by depressing the RUN
pushbutton.
Between -210 and -300 hours and every 10 hours
The compressor stops. Service request warning is given and the service led turns on. The compressor may be run again by depressing the RUN
pushbutton.
-300 hours
The compressor stops. Service request warning is given and the service led turns on. The compressor will run only after service is performed.
5.1. SERVICE ALARM OPTIONS
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 19 -
ICON
CODE
DESCRIPTION
FAULT LEVEL
ALARM 01
01
Pressure Safety Switch Open
ALARM
ALARM 02
02
High Pressure
ALARM
ALARM 03
03
Pressure sensor failure
ALARM
ALARM 04
04
High temperature Alarm
ALARM
ALARM 05
05
High Temperature Warning
WARNING
ALARM 06
06
Temperature sensor failure
ALARM
ALARM 07
07
Low temperature Alarm
ALARM
ALARM 08
08
Fan motor high temperature
ALARM
ALARM 09
09
Motor PTC high temperature
ALARM
ALARM 10
10
Voltage unbalance
ALARM
ALARM 11
11
High voltage
ALARM
ALARM 12
12
Low voltage
ALARM
ALARM 13
13
High frequency
ALARM
ALARM 14
14
Low frequency
ALARM
5.2. LIST OF FAULT CODES
DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 20 -
ICON
CODE
DESCRIPTION
FAULT LEVEL
ALARM 15
15
Phase order failure
ALARM
ALARM 16
16
Air filter clogged
WARNING
ALARM 17
17
Max starts per hour exceeded
WARNING
ALARM 18
18
Emergency stop
ALARM
ALARM 19
19
Internal failure
WARNING
ALARM 20
20
High differential pressure
ALARM
ALARM 21
21
Sensor-2 high pressure
ALARM
ALARM 22
22
Pressure sensor-2 failure
ALARM
ALARM 23
23
Sensor-2 high temperature / Delta_T (tS2-tS1) Alarm
ALARM
ALARM 24
24
Temperature sensor-2 failure
ALARM
ALARM 25
25
Sensor-2 low temperature alarm
ALARM
ALARM 26
26
Air in separator filter
WARNING
ALARM 27
27
Delta temperature sensor-2
WARNING
ALARM 28
28
Motor thermic protection switch open (Motor Overload)
ALARM
ALARM 29
29
Sensor-2 low pressure
ALARM
Loading...
+ 44 hidden pages