Instruction / Installation Sheet
AC Power Duplex Surge Module
Part #: 80-0050
DataComm Electronics, Inc.
Parts Included:
● 2 ¾” Steel Electrical Box, 12.5 cu in
● 15 Amp/125 Volt Duplex Surge Protector Outlet
● Four (4) #6-32 Screws
● Decora Wall Plate
● Two (2) Wall Plate Screws
DataComm Electronics’ AC Power Duplex Surge Module is designed to provide protection against short term over-voltage conditions as well as from RFI
(radio frequency interference). Surge Protector Outlet alerts you to the failure of the surge protection component by means of an audible signal. If alarm
sounds, device has “received” power surges in excess of its capacity and is no longer functioning as a surge protector. To shut off alarm, simply turn the
“Alarm Off” screw on the front of the outlet clockwise. Note: When alarm sounds and the “Alarm Off” screw is turn off, the outlet still functions as a normal
duplex outlet without surge protection.
WARNING:
Before installing or working on any electrical circuit be certain the power is off by switching the circuit breaker off. Test the power to make sure the power
is off. Be sure to install DataComm Electronics’ AC Power Duplex Surge Module in accordance with the National Electrical Code (NEC) and local codes.
Surge Protector Outlet Specifications:
Inside the AC Power Duplex Surge
Module are two 22mm square MOV’s
providing 240 joules /15000A of surge
protection for each mode. Meets UL
Standards 1449 3rd Edition and 498:
CSA Certified. Damage-alert alarm
sounds when surge protection is no
longer functioning and keeps sounding
until the muting screw is utilized or the
outlet is replaced. Power-on indicator
light verifies instantly that power is
available at the outlet and the
suppression circuit is fully functional;
light off means power has been
interrupted, flashing light indicates
surge protections circuitry has been
damaged.
Tools Needed:
● Phillips Head Screw Driver
● Wire Cutter and/or Wire Stripper
6349 Peachtree Street
Norcross, GA 30071-1725
888.223.7977
www.datacommelectronics.com
Installation Instructions:
1. To install the AC Power Duple Surge Module, begin by removing the rectangular knock-out in your telecommunication/low-voltage enclosure.
Then remove the necessary knock-out in the Steel Electrical Box.
2. Depending on your local electrical code, route 12/2 or 14/2 with ground UL approved electrical building wire that you have pulled from a power source
(an independent 15A circuit is recommended). Route through metal or plastic conduit when appropriate or required by code.
3. Now use the four (4) #6-32 screws provided to secure the electrical outlet box to the telecommunication/low-voltage enclosure. Secure conduit to
Steel Electrical Box if appropriate.
4. Using the Wire Cutters or Wire Strippers, strip off approximately 3 inches of the outer jacket of the UL approved building wire. Be careful not to cut the
jacket of the inner wires.
5. Connect the hot line (black) wire to the brass colored terminal screw and neutral (white) wire to the silver colored terminal screw.
6. Be sure to connect the grounding (green) or bare grounding wire to the green colored terminal screw.
7. Once you have wired the supplied Duplex Receptacle, screw it into the Electrical Outlet Box until it is firmly secured.
8. Install the Décor Wall Plate over the Duplex Receptacle with the two (2) included Wall Plate Screws.
DataComm Electronics’ products shall be installed and used only as indicated in DataComm Electronics’ product instruction sheets.
49MM