Data Aire Mini dap4 Installation, Operation & Maintenance Manual

Data Aire, Inc. reserves the right to make design changes for the purpose
of product improvement or to withdraw any design without notice.
Table of Contents
1.0 Introduction ............................................................................................................ 4
1.1 Standard Features .......................................................................................... 4
1.2 Operational Features ...................................................................................... 4
1.3 Diagnostics and Service Features .................................................................. 5
1.4 Conditions and Data Displayed ...................................................................... 5
1.5 Functions Displayed ....................................................................................... 5
1.6 Warnings and Alarm Displayed ....................................................................... 5
1.7 Historical Data Displayed ............................................................................... 6
1.8 Programmable Selections .............................................................................. 6
2.0 Getting Started ......................................................................................................7
2.1 Powering the Unit ON/OFF ............................................................................. 8
2.2 Accessing Menus/Passwords .........................................................................8
2.2.1 Changing the Service Level Password ................................................... 9
3.0 Menu Settings ...................................................................................................... 10
3.1 Menu A - ON/OFF ......................................................................................... 10
3.2 Menu B - Setpoints ....................................................................................... 10
3.4 Menu D - Input/Output .................................................................................. 15
3.5 Menu E - Historical Data ............................................................................... 17
3.6 Menu F - Information..................................................................................... 19
3.7 Menu G - Network Cong ............................................................................. 20
3.8 Menu H - Calibrate Sensors.......................................................................... 21
3.9 Menu I - Manual Control ............................................................................... 23
3.10 Menu J - Factory Settings ............................................................................ 24
3.11 Menu K - Alarms and Limits .........................................................................28
3.12 Menu L - Congure I/O ................................................................................35
4.0 Alarms/Clearing Alarms ...................................................................................... 40
4.1 Acknowledging an Alarm ............................................................................... 40
4.2 Clearing Alarms.............................................................................................42
5.0 Mini dap4 Control Logic ......................................................................................43
Temperature Sensor Chart ......................................................................................... 51
Addendum for the gPod Model ..................................................................................55
3 • Mini dap4 User Manual
1.0 INTRODUCTION
The Mini dap4 continues the tradition of advanced electronic devices from Data Aire for monitoring and control of computer room air conditioning units which began in 1977. Each generation has provided more accurate monitoring information and exibility in controlling the unit.
The Mini dap4 offers the denite answer for precision environmental control. The Mini dap4 control system not only controls and monitors temperature, humidity, airow and cleanliness, but also provides component run times, alarm history and an automatic self-test of the microprocessor. All messages are sequentially displayed on a backlit LCD (liquid crystal display). The Mini dap4 can interface with a variety of building management systems (BMS).
1.1 STANDARD FEATURES
Stand Alone Panel: Service terminals or additional devices are not required for programming or monitoring functions
Microprocessor Based: 32 bit, 44 MHz Micro controller. State-of-the-Art technology and reliability in a program-
mable logic control module
LED Illuminated Keys: Six highly reliable keys allow movement through the menus
Backlit Liquid Crystal Display (LCD): Information is displayed and presented in a format that is easily viewed and
understood
All Settings are Programmable from the Face of the Panel: Expedient and user friendly
Layered and Forward and Backward Menu Access: Facilitates programming with exible operation
USB Port: Allows download/upload of software
Multi-Level Password Access: Controls any unauthorized changes to settings and system functions
Database of Unit and Room Conditions: Historical data that facilitates service, apparatus set-up and ne tuning of
setpoints
Factory Programmed Menus: Menus that pertain to the type and method of cooling, reheat and humidication based on the unit’s components and options
Programmed Settings and Historical Data are Saved in Flash Memory: Non-volatile memory stored so all control settings and operational parameters are secured indenitely even during a power outage
Calibrated Temperature and Humidity Sensors: Accurate and consistent regulation especially in multiple unit ap­plications
1.2 OPERATIONAL FEATURES (Optional features may require additional components and/or sensors)
Sequential Load Activation: Time and temperature based logic that sequentially starts and stops stages of cooling
and reheat
Compressor Short-Cycle Control: Prevents excessive compressor wear by using restart and anti-cycle limits
Automatic or Manual Restart: Restart methods are programmable in the event of a power failure
Humidity Anticipation: Modies the humidity setpoint to reduce excess humidication and dehumidication
Dehumidication Mode Lockout: Inhibits dehumidication if not required for system performance
Start Time Delay:
Automatic Compressor Rotation: Periodically rotates the lead/lag compressor sequence to balance run times
4 • Mini dap4 User Manual
Programmable time delay staggers the start-up of multiple units to prevent high power demand peaks
1.3 DIAGNOSTICS AND SERVICE FEATURES
Alarms Displayed in Order of Occurrence: Sequence with time of occurrence assist in diagnosing the cause of
alarm(s)
Programmable Delays for Optional Alarms: Reduces nuisance and false alarms caused by temporary or transient conditions
Manual Diagnostics Program: Provides accessible procedures to test the processor and major system components
Adjustable Alarm Limits: Threshold levels for temperature and humidity alarms are programmable
Optional Programmable Alarm Contact: Allows selection of an alarm matrix that will operate the contact
Audio Alarm Tone: Three (3) programmable alarm tones are available
Alarm History: 100 alarms are stored for system follow-up
1.4 CONDITIONS and DATA DISPLAYED
UNIT TYPE: Data Aire model type TEMPERATURE SETPOINT: Current temperature setpoint (°F or °C)
TIME: Current time (hour/minute) UNIT ID/ZONE ID: Assigned unit ID and Zone Number*
UNIT STATUS: ON or OFF TEMPERATURE: Current return air temperature (°F or °C)
HUMIDITY: Current return air humidity (%) HUMIDITY SETPOINT: Current humidity setpoint (%)
DATE: Current date (month/day/year) DISCHARGE AIR: Current chilled water temperature (°F or °C)*
CHILLED WATER TEMPERATURE: Current Temperature (°F or °C)*
1.5 FUNCTIONS DISPLAYED
COOLING: 1st stage, 2nd stage* HUMIDIFICATION: Appears when operating*
DEHUMIDIFICATION: Appears when operating REHEAT: Appears when operating
CHILLED WATER FLOW: Valve Opening: 0 - 100%
1.6 WARNINGS and ALARMS DISPLAYED
HIGH TEMPERATURE WARNING LOW TEMPERATURE WARNING HIGH HUMIDITY WARNING LOW HUMIDITY WARNING POWER FAILURE RESTART NO AIRFLOW DIRTY FILTER* FIRESTAT TRIPPED MANUAL OVERRIDE* HUMIDIFIER PROBLEM* MAINTENANCE REQUIRED TEMPERATURE SENSOR FAILURE HUMIDITY SENSOR FAILURE SMOKE DETECTOR* CUSTOM MESSAGE* FAN MOTOR OVERLOAD* DISCHARGE AIR SENSOR ERROR* HIGH CONDENSATE WATER LEVEL STANDBY PUMP ON* PERSON TO CONTACT ON ALARM HIGH PRESSURE/COMP FAILS COMP 1 NO WATER FLOW* HIGH PRESSURE/COMP FAILS COMP 2*
For Chilled Water units, 3 optional alarms can be selected For DX units, single circuit, 2 optional alarms can be selected For DX units, dual circuits, 1 optional alarm can be selected
* This optional feature or data display may require additional components and/or sensors
5 • Mini dap4 User Manual
1.7 HISTORICAL DATA DISPLAYED
EQUIPMENT RUNTIMES: Blower, compressor 1, compressor 2 (as applicable), reheat, dehumidication, Energy Saver*, humidier, condenser and chilled water
ALARM HISTORY: Alarm list with time and date of occurrence
LAST 24 HOURS: High and low temperature, high and low humidity
AVERAGE PERCENT OF CAPACITY LAST HOUR: Compressor(s), humidier, reheat strips and water valve
1.8 PROGRAMMABLE SELECTIONS
TEMPERATURE SETPOINT TEMPERATURE DEADBAND HIGH TEMPERATURE ALARM LIMIT LOW TEMPERATURE ALARM LIMIT HUMIDITY SETPOINT HUMIDITY DEADBAND HIGH HUMIDITY ALARM LIMIT LOW HUMIDITY ALARM LIMIT COMPRESSOR LEAD/LAG SEQUENCE RESET EQUIPMENT RUNTIMES AUDIO ALARM MODE HUMIDITY ANTICIPATION COMPRESSOR SHORT CYCLE ALARM DEHUMIDIFICATION MODE LOW DISCHARGE TEMPERATURE ALARM LIMIT* POWER RESTART/RESTART MODE SYSTEM START DELAY MANUAL DIAGNOSTICS MESSAGE FOR OPTIONAL ALARM 1, 2, 3 PERSON TO CONTACT ON ALARM DELAY FOR OPTIONAL ALARM 1, 2, 3 TEMPERATURE SCALE COMPRESSOR ASSIST TO ENERGY SAVER REHEAT STAGES REMOTE ALARM SELECTION COMPRESSORS FIRESTAT TEMPERATURE ALARM LIMIT HUMIDIFIER CALIBRATE TEMPERATURE SENSOR WATER VALVE VOLTAGE RANGE CALIBRATE HUMIDITY SENSOR REVERSE ACTING WATER VALVE SCHEDULED NORMAL MAINTENANCE COOLING STAGE to STAGE BAND NETWORK PROTOCOL* ANALOG OUTPUT for MOD CW CALIBRATE DISCHARGE AIR SENSOR* ANALOG OUTPUT for MOD HUMID CALIBRATE CHILLED WATER TEMPERATURE SENSOR* WATER VALVE MODE
6 • Mini dap4 User Manual
2.0 GETTING STARTED
The Mini dap4 consists of two main components: the control module and the display panel. The control module is located in the electrical panel. The display panel is remotely mounted. The two are connected by special telephone type cable harness (units may be ordered with longer cables for optional remote wall mounting).
Note: Factory cable is required. This is a custom made cable and must be ordered from Data Aire. A regular tele­phone cable will not operate.
All data displayed on the display screen originates from the control module. The display panel has a backlit LCD (liq­uid crystal display). There are six keys on the face of the display panel to retrieve or enter settings.
Control Module
Display Module
Display Alarm
Enter Menu
Return to previous screen or hold to turn On or OFF
Button Functions
Allows viewing of active alarms Silences audible alarms Resets active alarms
Allows entry to Main Menu
Up
Enter/Select
Down
Allows scrolling to next screen Allows values changes (increase)
Allows entry to Menus Advances cursor
Return to previous screen Hold ve seconds to turn ON or OFF
7 • Mini dap4 User Manual
Returns to previous screen Allows value changes (decrease)
The main loop will ip though a series of screens that allow you to see set-points, current unit status (temperature, relative humidity and operating mode – cooling, humidication, etc.).
MINI-PLUS
08/02/11 08:25
Unit Status: UnitOn
Temp SP 72.00 Hum SP 50%
2.1 POWERING the Unit ON/OFF
Before powering unit ON, check that power is available and proper connections have been completed.
Turn the disconnect switch to the ON position. The controller display keys and screen will illuminate and the proces­sor will conduct a self-test (the screen will remain illuminated with no messages until the testing is complete). The self-test takes approximately 20 seconds. Once completed, the Main Menu screen will be displayed. For initial pro­gramming of setpoints, alarms, delays, etc., it is not necessary to have the unit ON. With the unit in the “OFF by Key” mode, all settings are available to view and change (other than Menus J – Factory Settings and L – Congure Inputs/ Outputs) if the proper password is entered.
The Main Menu screen will display the unit type, date and time, and unit status. In addition, the screen will scroll and display the temperature, relative humidity and operating mode.
The Unit Status will indicate the unit: ”OFF by Key”
The unit may be turned ON at any time. Hold the ESC key for approximately 5 seconds. The display will continue to scroll and display messages. At the same time the unit status is changed to “Unit On”. Once powered there will be a 5-600 second start delay indicated by “Time Before Start: XXs”.
Note: The start time delay is programmable from 5-600 seconds (Menu J – Factory Settings). The factory setting is 5 seconds.
2.2 ACCESSING MENUS/PASSWORDS
To access any Menu a numerical password is required. There are two levels of password:
• SERVICE LEVEL • FACTORY LEVEL
The SERVICE LEVEL password allows viewing and changes to the following Menus:
A. On/Off D. Input/Output G. Network Conguration K. Alarms/Limits B. Setpoint E. Historical Data H. Calibrate Sensors C. Clock/Scheduler F. Information I. Manual Control
The FACTORY LEVEL password allows changes to the SERVICE LEVEL Menus plus the following Menus:
J. Factory Settings L. Congure Inputs/Outputs
The ZONE MASTER is an optional feature and requires a factory provided activation code. Contact factory if ZONE MASTER control is required.
8 • Mini dap4 User Manual
To enter the Menu and Sub-Menu screens, press the MENU key on the display panel. A password will be requested. The password is a four digit entry (including 0). Units are shipped from the factory with the password requirement bypassed to accommodate start-up and set-up.
The display screen will have the following message:
The Service Level Password setting from the factory is: 0000
Security Access
Insert Service/Factory level password: 0000
The cursor will be ashing at the top of the screen. Press the ENTER key to move the cursor to the rst eld. Press the UP or DOWN keys to increase or decrease the value. Once the value is entered, press the ENTER key to move to the next input. Increase or decrease t
he value by pressing the UP or DOWN keys. Once the desired value is shown,
press the ENTER key to move to the next eld.
Once the correct password is entered and accepted, the Menus will display on the screen. Only those Menus allowed through the Service Password will be available. Use the UP or DOWN keys to scroll through the available Menus.
Note: Factory Level Menus are for conguring the unit. The Mini dap4 controller is used for a variety of equipment types. The controller is based on the unit type, unit components and options. Under normal circumstances these menus should not be changed. If they need to be changed, please consult with Data Aire engineering or service per­sonnel before proceeding.
2.2.1 Changing the Service Level Password
The Service Level password can be changed while the service level menu is active.
▼ After entering the Service password press Menu key again then press Down key, the screen will display the follow­ing message:
Service Security
Change service level password (PWI): 0000
▼ Press the ENTER key. The cursor will highlight the rst input. Change the input by pressing the UP or
DOWN Once the selected number is displayed, press the ENTER key to move to the next input. Repeat the same steps for each input.
After the last input has been entered the new password is stored. Press the MENU key to return to Main Menu.
9 • Mini dap4 User Manual
key.
3.0 ENTERING MENU SETTINGS
3.1 MENU A – ON/OFF
Use the UP or DOWN key to scroll through the menus. Once the desired menu is highlighted, press the ENTER key.
MENU A allows Start-Up Delay Time, Start-Up Mode and ON/OFF to be changed from the factory settings (the Ser­vice Level password is required for entry).
The following will appear on the display screen:
On/Off Unit Start-up Delay: 5s Start-up Mode: On
Hold ESC for 5 seconds to turn unit ON or OFF
The cursor will be ashing at the upper left hand corner. Press the ENTER key. The cursor will move to the “Start-up Delay”. The start-up delay is the time before the blower starts after being powered ON and the processor has com­pleted its self-test. Press either the UP or DOWN button to change the delay time. The range is 5 to 600 seconds. Once a time is selected, press the ENTER key to save the setting and move to the next line “Start-Up Mode”.
Press the UP or DOWN keys to change the mode from ON to OFF or from OFF to ON. The setting will determine what the unit will do if power is interrupted. With the setting ON, the unit will automatically start once the self-test is completed. With the setting OFF, the unit will require manually starting by holding the ESC key for ve (5) seconds. Depending on which selection is made (ON or OFF), the Status will display – Unit On or Unit Off by Key
Once selections are made, leave MENU A by pressing the MENU key. The Main Menu screen will continue to display other menus (B, C, E and F). To look at any of these menus scroll to the desired menu. Press the ENTER key. If you choose to return to the Main Screen, press the ESC key.
3.2 MENU B - SETPOINTS
MENU B allows viewing and changing of Setpoints (Service Level password is required for entry)
Press the UP or DOWN key until “B. Setpoint” appears and is highlighted. Press the ENTER key.
Use the UP or DOWN key to scroll through the screens. Menu B has two screens.
The following will appear on the rst Menu B screen (values are for reference only):
Setpoints Temp Setpoint: 72.0oF Temp Deadband: 2.0oF Stage-To-STAGE: 0.3oF
10 • Mini dap4 User Manual
Press the UP or DOWN key. The following will appear on the screen:
Setpoints Humidity Setpoint: 50% Humidity Deadband: 3%
Engy Svr SetPt: 50.0oF
Deadband: 1.0oF Change Over: 2.0oF
FACTORY SETTINGS:
TEMPERATURE: 72.0°F (Temperature range: 65 - 85°F) DEADBAND: 2.0°F (Temperature Deadband range: 1 - 5°F) STAGE TO STAGE: 0.3°F (Stage-to-Stage range: 0.3 - 3.0°F)
HUM SETPOINT: 50% (Humidity range: 25-70%) HUM DEADBAND: 3% (Humidity deadband range: 1 - 15%)
ENGY SVR SETPT: 50.0°F (Setpoint range: 40.0 - 60.0°F) DEADBAND: 1.0°F (Deadband range: 1.0 - 5.0°F) CHANGE OVER: 2.0°F (Change over range: 2.0 - 5.0°F)
If Humidity Anticipation is turned ON in humidity setting under Menu J - Factory Settings, the following page appears for reference (non-edit able):
Humidity Anticipation Setpoints
Humidity Setpoint: 50% Temperature Offset: 3% Anticipation SP: 5.3%
To change the value of any one of the setpoint values, move the cursor by pressing the ENTER key to the desired set­point. The cursor will ash on the input value. Press the UP or DOWN button to increase or decrease the value. Once the desired setpoint value has been changed, press the ENTER key to move to the next setting or until the cursor is at the top of the screen.
Exit the Setpoint Menu by pressing the ESC Key. The display screen will return to the MAIN MENU. Use the UP or DOWN Keys to advance to another Menu or press the ESC Key to return to the normal operating mode.
Note: Changes to any Setpoint input will remain and can only be changed manually (as described above).
3.3 MENU C – CLOCK/SCHEDULER
MENU C allows programming for setting night set-back, week-end and special day schedules.
Menu C should only be used for non-critical applications where units may be cycled off without any damage to sensitive electronic equipment. The typical application is comfort cooling where units may be shut down during non-working hours.
11 • Mini dap4 User Manual
Enter Menu C by pressing the ENTER key. The following message will be displayed (values are for reference only):
Clock Settings
Day: Saturday
Date: 05/16/11
Hour 09:39
To change the date or time, move the cursor by pressing the ENTER key to the date. To change the date, use the UP or DOWN keys. By pressing the ENTER key the cursor will move from segment to segment. Only the UP and DOWN keys will change the value. The day will automatically change when the date has been altered.
Press the ENTER key until the cursor is in the title block (upper left hand corner). Press the UP or DOWN key to see the next screen.
The following will be displayed (values are for reference only):
Set-Back Setting
Set-Back Enable: No
Override Time: 12Hrs Cooling Offset 5.0oF Humidity Offset: 10% Dehumidify Offset: 10%
Note: Leaving the “Set-Back Enable” as NO, the set-back feature is non-operational and is the recommended setting for applications with constant load and cooling requirements.
The factory setting is NO
Ranges:
Override Time - the range is 1-12 hours Cooling Offset - the range is 0-30°F Heating Offset - the range is 0-30°F Humidify Offset - the range is 0-30% Dehumidify Offset - the range is 0-30%
If Set-Back enable is YES, the Override Schedule will appear as the following (values are for reference only):
Set-Back Setting Set-Back Enable: Yes Override Schedule No Override Time: 12Hrs Cooling Offset 5.0oF Humidity Offset: 10% Dehumidify Offset: 10%
To change values, move the cursor to the desired input by pressing the ENTER key. Change the value by pressing either the UP or DOWN key. Once all changes are made to inputs on screen, move the cursor to the top and press the UP or DOWN keys to move to the next screen or press the MENU key to return to Main Menu screen.
12 • Mini dap4 User Manual
Week Day Scheduler (only appears if the above Set-Back Enable selection was YES)
From the “Set-Back Settings” screen (with cursor at the top), press the DOWN key.
The following will be displayed (values are for reference only):
Week Day Scheduler Day: MONDAY Copy to: Monday No
1: 06:00 Normal SP 2: 17:00 Normal SP 3: --:-- ---------
4. --:-- ______
Setting
Screen Inputs
Press the ENTER key to move the cursor. The cursor will ash at the day (Monday). By pressing the UP or DOWN key all the days of the week can be viewed (or selected).
Press the ENTER key. The cursor will ash on the “Copy to: Day” Pressing the UP or DOWN key all the days of the week can be viewed.
The “Copy to:” function allows the user to copy setting from other days without going through the settings routine. By pressing the ENTER key, position the cursor on the Day: Press the UP or DOWN keys to scroll through the days of the week. Select the day that has been programmed and is to be copied. Press the ENTER key. The cursor will ash on the “Copy to:”. Scroll through the days using the UP or DOWN key. Select the day to copy. Press the ENTER key. The cursor will ash by the NO message. Press the UP or DOWN key to change for to YES. Press the ENTER key. The display will have a SUCCESSFUL COPY message (which quickly is automatically removed).
The cursor will return to the title block. Repeat the same step for each day to be copied or select ALL.
▼ Press the ENTER key. The cursor will ash on the “NO or YES” setting. Pressing the UP or DOWN key will change from YES to NO or NO to YES. Leave in the NO setting until selections have been made.
▼ Press the ENTER key. The cursor will ash on the rst time setting. All time is on a 24 hour clock (i.e. 6:00 PM = 1800 hours). The start time (line # 1) is selected by pressing the UP or DOWN key.
▼ Press the ENTER key to change the hour. By pressing the UP or DOWN key, the hour will change. Once the cor­rect hour is selected, press the Enter key.
The cursor will ash on the minutes. By pressing the UP or DOWN key, the minutes will change. Once the correct minutes are selected, press the Enter key.
The cursor will be positioned on the settings input. Press the DOWN key to view the available selections:
Set-Back Normal SP (setpoint) Turn Off
▼ Press the ENTER key. The cursor will ash on the second time setting.
Repeat the steps to set the second time setting (and third and fourth if used).
Once the settings are complete, with the cursor in the title block, press the DOWN key to advance to the next screen or press ESC to return to the Main Menu or press the ESC key to return to normal operation.
13 • Mini dap4 User Manual
The following will be displayed (values are for reference only):
Holiday Scheduler Date Date Start Stop Settings
07/04 07/05 Turn Off
--/-- --/-- -----------
--/-- --/-- -----------
Available settings:
Normal SP Turn Off Set-Back
Once the settings are complete, with the cursor in the title block, press the DOWN key to advance to the next screen or press ESC to return to the Main Menu or press the ESC key to return to normal operation.
The following will be displayed (values are for reference only):
Special Day Scheduler
Day Day Setting
SD:1 --/-- --------­ SD:2 --/-- --------­ SD:3 --/-- --------­ SD:4 --/-- --------­ SD:5 --/-- --------­ SD:6 --/-- ---------
Available settings:
Normal SP Turn Off Set-Back
Once the settings are complete, with the cursor in the title block, press the DOWN key to advance to the next screen or press ESC to return to the Main Menu or press the ESC key to return to normal operation.
14 • Mini dap4 User Manual
3.4 MENU D – INPUT/OUTPUT
MENU D is a view only menu allowing the user to view the various input and outputs.
To view, press the Menu key. A prompt for the password will be displayed on the display module. Once the password is entered, the Main Menu screen will display the various menus. Scroll through the menus using either the UP or DOWN keys. Move Menu D to the highlighted area and press the ENTER key.
The following will be displayed (values are for reference only):
Digital Inputs
Digital Inputs
1 2 5 6 7 8
q = Input is Active
▼ Press the DOWN key to view the next screen.
The following will be displayed (values are for reference only):
Digital Outputs
q q q 4 5 6 q q
q = Output is Energized
▼ Press the DOWN key to view the next screen.
The following will be displayed (values are for reference only):
Analog Input
Humidity Input B02: 44.2
▼ Press the DOWN key to view the next screen.
15 • Mini dap4 User Manual
The following will be displayed (values are for reference only):
Analog Input
Retur n Air Temp Input B07: 70.8F
▼ Press the DOWN key to view the next screen.
The following will be displayed (values are for reference only):
Analog Output 2
Chilled Water Valve Output 8.50vdc
▼ Press the MENU key to return to the Main Menu. Choose another Menu by pressing the UP or DOWN keys or press ESC to return the normal operating mode.
16 • Mini dap4 User Manual
3.5 MENU E – HISTORICAL DATA
MENU E allows viewing alarms, component runtimes and resetting of component runtimes
The rst screen will display the most recent alarm (if any had occurred).
The following will be displayed (values are for reference only):
Time and Date of Alarm Alarm Type Humidity at time of occurrence Chilled Water temperature at time of occurrence (if applicable) Discharge Air Temperature at time of occurrence (if applicable)
18:29:26 9/10/11
-> Scroll Up/Down?
Humidity High Humidity: 59% Return Air: 74.2oF Chilled Water: 0.0
o
F
To view consecutive alarms press the ENTER key moving the cursor into the -> eld.
▼ Press the UP key and the display will show the previous alarm, with time and date. Continue to press the UP key to view all alarms. Once the last listed alarm is viewed, press the ENTER to move the cursor back to the top of the screen.
The screen will display the following:
Run Hours 1 Reset Blower: 0000 No Comp 1: 0000 No Comp 2: 0000 No Reheat: 0000 No Humidity: 0000 No Dehum 0000 No
▼ Press the ENTER key to move the cursor. The cursor will ash the reset choice of NO or YES. To reset and clear runtimes, press the UP or DOWN key.
▼ Press the ENTER key until the cursor is ashing on the title line. Press the DOWN key to move to next screen.
▼ Press the ENTER key to move the cursor. The cursor will ash the reset choice of NO or YES. To reset and clear runtimes, press the UP or DOWN key.
▼ Press the ENTER key until the cursor is ashing on the title line. Press the DOWN key to move to next screen.
17 • Mini dap4 User Manual
The screen will display the following:
Run Hours 2 Reset i
Engy Svr: 0000 No CW Cool: 0000 No Cond Aux: 0000 No
Reset all Runtimes: No (or Yes)
With the cursor ashing on the title line, press the UP or DOWN key to review the alarms or runtimes or press the MENU key to return to the Main Menu.
▼ Press the ESC key to return to the normal operating screen.
18 • Mini dap4 User Manual
Loading...
+ 42 hidden pages