DANLERS WACE RFS, CEFL RFS, DIN RFS, EX RFS, CEVO RFS Installation Notes

...
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK. Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388 E-mail: sales@danlers.co.uk Web: www.danlers.co.uk Company Registered Number 2570169 VAT Registration Number 543 5491 38
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
This product conforms to BS EN 60669-2-1.
Please ensure the most recent edition of the appropriate local wiring regulations are observed and suitable protection is provided e.g. 6 amps over current, 1kV over voltage. Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Precautions and Warranty
Installation notes
Radio receiver switches
WACE RFS CEFL RFS DIN RFS EX RFS
CEVO RFS CEVO RFS6A CERF S6A PORF S8A
DANLERS radio receiver switches can be user programmed to respond to any DANLERS radio frequency (RF) manual (or slave) senders. With a manual sender the radio receiver switch will switch the load on when an associated up button is pressed and switch the load off when the down button is pressed.
With a slave sender the radio receiver switch will follow the state of the input signal to the slave sender.
To dim a load use a radio receiver dimmer instead.
Mounting examples
WACE RFS Wall or Ceiling mounted onto a 16mm deep back box CEFL RFS Ceiling Flush (cutout ø 63mm) or in ceiling void DIN RFS Din rail mounting (w x h x d: 36 x 75 x 100mm) EX RFS External unit - rated to IP65
CEVO RFS Ceiling Void, ts cutout ø 60mm (35 x 55x 90mm) CEVO RFS6A Ceiling Void, ts cutout ø 90mm (55 x 75 x 130mm)
CERF S6A Ceiling mounted to Klik-AX socket. Order: CESO(SQ) PORF S8A Portable unit for plugging into square 3-pin socket
Loading limits
Sufx Resistive Fluorescent Fans
RFS 1500W 250W 250W S6A 1500W 1500W 250W S8A 2000W 250W 250W
Connection method
WACE, DIN, EX Via incorporated terminals CEFL, CEVO Via 2 metre ex CERF Klik-AX socket (round: CESO, square: CESO SQ) PORF Plugs into square 3-pin power socket
27/01/11 INS960 RFS
Preprogrammed options
DANLERS radio receiver switches can be factory programmed, with the associated senders, to perform more complex functions, such as:
• On - Auto Off after set time period
- with Manual Off
- with ashing warning 15 seconds before Auto Off
• Delayed Off or On, momentary On or ashing On
• Toggle On - Off with same button.
Faultnding
Radio receiver switch does not respond to sender:
• Ensure the sender is correctly associated to the radio receiver.
• The sender is too far away or RF absorbed by building or trees. Move sender closer to receiver or consider using a repeater.
• The sender battery is at (average life approx. 5 years).
Change battery, make reference to sender installation notes.
LoadandreceiverLEDashtwiceeverytimethesenderispressed:
• Ensure the radio receiver switch is not in programming mode.
Radio receiver relay clicks but load does not switch on / off:
• The load or in-rush current is too large and has damaged receiver. Use a contactor to switch over limit loads.
If you have a pre-programmed radio receiver switch please do not attempt to reprogram it.
Each radio receiver switch can be programmed to respond to up to 15 senders as outlined below. To assign a slave sender please refer to the installation notes received with the slave sender.
CEFL RFS and WACE RFS have a single programming hole, other units also have a smaller LED hole. WARNING: Do not probe the smaller LED hole.
Needed: A small screwdriver to ‘Press’ the internal programming
button of the radio receiver.
Notes: ‘Quick Press’ - less than half a second,
‘Wait Press’ - until next step is completed. To ‘Quick Press’ or ‘Wait Press’ the manual sender use either the up or down button.
Ensure the radio receiver switch is powered.
WARNING: The EX RFS must be open whilst programming, the terminals will be LIVE.
WARNING: If a load is connected during programming it will be
switched on when the LED is on.
To assign a Manual Sender
1 ‘Quick Press’ the radio receiver - LED switches on
2 ‘Quick Press’ the manual sender - LED ashes off twice
To assign more senders repeat step 2 3 ‘Quick Press’ the radio receiver - LED switches off
To de-assign a Manual Sender
1 ‘Quick Press’ the radio receiver - LED switches on
2 ‘Quick Press’ the manual sender - LED ashes off twice
To de-assign more senders repeat step 2 3 ‘Quick Press’ the radio receiver - LED switches off
To de-assign all Senders
1 ‘Quick Press the radio receiver - LED switches on
2 ‘Wait Press’ the radio receiver until LED ashes off ve times
3 Wait for 5 seconds - LED switches off
Installation procedure
1. Please read these notes carefully before commencing work. In case of doubt please consult a qualied electrician. Make sure the power is isolated from the circuit.
2. The radio receiver switch should be connected as: L Live N Neutral SL Switched line output (CERF: Kilk-AX socket ‘A’ terminal)
3.Typical wiring diagrams and mounting details are shown below.
4. EX RFS: unit should be xed using only the pre-drilled mounting holes
and 6-12mm diameter circular cables used. If IP65 rating not achieved then drain-hole guide on lower face of box should be carefully drilled through with 4mm drill to max depth of 10mm, enabling IP54.
5. Once the wiring has been completed and veried, switch on the supply
and program the radio receiver switch to the appropriate senders.
Installation diagrams
Programming procedure
CERF S6A CEFL RFS
Wiring diagram Mounting details
load
L
N
230 VAC
L N SL
‘A’
lighting socket
CERF S6A
Cut-out hole 63 or 64mm (2.5") diameter
Springs closed Springs opened out
WACE RFS, CEFL RFS, DIN RFS, CEVO RFS(6A) EX RFS
Wiring diagram Wiring diagram
load
L
N
230 VAC
SL
radio receiver switch
N
L
load
L
N
230 VAC
L N SL
isolation switch
EX RFS
optional wall switch for overriding off