DANLERS COPD17M Installation Notes

Page 1
Trouble shooting
Note: The COPD17M cannot be made to switch on / off according to variance in ambient light levels.
The PIR does not detect
• Person is too far from the COPD17M switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
The PIR stops working
• Ensure the unit is mounted correctly so that no water can enter.
The PIR False triggers
• Detector is exposed to air movement on breezy days.
Precautions and Warranty
This product conforms to BS EN 60669-2-1 and BS EN 55015.
Please ensure the most recent edition of the appropriate local wiring regulations are observed and suitable protection is provided e.g. a 10 amp circuit breaker and voltage surge protection. Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
Please call for more information or a free catalogue.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK. Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388 E-mail: sales@danlers.co.uk Web: www.danlers.co.uk Company Registered Number 2570169 VAT Registration Number 543 5491 38
08/05/19 INS416 COPD17M
Installation notes
Compact person detector, PIR switch
COPD17M
DANLERS Compact Person Detector can be mounted onto the end of lighting battens via the 20mm knock out. The switch includes the connection 20mm thread and can also be surface mounted onto an external wall. It incorporates a passive infra-red quad sensor to detect movement of a warm body within the detection zone (diagrams A & B).
The maximum detection range is up to 24m when mounted at the maximum mounting height of 17 metres over 120 degrees.
If no more movement is detected within a pre-selected time, then the PIR switch will turn the load off. This time lag can be set via the TIME adjuster to 10 seconds, 20 seconds, 40 seconds, 80 seconds, 2 minutes 30 seconds, 5 minutes,10 minutes, 20 minutes or 40 minutes (diagram C).
Loading
The switch should only be connected to a 230V 50Hz AC supply. These PIR switches can switch up to:
10 amps (2300W) of:
• Fluorescent lamps, either high frequency of switch start
• Incandescent or mains halogen lamps (recommended with integral safety fuse)
They can also switch up to:
• 6 amps (1500W) of electronic or wire wound transformers.
• 6amps(1500W)ofcompactuorescentorLEDlampsanddrivers (PF≥0.95).
• 1 amp (250W) of Fans.
Larger loads can be switched via a contactor.
Page 2
TIME
min max
LUX
max min
10 LUX
40m
20m
10m
5m
2.5m
80s
10s
20s
40s
1000 LUX
Installation procedure
up to 20m
up to 24m
Strong detection zone i.e. person moving arm or walking towards PIR
Secondary detection zone i.e. person walking perpendicular to PIR
10
65
37
24
60
frontside
20mm threaded entry spout
inside
4 x mounting holes. 3M screws recommended (not supplied)
17
48
1. Please read these notes carefully before commencing work.
Incaseofdoubtpleaseconsultaqualiedelectrician.
Make sure the power is isolated from the circuit.
2.
3. If mounting on a lighting batten, Remove the 20mm thread from the PIR and insert it through the 20mm knockout hole with the thread facing outwards.
4. The detector should be connected as shown in diagram D Brown - Live in. Blue - Neutral in. White - Switched Line out.
5. Feed your cable through the thread and with the PIR facing downwards tighten the 20mm thread to ensure a tight seal.
6. The detector can be mounted up to 17 metres high.
7. The detector can also be mounted via any of the four pre-drilled mounting holes (see
diagram E)
.
8. Make sure the power is still isolated from the circuit.
9.
Oncethewiringhasbeencompletedandveried,switchonthesupply
and test the operation.
Time set-up
To set the TIME to a value suitable for the application, turn the PIR time to the desired timeout (diagram C). lag will start again and the load will stay switched on.
A: Ceiling mounted
detection range
For optimum coverage recommended mounting height 17m
Whenever a person is detected, the time
B: Wall mounted detection range
C: Time adjustment
Inside detector housing
D: Wiring diagram
L
optional manual wall switch for overriding off
230 VAC
N
COPD17M can also be wired in parallel
E: Dimensions
Recommended wall mounting height 1 to 2.2 metres
Strong detection zone (up to 10m)
COPD17M
SL
N
load
Loading...