For any soft start situation. VLT® Soft Starters cover the full range – from simple start-stop operation to high end performance.
Soft starts: Protects processes, products and equipment with smooth motor control
An AC motor switched directly on to the mains power supply will struggle to reach its nomi­nal speed as quickly as possi­ble.
This draws maximum current from the power supply and accelerates the application with its maximum torque. Depending on the application, this can cause different problems.
Applications like pumps, conveyers, centrifuges and bandsaws must be started slowly, and sometimes stopped slowly, to prevent mechanical shocks such as water hammer, and strains on bands, couplings and shafts.
Principle of Phase Angle Control
A soft starter is an electronic device that regulates the voltage to the motor and this provides a smooth transition from standstill to full speed operation of the application.
VLT® Soft Starters all use the principle of phase angle control: Back-to-back coupled thyristors ramp up the motor voltage.
In some VLT® Soft Starters, current transformers measure the motor cur­rent, providing feedback for starting current control but also for numerous motor and application protection func­tions.
VLT® Soft Starters cover a comprehensive range
Soft starting and stopping can be controlled in a number of ways depending on the application. Some applications require non-linear volt­age ramp-up and the voltage ramp is therefore related to the actual current drawn. Conversely, a band-saw usually requires a quick stop function provided by a DC brake.
Then again, a number of applica­tions require a kick-start torque for an instantaneous period of time followed by a soft ramp-up acceleration. VLT® Soft Starters cover all of these applica­tions and much more.
2
VLT® Soft Starter MCD 500 VLT® Compact Starter MCD 200 VLT® Soft Starter MCD 100
n Fully featured Soft Starter for
motors up to 1100 HP
n Total motor starting solution n Advanced protection features n Adaptive Acceleration Control n Inside Delta connection n 4 line graphical display n Multiple programming setup
menus
n Compact Soft Starter for
motors up to 150 HP
n Voltage ramps, current limit start
and intregrated motor protection
n Integral bypass design reduces
heat dissipation
n Wide power range with advanced
accessory modules
n Micro Soft Start controller for
motors up to 15 HP
n Extremely robust SCR design
with heavy ratings as standard
n Unlimited number of starts
per hour
n Contactor style design for
easy selection, installation and commissioning
3
VLT® Soft Starter MCD 500
VLT® Soft Starter MCD 500 is a total motor starting solution. Current transformers measure motor current and provide feedback for controlled motor ramp proles.
AAC, the Adaptive Acceleration Control, automatically employs the best starting and stopping prole for the application. Adaptive Acceleration Control means that for each start and stop, the soft starter compares and adapts the process to the chosen prole best suited to the application.
The VLT® Soft Starter MCD 500 has a four-line graphical display and a logic keypad making programming easy. Advanced setup is possible displaying operational status.
Three menu systems: Quick Menu, Application Setup and Main Menu provide optimum programming approach.
The perfect solution, also for more severe applications:
n Pumps n Conveyors n Fans n Mixers n Compressors n Centrifuges n Mills n Saws n And many more
Power range
21 – 1600 A, 10-1100 HP (1.2 MW inside Delta Connection) Versions for 200 – 690 VAC
Features Benets
User friendly
AAC Adaptive Acceleration Control
Adjustable bus bars allow for both top and bottom entry on 360-1600 amp models (200-1100 HP)
DC injection braking distributed evenly over three phases
Inside Delta (6-wire connection)
Log menus, 99 events and trip log provide information on events, trips and performance
Auto Reset – Less down-time
Jog (slow-speed operation) – Application exibility
Second-order thermal model
Internal bypass contactors (21 – 215 A, 10-150 HP)
Auto-start/stop clock – Application exibility
Compact size – amongst the smallest in their class
4-line graphical display
Multiple programming setup (Standard Menu, Extended Menu, Quick Set)
8 language display options – Serving the whole world
– Automatically adapts to the chosen starting
and stopping prole
– Space saving, less cable cost
and easy retrotting
– Less installation cost and
less stress on the motor
– Smaller soft starter can be selected
for the application
– Eases analysis of the application
– Allows motors to be used to their
full potential without damage from overloading
– Save space and wiring compared to
external bypass
– Very little heat dissipates when running.
Eliminates costly external fans, wiring or bypass contactors
– Saves space in cabinets and other application
setups
– Optimum programming approach and setup
for viewing operational status
– Simplies the programming, allowing
maximum exibility