• Same user interface as
VLT® Soft Starter MCD 500
• Plug & play with MCD 500
• Copy/ paste of parameters
• Multiple monitoring setup
• Door-mount kit – 3 m cable
• IP 65 (NEMA 12)
8 | Danfoss Drives · DKDD.PB.551.A1.02
MCD 2 01
• Soft start/stop:
Timed voltage ramp
• Motor protection: not included
• System protection:
not included
• Metering: not included
• Start/stop control: via inputs or via
optional controller
• Network communication: optional
• Bypass: Internally bypassed
MCD 202
• Soft start: Current limit
• Soft stop: Timed voltage ramp
• Motor protection:
Thermistor, Motor overload,
Phase imbalance
• System protection: Phase rotation,
Excess start time, Bypass overload
& Instantaneous overload
• Metering: optional extra
• Start/stop control: via inputs or via
optional controller
• Network communication: optional
• Bypass: Internally bypassed
MCD 201 and MCD 202
• Current: 7.5 kW ~ 110 kW @400 V
• Mains voltage: 200 ~ 575 VAC
• Supply frequency: 45 ~ 66 Hz
• Enclosure: 7.5 ~ 55 kW IP 20,
75 ~ 110 kW IP00
Danfoss Drives · DKDD.PB.551.A1.02 | 9
MCD 100
• Micro Soft Start Controller for
motors up to 11 kW
• Extremely robust SCR design with
heavy ratings as standard
• Unlimited number of starts per hour
• Contactor style design for easy
selection, installation and commissioning
MCD 100
• Current: 1.5 kW ~ 11 kW @400 V
• Mains voltage: 208 ~ 600 VAC
• Control voltage: 24 – 480 VAC/VDC
• Enclosure: 1.5 ~ 11 kW IP 20
10 | Danfoss Drives · DKDD.PB.551.A1.02
Current Ratings
These duty ratings dene the load requirements , not
the starter capabilities. Starter capability is specied
separately in User Manua ls, Product Guides and
WinStar t. Use these charts to select a soft starter for a
particular application.
• Th e soft start er’s current ratin g at the required st art duty must b e at least equal to th e
motor’s nameplate rating. If the motor’s nameplate rating is not available, approximate
information is available from the following table.
AAC is the next evolution in soft starter technology.
Using AAC, the soft starter learns your motor’s performance during
start and stop, then adjusts control to optimize performance.
The soft starter estimates the motor’s speed throughout each
AAC start and stop, and adjusts power to the motor to provide the
selected acceleration or deceleration profile.
AAC is largely unaffected by changes in load, and is particularly
suitable for pumping situations.
AAC offers three starting and stopping profiles: early, constant and
late acceleration/deceleration.
EARLY
CONSTANT
SPEED
LATE
AAC is only available on MCD 500 soft starters.
14 | Danfoss Drives · DKDD.PB.551.A1.02
LATE
CONSTANT
EARLY
AC53 Utilisation Codes: What are AC53 Utilisation Codes?
AC53 utilisation codes describe the current rating for soft starters
under specied operating conditions.
The utilisation code determines the maximum motor size the
soft starter can be used with, under the specied conditions. The
current rating may change under dierent operating conditions.
AC53a: Non-bypassed soft starters
The rating depends on the number of starts per hour, the length
and current level of the start, and the percentage of the operating
cycle that the soft starter will be running (passing current).
AC53b: Bypassed soft starters
The rating depends on the number of starts per hour, the length
and current level of the start, and the amount of time the soft
starter will be o (not passing current) between starts.
Danfoss soft starters provide a relay output, which can
be used to control the main contactor. Ensure that the
inrush VA rating of the contactor coil does not exceed
the rating of the sof t starter’s relay input.
Danfoss Drives · DKDD.PB.551.A1.02 | 15
Auto-Transformer Starters: How does soft start
compare to auto-transformer starting?
Soft starters are much more exible than auto-transformer starters
and provide a much smoother start, generally at a lower cost.
Auto-transformer starters cannot accommodate varying load
conditions (e.g. loaded or unloaded starts) and the start torque
cannot be freely adjusted to match motor and load characteristics.
Damaging torque and current transients still occur at the steps
between voltages, and auto-transformer starters are not capable
of providing soft stop. Auto-transformer starters are large and
expensive, especially if high start frequency is required.
Fault nding: What are the key questions?
To assist your service engineer, they require the following
information:
• Model and serial number of the soft starter
• Motor kW and FLC
• Main supply voltage and frequency
• Control voltage
• Application (e.g. pump, compressor)
• Time installed before failure
• Details of other soft starters on the supply bus. Are these failing?
• If the soft starter trips, details of the code and mode of operation
• The installation’s power and control schematic diagram
16 | Danfoss Drives · DKDD.PB.551.A1.02
Braking:
What are DC braking and soft braking?
DC braking and soft braking both reduce motor stopping time,
unlike soft stopping which increases the stop time on frictional
loads.
DC braking uses DC injection to reduce the motor’s stopping time.
The soft starter slows the motor to approximately 70% of its full
running speed, then applies brake torque to stop the motor in the
selected braking time.
DC braking support is built into MCD 500 soft starters, and no
additional equipment is required. MCD 500 DC braking controls all
three phases, which reduces stress on the motor compared with
two phase braking solutions.
Soft braking uses reversing contactors on the input side of the
starter to start the motor in the reverse direction, which applies
braking torque to the load.
Soft braking causes less motor heating and provides more
braking torque for a given current than DC braking, and is better
for extremely high inertia loads (e.g. band saw and circular saw
applications).
Danfoss Drives · DKDD.PB.551.A1.02 | 17
Bypass Contactors:
When should a bypass contactor be used?
Bypass contactors bridge out the SCRs when the motor is running
at full speed, eliminating heat dissipation during run. This allows
the soft starter to be installed in enclosures without the need for
forced-air cabinet ventilation.
If a soft starter is installed in a totally sealed enclosure (>IP 54) it
must be bypassed.
Bypass contactors should be AC1 rated for the motor FLC (the
bypass contactor does not carry start current).
Soft starters may be internally or externally bypassed:
MCD 200 sof t starters are i nternally bypas sed,
with built-in bypass relays.
MCD 500 sof t starters are i nternally bypas sed up to 500 kW.
Non-bypassed models include relay outputs to control an
external bypass contactor. Dedicated bypass terminals
mean moto r protection sti ll operates even when the sta rter
is bypassed.
18 | Danfoss Drives · DKDD.PB.551.A1.02
Cabling: How is cable selected for
a soft starter installation?
Cable selection criteria depends on the circuit and the location of
the soft starter within the circuit.
1. Supply cable rating > nominal fuse/MCCB rating > motor FLC x 1.2
2. Inside delta motor circuit cable rating > motor FLC x 0.7
Installation factors (including grouping, ambient
temperature, method of installation and single or
parallel cabling) may aect the cable’s current rating.
Always follow the manufacturer’s guidelines and derate
appropriately.
Danfoss Drives · DKDD.PB.551.A1.02 | 19
Cabling: What is the maximum allowable cable,
distance between a soft starter and the motor?
The maximum distance between the soft starter and motor
depends on the voltage drop and the cable capacitance.
Cable must be selected so that when the motor is running fully
loaded, the voltage drop at the motor terminals does not exceed
the limit specied in local electrical regulations.
For distances greater than 500 metres or when using parallel
cabling, cable capacitance may be a factor. If in doubt, please
contact Danfoss with details of the soft starter model, mains
voltage and frequency. If you want to use standard products, we
recommend using Line Reactors.
Calculation
The main point is to limit the di/dt so the SCR’s are not damage
with the inrush currents due to increase cable capacitance. The
output inductors must be installed as close to the soft starter as
possible.
The output inductors must be smaller than the inductance of the
motor.
Minimum rated current of coil, is stated from start current.
(Soft starter selection and application, normally 3 – 4,5 x FLC)
V
p
< L
di
(
dt
)
Vp Vp = V
di
dt
V Motor supply voltage
Ilr Locked rotor current
ω 2 × π × frequency
L
Coil Inductance
coil
20 | Danfoss Drives · DKDD.PB.551.A1.02
V
coil
(√3 I
) ω
LR
× √2
rms
100 A
.
1 μS
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.