Danfoss Electronics VLT Micro Drive Programming Manual

MAKING MODERN LIVING POSSIBLE
PProgramming Guide
VLTp Micro Drive
Contents
Contents
VLT® Micro Drive FC 51 Programming Guide
1 Safety
1.1.1 High Voltage Warning 3
1.1.2 Safety Instructions 3
1.1.3 Software Version and Approvals 3
1.1.4 General Warning 3
1.1.5 IT Mains 4
1.1.6 Avoid unintended Start 4
1.1.8 Before Commencing Repair Work 4
2 Introduction
2.1.1 FC Identification 5
2.1.2 Type Code 6
3 Programming
3.1 How to Programme
3.1.1 Programming with MCT 10 Set-up Software 8
3.1.2 Programming with the LCP 11 or LCP 12 8
3.2 Status Menu
3
5
8 8
9
3.3 Quick Menu
3.4 Main Menu
4 Parameter Descriptions
4.1 Parameter Group 0: Operation/Display
4.2 Parameter Group 1: Load/Motor
4.3 Parameter Group 2: Brakes
4.4 Parameter Group 3: Reference/Ramps
4.5 Parameter Group 4: Limits/Warnings
4.6 Parameter Group 5: Digital In/Out
4.7 Parameter Group 6: Analog In/Out
4.7.3 6-1* Analog Input 1 32
4.8 Parameter Group 7: Controllers
4.9 Parameter Group 8: Communication
4.9.6 8-8* Bus communication diagnostics 39
4.10 Parameter Group 13: Smart Logic
4.10.1 13-** Programming Features 40
4.11 Parameter Group 14: Special Functions
10 10
11 11 14 19 21 25 28 32
36 37
40
45
4.12 Parameter Group 15: Drive Information
4.12.2 15-4* Drive Identification 47
4.13 Parameter Group 16: Data Readouts
MG02C602 - VLT® is a registered Danfoss trademark
47
48
1
Contents
VLT® Micro Drive FC 51 Programming Guide
5 Parameter Lists
5.1.1 Conversion Index 54
5.1.2 Change during operation 54
5.1.3 2-Set-up 54
5.1.4 Type 54
5.1.5 0-** Operation/Display 55
5.1.6 1-** Load/Motor 56
5.1.7 2-** Brakes 57
5.1.8 3-** Reference/Ramps 57
5.1.9 4-** Limits/Warnings 58
5.1.10 5-** Digital In/Out 58
5.1.11 6-** Analog In/Out 59
5.1.12 7-** Controllers 59
5.1.13 8-** Comm. and Options 60
5.1.14 13-** Smart Logic 60
5.1.15 14-** Special Functions 61
5.1.16 15-** Drive Information 61
50
5.1.17 16-** Data Readouts 62
6 Troubleshooting
6.1.1 Alarm, Warning and Extended Status Word 65
Index
63
69
2 MG02C602 - VLT® is a registered Danfoss trademark
Safety
VLT® Micro Drive FC 51 Programming Guide
1 Safety
1.1.1 High Voltage Warning
WARNING
The voltage of the frequency converter is dangerous whenever the motor or frequency converter may cause damage to the equipment, serious injury or death. Consequently, it is essential to comply with the instructions in this manual as well as local and national rules and safety regulations.
it is connected to mains. Incorrect installation of
1.1.2 Safety Instructions
CAUTION
using functions directly or indirectly influencing
Before personal safety (e.g. Safe Stop, Fire Mode or other functions either forcing the motor to stop or attempting to keep it functioning) a thorough risk analysis and system test must be carried through. The system tests must include testing failure modes regarding the control signaling (analog and digital signals and serial communi­cation.
1.1.3 Software Version and Approvals
Software Version
Programming
VLT® Micro Drive
FC 51 Series
This Programming Guide can be used for all VLT
Drive frequency converters with software
Micro
version 2.7X.
The software version number can be read in
15-43 Software Version.
Table 1.1
Guide
1 1
®
NOTE
using Fire Mode, contact Danfoss
Before
sure the frequency converter is properly
Make
connected to earth. Do not remove mains connections, motor
connections or other power connections while the frequency converter is connected to power.
Protect users against supply voltage.
Protect the motor against overloading according
to national and local regulations. The earth leakage current exceeds 3.5 mA.
The [Off] key is not a safety switch. It does not
disconnect the frequency converter from mains.
1.1.4 General Warning
WARNING
ELECTRICAL SHOCK HAZARD Touching equipment has been disconnected from mains. Also make sure that other voltage inputs have been disconnected (linkage of DC intermediate circuit). Be aware that there may be high voltage on the DC link even when the LEDs are turned off. Before touching any potentially live parts of the frequency converter, wait at least 4 min for all sizes. Shorter time is allowed only if indicated on the nameplate for the specific unit.
the electrical parts may be fatal - even after the
MG02C602 - VLT® is a registered Danfoss trademark
3
Safety
VLT® Micro Drive FC 51 Programming Guide
11
CAUTION
Leakage Current
earth leakage current from the frequency converter
The exceeds 3.5 mA. According to IEC 61800-5-1 a reinforced Protective Earth connection must be ensured by means of a min. 10 mm² Cu or an additional PE wire - with the same cable cross section as the Mains wiring - must be terminated separately. Residual Current Device This product can cause a DC current in the protective conductor. Where a residual current device (RCD) is used for extra protection, only an RCD of Type B (time delayed) shall be used on the supply side of this product. See also Danfoss Application Note on RCD, MN90GX. Protective earthing of the frequency converter and the use of RCDs must always follow national and local regulations.
CAUTION
Motor overload protection is possible by setting 1-90 Thermal Protection to the value ETR trip. For the North American market: ETR functions provide class 20 motor overload protection, in accordance with NEC.
Motor
1.1.7 Disposal Instruction
Equipment containing electrical components
not be disposed of together with domestic
must waste. It must be separately collected with electrical and electronic waste according to local and currently valid legislation.
Table 1.2
1.1.8 Before Commencing Repair Work
1. Disconnect FC 51 from mains (and external DC supply,
2. Wait for 4 minutes (M1, M2 and M3) and 15 min (M4 and M5) for discharge of the DC-link.
3. Disconnect DC bus terminals and brake terminals (if present)
4. Remove motor cable
if present).
WARNING
Installation in high altitudes: For altitudes above 2 km, please contact Danfoss regarding PELV.
1.1.5 IT Mains
CAUTION
IT Mains Installation Max. supply voltage allowed when connected to mains: 440 V.
As an option, Danfoss offers line filters for improved harmonics
1.1.6 Avoid unintended Start
While the frequency converter is connected to mains, the motor commands, references or via the Local Control Panel.
on isolated mains source, i.e. IT mains.
performance.
can be started/stopped using digital commands, bus
Disconnect the frequency converter from mains to avoid unintended start of any motors.
To avoid unintended start, always press the [Off] key before changing parameters.
4 MG02C602 - VLT® is a registered Danfoss trademark
Introduction
2 Introduction
VLT® Micro Drive FC 51 Programming Guide
2.1.1 FC Identification
The nameplate sticker is located on the top of each frequency warnings catalog number, and other relevant data for each unit. See Table 2.1 for details, how to read the type code string.
converter and shows the ratings, serial number,
2 2
Illustration 2.1 This Example Shows the Nameplate Sticker
MG02C602 - VLT® is a registered Danfoss trademark
5
Introduction
VLT® Micro Drive FC 51 Programming Guide
2.1.2 Type Code
22
Illustration 2.2
Description Pos. Possible choice Product group 1-3 Frequency converters Series and product type 4-6 Micro Drive Power size 7-10 0.18-7.5 kW Mains voltage 11-12 S2: Single phase 200-240 V AC
2: Three phase 200-240 V AC
T
T 4: Three phase 380-480 V AC Enclosure 13-15 IP20/Chassis RFI filter 16-17 HX: No RFI filter
RFI filter class A1/B
H1:
H3:RFI filter A1/B (reduced cable length*) Brake 18 B: Brake chopper included (from 1.5 kW and up)
No brake chopper included
X: Display 19 X: No Local Control Panel
Numerical Local Control Panel (LCP)
N:
P: Numerical Local Control Panel (LCP)) with potentiometer Coating PCB 20 C: Coated PCB
No coated PCB
X. Mains option 21 X: No mains option Adaptation A 22 X: No adaptation Adaptation B 23 X: No adaptation Software release 24-27 SXXX: Latest release - std. software
Table 2.1 Type Code Description
®
*See VLT
Micro Drive Design Guide, MG02K
6 MG02C602 - VLT® is a registered Danfoss trademark
Introduction
2.1.3 Warnings and Approvals
VLT® Micro Drive FC 51 Programming Guide
Symbols used in this Programming Guide.
Symbols
following symbols are used in this manual.
The
CAUTION
Indicates a potentially hazardous situation which, if not avoided, also be used to alert against unsafe practices.
may result in minor or moderate injury. It may
WARNING
Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
2.1.4 Abbreviations and Standards
Abbreviations Terms SI-units I-P units
a Acceleration
AWG American wire gauge
Auto Tune Automatic Motor Tuning
°C
I Current A Amp
I
LIM
IT mains Mains supply with star point in transformer floating to ground
Joule Energy J=N∙m ft-lb, Btu
°F
FC frequency converter
f Frequency Hz Hz kHz Kilohertz kHz kHz LCP Local Control Panel mA Milliampere
ms Millisecond
min Minute
MCT Motion Control Tool
M-TYPE Motor Type Dependent
Nm Newton Metres in-lbs I
M,N
f
M,N
P
M,N
U
M,N
PELV Protective Extra Low Voltage Watt Power W Btu/hr, hp
Pascal Pressure Pa = N/m² psi, psf, ft of water
I
INV
RPM Revolutions Per Minute
s Second
SR Size Related
T Temperature C F t Time s s,hr
T
LIM
U Voltage V V
Celsius
Current limit
Fahrenheit
Nominal motor current Nominal motor frequency Nominal motor power Nominal motor voltage
Rated Inverter Output Current
Torque limit
CAUTION
Indicates property-damage-only accidents.
a situation that may result in equipment or
2
m/s
ft/s
2 2
2
Table 2.2 Abbreviation and Standards Table
MG02C602 - VLT® is a registered Danfoss trademark
7
Programming
VLT® Micro Drive FC 51 Programming Guide
3 Programming
The display
3.1 How to Programme
Different
information can be read from the display.
33
3.1.1 Programming with MCT 10 Set-up Software
The frequency converter can be programmed from a PC
RS-485 com-port by installing the MCT 10 Set-up
via Software.
This software can either be ordered using code number 130B1000 or downloaded from the Danfoss Web site:
www.danfoss.com/BusinessAreas/DrivesSolutions/software­download
Set-up number shows the active set-up and the edit set­up. If the same set-up acts as both active and edit set-up, only that set-up number is shown (factory setting). When active and edit set-up differ, both numbers are shown in the display (Set-up 12). The number flashing, indicates the edit set-up.
Refer to the manual for Motion Control Tools MG10R.
3.1.2 Programming with the LCP 11 or LCP 12
The LCP is divided into four functional groups:
1. Numeric
2. Menu key.
3. Navigation keys.
4. Operation keys and indicator lights (LEDs).
Illustration 3.1 LCP 12 with Potentiometer
display.
Illustration 3.3 Indicating Set-up
The small digits to the left are the selected parameter number.
Illustration 3.4 Indicating Selected Parameter Number
The large digits in the middle of the display show the
of
value
the selected parameter.
Illustration 3.5 Indicating Value of Selected Parameter
The right side of the display shows the unit of parameter. This can be either Hz, A, V, kW, HP, %, s or RPM.
Illustration 3.2 LCP 11 without Potentiometer
8 MG02C602 - VLT® is a registered Danfoss trademark
Illustration 3.6 Indicating Unit of Selected Parameter
the selected
Programming
is
Motor direction
- indicated by a small arrow pointing either clockwise or
counterclockwise.
Illustration 3.7 Indicating Motor Direction
Press the [Menu] key to select one of the following menus
Status Menu The Status Menu is either in Readout Mode or Hand on Mode. In Readout Mode the value of the currently selected readout parameter is shown in the display.
shown to the bottom left of the display
VLT® Micro Drive FC 51 Programming Guide
Operation Keys
yellow light above the operation keys indicates the
A active key. [Hand On]: Starts the motor and enables control of the frequency converter via the LCP. [Off/Reset]: The motor stops except in alarm mode. In that case the motor will be reset. [Auto On]: The frequency converter is controlled either via control terminals or serial communication. [Potentiometer] (LCP 12): The potentiometer works in two ways depending on the mode in which the frequency converter is running. In Auto Mode the potentiometer acts as an extra programmable analog input. In Hand on Mode the potentiometer controls local reference.
3.2 Status Menu
3 3
In Hand on Mode the local LCP reference is displayed.
Quick Menu Displays Quick Menu parameters and their settings. Parameters in the Quick Menu can be accessed and edited from here. Most applications can be run by setting the parameters in the Quick Menus.
Main Menu Displays Main Menu parameters and their settings. All parameters can be accessed and edited here.
Indicator lights
Green LED: The frequency converter is on.
Yellow LED: Indicates a warning. See 6 Trouble-
shooting. Flashing red LED: Indicates an alarm. See
6 Troubleshooting.
Navigation Keys [Back]: For moving to the previous step or layer in the navigation structure.
[▲] [▼]: For maneuvering between parameter groups, parameters and within parameters. [OK]: For selecting a parameter and for accepting changes to parameter settings.
After power up the Status Menu is active. Press [Menu] to
between Status, Quick Menu and Main Menu.
toggle
[▲] and [▼] toggles between the choices in each menu.
The display indicates the status mode with a small arrow above “Status”.
Illustration 3.8 Indicating Status Mode
Pressing [OK] for more than 1 s enters 'Adjust' mode. In 'Adjust' mode, it is possible to make fast adjustment by pressing [] [] combined with [OK].
Press [] [] to change value. Press [OK] to shift between digits quickly.
To exit 'Adjust' mode, press [OK] more than 1 s again with changes saving or press [Back] without changes saving.
MG02C602 - VLT® is a registered Danfoss trademark
9
Programming
VLT® Micro Drive FC 51 Programming Guide
3.3 Quick Menu
The Quick Menu gives easy access to the most frequently
parameters.
used
1. To enter the Quick Menu, press [Menu] key until
33
indicator in display is placed above Quick Menu.
2.
Press [▲] [▼] to select either QM1 or QM2, then press [OK].
3.
Press [▲] [▼] to browse through the parameters in the Quick Menu.
4. Press [OK] to select a parameter.
5.
Press [▲] [▼] to change the value of a parameter setting.
6. Press [OK] to accept the change.
7.
To exit, press either [Back] twice to enter Status, or press [Menu] once to enter Main Menu.
Illustration 3.9 Indicating Quick Menu Mode
3.4 Main Menu
The Main Menu gives access to all parameters.
1.
2.
3. Press [OK] to select a parameter group.
4.
5. Press [OK] to select the parameter.
6.
7. Press [OK] to accept the value.
8.
enter the Main Menu, press [Menu] key until
To indicator in display is placed above Main Menu.
Press [▲] [▼] to browse through the parameter groups.
Press [▲] [▼] to browse through the parameters in the specific group.
Press [▲] [▼] to set/change the parameter value.
To exit, press either [Back] twice to enter Quick Menu, or press [Menu] once to enter Status.
Illustration 3.10 Indicating Main Menu Mode
10 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4 Parameter Descriptions
4.1 Parameter Group 0: Operation/Display
0-03 Regional Settings
Option: Function:
In order to meet the needs for different default
in different parts of the world, 0-03
settings Regional Settings, is implemented in the frequency converter. The selected setting influences the default setting of the motor nominal frequency.
[0 ] * Interna-
tional
[1] US
Sets default of 1-23 shows 1-20 Motor Power in kW. Sets default of 1-23 shows 1-20 Motor Power in HP.
Motor Frequency, to 50 Hz,
Motor Frequency, to 60 Hz,
NOTE
This parameter cannot be changed while motor runs.
0-04 Operating State at Power-up (Hand Mode)
Option: Function:
This parameter controls whether or not the frequency when powering up after a power down in Hand mode.
converter start running the motor
NOTE
If LCP with potentiometer is mounted, reference is set according to actual potentiometer value.
[0] Resume Frequency converter starts in same Hand or
Off State as when powered off. Local reference is stored and used after power-up.
[1] * Forced
Stop, Ref=Old
[2] Forced
Stop,
Frequency converter powers up in Off State meaning up. Local reference is stored and used after power-up. Frequency converter powers up in Off State
Ref=0
meaning that motor is stopped after power up. Local reference is set to 0. Thus motor will not start running before local reference has been increased.
that motor is stopped after power
4.1.1 0-1* Set-up Handling
User-defined parameters and miscellaneous external inputs (eg.
bus, LCP, analog/digital inputs, feedback, etc.) controls
the functionality of the frequency converter.
A complete set of all parameters controlling the frequency converter is called a set-up. The frequency converter contains 2 set-ups, Set-up 1 and Set-up 2. Furthermore, a fixed set of factory settings can be copied into one or more set-ups.
Some of the advantages of having more than one set-up in the frequency converter are
Run motor in one set-up (Active Set-up) while
updating parameters in another set-up (Edit Set­up)
Connect various motors (one at a time) to
frequency converter. Motor data for various motors can be placed in different set-ups.
Rapidly change settings of frequency converter
and/or motor while motor is running (eg. ramp time or preset references) via bus or digital inputs.
The Active Set-up can be set as Multi Set-up where the active set-up is selected via input on a digital input terminal and/or via the bus control word.
NOTE
Factory
Set-up cannot be used as Active Set-up.
0-10 Active Set-up
Option: Function:
Active Set-up controls Shifts between set-ups can only happen when
the motor is coasted
OR
the set-ups between which the shift
happens are linked to each other (see 0-12 Linked Set-ups).
If changing between set-ups that are not linked, the change will not happen before motor is coasted.
the motor.
NOTE
The motor is only considered stopped when it is coasted.
4 4
MG02C602 - VLT® is a registered Danfoss trademark
11
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
0-10 Active Set-up
Option: Function:
[1 ] * Set-up 1 [2]
Set-up 2 Multi
[9]
Set-up
is active.
Set-up 1 Set-up 2 is active.
Select the active set-up via digital input and/or
see 5-1* Digital Inputs choice [23].
bus,
0-11 Edit Set-up
44
Option: Function:
Set-up
The Edit the frequency converter from either LCP or bus. It can be identical or different from the Active Set-up. All set-ups can be edited during operation,
independently of the active set-up. [1 ] * Set-up 1 [2] Set-up 2 [9] Active Set-upUpdate parameters in set-up selected as
Update parameters in Set-up
Update parameters in Set-up
Set-up (see 0-10 Active Set-up).
Active
is for updating parameters in
1.
2.
0-12 Link Set-ups
Option: Function:
The link ensures synchronizing of the “not changeable during operation” parameter values enabling shift from one set-up to another during operation. If the set-ups are not linked, a change between them is not possible while the motor is running. Thus the set-up change does not occur until the motor is coasted.
[0] Not
linked
[1 ] * Linked Copy parameters “not changeable during
Leaves parameters unchanged in both set-ups
cannot be changed while motor runs.
and
operation” selected Edit Set-up.
parameter values into presently
NOTE
This parameter cannot be changed while motor runs.
0-31 Custom Readout Min Scale
Range: Function:
0.00 * [0.00–
9999.00
It is possible to create a customized
]
readout related to the output frequency of the unit. The value entered in 0-31 Custom Readout Min Scale will be shown at 0 Hz. The readout can be shown in the LCP display when in Status Mode or it can be read in 16-09 Custom Readout
0-32 Custom Readout Max Scale
Range: Function:
100.0* [0.00–
9999.00]
It is possible to create a customized readout
to the output frequency of the unit.
related The value entered in 0-32 Custom Readout Max Scale will be shown at the frequency programmed in 4-14 Motor Speed High Limit. The readout can be shown in the LCP display when in Status Mode or it can be read in 16-09 Custom Readout
4.1.2 0-4* LCP
The frequency converter can operate in the following three modes: Hand Hand: The frequency converter is locally operated and does not allow any remote control. By activating Hand a start signal is given. OFF: The frequency converter stops with a normal stop ramp. When Off is chosen the frequency converter can only be started by pressing either Hand or Auto on the LCP. Auto: In Auto-mode the frequency converter can be remote controlled (bus/digital).
0-40 [Hand On] Key on LCP
Option: Function:
[0] Disabled [Hand On] key has no function. [1 ] * Enabled [Hand On] key is functional.
0-41 [Off/Reset] Key on LCP
Option: Function:
[0] Disable Off/Reset [Off/Reset] key has no function. [1 ] * Enable Off/Reset Stop signal and reset of any faults. [2] Enable Reset Only Reset only. Stop (Off) function is
0-42 [Auto On] Key on LCP
Option: Function:
[0] Disabled [Auto On] key has no function. [1 ] * Enabled [Auto On] key is functional.
, Off and Auto.
disabled.
12 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.1.3 0-5* Copy/Save
0-50 LCP Copy
Option: Function:
The detachable LCP of the frequency converter and thus for transferring data when moving parameter settings from one frequency converter to another.
can be used for storing setups,
NOTE
LCP Copy can only be activated from the LCP and ONLY when the motor is coasted.
[1] All to LCP Copy all setups from the frequency
converter
[2] All from LCP Copy all setups from LCP to frequency
converter.
[3] Size independent
LCP
from
Copy non motor size dependent data from LCP to frequency converter.
0-51 Set-up Copy
Option: Function:
Use this function to copy a set-up content into
the Edit Set-up.
In order to be able to make a set-up copy ensure that
into the LCP.
the motor is coasted
0-10 Active Set-up, Active Set-up, is set to either [1] Set-up 1 or [2] Set-
up 2
4.1.4 0-6* Password
0-60 (Main) Menu Password
Range: Function:
Use password for protection against unintended
of sensitive parameters, eg. motor
change parameters.
0 * [0-999] Enter the password for access to Main Menu via
[Main Menu] key. Select the number that
the should allow for changing other parameter values. 0 means there is no password.
NOTE
A password has affect on the LCP - not on the bus communication.
NOTE
Pressing This will automatically enter the parameter editing screen in Quick Menu or Main Menu.
[0] * Full access
[1] LCP: Read Only
[2] LCP: No Access
[Menu], [OK] and [▼] will unlock the password.
0-61 Access to Main/Quick Menu w/o Password
Option: Function:
Select [0] Full Access to disable the password in 0-60 (Main) Menu Password. Select [1] Read Only editing of Main/Quick menu parameter. Select [2] No Access editing and viewing of Main/Quick menu parameter.
to block unauthorized
to block unauthorized
4 4
NOTE
The keyboard/parameter database are blocked while Set-up Copy is running.
[0 ] * No Copy Copy function is inactive [1] Copy from
Set-up
[2] Copy from
Set-up
[9] Copy from
Factory up
Copy from Set-up 1 to edit set-up chosen in
1
0-11 Edit Set-up. Copy from Set-up 2 to edit set-up chosen in
2
0-11 Edit Set-up. Copy from Factory Settings to edit set-up
Set-
chosen in 0-11 Edit set-up.
MG02C602 - VLT® is a registered Danfoss trademark
13
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.2 Parameter Group 1: Load/Motor
1-05 Hand Mode Configuration
Option: Function:
1-00 Configuration Mode
Option: Function:
Use this parameter for selecting the application a Remote Reference is active.
NOTE
44
Changing this parameter will reset 3-00 Reference Range, 3-02 Minimum Reference and 3-03 Maximum Reference to their
control principle to be used when
[2] * As config-
uration
1-00 Configu­ration Mode.
default values.
NOTE
parameter cannot be adjusted
[0 ] * Speed
Open Loop
[3] Process
Closed Loop
This while motor runs.
For normal speed control (References).
Enables process closed loop control. See parameter further information on PI-controller.
group 7-3* Process PI Control for
4.2.1 1-2* Motor Data
Enter the correct motor nameplate data (power, voltage, frequency, Run AMT, see 1-29 Automatic Motor Tuning (AMT). Factory settings for advanced motor data, parameter group 1-3* Adv. Motor Data, are automatically calculated.
frequency limited by Motor Speed High/Low
(4-14 Motor Speed High Limit and 4-12
Limit Motor Speed Low Limit). If 1-00 Configuration Mode is set to [1] Open
in
Loop function is as described above. If 1-00 Configuration Mode is set to [3] Process Closed Loop changing from Auto mode to Hand mode results in a setpoint change via local potentiometer or Arrow up/down. The change is limited by Reference Max/Min (3-02 Minimum Reference and 3-03 Maximum Reference).
current and speed).
1-01 Motor Control Principle
Option: Function:
[0] U/f Is used for parallel connected motors and/or special
applications. The U/f settings are set in 1-55
motor U/f Characteristic -U and 1-56 U/f Characteristic -F.
NOTE
When running U/f control slip- and load compensations are not included.
[1] * VVC+ Normal running mode, including slip- and load
compensations.
1-03 Torque Characteristics
Option: Function:
With more torque characteristics it is possible well as high torque applications.
[0 ] * Constant
Torque
[2] Automatic
Optimi-
Energy sation
Motor shaft output provides constant torque This function automatically optimizes energy consumption in centrifugal pump and fan applications. See 14-41 AEO Minimum Magnetisation.
1-05 Hand Mode Configuration
Option: Function:
This parameter is only relevant when 1-00
Configuration Loop. The parameter is used for determining
the reference or setpoint handling when changing from Auto Mode to Hand Mode on the LCP.
[0] Speed
Open Loop
In Hand Mode the drive always runs in Open
configuration regardless of setting in 1-00
Loop Configuration Mode. Local potentiometer (if present) or Arrow up/down determines output
to run low energy consuming, as
under variable speed control.
Mode is set to [3] Process Closed
NOTE
Parameters adjusted while motor runs.
1-20 Motor Power [kW]/[HP] (P
Option: Function:
[1] 0.09 kW/0.12 HP [2] 0.12 kW/0.16 HP [3] 0.18kW/0.25 HP [4] 0.25 kW/0.33 HP [5] 0.37kW/0.50 HP [6] 0.55 kW/0.75 HP [7] 0.75 kW/1.00 HP [8] 1.10 kW/1.50 HP [9] 1.50 kW/2.00 HP [10] 2.20 kW/3.00 HP [11] 3.00 kW/4.00 HP [12] 3.70 kW/5.00 HP [13] 4.00 kW/5.40 HP [14] 5.50 kW/7.50 HP [15] 7.50 kW/10.0 HP [16] 11.00 kW/15.00 HP [17] 15.00 kW/20.00 HP [18] 18.50 kW/25.00 HP [19] 22.00 kW/29.50 HP [20] 30.00 kW/40.00 HP
in parameter group 1-2* Motor Data cannot be
Enter motor power from nameplate data.
sizes down, one size up from
Two nominal VLT rating.
m.n
)
14 MG02C602 - VLT® is a registered Danfoss trademark
130BA375.11
R
S
P 1-30
R
1s
X
h
P1-35
R
1
X
2
X
1
U
1
I
1
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
NOTE
Changing
Voltage to 1-25 Motor Frequency, 1-30 Stator Resistance, 1-33 Stator Leakage Reactance and 1-35 Main Reactance.
1-22 Motor Voltage (U_
Range: Function:
230/400 V [50-999 V] Enter motor voltage from nameplate
1-23 Motor Frequency (f_
Range: Function:
50 Hz* [20-400 Hz] Enter motor frequency from nameplate
1-24 Motor Current (I_
Range: Function:
M-type dependent* [0.01-100.00 A] Enter motor current from
1-25 Motor Nominal Speed (n_
Range: Function:
M-type Dependent* [100-9999 RPM] Enter motor nominal
this parameter affects parameters 1-22 Motor
)
m.n
data.
)
m.n
data.
)
m.n
nameplate
)
m.n
speed data.
data.
from nameplate
4.2.2 1-3* Adv. Motor Data
Adjust advanced motor data using one of these methods:
1. Run
AMT on cold motor. The frequency converter
measures value from motor.
2. Enter X1 value manually. Obtain value from motor supplier.
3. Use Rs, X1, and X2 default setting. The frequency converter establishes setting based on motor nameplate data.
NOTE
parameters cannot be changed while the motor
These runs.
4 4
1-29 Automatic Motor Tuning (AMT)
Illustration 4.1
Option: Function:
Use AMT to optimize motor performance.
NOTE
This parameter cannot be changed while motor runs.
1. Stop the frequency converter - make motor is at standstill
sure
2.
Choose [2] Enable AMT
3. Apply start signal
- Via LCP: Press [Hand On]
- Or in Remote On mode: Apply start signal on terminal 18
[0] * Off AMT function is disabled. [2] Enable
AMT
AMT function starts running.
NOTE
gain optimum tuning of the frequency
To converter, run AMT on a cold motor.
1-30 Stator Resistance (Rs)
Range: Function:
Depending on motor data* [Ohm] Set stator resistance value.
1-33 Stator Leakage Reactance (X1)
Range: Function:
Depending on motor data*
[Ohm] Set stator leakage reactance
motor.
of
1-35 Main Reactance (X2)
Range: Function:
Depending on motor data* [Ohm] Set motor main reactance.
4.2.3 1-5* Load Independent Setting
This parameter group is for setting the load independent
settings.
motor
1-50 Motor Magnetization at Zero Speed
Range: Function:
This parameter enables different thermal
on motor when running at low speed.
100 %* [ 0-300%] Enter a percentage of rated magnetizing
load
If setting is too low, motor shaft
current. torque may be reduced.
MG02C602 - VLT® is a registered Danfoss trademark
15
Magn. current
130BD016.10
Hz
Par.1-50
Par.1-51
100%
Par.1-52 RPM
Motor Voltage Par 1-55 [x]
Output Frequency
Par 1-56 [x]
1-55[5]
1-55[4]
1-55[3]
1-55[2]
1-55[1] 1-55[0]
1-56 [0]
1-56 [1]
1-56 [2]
1-56 [3]
1-56 [4]
1-56 [5]
130BD017.10
130BD018.10
60%
0%
100%
U
m
Changeover
f
out
Par.1-60 Par.1-61
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
1-52 Min. Speed Normal Magnetizing [Hz]
Range: Function:
Use this parameter along with 1-50
Motor
Magnetizing at Zero Speed.
0.0 Hz* [0.0-10.0 Hz] Set frequency required for normal magnetizing
current. If frequency is set
lower than motor slip frequency, 1-50 Motor Magnetizing at Zero Speed is
44
inactive.
Illustration 4.3 U/f Characteristics
Illustration 4.2
NOTE
1-55 U/f Characteristic - U
Range: Function:
This parameter is an array parameter [0-5]
is only functional when 1-01 Motor
and Control Principle is set to [0] U/f.
0.0 V* [0.0-999.9 V] Enter voltage at each frequency point to
manually
form a U/f characteristic
matching motor. Frequency points are defined in 1-56 U/f characteristics - F.
1-56 U/f Characteristic - F
Range: Function:
This parameter is an array parameter [0-5]
is only functional when 1-01 Motor
and Control Principle is set to [0] U/f.
0.0
Hz*
[0.0-1000.0 Hz]
Enter frequency points to manually form a
characteristic matching motor. Voltage
U/f at each point is defined in 1-55 U/f Characteristic - U. Make a U/f characteristic based on 6 definable voltages and frequencies, see Illustration 4.3. Simplify U/f characteristics by merging 2 or more points (voltages and frequencies), respectively, are set equal.
For 1-56 [0] [1] [2] [3] [4] [5]
4.2.4 1-6* Load Dependent Setting
Parameters for adjusting the load-dependent motor settings.
U/f characteristics - F the following applies
1-60 Low Speed Load Compensation
Range: Function:
Use this parameter to gain optimum U/f characteristic
100 %* [0-199 %] Enter percentage in relation to load when
motor Change-over point is automatically calculated based on motor size.
when running at low speed.
runs at low speed.
16 MG02C602 - VLT® is a registered Danfoss trademark
Illustration 4.4
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
1-61 High Speed Load Compensation
Range: Function:
Use this parameter to obtain optimum load compensation
100 %* [0-199 %] Enter percentage to compensate in relation
load when motor runs at high speed.
to Change-over point is automatically calculated based on motor size.
when running at high speed.
1-62 Slip Compensation
Range: Function:
100 %* [-400-399%]Compensation for load dependent motor
slip.
compensation is calculated automat-
Slip ically based on rated motor speed, n
M,N
NOTE
This
function is only active when
1-00 Configuration Mode, is set to [0] Speed Open Loop and when 1-01 Motor Control Principle, is set to [1]
plus
VVC
1-63 Slip Compensation Time
Range: Function:
0.10 s [0.05-5.00 s] Enter slip compensation reaction speed. A
high value results in slow reaction whereas a low value results in quick reaction. If low-frequency resonance problems arise, use longer time setting.
4.2.5 1-7* Start Adjustments
Considering the need for various start functions in different applications, in this parameter group.
1-71 Start Delay
Range: Function:
0.0 s* [0.0-10.0s]Enter the time delay required before
it is possible to select a number of functions
The start delay defines the time to pass from
start command is given until the motor
a starts accelerating. Setting start delay to 0.0 s disables 1-72 Start Function, when start command is given.
commencing
1-72 Start Function is active during Start delay time.
acceleration.
1-72 Start Function
Option: Function:
[0] DC Hold/Delay
Time
[1] DC Brake/Delay
Time
[2] * Coast/Delay
Time
Motor is energised with DC holding
(2-00 DC Hold Current) during
current start delay time. Motor is energised with DC braking
(2-01 DC Brake Current) during
current start delay time. Inverter is coasted during start delay time (inverter
off).
1-73 Flying Start
Option: Function:
The Flying Start parameter is used to catch a
.
spinning
motor after eg. mains drop-out.
NOTE
This function is not suitable for hoisting applications.
[0] * Disabled Flying start is not required. [1] Enabled Frequency converter enabled to catch spinning
motor.
NOTE
flying start is enabled 1-71 Start Delay,
When and 1-72 Start Function, have no function.
4.2.6 1-8* Stop Adjustments
To meet the need for various stop functions in different application features for the motor.
1-80 Function at Stop
Option: Function:
[0] * Coast The inverter is coasted. [1] DC
these parameters offer some special stop
The selected function at stop is active in following situations:
Stop command is given and output
speed is ramped down to Min. Speed for Function at Stop.
Start command is removed (standby),
and output speed is ramped down to Min. Speed for Function at Stop.
DC-brake command is given, and DC-
brake time has passed
While running and calculated output
speed is below Min. Speed for Function at Stop.
The motor is energised with a DC current. See
hold
DC Hold Current for more information.
2-00
4 4
1-82 Min. Speed For Function at Stop [Hz]
Range: Function:
0.0 Hz* [0.0-20.0 Hz]
MG02C602 - VLT® is a registered Danfoss trademark
Set the speed at which to activate 1-80
Function
at Stop.
17
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.2.7 1-9* Motor Temperature
1-93 Thermistor Resource
Option: Function:
With an estimated motor temperature monitor the frequency without having a thermistor mounted. It is thus possible to receive a warning or an alarm, if motor temperature exceeds upper operational limit.
converter is able to estimate motor temperature
[0] * None No thermistor is connected. [1] Analog
Input
1-90 Motor Thermal Protection
44
Option: Function:
Using ETR (Electronic Terminal Relay) the
temperature is calculated based on
motor frequency, speed and time. Danfoss recommends using The ETR function, if a thermistor is not present.
[6] Digital
input 29
NOTE
ETRElectronic Overload calculation is based on motor data from parameter group 1-2* Motor Data.
[0] * No Protection Disables temperature monitoring. [1] Thermistor
Warning
[2] Thermistor
Trip
[3] ETR Warning If calculated upper limit of motor
[4] ETR Trip If 90% of calculated upper limit of motor
A thermistor connected to either digital or
input gives a warning if upper limit
analog of motor temperature range is exceeded, (see 1-93 Thermistor Resource). A thermistor connected to either digital or
input gives an alarm and makes the
analog frequency converter trip if upper limit of motor temperature range is exceeded, (see 1-93 Thermistor Resource.
temperature occurs.
temperature occurs and the frequency converter trips.
range is exceeded, a warning
range is exceeded, an alarm
Select the thermistor input terminal.
Connect thermistor to analog input terminal
53
53.
NOTE
Analog input 53 cannot be selected for other purposes when selected as thermistor resource.
Connect thermistor to digital input terminal 29. While this input functions as thermistor input, it will not respond to the function chosen in
5-13 Digital Input 29. The value of 5-13 Digital Input 29 remains however unchanged in
parameter database while function is inactive.
Input Digital/
Analog
Digital 10 V
Analog 10
Table 4.1
Supply
Voltage
V
Threshold Cut-
out
Values
<800 Ω 2.9 kohm
<800 Ω 2.9 kohm
NOTE
When
the ETR function has been selected the drive will store the recorded temperature at power down and this temperature will resume at power up regardless of the elapsed time. Changing 1-90 Motor Thermal Protection back to [0] No Protection will reset the recorded temperature.
18 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.3 Parameter Group 2: Brakes
4.3.1 2-** Brakes
4.3.2 2-0* DC-Brake
The purpose of DC-brake function is to brake a rotating
by applying DC-current to the motor.
motor
2-00 DC Hold Current
Range: Function:
This parameter either holds the motor (holding
or pre-heats the motor.
torque) The parameter is active if DC Hold has been selected in either 1-72 Start Function or 1-80 Function at Stop.
50%* [0-100%] Enter a value for holding current as a
percentage 1-24 Motor Current. 100% DC holding current corresponds to I
of the rated motor current set in
.
M,N
NOTE
100% current too long as it may overheat the motor.
Avoid
2-01 DC Brake Current
Range: Function:
50%* [0-150%] Set DC-current needed to brake rotating
motor. Activate ways:
DC-brake in one of the four following
1.
DC-brake command, see 5-1* Digital Inputs choice [5]
2.
DC Cut-in function, see 2-04 DC-Brake
Cut-in Speed
3. DC-brake selected as start function,
see 1-72 Start Function
4.
DC-brake in connection with Flying Start, 1-73 Flying Start.
2-02 DC-Braking Time
Range: Function:
DC-braking time defines the period during which DC-brake current is applied to the motor.
10.0 s* [0.0-60 s]
Set the time DC-braking current, set in 2-01
Brake Current, must be applied.
DC
NOTE
If
DC-brake is activated as start function, DC-brake time is
defined by start delay time.
2-04 DC-Brake Cut-in Speed
Range: Function:
0.0 Hz* [0.0-400.0 Hz] Set DC-brake cut-in speed to activate
braking current, set in 2-01 DC Brake
DC Current, when ramping down. When set to 0 the function is off.
4.3.3 2-1* Brake Energy Function
Use the parameters in this group for selecting dynamic braking
parameters.
2-10 Brake Function
Option: Function:
Resistor Brake:
resistor brake limits voltage in the
The intermediate circuit when the motor acts as generator. Without brake resistor, the frequency converter eventually trips. The resistor brake consumes surplus energy resulting from motor braking. A frequency converter with brake, stops a motor faster than without a brake, which is used in many applications. Requires connection of external brake resistor. An alternative to the resistor brake is the AC brake.
NOTE
Resistor brake is only functional in frequency converters with integrated dynamic brake. An external resistor must be connected.
AC Brake:
AC brake consumes surplus energy by
The creating power loss in the motor. It is important to keep in mind that an increase
in power loss causes motor temperature to rise. [0] * Off No brake function. [1] Resistor
Brake
[2] AC Brake AC brake is active.
2-11 Brake Resistor (Ohm)
Range: Function:
5 Ω* [5-5000 Ω] Set brake resistor value.
2-16 AC Brake, Max Current
Range: Function:
100.0%* [0.0-150.0%] Enter max. permissible current for AC-
Resistor brake is active.
to avoid overheating of motor.
braking 100% equals motor current set in 1-24 Motor Current.
4 4
MG02C602 - VLT® is a registered Danfoss trademark
19
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
2-17 Over-Voltage Control
Option: Function:
Use Over-voltage Control (OVC) to reduce
risk of the frequency converter tripping
the due to an over voltage on the DC link caused by generative power from the load. An over-voltage occurs eg. if the ramp down time is set too short compared to the actual
44
[0] * Disabled The OVC is not active/required. [1] Enabled, not
stop
at
[2] Enabled OVC is running, also when a stop signal is
load inertia.
OVC is running unless a stop signal is active.
active.
NOTE
If
Resistor Brake has been chosen in 2-10 Brake Function
the OVC is not active even though enabled in this
2-22 Activating Mechanical Brake
Range: Function:
If the motor is stopped using ramp, the
brake is activated when motor
A start command is removed (stand
by)
A stop command is activated
Quick-stop is activated (Q-stop ramp is
used)
when ramping down.
0 Hz* [0-400
Hz]
mechanical
speed is less than Active Brake Speed.
Motor is ramped down to stop in the following
situations:
Select motor speed at which mechanical brake
activates
Mechanical brake automatically activates if
frequency converter trips or reports an alarm.
parameter.
4.3.4 2-2* Mechanical Brake
For hoisting applications an electro-magnetic brake is required. the brake when activated.
The brake is controlled by a relay, which releases
The brake activates if the frequency converter trips or a coast command is given. Furthermore, it activates when motor speed is ramped down below the speed set in 2-22 Active Brake Speed.
2-20 Release Brake Current
Range: Function:
0.00 A* [0.00-100 A] Select motor current at which mechanical releases.
brake
CAUTION
If start delay time has passed, and
current is below Release brake
motor current, frequency converter trips.
20 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.4 Parameter Group 3: Reference/Ramps
4.4.1 3-** Reference/Ramps
Parameters for reference handling, definition of limitations,
configuration of the frequency converter's reaction to
and changes
4.4.2 3-0* Reference Limits
Parameters for setting the reference unit, limits and ranges.
3-00 Reference Range
Option: Function:
Select the range of reference and feedback signals.
[0] * Min to
Max
[1] -Max to
+Max
3-02 Minimum Reference
Range: Function:
0.00* [-4999-4999] Enter value for minimum reference.
3-03 Maximum Reference
Range: Function:
50.00* [-4999-4999] Enter value for Maximum Reference.
Reference setpoint ranges can have positive
only.
values Select this if running in Process Closed Loop. Ranges can have both positive and negative values.
potentiometer is used to adjust motor running
If in both direction, set reference range to –Max Reference to Max Reference by par.=[1] Choose hand on mode by LCP. Adjust the potentiometer to minimum, the motor can run in anti-clockwise with max speed. Then adjust the potentiometer to maximum, the motor will ramp down to 0 and run clockwise with max speed.
The sum of all internal and external references are clamped (limited) to the minimum reference value, 3-02 Minimum Reference.
Maximum Reference is adjustable in the
Minimum Reference -4999.
range
sum of all internal and external
The references are clamped (limited) to the maximum reference value, 3-03 Maximum Reference.
4.4.3 3-1* References
Parameters for setting up the reference sources. Select the
references for the corresponding digital inputs in
preset parameter group, 5-1* Digital Inputs.
3-10 Preset Reference
Option: Function:
Each parameter set-up contains 8 preset references digital inputs or bus.
Table 4.2 Parameter Group 5-1* Digital Inputs
[0.00]*-100.00-100.00% Enter the different preset references
using Normally, 100% = value set in 3-03 Maximum Reference. However, there are exceptions if 3-00 Reference Range is set to [0] Min - Max. Example 1:
3-02 Minimum Reference is set to 20 and 3-03 Maximum Reference is set to 50. In
this case 0%=0 and 100%=50. Example 2: 3-02 Minimum Reference is set to -70 and 3-03 Maximum Reference is set to
50. In this case 0%=0 and 100%=70.
3-11 Jog Speed [Hz]
Range: Function:
Jog speed is a fixed output speed and overrules parameter group 5-1* Digital Inputs option [14]. If the motor is stopped while in jog mode, the jog signal acts as a start signal. Removing the jog signal makes the motor run according to the selected configu­ration.
5.0Hz [0.0-400.0 Hz]
Select speed to function as jog speed.
which are selectable via 3
[18]
Bit2
0 0 0 0 0 0 1 1 0 1 0 2 0 1 1 3 1 0 0 4 1 0 1 5 1 1 0 6 1 1 1 7
[17]
Bit1
Option [16], [17] and [18]
array programming.
the selected reference speed, see
[16] Bit0
[16] Bit0
4 4
MG02C602 - VLT® is a registered Danfoss trademark
21
Relative Z=X+X*Y/100
Resulting actual reference
Y
X
130BA059.12
Z
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
3-12 Catch Up/Slow Down Value
Range: Function:
0% * [0-100%]
The Catch-up/Slowdown an input command (see 5-1* Digital Inputs, choice [28]/[29]). If the command is active, the Catch-up/Slowdown value (in %) is added to the reference function as follows:
Reference
=
Reference
Catchup Slowdown
44
×
Reference
×
100
=
Catchup Slowdown
100
Reference
When the input command is inactivated, the reference
returns to its original value ie.
Reference=Reference + 0.
function is activated by
+
Reference
Reference
3-16 Reference 2 Source
Option: Function:
See 3-15
Reference 1 Source
description. [0] No Function No reference signal is defined. [1] Analog Input 53 Use signals from analog input 53 as
reference. [2] * Analog Input 60 Use signals from analog input 60 as
reference. [8] Pulse input 33 Use signals from pulse input as
see parameter group 5-5*
reference,
Pulse Input. [11] Local Bus
Reference
Use signals from local bus as
reference. [21] LCP Potentiometer Use signals from LCP potentiometer as
for
reference.
3-14 Preset Relative Reference
Range: Function:
0.00% [-100.00-100.00%] Define fixed value in % to be added to
variable value defined in 3-18
Relative Scaling Reference Source. The sum of fixed and variable values (labeled Y in illustration below) is multiplied with actual reference (labeled X in illustration). This product is added to actual reference
X
+ X ×
Illustration 4.5
Y
100
3-17 Reference 3 Source
Option: Function:
See 3-15 Reference 2 Source
description. [0] No Function No reference signal is defined. [1] Analog Input 53 Use signals from analog input 53 as
reference. [2] Analog Input 60 Use signals from analog input 60 as
reference. [8] Pulse input 33 Use signals from pulse input as
see parameter group 5-5*
reference,
Pulse Input. [11] * Local Bus
Reference
Use signals from local bus as
reference. [21] LCP Potentiometer Use signals from LCP potentiometer
reference.
as
for
3-15 Reference 1 Source
Option: Function:
3-15 Reference 1 Source, 3-16 Source and 3-17 Reference 3 Source define
up to three different reference signals. The sum of these reference signals defines
the actual reference. [0] No Function No reference signal is defined. [1] * Analog Input53Use signals from analog input 53 as
reference,
see parameter group 6-1*
Analog Input 1. [2] Analog Input60Use signals from analog input 60 as
reference,
see parameter group 6-2*
Analog Input 2. [8] Pulse input 33 Use signals from pulse input as reference,
parameter group 5-5* Pulse Input.
see [11] Local Bus
Reference
[21] LCP Potenti-
ometer
Use signals from local bus as reference,
parameter group 8-9* Bus Feedback.
see
Use signals from LCP potentiometer as
reference,
parameter group 6-8* LCP
Potentiometer.
Reference 2
3-18 Relative Scaling Reference Source
Option: Function:
Select the source for a variable value to
added to the fixed value defined in
be 3-14 Preset Relative Reference.
[0] * No Function The function is disabled [1] Analog Input 53 Select analog input 53 as relative
reference source.
scaling
[2] Analog Input 60 Select analog input 60 as relative
reference source.
scaling
[8] Pulse Input 33 Select pulse input 33 as relative scaling
reference
[11] Local Bus
Reference
Select local bus ref. as relative scaling reference
[21] LCP Potentiometer Select LCP potentiometer as relative
scaling
source.
source.
reference source.
22 MG02C602 - VLT® is a registered Danfoss trademark
130BA168.10
Ramp (X) S-Ramp Ratio at Accel.End
Jerk compensated
Ramp (X) Up Time
Ramp (X) S-Ramp Ratio at
Accel.End
Linear
Speed
Ramp (X) Down Time
Ramp (X)
S-Ramp Ratio at Dec.End
Ramp (X) S-Ramp Ratio at Dec.End
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.4.4 3-4* Ramp 1
A linear ramp is characterized by ramping up at a constant
until the desired motor speed has been reached.
speed Some overshoot may be experienced when reaching speed, which may cause speed jerks for a short while before stabilizing. An S-ramp accelerates more smoothly thus compensating for jerks when the speed is reached.
See Illustration 4.6 for a comparison of the two ramp types.
Illustration 4.6
3-41 Ramp1 Ramp-up Time
Range: Function:
Size related*
[0.05-3600.00 s] Enter ramp-up time from 0 Hz to
rated in 1-23 Motor Frequency. Choose a ramp-up time ensuring that torque limit is not exceeded, see 4-16 Torque Limit in Motor Mode.
3-42 Ramp1 Ramp-down Time
Range: Function:
Size related*
[0.05-3600.00s]Enter ramp down time from rated
frequency (f
motor Motor Frequency to 0 Hz. Choose a ramp down time that does not cause over-voltage in inverter due to regenerative operation of motor. Furthermore, regenerative torque must not exceed limit set in 4-17 Torque Limit in Generator Mode.
4.4.5 3-5* Ramp2
motor frequency (f
) in 1-23
M,N
M,N
) set
4 4
Ramp Times Ramp
up: Acceleration time from 0 to nominal motor
frequency (1-23 Motor Frequency). Deceleration time from nominal motor frequency (1-23 Motor Frequency) to 0.
Limitation Too short ramp up time can result in Torque limit warning (W12) and/or DC over voltage warning (W7). Ramping is stopped when the frequency converter has reached Torque limit motor mode (4-16 Torque Limit in Motor Mode). Too short ramp down time can result in Torque limit warning (W12) and/or DC over voltage warning (W7). Ramping is stopped when the frequency converter reaches the Torque limit generator mode (4-17 Torque Limit in Generator Mode) and/or the internal DC over voltage limit.
3-40 Ramp1 Type
Option: Function:
[0] * Linear Constant acceleration/deceleration. [2] S-ramp Smooth jerk compensated acceleration/
deceleration.
See parameter group 3-4*
Ramp 1 for a description of
ramp types.
NOTE
Ramp2
- alternative ramp times:
Changing from Ramp1 to Ramp2 is done via the digital input. See 5-1* Digital Inputs, option [34].
3-50 Ramp2 Type
Option: Function:
[0] * Linear Constant acceleration/deceleration. [2] S-ramp Smooth jerk compensated acceleration/
deceleration.
3-51 Ramp2 Ramp-up Time
Range: Function:
Size related*
[0.05-3600.00 s] Enter ramp-up time from 0 Hz to
motor frequency (f
rated in 1-23 Motor Frequency. Choose a ramp-up time ensuring that torque limit is not exceeded, see 4-16 Torque Limit in Motor Mode.
M,N
) set
MG02C602 - VLT® is a registered Danfoss trademark
23
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
3-52 Ramp2 Ramp-down Time
Range: Function:
Size related
44
[0.05-3600.00s]Enter ramp down time from rated
frequency (f
motor Frequency to 0 Hz. Choose a ramp down time that does not cause over-voltage in inverter due to regenerative operation of motor. Furthermore, regenerative torque must not exceed limit set in 4-17 Torque Limit in Generator Mode.
) in 1-23 Motor
M,N
4.4.6 3-8* Other Ramps
This section contains parameters for Jog and Quick Stop Ramps.
With
a Jog Ramp it is possible to both ramp up and down whereas, it is only possible to ramp down with the Quick Stop Ramp.
3-80 Jog Ramp Time
Range: Function:
Size related*
[0.05-3600.00s]A linear ramp applicable when Jog
activated. See parameter group
is 5-1* Digital Inputs, option [14]. Ramp up time = Ramp down time. Jog Ramp time starts upon activation of a jog signal via a selected digital input or serial communication port.
3-81 Quick Stop Ramp Time
Range: Function:
Size related* [0.05-3600.00 s] A linear ramp applicable when
is activated. See
Q-stop parameter group 5-1* Digital Inputs, option [4].
24 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.5 Parameter Group 4: Limits/Warnings
4.5.1 4-** Motor Limits
Parameter group for configuring limits and warning.
4.5.2 4-1* Motor Limits
Use these parameters for defining the speed, torque and current
working range for the motor.
4-10 Motor Speed Direction
Option: Function:
If terminals 96, 97 and 98 are connected to U, V
and W respectively, the motor runs
clockwise when seen from the front.
NOTE
This parameter cannot be adjusted while the motor is running
[0] * Clockwise The motor shaft rotates in clockwise direction.
This setting prevents the motor from running in counterclockwise direction. If 1-00 Configu-
ration Mode is set to close loop control, 4-10 Motor Speed Direction will be automatically set
to clockwise.
[1] Counter-
clockwise
[2] * Both With this setting the motor can run in both
The motor shaft rotates in counterclockwise direction. running in clockwise direction.
directions. limited to the range: Motor Speed Low Limit (4-12 Motor Speed Low Limit) to Motor Speed High Limit (4-14 Motor Speed High Limit). If 1-00 Configuration Mode is set to open loop control, 4-10 Motor Speed Direction will be automatically set to both direction
This setting prevents the motor from
However, the output frequency is
4-16 Torque Limit in Motor Mode
Range: Function:
150 %* [0-400%] Set the torque limit for motor operation.
setting is not automatically reset to
The default when changing settings in 1-00 Configuration Mode to 1-25 Load & Motor.
4-17 Torque Limit in Generator Mode
Range: Function:
100 %* [0-400%] Set the torque limit for generator mode
operation. The
setting is not automatically reset to
default when changing settings in 1-00 Configuration Mode to 1-25 Load & Motor.
4 4
4-12 Motor Speed Low Limit
Range: Function:
0.0 Hz* [0.0-400.0 Hz]
Set the Minimum Motor Speed Limit corresponding to the minimum output frequency of the motor shaft.
NOTE
As the minimum output frequency is an absolute value, it cannot be deviated from.
4-14 Motor Speed High Limit
Range: Function:
65.0 Hz* [0.0-400.0 Hz]
Set the Maximum corresponding to the maximum output frequency of the motor shaft.
NOTE
As the maximum output frequency is an absolute value, it cannot be deviated from.
Motor Speed
MG02C602 - VLT® is a registered Danfoss trademark
25
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.5.3 4-4* Adjustable Warnings 2
4-51 Warning Current High
Range: Function:
4-40 Warning Frequency Low
Range: Function:
0.00 Hz*
44
[0.0 Hz-
on the
Depend value of 4-41
Warning Frequency High]
4-41 Warning Frequency High
Range: Function:
400.0 Hz*
[Depend on
value of
the
4-40 Warning Frequency Low
-400.0 Hz]
Use this parameter to set a lower limit for the frequency range. When the motor speed falls below this limit, the display reads SPEED LOW. Warning bit 10 is set in 16-94 Ext. Status Word. Output Relay can be configured to indicate this warning. LCP warning light does not light when this parameter set limit is reached.
Use this parameter to set a higher limit for the frequency range. When the motor speed exceeds this limit, the display reads SPEED HIGH. Warning bit 9 is set in 16-94 Ext. Status Word. Output Relay can be configured to indicate this warning. LCP warning light does not light when this parameter set limit is reached.
26.00A* [0.00-26.00A]Set upper current limit.
4-54 Warning Reference Low
Range: Function:
-4999.000* [-4999.000­Depend value of 4-55
Warning Reference High]
Use this parameter to set an upper limit
the current range.
for If current exceeds the set limit, warning bit 7 is set in 16-94 Ext. Status Word. Output Relay can be configured to indicate this warning. LCP warning light does not light when this parameter's set limit is reached.
Use this parameter to set a lower
on the
limit for the reference range. When the actual reference falls below this limit, the display reads Reference Low. Warning bit 20 is set in 16-94 Ext. Status Word. Output Relay can be configured to indicate this warning. LCP warning light does not light when this parameter set limit is reached.
4.5.4 4-5* Adjustable Warnings
Parameter group containing adjustable warning limits for current,
Warnings are shown in display, programmed output or serial bus.
speed, reference and feedback.
4-50 Warning Current Low
Range: Function:
Use this parameter to set a lower limit
the current range.
for If current drops below the set limit, warning bit 8 is set in 16-94 Ext. Status Word. Output Relay can be configured to indicate this warning. LCP warning light does not light when this parameter's set limit is reached.
0.00A* [0.00-26.00A]Set value for low current limit.
26 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4-55 Warning Reference High
Range: Function:
4999.000* [Depend on value of
the
4-54 Warning Reference Low-
4999.000]
Use this parameter to set a higher limit for the reference range. When the actual reference exceeds this limit, the display reads Reference High. Warning bit 19 is set in 16-94 Ext. Status Word. Output Relay can be configured to indicate this warning. LCP warning light does not light when this parameter set limit is reached.
4-56 Warning Feedback Low
Range: Function:
-4999.000* [-4999.000-
Depend
on the
value of 4-57
Warning Feedback High]
Use this parameter to set a lower limit for the feedback range. When the feedback falls below this limit, the display reads Feedback Low. Warning bit 6 is set in 16-94 Ext. Status Word. Output Relay can be configured to indicate this warning. LCP warning light does not light when this parameter set limit is reached.
4.5.5 4-6* Speed Bypass
In some applications mechanical resonance may occur.
resonance points by creating a bypass. The
Avoid frequency converter ramps through the bypass area thereby passing mechanical resonance points quickly.
4-61 Speed Bypass From [Hz]
Array [2]
Range: Function:
0.0 Hz* [0.0-400.0 Hz] Enter either the lower or upper limit of speeds to be avoided.
the It does not matter whether Bypass From or Bypass To is the upper or lower limit, however the Speed Bypass function is disabled if the two parameters are set to the same value.
4-63 Speed Bypass To [Hz]
Array [2]
Range: Function:
0.0 Hz* [0.0-400.0 Hz] Enter either the upper or lower limit of speed area to be avoided.
the Make sure to enter the opposite limit of that in 4-61 Speed Bypass From [Hz].
4 4
4-57 Warning Feedback High
Range: Function:
4999.000* [Depend on
value of 4-56
the
Warning Feedback Low
-4999.000]
Use this parameter to set a higher limit for the feedback range. When the feedback exceeds this limit, the display reads Feedback High. Warning bit 5 is set in 16-94 Ext. Status Word. Output Relay can be configured to indicate this warning. LCP warning light does not light when this parameter set limit is reached.
4-58 Missing Motor Phase Function
Option: Function:
A missing motor phase causes the motor torque to
This monitor may be disabled for special
drop. purposes (eg. small motors running pure U/f mode), but as there is a risk of overheating the motor, Danfoss strongly recommends that the function is On. A missing motor phase causes the frequency converter to trip and report an alarm.
NOTE
This parameter cannot be changed while motor runs.
[0] Off Function is disabled. [1] * On Function is enabled.
MG02C602 - VLT® is a registered Danfoss trademark
27
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.6 Parameter Group 5: Digital In/Out
4.6.1 5-** Digital In/Out
The following describes all digital input command functions
and signals.
4.6.2 5-1* Digital Inputs
44
Parameters for configuring the functions for the input terminals. The
digital inputs are used for selecting various functions in the frequency converter. All digital inputs can be set to the following:
[0] No Operation The frequency converter will not react to
transmitted to the terminal.
signals
[1] Reset Reset the frequency converter after a Trip/
Not all alarms can be reset.
Alarm.
[2 ] Coast Inverse Coasting stop, inverted input (NC). The
frequency mode.
[3] Coast and
inv.
reset
[4] Quick stop
inverse
[5] DC-brake inv. Inverted input for DC braking (NC). Stops
[6] Stop inv. Stop inverted function. Generates stop
[8] Start Select start for a start/stop command.
[9] Latched start Motor starts if a pulse is applied for min. 2
[10] Reversing Change direction of motor shaft rotation.
[11] Start
reversing
[12] Enable start
forward
Reset and coasting stop inverted input (NC). The frequency converter resets and leaves the motor in free mode. Inverted input (NC). Generates a stop in accordance set in 3-81 Quick Stop Ramp Time. When motor stops, shaft is in free mode.
motor certain time period, see 2-01 DC Brake Current. Function is only active when value in 2-02 DC-Braking Time is different from 0.
function logical level “1” to “0”. Stop is performed according to selected ramp time.
= Start, 0 = stop.
1
ms. activated.
Reversing rotation; it does not activate start function. Select [2] Both directions in 4.10 Motor Speed Direction. 0 = normal, 1 = reversing. Use for start/stop and for reversing at the same allowed at the same time. 0 = stop, 1 = start reversing. Use if motor shaft must rotate clockwise at start.
converter leaves the motor in free
with the quick-stop ramp time
by energizing it with DC current for a
when selected terminal goes from
Motor stops when Stop inverse is
signal only changes direction of
time. Signals on start [8] are not
[13] Enable start
reverse
[14] Jog
[16] Preset
reference 0
[17] Preset
reference 1
[18] Preset
reference 2
[19] Freeze
reference
[20] Freeze output Freeze the actual motor frequency (Hz). The
[21] Speed up Select Speed up and Speed down if digital
[22] Speed down Same as Speed-up [21]. [23] Setup select
0
bit
[26] Precise stop
inverse terminal 33)
[27] Start, precise
(only
stop terminal 33)
Use if motor shaft must rotate counter­clockwise Use for activating jog speed. See 3-11 Speed. Preset reference bit 0, 1 and 2 enables a
bit
choice between one of the eight preset references according to below. Same as preset reference bit 0 [16], see 3-10
bit
Preset Reference.
Same as preset reference bit 0 [16].
bit
Freeze actual reference. The frozen reference is Speed up and Speed down to be used. If Speed up/down is used, speed change always follows ramp 2 (3-51 Ramp2 Ramp-up Time and 3-52 Ramp2 Ramp-down Time) in the range 3-02 Minimum Reference - 3-03 Maximum Reference.
frozen enable/condition for Speed up and Speed down to be used. If Speed up/down is used, the speed change always follows ramp 2 in the range 4-12 Motor Speed Low Limit - 4-14 Motor Speed High Limit.
at start.
now the point of enable/condition for
motor frequency is now the point of
NOTE
When freeze output is active, the frequency converter cannot be stopped via a low [8] Start signal. Stop the frequency converter via a terminal programmed for Coasting Inverse [2] or Coast and reset, inverse [3].
of the up/down speed is desired
control (motor potentiometer). Activate this function by selecting either Freeze reference or Freeze output. When Speed-up is activated for less than 400 ms. the resulting reference will be increased by 0.1%. If Speed-up is activated for more than 400 ms. the resulting reference will ramp according to ramp 2 in 3-51 Ramp2 Ramp-up Time.
Set 0-10 Active set-up to Multi set-up. Logic 0 = set up 1, Logic 1 = Set up 2. Prolong the stop signal to give a precise
(only
stop independent of scan time. The function is available for terminal 33 only. As [26], but including Start.
Jog
28 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
[28] Catch up Select Catch up/Slow down to increase or
the resulting reference value by the
reduce percentage set in 3-12 Catch Up/Slow Down
Value
[29] Slow down Same as Catch up [28] [32] Pulse input
terminal
(only
33)
[34] Ramp bit 0
[60] Counter A
(up)
[61] Counter A
(down)
[62] Reset counterAInput for reset of counter A.
[63] Counter B
(up)
[64] Counter B
(down)
[65] Reset counterBInput for reset of counter B.
Select Pulse input when using a pulse sequence as either reference or feedback. Scaling is done in parameter group 5-5*
Pulse Input Logic 0=Ramp1, see parameter group 3-4* Ramp1
1=Ramp2, see parameter group 3-5*
Logic Ramp2. Input for counter A.
Input for counter A.
Input for counter B.
Input for counter B.
5-10 Terminal 18 Digital Input
Option: Function:
[8] * Start Select function from available digital input range.
parameter group 5-1* Digital Inputs for choices.
See
5-11 Terminal 19 Digital Input
Option: Function:
[10] * Reversing Select function from available digital input
range.
parameter group 5-1* Digital Inputs for
See choices.
5-12 Terminal 27 Digital Input
Option: Function:
[1] * Reset Select function from available digital input range.
parameter group 5-1* Digital Inputs* for choices.
See
5-13 Terminal 29 Digital Input
Option: Function:
[14] * Jog Select function from available digital input range.
See
parameter group 5-1* Digital Inputs for choices.
5-15 Terminal 33 Digital Input
Option: Function:
[16] * Preset bit 0 Select function from available digital input
range.
parameter group 5-1* Digital Inputs for
See choices.
4.6.3 5-3* Digital Outputs
5-34 On delay, Terminal 42 Digital Output
Range: Function:
0.01 s* [0.00-600.00 s]
5-35 Off delay, Terminal 42 Digital Output
Range: Function:
0.01 s* [0.00-600.00 s]
4.6.4 5-4* Relays
Parameter group for configuring timing and output functions
[0] No Operation Default for all digital and relay outputs. [1] Control Ready Control board receives supply voltage. [2] Drive Ready Frequency converter is ready for
[3] Drive Ready,
[4] Enable/No
[5] Drive Running Motor is running. [6] Running/No
[7] Run in Range/No
[8] Run on ref/No
[9] Alarm An alarm activates output. [10] Alarm on Warning An alarm or warning activates output. [12] Out of Current
[13] Below Current,
[14] Above Current,
[16] Below Frequency,
[17] Above Frequency,
[19] Below Feedback,
[20] Above Feedback,
[21] Thermal Warning Thermal warning is present when
for relays.
Remote
Warning
Warning
Warning
Warning
Range
low
high
low
high
low
high
operation control board. Frequency converter is ready for operation Frequency converter is ready for operation. given. No warnings are present.
Motor runs, and no warning are present. Motor runs within programmed current ranges, and 4-51 Warning Current High. No warnings are present. Motor runs at reference speed.
Motor current is outside range set in
4-50 Warning Current High. Motor current is lower than set in 4-50 Warning Motor current is higher than set in 4-51 Warning Motor speed is lower than set in 4-40 Warning Motor speed is higher than set in 4-41 Warning Feedback is lower than set in 4-56 Warning Feedback is higher than set in 4-57 Warning
temperature frequency converter, brake resistor or thermistor.
and applies supply signal on
in Auto On-mode.
No start or stop command is
see 4-50 Warning Current Low
Warning Current Low and 4-51
Current Low.
Current High.
Frequency Low.
Frequency High.
Feedback Low.
Feedback High.
exceeds limit in motor,
4 4
MG02C602 - VLT® is a registered Danfoss trademark
29
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
[22] Ready, No
Thermal
[23] Remote Ready, No
Thermal
[24] Ready, Voltage OK Frequency converter is ready for
44
[25] Reverse Motor runs/is ready to run clockwise
[26] Bus OK Active communication (no time-out) via
[28] Brake, No Warn Brake is active, and no warnings are
[29] Brake Ready/No
Fault
[30] Brake Fault (IGBT) Protects frequency converter if fault on
[32] Mech. Brake
Control
[36] Control Word Bit11Bit 11 in control word controls relay.
[41] Below Reference,
low
[42] Above Reference,
high
[51] Local Reference
Active
[52] Remote Reference
Active [53] No Alarm [54] Start Cmd Active [55] Running Reverse [56] Drive in Hand
Mode [57] Drive in Auto
Mode [60] Comparator 0
[61] Comparator 1
[62] Comparator 2
Warning
Warning
Frequency converter is ready for operation and no over-temperature warning is present. Frequency converter is ready for operation in Auto mode, and no over­temperature warning is present.
operation specified voltage range.
when when logic = 1. Output changes as soon as reversing signal is applied.
serial
present. Brake is ready for operation, and no faults
brake cut out main voltage from frequency converter. Enables control of external mechanical brake, Mechanical Brake.
Reference is lower than set in 4-54
Warning Reference is higher than set in 4-55 Warning
See parameter group 13-1* Comparators.
evaluated as TRUE, output goes high. Otherwise, it is low. See parameter group 13-1* Comparators. evaluated as TRUE, output goes high. Otherwise, it is low. See parameter group 13-1* Comparators. evaluated as TRUE, output goes high. Otherwise, it is low.
and mains voltage is within
logic = 0 and counter clockwise
communication port.
are present.
modules is present. Use relay to
see parameter group 2-2*
Reference Low.
Reference High.
If comparator 0 is
If comparator 1 is
If comparator 2 is
[63] Comparator 3
[70] Logic Rule 0
[71] Logic Rule 1
[72] Logic Rule 2
[73] Logic Rule 3
[81] SL Digital Output
B
See parameter group 13-1* Comparators. evaluated as TRUE, output goes high. Otherwise, it is low. See parameter group 13-4* If Logic Rule 1 is evaluated as TRUE, output goes high. Otherwise, it is low. See parameter group 13-4* If Logic Rule 2 is evaluated as TRUE, output goes high. Otherwise, it is low. See parameter group 13-4* If Logic Rule 3 is evaluated as TRUE, output goes high. Otherwise, it is low. See parameter group 13-4* If Logic Rule 3 is evaluated as TRUE, output goes high. Otherwise, it is low. See 13-52 SL Control Action. When Smart Logic executed, input goes high. When Smart Logic Action [33] Set dig. out. A low is executed, input goes low.
If comparator 3 is
Logic Rules.
Logic Rules.
Logic Rules.
Logic Rules.
Action [39] Set dig. out. A high is
5-40 Function Relay
Option: Function:
[0] * No Operation Select function from available relay output
range.
5-41 On delay, Relay
Option: Function:
[0.01 s] * [0.00-600.00 s] Enter the delay of the relay cut-in time.
the Selected Event condition changes
If before the On delay timer expires, the relay output is unaffected. The function to control the relay see 5-40 Function Relay.
5-42 Off delay, Relay
Option: Function:
[0.01 s] * [0.00-600.00 s] Enter the delay of the relay cut-off
If the Selected Event condition
time. changes before the off delay timer expires, the relay output is unaffected. The function to control the relay see 5-40 Function Relay.
4.6.5 5-5* Pulse Input
Set 5-15 Terminal 33 Digital Input Now terminal 33 handles a pulse input in the range from Low frequency, 5-55 Terminal 33 Low Frequency, to 5-56
Terminal 33 High Frequency. Scale frequency input via 5-57 Terminal 33 Low Ref./Feedb. Value and 5-58 Terminal 33 High Ref./Feedb. Value.
to choice [32] pulse input.
30 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
5-55 Terminal 33 Low Frequency
Range: Function:
20 Hz* [20-4999 Hz] Enter low frequency corresponding to low
shaft speed (i.e. low reference
motor value) in 5-57 Terminal 33 Low Ref./Feedb. Value.
5-56 Terminal 33 High Frequency
Range: Function:
5000 Hz* [21-5000 Hz] Enter high frequency corresponding to
high
motor shaft speed (i.e. high
reference value) in 5-58 Terminal 33 High Ref./Feedb. Value.
5-57 Terminal 33 Low Ref./Feedb. Value
Range: Function:
0.000* [-4999-4999] Set reference/feedback value
corresponding value set in 5-55 Terminal 33 Low Frequency.
to low pulse frequency
4 4
5-58 Terminal 33 High Ref./Feedb. Value
Range: Function:
50.000* [-4999-4999] Set reference/feedback value
corresponding value set in 5-56 Terminal 33 High Frequency.
to high pulse frequency
MG02C602 - VLT® is a registered Danfoss trademark
31
Ref./Feedback
[RPM]
Analog input
High Ref./
Feedb. Value'
Low Ref./
Feedb. Value'
'Low Voltage'or
'Low Current'
'High Voltage'or
'High Current'
130BD019.10
1 V 5 V 10 V
300
600
900
1200
1500
[V]
150
Par 6-xx
Par 6-xx
Par 6-xx
Par 6-xx
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.7 Parameter Group 6: Analog In/Out
4.7.1 6-** Analog In/Out
NOTE
Micro
switch 4 in position U:
6-10 Terminal 53 Low Voltage and 6-11 Terminal 53 High Voltage are active.
Parameter group for configuring analog inputs and outputs.
Micro switch 4 in position I:
6-12 Terminal 53 Low Current and 6-13 Terminal 53 High Current are active.
4.7.2 6-0* Analog I/O Mode
44
Parameter group for setting up the analog I/O configu­ration.
6-00 Live Zero Timeout Time
Range: Function:
The Live Zero function is used for monitoring the
signal on an analog input. If the signal
disappears, a Live Zero warning is reported.
10 s* [1-99 s]
Set delay time before Live is applied (6-01 Live Zero Timeout Time). If the signal reappears during the set delay, timer will be reset. When live zero is detected, the frequency converter freezes output frequency and starts
Live Zero Timeout timer.
Zero Timeout Function
Illustration 4.7
6-01 Live Zero Timeout Function
Option: Function:
Function is activated if input signal is below
of value set in 6-10 Terminal 53 Low
50%
Voltage, 6-12 Terminal 53 Low Current or 6-22 Terminal 60 Low Current.
[0] * Off Function is disabled. [1] Freeze
output
[2] Stop Frequency converter ramps down to 0 Hz.
[3] Jogging Frequency converter ramps to jog speed, see
[4] Max Speed Frequency converter ramps to Motor Speed
[5] Stop and
Trip
4.7.3 6-1* Analog Input 1
Parameters for configuring scaling and limits for analog input
1 (terminal 53).
32 MG02C602 - VLT® is a registered Danfoss trademark
Output frequency remains at value it had
live zero was detected.
when
Remove restarting frequency converter.
3-11
High Frequency converter ramps down to 0 Hz and and activate reset before restarting the frequency converter.
live zero error condition before
Jog Speed.
Limit, see 4-14 Motor Speed High Limit.
then trips. Remove live zero condition
Illustration 4.8
6-10 Terminal 53 Low Voltage
Range: Function:
0.07 V* [0.00-9.90 V] Enter low voltage value.
CAUTION
The value must be set to min. 1 V in order to activate the Live Zero Timeout function in 6-01 Live Zero Timeout Function.
This scaling value should correspond to minimum Terminal 53 Low Ref./Feedb. Value. See also 4.4 Parameter Group 3: Reference/ Ramps.
reference value set in 6-14
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
6-11 Terminal 53 High Voltage
Range: Function:
This scaling value should correspond to maximum Terminal 53 High Ref./Feedb. Value.
10.0 V* [0.10-10.00 V] Enter high voltage value.
reference value set in 6-15
6-12 Terminal 53 Low Current
Range: Function:
This reference signal should correspond value set in 6-14 Terminal 53 Low Ref./Feedb. Value.
0.14 mA* [0.00-19.90 mA] Enter low current value.
to minimum reference
CAUTION
The value must be set to min. 2 mA in order to activate the
Live Zero Timeout function in 6-01 Live Zero Timeout
Function.
6-13 Terminal 53 High Current
Range: Function:
This reference signal should correspond reference value set in 6-15 Terminal 53 High Ref./Feedb. Value.
20.00 mA* [0.10-20.00 mA] Enter high current value.
6-14 Terminal 53 Low Ref./Feedb. Value
Range: Function:
The scaling value corresponding to the
voltage/low current set in 6-10
low
Terminal 53 Low Voltage and 6-12 Terminal 53 Low Current.
0.000* [-4999-4999] Enter analog input scaling value.
6-15 Terminal 53 High Ref./Feedb. Value
Range: Function:
The scaling value corresponding to set in 6-11 Terminal 53 High
Voltage and 6-13 Terminal 53 High Current.
50.000* [-4999.000-4999.000] Enter analog input scaling value.
6-16 Terminal 53 Filter Time Constant
Range: Function:
A first-order digital low pass filter time constant for suppressing electrical noise in terminal 53. A high time constant value improves dampening but also increases time delay through the filter.
0.01 s* [0.01-10.00 s] Enter time constant.
to the maximum
the high voltage/high current
6-19 Terminal 53 Mode
Option: Function:
Select the input to be present on terminal
53.
CAUTION
6-19 Terminal 53 Mode MUST according to Micro switch 4 setting.
[0] * Voltage Mode [1] Current Mode
4.7.4 6-2* Analog Input 2
Parameters for configuring scaling and limits for analog
2, terminal 60.
input
6-22 Terminal 60 Low Current
Range: Function:
This reference signal should correspond value set in 6-24 Terminal 60 Low Ref./Feedb. Value.
0.14 mA* [0.00-19.90 mA] Enter low current value.
to minimum reference
be set
CAUTION
The value must be set to min. 2 mA in order to activate the
Live Zero Timeout function in 6-01 Live Zero Timeout
Time.
6-23 Terminal 60 High Current
Range: Function:
This reference signal should correspond value set in 6-25 Terminal 60 High Ref./Feedb. Value.
20.00 mA* [0.10-20.00 mA] Enter high current value.
6-24 Terminal 60 Low Ref./Feedb. Value
Range: Function:
The scaling value corresponding to the
current set in 6-22 Terminal 60 Low
low Current.
0.000* [-4999-4999] Enter analog input scaling value.
6-25 Terminal 60 High Ref./Feedb. Value
Range: Function:
The scaling value corresponding to the
current set in 6-23 Terminal 60 High
high Current.
50.00* [-4999-4999] Enter analog input scaling value.
to the high current
4 4
MG02C602 - VLT® is a registered Danfoss trademark
33
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
6-26 Terminal 60 Filter Time Constant
4.7.6 6-9* Analog Output
Range: Function:
A first-order digital low pass filter time constant in terminal 60. A high time constant value improves dampening, but also increases time delay through the filter.
for suppressing electrical noise
NOTE
44
0.01 s* [0.01-10.00 s] Enter time constant.
4.7.5 6-8* LCP Potentiometer
This parameter cannot be changed while motor runs.
These parameters are for configuring the analog outputs of
frequency converter.
the
6-90 Terminal 42 Mode
Option: Function:
[0] * 0-20 mA Range for analog outputs is 0-20 mA [1] 4-20 mA Range for analog outputs is 4-20 mA [2] Digital output Functions as slow reacting digital output.
value to either 0 mA (off) or 20 mA (on),
Set see 6-92 Terminal 42 Digital Output.
6-91 Terminal 42 Analog Output
Option: Function:
The LCP potentiometer can be selected either as Reference Resource
or Relative Reference Resource.
NOTE
In
Hand mode the LCP potentiometer functions as local
reference.
6-80 LCP Potmeter Enable
Option: Function:
If LCP Potmeter is disabled, [] local reference, and Potmeter value does not give
any reference in Auto/Hand mode. [0] Disabled [1] * Enable
6-81 LCP Potentiometer Low Ref. Value
Range: Function:
The scaling value corresponding to 0.
0.000* [-4999-4999] Enter low reference value.
reference value corresponding to
The potentiometer turned fully counter­clockwise (0 degrees).
6-82 LCP Potentiometer High Ref. Value
Range: Function:
The scaling value corresponding to the maximum 3-03 Maximum Reference.
50.00* [-4999-4999] Enter high reference value.
The potentiometer turned fully clockwise (200 degrees).
reference feedback value set in
reference value corresponding to
[] can adjust
[0] * No Operation [10] Output Frequency [0-100
Hz]
[11] Reference (REF min-max)
[12] Feedback (FB min-max) [13] Motor Current (0-I [16] Power (0-P
[19] DC Link Voltage (0-1000
V)
[20] Bus Reference [0.0%
-100.0%]
nom
max
)
6-92 Terminal 42 Digital Output
Option: Function:
See parameter group 5-4*
choices and descriptions. [0] * No Operation [80] SL Digital
Output
A
See 13-52 SL Control Action. When Smart
Logic Action [38] Set dig. out. A high is
executed, input goes high. When Smart
Logic Action [32] Set dig. out. A low is
executed, input goes low.
6-93 Terminal 42 Output Min. Scale
Range: Function:
0.00% [0.00-200.0%] Scale minimum output of selected analog
signal
maximum signal value. E.g. if 0 mA (or 0
Hz) is desired at 25% of maximum output
value, program 25%. Scaling values up to
100% can never be higher than
corresponding setting in 6-94 Terminal 42
Output Min. Scale.
Select the function for terminal
as an analog output.
42
3-02 Minimum Reference Minimum Reference.
)
16-37 Inv. Max. Current 1-20 Motor Power is
(motor).
The analog output will follow
reference value set on the
the RS-485 bus.
Relays, for
at terminal 42 as percentage of
to 3-03
is
I
.
max
P
nom
34 MG02C602 - VLT® is a registered Danfoss trademark
130BD020.10
(mA)
0%
20
0/4
100%
Current
Analogue output Min Scale par. 6-93
Variable for output example: Speed (RPM)
Analogue Output Max Scale par. 6-94
Parameter Descriptions
Illustration 4.9
6-94 Terminal 42 Output Max. Scale
Range: Function:
100.00%* [0.00-200.00%]
Scale maximum output of selected
signal at terminal 42. Set value
analog to maximum value of current signal output. Scale output to give a current lower than 20 mA at full scale; or 20 mA at an output below 100% of maximum signal value. If 20 mA is the desired output current at a value between 0-100% of the full­scale output, programme percentage value in the parameter, i.e. 50% = 20 mA. If a current between 4 and 20 mA is desired at maximum output (100%), calculate percentage value as follows:
desired maximum current
i.e.
10 mA =
mA
20
20
× 100 = 200 %
10
VLT® Micro Drive FC 51 Programming Guide
4 4
× 100 %
MG02C602 - VLT® is a registered Danfoss trademark
35
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.8 Parameter Group 7: Controllers
4.8.1 7-** Controllers
Parameters group for configuring application controls.
4.8.2 7-2* Process Ctrl. Feedback
7-33 Process PI Proportional Gain
Option: Function:
[0.01] * 0.00-10.00 Enter the value for the P proportional gain,
the multiplication factor of the error
i.e. between the set point and the feedback signal.
NOTE
0.00 = Off.
Select feedback sources and handling for Process PI
44
Control.
7-34 Process PI Integral Time
Range: Function:
NOTE
Set 3-15 use Analog Input as a feedback signal. In order to use analog input as a feedback resource, do not use the same resource as reference resource in 3-15, 3-16 and 3-17.
4.8.3 7-3* Process PI Control
Reference 1 Source to [0] No Function in order to
7-20 Process CL Feedback Resources
Option: Function:
Select input to function as feedback
signal. [0] * No Function [1] Analog Input 53 [2] Analog Input 60 [8] Pulse Input 33 [11] Local Bus Ref.
7-30 Process PI Normal/Inverse Control
Option: Function:
[0] * Normal Feedback larger than setpoint result in a speed
reduction. Feedback increase.
[1] Inverse Feedback larger than setpoint result in a speed
increase. Feedback reduction.
less than setpoint result in a speed
less than setpoint result in a speed
9999.00 s* [0.10-9999.00 s] The integrator provides an increasing between the set point and the feedback signal. The integral time is the time needed by the integrator to reach the same gain as the proportional gain.
gain at a constant error
7-38 Process Feed Forward Factor
Range: Function:
0%* [0-400%] The FF factor sends a part of the reference
around the PI controller which then only
signal affects part of the control signal. By activating the FF factor less overshoot and high dynamics are gained when changing the setpoint. This parameter is always active when 1-00 Configuration Mode is set to [3] Process.
7-39 On Reference Bandwidth
Range: Function:
5% [0-200% ] Enter the value for the On Reference Bandwidth.
PI control error is the difference between
The setpoint and feedback and when this is less than the value set in this parameter the On Reference is active.
7-31 Process PI Anti Windup
Option: Function:
[0] Disable Regulation of a given error will continue even
when the output frequency cannot be increased/ decreased.
[1] * Enable PI-controller ceases from regulating a given error
the output frequency cannot be increased/
when decreased.
7-32 Process PI Start Speed
Range: Function:
0.0 Hz* [0.0-200.0 Hz] Until the set motor speed has been reached operates in Open Loop mode.
36 MG02C602 - VLT® is a registered Danfoss trademark
the frequency converter
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.9 Parameter Group 8: Communication
4.9.1 8-** Communication
Parameter group for configuring communication.
4.9.2 8-0* General Settings
Use this parameter group for configuring the general settings
for communication.
8-01 Control Site
Option: Function:
[0] * Digital and
Control
Word [1] Digital Only Use digital input as control. [2] Control Word
Only
Use both digital input and control word as control.
Use control word only as control.
NOTE
setting in this parameter
The overrules settings in 8-50 Coasting Select to 8-56 Preset Reference Select.
8-02 Control Word Source
Option: Function:
[0] None Function is inactive [1] * FC RS-485 Monitoring control word source is done via
communication port RS-485.
serial
8-03 Control Word Timeout Time
Range: Function:
1.0 s* [0.1-6500 s] Enter time to pass before control word
function (8-04 Control Word Timeout
timeout Function) must be carried out.
8-04 Control Word Timeout Function
Option: Function:
Select the action to be taken in case of a
timeout. [0] * Off No function. [1] Freeze Output Freeze output until communication
resumes. [2] Stop Stop with auto restart when communication
resumes. [3] Jogging Run motor at jog frequency until communi-
resumes.
cation [4] Max. Speed Run motor at max. frequency until
communication [5] Stop and Trip Stop motor, then reset frequency converter
order to restart either via LCP or digital
in
input.
resumes.
8-06 Reset Control Word Timeout
Option: Function:
Resetting the control word timeout will
any timeout function.
remove [0] * No Function Control word timeout is not reset. [1] Do Reset Control word timeout is reset, and parameter
into [0] No Function state.
goes
4.9.3 8-3* FC Port Settings
Parameters for configuring the FC Port.
8-30 Protocol
Option: Function:
Select the protocol to be used. Note that changing
after powering off the frequency converter. [0] * FC [2] Modbus RTU
protocol will not be effective until
8-31 Address
Range: Function:
Select the address for the bus.
1* [1 - Protocol-dependent] FC-bus range is 1-126.
Modbus
range is 1-247.
8-32 FC Port Baud Rate
Option: Function:
Select baud rate for FC Port.
NOTE
Changing responding to any ongoing bus-requests.
[0] 2400 Baud [1] 4800 Baud [2] * 9600 Baud When choosing FC bus in 8-30 [3] * 19200 Baud When choosing Modbus in 8-30 [4] 38400 Baud
8-33 FC Port Parity
Option: Function:
[0] * Even Parity (1 stopbit) [1] Odd parity [2] No Parity (1 stopbit) Select this for Modbus RTU [3] No Parity (2 stopbit)
8-35 Minimum Response Delay
Range: Function:
0.010 s* [0.001-0.500 s] Specify minimum delay time between
baud rate will be effective after
This parameter only affects Modbus
FC bus always has even parity.
as
receiving response.
a request and transmitting a
4 4
MG02C602 - VLT® is a registered Danfoss trademark
37
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
8-36 Max Response Delay
Range: Function:
5.000 s* [0.010-10.00 s] Specify maximum permissible delay between transmitting a request
time and receiving a response. Exceeding this time delay causes control word timeout.
44
4.9.4 8-4* FC MC Protocol Set
8-43 FC Port PCD Read Configuration
Array [16]
Option: Function:
the telegrams. This table is
for [0] array and [1]
not array . For these two arrays, index 1 is fixed to [7] and index 2 is fixed to [8]. These two arrays cannot be changed by end user.
8-43 FC Port PCD Read Configuration
Array [16]
Option: Function:
[0] * None [1] 1500 Operation Hours [2] 1501 Running Hours [3] 1502 kWh Counter [4] 1600 Control Word [5] 1601 Reference [Unit] [6] 1602 Reference % [7] 1603 Status Word [8] 1605 Main Actual Value [%] [9] 1609 Custom Readout [10] 1610 Power [kW] [11] 1611 Power [hp] [12] 1612 Motor Voltage [13] 1613 Frequency [14] 1614 Motor Current [15] 1615 Frequency [%] [16] 1618 Motor Thermal [17] 1630 DC Link Voltage [18] 1634 Heatsink Temp. [19] 1635 Inverter Thermal [20] 1638 SL Controller State [21] 1650 External Reference [22] 1651 Pulse Reference [23] 1652 Feedback [Unit] [24] 1660 Digital Input 18,19,27,33 [25] 1661 Digtial Input 29 [26] 1662 Analog Input 53(V) [27] 1663 Analog Input 53(mA) [28] 1664 Analog Input 60 [29] 1665 Analog Output 42 [mA] [30] 1668 Freq. Input 33 [Hz] [31] 1671 Relay Output [bin] [32] 1672 Counter A [33] 1673 Counter B [34] 1690 Alarm Word [35] 1692 Warning Word [36] 1694 Ext. Status Word
Select the parameters to be assigned telegrams. The number of available PCDs depends on
to PCD's of
4.9.5 8-5* Digital/Bus
Parameters for configuring control word Digital/Bus merging.
NOTE
Parameters [0] Digital and control word.
8-50 Coasting Select
Option: Function:
[0] Digital Input Activation via a digital input. [1] Bus Activation via serial communication port. [2] LogicAnd Activation via serial communication port and
[3] * LogicOr Activation via serial communication port or a
8-51 Quick Stop Select
Option: Function:
[0] Digital Input Activation via a digital input. [1] Bus Activation via serial communication port. [2] LogicAnd Activation via serial communication port and
[3] * LogicOr Activation via serial communication port or a
8-52 DC Brake Select
Option: Function:
[0] Digital Input Activation via a digital input. [1] Bus Activation via serial communication port. [2] LogicAnd Activation via serial communication port and
[3] * LogicOr Activation via serial communication port or a
are only active when 8-01 Control Site, is set to
Select control of coasting function via digital
and/or bus.
input
digital input.
a
input.
digital
Select control of quick stop function via
input and/or bus.
digital
digital input.
a
input.
digital
Select control of DC brake via digital input and/or
bus.
digital input.
a
input.
digital
38 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
8-53 Start Select
Option: Function:
Select control of start function via digital
and/or bus.
input [0] Digital Input Activation via a digital input. [1] Bus Activation via serial communication port. [2] LogicAnd Activation via serial communication port and
digital input.
a [3] * LogicOr Activation via serial communication port or a
input.
digital
8-54 Reversing Select
Option: Function:
Select control of reversing function via digital
and/or bus.
input [0] Digital Input Activation via a digital input. [1] Bus Activation via serial communication port. [2] LogicAnd Activation via serial communication port and
digital input.
a [3] * LogicOr Activation via serial communication port or a
input.
digital
8-55 Set-up Select
Option: Function:
Select control of set-up selection via digital
and/or bus.
input [0] Digital Input Activation via a digital input. [1] Bus Activation via serial communication port. [2] LogicAnd Activation via serial communication port and
digital input.
a [3] * LogicOr Activation via serial communication port or a
input.
digital
8-81 Bus Error Count
Range: Function:
0 N/A* [0-0 N/A] This parameter shows the number of
telegrams detected on the bus.
with faults (e.g. CRC fault),
8-82 Slave Messages Rcvd
Range: Function:
0 N/A* [0-0 N/A] This parameter shows the number of valid
telegrams frequency converter.
addressed to the slave, sent by the
8-83 Slave Error Count
Range: Function:
0 N/A* [0-0 N/A] This parameter shows the number of error
telegrams, frequency converter.
which could be executed by the
4.9.7 8-9* Bus Feedback
Parameter for configuring bus feedback.
8-94 Bus Feedback 1
Range: Function:
0* [0x8000-0x7FFF] Bus feedback is delivered via FC or
Modbus this parameter.
by writing the feedback value into
4 4
8-56 Preset Reference Select
Option: Function:
Select control of Preset Reference selection
digital input and/or bus.
via [0] Digital Input Activation via a digital input. [1] Bus Activation via serial communication port. [2] LogicAnd Activation via serial communication port and
digital input.
a [3] * LogicOr Activation via serial communication port or a
input.
digital
4.9.6 8-8* Bus communication diagnostics
These parameters are used for monitoring the Bus communication
8-80 Bus Message Count
Range: Function:
0 N/A* [0-0 N/A] This parameter shows the number of valid
via the Port.
telegrams
detected on the bus.
MG02C602 - VLT® is a registered Danfoss trademark
39
130BD021.10
State 1 Event 1/ Action 1
State 2 Event 2/ Action 2
Start event P13-01
State 3 Event 3/ Action 3
State 4 Event 4/ Action 4
Stop event P13-02
Stop event P13-02
Stop event P13-02
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
44
4.10 Parameter Group 13: Smart Logic
4.10.1 13-** Programming Features
4.10.2 13-0* SLC Settings
Use SLC settings to activate, deactivate and reset the Smart
Smart Logic Control (SLC)is a sequence of user-defined actions
(13-52 SL Controller Action [X]) executed by the SLC when the associated user-defined event (13-51 SL Controller Event [X]) is set to True.
Events and actions are linked in pairs, meaning that when an event is true, the linked action is carried out. After this the next event is evaluated and its belonging action
13-00 SL Controller Mode
Option: Function:
[0] * Off Function is disabled. [1] On SLC is active.
13-01 Start Event
Option: Function:
carried out and so on. Only one event is evaluated at the time.
[0] False
If an event is evaluated as False, the SLC takes no action during the scan interval and no other events are evaluated.
It is possible to programme from 1 to 20 events and
[1] True [2] Running
[3] InRange
actions. When the last event/action has been executed, the
[4] OnReference
sequence starts again from event/action [0].
[7] Out of Current
[8] BelowILow
[9] AboveIHigh
[16] ThermalWarning
[17] MainsOutOfRange Mains voltage is outside the
[18] Reversing
[19] Warning A warning is active.
Illustration 4.10 Example with Three Events/Actions
[20] Alarm_Trip A trip alarm is active. [21] Alarm_TripLock A trip lock alarm is active. [22] Comparator 0 Use result of comparator 0 in logic
Starting and stopping the SLC
the SLC by selecting [1] On in 13-00 SL Controller
Start
[23] Comparator 1 Use result of comparator 1 in logic
Mode The SLC starts evaluating Event 0, and if this is evaluated as TRUE, the SLC continues its cycle.
The SLC stops when the Stop Event, 13-02 Stop Event, is
[24] Comparator 2 Use result of comparator 2 in logic
[25] Comparator 3 Use result of comparator 3 in logic
TRUE. The SLC can also be stopped by selecting [0] Off in 13-00 SL Controller Mode.
To reset all SLC parameters select [1] Reset SLC in 13-03
[26] LogicRule 0 Use result of logic rule 0 in logic
[27] LogicRule 1 Use result of logic rule 1 in logic
Reset Smart Logic Controller and start programming from scratch.
40 MG02C602 - VLT® is a registered Danfoss trademark
[28] LogicRule 2 Use result of logic rule 2 in logic
[29] LogicRule 3 Use result of logic rule 3 in logic
[33] DigitalInput_18 Use value of DI 18 in logic rule. [34] DigitalInput_19 Use value of DI 19 in logic rule. [35] DigitalInput_27 Use value of DI 27 in logic rule.
Logic Control.
Range
Select input to activate Smart Logic Control. Enters False in Enters True in See parameter group 5-4* for description. See parameter group 5-4* for description. See parameter group 5-4* for description. See parameter group 5-4* for description. See parameter group 5-4* for description. See parameter group 5-4* for description. See parameter group 5-4* for description.
specified See parameter group 5-4* for description.
rule.
rule.
rule.
rule.
rule.
rule.
rule.
rule.
logic rule.
logic rule.
Relays [5]
Relays [7]
Relays [8]
Relays [12]
Relays [13]
Relays [14]
Relays [21]
voltage range.
Relays [25]
Par. 13-11 Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10 Comparator Operand
Par. 13-12 Comparator Value
130BD022.10
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
[36] DigitalInput_29 Use value of DI 29 in logic rule. [38] DigitalInput_33 [39] * StartCommand
[40] DriveStopped
[0] False [1] True [2] Running
[3] InRange
[4] OnReference
[7] Out of Current
[8] BelowILow
[9] AboveIHigh
[16] ThermalWarning
[17] MainsOutOfRange Mains voltage is outside the
[18] Reversing
[19] Warning A warning is active. [20] Alarm_Trip A trip alarm is active. [21] Alarm_TripLock A trip lock alarm is active. [22] Comparator 0 Use result of comparator 0 in logic
[23] Comparator 1 Use result of comparator 1 in logic
[24] Comparator 2 Use result of comparator 2 in logic
[25] Comparator 3 Use result of comparator 3 in logic
[26] LogicRule 0 Use result of logic rule 0 in logic
[27] LogicRule 1 Use result of logic rule 1 in logic
[28] LogicRule 2 Use result of logic rule 2 in logic
[29] LogicRule 3 Use result of logic rule 3 in logic
[30] SL Timeout0 Use result of timer 0 in logic rule.
13-01 Start Event
Option: Function:
This event is True, converter is started by any means (digital input or other). This event is True, converter is stopped or coasted by any means (digital input or other).
13-02 Stop Event
Option: Function:
Select input to activate Smart Logic Control. Enters False in Enters True in See parameter group 5-4* for description. See parameter group 5-4* for description. See parameter group 5-4* for description. See parameter group 5-4*
Range
for description. See parameter group 5-4* for description. See parameter group 5-4* for description. See parameter group 5-4* for description.
specified See parameter group 5-4* for description.
rule.
rule.
rule.
rule.
rule.
rule.
rule.
rule.
13-02 Stop Event
Option: Function:
[31] SL Timeout1 Use result of timer 1 in logic rule. [32] SL Timeout2 Use result of timer 2 in logic rule.
if frequency
if frequency
logic rule.
logic rule.
voltage range.
Relays [5]
Relays [7]
Relays [8]
Relays [12]
Relays [13]
Relays [14]
Relays [21]
Relays [25]
[33] DigitalInput_18 Use value of DI 18 in logic rule. [34] DigitalInput_19 Use value of DI 19 in logic rule. [35] DigitalInput_27 Use value of DI 27 in logic rule. [36] DigitalInput_29 Use value of DI 29 in logic rule. [38] DigitalInput_33 [39] StartCommand
[40] * DriveStopped
13-03 Reset SLC
Option: Function:
[0] * Do Not Reset Retains all settings programmed in
[1] Reset SLC Reset all group 13 parameters to default
4.10.3 13-04 Comparators
Comparators are used for comparing continuous variables
output frequency, output current, analog input etc.) to
(i.e. fixed preset values.
Illustration 4.11
In addition, there are digital values that will be compared
fixed time values. See explanation in 13-10 Comparator
to Operand. Comparators are evaluated once in each scan interval. Use the result (TRUE or FALSE) directly. All parameters in this parameter group are array parameters with index 0 to 5. Select index 0 toprogramme Comparator 0, select index 1 to programme Comparator 1, and so on.
13-10 Comparator Operand
Array [4]
Option: Function:
[0] * Disabled Comparator is disabled. [1] Reference Resulting remote reference (not local) as a
MG02C602 - VLT® is a registered Danfoss trademark
This event is True, converter is started by any means (digital input or other). This event is True, converter is stopped or coasted by any means (digital input or other).
parameter
settings.
Select variable to be monitored by comparator.
percentage.
group 13.
if frequency
if frequency
4 4
41
. . . . . .
. . . . . .
Par. 13-43 Logic Rule Operator 2
Par. 13-41 Logic Rule Operator 1
Par. 13-40 Logic Rule Boolean 1
Par. 13-42 Logic Rule Boolean 2
Par. 13-44 Logic Rule Boolean 3
130BD023.10
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
44
13-10 Comparator Operand
Array [4]
Option: Function:
[2] Feedback Feedback in [Hz]. [3] MotorSpeed Motor speed in Hz. [4] MotorCurrent Motor current in [A]. [6] MotorPower Motor power in either [kW] or [hp]. [7] MotorVoltage Motor voltage in [V]. [8] DCLinkVoltage DC-link voltage in [V]. [12] AnalogInput53 Expressed as actual value. [13] AnalogInput60 Expressed as actual value. [18] PulseInput33 Expressed as actual value. [20] AlarmNumber Shows number of the alarm. [30] CounterA Number of counts. [31] CounterB Number of counts.
13-20 SLC Controller Timer
Array [3]
Range: Function:
0.0 s* [0.0-3600 s]
4.10.5 13-4* Logic Rules
Combine up to three boolean inputs (TRUE/FALSE inputs)
timers, comtors, digital inputs, status bits and events
from using the logical operators AND, OR, and NOT. Select boolean inputs for the calculation in LC-40 Logic Rule
Boolean 1, LC-42 Logic Rule Boolean 2 and LC-44 Logic Rule Boolean 3. Define the operators used to logically combine
13-11 Comparator Operator
Array [4]
the selected inputs in LC-41 Logic Rule Operator 1 and LC-43 Logic Rule Operator 2.
Option: Function:
Select operator to be used in comparison.
[0] Less Than <
[1] * Approxi-
mately
[2] Greater Than>Inverse logic of option [0].
Result of evaluation is True selected in 13-10 Comparator Operand is smaller than fixed value in 13-12 Comparator Value. Result is False if variable selected in 13-10 Comparator Operand is greater than fixed value in 13-12 Comparator Value. Result of evaluation is True if variable
equals
selected in 13-10 Comparator Operand is approximately equal to fixed value in 13-12 Comparator Value.
if
variable
Illustration 4.12
Priority of calculation The
results of LC-40 Logic Rule Boolean 1, LC-41 Logic Rule
Operator 1 and LC-42 Logic Rule Boolean 2 are calculated first. The outcome (TRUE/FALSE) of this calculation is
13-12 Comparator Value
Array [4]
Range: Function:
0.0* [-9999-9999] Enter “trigger level” for variable monitored this comparator.
by
combined with the settings of LC-43 Logic Rule Operator 2 and LC-44 Logic Rule Boolean 3, yielding the final result (TRUE/FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [4]
Option: Function:
4.10.4 13-2* Timers
Use the timer results to define an event (13-51
Action) or as boolean input in a logic rule (13-40 Logic Rule Boolean 1, 13-42 Logic Rule Boolean 2 or 13-44 Logic Rule Boolean 3).
When timer value has elapsed timer changes state from False to True.
42 MG02C602 - VLT® is a registered Danfoss trademark
SL Controller
[0] * False [1] True [2] Running
[3] InRange
[4] OnReference
[7] Out of Current
Range
[8] BelowILow
Enter value to define duration of the False
from programmed timer. A timer is
output only False if it is started by an action and until the given timer value has elapsed.
Select first boolean input for selected
rule.
logic Enters False in Enters True in See parameter group 5-4* for description. See parameter group 5-4* for description. See parameter group 5-4* for description. See parameter group 5-4* for description. See parameter group 5-4* for description.
logic rule.
logic rule.
Relays [5]
Relays [7]
Relays [8]
Relays [12]
Relays [13]
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
13-40 Logic Rule Boolean 1
Array [4]
Option: Function:
[9] AboveIHigh
[16] ThermalWarning
[17] MainsOutOfRange Mains voltage is outside the specified
[18] Reversing
[19] Warning A warning is active. [20] Alarm_Trip A trip alarm is active. [21] Alarm_TripLock A trip lock alarm is active. [22] Comparator 0 Use result of comparator 0 in logic
[23] Comparator 1 Use result of comparator 1 in logic
[24] Comparator 2 Use result of comparator 2 in logic
[25] Comparator 3 Use result of comparator 3 in logic
[26] LogicRule 0 Use result of logic rule 0 in logic rule. [27] LogicRule 1 Use result of logic rule 1 in logic rule. [28] LogicRule 2 Use result of logic rule 2 in logic rule. [29] LogicRule 3 Use result of logic rule 3 in logic rule. [30] SL Timeout0 Use result of timer 0 in logic rule. [31] SL Timeout1 Use result of timer 1 in logic rule. [32] SL Timeout2 Use result of timer 2 in logic rule. [33] DigitalInput_18 Use value of DI 18 in logic rule. [34] DigitalInput_19 Use value of DI 19 in logic rule. [35] DigitalInput_27 Use value of DI 27 in logic rule. [36] DigitalInput_29 Use value of DI 29 in logic rule. [38] DigitalInput_33 Use value of DI 33 in logic rule [39] StartCommand
[40] DriveStopped
See parameter group 5-4* for description. See parameter group 5-4* for description.
range.
voltage See parameter group 5-4* for description.
rule.
rule.
rule.
rule.
This event is True, converter is started by any means (digital input or other). This event is True, converter is stopped or coasted by any means (digital input or other).
Relays [14]
Relays [21]
Relays [25]
if frequency
if frequency
13-41 Logic Rule Operator 1
Array [4]
Option: Function:
[6] Not or Evaluates expression NOT [13-40] OR [13-42]. [7] Not and not Evaluates expression NOT [13-40] AND NOT
[13-42].
[8] Not or not Evaluates expression NOT [13-40] OR NOT
[13-42].
13-42 Logic Rule Boolean 2
Array [4]
Option: Function:
Select second boolean input for selected logic rule. See 13-40 descriptions.
Logic Rule Boolean 1 for choices and
13-43 Logic Rule Operator 2
Array [4]
Option: Function:
Select second logical operator to use on
inputs calculated in 13-40 Logic Rule
boolean
Boolean 1, 13-41 Logic Rule Operator 1, and 13-42 Logic Rule Boolean 2 and the boolean
input from 13-42 Logic Rule Boolean 2.
[0] * Disabled [1] And Evaluates expression [13-40/13-42] AND
[2] Or Evaluates expression [13-40/13-42] OR [13-44]. [3] And not Evaluates expression [13-40/13-42] AND NOT
[4] Or not Evaluates expression [13-40/13-42] OR NOT
[5] Not and Evaluates expression NOT [13-40/13-42] and
[6] Not or Evaluates expression NOT [13-40/13-42] OR
[7] Not and not Evaluates expression NOT [13-40/13-42] AND
[8] Not or not Evaluates expression NOT [13-40/13-42] OR
Ignores 13-44
[13-44].
[13-44].
[13-44].
[13-44].
[13-44].
[13-44].
NOT
[13-44].
NOT
Logic Rule Boolean 3.
4 4
13-41 Logic Rule Operator 1
Array [4]
Option: Function:
Select first logical operator to use on boolean
from 13-40 Logic Rule Boolean 1 and
inputs 13-42 Logic Rule Boolean 2.
[0] * Disabled
[1] And Evaluates expression [13-40] AND [13-42]. [2] Or Evaluates expression [13-40] OR [13-42]. [3] And not Evaluates expression [13-40] AND NOT [13-42]. [4] Or not Evaluates expression [13-40] OR NOT [13-42]. [5] Not and Evaluates expression NOT [13-40] and [13-42].
Ignores 13-42
Rule Operator 2 and 13-44 Logic Rule Boolean
3.
Logic Rule Boolean 2, 13-43 Logic
MG02C602 - VLT® is a registered Danfoss trademark
13-44 Logic Rule Boolean 3
Array [4]
Option: Function:
Select third boolean input for selected logic rule.
13-40
See descriptions.
Logic Rule Boolean 1 for choices and
43
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.10.6 13-5* States
13-51 SL Controller Event
Array [20]
Option: Function:
Select boolean input to define Smart Controller Event.
13-40
See descriptions.
44
13-52 SL Controller Action
Array [20]
Option: Function:
[0] * Disabled Function is disabled. [1] No Action No action is taken. [2] Select Set-up1 Changes active set-up to Set-up 1. [3] Select Set-up2 Changes active set-up to Set-up 2. [10] SelectPresetRef0 Selects preset reference 0 [11] SelectPresetRef1 Selects preset reference 1 [12] SelectPresetRef2 Selects preset reference 2 [13] SelectPresetRef3 Selects preset reference 3 [14] SelectPresetRef4 Selects preset reference 4 [15] SelectPresetRef5 Selects preset reference 5 [16] SelectPresetRef6 Selects preset reference 6 [17] SelectPresetRef7 Selects preset reference 7 [18] SelectRamp1 Selects ramp 1 [19] SelectRamp2 Selects ramp 2 [22] Run Issues start command to frequency
[23] RunReverse Issues start reverse command to
[24] Stop Issues stop command to frequency
[25] Qstop Issues quick stop command to frequency
[26] DCstop Issues DC stop command to frequency
[27] Coast frequency converter coasts immediately.
[28] Freeze Output Freezes output frequency. [29] StartTimer0 Starts timer 0. [30] StartTimer1 Starts timer 1 [31] StartTimer2 Starts timer 2 [32] SetDO42Low Set Digital output 42 low. [33] SetRelayLow Set Relay low. [38] SetDO42High Set Digital output 42 high. [39] SetRelayHigh Set Relay high. [60] ResetCounterA Resets counter A to 0. [61] ResetCounterB Resets counter B to 0.
Logic Rule Boolean 1 for choices and
Select action corresponding to SLC event.
are executed when corresponding
Actions event (13-51 SL Controller Event) is evaluated as True.
converter.
frequency
converter.
converter.
converter.
All command stop the SLC.
converter.
stop commands including coast
44 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.11 Parameter Group 14: Special Functions
4.11.1 14-** Special Functions
Parameter group for configuring special frequency converter
functions.
4.11.2 14-0* Inverter Switching
14-01 Switching Frequency
Option: Function:
Select the switching frequency in order to minimize
maximizing efficiency. [0] 2 KHz [1] * 4 KHz [2] 8 KHz [4] 16 KHz
e.g. acoustic noise and power loss or
NOTE
For
18.5 kW and 22 kW frequency converter, the option [4]
is not available.
14-03 Overmodulation
Option: Function:
This feature allows more accurate speed control near
over nominal speed (50/60 Hz). Another
and advantage with overmodulation is the ability of staying at a constant speed even though main is dropping.
[0] Off Disables the overmodulation function to avoid torque
on the motor shaft.
ripple
[1] * On Connects the overmodulation function to obtain an
voltage up to 15% greater than mains voltage.
output
4.11.3 14-1* Mains Monitoring
This parameter group supplies functions for handling imbalance
14-12 Functions at Mains Imbalance
Option: Function:
[0] * Trip Frequency converter trips. [1] Warning Frequency converter issues a warning. [2] Disabled No action taken.
Parameters for configuring auto reset handling, special trip handling
on mains.
Operation under severe mains imbalance conditions Select function to take place when severe mains imbalance is detected.
reduces drive lift time.
and control card self test or initialisation.
14-20 Reset Mode
Option: Function:
Select reset function after tripping. Once
the frequency converter can be
reset,
restarted. [0] * Manual Reset Perform reset via [Reset] or digital inputs. [1] AutoReset 1 Performs one automatic reset after
tripping. [2] AutoReset 2 Performs two automatic resets after
tripping. [3] AutoReset 3 Performs three automatic resets after
tripping. [4] AutoReset 4 Performs four automatic resets after
tripping. [5] AutoReset 5 Performs five automatic resets after
tripping. [6] AutoReset 6 Performs six automatic resets after
tripping. [7] AutoReset 7 Performs seven automatic resets after
tripping. [8] AutoReset 8 Performs eight automatic resets after
tripping. [9] AutoReset 9 Performs nine automatic resets after
tripping. [10] AutoReset 10 Performs ten automatic resets after
tripping. [11] AutoReset 15 Performs fifteen automatic resets after
tripping. [12] AutoReset 20 Performs twenty automatic resets after
tripping. [13] Infinite auto
reset
[14] Reset at
power-up
Performs an infinite number of automatic
after tripping.
resets
Trip-lock alarm can be reset at power up.
CAUTION
Motor may start without warning.
14-21 Automatic Restart Time
Range: Function:
10 s* [0-600 s] Enter time interval from trip to start of
automatic active when 14-20 Reset Mode, is set to [1] to [13] Automatic Reset.
reset function. This parameter is
14-22 Operation Mode
Option: Function:
Use this parameter for specifying normal operation except 15-03 Power Ups, 15-04 Over Temps and 15-05 Over Volts.
[0] * Normal
Operation
[2] Initialization Resets all parameters to default settings,
Frequency converter runs normal operation.
except Temps and 15-05 Over Volts. Frequency converter resets during next power-up.
or to initialize all parameters,
for 15-03 Power Ups, 15-04 Over
4 4
MG02C602 - VLT® is a registered Danfoss trademark
45
Parameter Descriptions
14-22 Operation Mode
Option: Function:
14-22 Operation Mode setting [0] Normal Operation.
14-26 Action at Inverter Fault
Option: Function:
[0] Trip When the frequency converter detects an over-
it will trip immediately.
44
[1] * Warning When the frequency converter detects an over-
voltage,
NOTE
It is recommended to choose [0] Trip in hoisting applications.
voltage, it will give warning immediately. After protection filter, it will trip.
VLT® Micro Drive FC 51 Programming Guide
also
reverts to default
NOTE
It is recommended to disable protection mode in hoisting applications.
4.11.4 15-4* Drive Identification
Parameters containing read only information about the hardware converter.
14-41 AEO Minimum Magnetization
Range: Function:
66%* [40-75%] Enter the minimum allowable magnetization
and software configuration of the frequency
AEO. Selecting a low value reduces energy
for loss in the motor, but may also reduce resistance to sudden load changes.
46 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.12 Parameter Group 15: Drive Information
Parameter group containing information on operating
hardware configuration, software version, etc.
data,
15-00 Operating Time
Range: Function:
0 days* [0-65535
days]
15-01 Running Hours
Range: Function:
0* [0- 2147483647] View running hours of motor.
15-02 kWh Counter
Range: Function:
0 [0-65535] View power consumption in kWh as a mean value
over Reset counter in 15-06 Reset kWh Counter.
15-03 Power Ups
Range: Function:
0 [0-2147483647] View number of times frequency converter
15-04 Over Temps
Range: Function:
0 [0-65535] View number of times frequency converter has
tripped Counter cannot be reset.
15-05 Over Volts
Range: Function:
0* [0-65535] View number of times frequency converter has
tripped Counter cannot be reset.
15-06 Reset kWh Counter
Option: Function:
[0] * Do Not Reset Counter is not reset. [1] Reset Counter Counter is reset.
View how many days the frequency converter The value is saved at power off and cannot be reset.
The value is saved at power off and can be reset in 15-07 Reset Running Hours Counter.
one hour.
been powered up.
has Counter cannot be reset.
due to over temperature.
due to over voltage.
has been powered up.
4.12.1 15-3* Fault Log
This parameter group contains a fault log showing reasons
the ten latest trips.
for
15-30 Fault Log: Error Code
Range: Function:
0 [0-255]
View error code and look it up in VLT
Guide, MG02B.
Micro Quick
4.12.2 15-4* Drive Identification
Parameters containing read only information about the hardware converter.
15-40 FC Type
Option: Function:
15-41 Power Section
Option: Function:
15-42 Voltage
Option: Function:
15-43 Software Version
Option: Function:
15-46 Frequency Converter Ordering No
Option: Function:
15-48 LCP ID No
Option: Function:
15-51 Frequency Converter Serial Number
Option: Function:
and software configuration of the frequency
View FC type.
View power section of frequency converter.
View voltage of frequency converter.
View software version of frequency converter.
View ordering number for re-ordering frequency converter
in its original configuration.
View LCP ID number.
View frequency converter serial number.
4 4
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do Not Reset Counter is not reset. [1] Reset Counter Counter is reset.
MG02C602 - VLT® is a registered Danfoss trademark
47
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.13 Parameter Group 16: Data Readouts
16-13 Frequency
Range: Function:
16-00 Control Word
0.0 Hz* [0.0-400.0 Hz] View output frequency in Hz.
Range: Function:
0* [0-65535] View latest valid control word sent to frequency
converter
via serial communication port.
16-01 Reference [Unit]
Range: Function:
44
0.000* [-4999.000-4999.000] View total remote reference. Total reference is sum of pulse, analog, preset, LCP potentiometer, local bus and freeze reference.
16-02 Reference %
Range: Function:
0.0* [-200.0-200.0%] View total remote reference in percent.
reference is sum of pulse, analog,
Total preset, LCP potentiometer, local bus and freeze reference.
16-14 Motor Current
Range: Function:
0.00 A* [0.00-655 A] View motor phase current.
16-15 Frequency [%]
Range: Function:
0.00* [-100.00-100.00%] View a two-byte word reporting actual frequency as a percentage of
motor
4-14 Motor Speed High Limit
16-18 Motor Thermal
Range: Function:
0%* [0-100%] View calculated thermal motor load as
percentage
of estimated thermal motor load.
4.13.2 16-3* Drive Status
16-03 Status Word
Range: Function:
0* [0-65535] View status word sent to frequency converter via
communication port.
serial
16-30 DC Link Voltage
Range: Function:
0 V* [0-10000 V] View DC-link voltage.
16-05 Main Actual Value %
Range: Function:
0.00* [-100.00-100.00%] View two-byte word sent with status to bus Master reporting main
word actual value.
16-09 Custom Readout
Range: Function:
0.00* [0.00-9999.00%]
Customized readout based on the
of 0-31 Custom Readout Min
settings Scale, 0-32 Custom Readout Max Scale and 4-14 Motor Speed High Limit
4.13.1 16-1* Motor Status
16-10 Power [kW]
Range: Function:
0 kW* [0-99 kW] View output power in kW.
16-11 Power [hp]
Range: Function:
0 hp [0-99 hp ] View output power in hp.
16-34 Heat Sink Temp.
Range: Function:
0*
[0-255°C]
View heat sink temperature of frequency converter.
16-35 Inverter Thermal
Range: Function:
0%* [0-100%] View calculated thermal load on frequency
converter on frequency converter.
in relation to estimated thermal load
16-36 Inv. Nom. Current
Range: Function:
0.00 A* [0.01-655A] View continuous nominal inverter current.
16-37 Inv. Max. Current
Range: Function:
0.00 A* [0.1-655A] View intermittent maximum inverter current (150%).
16-38 SL Controller State
Range: Function:
0* [0-255] View number of active SLC state.
16-12 Motor Voltage
4.13.3 16-5* Ref. & Feedb.
Range: Function:
0.0* [0.0-999.9 V] View motor phase voltage.
16-50 External Reference
Range: Function:
0.0%* [-200.0-200.0%] View sum of all external references in
48 MG02C602 - VLT® is a registered Danfoss trademark
percent.
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
16-51 Pulse Reference
Range: Function:
0.0 %* [-200.0-200.0%] View actual pulse input converted to a reference
in percent.
16-52 Feedback
Range: Function:
0.000* [-4999.000-4999.000] View analog or pulse feedback in
Hz.
4.13.4 16-6* Inputs and Outputs
16-60 Digital Input 18, 19, 27, 33
Range: Function:
0* [0-1111] View signal states from active digital inputs.
16-61 Digital Input 29
Range: Function:
0* [0-1] View signal state on digital input 29.
16-62 Analog Input 53 (volt)
Range: Function:
0.00* [0.00-10.00 V] View input voltage on analog input
terminal.
16-63 Analog Input 53 (current)
Range: Function:
0.00* [0.00-20.00 mA] View input current on analog input
terminal.
4.13.5 16-8* FC Port
Parameter for viewing references from FC Port.
16-86 FC Port REF 1
Range: Function:
0* [0x8000-0x7FFF] View currently received reference from FC
Port.
4.13.6 16-9* Diagnosis Read-Outs
16-90 Alarm Word
Range: Function:
0* [0-0xFFFFFFFF] Via alarm word sent via serial communi-
port in hex code.
cation
16-92 Warning Word
Range: Function:
0* [0-0xFFFFFFFF] View warning word sent via serial communi-
cation
port in hex code.
16-94 Ext. Status Word
Range: Function:
0* [0-0xFFFFFFFF] View extended warning word sent via serial
communication
port in hex code.
4 4
16-64 Analog Input 60
Range: Function:
0.00* [0.00-20.00 mA] View actual value at input 60 either as
reference
or protection value.
16-65 Analog Output 42 [mA]
Range: Function:
0.00 mA* [0.00-20.00 mA] View output current on analog
42.
output
16-68 Pulse Input
Range: Function:
20 Hz* [20-5000 Hz] View input frequency on pulse input
terminal.
16-71 Relay Output [bin]
Range: Function:
0* [0-1] View relay setting.
16-72 Counter A
Range: Function:
0* [-32768-32767] View present value of Counter A.
16-73 Counter B
Range: Function:
0* [-32768-32767] View present value of Counter B.
MG02C602 - VLT® is a registered Danfoss trademark
49
Parameter Lists
VLT® Micro Drive FC 51 Programming Guide
5 Parameter Lists
Parameter Overview
0-** Operation/Display
Basic Settings
0-0/
0-03 Regional Settings *[0] International [1] US 0-04 Oper. State at Power-up (Hand)
55
[0] Resume [1] Forced stop, ref=f”old [2] Forced stop, re=0
0-1* Set-up Handling
0-10 Active Set-up *[1] Setup 1 [2] Setup 2 [9] Multi Setup 0-11 Edit Set-up *[1] Setup 1 [2] Setup 2 [9] Active Setup 0-12 Link Setups [0] Not Linked *[20] Linked 0-31 Custom Readout Min Scale
0.00–9999.00 *0.00 0-32 Custom Readout Max Scale
0.00–9999.00 *100.0
0-4* LCP Keypad
0-40 [Hand on] Key on LCP [0] Disabled *[1] Enabled 0-41 [Off / Reset] Key on LCP [0] Disable All *[1] Enable All [2] Enable Reset Only 0-42 [Auto on] Key on LCP [0] Disabled *[1] Enabled
0-5* Copy/Save
0-50 LCP Copy *[0] No copy [1] All to LCP [2] All from LCP [3] Size indep. from LCP 0-51 Set-up Copy *[0] No copy [1] Copy from setup 1 [2] Copy from setup 2 [9] Copy from Factory setup
0-6* Password
0-60 (Main) Menu Password 0-999 *0 0-61 Access to Main/Quick Menu w/o Password *[0] Full access [1] LCP: Read Only [2] LCP: No Access
1-** Load/Motor 1-0* General Settings
1-00 Configuration Mode *[0] Speed open loop [3] Process 1-01 Motor Control Principle [0] U/f
plus
*[1] VVC 1-03 Torque Characteristics *[0] Constant torque [2] Automatic Energy Optim. 1-05 Local Mode Configuration [0] Speed Open Loop *[2] As config in par. 1-00
1-2* Motor Data
1-20 Motor Power [kW] [HP] [1] 0.09 kW/0.12 HP [2] 0.12 kW/0.16 HP [3] 0.18 kW/0.25 HP [4] 0.25 kW/0.33 HP [5] 0.37 kW/0.50 HP [6] 0.55 kW/0.75 HP [7] 0.75 kW/1.00 HP [8] 1.10 kW/1.50 HP [9] 1.50 kW/2.00 HP [10] 2.20 kW/3.00 HP [11] 3.00 kW/4.00 HP [12] 3.70 kW/5.00 HP [13] 4.00 kW/5.40 HP [14] 5.50 kW/7.50 HP [15] 7.50 kW/10.00 HP [16] 11.00 kW/15.00 HP [17] 15.00 kW/20.00 HP [18] 18.50 kW/25.00 HP [19] 22.00 kW/29.50 HP [20] 30.00 kW/40.00 HP 1-22 Motor Voltage 50-999 V * 230-400 V 1-23 Motor Frequency 20-400 Hz *50 Hz 1-24 Motor Current
0.01-100.00 A *Motortype dep. 1-25 Motor Nominal Speed 100-9999 rpm * Motortype dep.
1-29 Automatic Motor Tuning (AMT) *[0] Off [2] EnableAMT
1-3* Adv. Motor Data
1-30 Stator Resistance (Rs) [Ohm] * Dep. on motor data 1-33 Stator Leakage Reactance (X1) [Ohm] * Dep. on motor data 1-35 Main Reactance (Xh) [Ohm] * Dep. on motor data
1-5* Load Indep. Setting
1-50 Motor Magnetisation at 0 Speed 0-300% *100% 1-52 Min Speed Norm. Magnet. [Hz]
0.0-10.0 Hz *0.0 Hz 1-55 U/f Characteristic - U 0-999.9 V 1-56 U/f Characteristic - F 0-400 Hz
1-6* Load Depen. Setting
1-60 Low Speed Load Compen­sation 0-199% Load CompensationLoad Compensation *100% 1-61 High Speed Load Compen­sation 0-199% *100% 1-62 Slip Compensation
-400-399% *100% 1-63 Slip Compensation Time Constant
0.05-5.00 s *0.10 s
1-7* Start Adjustments
1-71 Start Delay
0.0-10.0 s * 0.0 s 1-72 Start Function [0] DC hold/delay time [1] DC brake/delay time *[2] Coast/delay time 1-73 Flying Start *[0] Disabled [1] Enabled
1-8* Stop Adjustments
1-80 Function at Stop *[0] Coast [1] DC hold
1-82 Min Speed for Funct. at Stop [Hz]
0.0-20.0 Hz *0.0 Hz
1-9* Motor Temperature
1-90 Motor Thermal Protection *[0] No protection [1] Thermistor warning [2] Thermistor trip [3] Etr warning [4] Etr trip 1-93 Thermistor Resource *[0] None [1] Analog input 53 [6] Digital input 29
2-** Brakes 2-0* DC-Brake
2-00 DC Hold Current 0-150% *50% 2-01 DC Brake Current 0-150% *50% 2-02 DC Braking Time
0.0-60.0 s *10.0 s 2-04 DC Brake Cut In Speed
0.0-400.0 Hz * 0.0 Hz
2-1* Brake Energy Funct.
2-10 Brake Function *[0] Off [1] Resistor brake [2] AC brake 2-11 Brake Resistor (ohm) 5-5000 *5 2-16 AC Brake, Max current 0-150% *100% 2-17 Over-voltage Control *[0] Disabled [1] Enabled (not at stop) [2] Enabled
2-2* Mechanical Brake
2-20 Release Brake Current
0.00-100.0 A *0.00 A 2-22 Activate Brake Speed [Hz]
0.0-400.0 Hz * 0.0 Hz
3-** Reference / Ramps 3-0* Reference Limits
3-00 Reference Range *[0] Min to Max [1] -Max to+Max 3-02 Minimum Reference
-4999-4999 *0.000 3-03 Maximum Reference
-4999-4999 *50.00
Table 5.1
50 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Lists
VLT® Micro Drive FC 51 Programming Guide
3-1* References
Preset Reference
3-10
-100.0-100.0% *0.00% 3-11 Jog Speed [Hz]
0.0-400.0 Hz *5.0 Hz 3-12 Catch up/slow Down Value
0.00-100.0% *0.00% 3-14 Preset Relative Reference
-100.0-100.0% *0.00% 3-15 Reference Resource 1 [0] No function *[1] Analog Input 53 [2] Analog input 60 [8] Pulse input 33 [11] Local bus ref [21] LCP Potentiometer 3-16 Reference Resource 2 [0] No function [1] Analog Input 53 *[2] Analog input 60 [8] Pulse input 33 *[11] Local bus ref [21] LCP Potentiometer 3-17 Reference Resource 3 [0] No function [1] Analog Input 53 [2] Analog input 60 [8] Pulse input 33 *[11] Local bus ref [21] LCP Potentiometer 3-18 Relative Scaling Ref. Resource *[0] No function [1] Analog Input 53 [2] Analog input 60 [8] Pulse input 33 [11] Local bus ref [21] LCP Potentiometer
3-4* Ramp 1
3-40 Ramp 1 Type *[0] Linear [2] Sine2 ramp 3-41 Ramp 1 Ramp up Time
0.05-3600 s *3.00 s (10.00 s1)) 3-42 Ramp 1 Ramp Down Time
0.05-3600 s *3.00 s (10.00 s 1))
3-5* Ramp 2
3-50 Ramp 2 Type *[0] Linear [2] Sine2 ramp 3-51 Ramp 2 Ramp up Time
0.05-3600 s *3.00 s (10.00 s 1)) 3-52 Ramp 2 Ramp down Time
0.05-3600 s *3.00 s (10.00 s1))
1)
M4
and M5 only
3-8* Other Ramps
3-80
Jog Ramp Time
0.05-3600 s *3.00 s (10.00 s1)) 3-81 Quick Stop Ramp Time
0.05-3600 s *3.00 s(10.00 s1))
4-** Limits/Warnings 4-1* Motor Limits
4-10 Motor Speed Direction [0] Clockwise if Par. 1-00 is set to [3] [1] CounterClockwise *[2] Both if Par. 1-00 is set to [0] 4-12 Motor Speed Low Limit [Hz]
0.0-400.0 Hz * 0.0 Hz 4-14 Motor Speed High Limit [Hz]
0.1-400.0 Hz *65.0 Hz 4-16 Torque Limit Motor Mode 0-400% *150% 4-17 Torque Limit Generator Mode 0-400% *100%
4-4* Adj. Warnings 2
4-40 Warning Frequency Low
0.00-Value of 4-41 Hz *0.0 Hz 4-41 Warning Frequency High Value of 4-40-400.0 Hz *400.0 Hz
4-5* Adj. Warnings
4-50 Warning Current Low
0.00-100.00 A *0.00 A 4-51 Warning Current High
0.00-100.00 A *100.00 A 4-54 Warning Reference Low
-4999.000-Value of 4-55 *-4999.000 4-55 Warning Reference High Value of 4-54-4999.000 *4999.000 4-56 Warning Feedback Low
-4999.000-Value of 4-57 *-4999.000 4-57 Warning Feedback High Value of 4-56-4999.000 *4999.000 4-58 Missing Motor Phase Function [0] Off *[1] On
4-6* Speed Bypass
4-61 Bypass Speed From [Hz]
0.0-400.0 Hz * 0.0 Hz 4-63 Bypass Speed To [Hz]
0.0-400.0 Hz * 0.0 Hz
5-1* Digital Inputs
5-10 Terminal 18 Digital Input [0] No function
[1] Reset [2]
Coast inverse [3] Coast and reset inv. [4] Quick stop inverse [5] DC-brake inv. [6] Stop inv *[8] Start [9] Latched start [10] Reversing [11] Start reversing [12] Enable start forward [13] Enable start reverse [14] Jog [16-18] Preset ref bit 0-2 [19] Freeze reference [20] Freeze output [21] Speed up [22] Speed down [23] Setup select bit 0 [28] Catch up [29] Slow down [34] Ramp bit 0 [60] Counter A (up) [61] Counter A (down) [62] Reset counter A [63] Counter B (up) [64] Counter B (down) [65] ResetCounter B 5-11 Terminal 19 Digital Input See par. 5-10. *[10] Reversing 5-12 Terminal 27 Digital Input See par. 5-10. * [1] Reset 5-13 Terminal 29 Digital Input See par. 5-10. * [14] Jog 5-15 Terminal 33 Digital Input See par. 5-10. * [16] Preset ref bit 0 [26] Precise Stop Inverse [27] Start, Precise Stop [32] Pulse Input
5-3* Digital Outputs
5-34 On Delay, Terminal 42 Digital Output
0.00-600.00 s *0.01 s 5-35 Off Delay, Terminal 42 Digital Output
0.00-600.00 s *0.01 s
5-4* Relays
5-40 Function Relay *[0] No operation [1] Control ready [2] Drive ready [3] Drive ready, Remote
[4] Enable/No warning [5] Drive running [6] Running/No warning [7] Run in range/No warning [8] Run on ref/No warning [9] Alarm [10] Alarm or warning [12] Out of current range [13] Below current, low [14] Above current, high [16] Below frequency, low [17] Above frequency, high [19] Below feedback, low [20] Above feedback, high [21] Thermal warning [22] Ready, No thermal warning [23] Remote ready, No thermal warning [24] Ready, Voltage ok [25] Reverse [26] Bus ok [28] Brake,NoWarn [29] Brake ready/NoFault [30] BrakeFault (IGBT) [32] Mech.brake control [36] Control word bit 11 [41] Below reference, low [42] Above reference, high [51] Local ref. active [52] Remote ref. active [53] No alarm [54] Start cmd active [55] Running reverse [56] Drive in hand mode [57] Drive in auto mode [60-63] Comparator 0-3 [70-73] Logic rule 0-3 [81] SL digital output B 5-41 On Delay, Relay
0.00-600.00 s *0.01 s 5-42 Off Delay, Relay
0.00-600.00 s *0.01 s
5-5* Pulse Input
5-55 Terminal 33 Low Frequency 20-4999 Hz * 20 Hz 5-56 Terminal 33 High Frequency 21-5000 Hz *5000 Hz 5-57 Term. 33 Low Ref./Feedb. Value
-4999-4999 *0.000 5-58 Term. 33 High Ref./Feedb. Value
-4999-4999 *50.000
6-** Analog In/Out
5 5
Table 5.2
MG02C602 - VLT® is a registered Danfoss trademark
51
Parameter Lists
VLT® Micro Drive FC 51 Programming Guide
6-0* Analog I/O Mode
Live Zero Timeout Time
6-00 1-99 s *10 s 6-01 Live Zero TimeoutFunction *[0] Off [1] Freeze output [2] Stop [3] Jogging [4] Max speed [5] Stop and trip
6-1* Analog Input 1
6-10 Terminal 53 Low Voltage
55
0.00-9.99 V *0.07 V 6-11 Terminal 53 High Voltage
0.01-10.00 V *10.00 V 6-12 Terminal 53 Low Current
0.00-19.99 mA *0.14 mA 6-13 Terminal 53 High Current
0.01-20.00 mA *20.00 mA 6-14 Term. 53 Low Ref./Feedb. Value
-4999-4999 *0.000 6-15 Term. 53 High Ref./Feedb. Value
-4999-4999 *50.000 6-16 Terminal 53 Filter Time Constant
0.01-10.00 s *0.01 s 6-19 Terminal 53 mode *[0] Voltage mode [1] Current mode
6-2* Analog Input 2
6-22 Terminal 60 Low Current
0.00-19.99 mA *0.14 mA 6-23 Terminal 60 High Current
0.01-20.00 mA *20.00 mA 6-24 Term. 60 Low Ref./Feedb. Value
-4999-4999 *0.000 6-25 Term. 60 High Ref./Feedb. Value
-4999-4999 *50.00 6-26 Terminal 60 Filter Time Constant
0.01-10.00 s *0.01 s
6-8* LCP potentiometer
6-80 LCP LCP Potmeter Enable [0] Disabled [1] * Enable 6-81 LCP potm. Low Reference
-4999-4999 *0.000 6-82 LCP potm. High Reference
-4999-4999 *50.00
6-9* Analog Output xx
6-90 Terminal 42 Mode *[0] 0-20 mA
[1] 4-20 mA [2] Digital Output 6-91 Terminal 42 Analog Output *[0] No operation [10] Output Frequency [11] Reference [12] Feedback [13] Motor Current [16] Power [20] Bus Reference 6-92 Terminal 42 Digital Output See par. 5-40 *[0] No Operation [80] SL Digital Output A 6-93 Terminal 42 Output Min Scale
0.00-200.0% *0.00% 6-94 Terminal 42 Output Max Scale
0.00-200.0% *100.0%
7-** Controllers 7-2* Process Ctrl. Feedb
7-20 Process CL Feedback 1 Resource *[0] NoFunction [1] Analog Input 53 [2] Analog input 60 [8] PulseInput33 [11] LocalBusRef
7-3* Process PI
Ctrl. 7-30 Process PI Normal/ Inverse Ctrl *[0] Normal [1] Inverse 7-31 Process PI Anti Windup [0] Disable *[1] Enable 7-32 Process PI Start Speed
0.0-200.0 Hz *0.0 Hz 7-33 Process PI Proportional Gain
0.00-10.00 *0.01 7-34 Process PI Integral Time
0.10-9999 s *9999 s 7-38 Process PI Feed Forward Factor 0-400% *0% 7-39 On Reference Bandwidth 0-200% *5%
8-** Comm. and Options 8-0* General Settings
8-01 Control Site *[0] Digital and ControlWord [1] Digital only [2] ControlWord only
8-02 Control Word Source [0] None *[1] FC RS485 8-03 Control Word Timeout Time
0.1-6500 s *1.0 s 8-04 Control Word Timeout Function *[0] Off [1] Freeze Output [2] Stop [3] Jogging [4] Max. Speed [5] Stop and trip 8-06 Reset Control Word Timeout *[0] No Function [1] Do reset
8-3* FC Port Settings
8-30 Protocol *[0] FC [2] Modbus 8-31 Address 1-247 *1 8-32 FC Port Baud Rate [0] 2400 Baud [1] 4800 Baud *[2] 9600 Baud For choosing FC bus in 8-30 * [3] 19200 Baud For choosing FC bus in 8-30 *[4] 38400 Baud 8-33 FC Port Parity *[0] Even Parity, 1 Stop Bit [1] Odd Parity, 1 Stop Bit [2] No Parity, 1 Stop Bit [3] No Parity, 2 Stop Bits 8-35 Minimum Response Delay
0.001-0.5 *0.010 s 8-36 Max Response Delay
0.100-10.00 s *5.000 s 8-4* FC MC protocol set 8-43 FC Port PCD Read Configu­ration *[0] None Expressionlimit [1] [1500] Operation Hours [2] [1501] Running Hours [3] [1502] kWh Counter [4] [1600] Control Word [5] [1601] Reference [Unit] [6] [1602] Reference % [7] [1603] Status Word [8] [1605] Main Actual Value [%] [9] [1609] Custom Readout [10] [1610] Power [kW] [11] [1611] Power [hp] [12] [1612] Motor Voltage
[13] [1613] Frequency [14] [1614] Motor Current [15] [1615] Frequency [%] [16] [1618] Motor Thermal [17] [1630] DC Link Voltage [18] [1634] Heatsink Temp. [19] [1635] Inverter Thermal [20] [1638] SL Controller State [21] [1650] External Reference [22] [1651] Pulse Reference [23] [1652] Feedback [Unit] [24] [1660] Digital Input 18,19,27,33 [25] [1661] Digtial Input 29 [26] [1662] Analog Input 53(V) [27] [1663] Analog Input 53(mA) [28] [1664] Analog Input 60 [29] [1665] Analog Output 42 [mA] [30] [1668] Freq. Input 33 [Hz] [31] [1671] Relay Output [bin] [32] [1672] Counter A [33] [1673] Counter[34] [1690] Alarm Word [34] [1690] Alarm Word [35] [1692] Warning Word [36] [1694] Ext. Status Word
8-5* Digital/Bus
8-50 Coasting Select [0] DigitalInput [1] Bus [2] LogicAnd *[3] LogicOr 8-51 Quick Stop Select See par. 8-50 * [3] LogicOr 8-52 DC Brake Select See par. 8-50 * [3] LogicOr 8-53 Start Select See par. 8-50 * [3] LogicOr 8-54 Reversing Select See par. 8-50 * [3] LogicOr 8-55 Set-up Select See par. 8-50 * [3] LogicOr 8-56 Preset Reference Select See par. 8-50 * [3] LogicOr
8-8X Bus communication Diagnostics
8-80 Bus Message Count 0-0 N/A *0 N/A 8-81 Bus Error Count 0-0 N/A *0 N/A 8-82 Slave Messages Rcvd 0-0 N/A *0 N/A 8-83 Slave Error Count 0-0 N/A *0 N/A
Table 5.3
52 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Lists
VLT® Micro Drive FC 51 Programming Guide
8-9* Bus Jog / Feedback
Bus feedback 1
8-94 0x8000-0x7FFF *0
13-** Smart Logic 13-0* SLC Settings
13-00 SL Controller Mode *[0] Off [1] On 13-01 Start Event [0] False [1] True [2] Running [3] InRange [4] OnReference [7] OutOfCurrentRange [8] BelowILow [9] AboveIHigh [16] ThermalWarning [17] MainOutOfRange [18] Reversing [19] Warning [20] Alarm_Trip [21] Alarm_TripLock [22-25] Comparator 0-3 [26-29] LogicRule0-3 [33] DigitalInput_18 [34] DigitalInput_19 [35] DigitalInput_27 [36] DigitalInput_29 [38] DigitalInput_33 *[39] StartCommand [40] DriveStopped 13-02 Stop Event See par. 13-01 * [40] DriveS­topped 13-03 Reset SLC *[0] Do not reset [1] Reset SLC
13-1* Comparators
13-10 Comparator Operand *[0] Disabled [1] Reference [2] Feedback [3] MotorSpeed [4] MotorCurrent [6] MotorPower [7] MotorVoltage [8] DCLinkVoltage [12] AnalogInput53 [13] AnalogInput60 [18] PulseInput33 [20] AlarmNumber [30] CounterA [31] CounterB 13-11 Comparator Operator [0] Less Than
*[1] Approximately equals [2] Greater Than 13-12 Comparator Value
-9999-9999 *0.0
13-2* Timers
13-20 SL Controller Timer
0.0-3600 s *0.0 s
13-4* Logic Rules
13-40 Logic Rule Boolean 1 See par. 13-01 * [0] False [30]-[32] SL Time-out 0-2 13-41 Logic Rule Operator 1 *[0] Disabled [1] And [2] Or [3] And not [4] Or not [5] Not and [6] Not or [7] Not and not [8] Not or not 13-42 Logic Rule Boolean 2 See par. 13-40 13-43 Logic Rule Operator 2 See par. 13-41 * [0] Disabled 13-44 Logic Rule Boolean 3 See par. 13-40
13-5* States
13-51 SL Controller Event See par. 13-40 13-52 SL Controller Action *[0] Disabled [1] NoAction [2] SelectSetup1 [3] SelectSetup2 [10-17] SelectPresetRef0-7 [18] SelectRamp1 [19] SelectRamp2 [22] Run [23] RunReverse [24] Stop [25] Qstop [26] DCstop [27] Coast [28] FreezeOutput [29] StartTimer0 [30] StartTimer1 [31] StartTimer2 et Digital Output B High [32] Set Digital Output A Low [33] Set Digital Output B Low [38] Set Digital Output A High [39] Set Digital Output B High [60] ResetCounterA [61] ResetCounterB
14-** Special Functions 14-0*Inverter Switching
14-01 Switching Frequency [0] 2 kHz *[1] 4 kHz [2] 8 kHz [4] 16 kHz not available for M5 14-03 Overmodulation [0] Off *[1] On
14-1* Mains monitoring
14-12 Function at mains imbalance *[0] Trip [1] Warning [2] Disabled
14-2* Trip Reset
14-20 Reset Mode *[0] Manual reset [1-9] AutoReset 1-9 [10] AutoReset 10 [11] AutoReset 15 [12] AutoReset 20 [13] Infinite auto reset [14] Reset at power up 14-21 Automatic Restart Time 0-600 s * 10 s 14-22 Operation Mode *[0] Normal Operation [2] Initialisation 14-26 Action At Inverter Fault *[0] Trip [1] Warning
14-4* Energy Optimising
14-41 AEO Minimum Magneti­sation 40-75% *66%
15-** Drive Information 15-0* Operating Data
15-00 Operating Days 15-01 Running Hours 15-02 kWh Counter 15-03 Power Ups 15-04 Over Temps 15-05 Over Volts 15-06 Reset kWh Counter *[0] Do not reset [1] Reset counter 15-07 Reset Running Hours Counter *[0] Do not reset [1] Reset counter
15-3* Fault Log
15-30 Fault Log: Error Code
15-4* Drive Identification
15-40 FC Type
15-41 Power Section 15-42 Voltage 15-43 Software Version 15-46 Frequency Converter Order. No 15-48 LCP Id No 15-51 Frequency Converter Serial No
16-** Data Readouts 16-0* General Status
16-00 Control Word 0-0XFFFF 16-01 Reference [Unit]
-4999-4999 16-02 Reference %
-200.0-200.0 % 16-03 Status Word 0-0XFFFF 16-05 Main Actual Value [%]
-200.0-200.0 % 16-09 Custom Readout Dep. on par. 0-31, 0-32 and 4-14
16-1* Motor Status
16-10 Power [kW] 16-11 Power [hp] 16-12 Motor Voltage [V] 16-13 Frequency [Hz] 16-14 Motor Current [A] 16-15 Frequency [%] 16-18 Motor Thermal [%]
16-3* Drive Status
16-30 DC Link Voltage 16-34 Heatsink Temp. 16-35 Inverter Thermal 16-36 Inv.Nom. Current 16-37 Inv. Max. Current 16-38 SL Controller State
16-5* Ref. / Feedb.
16-50 External Reference 16-51 Pulse Reference 16-52 Feedback [Unit]
16-6* Inputs/Outputs
16-60 Digital Input 18,19,27,33 0-1111 16-61 Digital Input 29 0-1 16-62 Analog Input 53 (volt) 16-63 Analog Input 53 (current) 16-64 Analog Input 60 16-65 Analog Output 42 [mA]16-68 Pulse Input [Hz] 16-71 Relay Output [bin] 16-72 Counter A 16-73 Counter B
16-8* Fieldbus/FC Port
16-86 FC Port REF 1 0x8000-0x7FFFF
5 5
Table 5.4
MG02C602 - VLT® is a registered Danfoss trademark
53
Parameter Lists
VLT® Micro Drive FC 51 Programming Guide
16-9* Diagnosis Readouts
Alarm Word
16-90 0-0XFFFFFFFF
Table 5.5
5.1.1 Conversion Index
16-92 Warning Word 0-0XFFFFFFFF 16-94 Ext. Status Word 0-0XFFFFFFFF
18-** Extended Motor Data 18-8* Motor Resistors
18-80 Stator Resistance (High resolution)
0.000-99.990 ohm *0.000 ohm
1-24 Motor Current
has
18-81 Stator Leakage Reactance (High resolution)
0.000-99.990 ohm *0.000 ohm
a conversion index of -2 (i.e.
conversion factor of 0.01 according to Table 5.6). To set the
The various attributes of each parameter are displayed in
section Factory Settings. Parameter values are
the
55
transferred as whole numbers only. Conversion factors are therefore used to transfer decimals according to Table 5.6.
parameter to 2.25 A, transfer the value 225 via Modbus.
The Conversion Factor of 0.01 means that the value
transferred is multiplied by 0.01 in the frequency converter.
The vale 225 transferred on the bus is thus perceived as
2.25 A in the frequency converter.
Example:
Conversion index Conversion factor 2 10 1 100 0 1
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
-5 0.00001
Table 5.6 Conversion Table
5.1.2 Change during operation
“TRUE” means that the parameter can be changed while
frequency converter is in operation and “FALSE” means
the that the frequency converter must be stopped before a change can be made.
5.1.3 2-Set-up
“All set-up”: The parameter can be set individually in each
of the two set-ups, i.e. one single parameter can have two
different data values.
”1 set-up”: Data value will be the same in both set-ups.
5.1.4 Type
Data Type Description Type 2 Integer 8 Int8 3 Integer 16 Int16 4 Integer 32 Int32 5 Unsigned 8 Uint8 6 Unsigned 16 Uint16 7 Unsigned 32 Uint32 9 Visible string VisibleString
Table 5.7
54 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Lists
5.1.5 0-** Operation/Display
VLT® Micro Drive FC 51 Programming Guide
Parameter
Number
0-03 Regional Settings [0] International 1 set-up FALSE - Uint8
0-04 0-10 Active Set-up [1] Set-up 1 1 set-up TRUE - Uint8 0-11 Edit Set-up [1] Set-up 1 1 set-up TRUE - Uint8 0-12 Link Setups [20] Linked All set-ups FALSE - Uint8 0-31 Custom Readout Min Scale 0 1 set-up TRUE -2 Int32 0-32 Custom Readout Max Scale 0 1 set-up TRUE -2 Int32 0-40 [Hand On] Key on LCP [1] Enabled All set-ups TRUE - Uint8 0-41 [Off / Reset] Key on LCP [1] Enable All All set-ups TRUE - Uint8 0-42 [Auto on] Key on LCP [1] Enabled All set-ups TRUE - Uint8 0-50 LCP Copy [0] No copy 1 set-up FALSE - Uint8 0-51 Set-up Copy [0] No copy 1 set-up FALSE - Uint8 0-60 Main Menu Password 0 1 set-up TRUE 0 Uint16
0-61
Table 5.8
Parameter Description Default Value 2 Setup
Operating State at Power-up (Hand) [1] Forced stop ref=old All set-ups TRUE - Uint8
Access to Main/Quick menu w/o Password 0 1 set-up TRUE - Uint8
Change During
Operation
Conversi
Index
on
Type
5 5
MG02C602 - VLT® is a registered Danfoss trademark
55
Parameter Lists
5.1.6 1-** Load/Motor
VLT® Micro Drive FC 51 Programming Guide
Parameter
Number 1-00 Configuration Mode [0] Speed open loop All set-ups TRUE - Uint8 1-01 Motor Control Principle [1] VVC+ All set-ups FALSE - Uint8 1-03 Torque Characteristics [0] Constant torque All set-ups TRUE - Uint8
1-05 Hand Mode Configuration 1-20 Motor Power All set-ups FALSE - Uint8 1-22 Motor Voltage All set-ups FALSE 0 Uint16
55
1-23 Motor Frequency All set-ups FALSE 0 Uint16 1-24 Motor Current All set-ups FALSE -2 Uint16 1-25 Motor Nominal Speed All set-ups FALSE 0 Uint16 1-29 Automatic Motor Tuning (AMT) [0] Off 1 set-up FALSE - Uint8 1-30 Stator Resistance (Rs) All set-ups FALSE -2 Uint16 1-33 Stator Leakage Reactance (X1) All set-ups FALSE -2 Uint32 1-35 Main Reactance (Xh) All set-ups FALSE -2 Uint32
1-50
1-52 1-55 U/f Characteristic-U All set-ups TRUE 0 Uint16 1-56 U/f Characteristic-F All set-ups TRUE 0 Uint16 1-60 Low Speed Load Compensation 100% All set-ups TRUE 0 Uint16 1-61 High Speed Load Compensation 100% All set-ups TRUE 0 Uint16 1-62 Slip Compensation 100% All set-ups TRUE 0 Int16
1-63 1-71 Start Delay 0 s All set-ups TRUE -1 Uint8 1-72 Start Function [2] Coast/delay time All set-ups TRUE - Uint8 1-73 Flying Start [0] Disabled All set-ups FALSE - Uint8 1-80 Function at Stop [0] Coast All set-ups TRUE - Uint8
1-82 1-90 Motor Thermal Protection [0] No protection All set-ups TRUE - Uint8 1-93 Thermistor Resource [0] None All set-ups FALSE - Uint8
Parameter Description Default Value 2 Setup
Configuration
Mode
All set-ups TRUE - Uint8
[2] As mode 1-00
Motor Magnetisation at Zero Speed 100% All set-ups TRUE 0 Uint16 Min Speed Normal Magnetising [Hz] 0 Hz All set-ups TRUE -1 Uint16
Slip Compensation Time Constant 0.1 s All set-ups TRUE -2 Uint16
Min Speed for Function at Stop [Hz] 0 Hz All set-ups TRUE -1 Uint16
Change During
Operation
Conversi
Index
on
Type
Table 5.9
56 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Lists
5.1.7 2-** Brakes
VLT® Micro Drive FC 51 Programming Guide
Parameter
Number 2-00 DC Hold Current 50% All set-ups TRUE 0 Uint16 2-01 DC Brake Current 50% All set-ups TRUE 0 Uint16 2-02 DC Braking Time 10 s All set-ups TRUE -1 Uint16 2-04 DC Brake Cut In Speed 0 Hz All set-ups TRUE -1 Uint16 2-10 Brake Function [0] Off All set-ups TRUE - Uint8 2-11 Brake Resistor (Ω) All set-ups TRUE 0 Uint16 2-16 AC Brake, Max current 100% All set-ups TRUE 0 Uint16 2-17 Over-voltage Control [0] Disabled All set-ups TRUE - Uint8 2-20 Release Brake Current 0 A All set-ups TRUE -2 Uint32 2-22 Activate Brake Speed [Hz] 0 Hz All set-ups TRUE -1 Uint16
Table 5.10
Parameter Description Default Value 2 Setup
Change During
Operation
Conversi
Index
on
Type
5.1.8 3-** Reference/Ramps
Parameter
Number 3-00 Reference Range [0] Min to Max All set-ups TRUE - Uint8 3-02 Minimum Reference 0 All set-ups TRUE -3 Int32 3-03 Maximum Reference 50 All set-ups TRUE -3 Int32 3-10 Preset Reference 0% All set-ups TRUE -2 Int16 3-11 Jog Speed [Hz] 5 Hz All set-ups TRUE -1 Uint16 3-12 Catch up/slow Down Value 0% All set-ups TRUE -2 Int16 3-14 Preset Relative Reference 0% All set-ups TRUE -2 Int16 3-15 Reference Resource 1 [1] Analog in 53 All set-ups TRUE - Uint8 3-16 Reference Resource 2 [2] Analog in 60 All set-ups TRUE - Uint8 3-17 Reference Resource 3 [11] Local bus reference All set-ups TRUE - Uint8
3-18 3-40 Ramp 1 Type [0] Linear All set-ups TRUE - Uint8 3-41 Ramp 1 Ramp up Time 3 s All set-ups TRUE -2 Uint32 3-42 Ramp 1 Ramp Down Time 3 s All set-ups TRUE -2 Uint32 3-50 Ramp 2 Type [0] Linear All set-ups TRUE - Uint8 3-51 Ramp 2 Ramp up Time 3 s All set-ups TRUE -2 Uint32 3-52 Ramp 2 Ramp down Time 3 s All set-ups TRUE -2 Uint32 3-80 Jog Ramp Time 3 s All set-ups TRUE -2 Uint32 3-81 Quick Stop Ramp Time 3 s 1 set-up TRUE -2 Uint32
Parameter Description Default Value 2 Setup
Relative Scaling Reference Resource [0] No function All set-ups TRUE - Uint8
Change During
Operation
Conversi on
Index
Type
5 5
Table 5.11
MG02C602 - VLT® is a registered Danfoss trademark
57
Parameter Lists
5.1.9 4-** Limits/Warnings
VLT® Micro Drive FC 51 Programming Guide
Parameter
Number 4-10 Motor Speed Direction [2] Both directions All set-ups FALSE - Uint8 4-12 Motor Speed Low Limit [Hz] 0 Hz All set-ups FALSE -1 Uint16 4-14 Motor Speed High Limit [Hz] 65 Hz All set-ups FALSE -1 Uint16 4-16 Torque Limit Motor Mode 150% All set-ups TRUE 0 Uint16 4-17 Torque Limit Generator Mode 100% All set-ups TRUE 0 Uint16 4-40 Warning Frequency Low 0Hz All set-ups TRUE -1 Uint16 4-41 Warning Frequency High 400Hz All set-ups TRUE -1 Uint16
55
4-50 Warning Current Low 0 A All set-ups TRUE -2 Uint32 4-51 Warning Current High 26 A All set-ups TRUE -2 Uint32 4-54 Warning Reference Low -4999 All set-ups TRUE -3 Int32 4-55 Warning Reference High 4999 All set-ups TRUE -3 Int32 4-56 Warning Feedback Low -4999 All set-ups TRUE -3 Int32 4-57 Warning Feedback High 4999 All set-ups TRUE -3 Int32 4-58 Missing Motor Phase Function [1] On All set-ups FALSE - Uint8 4-61 Bypass Speed From [Hz] 0 Hz All set-ups TRUE -1 Uint16 4-63 Bypass Speed To [Hz] 0 Hz All set-ups TRUE -1 Uint16
Table 5.12
Parameter Description Default Value 2 Setup
Change During
Operation
Conversi
Index
on
Type
5.1.10 5-** Digital In/Out
Parameter
Number
5-10 Terminal 18 Digital Input [8] Start All set-ups TRUE - Uint8 5-11 Terminal 19 Digital Input [10] Reversing All set-ups TRUE - Uint8 5-12 Terminal 27 Digital Input [1] Reset All set-ups TRUE - Uint8 5-13 Terminal 29 Digital Input [14] Jog All set-ups TRUE - Uint8 5-15 Terminal 33 Digital Input [16] Preset ref bit 0 All set-ups TRUE - Uint8 5-34 On Delay, Terminal 42 Digital Output 0.01s All set-ups TRUE -2- Uint16 5-35 Off Delay, Terminal 42 Digital Output 0.01s All set-ups TRUE -2 Uint16 5-40 Function Relay [0] No operation All set-ups TRUE - Uint8 5-41 On Delay, Relay 0.01s All set-ups TRUE -2 Uint16 5-42 Off Delay, Relay 0.01s All set-ups TRUE -2 Uint16 5-55 Terminal 33 Low Frequency 20 Hz All set-ups TRUE 0 Uint16 5-56 Terminal 33 High Frequency 5000 Hz All set-ups TRUE 0 Uint16 5-57 Terminal 33 Low Ref./Feedb. Value 0 All set-ups TRUE -3 Int32 5-58 Terminal 33 High Ref./Feedb. Value 50 All set-ups TRUE -3 Int32
Parameter Description Default Value 2 Setup
Change During
Operation
Conversi
on
Index
Type
Table 5.13
58 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Lists
5.1.11 6-** Analog In/Out
VLT® Micro Drive FC 51 Programming Guide
Parameter
Number 6-00 Live Zero Timeout Time 10 s All set-ups TRUE 0 Uint8 6-01 Live Zero TimeoutFunction [0] Off All set-ups TRUE - Uint8 6-10 Terminal 53 Low Voltage 0.07 V All set-ups TRUE -2 Uint16 6-11 Terminal 53 High Voltage 10 V All set-ups TRUE -2 Uint16 6-12 Terminal 53 Low Current 0.14 mA All set-ups TRUE -2 Uint16 6-13 Terminal 53 High Current 20 mA All set-ups TRUE -2 Uint16
6-14
6-15 6-16 Terminal 53 Filter Time Constant 0.01 s All set-ups TRUE -2 Uint16 6-19 Terminal 53 mode [0] Voltage mode 1 set-up TRUE - Uint8 6-22 Terminal 60 Low Current 0.14 mA All set-ups TRUE -2 Uint16 6-23 Terminal 60 High Current 20 mA All set-ups TRUE -2 Uint16
6-24
6-25 6-26 Terminal 60 Filter Time Constant 0.01 s All set-ups TRUE -2 Uint16 6-80 LCP Potmeter Enable 1 1 set-up FALSE - Uint8 6-81 LCP potentiometer Low Ref. 0 All set-ups TRUE -3 Int32 6-82 LCP potentiometer High Ref. 50 All set-ups TRUE -3 Int32 6-90 Terminal 42 Mode [0] 0-20 mA All set-ups TRUE - Uint8 6-91 Terminal 42 Analog Output [0] No operation All set-ups TRUE - Uint8 6-92 Terminal 42 Digital Output [0] No operation All set-ups TRUE - Uint8 6-93 Terminal 42 Output Min Scale 0% All set-ups TRUE -2 Uint16 6-94 Terminal 42 Output Max Scale 100% All set-ups TRUE -2 Uint16
Parameter Description Default Value 2 Setup
Terminal 53 Low Ref./Feedb. Value 0 All set-ups TRUE -3 Int32 Terminal 53 High Ref./Feedb. Value 50 All set-ups TRUE -3 Int32
Terminal 60 Low Ref./Feedb. Value 0 All set-ups TRUE -3 Int32 Terminal 60 High Ref./Feedb. Value 50 All set-ups TRUE -3 Int32
Change During
Operation
Conversi
Index
on
Type
5 5
Table 5.14
5.1.12 7-** Controllers
Parameter
Number 7-20 Process CL Feedback 1 Resource [0] No function All set-ups TRUE - Uint8
7-30 7-31 Process PI Anti Windup [1] Enabled All set-ups TRUE - Uint8 7-32 Process PI Start Speed 0 Hz All set-ups TRUE -1 Uint16 7-33 Process PI Proportional Gain 0.01 All set-ups TRUE -2 Uint16 7-34 Process PI Integral Time 9999 s All set-ups TRUE -2 Uint32 7-38 Process PI Feed Forward Factor 0% All set-ups TRUE 0 Uint16 7-39 On Reference Bandwidth 5% All set-ups TRUE 0 Uint8
Table 5.15
Parameter Description Default Value 2 Setup
Process PI Normal/ Inverse Control [0] Normal All set-ups TRUE - Uint8
Change During
Operation
Conversi on
Index
Type
MG02C602 - VLT® is a registered Danfoss trademark
59
Parameter Lists
5.1.13 8-** Comm. and Options
VLT® Micro Drive FC 51 Programming Guide
Parameter
Number 8-01 Control Site [0] Digital and ctrl.word All set-ups TRUE - Uint8 8-02 Control Word Source [1] FC RS485 All set-ups TRUE - Uint8 8-03 Control Word Timeout Time 1 s 1 set-up TRUE -1 Uint16 8-04 Control Word Timeout Function [0] Off 1 set-up TRUE - Uint8 8-06 Reset Control Word Timeout [0] No function 1 set-up TRUE - Uint8 8-30 Protocol [0] FC 1 set-up TRUE 0 Uint8 8-31 Address 1 1 set-up TRUE 0 Uint8
55
8-32 FC Port Baud Rate [2] 9600 Baud 1 set-up TRUE - Uint8 8-33 FC Port Parity [0] Even Parity 1 Stop Bit 1 set-up TRUE - Uint8 8-35 Minimum Response Delay 0.01 s 1 set-up TRUE -3 Uint16 8-36 Max Response Delay 5 s 1 set-up TRUE -3 Uint16 8-43 FC Port PCD Read Configuration 0 1 set-up TRUE - Uint8 8-50 Coasting Select [3] Logic OR All set-ups TRUE - Uint8 8-51 Quick Stop Select [3] Logic OR All set-ups TRUE - Uint8 8-52 DC Brake Select [3] Logic OR All set-ups TRUE - Uint8 8-53 Start Select [3] Logic OR All set-ups TRUE - Uint8 8-54 Reversing Select [3] Logic OR All set-ups TRUE - Uint8 8-55 Set-up Select [3] Logic OR All set-ups TRUE - Uint8 8-56 Preset Reference Select [3] Logic OR All set-ups TRUE - Uint8 8-94 Bus feedback 1 0 All set-ups TRUE 0 Int16
Table 5.16
Parameter Description Default Value 2 Setup
Change During
Operation
Conversi
Index
on
Type
5.1.14 13-** Smart Logic
Parameter
Number 13-00 SL Controller Mode [0] Off 1 set-up TRUE - Uint8 13-01 Start Event [39] Start command 1 set-up TRUE - Uint8 13-02 Stop Event [40] Drive stopped 1 set-up TRUE - Uint8 13-03 Reset SLC [0] Do not reset 1 set-up TRUE - Uint8 13-10 Comparator Operand [0] Disabled 1 set-up TRUE - Uint8 13-11 Comparator Operator [1] ApproxEqual 1 set-up TRUE - Uint8 13-12 Comparator Value 0 1 set-up TRUE -1 Int32 13-20 SL Controller Timer 0 s 1 set-up TRUE -1 Uint32 13-40 Logic Rule Boolean 1 [0] False 1 set-up TRUE - Uint8 13-41 Logic Rule Operator 1 [0] Disabled 1 set-up TRUE - Uint8 13-42 Logic Rule Boolean 2 [0] False 1 set-up TRUE - Uint8 13-43 Logic Rule Operator 2 [0] Disabled 1 set-up TRUE - Uint8 13-44 Logic Rule Boolean 3 [0] False 1 set-up TRUE - Uint8 13-51 SL Controller Event [0] False 1 set-up TRUE - Uint8 13-52 SL Controller Action [0] Disabled 1 set-up TRUE - Uint8
Table 5.17
Parameter Description Default Value 2 Setup
Change During
Operation
Conversi on
Index
Type
60 MG02C602 - VLT® is a registered Danfoss trademark
Parameter Lists
5.1.15 14-** Special Functions
VLT® Micro Drive FC 51 Programming Guide
Parameter
Number 14-01 Switching Frequency [1] 4.0 kHz All set-ups TRUE - Uint8 14-03 Overmodulation [1] On All set-ups FALSE - Uint8 14-12 Function at Mains Imbalance [0] Trip All set-ups TRUE - Uint8 14-20 Reset Mode [0] Manual reset All set-ups TRUE - Uint8 14-21 Automatic Restart Time 10 s All set-ups TRUE 0 Uint16 14-22 Operation Mode [0] Normal operation 1 set-up TRUE - Uint8 14-26 Action At Inverter Fault [0] Trip All set-ups TRUE - Uint8 14-41 AEO Minimum Magnetisation 66 % All set-ups TRUE 0 Uint8
Table 5.18
Parameter Description Default Value 2 Setup
Change During
Operation
Conversi
Index
on
Type
5.1.16 15-** Drive Information
Parameter
Number
15-00 Operating Time 0 1 set-up TRUE 0 Uint32 15-01 Running Hours 0 1 set-up TRUE 0 Uint32 15-02 kWh Counter 0 1 set-up TRUE 0 Uint32 15-03 Power Up's 0 1 set-up TRUE 0 Uint32 15-04 Over Temp's 0 1 set-up TRUE 0 Uint16 15-05 Over Volt's 0 1 set-up TRUE 0 Uint16 15-06 Reset kWh Counter [0] Do not reset 1 set-up TRUE - Uint8 15-07 Reset Running Hours Counter [0] Do not reset 1 set-up TRUE - Uint8 15-30 Fault Log: Error Code 0 1 set-up TRUE 0 Uint8 15-40 FC Type 1 set-up FALSE 0 VisibleString 15-41 Power Section 1 set-up FALSE 0 VisibleString 15-42 Voltage 1 set-up FALSE 0 VisibleString 15-43 SW ID Control Card 1 set-up FALSE 0 VisibleString
15-46 15-48 LCP Id No 1 set-up FALSE 0 VisibleString
15-51
Parameter Description Default Value 2 Setup
Frequency Converter Ordering No 1 set-up FALSE 0 VisibleString
Frequency Converter Serial Number 1 set-up FALSE 0 VisibleString
Change During
Operation
Conver
sion
Index
Type
5 5
Table 5.19
MG02C602 - VLT® is a registered Danfoss trademark
61
Parameter Lists
5.1.17 16-** Data Readouts
VLT® Micro Drive FC 51 Programming Guide
Parameter
Number 16-00 Control Word 0 1 set-up TRUE 0 Uint16 16-01 Reference [Unit] 0 1 set-up TRUE -3 Int32 16-02 Reference % 0 1 set-up TRUE -1 Int16 16-03 Status Word 0 1 set-up TRUE 0 Uint16 16-05 Main Actual Value [%] 0 1 set-up TRUE -2 Int16 16-09 Custom Readout 0 1 set-up TRUE -2 Int32 16-10 Power [kW] 0 1 set-up TRUE -3 Uint16
55
16-11 Power [hp] 0 1 set-up TRUE -3 Uint16 16-12 Motor Voltage 0 1 set-up TRUE 0 Uint16 16-13 Frequency 0 1 set-up TRUE -1 Uint16 16-14 Motor Current 0 1 set-up TRUE -2 Uint16 16-15 Frequency [%] 0 1 set-up TRUE -1 Uint16 16-18 Motor Thermal 0 1 set-up TRUE 0 Uint8 16-30 DC Link Voltage 0 1 set-up TRUE 0 Uint16 16-34 Heatsink Temp. 0 1 set-up TRUE 0 Uint8 16-35 Inverter Thermal 0 1 set-up TRUE 0 Uint8 16-36 Inv. Nom. Current 0 1 set-up TRUE -2 Uint16 16-37 Inv. Max. Current 0 1 set-up TRUE -2 Uint16 16-38 SL Controller State 0 1 set-up TRUE 0 Uint8 16-50 External Reference 0 1 set-up TRUE -1 Int16 16-51 Pulse Reference 0 1 set-up TRUE -1 Int16 16-52 Feedback [Unit] 0 1 set-up TRUE -3 Int32 16-60 Digital input 18,19,27,33 0 1 set-up TRUE 0 Uint16 16-61 Digital input 29 0 1 set-up TRUE 0 Uint8
16-62 Analog Input 53 (V) 0 1 set-up TRUE -2 Uint16 16-63 Analog Input 53 (mA) 0 1 set-up TRUE -2 Uint16 16-64 Analog Input 60 0 1 set-up TRUE -2 Uint16 16-65 Analog Output 42 [mA] 0 1 set-up TRUE -2 Uint16 16-68 Pulse input 33 20 1 set-up TRUE 0 Uint16 16-71 Relay Output [bin] 0 1 set-up TRUE 0 Uint8 16-72 Counter A 0 1 set-up TRUE 0 Int16 16-73 Counter B 0 1 set-up TRUE 0 Int16 16-86 FC Port REF 1 0 1 set-up TRUE 0 Int16 16-90 Alarm Word 0 1 set-up TRUE 0 Uint32 16-92 Warning Word 0 1 set-up TRUE 0 Uint32 16-94 Ext. Status Word 0 1 set-up TRUE 0 Uint32
Parameter Description Default Value 2 Setup
Change During
Operation
Conversi
Index
on
Type
Table 5.20
62 MG02C602 - VLT® is a registered Danfoss trademark
Troubleshooting
6 Troubleshooting
VLT® Micro Drive FC 51 Programming Guide
A warning or an alarm is signalled by the relevant LED on
front of the frequency converter and indicated by a
the code on the display.
A warning remains active until its cause is no longer present. Under certain circumstances operation of the motor may still be continued. Warning messages may be critical, but are not necessarily so.
In the event of an alarm, the frequency converter will have tripped. Alarms must be reset to restart operation once their cause has been rectified.
This may be done in four ways:
1. By pressing [Reset].
2. Via a digital input with the “Reset” function.
3. Via serial communication.
NOTE
After
a manual reset press [Reset], [Auto On] or [Hand On]
to restart the motor.
If an alarm cannot be reset, the reason may be that its
has not been rectified, or the alarm is trip-locked
cause (see also Table 6.1).
CAUTION
Alarms that are trip-locked offer additional protection, means
that the mains supply must be switched off before the alarm can be reset. After being switched back on, the frequency converter is no longer blocked and may be reset as described above once the cause has been rectified. Alarms that are not trip-locked can also be reset using the automatic reset function in 14-20 Reset Mode (Warning: automatic wake-up is possible!) If a warning and alarm is marked against a code in the Table 6.1, this means that either a warning occurs before an alarm, or it can be specified whether it is a warning or an alarm that is to be displayed for a given fault. This is possible, for instance, in 1-90 Motor Thermal Protection. After an alarm or trip, the motor carries on coasting, and the alarm and warning flash on the frequency converter. Once the problem has been rectified, only the alarm continues flashing.
6 6
No. Description Warning Alarm Trip Lock Error Parameter
Reference
2 Live zero error (X) (X) 6-01 4 Mains phase loss (X) (X) (X) 14-12 7 DC over voltage X X 8 DC under voltage X X 9 Inverter overloaded X X 10 Motor ETR over temperature (X) (X) 1-90 11 Motor thermistor over temperature (X) (X) 1-90 12 Torque limit (X) 4-16, 4-17 13 Over Current X X X 14 Earth fault X X X 16 Short Circuit X X 17 Control word timeout (X) (X) 8-04 25 Brake resistor short-circuited X X 27 Brake chopper short-circuited X X 28 Brake Check X 29 Power board over temp X X 30 Motor phase U missing (X) (X) 4-58 31 Motor phase V missing (X) (X) 4-58 32 Motor phase W missing (X) (X) 4-58 38 Internal fault X X 44 Earth fault 2 X X 47 Control Voltage Fault X X
MG02C602 - VLT® is a registered Danfoss trademark
63
Troubleshooting
VLT® Micro Drive FC 51 Programming Guide
No. Description Warning Alarm Trip Lock Error Parameter
Reference
and
51 AMT check U 52 AMT low I 53 AMT motor too big X 54 AMT motor too small X 55 AMT Parameter out of range X 59 Current limit X 63 Mechanical Brake Low X 80 Drive Initialized to Default Value X 84 The connection between drive and LCP is lost X 85 Button disabled X 86 Copy fail X 87 LCP data invalid X
66
88 LCP data not compatible X 89 Parameter read only X 90 Parameter database busy X 91 Parameter value is not valid in this mode X 92 Parameter value exceeds the min/max limits X
nom
nom
I
nom
X X
Table 6.1 Alarm/Warning Code List
(X) Dependent on parameter
trip is the action when an alarm has appeared. The trip
A will coast the motor and can be reset by pressing [Reset] or make a reset by a digital input (parameter group 5-1* [1]). The original event that caused an alarm cannot damage the frequency converter or cause dangerous conditions. A trip lock is an action when an alarm occurs, which may cause damage to frequency converter or connected parts. A trip lock situation can only be reset by a power cycling.
LED indication
Warning yellow
Alarm flashing red
Table 6.2
The
alarm words, warning words and extended status
words can be read out via serial bus or optional fieldbus for diagnosis. See also 16-90 Alarm Word, 16-92 Warning Word and 16-94 Ext. Status Word.
64 MG02C602 - VLT® is a registered Danfoss trademark
Troubleshooting
VLT® Micro Drive FC 51 Programming Guide
6.1.1 Alarm, Warning and Extended Status Word
Par. 16-90 Par. 16-92 Par. 16-94
Bit Hex Dec AlarmWord WarningWord ExtendedStatusWord
0 1 1 Brake check Ramping 1 2 2 Pwr.card temp Pwr.card temp AMT running 2 4 4 Earth Fault Start CW/CCW 3 8 8 Slow down 4 10 16 Ctrl.word TO Ctrl.word TO Catch up 5 20 32 Over Current Over Current Above Feedback High 6 40 64 Torque limit Below Feedback Low 7 80 128 Motor th over Motor th over Output current high 8 100 256 Motor ETR over Motor ETR over Output current low
9 200 512 Inverter overload Inverter overload Above Frequency High 10 400 1024 DC under volt DC under volt Below Frequency Low 11 800 2048 DC over volt DC over volt 12 1000 4096 Short Circuit 13 2000 8192 Braking 14 4000 16384 Mains ph. loss Mains ph. loss 15 8000 32768 "AMT Not OK" OVC active 16 10000 65536 Live zero error Live zero error AC brake 17 20000 131072 Internal fault 18 40000 262144 19 80000 524288 U phase loss Above Reference High 20 100000 1048576 V phase loss Below Reference Low 21 200000 2097152 W phase loss Local Ref./Remote Ref. 22 400000 4194304 23 800000 8388608 Control Voltage Fault 24 1000000 16777216 25 2000000 33554432 Current limit 26 4000000 67108864 Brake resistor short-circuit 27 8000000 134217728 Brake IGBT short-circuit 28 10000000 268435456 M4/M5: Earth Fault (Desat) MotorPhaseMissing 29 20000000 536870912 Drive initialised 30 40000000 1073741824 Undefined 31 80000000 2147483648 Mech. brake low DatabaseBusy
6 6
Table 6.3
The alarm words, warning words and extended staus
can be read out via serial bus for diagnose. See also
words 16-94 Ext. Status Word.
WARNING/ALARM 2, Live zero error Signal on terminal 53 or 60 is less than 50% of value set in 6-10 Terminal 53 Low Voltage, 6-12 Terminal 53 Low Current and 6-22 Terminal 60 Low Current.
WARNING/ALARM 4, Mains phase loss A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectifier on the frequency converter.
Troubleshooting: Check the supply voltage and supply currents to the frequency converter. The fault may be caused by mains distortions. Installing Danfoss Line Filter may rectify this problem.
MG02C602 - VLT® is a registered Danfoss trademark
WARNING/ALARM 7, DC overvoltage
the intermediate circuit voltage exceeds the limit, the
If frequency converter trips after a time.
Troubleshooting
Connect a brake resistor Extend the ramp time Change the ramp type Activate the functions in 2-10 Brake Function Increase 14-26 Trip Delay at Inverter Fault
The fault may be caused by mains distortions. Installing Danfoss Line Filter may rectify this problem.
65
Troubleshooting
VLT® Micro Drive FC 51 Programming Guide
WARNING/ALARM 8, DC under voltage
the intermediate circuit voltage (DC link) drops below
If the under voltage limit, the frequency converter checks if a 24 V DC backup supply is connected. If no 24 V DC backup supply is connected, the frequency converter trips after a fixed time delay. The time delay varies with unit size.
Troubleshooting
Check that the supply voltage matches the frequency converter voltage.
Perform input voltage test. Perform soft charge circuit test.
WARNING/ALARM 9, Inverter overload The frequency converter is about to cut out because of an
66
overload (too high current for too long). The counter for electronic, thermal inverter protection issues a warning at 98% and trips at 100%, while giving an alarm. The frequency converter cannot be reset until the counter is below 90%. The fault is that the frequency converter has run with more than 100% overload for too long.
Troubleshooting
Compare the output current shown on the LCP with the frequency converter rated current.
Compare the output current shown on the LCP with measured motor current.
Display the Thermal Drive Load on the LCP and monitor the value. When running above the frequency converter continuous current rating, the counter increases. When running below the frequency converter continuous current rating, the counter decreases.
WARNING/ALARM 10, Motor overload temperature According to the electronic thermal protection (ETR), the motor is too hot. Select whether the frequency converter gives a warning or an alarm when the counter reaches 100% in 1-90 Motor Thermal Protection. The fault occurs when the motor is overloaded by more than 100% for too long.
Troubleshooting
Check for motor overheating. Check if the motor is mechanically overloaded Check that the motor current set in 1-24 Motor
Current is correct. Ensure that Motor data in parameters 1-20
through 1-25 are set correctly. Running AMT in 1-29 Automatic Motor Tuning
(AMT). The inverter peak current limit (approx. 200% of the rated current) is exceeded. The warning will last approx. 8-12 s, then the frequency converter trips and issues an alarm. Turn off the frequency converter and check if the motor shaft can be turned and if the motor size
WARNING/ALARM 11, Motor thermistor over temp The thermistor might be disconnected. Select whether the frequency converter gives a warning or an alarm in 1-90 Motor Thermal Protection.
Troubleshooting
WARNING/ALARM 13, Over current The inverter peak current limit (approx. 200% of the rated current) is exceeded. The warning will last approx. 8-12 s, then the frequency converter trips and issues an alarm. Turn off the frequency converter and check if the motor shaft can be turned and if the motor size matches the frequency converter. If extended mechanical brake control is selected, trip can be reset externally.
Troubleshooting:
ALARM 14, Earth (ground) fault There is current from the output phases to earth, either in the cable between the frequency converter and the motor or in the motor itself.
Troubleshooting:
ALARM 16, Short circuit There is short-circuiting in the motor or motor wiring.
Remove power to the frequency converter and repair the short circuit.
WARNING/ALARM 17, Control word timeout There is no communication to the frequency converter. The warning is only active when 8-04 Control Word Timeout Function is NOT set to OFF. If 8-04 Control Word Timeout Function is set to Stop and Trip, a warning appears and the frequency converter ramps down until it trips, while giving an alarm. 8-03 Control Timeout Time could possibly be increased.
matches the frequency converter. If extended mechanical reset externally. may tune the frequency converter to the motor more accurately and reduce thermal loading.
Check for motor overheating. Check if the motor is mechanically overloaded.
Remove power and check if the motor shaft can be turned.
Check that the motor size matches the frequency converter.
Check parameters 1-20 through 1-25. for correct motor data.
Remove power to the frequency converter and repair the earth fault.
Check for earth faults in the motor by measuring the resistance to ground of the motor leads and the motor with a megohmmeter.
brake control is selected, trip can be
66 MG02C602 - VLT® is a registered Danfoss trademark
Troubleshooting
VLT® Micro Drive FC 51 Programming Guide
Troubleshooting:
connections on the serial communication
Check cable.
Increase 8-03 Control Word Timeout Time Check the operation of the communication
equipment. Verify a proper installation based on EMC
requirements.
WARNING 25, Brake resistor short circuit The brake resistor is monitored during operation. If a short circuit occurs, the brake function is disabled and the warning appears. The frequency converter is still operational but without the brake function. Remove power to the frequency converter and replace the brake resistor (see 2-15 Brake Check).
WARNING/ALARM 27, Brake chopper fault The brake transistor is monitored during operation and if a short circuit occurs, the brake function is disabled and a warning is issued. The frequency converter is still operational but, since the brake transistor has short­circuited, substantial power is transmitted to the brake resistor, even if it is inactive. Remove power to the frequency converter and remove the brake resistor.
WARNING/ALARM 28, Brake check failed The brake resistor is not connected or not working.
ALARM 29, Heatsink temp The maximum temperature of the heatsink has been exceeded. The temperature fault will not reset until the temperature falls below a defined heatsink temperature. The trip and reset points are different based on the frequency converter power size.
Troubleshooting
Check for the following conditions.
Ambient temperature too high. Motor cable too long. Incorrect airflow clearance above and below the
frequency converter. Blocked airflow around the frequency converter. Damaged heatsink fan. Dirty heatsink.
ALARM 30, Motor phase U missing Motor phase U between the frequency converter and the motor is missing.
Remove power from the frequency converter and check motor phase U.
ALARM 31, Motor phase V missing Motor phase V between the frequency converter and the motor is missing.
Remove power from the frequency converter and check motor phase V.
ALARM 32, Motor phase W missing Motor phase W between the frequency converter and the motor is missing.
Remove power from the frequency converter and check motor phase W.
ALARM 38, Internal fault
Troubleshooting
Cycle power Check that the option is properly installed Check for loose or missing wiring
It may be necessary to contact the local Danfoss supplier or service department. Note the code number for further troubleshooting directions.
WARNING 47, 24 V supply low The 24 V DC is measured on the control card. The external 24 V DC backup power supply may be overloaded, otherwise contact the Danfoss supplier.
ALARM 51, AMT check U The settings for motor voltage, motor current, and motor power are wrong. Check the settings in parameters 1-20 to 1-25.
ALARM 55, AMA parameter out of range The parameter values of the motor are outside of the acceptable range. AMA does not run.
ALARM 63, Mechanical brake low The actual motor current has not exceeded the “release brake” current within the “Start delay” time window.
ALARM 80, Drive initialised to default value Parameter settings are initialised to default settings after a manual reset. Reset the unit to clear the alarm.
ALARM 84,The connection between drive and LCP is lost Try to reassemble the LCP gently.
ALARM 85, Button disabled See parameter group 0-4* LCP
ALARM 86, Copy fail An error occurred while copying from frequency converter to LCP or vice versa.
ALARM 87, LCP data invalid Occurs when copying from LCP if the LCP contains erroneous data - or if no data was uploaded to the LCP.
ALARM 88,LCP data not compatible Occurs when copying from LCP if data are moved between frequency converters with major differences in software versions.
WARNING 89, Parameter read only Occurs when trying to write to a read-only parameter.
ALARM 90, Parameter database busy LCP and RS-485 connection are trying to update parameters simultaneously.
nom
and I
nom
6 6
MG02C602 - VLT® is a registered Danfoss trademark
67
Troubleshooting
ALARM 91, Parameter value is not valid in this mode
when trying to write an illegal value to a
Occurs parameter.
ALARM 92, Parameter value exceeds the min/max limits Occurs when trying to set a value outside the range. Parameter can only be changed when the motor is stopped. Err. A wrong password was entered, occurs when using a wrong password for changing a password­protected parameter.
VLT® Micro Drive FC 51 Programming Guide
66
68 MG02C602 - VLT® is a registered Danfoss trademark
Index
VLT® Micro Drive FC 51 Programming Guide
Index
A
Abbreviations And Standards............................................................ 7
Active Set-up.................................................. 8, 44, 28, 11, 13, 50, 55
Alarm, Warning And Extended Status Word.............................. 65
Alarm/Warning Code List.................................................................. 64
Alarms And Warnings......................................................................... 63
Analog In/Out........................................................................................ 59
Automatic Motor Tuning (AMT)...................................................... 15
L
LCP
11.............................................................................................................. 8
12.............................................................................................................. 8
Leakage Current...................................................................................... 4
Limits/Warnings.................................................................................... 58
Load
Compensation.....................................................................
Compensations.................................................................................
Load/Motor............................................................................................. 56
16, 50, 56
14
B
Brake
Resistor.................................................................................. 19, 29, 57
Resistor (ohm)................................................................................... 50
Brakes........................................................................................................ 57
C
Comm. And Options............................................................................ 60
Controllers............................................................................................... 59
Conversion Index
Current Rating....................................................................................... 66
.................................................................................. 54
D
Data Readouts....................................................................................... 62
DC-brake.................................................................................... 17, 19, 28
DC-Brake.................................................................................................. 50
Digital In/Out......................................................................................... 58
Display........................................................................................................ 8
Disposal Instruction............................................................................... 4
Drive
Identification.............................................................................. 46, 47
Information........................................................................................ 61
E
Earth Leakage Current...................................................................... 3, 4
Edit Set-up.............................................................. 8, 11, 12, 13, 50, 55
Electronic Waste...................................................................................... 4
EMC............................................................................................................ 67
M
Main Menu.......................................................................................... 9, 10
Maximum Reference
MCT 10 Set-up Software....................................................................... 1
Minimum Reference............................................................................ 21
Motor
Current.......................................................................................... 67, 15
Data....................................................................................................... 66
Direction................................................................................................ 9
Frequency........................................................................................... 15
Nominal Speed................................................................................. 15
Overload Protection.......................................................................... 4
Phase............................................................................... 48, 27, 50, 58
Power............................................................................................ 67, 14
Status.................................................................................................... 48
Temperature........................................................................ 18, 19, 50
Voltage................................................................................................. 15
........................................................................... 21
N
Navigation Keys....................................................................................... 9
Not Changeable During Operation................................................ 12
O
Operation Keys Operation/Display
Output Current...................................................................................... 66
Over-voltage Control............................................................ 20, 50, 57
......................................................................................... 9
................................................................................ 55
P
Parameter Number................................................................................. 8
H
Hand Mode................................................................. 34, 11, 14, 30, 56
I
Indicator Lights........................................................................................ 9
Isolated Mains Source........................................................................... 4
IT Mains....................................................................................................... 4
MG02C602 - VLT® is a registered Danfoss trademark
Q
Quick Menu........................................................................................ 9, 10
R
Ramp1
Ramp-down Time............................................................................ 23
Ramp-up Time...................................................................................
Rated Magnetizing Current
Readout Mode.......................................................................................... 9
.............................................................. 15
23
69
Index
Reference/Ramps................................................................................. 57
Reset................................................................................................... 66, 67
Residual Current Device....................................................................... 4
VLT® Micro Drive FC 51 Programming Guide
S
Serial Communication.......................... 9, 24, 30, 37, 38, 39, 48, 49
Set-up Number........................................................................................ 8
Short Circuit............................................................................................ 66
Slip Compensation................................................................. 17, 50, 56
Smart Logic............................................................................................. 60
Special Functions........................................................................... 45, 61
Status Menu
Symbols...................................................................................................... 7
.............................................................................................. 9
T
Thermal Load.................................................................................. 15, 48
Thermistor
Thermistor............................................................................ 18, 66, 50
Resource.............................................................................................. 56
Trip Reset................................................................................................. 45
Troubleshooting................................................................................... 63
Type Code String
..................................................................................... 5
U
Unit............................................................................................................... 8
V
Value............................................................................................................ 8
70 MG02C602 - VLT® is a registered Danfoss trademark
*MG02C602*
Loading...