2MG02C602 - VLT® is a registered Danfoss trademark
Safety
VLT® Micro Drive FC 51 Programming Guide
1 Safety
1.1.1 High Voltage Warning
WARNING
The voltage of the frequency converter is dangerous
whenever
the motor or frequency converter may cause damage to
the equipment, serious injury or death. Consequently, it is
essential to comply with the instructions in this manual as
well as local and national rules and safety regulations.
it is connected to mains. Incorrect installation of
1.1.2 Safety Instructions
CAUTION
using functions directly or indirectly influencing
Before
personal safety (e.g. Safe Stop, Fire Mode or other
functions either forcing the motor to stop or attempting to
keep it functioning) a thorough risk analysis and system
test must be carried through. The system tests must
include testing failure modes regarding the control
signaling (analog and digital signals and serial communication.
1.1.3 Software Version and Approvals
Software Version
Programming
VLT® Micro Drive
FC 51 Series
This Programming Guide can be used for all VLT
Drive frequency converters with software
Micro
version 2.7X.
The software version number can be read in
15-43 Software Version.
Table 1.1
Guide
11
®
NOTE
using Fire Mode, contact Danfoss
Before
sure the frequency converter is properly
Make
•
connected to earth.
Do not remove mains connections, motor
•
connections or other power connections while
the frequency converter is connected to power.
Protect users against supply voltage.
•
Protect the motor against overloading according
•
to national and local regulations.
The earth leakage current exceeds 3.5 mA.
•
The [Off] key is not a safety switch. It does not
•
disconnect the frequency converter from mains.
1.1.4 General Warning
WARNING
ELECTRICAL SHOCK HAZARD
Touching
equipment has been disconnected from mains.
Also make sure that other voltage inputs have been
disconnected (linkage of DC intermediate circuit).
Be aware that there may be high voltage on the DC link
even when the LEDs are turned off.
Before touching any potentially live parts of the frequency
converter, wait at least 4 min for all sizes.
Shorter time is allowed only if indicated on the nameplate
for the specific unit.
the electrical parts may be fatal - even after the
MG02C602 - VLT® is a registered Danfoss trademark
3
Safety
VLT® Micro Drive FC 51 Programming Guide
11
CAUTION
Leakage Current
earth leakage current from the frequency converter
The
exceeds 3.5 mA. According to IEC 61800-5-1 a reinforced
Protective Earth connection must be ensured by means of
a min. 10 mm² Cu or an additional PE wire - with the same
cable cross section as the Mains wiring - must be
terminated separately.
Residual Current Device
This product can cause a DC current in the protective
conductor. Where a residual current device (RCD) is used
for extra protection, only an RCD of Type B (time delayed)
shall be used on the supply side of this product. See also
Danfoss Application Note on RCD, MN90GX.
Protective earthing of the frequency converter and the use
of RCDs must always follow national and local regulations.
CAUTION
Motor overload protection is possible by setting 1-90 Thermal Protection to the value ETR trip. For the North
American market: ETR functions provide class 20 motor
overload protection, in accordance with NEC.
Motor
1.1.7 Disposal Instruction
Equipment containing electrical components
not be disposed of together with domestic
must
waste.
It must be separately collected with electrical
and electronic waste according to local and
currently valid legislation.
Table 1.2
1.1.8 Before Commencing Repair Work
1.Disconnect FC 51 from mains (and external DC
supply,
2.Wait for 4 minutes (M1, M2 and M3) and 15 min
(M4 and M5) for discharge of the DC-link.
3.Disconnect DC bus terminals and brake terminals
(if present)
4.Remove motor cable
if present).
WARNING
Installation in high altitudes:
For altitudes above 2 km, please contact Danfoss regarding
PELV.
1.1.5 IT Mains
CAUTION
IT Mains
Installation
Max. supply voltage allowed when connected to mains:
440 V.
As an option, Danfoss offers line filters for improved
harmonics
1.1.6 Avoid unintended Start
While the frequency converter is connected to mains, the
motor
commands, references or via the Local Control Panel.
•
•
on isolated mains source, i.e. IT mains.
performance.
can be started/stopped using digital commands, bus
Disconnect the frequency converter from mains
to avoid unintended start of any motors.
To avoid unintended start, always press the [Off]
key before changing parameters.
4MG02C602 - VLT® is a registered Danfoss trademark
Introduction
2 Introduction
VLT® Micro Drive FC 51 Programming Guide
2.1.1 FC Identification
The nameplate sticker is located on the top of each
frequency
warnings catalog number, and other relevant data for each
unit. See Table 2.1 for details, how to read the type code
string.
converter and shows the ratings, serial number,
22
Illustration 2.1 This Example Shows the Nameplate Sticker
MG02C602 - VLT® is a registered Danfoss trademark
5
Introduction
VLT® Micro Drive FC 51 Programming Guide
2.1.2 Type Code
22
Illustration 2.2
DescriptionPos.Possible choice
Product group1-3Frequency converters
Series and product type4-6Micro Drive
Power size7-100.18-7.5 kW
Mains voltage11-12S2: Single phase 200-240 V AC
2: Three phase 200-240 V AC
T
T 4: Three phase 380-480 V AC
Enclosure13-15IP20/Chassis
RFI filter16-17HX: No RFI filter
RFI filter class A1/B
H1:
H3:RFI filter A1/B (reduced cable length*)
Brake18B: Brake chopper included (from 1.5 kW and up)
No brake chopper included
X:
Display19X: No Local Control Panel
Numerical Local Control Panel (LCP)
N:
P: Numerical Local Control Panel (LCP)) with potentiometer
Coating PCB20C: Coated PCB
No coated PCB
X.
Mains option21X: No mains option
Adaptation A22X: No adaptation
Adaptation B23X: No adaptation
Software release24-27SXXX: Latest release - std. software
Table 2.1 Type Code Description
®
*See VLT
Micro Drive Design Guide, MG02K
6MG02C602 - VLT® is a registered Danfoss trademark
Introduction
2.1.3 Warnings and Approvals
VLT® Micro Drive FC 51 Programming Guide
Symbols used in this Programming Guide.
Symbols
following symbols are used in this manual.
The
CAUTION
Indicates a potentially hazardous situation which, if not
avoided,
also be used to alert against unsafe practices.
may result in minor or moderate injury. It may
WARNING
Indicates a potentially hazardous situation which, if not
avoided,
could result in death or serious injury.
2.1.4 Abbreviations and Standards
AbbreviationsTermsSI-unitsI-P units
aAcceleration
AWGAmerican wire gauge
Auto TuneAutomatic Motor Tuning
°C
ICurrentAAmp
I
LIM
IT mainsMains supply with star point in transformer floating to ground
JouleEnergyJ=N∙mft-lb, Btu
°F
FCfrequency converter
fFrequencyHzHz
kHzKilohertzkHzkHz
LCPLocal Control Panel
mAMilliampere
msMillisecond
minMinute
MCTMotion Control Tool
M-TYPEMotor Type Dependent
NmNewton Metresin-lbs
I
M,N
f
M,N
P
M,N
U
M,N
PELVProtective Extra Low Voltage
WattPowerWBtu/hr, hp
PascalPressurePa = N/m²psi, psf, ft of water
I
INV
RPMRevolutions Per Minute
sSecond
SRSize Related
TTemperatureCF
tTimess,hr
T
LIM
UVoltageVV
Celsius
Current limit
Fahrenheit
Nominal motor current
Nominal motor frequency
Nominal motor power
Nominal motor voltage
Rated Inverter Output Current
Torque limit
CAUTION
Indicates
property-damage-only accidents.
a situation that may result in equipment or
2
m/s
ft/s
22
2
Table 2.2 Abbreviation and Standards Table
MG02C602 - VLT® is a registered Danfoss trademark
7
Programming
VLT® Micro Drive FC 51 Programming Guide
3 Programming
The display
3.1 How to Programme
Different
information can be read from the display.
33
3.1.1 Programming with MCT 10 Set-up
Software
The frequency converter can be programmed from a PC
RS-485 com-port by installing the MCT 10 Set-up
via
Software.
This software can either be ordered using code number
130B1000 or downloaded from the Danfoss Web site:
Set-up number shows the active set-up and the edit setup. If the same set-up acts as both active and edit set-up,
only that set-up number is shown (factory setting).
When active and edit set-up differ, both numbers are
shown in the display (Set-up 12). The number flashing,
indicates the edit set-up.
Refer to the manual for Motion Control Tools MG10R.
3.1.2 Programming with the LCP 11 or LCP
12
The LCP is divided into four functional groups:
1.Numeric
2.Menu key.
3.Navigation keys.
4.Operation keys and indicator lights (LEDs).
Illustration 3.1 LCP 12 with Potentiometer
display.
Illustration 3.3 Indicating Set-up
The small digits to the left are the selected parameter
number.
Illustration 3.4 Indicating Selected Parameter Number
The large digits in the middle of the display show the
of
value
the selected parameter.
Illustration 3.5 Indicating Value of Selected Parameter
The right side of the display shows the unit of
parameter. This can be either Hz, A, V, kW, HP, %, s or
RPM.
Illustration 3.2 LCP 11 without Potentiometer
8MG02C602 - VLT® is a registered Danfoss trademark
Illustration 3.6 Indicating Unit of Selected Parameter
the selected
Programming
is
Motor direction
- indicated by a small arrow pointing either clockwise or
counterclockwise.
Illustration 3.7 Indicating Motor Direction
Press the [Menu] key to select one of the following menus
Status Menu
The Status Menu is either in Readout Mode or Hand onMode. In Readout Mode the value of the currently selected
readout parameter is shown in the display.
shown to the bottom left of the display
VLT® Micro Drive FC 51 Programming Guide
Operation Keys
yellow light above the operation keys indicates the
A
active key.
[Hand On]: Starts the motor and enables control of the
frequency converter via the LCP.
[Off/Reset]: The motor stops except in alarm mode. In that
case the motor will be reset.
[Auto On]: The frequency converter is controlled either via
control terminals or serial communication.
[Potentiometer] (LCP 12): The potentiometer works in two
ways depending on the mode in which the frequency
converter is running.
In Auto Mode the potentiometer acts as an extra
programmable analog input.
In Hand on Mode the potentiometer controls local
reference.
3.2 Status Menu
33
In Hand on Mode the local LCP reference is displayed.
Quick Menu
Displays Quick Menu parameters and their settings.
Parameters in the Quick Menu can be accessed and edited
from here. Most applications can be run by setting the
parameters in the Quick Menus.
Main Menu
Displays Main Menu parameters and their settings. All
parameters can be accessed and edited here.
Indicator lights
Green LED: The frequency converter is on.
•
Yellow LED: Indicates a warning. See 6 Trouble-
•
shooting.
Flashing red LED: Indicates an alarm. See
•
6 Troubleshooting.
Navigation Keys
[Back]: For moving to the previous step or layer in the
navigation structure.
[▲] [▼]: For maneuvering between parameter groups,
parameters and within parameters.
[OK]: For selecting a parameter and for accepting changes
to parameter settings.
After power up the Status Menu is active. Press [Menu] to
between Status, Quick Menu and Main Menu.
toggle
[▲] and [▼] toggles between the choices in each menu.
The display indicates the status mode with a small arrow
above “Status”.
Illustration 3.8 Indicating Status Mode
Pressing [OK] for more than 1 s enters 'Adjust' mode. In
'Adjust' mode, it is possible to make fast adjustment by
pressing [▲] [▼] combined with [OK].
Press [▲] [▼] to change value. Press [OK] to shift between
digits quickly.
To exit 'Adjust' mode, press [OK] more than 1 s again with
changes saving or press [Back] without changes saving.
MG02C602 - VLT® is a registered Danfoss trademark
9
Programming
VLT® Micro Drive FC 51 Programming Guide
3.3 Quick Menu
The Quick Menu gives easy access to the most frequently
parameters.
used
1.To enter the Quick Menu, press [Menu] key until
33
indicator in display is placed above Quick Menu.
2.
Press [▲] [▼] to select either QM1 or QM2, then
press [OK].
3.
Press [▲] [▼] to browse through the parameters
in the Quick Menu.
4.Press [OK] to select a parameter.
5.
Press [▲] [▼] to change the value of a parameter
setting.
6.Press [OK] to accept the change.
7.
To exit, press either [Back] twice to enter Status,
or press [Menu] once to enter Main Menu.
Illustration 3.9 Indicating Quick Menu Mode
3.4 Main Menu
The Main Menu gives access to all parameters.
1.
2.
3.Press [OK] to select a parameter group.
4.
5.Press [OK] to select the parameter.
6.
7.Press [OK] to accept the value.
8.
enter the Main Menu, press [Menu] key until
To
indicator in display is placed above Main Menu.
Press [▲] [▼] to browse through the parameter
groups.
Press [▲] [▼] to browse through the parameters
in the specific group.
Press [▲] [▼] to set/change the parameter value.
To exit, press either [Back] twice to enter QuickMenu, or press [Menu] once to enter Status.
Illustration 3.10 Indicating Main Menu Mode
10MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4 Parameter Descriptions
4.1 Parameter Group 0: Operation/Display
0-03 Regional Settings
Option:Function:
In order to meet the needs for different default
in different parts of the world, 0-03
settings
Regional Settings, is implemented in the
frequency converter. The selected setting
influences the default setting of the motor
nominal frequency.
[0 ] * Interna-
tional
[1]US
Sets default of 1-23
shows 1-20 Motor Power in kW.
Sets default of 1-23
shows 1-20 Motor Power in HP.
Motor Frequency, to 50 Hz,
Motor Frequency, to 60 Hz,
NOTE
This parameter cannot be changed while
motor runs.
0-04 Operating State at Power-up (Hand Mode)
Option:Function:
This parameter controls whether or not the
frequency
when powering up after a power down in
Hand mode.
converter start running the motor
NOTE
If LCP with potentiometer is mounted,
reference is set according to actual
potentiometer value.
[0]ResumeFrequency converter starts in same Hand or
Off State as when powered off.
Local reference is stored and used after
power-up.
[1] * Forced
Stop,
Ref=Old
[2]Forced
Stop,
Frequency converter powers up in Off State
meaning
up.
Local reference is stored and used after
power-up.
Frequency converter powers up in Off State
Ref=0
meaning that motor is stopped after power
up.
Local reference is set to 0. Thus motor will
not start running before local reference has
been increased.
that motor is stopped after power
4.1.1 0-1* Set-up Handling
User-defined parameters and miscellaneous external inputs
(eg.
A complete set of all parameters controlling the frequency
converter is called a set-up. The frequency converter
contains 2 set-ups, Set-up 1 and Set-up 2.
Furthermore, a fixed set of factory settings can be copied
into one or more set-ups.
Some of the advantages of having more than one set-up
in the frequency converter are
Run motor in one set-up (Active Set-up) while
•
updating parameters in another set-up (Edit Setup)
Connect various motors (one at a time) to
•
frequency converter. Motor data for various
motors can be placed in different set-ups.
Rapidly change settings of frequency converter
•
and/or motor while motor is running (eg. ramp
time or preset references) via bus or digital
inputs.
The Active Set-up can be set as Multi Set-up where the
active set-up is selected via input on a digital input
terminal and/or via the bus control word.
NOTE
Factory
Set-up cannot be used as Active Set-up.
0-10 Active Set-up
Option:Function:
Active Set-up controls
Shifts between set-ups can only happen when
the motor is coasted
•
OR
the set-ups between which the shift
•
happens are linked to each other (see
0-12 Linked Set-ups).
If changing between set-ups that are not linked,
the change will not happen before motor is
coasted.
the motor.
NOTE
The motor is only considered stopped
when it is coasted.
44
MG02C602 - VLT® is a registered Danfoss trademark
11
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
0-10 Active Set-up
Option:Function:
[1 ] * Set-up 1
[2]
Set-up 2
Multi
[9]
Set-up
is active.
Set-up 1
Set-up 2 is active.
Select the active set-up via digital input and/or
see 5-1* Digital Inputs choice [23].
bus,
0-11 Edit Set-up
44
Option:Function:
Set-up
The Edit
the frequency converter from either LCP or
bus. It can be identical or different from the
Active Set-up.
All set-ups can be edited during operation,
independently of the active set-up.
[1 ] * Set-up 1
[2]Set-up 2
[9]Active Set-upUpdate parameters in set-up selected as
Update parameters in Set-up
Update parameters in Set-up
Set-up (see 0-10 Active Set-up).
Active
is for updating parameters in
1.
2.
0-12 Link Set-ups
Option:Function:
The link ensures synchronizing of the “not
changeable during operation” parameter values
enabling shift from one set-up to another
during operation.
If the set-ups are not linked, a change between
them is not possible while the motor is running.
Thus the set-up change does not occur until the
motor is coasted.
[0]Not
linked
[1 ] * LinkedCopy parameters “not changeable during
Leaves parameters unchanged in both set-ups
cannot be changed while motor runs.
and
operation”
selected Edit Set-up.
parameter values into presently
NOTE
This parameter cannot be changed while
motor runs.
0-31 Custom Readout Min Scale
Range:Function:
0.00 * [0.00–
9999.00
It is possible to create a customized
]
readout related to the output frequency of
the unit. The value entered in 0-31 CustomReadout Min Scale will be shown at 0 Hz.
The readout can be shown in the LCP
display when in Status Mode or it can be
read in 16-09 Custom Readout
0-32 Custom Readout Max Scale
Range:Function:
100.0* [0.00–
9999.00]
It is possible to create a customized readout
to the output frequency of the unit.
related
The value entered in 0-32 Custom ReadoutMax Scale will be shown at the frequency
programmed in 4-14 Motor Speed High Limit.
The readout can be shown in the LCP
display when in Status Mode or it can be
read in 16-09 Custom Readout
4.1.2 0-4* LCP
The frequency converter can operate in the following three
modes: HandHand: The frequency converter is locally operated and does
not allow any remote control. By activating Hand a start
signal is given.
OFF: The frequency converter stops with a normal stop
ramp. When Off is chosen the frequency converter can
only be started by pressing either Hand or Auto on the
LCP.
Auto: In Auto-mode the frequency converter can be
remote controlled (bus/digital).
0-40 [Hand On] Key on LCP
Option:Function:
[0]Disabled[Hand On] key has no function.
[1 ] *Enabled[Hand On] key is functional.
0-41 [Off/Reset] Key on LCP
Option:Function:
[0]Disable Off/Reset[Off/Reset] key has no function.
[1 ] * Enable Off/ResetStop signal and reset of any faults.
[2]Enable Reset Only Reset only. Stop (Off) function is
0-42 [Auto On] Key on LCP
Option:Function:
[0]Disabled[Auto On] key has no function.
[1 ] *Enabled[Auto On] key is functional.
, Off and Auto.
disabled.
12MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.1.3 0-5* Copy/Save
0-50 LCP Copy
Option:Function:
The detachable LCP of the frequency
converter
and thus for transferring data when
moving parameter settings from one
frequency converter to another.
can be used for storing setups,
NOTE
LCP Copy can only be activated from
the LCP and ONLY when the motor
is coasted.
[1] All to LCPCopy all setups from the frequency
converter
[2] All from LCPCopy all setups from LCP to frequency
converter.
[3] Size independent
LCP
from
Copy non motor size dependent data
from LCP to frequency converter.
0-51 Set-up Copy
Option:Function:
Use this function to copy a set-up content
into
the Edit Set-up.
In order to be able to make a set-up copy
ensure that
•
•
into the LCP.
the motor is coasted
0-10 Active Set-up, Active Set-up, is
set to either [1] Set-up 1 or [2] Set-
up 2
4.1.4 0-6* Password
0-60 (Main) Menu Password
Range:Function:
Use password for protection against unintended
of sensitive parameters, eg. motor
change
parameters.
0 * [0-999] Enter the password for access to Main Menu via
[Main Menu] key. Select the number that
the
should allow for changing other parameter values.
0 means there is no password.
NOTE
A password has affect on the LCP - not on the bus
communication.
NOTE
Pressing
This will automatically enter the parameter editing screen
in Quick Menu or Main Menu.
[0] * Full access
[1]LCP: Read Only
[2]LCP: No Access
[Menu], [OK] and [▼] will unlock the password.
0-61 Access to Main/Quick Menu w/o Password
Option:Function:
Select [0] Full Access to disable the
password in 0-60 (Main) Menu Password.
Select [1] Read Only
editing of Main/Quick menu parameter.
Select [2] No Access
editing and viewing of Main/Quick menu
parameter.
to block unauthorized
to block unauthorized
44
NOTE
The keyboard/parameter database are
blocked while Set-up Copy is running.
[0 ] * No CopyCopy function is inactive
[1]Copy from
Set-up
[2]Copy from
Set-up
[9]Copy from
Factory
up
Copy from Set-up 1 to edit set-up chosen in
1
0-11 Edit Set-up.
Copy from Set-up 2 to edit set-up chosen in
2
0-11 Edit Set-up.
Copy from Factory Settings to edit set-up
Set-
chosen in 0-11 Edit set-up.
MG02C602 - VLT® is a registered Danfoss trademark
13
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.2 Parameter Group 1: Load/Motor
1-05 Hand Mode Configuration
Option:Function:
1-00 Configuration Mode
Option:Function:
Use this parameter for selecting the
application
a Remote Reference is active.
NOTE
44
Changing this parameter will reset 3-00Reference Range, 3-02 Minimum Reference
and 3-03 Maximum Reference to their
control principle to be used when
[2] * As config-
uration
1-00
Configuration
Mode.
default values.
NOTE
parameter cannot be adjusted
[0 ] * Speed
Open Loop
[3]Process
Closed
Loop
This
while motor runs.
For normal speed control (References).
Enables process closed loop control. See
parameter
further information on PI-controller.
group 7-3* Process PI Control for
4.2.1 1-2* Motor Data
Enter the correct motor nameplate data (power, voltage,
frequency,
Run AMT, see 1-29 Automatic Motor Tuning (AMT).
Factory settings for advanced motor data, parameter group
1-3* Adv. Motor Data, are automatically calculated.
frequency limited by Motor Speed High/Low
(4-14 Motor Speed High Limit and 4-12
Limit
Motor Speed Low Limit).
If 1-00 Configuration Mode is set to [1] Open
in
Loop function is as described above.
If 1-00 Configuration Mode is set to [3] ProcessClosed Loop changing from Auto mode to Hand
mode results in a setpoint change via local
potentiometer or Arrow up/down. The change
is limited by Reference Max/Min (3-02 MinimumReference and 3-03 Maximum Reference).
current and speed).
1-01 Motor Control Principle
Option:Function:
[0]U/fIs used for parallel connected motors and/or special
applications. The U/f settings are set in 1-55
motor
U/f Characteristic -U and 1-56 U/f Characteristic -F.
NOTE
When running U/f control slip- and load
compensations are not included.
[1] * VVC+ Normal running mode, including slip- and load
compensations.
1-03 Torque Characteristics
Option:Function:
With more torque characteristics it is
possible
well as high torque applications.
[0 ] * Constant
Torque
[2]Automatic
Optimi-
Energy
sation
Motor shaft output provides constant
torque
This function automatically optimizes
energy consumption in centrifugal pump
and fan applications. See 14-41 AEOMinimum Magnetisation.
1-05 Hand Mode Configuration
Option:Function:
This parameter is only relevant when 1-00
Configuration
Loop. The parameter is used for determining
the reference or setpoint handling when
changing from Auto Mode to Hand Mode on
the LCP.
[0]Speed
Open
Loop
In Hand Mode the drive always runs in Open
configuration regardless of setting in 1-00
Loop
Configuration Mode. Local potentiometer (if
present) or Arrow up/down determines output
to run low energy consuming, as
under variable speed control.
Mode is set to [3] Process Closed
NOTE
Parameters
adjusted while motor runs.
1-20 Motor Power [kW]/[HP] (P
Option:Function:
[1]0.09 kW/0.12 HP
[2]0.12 kW/0.16 HP
[3]0.18kW/0.25 HP
[4]0.25 kW/0.33 HP
[5]0.37kW/0.50 HP
[6]0.55 kW/0.75 HP
[7]0.75 kW/1.00 HP
[8]1.10 kW/1.50 HP
[9]1.50 kW/2.00 HP
[10] 2.20 kW/3.00 HP
[11] 3.00 kW/4.00 HP
[12] 3.70 kW/5.00 HP
[13] 4.00 kW/5.40 HP
[14] 5.50 kW/7.50 HP
[15] 7.50 kW/10.0 HP
[16] 11.00 kW/15.00 HP
[17] 15.00 kW/20.00 HP
[18] 18.50 kW/25.00 HP
[19] 22.00 kW/29.50 HP
[20] 30.00 kW/40.00 HP
in parameter group 1-2* Motor Data cannot be
Enter motor power from nameplate
data.
sizes down, one size up from
Two
nominal VLT rating.
m.n
)
14MG02C602 - VLT® is a registered Danfoss trademark
130BA375.11
R
S
P 1-30
R
1s
X
h
P1-35
R
1
X
2
X
1
U
1
I
1
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
NOTE
Changing
Voltage to 1-25 Motor Frequency, 1-30 Stator Resistance, 1-33
Stator Leakage Reactance and 1-35 Main Reactance.
1-22 Motor Voltage (U_
Range:Function:
230/400 V [50-999 V] Enter motor voltage from nameplate
1-23 Motor Frequency (f_
Range:Function:
50 Hz* [20-400 Hz] Enter motor frequency from nameplate
1-24 Motor Current (I_
Range:Function:
M-type dependent* [0.01-100.00 A] Enter motor current from
1-25 Motor Nominal Speed (n_
Range:Function:
M-type Dependent* [100-9999 RPM] Enter motor nominal
this parameter affects parameters 1-22 Motor
)
m.n
data.
)
m.n
data.
)
m.n
nameplate
)
m.n
speed
data.
data.
from nameplate
4.2.2 1-3* Adv. Motor Data
Adjust advanced motor data using one of these methods:
1.Run
AMT on cold motor. The frequency converter
measures value from motor.
2.Enter X1 value manually. Obtain value from motor
supplier.
3.Use Rs, X1, and X2 default setting. The frequency
converter establishes setting based on motor
nameplate data.
NOTE
parameters cannot be changed while the motor
These
runs.
44
1-29 Automatic Motor Tuning (AMT)
Illustration 4.1
Option:Function:
Use AMT to optimize motor performance.
NOTE
This parameter cannot be changed while
motor runs.
1.Stop the frequency converter - make
motor is at standstill
sure
2.
Choose [2] Enable AMT
3.Apply start signal
- Via LCP: Press [Hand On]
- Or in Remote On mode: Apply start
signal on terminal 18
[0] * OffAMT function is disabled.
[2]Enable
AMT
AMT function starts running.
NOTE
gain optimum tuning of the frequency
To
converter, run AMT on a cold motor.
1-30 Stator Resistance (Rs)
Range:Function:
Depending on motor data* [Ohm] Set stator resistance value.
1-33 Stator Leakage Reactance (X1)
Range:Function:
Depending on motor
data*
[Ohm] Set stator leakage reactance
motor.
of
1-35 Main Reactance (X2)
Range:Function:
Depending on motor data* [Ohm] Set motor main reactance.
4.2.3 1-5* Load Independent Setting
This parameter group is for setting the load independent
settings.
motor
1-50 Motor Magnetization at Zero Speed
Range:Function:
This parameter enables different thermal
on motor when running at low speed.
100 %* [ 0-300%] Enter a percentage of rated magnetizing
load
If setting is too low, motor shaft
current.
torque may be reduced.
MG02C602 - VLT® is a registered Danfoss trademark
15
Magn. current
130BD016.10
Hz
Par.1-50
Par.1-51
100%
Par.1-52RPM
Motor Voltage
Par 1-55 [x]
Output Frequency
Par 1-56 [x]
1-55[5]
1-55[4]
1-55[3]
1-55[2]
1-55[1]
1-55[0]
1-56
[0]
1-56
[1]
1-56
[2]
1-56
[3]
1-56
[4]
1-56
[5]
130BD017.10
130BD018.10
60%
0%
100%
U
m
Changeover
f
out
Par.1-60Par.1-61
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
1-52 Min. Speed Normal Magnetizing [Hz]
Range:Function:
Use this parameter along with 1-50
Motor
Magnetizing at Zero Speed.
0.0 Hz* [0.0-10.0 Hz] Set frequency required for normal
magnetizing
current. If frequency is set
lower than motor slip frequency, 1-50Motor Magnetizing at Zero Speed is
44
inactive.
Illustration 4.3 U/f Characteristics
Illustration 4.2
NOTE
1-55 U/f Characteristic - U
Range:Function:
This parameter is an array parameter [0-5]
is only functional when 1-01 Motor
and
Control Principle is set to [0] U/f.
0.0 V* [0.0-999.9 V] Enter voltage at each frequency point to
manually
form a U/f characteristic
matching motor. Frequency points are
defined in 1-56 U/f characteristics - F.
1-56 U/f Characteristic - F
Range:Function:
This parameter is an array parameter [0-5]
is only functional when 1-01 Motor
and
Control Principle is set to [0] U/f.
0.0
Hz*
[0.0-1000.0
Hz]
Enter frequency points to manually form a
characteristic matching motor. Voltage
U/f
at each point is defined in 1-55 U/fCharacteristic - U.
Make a U/f characteristic based on 6
definable voltages and frequencies, see
Illustration 4.3.
Simplify U/f characteristics by merging 2
or more points (voltages and frequencies),
respectively, are set equal.
For 1-56
[0] ≦ [1] ≦ [2] ≦ [3] ≦ [4] ≦ [5]
4.2.4 1-6* Load Dependent Setting
Parameters for adjusting the load-dependent motor
settings.
U/f characteristics - F the following applies
1-60 Low Speed Load Compensation
Range:Function:
Use this parameter to gain optimum U/f
characteristic
100 %* [0-199 %] Enter percentage in relation to load when
motor
Change-over point is automatically
calculated based on motor size.
when running at low speed.
runs at low speed.
16MG02C602 - VLT® is a registered Danfoss trademark
Illustration 4.4
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
1-61 High Speed Load Compensation
Range:Function:
Use this parameter to obtain optimum load
compensation
100 %* [0-199 %] Enter percentage to compensate in relation
load when motor runs at high speed.
to
Change-over point is automatically
calculated based on motor size.
when running at high speed.
1-62 Slip Compensation
Range:Function:
100 %* [-400-399%]Compensation for load dependent motor
slip.
compensation is calculated automat-
Slip
ically based on rated motor speed, n
M,N
NOTE
This
function is only active when
1-00 Configuration Mode, is set to [0]
Speed Open Loop and when 1-01
Motor Control Principle, is set to [1]
plus
VVC
1-63 Slip Compensation Time
Range:Function:
0.10 s [0.05-5.00 s] Enter slip compensation reaction speed. A
high value results in slow reaction whereas
a low value results in quick reaction.
If low-frequency resonance problems arise,
use longer time setting.
4.2.5 1-7* Start Adjustments
Considering the need for various start functions in different
applications,
in this parameter group.
1-71 Start Delay
Range:Function:
0.0 s* [0.0-10.0s]Enter the time delay required before
it is possible to select a number of functions
The start delay defines the time to pass from
start command is given until the motor
a
starts accelerating.
Setting start delay to 0.0 s disables 1-72 StartFunction, when start command is given.
commencing
1-72 Start Function is active during Start delay
time.
acceleration.
1-72 Start Function
Option:Function:
[0]DC Hold/Delay
Time
[1]DC Brake/Delay
Time
[2] * Coast/Delay
Time
Motor is energised with DC holding
(2-00 DC Hold Current) during
current
start delay time.
Motor is energised with DC braking
(2-01 DC Brake Current) during
current
start delay time.
Inverter is coasted during start delay time
(inverter
off).
1-73 Flying Start
Option:Function:
The Flying Start parameter is used to catch a
.
spinning
motor after eg. mains drop-out.
NOTE
This function is not suitable for hoisting
applications.
[0] * Disabled Flying start is not required.
[1]Enabled Frequency converter enabled to catch spinning
motor.
NOTE
flying start is enabled 1-71 Start Delay,
When
and 1-72 Start Function, have no function.
4.2.6 1-8* Stop Adjustments
To meet the need for various stop functions in different
application
features for the motor.
1-80 Function at Stop
Option:Function:
[0] * CoastThe inverter is coasted.
[1]DC
these parameters offer some special stop
The selected function at stop is active in following
situations:
Stop command is given and output
•
speed is ramped down to Min. Speed forFunction at Stop.
Start command is removed (standby),
•
and output speed is ramped down to
Min. Speed for Function at Stop.
DC-brake command is given, and DC-
•
brake time has passed
While running and calculated output
•
speed is below Min. Speed for Function atStop.
The motor is energised with a DC current. See
hold
DC Hold Current for more information.
2-00
44
1-82 Min. Speed For Function at Stop [Hz]
Range:Function:
0.0 Hz* [0.0-20.0 Hz]
MG02C602 - VLT® is a registered Danfoss trademark
Set the speed at which to activate 1-80
Function
at Stop.
17
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.2.7 1-9* Motor Temperature
1-93 Thermistor Resource
Option:Function:
With an estimated motor temperature monitor the
frequency
without having a thermistor mounted. It is thus possible to
receive a warning or an alarm, if motor temperature
exceeds upper operational limit.
converter is able to estimate motor temperature
[0] * NoneNo thermistor is connected.
[1]Analog
Input
1-90 Motor Thermal Protection
44
Option:Function:
Using ETR (Electronic Terminal Relay) the
temperature is calculated based on
motor
frequency, speed and time. Danfoss
recommends using The ETR function, if a
thermistor is not present.
[6]Digital
input 29
NOTE
ETRElectronic Overload calculation is
based on motor data from parameter
group 1-2* Motor Data.
[0] * No Protection Disables temperature monitoring.
[1]Thermistor
Warning
[2]Thermistor
Trip
[3]ETR WarningIf calculated upper limit of motor
[4]ETR TripIf 90% of calculated upper limit of motor
A thermistor connected to either digital or
input gives a warning if upper limit
analog
of motor temperature range is exceeded,
(see 1-93 Thermistor Resource).
A thermistor connected to either digital or
input gives an alarm and makes the
analog
frequency converter trip if upper limit of
motor temperature range is exceeded, (see
1-93 Thermistor Resource.
temperature
occurs.
temperature
occurs and the frequency converter trips.
range is exceeded, a warning
range is exceeded, an alarm
Select the thermistor input terminal.
Connect thermistor to analog input terminal
53
53.
NOTE
Analog input 53 cannot be selected for
other purposes when selected as
thermistor resource.
Connect thermistor to digital input terminal 29.
While this input functions as thermistor input,
it will not respond to the function chosen in
5-13 Digital Input 29. The value of 5-13 Digital
Input 29 remains however unchanged in
parameter database while function is inactive.
Input Digital/
Analog
Digital10 V
Analog10
Table 4.1
Supply
Voltage
V
Threshold Cut-
out
Values
<800 Ω ⇒ 2.9
kohm
<800 Ω ⇒ 2.9
kohm
NOTE
When
the ETR function has been selected the drive will
store the recorded temperature at power down and this
temperature will resume at power up regardless of the
elapsed time. Changing 1-90 Motor Thermal Protection back
to [0] No Protection will reset the recorded temperature.
18MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.3 Parameter Group 2: Brakes
4.3.1 2-** Brakes
4.3.2 2-0* DC-Brake
The purpose of DC-brake function is to brake a rotating
by applying DC-current to the motor.
motor
2-00 DC Hold Current
Range:Function:
This parameter either holds the motor (holding
or pre-heats the motor.
torque)
The parameter is active if DC Hold has been
selected in either 1-72 Start Function or 1-80Function at Stop.
50%* [0-100%] Enter a value for holding current as a
percentage
1-24 Motor Current. 100% DC holding current
corresponds to I
of the rated motor current set in
.
M,N
NOTE
100% current too long as it may overheat the motor.
Avoid
2-01 DC Brake Current
Range:Function:
50%* [0-150%] Set DC-current needed to brake rotating
motor.
Activate
ways:
DC-brake in one of the four following
1.
DC-brake command, see 5-1* DigitalInputs choice [5]
2.
DC Cut-in function, see 2-04 DC-Brake
Cut-in Speed
3.DC-brake selected as start function,
see 1-72 Start Function
4.
DC-brake in connection with FlyingStart, 1-73 Flying Start.
2-02 DC-Braking Time
Range:Function:
DC-braking time defines the period during
which DC-brake current is applied to the
motor.
10.0 s* [0.0-60 s]
Set the time DC-braking current, set in 2-01
Brake Current, must be applied.
DC
NOTE
If
DC-brake is activated as start function, DC-brake time is
defined by start delay time.
2-04 DC-Brake Cut-in Speed
Range:Function:
0.0 Hz* [0.0-400.0 Hz] Set DC-brake cut-in speed to activate
braking current, set in 2-01 DC Brake
DC
Current, when ramping down.
When set to 0 the function is off.
4.3.3 2-1* Brake Energy Function
Use the parameters in this group for selecting dynamic
braking
parameters.
2-10 Brake Function
Option:Function:
Resistor Brake:
resistor brake limits voltage in the
The
intermediate circuit when the motor acts as
generator. Without brake resistor, the frequency
converter eventually trips.
The resistor brake consumes surplus energy
resulting from motor braking. A frequency
converter with brake, stops a motor faster than
without a brake, which is used in many
applications. Requires connection of external
brake resistor.
An alternative to the resistor brake is the AC
brake.
NOTE
Resistor brake is only functional in
frequency converters with integrated
dynamic brake. An external resistor must
be connected.
AC Brake:
AC brake consumes surplus energy by
The
creating power loss in the motor.
It is important to keep in mind that an increase
in power loss causes motor temperature to rise.
[0] * OffNo brake function.
[1]Resistor
Brake
[2]AC Brake AC brake is active.
2-11 Brake Resistor (Ohm)
Range:Function:
5 Ω* [5-5000 Ω]Set brake resistor value.
2-16 AC Brake, Max Current
Range:Function:
100.0%* [0.0-150.0%] Enter max. permissible current for AC-
Resistor brake is active.
to avoid overheating of motor.
braking
100% equals motor current set in 1-24Motor Current.
44
MG02C602 - VLT® is a registered Danfoss trademark
19
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
2-17 Over-Voltage Control
Option:Function:
Use Over-voltage Control (OVC) to reduce
risk of the frequency converter tripping
the
due to an over voltage on the DC link
caused by generative power from the load.
An over-voltage occurs eg. if the ramp down
time is set too short compared to the actual
44
[0] * DisabledThe OVC is not active/required.
[1]Enabled, not
stop
at
[2]EnabledOVC is running, also when a stop signal is
load inertia.
OVC is running unless a stop signal is active.
active.
NOTE
If
Resistor Brake has been chosen in 2-10 Brake Function
the OVC is not active even though enabled in this
2-22 Activating Mechanical Brake
Range:Function:
If the motor is stopped using ramp, the
brake is activated when motor
A start command is removed (stand
•
by)
A stop command is activated
•
Quick-stop is activated (Q-stop ramp is
•
used)
when ramping down.
0 Hz* [0-400
Hz]
mechanical
speed is less than Active Brake Speed.
Motor is ramped down to stop in the following
situations:
Select motor speed at which mechanical brake
activates
Mechanical brake automatically activates if
frequency converter trips or reports an alarm.
parameter.
4.3.4 2-2* Mechanical Brake
For hoisting applications an electro-magnetic brake is
required.
the brake when activated.
The brake is controlled by a relay, which releases
The brake activates if the frequency converter trips or a
coast command is given. Furthermore, it activates when
motor speed is ramped down below the speed set in 2-22Active Brake Speed.
2-20 Release Brake Current
Range:Function:
0.00 A* [0.00-100 A] Select motor current at which mechanical
releases.
brake
CAUTION
If start delay time has passed, and
current is below Release brake
motor
current, frequency converter trips.
20MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.4 Parameter Group 3: Reference/Ramps
4.4.1 3-** Reference/Ramps
Parameters for reference handling, definition of limitations,
configuration of the frequency converter's reaction to
and
changes
4.4.2 3-0* Reference Limits
Parameters for setting the reference unit, limits and ranges.
3-00 Reference Range
Option:Function:
Select the range of reference and feedback
signals.
[0] * Min to
Max
[1]-Max to
+Max
3-02 Minimum Reference
Range:Function:
0.00* [-4999-4999] Enter value for minimum reference.
3-03 Maximum Reference
Range:Function:
50.00* [-4999-4999] Enter value for Maximum Reference.
Reference setpoint ranges can have positive
only.
values
Select this if running in Process Closed Loop.
Ranges can have both positive and negative
values.
potentiometer is used to adjust motor running
If
in both direction, set reference range to –Max
Reference to Max Reference by par.=[1] Choose
hand on mode by LCP. Adjust the potentiometer
to minimum, the motor can run in anti-clockwise
with max speed. Then adjust the potentiometer
to maximum, the motor will ramp down to 0
and run clockwise with max speed.
The sum of all internal and external
references are clamped (limited) to the
minimum reference value, 3-02 MinimumReference.
Maximum Reference is adjustable in the
Minimum Reference -4999.
range
sum of all internal and external
The
references are clamped (limited) to the
maximum reference value, 3-03 MaximumReference.
4.4.3 3-1* References
Parameters for setting up the reference sources. Select the
references for the corresponding digital inputs in
preset
parameter group, 5-1* Digital Inputs.
3-10 Preset Reference
Option:Function:
Each parameter set-up contains 8 preset
references
digital inputs or bus.
Table 4.2 Parameter Group 5-1* Digital
Inputs
[0.00]*-100.00-100.00% Enter the different preset references
using
Normally, 100% = value set in 3-03Maximum Reference.
However, there are exceptions if 3-00Reference Range is set to [0] Min - Max.
Example 1:
3-02 Minimum Reference is set to 20 and
3-03 Maximum Reference is set to 50. In
this case 0%=0 and 100%=50.
Example 2:
3-02 Minimum Reference is set to -70
and 3-03 Maximum Reference is set to
50. In this case 0%=0 and 100%=70.
3-11 Jog Speed [Hz]
Range:Function:
Jog speed is a fixed output speed and
overrules
parameter group 5-1* Digital Inputs option
[14].
If the motor is stopped while in jog mode,
the jog signal acts as a start signal.
Removing the jog signal makes the motor
run according to the selected configuration.
5.0Hz [0.0-400.0
Hz]
Select speed to function as jog speed.
which are selectable via 3
[18]
Bit2
0000
0011
0102
0113
1004
1015
1106
1117
[17]
Bit1
Option [16], [17] and [18]
array programming.
the selected reference speed, see
[16]
Bit0
[16]
Bit0
44
MG02C602 - VLT® is a registered Danfoss trademark
21
Relative
Z=X+X*Y/100
Resulting
actual
reference
Y
X
130BA059.12
Z
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
3-12 Catch Up/Slow Down Value
Range:Function:
0% * [0-100%]
The Catch-up/Slowdown
an input command (see 5-1* Digital Inputs,
choice [28]/[29]). If the command is active, the
Catch-up/Slowdown value (in %) is added to
the reference function as follows:
Reference
=
Reference
Catchup Slowdown
44
×
Reference
×
100
=
Catchup Slowdown
100
Reference
When the input command is inactivated, the
reference
returns to its original value ie.
Reference=Reference + 0.
function is activated by
+
Reference
−
Reference
3-16 Reference 2 Source
Option:Function:
See 3-15
Reference 1 Source
description.
[0]No FunctionNo reference signal is defined.
[1]Analog Input 53Use signals from analog input 53 as
reference.
[2] * Analog Input 60Use signals from analog input 60 as
reference.
[8]Pulse input 33Use signals from pulse input as
see parameter group 5-5*
reference,
Pulse Input.
[11] Local Bus
Reference
Use signals from local bus as
reference.
[21] LCP Potentiometer Use signals from LCP potentiometer as
for
reference.
3-14 Preset Relative Reference
Range:Function:
0.00% [-100.00-100.00%] Define fixed value in % to be added
to
variable value defined in 3-18
Relative Scaling Reference Source.
The sum of fixed and variable values
(labeled Y in illustration below) is
multiplied with actual reference
(labeled X in illustration). This
product is added to actual reference
X
+ X ×
Illustration 4.5
Y
100
3-17 Reference 3 Source
Option:Function:
See 3-15 Reference 2 Source
description.
[0]No FunctionNo reference signal is defined.
[1]Analog Input 53Use signals from analog input 53 as
reference.
[2]Analog Input 60Use signals from analog input 60 as
reference.
[8]Pulse input 33Use signals from pulse input as
see parameter group 5-5*
reference,
Pulse Input.
[11] * Local Bus
Reference
Use signals from local bus as
reference.
[21]LCP Potentiometer Use signals from LCP potentiometer
up to three different reference signals.
The sum of these reference signals defines
the actual reference.
[0]No FunctionNo reference signal is defined.
[1] * Analog Input53Use signals from analog input 53 as
reference,
see parameter group 6-1*
Analog Input 1.
[2]Analog Input60Use signals from analog input 60 as
reference,
see parameter group 6-2*
Analog Input 2.
[8]Pulse input 33Use signals from pulse input as reference,
parameter group 5-5* Pulse Input.
see
[11] Local Bus
Reference
[21] LCP Potenti-
ometer
Use signals from local bus as reference,
parameter group 8-9* Bus Feedback.
see
Use signals from LCP potentiometer as
reference,
parameter group 6-8* LCP
Potentiometer.
Reference 2
3-18 Relative Scaling Reference Source
Option:Function:
Select the source for a variable value to
added to the fixed value defined in
be
3-14 Preset Relative Reference.
[0] * No FunctionThe function is disabled
[1]Analog Input 53Select analog input 53 as relative
reference source.
scaling
[2]Analog Input 60Select analog input 60 as relative
reference source.
scaling
[8]Pulse Input 33Select pulse input 33 as relative scaling
reference
[11] Local Bus
Reference
Select local bus ref. as relative scaling
reference
[21] LCP Potentiometer Select LCP potentiometer as relative
scaling
source.
source.
reference source.
22MG02C602 - VLT® is a registered Danfoss trademark
130BA168.10
Ramp (X) S-Ramp
Ratio at Accel.End
Jerk compensated
Ramp (X)
Up Time
Ramp (X)
S-Ramp
Ratio at
Accel.End
Linear
Speed
Ramp (X)
Down Time
Ramp (X)
S-Ramp
Ratio at
Dec.End
Ramp (X) S-Ramp
Ratio at Dec.End
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.4.4 3-4* Ramp 1
A linear ramp is characterized by ramping up at a constant
until the desired motor speed has been reached.
speed
Some overshoot may be experienced when reaching
speed, which may cause speed jerks for a short while
before stabilizing.
An S-ramp accelerates more smoothly thus compensating
for jerks when the speed is reached.
See Illustration 4.6 for a comparison of the two ramp types.
Illustration 4.6
3-41 Ramp1 Ramp-up Time
Range:Function:
Size
related*
[0.05-3600.00 s] Enter ramp-up time from 0 Hz to
rated
in 1-23 Motor Frequency.
Choose a ramp-up time ensuring
that torque limit is not exceeded,
see 4-16 Torque Limit in MotorMode.
3-42 Ramp1 Ramp-down Time
Range:Function:
Size
related*
[0.05-3600.00s]Enter ramp down time from rated
frequency (f
motor
Motor Frequency to 0 Hz.
Choose a ramp down time that
does not cause over-voltage in
inverter due to regenerative
operation of motor. Furthermore,
regenerative torque must not
exceed limit set in 4-17 TorqueLimit in Generator Mode.
4.4.5 3-5* Ramp2
motor frequency (f
) in 1-23
M,N
M,N
) set
44
Ramp Times
Ramp
up: Acceleration time from 0 to nominal motor
frequency (1-23 Motor Frequency).
Deceleration time from nominal motor frequency (1-23Motor Frequency) to 0.
Limitation
Too short ramp up time can result in Torque limit warning
(W12) and/or DC over voltage warning (W7). Ramping is
stopped when the frequency converter has reached Torque
limit motor mode (4-16 Torque Limit in Motor Mode).
Too short ramp down time can result in Torque limit
warning (W12) and/or DC over voltage warning (W7).
Ramping is stopped when the frequency converter reaches
the Torque limit generator mode (4-17 Torque Limit inGenerator Mode) and/or the internal DC over voltage limit.
rated
in 1-23 Motor Frequency.
Choose a ramp-up time ensuring
that torque limit is not exceeded,
see 4-16 Torque Limit in MotorMode.
M,N
) set
MG02C602 - VLT® is a registered Danfoss trademark
23
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
3-52 Ramp2 Ramp-down Time
Range:Function:
Size
related
44
[0.05-3600.00s]Enter ramp down time from rated
frequency (f
motor
Frequency to 0 Hz.
Choose a ramp down time that
does not cause over-voltage in
inverter due to regenerative
operation of motor. Furthermore,
regenerative torque must not
exceed limit set in 4-17 Torque Limitin Generator Mode.
) in 1-23 Motor
M,N
4.4.6 3-8* Other Ramps
This section contains parameters for Jog and Quick Stop
Ramps.
With
a Jog Ramp it is possible to both ramp up and down
whereas, it is only possible to ramp down with the Quick
Stop Ramp.
3-80 Jog Ramp Time
Range:Function:
Size
related*
[0.05-3600.00s]A linear ramp applicable when Jog
activated. See parameter group
is
5-1* Digital Inputs, option [14].
Ramp up time = Ramp down time.
Jog Ramp time starts upon
activation of a jog signal via a
selected digital input or serial
communication port.
3-81 Quick Stop Ramp Time
Range:Function:
Size related* [0.05-3600.00 s] A linear ramp applicable when
is activated. See
Q-stop
parameter group 5-1* DigitalInputs, option [4].
24MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.5 Parameter Group 4: Limits/Warnings
4.5.1 4-** Motor Limits
Parameter group for configuring limits and warning.
4.5.2 4-1* Motor Limits
Use these parameters for defining the speed, torque and
current
working range for the motor.
4-10 Motor Speed Direction
Option:Function:
If terminals 96, 97 and 98 are connected to U,
V
and W respectively, the motor runs
clockwise when seen from the front.
NOTE
This parameter cannot be adjusted while
the motor is running
[0] * ClockwiseThe motor shaft rotates in clockwise direction.
This setting prevents the motor from running
in counterclockwise direction. If 1-00 Configu-
ration Mode is set to close loop control, 4-10
Motor Speed Direction will be automatically set
to clockwise.
[1]Counter-
clockwise
[2] * BothWith this setting the motor can run in both
The motor shaft rotates in counterclockwise
direction.
running in clockwise direction.
directions.
limited to the range: Motor Speed Low Limit
(4-12 Motor Speed Low Limit) to Motor Speed
High Limit (4-14 Motor Speed High Limit). If
1-00 Configuration Mode is set to open loop
control, 4-10 Motor Speed Direction will be
automatically set to both direction
This setting prevents the motor from
However, the output frequency is
4-16 Torque Limit in Motor Mode
Range:Function:
150 %* [0-400%] Set the torque limit for motor operation.
setting is not automatically reset to
The
default when changing settings in 1-00Configuration Mode to 1-25 Load & Motor.
4-17 Torque Limit in Generator Mode
Range:Function:
100 %* [0-400%] Set the torque limit for generator mode
operation.
The
setting is not automatically reset to
default when changing settings in 1-00Configuration Mode to 1-25 Load & Motor.
44
4-12 Motor Speed Low Limit
Range:Function:
0.0 Hz* [0.0-400.0 Hz]
Set the Minimum Motor Speed Limit
corresponding to the minimum output
frequency of the motor shaft.
NOTE
As the minimum output frequency
is an absolute value, it cannot be
deviated from.
4-14 Motor Speed High Limit
Range:Function:
65.0 Hz* [0.0-400.0 Hz]
Set the Maximum
corresponding to the maximum output
frequency of the motor shaft.
NOTE
As the maximum output frequency
is an absolute value, it cannot be
deviated from.
Motor Speed
MG02C602 - VLT® is a registered Danfoss trademark
25
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.5.3 4-4* Adjustable Warnings 2
4-51 Warning Current High
Range:Function:
4-40 Warning Frequency Low
Range:Function:
0.00
Hz*
44
[0.0 Hz-
on the
Depend
value of 4-41
Warning
Frequency High]
4-41 Warning Frequency High
Range:Function:
400.0
Hz*
[Depend on
value of
the
4-40 Warning
Frequency Low
-400.0 Hz]
Use this parameter to set a lower limit
for the frequency range.
When the motor speed falls below this
limit, the display reads SPEED LOW.
Warning bit 10 is set in 16-94 Ext.Status Word. Output Relay can be
configured to indicate this warning.
LCP warning light does not light when
this parameter set limit is reached.
Use this parameter to set a higher
limit for the frequency range.
When the motor speed exceeds this
limit, the display reads SPEED HIGH.
Warning bit 9 is set in 16-94 Ext.Status Word. Output Relay can be
configured to indicate this warning.
LCP warning light does not light
when this parameter set limit is
reached.
26.00A* [0.00-26.00A]Set upper current limit.
4-54 Warning Reference Low
Range:Function:
-4999.000* [-4999.000Depend
value of 4-55
Warning
Reference High]
Use this parameter to set an upper limit
the current range.
for
If current exceeds the set limit, warning
bit 7 is set in 16-94 Ext. Status Word.
Output Relay can be configured to
indicate this warning. LCP warning light
does not light when this parameter's
set limit is reached.
Use this parameter to set a lower
on the
limit for the reference range.
When the actual reference falls
below this limit, the display reads
Reference Low. Warning bit 20 is
set in 16-94 Ext. Status Word.
Output Relay can be configured to
indicate this warning. LCP warning
light does not light when this
parameter set limit is reached.
4.5.4 4-5* Adjustable Warnings
Parameter group containing adjustable warning limits for
current,
Warnings are shown in display, programmed output or
serial bus.
speed, reference and feedback.
4-50 Warning Current Low
Range:Function:
Use this parameter to set a lower limit
the current range.
for
If current drops below the set limit,
warning bit 8 is set in 16-94 Ext. StatusWord.
Output Relay can be configured to
indicate this warning. LCP warning light
does not light when this parameter's set
limit is reached.
0.00A* [0.00-26.00A]Set value for low current limit.
26MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4-55 Warning Reference High
Range:Function:
4999.000* [Depend on
value of
the
4-54 Warning
Reference Low-
4999.000]
Use this parameter to set a higher
limit for the reference range.
When the actual reference exceeds
this limit, the display reads
Reference High. Warning bit 19 is
set in 16-94 Ext. Status Word. Output
Relay can be configured to indicate
this warning. LCP warning light does
not light when this parameter set
limit is reached.
4-56 Warning Feedback Low
Range:Function:
-4999.000* [-4999.000-
Depend
on the
value of 4-57
Warning
Feedback High]
Use this parameter to set a lower
limit for the feedback range.
When the feedback falls below
this limit, the display reads
Feedback Low. Warning bit 6 is set
in 16-94 Ext. Status Word. Output
Relay can be configured to
indicate this warning. LCP warning
light does not light when this
parameter set limit is reached.
4.5.5 4-6* Speed Bypass
In some applications mechanical resonance may occur.
resonance points by creating a bypass. The
Avoid
frequency converter ramps through the bypass area
thereby passing mechanical resonance points quickly.
4-61 Speed Bypass From [Hz]
Array [2]
Range:Function:
0.0 Hz* [0.0-400.0 Hz] Enter either the lower or upper limit of
speeds to be avoided.
the
It does not matter whether Bypass From
or Bypass To is the upper or lower limit,
however the Speed Bypass function is
disabled if the two parameters are set to
the same value.
4-63 Speed Bypass To [Hz]
Array [2]
Range:Function:
0.0 Hz* [0.0-400.0 Hz] Enter either the upper or lower limit of
speed area to be avoided.
the
Make sure to enter the opposite limit of
that in 4-61 Speed Bypass From [Hz].
44
4-57 Warning Feedback High
Range:Function:
4999.000* [Depend on
value of 4-56
the
Warning
Feedback Low
-4999.000]
Use this parameter to set a higher
limit for the feedback range.
When the feedback exceeds this
limit, the display reads Feedback
High. Warning bit 5 is set in 16-94Ext. Status Word. Output Relay can
be configured to indicate this
warning. LCP warning light does
not light when this parameter set
limit is reached.
4-58 Missing Motor Phase Function
Option:Function:
A missing motor phase causes the motor torque to
This monitor may be disabled for special
drop.
purposes (eg. small motors running pure U/f mode),
but as there is a risk of overheating the motor,
Danfoss strongly recommends that the function is On.
A missing motor phase causes the frequency converter
to trip and report an alarm.
NOTE
This parameter cannot be changed while motor
runs.
[0]Off Function is disabled.
[1] * On Function is enabled.
MG02C602 - VLT® is a registered Danfoss trademark
27
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.6 Parameter Group 5: Digital In/Out
4.6.1 5-** Digital In/Out
The following describes all digital input command
functions
and signals.
4.6.2 5-1* Digital Inputs
44
Parameters for configuring the functions for the input
terminals.
The
digital inputs are used for selecting various functions
in the frequency converter. All digital inputs can be set to
the following:
[0]No Operation The frequency converter will not react to
transmitted to the terminal.
signals
[1]ResetReset the frequency converter after a Trip/
Not all alarms can be reset.
Alarm.
[2 ] Coast Inverse Coasting stop, inverted input (NC). The
frequency
mode.
[3]Coast and
inv.
reset
[4]Quick stop
inverse
[5]DC-brake inv.Inverted input for DC braking (NC). Stops
[9]Latched startMotor starts if a pulse is applied for min. 2
[10] ReversingChange direction of motor shaft rotation.
[11] Start
reversing
[12] Enable start
forward
Reset and coasting stop inverted input (NC).
The frequency converter resets and leaves
the motor in free mode.
Inverted input (NC). Generates a stop in
accordance
set in 3-81 Quick Stop Ramp Time. When
motor stops, shaft is in free mode.
motor
certain time period, see 2-01 DC BrakeCurrent. Function is only active when value
in 2-02 DC-Braking Time is different from 0.
function
logical level “1” to “0”. Stop is performed
according to selected ramp time.
= Start, 0 = stop.
1
ms.
activated.
Reversing
rotation; it does not activate start function.
Select [2] Both directions in 4.10 Motor SpeedDirection.
0 = normal, 1 = reversing.
Use for start/stop and for reversing at the
same
allowed at the same time.
0 = stop, 1 = start reversing.
Use if motor shaft must rotate clockwise at
start.
converter leaves the motor in free
with the quick-stop ramp time
by energizing it with DC current for a
when selected terminal goes from
Motor stops when Stop inverse is
signal only changes direction of
time. Signals on start [8] are not
[13] Enable start
reverse
[14] Jog
[16] Preset
reference
0
[17] Preset
reference
1
[18] Preset
reference
2
[19] Freeze
reference
[20] Freeze output Freeze the actual motor frequency (Hz). The
[21] Speed upSelect Speed up and Speed down if digital
[22] Speed downSame as Speed-up [21].
[23] Setup select
0
bit
[26] Precise stop
inverse
terminal 33)
[27] Start, precise
(only
stop
terminal 33)
Use if motor shaft must rotate counterclockwise
Use for activating jog speed. See 3-11 Speed.
Preset reference bit 0, 1 and 2 enables a
bit
choice between one of the eight preset
references according to below.
Same as preset reference bit 0 [16], see 3-10
bit
Preset Reference.
Same as preset reference bit 0 [16].
bit
Freeze actual reference. The frozen reference
is
Speed up and Speed down to be used. If
Speed up/down is used, speed change
always follows ramp 2 (3-51 Ramp2 Ramp-upTime and 3-52 Ramp2 Ramp-down Time) in
the range 3-02 Minimum Reference - 3-03Maximum Reference.
frozen
enable/condition for Speed up and Speed
down to be used. If Speed up/down is used,
the speed change always follows ramp 2 in
the range 4-12 Motor Speed Low Limit - 4-14Motor Speed High Limit.
at start.
now the point of enable/condition for
motor frequency is now the point of
NOTE
When freeze output is active, the
frequency converter cannot be stopped
via a low [8] Start signal. Stop the
frequency converter via a terminal
programmed for Coasting Inverse [2] or
Coast and reset, inverse [3].
of the up/down speed is desired
control
(motor potentiometer). Activate this function
by selecting either Freeze reference or
Freeze output. When Speed-up is activated
for less than 400 ms. the resulting reference
will be increased by 0.1%. If Speed-up is
activated for more than 400 ms. the
resulting reference will ramp according to
ramp 2 in 3-51 Ramp2 Ramp-up Time.
Set 0-10 Active set-up to Multi set-up.
Logic 0 = set up 1, Logic 1 = Set up 2.
Prolong the stop signal to give a precise
(only
stop independent of scan time. The function
is available for terminal 33 only.
As [26], but including Start.
Jog
28MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
[28] Catch upSelect Catch up/Slow down to increase or
the resulting reference value by the
reduce
percentage set in 3-12 Catch Up/Slow Down
Value
[29] Slow downSame as Catch up [28]
[32] Pulse input
terminal
(only
33)
[34] Ramp bit 0
[60] Counter A
(up)
[61] Counter A
(down)
[62] Reset counterAInput for reset of counter A.
[63] Counter B
(up)
[64] Counter B
(down)
[65] Reset counterBInput for reset of counter B.
Select Pulse input when using a pulse
sequence as either reference or feedback.
Scaling is done in parameter group 5-5*
Pulse Input
Logic 0=Ramp1, see parameter group 3-4*
Ramp1
1=Ramp2, see parameter group 3-5*
Logic
Ramp2.
Input for counter A.
Input for counter A.
Input for counter B.
Input for counter B.
5-10 Terminal 18 Digital Input
Option:Function:
[8] * Start Select function from available digital input range.
parameter group 5-1* Digital Inputs for choices.
See
5-11 Terminal 19 Digital Input
Option:Function:
[10] * Reversing Select function from available digital input
range.
parameter group 5-1* Digital Inputs for
See
choices.
5-12 Terminal 27 Digital Input
Option:Function:
[1] * Reset Select function from available digital input range.
parameter group 5-1* Digital Inputs* for choices.
See
5-13 Terminal 29 Digital Input
Option:Function:
[14] * Jog Select function from available digital input range.
See
parameter group 5-1* Digital Inputs for choices.
5-15 Terminal 33 Digital Input
Option:Function:
[16] * Preset bit 0 Select function from available digital input
range.
parameter group 5-1* Digital Inputs for
See
choices.
4.6.3 5-3* Digital Outputs
5-34 On delay, Terminal 42 Digital Output
Range:Function:
0.01 s* [0.00-600.00 s]
5-35 Off delay, Terminal 42 Digital Output
Range:Function:
0.01 s* [0.00-600.00 s]
4.6.4 5-4* Relays
Parameter group for configuring timing and output
functions
[0]No OperationDefault for all digital and relay outputs.
[1]Control ReadyControl board receives supply voltage.
[2]Drive ReadyFrequency converter is ready for
[3]Drive Ready,
[4]Enable/No
[5]Drive RunningMotor is running.
[6]Running/No
[7]Run in Range/No
[8]Run on ref/No
[9]AlarmAn alarm activates output.
[10] Alarm on Warning An alarm or warning activates output.
[12] Out of Current
[13] Below Current,
[14] Above Current,
[16] Below Frequency,
[17] Above Frequency,
[19] Below Feedback,
[20] Above Feedback,
[21] Thermal WarningThermal warning is present when
for relays.
Remote
Warning
Warning
Warning
Warning
Range
low
high
low
high
low
high
operation
control board.
Frequency converter is ready for
operation
Frequency converter is ready for
operation.
given. No warnings are present.
Motor runs, and no warning are
present.
Motor runs within programmed current
ranges,
and 4-51 Warning Current High. No
warnings are present.
Motor runs at reference speed.
Motor current is outside range set in
4-50
Warning Current High.
Motor current is lower than set in 4-50
Warning
Motor current is higher than set in 4-51
Warning
Motor speed is lower than set in 4-40
Warning
Motor speed is higher than set in 4-41
Warning
Feedback is lower than set in 4-56
Warning
Feedback is higher than set in 4-57
Warning
temperature
frequency converter, brake resistor or
thermistor.
and applies supply signal on
in Auto On-mode.
No start or stop command is
see 4-50 Warning Current Low
Warning Current Low and 4-51
Current Low.
Current High.
Frequency Low.
Frequency High.
Feedback Low.
Feedback High.
exceeds limit in motor,
44
MG02C602 - VLT® is a registered Danfoss trademark
29
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
[22] Ready, No
Thermal
[23] Remote Ready, No
Thermal
[24] Ready, Voltage OK Frequency converter is ready for
44
[25] ReverseMotor runs/is ready to run clockwise
[26] Bus OKActive communication (no time-out) via
[28] Brake, No WarnBrake is active, and no warnings are
[29] Brake Ready/No
Fault
[30] Brake Fault (IGBT)Protects frequency converter if fault on
[32] Mech. Brake
Control
[36] Control Word Bit11Bit 11 in control word controls relay.
[41] Below Reference,
low
[42] Above Reference,
high
[51] Local Reference
Active
[52] Remote Reference
Active
[53] No Alarm
[54] Start Cmd Active
[55] Running Reverse
[56] Drive in Hand
Mode
[57] Drive in Auto
Mode
[60] Comparator 0
[61] Comparator 1
[62] Comparator 2
Warning
Warning
Frequency converter is ready for
operation and no over-temperature
warning is present.
Frequency converter is ready for
operation in Auto mode, and no overtemperature warning is present.
operation
specified voltage range.
when
when logic = 1. Output changes as
soon as reversing signal is applied.
serial
present.
Brake is ready for operation, and no
faults
brake
cut out main voltage from frequency
converter.
Enables control of external mechanical
brake,
Mechanical Brake.
Reference is lower than set in 4-54
Warning
Reference is higher than set in 4-55
Warning
See parameter group 13-1*
Comparators.
evaluated as TRUE, output goes high.
Otherwise, it is low.
See parameter group 13-1*Comparators.
evaluated as TRUE, output goes high.
Otherwise, it is low.
See parameter group 13-1*Comparators.
evaluated as TRUE, output goes high.
Otherwise, it is low.
and mains voltage is within
logic = 0 and counter clockwise
communication port.
are present.
modules is present. Use relay to
see parameter group 2-2*
Reference Low.
Reference High.
If comparator 0 is
If comparator 1 is
If comparator 2 is
[63] Comparator 3
[70] Logic Rule 0
[71] Logic Rule 1
[72] Logic Rule 2
[73] Logic Rule 3
[81] SL Digital Output
B
See parameter group 13-1*Comparators.
evaluated as TRUE, output goes high.
Otherwise, it is low.
See parameter group 13-4*
If Logic Rule 1 is evaluated as TRUE,
output goes high. Otherwise, it is low.
See parameter group 13-4*
If Logic Rule 2 is evaluated as TRUE,
output goes high. Otherwise, it is low.
See parameter group 13-4*
If Logic Rule 3 is evaluated as TRUE,
output goes high. Otherwise, it is low.
See parameter group 13-4*
If Logic Rule 3 is evaluated as TRUE,
output goes high. Otherwise, it is low.
See 13-52 SL Control Action. When Smart
Logic
executed, input goes high. When Smart
Logic Action [33] Set dig. out. A low is
executed, input goes low.
If comparator 3 is
Logic Rules.
Logic Rules.
Logic Rules.
Logic Rules.
Action [39] Set dig. out. A high is
5-40 Function Relay
Option:Function:
[0] * No Operation Select function from available relay output
range.
5-41 On delay, Relay
Option:Function:
[0.01 s] * [0.00-600.00 s] Enter the delay of the relay cut-in time.
the Selected Event condition changes
If
before the On delay timer expires, the
relay output is unaffected. The function
to control the relay see 5-40 FunctionRelay.
5-42 Off delay, Relay
Option:Function:
[0.01 s] * [0.00-600.00 s] Enter the delay of the relay cut-off
If the Selected Event condition
time.
changes before the off delay timer
expires, the relay output is unaffected.
The function to control the relay see
5-40 Function Relay.
4.6.5 5-5* Pulse Input
Set 5-15 Terminal 33 Digital Input
Now terminal 33 handles a pulse input in the range from
Low frequency, 5-55 Terminal 33 Low Frequency, to 5-56
Terminal 33 High Frequency. Scale frequency input via 5-57
Terminal 33 Low Ref./Feedb. Value and 5-58 Terminal 33 High
Ref./Feedb. Value.
to choice [32] pulse input.
30MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
5-55 Terminal 33 Low Frequency
Range:Function:
20 Hz* [20-4999 Hz] Enter low frequency corresponding to low
shaft speed (i.e. low reference
motor
value) in 5-57 Terminal 33 Low Ref./Feedb.Value.
5-56 Terminal 33 High Frequency
Range:Function:
5000 Hz* [21-5000 Hz] Enter high frequency corresponding to
high
motor shaft speed (i.e. high
reference value) in 5-58 Terminal 33High Ref./Feedb. Value.
5-57 Terminal 33 Low Ref./Feedb. Value
Range:Function:
0.000* [-4999-4999] Set reference/feedback value
corresponding
value set in 5-55 Terminal 33 LowFrequency.
to low pulse frequency
44
5-58 Terminal 33 High Ref./Feedb. Value
Range:Function:
50.000* [-4999-4999] Set reference/feedback value
corresponding
value set in 5-56 Terminal 33 HighFrequency.
to high pulse frequency
MG02C602 - VLT® is a registered Danfoss trademark
31
Ref./Feedback
[RPM]
Analog input
High Ref./
Feedb. Value'
Low Ref./
Feedb. Value'
'Low Voltage'or
'Low Current'
'High Voltage'or
'High Current'
130BD019.10
1 V5 V10 V
300
600
900
1200
1500
[V]
150
Par 6-xx
Par 6-xx
Par 6-xx
Par 6-xx
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.7 Parameter Group 6: Analog In/Out
4.7.1 6-** Analog In/Out
NOTE
Micro
switch 4 in position U:
6-10 Terminal 53 Low Voltage and 6-11 Terminal 53 High
Voltage are active.
Parameter group for configuring analog inputs and
outputs.
Micro switch 4 in position I:
6-12 Terminal 53 Low Current and 6-13 Terminal 53 High
Current are active.
4.7.2 6-0* Analog I/O Mode
44
Parameter group for setting up the analog I/O configuration.
6-00 Live Zero Timeout Time
Range:Function:
The Live Zero function is used for monitoring
the
signal on an analog input. If the signal
disappears, a Live Zero warning is reported.
10 s* [1-99 s]
Set delay time before Live
is applied (6-01 Live Zero Timeout Time).
If the signal reappears during the set delay,
timer will be reset.
When live zero is detected, the frequency
converter freezes output frequency and starts
Live Zero Timeout timer.
Zero Timeout Function
Illustration 4.7
6-01 Live Zero Timeout Function
Option:Function:
Function is activated if input signal is below
of value set in 6-10 Terminal 53 Low
50%
Voltage, 6-12 Terminal 53 Low Current or 6-22
Terminal 60 Low Current.
[0] * OffFunction is disabled.
[1]Freeze
output
[2]StopFrequency converter ramps down to 0 Hz.
[3]JoggingFrequency converter ramps to jog speed, see
[4]Max SpeedFrequency converter ramps to Motor Speed
[5]Stop and
Trip
4.7.3 6-1* Analog Input 1
Parameters for configuring scaling and limits for analog
input
1 (terminal 53).
32MG02C602 - VLT® is a registered Danfoss trademark
Output frequency remains at value it had
live zero was detected.
when
Remove
restarting frequency converter.
3-11
High
Frequency converter ramps down to 0 Hz
and
and activate reset before restarting the
frequency converter.
live zero error condition before
Jog Speed.
Limit, see 4-14 Motor Speed High Limit.
then trips. Remove live zero condition
Illustration 4.8
6-10 Terminal 53 Low Voltage
Range:Function:
0.07 V* [0.00-9.90 V] Enter low voltage value.
CAUTION
The value must be set to min. 1 V in order to activate the
Live Zero Timeout function in 6-01 Live Zero TimeoutFunction.
This scaling value should correspond to
minimum
Terminal 53 Low Ref./Feedb. Value. See
also 4.4 Parameter Group 3: Reference/Ramps.
reference value set in 6-14
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
6-11 Terminal 53 High Voltage
Range:Function:
This scaling value should correspond to
maximum
Terminal 53 High Ref./Feedb. Value.
10.0 V* [0.10-10.00 V] Enter high voltage value.
reference value set in 6-15
6-12 Terminal 53 Low Current
Range:Function:
This reference signal should
correspond
value set in 6-14 Terminal 53 LowRef./Feedb. Value.
0.14 mA* [0.00-19.90 mA] Enter low current value.
to minimum reference
CAUTION
The value must be set to min. 2 mA in order to activate
the
Live Zero Timeout function in 6-01 Live Zero Timeout
Function.
6-13 Terminal 53 High Current
Range:Function:
This reference signal should
correspond
reference value set in 6-15 Terminal53 High Ref./Feedb. Value.
20.00 mA* [0.10-20.00 mA] Enter high current value.
6-14 Terminal 53 Low Ref./Feedb. Value
Range:Function:
The scaling value corresponding to the
voltage/low current set in 6-10
low
Terminal 53 Low Voltage and 6-12 Terminal
53 Low Current.
0.000* [-4999-4999] Enter analog input scaling value.
6-15 Terminal 53 High Ref./Feedb. Value
Range:Function:
The scaling value corresponding
to
set in 6-11 Terminal 53 High
Voltage and 6-13 Terminal 53
High Current.
50.000* [-4999.000-4999.000] Enter analog input scaling value.
6-16 Terminal 53 Filter Time Constant
Range:Function:
A first-order digital low pass filter time
constant for suppressing electrical noise
in terminal 53. A high time constant
value improves dampening but also
increases time delay through the filter.
0.01 s* [0.01-10.00 s] Enter time constant.
to the maximum
the high voltage/high current
6-19 Terminal 53 Mode
Option:Function:
Select the input to be present on terminal
53.
CAUTION
6-19 Terminal 53 Mode MUST
according to Micro switch 4 setting.
[0] * Voltage Mode
[1]Current Mode
4.7.4 6-2* Analog Input 2
Parameters for configuring scaling and limits for analog
2, terminal 60.
input
6-22 Terminal 60 Low Current
Range:Function:
This reference signal should
correspond
value set in 6-24 Terminal 60 LowRef./Feedb. Value.
0.14 mA* [0.00-19.90 mA] Enter low current value.
to minimum reference
be set
CAUTION
The value must be set to min. 2 mA in order to activate
the
Live Zero Timeout function in 6-01 Live Zero Timeout
Time.
6-23 Terminal 60 High Current
Range:Function:
This reference signal should
correspond
value set in 6-25 Terminal 60 HighRef./Feedb. Value.
20.00 mA* [0.10-20.00 mA] Enter high current value.
6-24 Terminal 60 Low Ref./Feedb. Value
Range:Function:
The scaling value corresponding to the
current set in 6-22 Terminal 60 Low
low
Current.
0.000* [-4999-4999] Enter analog input scaling value.
6-25 Terminal 60 High Ref./Feedb. Value
Range:Function:
The scaling value corresponding to the
current set in 6-23 Terminal 60 High
high
Current.
50.00* [-4999-4999] Enter analog input scaling value.
to the high current
44
MG02C602 - VLT® is a registered Danfoss trademark
33
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
6-26 Terminal 60 Filter Time Constant
4.7.6 6-9* Analog Output
Range:Function:
A first-order digital low pass filter time
constant
in terminal 60. A high time constant
value improves dampening, but also
increases time delay through the filter.
for suppressing electrical noise
NOTE
44
0.01 s* [0.01-10.00 s] Enter time constant.
4.7.5 6-8* LCP Potentiometer
This parameter cannot be changed
while motor runs.
These parameters are for configuring the analog outputs of
frequency converter.
the
6-90 Terminal 42 Mode
Option:Function:
[0] * 0-20 mARange for analog outputs is 0-20 mA
[1]4-20 mARange for analog outputs is 4-20 mA
[2]Digital output Functions as slow reacting digital output.
value to either 0 mA (off) or 20 mA (on),
Set
see 6-92 Terminal 42 Digital Output.
6-91 Terminal 42 Analog Output
Option:Function:
The LCP potentiometer can be selected either as Reference
Resource
or Relative Reference Resource.
NOTE
In
Hand mode the LCP potentiometer functions as local
reference.
6-80 LCP Potmeter Enable
Option:Function:
If LCP Potmeter is disabled, [▲]
local reference, and Potmeter value does not give
any reference in Auto/Hand mode.
[0]Disabled
[1] * Enable
6-81 LCP Potentiometer Low Ref. Value
Range:Function:
The scaling value corresponding to 0.
0.000* [-4999-4999] Enter low reference value.
reference value corresponding to
The
potentiometer turned fully counterclockwise (0 degrees).
6-82 LCP Potentiometer High Ref. Value
Range:Function:
The scaling value corresponding to the
maximum
3-03 Maximum Reference.
50.00* [-4999-4999] Enter high reference value.
The
potentiometer turned fully clockwise (200
degrees).
reference feedback value set in
reference value corresponding to
[▼] can adjust
[0] * No Operation
[10] Output Frequency [0-100
Hz]
[11] Reference (REF min-max)
[12] Feedback (FB min-max)
[13] Motor Current (0-I
[16] Power (0-P
[19] DC Link Voltage (0-1000
V)
[20] Bus Reference [0.0%
-100.0%]
nom
max
)
6-92 Terminal 42 Digital Output
Option:Function:
See parameter group 5-4*
choices and descriptions.
[0] * No Operation
[80] SL Digital
Output
A
See 13-52 SL Control Action. When Smart
Logic Action [38] Set dig. out. A high is
executed, input goes high. When Smart
Logic Action [32] Set dig. out. A low is
executed, input goes low.
6-93 Terminal 42 Output Min. Scale
Range:Function:
0.00% [0.00-200.0%] Scale minimum output of selected analog
signal
maximum signal value. E.g. if 0 mA (or 0
Hz) is desired at 25% of maximum output
value, program 25%. Scaling values up to
100% can never be higher than
corresponding setting in 6-94 Terminal 42
Output Min. Scale.
Select the function for terminal
as an analog output.
42
3-02 Minimum Reference
Minimum Reference.
)
16-37 Inv. Max. Current
1-20 Motor Power is
(motor).
The analog output will follow
reference value set on the
the
RS-485 bus.
Relays, for
at terminal 42 as percentage of
to 3-03
is
I
.
max
P
nom
34MG02C602 - VLT® is a registered Danfoss trademark
130BD020.10
(mA)
0%
20
0/4
100%
Current
Analogue
output
Min Scale
par. 6-93
Variable
for
output
example:
Speed
(RPM)
Analogue
Output
Max Scale
par. 6-94
Parameter Descriptions
Illustration 4.9
6-94 Terminal 42 Output Max. Scale
Range:Function:
100.00%*
[0.00-200.00%]
Scale maximum output of selected
signal at terminal 42. Set value
analog
to maximum value of current signal
output. Scale output to give a current
lower than 20 mA at full scale; or 20
mA at an output below 100% of
maximum signal value.
If 20 mA is the desired output current
at a value between 0-100% of the fullscale output, programme percentage
value in the parameter, i.e. 50% = 20
mA. If a current between 4 and 20
mA is desired at maximum output
(100%), calculate percentage value as
follows:
desired maximum current
i.e.
10 mA =
mA
20
20
× 100 = 200 %
10
VLT® Micro Drive FC 51 Programming Guide
44
× 100 %
MG02C602 - VLT® is a registered Danfoss trademark
35
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.8 Parameter Group 7: Controllers
4.8.1 7-** Controllers
Parameters group for configuring application controls.
4.8.2 7-2* Process Ctrl. Feedback
7-33 Process PI Proportional Gain
Option:Function:
[0.01] * 0.00-10.00 Enter the value for the P proportional gain,
the multiplication factor of the error
i.e.
between the set point and the feedback
signal.
NOTE
0.00 = Off.
Select feedback sources and handling for Process PI
44
Control.
7-34 Process PI Integral Time
Range:Function:
NOTE
Set 3-15
use Analog Input as a feedback signal.
In order to use analog input as a feedback resource, do
not use the same resource as reference resource in 3-15,
3-16 and 3-17.
4.8.3 7-3* Process PI Control
Reference 1 Source to [0] No Function in order to
7-20 Process CL Feedback Resources
Option:Function:
Select input to function as feedback
signal.
[0] * No Function
[1]Analog Input 53
[2]Analog Input 60
[8]Pulse Input 33
[11] Local Bus Ref.
7-30 Process PI Normal/Inverse Control
Option:Function:
[0] * Normal Feedback larger than setpoint result in a speed
reduction.
Feedback
increase.
[1]Inverse Feedback larger than setpoint result in a speed
increase.
Feedback
reduction.
less than setpoint result in a speed
less than setpoint result in a speed
9999.00 s* [0.10-9999.00 s] The integrator provides an
increasing
between the set point and the
feedback signal. The integral time
is the time needed by the
integrator to reach the same gain
as the proportional gain.
gain at a constant error
7-38 Process Feed Forward Factor
Range:Function:
0%* [0-400%] The FF factor sends a part of the reference
around the PI controller which then only
signal
affects part of the control signal.
By activating the FF factor less overshoot and
high dynamics are gained when changing the
setpoint.
This parameter is always active when 1-00Configuration Mode is set to [3] Process.
7-39 On Reference Bandwidth
Range:Function:
5% [0-200% ] Enter the value for the On Reference Bandwidth.
PI control error is the difference between
The
setpoint and feedback and when this is less
than the value set in this parameter the On
Reference is active.
7-31 Process PI Anti Windup
Option:Function:
[0]Disable Regulation of a given error will continue even
when the output frequency cannot be increased/
decreased.
[1] * Enable PI-controller ceases from regulating a given error
the output frequency cannot be increased/
when
decreased.
7-32 Process PI Start Speed
Range:Function:
0.0 Hz* [0.0-200.0 Hz] Until the set motor speed has been
reached
operates in Open Loop mode.
36MG02C602 - VLT® is a registered Danfoss trademark
the frequency converter
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.9 Parameter Group 8: Communication
4.9.1 8-** Communication
Parameter group for configuring communication.
4.9.2 8-0* General Settings
Use this parameter group for configuring the general
settings
for communication.
8-01 Control Site
Option:Function:
[0] * Digital and
Control
Word
[1]Digital OnlyUse digital input as control.
[2]Control Word
Only
Use both digital input and control word
as control.
Use control word only as control.
NOTE
setting in this parameter
The
overrules settings in 8-50 CoastingSelect to 8-56 Preset Reference Select.
8-02 Control Word Source
Option:Function:
[0]NoneFunction is inactive
[1] * FC RS-485 Monitoring control word source is done via
communication port RS-485.
serial
8-03 Control Word Timeout Time
Range:Function:
1.0 s* [0.1-6500 s] Enter time to pass before control word
function (8-04 Control Word Timeout
timeout
Function) must be carried out.
8-04 Control Word Timeout Function
Option:Function:
Select the action to be taken in case of a
timeout.
[0] * OffNo function.
[1]Freeze Output Freeze output until communication
resumes.
[2]StopStop with auto restart when communication
resumes.
[3]JoggingRun motor at jog frequency until communi-
resumes.
cation
[4]Max. SpeedRun motor at max. frequency until
communication
[5]Stop and Trip Stop motor, then reset frequency converter
order to restart either via LCP or digital
in
input.
resumes.
8-06 Reset Control Word Timeout
Option:Function:
Resetting the control word timeout will
any timeout function.
remove
[0] * No Function Control word timeout is not reset.
[1]Do ResetControl word timeout is reset, and parameter
into [0] No Function state.
goes
4.9.3 8-3* FC Port Settings
Parameters for configuring the FC Port.
8-30 Protocol
Option:Function:
Select the protocol to be used. Note that
changing
after powering off the frequency converter.
[0] * FC
[2]Modbus RTU
protocol will not be effective until
8-31 Address
Range:Function:
Select the address for the bus.
1* [1 - Protocol-dependent]FC-bus range is 1-126.
Modbus
range is 1-247.
8-32 FC Port Baud Rate
Option:Function:
Select baud rate for FC Port.
NOTE
Changing
responding to any ongoing bus-requests.
[0]2400 Baud
[1]4800 Baud
[2] * 9600 BaudWhen choosing FC bus in 8-30
[3] * 19200 Baud When choosing Modbus in 8-30
[4]38400 Baud
8-33 FC Port Parity
Option:Function:
[0] * Even Parity (1 stopbit)
[1]Odd parity
[2]No Parity (1 stopbit)Select this for Modbus RTU
[3]No Parity (2 stopbit)
8-35 Minimum Response Delay
Range:Function:
0.010 s* [0.001-0.500 s] Specify minimum delay time between
baud rate will be effective after
This parameter only affects Modbus
FC bus always has even parity.
as
receiving
response.
a request and transmitting a
44
MG02C602 - VLT® is a registered Danfoss trademark
37
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
8-36 Max Response Delay
Range:Function:
5.000 s* [0.010-10.00 s] Specify maximum permissible delay
between transmitting a request
time
and receiving a response. Exceeding
this time delay causes control word
timeout.
44
4.9.4 8-4* FC MC Protocol Set
8-43 FC Port PCD Read Configuration
Array [16]
Option:Function:
the telegrams. This table is
for [0] array and [1]
not
array . For these two arrays,
index 1 is fixed to [7] and
index 2 is fixed to [8]. These
two arrays cannot be
changed by end user.
8-43 FC Port PCD Read Configuration
Array [16]
Option:Function:
[0] * None
[1]1500 Operation Hours
[2]1501 Running Hours
[3]1502 kWh Counter
[4]1600 Control Word
[5]1601 Reference [Unit]
[6]1602 Reference %
[7]1603 Status Word
[8]1605 Main Actual Value [%]
[9]1609 Custom Readout
[10] 1610 Power [kW]
[11] 1611 Power [hp]
[12] 1612 Motor Voltage
[13] 1613 Frequency
[14] 1614 Motor Current
[15] 1615 Frequency [%]
[16] 1618 Motor Thermal
[17] 1630 DC Link Voltage
[18] 1634 Heatsink Temp.
[19] 1635 Inverter Thermal
[20] 1638 SL Controller State
[21] 1650 External Reference
[22] 1651 Pulse Reference
[23] 1652 Feedback [Unit]
[24] 1660 Digital Input 18,19,27,33
[25] 1661 Digtial Input 29
[26] 1662 Analog Input 53(V)
[27] 1663 Analog Input 53(mA)
[28] 1664 Analog Input 60
[29] 1665 Analog Output 42 [mA]
[30] 1668 Freq. Input 33 [Hz]
[31] 1671 Relay Output [bin]
[32] 1672 Counter A
[33] 1673 Counter B
[34] 1690 Alarm Word
[35] 1692 Warning Word
[36] 1694 Ext. Status Word
Select the parameters to be
assigned
telegrams. The number of
available PCDs depends on
to PCD's of
4.9.5 8-5* Digital/Bus
Parameters for configuring control word Digital/Bus
merging.
NOTE
Parameters
[0] Digital and control word.
8-50 Coasting Select
Option:Function:
[0]Digital Input Activation via a digital input.
[1]BusActivation via serial communication port.
[2]LogicAndActivation via serial communication port and
[3] * LogicOrActivation via serial communication port or a
8-51 Quick Stop Select
Option:Function:
[0]Digital Input Activation via a digital input.
[1]BusActivation via serial communication port.
[2]LogicAndActivation via serial communication port and
[3] * LogicOrActivation via serial communication port or a
8-52 DC Brake Select
Option:Function:
[0]Digital Input Activation via a digital input.
[1]BusActivation via serial communication port.
[2]LogicAndActivation via serial communication port and
[3] * LogicOrActivation via serial communication port or a
are only active when 8-01 Control Site, is set to
Select control of coasting function via digital
and/or bus.
input
digital input.
a
input.
digital
Select control of quick stop function via
input and/or bus.
digital
digital input.
a
input.
digital
Select control of DC brake via digital input
and/or
bus.
digital input.
a
input.
digital
38MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
8-53 Start Select
Option:Function:
Select control of start function via digital
and/or bus.
input
[0]Digital Input Activation via a digital input.
[1]BusActivation via serial communication port.
[2]LogicAndActivation via serial communication port and
digital input.
a
[3] * LogicOrActivation via serial communication port or a
input.
digital
8-54 Reversing Select
Option:Function:
Select control of reversing function via digital
and/or bus.
input
[0]Digital Input Activation via a digital input.
[1]BusActivation via serial communication port.
[2]LogicAndActivation via serial communication port and
digital input.
a
[3] * LogicOrActivation via serial communication port or a
input.
digital
8-55 Set-up Select
Option:Function:
Select control of set-up selection via digital
and/or bus.
input
[0]Digital Input Activation via a digital input.
[1]BusActivation via serial communication port.
[2]LogicAndActivation via serial communication port and
digital input.
a
[3] * LogicOrActivation via serial communication port or a
input.
digital
8-81 Bus Error Count
Range:Function:
0 N/A* [0-0 N/A] This parameter shows the number of
telegrams
detected on the bus.
with faults (e.g. CRC fault),
8-82 Slave Messages Rcvd
Range:Function:
0 N/A* [0-0 N/A] This parameter shows the number of valid
telegrams
frequency converter.
addressed to the slave, sent by the
8-83 Slave Error Count
Range:Function:
0 N/A* [0-0 N/A] This parameter shows the number of error
telegrams,
frequency converter.
which could be executed by the
4.9.7 8-9* Bus Feedback
Parameter for configuring bus feedback.
8-94 Bus Feedback 1
Range:Function:
0* [0x8000-0x7FFF] Bus feedback is delivered via FC or
Modbus
this parameter.
by writing the feedback value into
44
8-56 Preset Reference Select
Option:Function:
Select control of Preset Reference selection
digital input and/or bus.
via
[0]Digital Input Activation via a digital input.
[1]BusActivation via serial communication port.
[2]LogicAndActivation via serial communication port and
digital input.
a
[3] * LogicOrActivation via serial communication port or a
input.
digital
4.9.6 8-8* Bus communication diagnostics
These parameters are used for monitoring the Bus
communication
8-80 Bus Message Count
Range:Function:
0 N/A* [0-0 N/A] This parameter shows the number of valid
via the Port.
telegrams
detected on the bus.
MG02C602 - VLT® is a registered Danfoss trademark
39
130BD021.10
State 1
Event 1/
Action 1
State 2
Event 2/
Action 2
Start
event P13-01
State 3
Event 3/
Action 3
State 4
Event 4/
Action 4
Stop
event P13-02
Stop
event P13-02
Stop
event P13-02
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
44
4.10 Parameter Group 13: Smart Logic
4.10.1 13-** Programming Features
4.10.2 13-0* SLC Settings
Use SLC settings to activate, deactivate and reset the
Smart
Smart Logic Control (SLC)is a sequence of user-defined
actions
(13-52 SL Controller Action [X]) executed by the SLC
when the associated user-defined event (13-51 SL ControllerEvent [X]) is set to True.
Events and actions are linked in pairs, meaning that when
an event is true, the linked action is carried out. After this
the next event is evaluated and its belonging action
13-00 SL Controller Mode
Option:Function:
[0] *OffFunction is disabled.
[1]OnSLC is active.
13-01 Start Event
Option:Function:
carried out and so on. Only one event is evaluated at the
time.
[0]False
If an event is evaluated as False, the SLC takes no action
during the scan interval and no other events are evaluated.
It is possible to programme from 1 to 20 events and
[1]True
[2]Running
[3]InRange
actions.
When the last event/action has been executed, the
[4]OnReference
sequence starts again from event/action [0].
[7]Out of Current
[8]BelowILow
[9]AboveIHigh
[16]ThermalWarning
[17]MainsOutOfRangeMains voltage is outside the
[18]Reversing
[19]WarningA warning is active.
Illustration 4.10 Example with Three Events/Actions
[20]Alarm_TripA trip alarm is active.
[21]Alarm_TripLockA trip lock alarm is active.
[22]Comparator 0Use result of comparator 0 in logic
Starting and stopping the SLC
the SLC by selecting [1] On in 13-00 SL Controller
Start
[23]Comparator 1Use result of comparator 1 in logic
Mode The SLC starts evaluating Event 0, and if this is
evaluated as TRUE, the SLC continues its cycle.
The SLC stops when the Stop Event, 13-02 Stop Event, is
[24]Comparator 2Use result of comparator 2 in logic
[25]Comparator 3Use result of comparator 3 in logic
TRUE. The SLC can also be stopped by selecting [0] Off in
13-00 SL Controller Mode.
To reset all SLC parameters select [1] Reset SLC in 13-03
[26]LogicRule 0Use result of logic rule 0 in logic
[27]LogicRule 1Use result of logic rule 1 in logic
Reset Smart Logic Controller and start programming from
scratch.
40MG02C602 - VLT® is a registered Danfoss trademark
[28]LogicRule 2Use result of logic rule 2 in logic
[29]LogicRule 3Use result of logic rule 3 in logic
[33]DigitalInput_18Use value of DI 18 in logic rule.
[34]DigitalInput_19Use value of DI 19 in logic rule.
[35]DigitalInput_27Use value of DI 27 in logic rule.
Logic Control.
Range
Select input to activate Smart Logic
Control.
Enters False in
Enters True in
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
specified
See parameter group 5-4*
for description.
rule.
rule.
rule.
rule.
rule.
rule.
rule.
rule.
logic rule.
logic rule.
Relays [5]
Relays [7]
Relays [8]
Relays [12]
Relays [13]
Relays [14]
Relays [21]
voltage range.
Relays [25]
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
130BD022.10
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
[36]DigitalInput_29Use value of DI 29 in logic rule.
[38]DigitalInput_33
[39] * StartCommand
[40]DriveStopped
[0]False
[1]True
[2]Running
[3]InRange
[4]OnReference
[7]Out of Current
[8]BelowILow
[9]AboveIHigh
[16]ThermalWarning
[17]MainsOutOfRangeMains voltage is outside the
[18]Reversing
[19]WarningA warning is active.
[20]Alarm_TripA trip alarm is active.
[21]Alarm_TripLockA trip lock alarm is active.
[22]Comparator 0Use result of comparator 0 in logic
[23]Comparator 1Use result of comparator 1 in logic
[24]Comparator 2Use result of comparator 2 in logic
[25]Comparator 3Use result of comparator 3 in logic
[26]LogicRule 0Use result of logic rule 0 in logic
[27]LogicRule 1Use result of logic rule 1 in logic
[28]LogicRule 2Use result of logic rule 2 in logic
[29]LogicRule 3Use result of logic rule 3 in logic
[30]SL Timeout0Use result of timer 0 in logic rule.
13-01 Start Event
Option:Function:
This event is True,
converter is started by any means
(digital input or other).
This event is True,
converter is stopped or coasted by
any means (digital input or other).
13-02 Stop Event
Option:Function:
Select input to activate Smart Logic
Control.
Enters False in
Enters True in
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
See parameter group 5-4*
Range
for description.
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
specified
See parameter group 5-4*
for description.
rule.
rule.
rule.
rule.
rule.
rule.
rule.
rule.
13-02 Stop Event
Option:Function:
[31]SL Timeout1Use result of timer 1 in logic rule.
[32]SL Timeout2Use result of timer 2 in logic rule.
if frequency
if frequency
logic rule.
logic rule.
voltage range.
Relays [5]
Relays [7]
Relays [8]
Relays [12]
Relays [13]
Relays [14]
Relays [21]
Relays [25]
[33]DigitalInput_18Use value of DI 18 in logic rule.
[34]DigitalInput_19Use value of DI 19 in logic rule.
[35]DigitalInput_27Use value of DI 27 in logic rule.
[36]DigitalInput_29Use value of DI 29 in logic rule.
[38]DigitalInput_33
[39]StartCommand
[40] * DriveStopped
13-03 Reset SLC
Option:Function:
[0] * Do Not Reset Retains all settings programmed in
[1]Reset SLCReset all group 13 parameters to default
4.10.3 13-04 Comparators
Comparators are used for comparing continuous variables
output frequency, output current, analog input etc.) to
(i.e.
fixed preset values.
Illustration 4.11
In addition, there are digital values that will be compared
fixed time values. See explanation in 13-10 Comparator
to
Operand. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All
parameters in this parameter group are array parameters
with index 0 to 5. Select index 0 toprogramme Comparator
0, select index 1 to programme Comparator 1, and so on.
13-10 Comparator Operand
Array [4]
Option:Function:
[0] * DisabledComparator is disabled.
[1]ReferenceResulting remote reference (not local) as a
MG02C602 - VLT® is a registered Danfoss trademark
This event is True,
converter is started by any means
(digital input or other).
This event is True,
converter is stopped or coasted by
any means (digital input or other).
parameter
settings.
Select variable to be monitored by
comparator.
percentage.
group 13.
if frequency
if frequency
44
41
. . .
. . .
. . .
. . .
Par. 13-43
Logic Rule Operator 2
Par. 13-41
Logic Rule Operator 1
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-44
Logic Rule Boolean 3
130BD023.10
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
44
13-10 Comparator Operand
Array [4]
Option:Function:
[2]FeedbackFeedback in [Hz].
[3]MotorSpeedMotor speed in Hz.
[4]MotorCurrentMotor current in [A].
[6]MotorPowerMotor power in either [kW] or [hp].
[7]MotorVoltageMotor voltage in [V].
[8]DCLinkVoltage DC-link voltage in [V].
[12] AnalogInput53 Expressed as actual value.
[13] AnalogInput60 Expressed as actual value.
[18] PulseInput33Expressed as actual value.
[20] AlarmNumber Shows number of the alarm.
[30] CounterANumber of counts.
[31] CounterBNumber of counts.
13-20 SLC Controller Timer
Array [3]
Range:Function:
0.0 s* [0.0-3600 s]
4.10.5 13-4* Logic Rules
Combine up to three boolean inputs (TRUE/FALSE inputs)
timers, comtors, digital inputs, status bits and events
from
using the logical operators AND, OR, and NOT. Select
boolean inputs for the calculation in LC-40 Logic Rule
Boolean 1, LC-42 Logic Rule Boolean 2 and LC-44 Logic Rule
Boolean 3. Define the operators used to logically combine
13-11 Comparator Operator
Array [4]
the selected inputs in LC-41 Logic Rule Operator 1 and
LC-43 Logic Rule Operator 2.
Option:Function:
Select operator to be used in comparison.
[0]Less Than <
[1] * Approxi-
mately
≈
[2]Greater Than>Inverse logic of option [0].
Result of evaluation is True
selected in 13-10 Comparator Operand is
smaller than fixed value in 13-12Comparator Value. Result is False if variable
selected in 13-10 Comparator Operand is
greater than fixed value in 13-12Comparator Value.
Result of evaluation is True if variable
equals
selected in 13-10 Comparator Operand is
approximately equal to fixed value in 13-12Comparator Value.
if
variable
Illustration 4.12
Priority of calculation
The
results of LC-40 Logic Rule Boolean 1, LC-41 Logic Rule
Operator 1 and LC-42 Logic Rule Boolean 2 are calculated
first. The outcome (TRUE/FALSE) of this calculation is
13-12 Comparator Value
Array [4]
Range:Function:
0.0* [-9999-9999] Enter “trigger level” for variable monitored
this comparator.
by
combined with the settings of LC-43 Logic Rule Operator 2
and LC-44 Logic Rule Boolean 3, yielding the final result
(TRUE/FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [4]
Option:Function:
4.10.4 13-2* Timers
Use the timer results to define an event (13-51
Action) or as boolean input in a logic rule (13-40 Logic Rule
Boolean 1, 13-42 Logic Rule Boolean 2 or 13-44 Logic Rule
Boolean 3).
When timer value has elapsed timer changes state from
False to True.
42MG02C602 - VLT® is a registered Danfoss trademark
SL Controller
[0] * False
[1]True
[2]Running
[3]InRange
[4]OnReference
[7]Out of Current
Range
[8]BelowILow
Enter value to define duration of the False
from programmed timer. A timer is
output
only False if it is started by an action and
until the given timer value has elapsed.
Select first boolean input for selected
rule.
logic
Enters False in
Enters True in
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
logic rule.
logic rule.
Relays [5]
Relays [7]
Relays [8]
Relays [12]
Relays [13]
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
13-40 Logic Rule Boolean 1
Array [4]
Option:Function:
[9]AboveIHigh
[16] ThermalWarning
[17] MainsOutOfRangeMains voltage is outside the specified
[18] Reversing
[19] WarningA warning is active.
[20] Alarm_TripA trip alarm is active.
[21] Alarm_TripLockA trip lock alarm is active.
[22] Comparator 0Use result of comparator 0 in logic
[23] Comparator 1Use result of comparator 1 in logic
[24] Comparator 2Use result of comparator 2 in logic
[25] Comparator 3Use result of comparator 3 in logic
[26] LogicRule 0Use result of logic rule 0 in logic rule.
[27] LogicRule 1Use result of logic rule 1 in logic rule.
[28] LogicRule 2Use result of logic rule 2 in logic rule.
[29] LogicRule 3Use result of logic rule 3 in logic rule.
[30] SL Timeout0Use result of timer 0 in logic rule.
[31] SL Timeout1Use result of timer 1 in logic rule.
[32] SL Timeout2Use result of timer 2 in logic rule.
[33] DigitalInput_18Use value of DI 18 in logic rule.
[34] DigitalInput_19Use value of DI 19 in logic rule.
[35] DigitalInput_27Use value of DI 27 in logic rule.
[36] DigitalInput_29Use value of DI 29 in logic rule.
[38] DigitalInput_33Use value of DI 33 in logic rule
[39] StartCommand
[40] DriveStopped
See parameter group 5-4*
for description.
See parameter group 5-4*
for description.
range.
voltage
See parameter group 5-4*
for description.
rule.
rule.
rule.
rule.
This event is True,
converter is started by any means
(digital input or other).
This event is True,
converter is stopped or coasted by
any means (digital input or other).
Relays [14]
Relays [21]
Relays [25]
if frequency
if frequency
13-41 Logic Rule Operator 1
Array [4]
Option:Function:
[6]Not orEvaluates expression NOT [13-40] OR [13-42].
[7]Not and not Evaluates expression NOT [13-40] AND NOT
[13-42].
[8]Not or notEvaluates expression NOT [13-40] OR NOT
[13-42].
13-42 Logic Rule Boolean 2
Array [4]
Option: Function:
Select second boolean input for selected logic rule.
See 13-40
descriptions.
Logic Rule Boolean 1 for choices and
13-43 Logic Rule Operator 2
Array [4]
Option:Function:
Select second logical operator to use on
inputs calculated in 13-40 Logic Rule
boolean
Boolean 1, 13-41 Logic Rule Operator 1, and
13-42 Logic Rule Boolean 2 and the boolean
input from 13-42 Logic Rule Boolean 2.
[0] * Disabled
[1]AndEvaluates expression [13-40/13-42] AND
[2]OrEvaluates expression [13-40/13-42] OR [13-44].
[3]And notEvaluates expression [13-40/13-42] AND NOT
[4]Or notEvaluates expression [13-40/13-42] OR NOT
[5]Not andEvaluates expression NOT [13-40/13-42] and
[6]Not orEvaluates expression NOT [13-40/13-42] OR
[7]Not and not Evaluates expression NOT [13-40/13-42] AND
[8]Not or notEvaluates expression NOT [13-40/13-42] OR
Ignores 13-44
[13-44].
[13-44].
[13-44].
[13-44].
[13-44].
[13-44].
NOT
[13-44].
NOT
Logic Rule Boolean 3.
44
13-41 Logic Rule Operator 1
Array [4]
Option:Function:
Select first logical operator to use on boolean
from 13-40 Logic Rule Boolean 1 and
inputs
13-42 Logic Rule Boolean 2.
[0] * Disabled
[1]AndEvaluates expression [13-40] AND [13-42].
[2]OrEvaluates expression [13-40] OR [13-42].
[3]And notEvaluates expression [13-40] AND NOT [13-42].
[4]Or notEvaluates expression [13-40] OR NOT [13-42].
[5]Not andEvaluates expression NOT [13-40] and [13-42].
Ignores 13-42
Rule Operator 2 and 13-44 Logic Rule Boolean
3.
Logic Rule Boolean 2, 13-43 Logic
MG02C602 - VLT® is a registered Danfoss trademark
13-44 Logic Rule Boolean 3
Array [4]
Option: Function:
Select third boolean input for selected logic rule.
13-40
See
descriptions.
Logic Rule Boolean 1 for choices and
43
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.10.6 13-5* States
13-51 SL Controller Event
Array [20]
Option: Function:
Select boolean input to define Smart Controller Event.
18.5 kW and 22 kW frequency converter, the option [4]
is not available.
14-03 Overmodulation
Option:Function:
This feature allows more accurate speed control near
over nominal speed (50/60 Hz). Another
and
advantage with overmodulation is the ability of
staying at a constant speed even though main is
dropping.
[0]Off Disables the overmodulation function to avoid torque
on the motor shaft.
ripple
[1] * On Connects the overmodulation function to obtain an
voltage up to 15% greater than mains voltage.
output
4.11.3 14-1* Mains Monitoring
This parameter group supplies functions for handling
imbalance
14-12 Functions at Mains Imbalance
Option:Function:
[0] * TripFrequency converter trips.
[1]Warning Frequency converter issues a warning.
[2]Disabled No action taken.
Parameters for configuring auto reset handling, special trip
handling
on mains.
Operation under severe mains imbalance
conditions
Select function to take place when severe mains
imbalance is detected.
reduces drive lift time.
and control card self test or initialisation.
14-20 Reset Mode
Option:Function:
Select reset function after tripping. Once
the frequency converter can be
reset,
restarted.
[0] * Manual ResetPerform reset via [Reset] or digital inputs.
[1]AutoReset 1Performs one automatic reset after
tripping.
[2]AutoReset 2Performs two automatic resets after
tripping.
[3]AutoReset 3Performs three automatic resets after
tripping.
[4]AutoReset 4Performs four automatic resets after
tripping.
[5]AutoReset 5Performs five automatic resets after
tripping.
[6]AutoReset 6Performs six automatic resets after
tripping.
[7]AutoReset 7Performs seven automatic resets after
tripping.
[8]AutoReset 8Performs eight automatic resets after
tripping.
[9]AutoReset 9Performs nine automatic resets after
tripping.
[10] AutoReset 10Performs ten automatic resets after
tripping.
[11] AutoReset 15Performs fifteen automatic resets after
tripping.
[12] AutoReset 20Performs twenty automatic resets after
tripping.
[13] Infinite auto
reset
[14] Reset at
power-up
Performs an infinite number of automatic
after tripping.
resets
Trip-lock alarm can be reset at power up.
CAUTION
Motor may start without warning.
14-21 Automatic Restart Time
Range:Function:
10 s* [0-600 s] Enter time interval from trip to start of
automatic
active when 14-20 Reset Mode, is set to [1] to[13] Automatic Reset.
reset function. This parameter is
14-22 Operation Mode
Option:Function:
Use this parameter for specifying normal
operation
except 15-03 Power Ups, 15-04 Over Temps
and 15-05 Over Volts.
[0] * Normal
Operation
[2]InitializationResets all parameters to default settings,
Frequency converter runs normal operation.
except
Temps and 15-05 Over Volts. Frequency
converter resets during next power-up.
or to initialize all parameters,
for 15-03 Power Ups, 15-04 Over
44
MG02C602 - VLT® is a registered Danfoss trademark
45
Parameter Descriptions
14-22 Operation Mode
Option:Function:
14-22 Operation Mode
setting [0] Normal Operation.
14-26 Action at Inverter Fault
Option:Function:
[0]TripWhen the frequency converter detects an over-
it will trip immediately.
44
[1] * Warning When the frequency converter detects an over-
voltage,
NOTE
It is recommended to choose [0] Trip in
hoisting applications.
voltage, it will give warning immediately. After
protection filter, it will trip.
VLT® Micro Drive FC 51 Programming Guide
also
reverts to default
NOTE
It is recommended to disable protectionmode in hoisting applications.
4.11.4 15-4* Drive Identification
Parameters containing read only information about the
hardware
converter.
14-41 AEO Minimum Magnetization
Range:Function:
66%* [40-75%] Enter the minimum allowable magnetization
and software configuration of the frequency
AEO. Selecting a low value reduces energy
for
loss in the motor, but may also reduce
resistance to sudden load changes.
46MG02C602 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.12 Parameter Group 15: Drive Information
Parameter group containing information on operating
hardware configuration, software version, etc.
data,
15-00 Operating Time
Range:Function:
0 days* [0-65535
days]
15-01 Running Hours
Range:Function:
0* [0- 2147483647] View running hours of motor.
15-02 kWh Counter
Range:Function:
0 [0-65535] View power consumption in kWh as a mean value
over
Reset counter in 15-06 Reset kWh Counter.
15-03 Power Ups
Range:Function:
0 [0-2147483647] View number of times frequency converter
15-04 Over Temps
Range:Function:
0 [0-65535] View number of times frequency converter has
tripped
Counter cannot be reset.
15-05 Over Volts
Range:Function:
0* [0-65535] View number of times frequency converter has
tripped
Counter cannot be reset.
15-06 Reset kWh Counter
Option:Function:
[0] *Do Not ResetCounter is not reset.
[1]Reset CounterCounter is reset.
View how many days the frequency
converter
The value is saved at power off and
cannot be reset.
The value is saved at power off and can be
reset in 15-07 Reset Running Hours Counter.
one hour.
been powered up.
has
Counter cannot be reset.
due to over temperature.
due to over voltage.
has been powered up.
4.12.1 15-3* Fault Log
This parameter group contains a fault log showing reasons
the ten latest trips.
for
15-30 Fault Log: Error Code
Range:Function:
0 [0-255]
View error code and look it up in VLT
Guide, MG02B.
Micro Quick
4.12.2 15-4* Drive Identification
Parameters containing read only information about the
hardware
converter.
15-40 FC Type
Option:Function:
15-41 Power Section
Option:Function:
15-42 Voltage
Option:Function:
15-43 Software Version
Option:Function:
15-46 Frequency Converter Ordering No
Option: Function:
15-48 LCP ID No
Option:Function:
15-51 Frequency Converter Serial Number
Option:Function:
and software configuration of the frequency
View FC type.
View power section of frequency converter.
View voltage of frequency converter.
View software version of frequency converter.
View ordering number for re-ordering frequency
converter
in its original configuration.
View LCP ID number.
View frequency converter serial number.
44
15-07 Reset Running Hours Counter
Option:Function:
[0] *Do Not ResetCounter is not reset.
[1]Reset CounterCounter is reset.
MG02C602 - VLT® is a registered Danfoss trademark
47
Parameter Descriptions
VLT® Micro Drive FC 51 Programming Guide
4.13 Parameter Group 16: Data Readouts
16-13 Frequency
Range:Function:
16-00 Control Word
0.0 Hz* [0.0-400.0 Hz]View output frequency in Hz.
Range:Function:
0* [0-65535] View latest valid control word sent to frequency
converter
via serial communication port.
16-01 Reference [Unit]
Range:Function:
44
0.000* [-4999.000-4999.000] View total remote reference. Total
reference is sum of pulse, analog,
preset, LCP potentiometer, local
bus and freeze reference.
16-02 Reference %
Range:Function:
0.0* [-200.0-200.0%] View total remote reference in percent.
reference is sum of pulse, analog,
Total
preset, LCP potentiometer, local bus and
freeze reference.
16-14 Motor Current
Range:Function:
0.00 A* [0.00-655 A]View motor phase current.
16-15 Frequency [%]
Range:Function:
0.00* [-100.00-100.00%] View a two-byte word reporting actual
frequency as a percentage of
motor
4-14 Motor Speed High Limit
16-18 Motor Thermal
Range:Function:
0%* [0-100%] View calculated thermal motor load as
percentage
of estimated thermal motor load.
4.13.2 16-3* Drive Status
16-03 Status Word
Range:Function:
0* [0-65535] View status word sent to frequency converter via
communication port.
serial
16-30 DC Link Voltage
Range:Function:
0 V* [0-10000 V]View DC-link voltage.
16-05 Main Actual Value %
Range:Function:
0.00* [-100.00-100.00%] View two-byte word sent with status
to bus Master reporting main
word
actual value.
16-09 Custom Readout
Range:Function:
0.00* [0.00-9999.00%]
Customized readout based on the
of 0-31 Custom Readout Min
settings
Scale, 0-32 Custom Readout Max Scale
and 4-14 Motor Speed High Limit
4.13.1 16-1* Motor Status
16-10 Power [kW]
Range:Function:
0 kW* [0-99 kW]View output power in kW.
16-11 Power [hp]
Range:Function:
0 hp [0-99 hp ]View output power in hp.
16-34 Heat Sink Temp.
Range:Function:
0*
[0-255°C]
View heat sink temperature of frequency
converter.
16-35 Inverter Thermal
Range:Function:
0%* [0-100%] View calculated thermal load on frequency
0-10 Active Set-up
*[1] Setup 1
[2] Setup 2
[9] Multi Setup
0-11 Edit Set-up
*[1] Setup 1
[2] Setup 2
[9] Active Setup
0-12 Link Setups
[0] Not Linked
*[20] Linked
0-31 Custom Readout Min Scale
0.00–9999.00
*0.00
0-32 Custom Readout Max Scale
0.00–9999.00
*100.0
0-4* LCP Keypad
0-40 [Hand on] Key on LCP
[0] Disabled
*[1] Enabled
0-41 [Off / Reset] Key on LCP
[0] Disable All
*[1] Enable All
[2] Enable Reset Only
0-42 [Auto on] Key on LCP
[0] Disabled
*[1] Enabled
0-5* Copy/Save
0-50 LCP Copy
*[0] No copy
[1] All to LCP
[2] All from LCP
[3] Size indep. from LCP
0-51 Set-up Copy
*[0] No copy
[1] Copy from setup 1
[2] Copy from setup 2
[9] Copy from Factory setup
0-6* Password
0-60 (Main) Menu Password
0-999 *0
0-61 Access to Main/Quick Menu
w/o Password
*[0] Full access
[1] LCP: Read Only
[2] LCP: No Access
1-** Load/Motor
1-0* General Settings
1-00 Configuration Mode
*[0] Speed open loop
[3] Process
1-01 Motor Control Principle
[0] U/f
plus
*[1] VVC
1-03 Torque Characteristics
*[0] Constant torque
[2] Automatic Energy Optim.
1-05 Local Mode Configuration
[0] Speed Open Loop
*[2] As config in par. 1-00
1-2* Motor Data
1-20 Motor Power [kW] [HP]
[1] 0.09 kW/0.12 HP
[2] 0.12 kW/0.16 HP
[3] 0.18 kW/0.25 HP
[4] 0.25 kW/0.33 HP
[5] 0.37 kW/0.50 HP
[6] 0.55 kW/0.75 HP
[7] 0.75 kW/1.00 HP
[8] 1.10 kW/1.50 HP
[9] 1.50 kW/2.00 HP
[10] 2.20 kW/3.00 HP
[11] 3.00 kW/4.00 HP
[12] 3.70 kW/5.00 HP
[13] 4.00 kW/5.40 HP
[14] 5.50 kW/7.50 HP
[15] 7.50 kW/10.00 HP
[16] 11.00 kW/15.00 HP
[17] 15.00 kW/20.00 HP
[18] 18.50 kW/25.00 HP
[19] 22.00 kW/29.50 HP
[20] 30.00 kW/40.00 HP
1-22 Motor Voltage
50-999 V * 230-400 V
1-23 Motor Frequency
20-400 Hz *50 Hz
1-24 Motor Current
0.01-100.00 A *Motortype dep.
1-25 Motor Nominal Speed
100-9999 rpm * Motortype dep.
1-29 Automatic Motor Tuning
(AMT)
*[0] Off
[2] EnableAMT
1-3* Adv. Motor Data
1-30 Stator Resistance (Rs)
[Ohm] * Dep. on motor data
1-33 Stator Leakage Reactance
(X1)
[Ohm] * Dep. on motor data
1-35 Main Reactance (Xh)
[Ohm] * Dep. on motor data
1-5* Load Indep. Setting
1-50 Motor Magnetisation at 0
Speed
0-300% *100%
1-52 Min Speed Norm. Magnet.
[Hz]
0.0-10.0 Hz *0.0 Hz
1-55 U/f Characteristic - U
0-999.9 V
1-56 U/f Characteristic - F
0-400 Hz
-400-399% *100%
1-63 Slip Compensation Time
Constant
0.05-5.00 s *0.10 s
1-7* Start Adjustments
1-71 Start Delay
0.0-10.0 s * 0.0 s
1-72 Start Function
[0] DC hold/delay time
[1] DC brake/delay time
*[2] Coast/delay time
1-73 Flying Start
*[0] Disabled
[1] Enabled
1-8* Stop Adjustments
1-80 Function at Stop
*[0] Coast
[1] DC hold
1-82 Min Speed for Funct. at
Stop [Hz]
0.0-20.0 Hz *0.0 Hz
1-9* Motor Temperature
1-90 Motor Thermal Protection
*[0] No protection
[1] Thermistor warning
[2] Thermistor trip
[3] Etr warning
[4] Etr trip
1-93 Thermistor Resource
*[0] None
[1] Analog input 53
[6] Digital input 29
2-** Brakes
2-0* DC-Brake
2-00 DC Hold Current
0-150% *50%
2-01 DC Brake Current
0-150% *50%
2-02 DC Braking Time
0.0-60.0 s *10.0 s
2-04 DC Brake Cut In Speed
0.0-400.0 Hz * 0.0 Hz
2-1* Brake Energy Funct.
2-10 Brake Function
*[0] Off
[1] Resistor brake
[2] AC brake
2-11 Brake Resistor (ohm)
5-5000 *5
2-16 AC Brake, Max current
0-150% *100%
2-17 Over-voltage Control
*[0] Disabled
[1] Enabled (not at stop)
[2] Enabled
2-2* Mechanical Brake
2-20 Release Brake Current
0.00-100.0 A *0.00 A
2-22 Activate Brake Speed [Hz]
0.0-400.0 Hz * 0.0 Hz
3-** Reference / Ramps
3-0* Reference Limits
3-00 Reference Range
*[0] Min to Max
[1] -Max to+Max
3-02 Minimum Reference
-4999-4999 *0.000
3-03 Maximum Reference
-4999-4999 *50.00
Table 5.1
50MG02C602 - VLT® is a registered Danfoss trademark
Parameter Lists
VLT® Micro Drive FC 51 Programming Guide
3-1* References
Preset Reference
3-10
-100.0-100.0% *0.00%
3-11 Jog Speed [Hz]
0.0-400.0 Hz *5.0 Hz
3-12 Catch up/slow Down Value
0.00-100.0% *0.00%
3-14 Preset Relative Reference
-100.0-100.0% *0.00%
3-15 Reference Resource 1
[0] No function
*[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
[11] Local bus ref
[21] LCP Potentiometer
3-16 Reference Resource 2
[0] No function
[1] Analog Input 53
*[2] Analog input 60
[8] Pulse input 33
*[11] Local bus ref
[21] LCP Potentiometer
3-17 Reference Resource 3
[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
*[11] Local bus ref
[21] LCP Potentiometer
3-18 Relative Scaling Ref.
Resource
*[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
[11] Local bus ref
[21] LCP Potentiometer
3-4* Ramp 1
3-40 Ramp 1 Type
*[0] Linear
[2] Sine2 ramp
3-41 Ramp 1 Ramp up Time
0.05-3600 s *3.00 s (10.00 s1))
3-42 Ramp 1 Ramp Down Time
0.05-3600 s *3.00 s (10.00 s 1))
3-5* Ramp 2
3-50 Ramp 2 Type
*[0] Linear
[2] Sine2 ramp
3-51 Ramp 2 Ramp up Time
0.05-3600 s *3.00 s (10.00 s 1))
3-52 Ramp 2 Ramp down Time
0.05-3600 s *3.00 s (10.00 s1))
1)
M4
and M5 only
3-8* Other Ramps
3-80
Jog Ramp Time
0.05-3600 s *3.00 s (10.00 s1))
3-81 Quick Stop Ramp Time
0.05-3600 s *3.00 s(10.00 s1))
4-** Limits/Warnings
4-1* Motor Limits
4-10 Motor Speed Direction
[0] Clockwise if Par. 1-00 is set to
[3]
[1] CounterClockwise
*[2] Both if Par. 1-00 is set to [0]
4-12 Motor Speed Low Limit [Hz]
0.0-400.0 Hz * 0.0 Hz
4-14 Motor Speed High Limit [Hz]
0.00-Value of 4-41 Hz *0.0 Hz
4-41 Warning Frequency High
Value of 4-40-400.0 Hz *400.0 Hz
4-5* Adj. Warnings
4-50 Warning Current Low
0.00-100.00 A *0.00 A
4-51 Warning Current High
0.00-100.00 A *100.00 A
4-54 Warning Reference Low
-4999.000-Value of 4-55
*-4999.000
4-55 Warning Reference High
Value of 4-54-4999.000 *4999.000
4-56 Warning Feedback Low
-4999.000-Value of 4-57
*-4999.000
4-57 Warning Feedback High
Value of 4-56-4999.000 *4999.000
4-58 Missing Motor Phase
Function
[0] Off
*[1] On
4-6* Speed Bypass
4-61 Bypass Speed From [Hz]
0.0-400.0 Hz * 0.0 Hz
4-63 Bypass Speed To [Hz]
0.0-400.0 Hz * 0.0 Hz
5-1* Digital Inputs
5-10 Terminal 18 Digital Input
[0] No function
[1] Reset
[2]
Coast inverse
[3] Coast and reset inv.
[4] Quick stop inverse
[5] DC-brake inv.
[6] Stop inv
*[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[12] Enable start forward
[13] Enable start reverse
[14] Jog
[16-18] Preset ref bit 0-2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Setup select bit 0
[28] Catch up
[29] Slow down
[34] Ramp bit 0
[60] Counter A (up)
[61] Counter A (down)
[62] Reset counter A
[63] Counter B (up)
[64] Counter B (down)
[65] ResetCounter B
5-11 Terminal 19 Digital Input
See par. 5-10. *[10] Reversing
5-12 Terminal 27 Digital Input
See par. 5-10. * [1] Reset
5-13 Terminal 29 Digital Input
See par. 5-10. * [14] Jog
5-15 Terminal 33 Digital Input
See par. 5-10. * [16] Preset ref bit
0
[26] Precise Stop Inverse
[27] Start, Precise Stop
[32] Pulse Input
5-3* Digital Outputs
5-34 On Delay, Terminal 42
Digital Output
0.00-600.00 s *0.01 s
5-35 Off Delay, Terminal 42
Digital Output
0.00-600.00 s *0.01 s
5-4* Relays
5-40 Function Relay
*[0] No operation
[1] Control ready
[2] Drive ready
[3] Drive ready, Remote
[4] Enable/No warning
[5] Drive running
[6] Running/No warning
[7] Run in range/No warning
[8] Run on ref/No warning
[9] Alarm
[10] Alarm or warning
[12] Out of current range
[13] Below current, low
[14] Above current, high
[16] Below frequency, low
[17] Above frequency, high
[19] Below feedback, low
[20] Above feedback, high
[21] Thermal warning
[22] Ready, No thermal warning
[23] Remote ready, No thermal
warning
[24] Ready, Voltage ok
[25] Reverse
[26] Bus ok
[28] Brake,NoWarn
[29] Brake ready/NoFault
[30] BrakeFault (IGBT)
[32] Mech.brake control
[36] Control word bit 11
[41] Below reference, low
[42] Above reference, high
[51] Local ref. active
[52] Remote ref. active
[53] No alarm
[54] Start cmd active
[55] Running reverse
[56] Drive in hand mode
[57] Drive in auto mode
[60-63] Comparator 0-3
[70-73] Logic rule 0-3
[81] SL digital output B
5-41 On Delay, Relay
0.00-600.00 s *0.01 s
5-42 Off Delay, Relay
0.00-600.00 s *0.01 s
5-5* Pulse Input
5-55 Terminal 33 Low Frequency
20-4999 Hz * 20 Hz
5-56 Terminal 33 High Frequency
21-5000 Hz *5000 Hz
5-57 Term. 33 Low Ref./Feedb.
Value
-4999-4999 *0.000
5-58 Term. 33 High Ref./Feedb.
Value
-4999-4999 *50.000
6-** Analog In/Out
55
Table 5.2
MG02C602 - VLT® is a registered Danfoss trademark
51
Parameter Lists
VLT® Micro Drive FC 51 Programming Guide
6-0* Analog I/O Mode
Live Zero Timeout Time
6-00
1-99 s *10 s
6-01 Live Zero TimeoutFunction
*[0] Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max speed
[5] Stop and trip
6-1* Analog Input 1
6-10 Terminal 53 Low Voltage
55
0.00-9.99 V *0.07 V
6-11 Terminal 53 High Voltage
0.01-10.00 V *10.00 V
6-12 Terminal 53 Low Current
0.00-19.99 mA *0.14 mA
6-13 Terminal 53 High Current
0.01-20.00 mA *20.00 mA
6-14 Term. 53 Low Ref./Feedb.
Value
-4999-4999 *0.000
6-15 Term. 53 High Ref./Feedb.
Value
-4999-4999 *50.000
6-16 Terminal 53 Filter Time
Constant
0.01-10.00 s *0.01 s
6-19 Terminal 53 mode
*[0] Voltage mode
[1] Current mode
6-2* Analog Input 2
6-22 Terminal 60 Low Current
0.00-19.99 mA *0.14 mA
6-23 Terminal 60 High Current
0.01-20.00 mA *20.00 mA
6-24 Term. 60 Low Ref./Feedb.
Value
-4999-4999 *0.000
6-25 Term. 60 High Ref./Feedb.
Value
-4999-4999 *50.00
6-26 Terminal 60 Filter Time
Constant
[1] 4-20 mA
[2] Digital Output
6-91 Terminal 42 Analog Output
*[0] No operation
[10] Output Frequency
[11] Reference
[12] Feedback
[13] Motor Current
[16] Power
[20] Bus Reference
6-92 Terminal 42 Digital Output
See par. 5-40
*[0] No Operation
[80] SL Digital Output A
6-93 Terminal 42 Output Min
Scale
0.00-200.0%
*0.00%
6-94 Terminal 42 Output Max
Scale
0.00-200.0% *100.0%
7-** Controllers
7-2* Process Ctrl. Feedb
7-20 Process CL Feedback 1
Resource
*[0] NoFunction
[1] Analog Input 53
[2] Analog input 60
[8] PulseInput33
[11] LocalBusRef
7-3* Process PI
Ctrl. 7-30 Process PI Normal/
Inverse Ctrl
*[0] Normal
[1] Inverse
7-31 Process PI Anti Windup
[0] Disable
*[1] Enable
7-32 Process PI Start Speed
0.0-200.0 Hz *0.0 Hz
7-33 Process PI Proportional Gain
0.00-10.00 *0.01
7-34 Process PI Integral Time
0.10-9999 s *9999 s
7-38 Process PI Feed Forward
Factor
0-400% *0%
7-39 On Reference Bandwidth
0-200% *5%
8-** Comm. and Options
8-0* General Settings
8-01 Control Site
*[0] Digital and ControlWord
[1] Digital only
[2] ControlWord only
8-02 Control Word Source
[0] None
*[1] FC RS485
8-03 Control Word Timeout Time
0.1-6500 s *1.0 s
8-04 Control Word Timeout
Function
*[0] Off
[1] Freeze Output
[2] Stop
[3] Jogging
[4] Max. Speed
[5] Stop and trip
8-06 Reset Control Word Timeout
*[0] No Function
[1] Do reset
8-3* FC Port Settings
8-30 Protocol
*[0] FC
[2] Modbus
8-31 Address
1-247 *1
8-32 FC Port Baud Rate
[0] 2400 Baud
[1] 4800 Baud
*[2] 9600 Baud For choosing FC
bus in 8-30
* [3] 19200 Baud For choosing
FC bus in 8-30
*[4] 38400 Baud
8-33 FC Port Parity
*[0] Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
0.001-0.5 *0.010 s
8-36 Max Response Delay
0.100-10.00 s *5.000 s
8-4* FC MC protocol set
8-43 FC Port PCD Read Configuration
*[0] None Expressionlimit
[1] [1500] Operation Hours
[2] [1501] Running Hours
[3] [1502] kWh Counter
[4] [1600] Control Word
[5] [1601] Reference [Unit]
[6] [1602] Reference %
[7] [1603] Status Word
[8] [1605] Main Actual Value [%]
[9] [1609] Custom Readout
[10] [1610] Power [kW]
[11] [1611] Power [hp]
[12] [1612] Motor Voltage
[13] [1613] Frequency
[14] [1614] Motor Current
[15] [1615] Frequency [%]
[16] [1618] Motor Thermal
[17] [1630] DC Link Voltage
[18] [1634] Heatsink Temp.
[19] [1635] Inverter Thermal
[20] [1638] SL Controller State
[21] [1650] External Reference
[22] [1651] Pulse Reference
[23] [1652] Feedback [Unit]
[24] [1660] Digital Input
18,19,27,33
[25] [1661] Digtial Input 29
[26] [1662] Analog Input 53(V)
[27] [1663] Analog Input 53(mA)
[28] [1664] Analog Input 60
[29] [1665] Analog Output 42
[mA]
[30] [1668] Freq. Input 33 [Hz]
[31] [1671] Relay Output [bin]
[32] [1672] Counter A
[33] [1673] Counter[34] [1690]
Alarm Word
[34] [1690] Alarm Word
[35] [1692] Warning Word
[36] [1694] Ext. Status Word
8-5* Digital/Bus
8-50 Coasting Select
[0] DigitalInput
[1] Bus
[2] LogicAnd
*[3] LogicOr
8-51 Quick Stop Select
See par. 8-50 * [3] LogicOr
8-52 DC Brake Select
See par. 8-50 * [3] LogicOr
8-53 Start Select
See par. 8-50 * [3] LogicOr
8-54 Reversing Select
See par. 8-50 * [3] LogicOr
8-55 Set-up Select
See par. 8-50 * [3] LogicOr
8-56 Preset Reference Select
See par. 8-50 * [3] LogicOr
*[1] Approximately equals
[2] Greater Than
13-12 Comparator Value
-9999-9999 *0.0
13-2* Timers
13-20 SL Controller Timer
0.0-3600 s *0.0 s
13-4* Logic Rules
13-40 Logic Rule Boolean 1
See par. 13-01 * [0] False
[30]-[32] SL Time-out 0-2
13-41 Logic Rule Operator 1
*[0] Disabled
[1] And
[2] Or
[3] And not
[4] Or not
[5] Not and
[6] Not or
[7] Not and not
[8] Not or not
13-42 Logic Rule Boolean 2
See par. 13-40
13-43 Logic Rule Operator 2
See par. 13-41 * [0] Disabled
13-44 Logic Rule Boolean 3
See par. 13-40
13-5* States
13-51 SL Controller Event
See par. 13-40
13-52 SL Controller Action
*[0] Disabled
[1] NoAction
[2] SelectSetup1
[3] SelectSetup2
[10-17] SelectPresetRef0-7
[18] SelectRamp1
[19] SelectRamp2
[22] Run
[23] RunReverse
[24] Stop
[25] Qstop
[26] DCstop
[27] Coast
[28] FreezeOutput
[29] StartTimer0
[30] StartTimer1
[31] StartTimer2
et Digital Output B High
[32] Set Digital Output A Low
[33] Set Digital Output B Low
[38] Set Digital Output A High
[39] Set Digital Output B High
[60] ResetCounterA
[61] ResetCounterB
14-** Special Functions
14-0*Inverter Switching
14-01 Switching Frequency
[0] 2 kHz
*[1] 4 kHz
[2] 8 kHz
[4] 16 kHz not available for M5
14-03 Overmodulation
[0] Off
*[1] On
14-1* Mains monitoring
14-12 Function at mains
imbalance
*[0] Trip
[1] Warning
[2] Disabled
14-2* Trip Reset
14-20 Reset Mode
*[0] Manual reset
[1-9] AutoReset 1-9
[10] AutoReset 10
[11] AutoReset 15
[12] AutoReset 20
[13] Infinite auto reset
[14] Reset at power up
14-21 Automatic Restart Time
0-600 s * 10 s
14-22 Operation Mode
*[0] Normal Operation
[2] Initialisation
14-26 Action At Inverter Fault
*[0] Trip
[1] Warning
14-4* Energy Optimising
14-41 AEO Minimum Magnetisation
40-75% *66%
15-** Drive Information 15-0*
Operating Data
15-00 Operating Days
15-01 Running Hours
15-02 kWh Counter
15-03 Power Ups
15-04 Over Temps
15-05 Over Volts
15-06 Reset kWh Counter
*[0] Do not reset
[1] Reset counter
15-07 Reset Running Hours
Counter
*[0] Do not reset
[1] Reset counter
15-3* Fault Log
15-30 Fault Log: Error Code
15-4* Drive Identification
15-40 FC Type
15-41 Power Section
15-42 Voltage
15-43 Software Version
15-46 Frequency Converter
Order. No
15-48 LCP Id No
15-51 Frequency Converter Serial
No
16-** Data Readouts
16-0* General Status
16-00 Control Word
0-0XFFFF
16-01 Reference [Unit]
-4999-4999
16-02 Reference %
-200.0-200.0 %
16-03 Status Word
0-0XFFFF
16-05 Main Actual Value [%]
-200.0-200.0 %
16-09 Custom Readout
Dep. on par. 0-31, 0-32 and 4-14
16-1* Motor Status
16-10 Power [kW]
16-11 Power [hp]
16-12 Motor Voltage [V]
16-13 Frequency [Hz]
16-14 Motor Current [A]
16-15 Frequency [%]
16-18 Motor Thermal [%]
16-3* Drive Status
16-30 DC Link Voltage
16-34 Heatsink Temp.
16-35 Inverter Thermal
16-36 Inv.Nom. Current
16-37 Inv. Max. Current
16-38 SL Controller State
Number
7-20Process CL Feedback 1 Resource[0] No functionAll set-upsTRUE-Uint8
7-30
7-31Process PI Anti Windup[1] EnabledAll set-upsTRUE-Uint8
7-32Process PI Start Speed0 HzAll set-upsTRUE-1Uint16
7-33Process PI Proportional Gain0.01All set-upsTRUE-2Uint16
7-34Process PI Integral Time9999 sAll set-upsTRUE-2Uint32
7-38Process PI Feed Forward Factor0%All set-upsTRUE0Uint16
7-39On Reference Bandwidth5%All set-upsTRUE0Uint8
Table 5.15
Parameter DescriptionDefault Value2 Setup
Process PI Normal/ Inverse
Control[0] NormalAll set-upsTRUE-Uint8
Change During
Operation
Conversi
on
Index
Type
MG02C602 - VLT® is a registered Danfoss trademark
59
Parameter Lists
5.1.13 8-** Comm. and Options
VLT® Micro Drive FC 51 Programming Guide
Parameter
Number
8-01Control Site[0] Digital and ctrl.wordAll set-upsTRUE-Uint8
8-02Control Word Source[1] FC RS485All set-upsTRUE-Uint8
8-03Control Word Timeout Time1 s1 set-upTRUE-1Uint16
8-04Control Word Timeout Function[0] Off1 set-upTRUE-Uint8
8-06Reset Control Word Timeout[0] No function1 set-upTRUE-Uint8
8-30Protocol[0] FC1 set-upTRUE0Uint8
8-31Address11 set-upTRUE0Uint8
62MG02C602 - VLT® is a registered Danfoss trademark
Troubleshooting
6 Troubleshooting
VLT® Micro Drive FC 51 Programming Guide
A warning or an alarm is signalled by the relevant LED on
front of the frequency converter and indicated by a
the
code on the display.
A warning remains active until its cause is no longer
present. Under certain circumstances operation of the
motor may still be continued. Warning messages may be
critical, but are not necessarily so.
In the event of an alarm, the frequency converter will have
tripped. Alarms must be reset to restart operation once
their cause has been rectified.
This may be done in four ways:
1.By pressing [Reset].
2.Via a digital input with the “Reset” function.
3.Via serial communication.
NOTE
After
a manual reset press [Reset], [Auto On] or [Hand On]
to restart the motor.
If an alarm cannot be reset, the reason may be that its
has not been rectified, or the alarm is trip-locked
cause
(see also Table 6.1).
CAUTION
Alarms that are trip-locked offer additional protection,
means
that the mains supply must be switched off before
the alarm can be reset. After being switched back on, the
frequency converter is no longer blocked and may be reset
as described above once the cause has been rectified.
Alarms that are not trip-locked can also be reset using the
automatic reset function in 14-20 Reset Mode (Warning:
automatic wake-up is possible!)
If a warning and alarm is marked against a code in the
Table 6.1, this means that either a warning occurs before
an alarm, or it can be specified whether it is a warning or
an alarm that is to be displayed for a given fault.
This is possible, for instance, in 1-90 Motor ThermalProtection. After an alarm or trip, the motor carries on
coasting, and the alarm and warning flash on the
frequency converter. Once the problem has been rectified,
only the alarm continues flashing.
51AMT check U
52AMT low I
53AMT motor too bigX
54AMT motor too smallX
55AMT Parameter out of rangeX
59Current limitX
63Mechanical Brake LowX
80Drive Initialized to Default ValueX
84The connection between drive and LCP is lostX
85Button disabledX
86Copy failX
87LCP data invalidX
66
88LCP data not compatibleX
89Parameter read onlyX
90Parameter database busyX
91Parameter value is not valid in this modeX
92Parameter value exceeds the min/max limitsX
nom
nom
I
nom
XX
Table 6.1 Alarm/Warning Code List
(X) Dependent on parameter
trip is the action when an alarm has appeared. The trip
A
will coast the motor and can be reset by pressing [Reset]
or make a reset by a digital input (parameter group 5-1*
[1]). The original event that caused an alarm cannot
damage the frequency converter or cause dangerous
conditions. A trip lock is an action when an alarm occurs,
which may cause damage to frequency converter or
connected parts. A trip lock situation can only be reset by
a power cycling.
LED indication
Warningyellow
Alarmflashing red
Table 6.2
The
alarm words, warning words and extended status
words can be read out via serial bus or optional fieldbus
for diagnosis. See also 16-90 Alarm Word, 16-92 WarningWord and 16-94 Ext. Status Word.
64MG02C602 - VLT® is a registered Danfoss trademark
Troubleshooting
VLT® Micro Drive FC 51 Programming Guide
6.1.1 Alarm, Warning and Extended Status Word
Par. 16-90Par. 16-92Par. 16-94
BitHexDecAlarmWordWarningWordExtendedStatusWord
011Brake checkRamping
122Pwr.card tempPwr.card tempAMT running
244Earth FaultStart CW/CCW
388Slow down
41016Ctrl.word TOCtrl.word TOCatch up
52032Over CurrentOver CurrentAbove Feedback High
64064Torque limitBelow Feedback Low
780128Motor th overMotor th overOutput current high
8100256Motor ETR overMotor ETR overOutput current low
9200512Inverter overloadInverter overloadAbove Frequency High
104001024DC under voltDC under voltBelow Frequency Low
118002048DC over voltDC over volt
1210004096Short Circuit
1320008192Braking
14400016384Mains ph. lossMains ph. loss
15800032768"AMT Not OK"OVC active
161000065536Live zero errorLive zero errorAC brake
1720000131072Internal fault
1840000262144
1980000524288U phase lossAbove Reference High
201000001048576V phase lossBelow Reference Low
212000002097152W phase lossLocal Ref./Remote Ref.
224000004194304
238000008388608Control Voltage Fault
24100000016777216
25200000033554432Current limit
26400000067108864Brake resistor short-circuit
278000000134217728Brake IGBT short-circuit
2810000000268435456M4/M5: Earth Fault (Desat)MotorPhaseMissing
2920000000536870912Drive initialised
30400000001073741824Undefined
31800000002147483648Mech. brake lowDatabaseBusy
66
Table 6.3
The alarm words, warning words and extended staus
can be read out via serial bus for diagnose. See also
words
16-94 Ext. Status Word.
WARNING/ALARM 2, Live zero error
Signal on terminal 53 or 60 is less than 50% of value set in
6-10 Terminal 53 Low Voltage, 6-12 Terminal 53 Low Current
and 6-22 Terminal 60 Low Current.
WARNING/ALARM 4, Mains phase loss
A phase is missing on the supply side, or the mains
voltage imbalance is too high. This message also appears
for a fault in the input rectifier on the frequency converter.
Troubleshooting: Check the supply voltage and supply
currents to the frequency converter. The fault may be
caused by mains distortions. Installing Danfoss Line Filter
may rectify this problem.
MG02C602 - VLT® is a registered Danfoss trademark
WARNING/ALARM 7, DC overvoltage
the intermediate circuit voltage exceeds the limit, the
If
frequency converter trips after a time.
Troubleshooting
Connect a brake resistor
Extend the ramp time
Change the ramp type
Activate the functions in 2-10 Brake Function
Increase 14-26 Trip Delay at Inverter Fault
The fault may be caused by mains distortions. Installing
Danfoss Line Filter may rectify this problem.
65
Troubleshooting
VLT® Micro Drive FC 51 Programming Guide
WARNING/ALARM 8, DC under voltage
the intermediate circuit voltage (DC link) drops below
If
the under voltage limit, the frequency converter checks if a
24 V DC backup supply is connected. If no 24 V DC backup
supply is connected, the frequency converter trips after a
fixed time delay. The time delay varies with unit size.
Troubleshooting
Check that the supply voltage matches the
frequency converter voltage.
Perform input voltage test.
Perform soft charge circuit test.
WARNING/ALARM 9, Inverter overload
The frequency converter is about to cut out because of an
66
overload (too high current for too long). The counter for
electronic, thermal inverter protection issues a warning at
98% and trips at 100%, while giving an alarm. The
frequency converter cannot be reset until the counter is
below 90%.
The fault is that the frequency converter has run with
more than 100% overload for too long.
Troubleshooting
Compare the output current shown on the LCP
with the frequency converter rated current.
Compare the output current shown on the LCP
with measured motor current.
Display the Thermal Drive Load on the LCP and
monitor the value. When running above the
frequency converter continuous current rating,
the counter increases. When running below the
frequency converter continuous current rating,
the counter decreases.
WARNING/ALARM 10, Motor overload temperature
According to the electronic thermal protection (ETR), the
motor is too hot. Select whether the frequency converter
gives a warning or an alarm when the counter reaches
100% in 1-90 Motor Thermal Protection. The fault occurs
when the motor is overloaded by more than 100% for too
long.
Troubleshooting
Check for motor overheating.
Check if the motor is mechanically overloaded
Check that the motor current set in 1-24 Motor
Current is correct.
Ensure that Motor data in parameters 1-20
through 1-25 are set correctly.
Running AMT in 1-29 Automatic Motor Tuning
(AMT). The inverter peak current limit (approx.
200% of the rated current) is exceeded. The
warning will last approx. 8-12 s, then the
frequency converter trips and issues an alarm.
Turn off the frequency converter and check if the
motor shaft can be turned and if the motor size
WARNING/ALARM 11, Motor thermistor over temp
The thermistor might be disconnected. Select whether the
frequency converter gives a warning or an alarm in
1-90 Motor Thermal Protection.
Troubleshooting
WARNING/ALARM 13, Over current
The inverter peak current limit (approx. 200% of the rated
current) is exceeded. The warning will last approx. 8-12 s,
then the frequency converter trips and issues an alarm.
Turn off the frequency converter and check if the motor
shaft can be turned and if the motor size matches the
frequency converter. If extended mechanical brake control
is selected, trip can be reset externally.
Troubleshooting:
ALARM 14, Earth (ground) fault
There is current from the output phases to earth, either in
the cable between the frequency converter and the motor
or in the motor itself.
Troubleshooting:
ALARM 16, Short circuit
There is short-circuiting in the motor or motor wiring.
Remove power to the frequency converter and repair the
short circuit.
WARNING/ALARM 17, Control word timeout
There is no communication to the frequency converter.
The warning is only active when 8-04 Control Word TimeoutFunction is NOT set to OFF.
If 8-04 Control Word Timeout Function is set to Stop and
Trip, a warning appears and the frequency converter ramps
down until it trips, while giving an alarm. 8-03 ControlTimeout Time could possibly be increased.
matches the frequency converter. If extended
mechanical
reset externally. may tune the frequency
converter to the motor more accurately and
reduce thermal loading.
Check for motor overheating.
Check if the motor is mechanically overloaded.
Remove power and check if the motor shaft can
be turned.
Check that the motor size matches the frequency
converter.
Check parameters 1-20 through 1-25. for correct
motor data.
Remove power to the frequency converter and
repair the earth fault.
Check for earth faults in the motor by measuring
the resistance to ground of the motor leads and
the motor with a megohmmeter.
brake control is selected, trip can be
66MG02C602 - VLT® is a registered Danfoss trademark
Troubleshooting
VLT® Micro Drive FC 51 Programming Guide
Troubleshooting:
connections on the serial communication
Check
cable.
Increase 8-03 Control Word Timeout Time
Check the operation of the communication
equipment.
Verify a proper installation based on EMC
requirements.
WARNING 25, Brake resistor short circuit
The brake resistor is monitored during operation. If a short
circuit occurs, the brake function is disabled and the
warning appears. The frequency converter is still
operational but without the brake function. Remove power
to the frequency converter and replace the brake resistor
(see 2-15 Brake Check).
WARNING/ALARM 27, Brake chopper fault
The brake transistor is monitored during operation and if a
short circuit occurs, the brake function is disabled and a
warning is issued. The frequency converter is still
operational but, since the brake transistor has shortcircuited, substantial power is transmitted to the brake
resistor, even if it is inactive.
Remove power to the frequency converter and remove the
brake resistor.
WARNING/ALARM 28, Brake check failed
The brake resistor is not connected or not working.
ALARM 29, Heatsink temp
The maximum temperature of the heatsink has been
exceeded. The temperature fault will not reset until the
temperature falls below a defined heatsink temperature.
The trip and reset points are different based on the
frequency converter power size.
Troubleshooting
Check for the following conditions.
Ambient temperature too high.
Motor cable too long.
Incorrect airflow clearance above and below the
frequency converter.
Blocked airflow around the frequency converter.
Damaged heatsink fan.
Dirty heatsink.
ALARM 30, Motor phase U missing
Motor phase U between the frequency converter and the
motor is missing.
Remove power from the frequency converter and check
motor phase U.
ALARM 31, Motor phase V missing
Motor phase V between the frequency converter and the
motor is missing.
Remove power from the frequency converter and check
motor phase V.
ALARM 32, Motor phase W missing
Motor phase W between the frequency converter and the
motor is missing.
Remove power from the frequency converter and check
motor phase W.
ALARM 38, Internal fault
Troubleshooting
Cycle power
Check that the option is properly installed
Check for loose or missing wiring
It may be necessary to contact the local Danfoss supplier
or service department. Note the code number for further
troubleshooting directions.
WARNING 47, 24 V supply low
The 24 V DC is measured on the control card. The external
24 V DC backup power supply may be overloaded,
otherwise contact the Danfoss supplier.
ALARM 51, AMT check U
The settings for motor voltage, motor current, and motor
power are wrong. Check the settings in parameters 1-20 to
1-25.
ALARM 55, AMA parameter out of range
The parameter values of the motor are outside of the
acceptable range. AMA does not run.
ALARM 63, Mechanical brake low
The actual motor current has not exceeded the “release
brake” current within the “Start delay” time window.
ALARM 80, Drive initialised to default value
Parameter settings are initialised to default settings after a
manual reset. Reset the unit to clear the alarm.
ALARM 84,The connection between drive and LCP is lost
Try to reassemble the LCP gently.
ALARM 85, Button disabled
See parameter group 0-4* LCP
ALARM 86, Copy fail
An error occurred while copying from frequency converter
to LCP or vice versa.
ALARM 87, LCP data invalid
Occurs when copying from LCP if the LCP contains
erroneous data - or if no data was uploaded to the LCP.
ALARM 88,LCP data not compatible
Occurs when copying from LCP if data are moved between
frequency converters with major differences in software
versions.
WARNING 89, Parameter read only
Occurs when trying to write to a read-only parameter.
ALARM 90, Parameter database busy
LCP and RS-485 connection are trying to update
parameters simultaneously.
nom
and I
nom
66
MG02C602 - VLT® is a registered Danfoss trademark
67
Troubleshooting
ALARM 91, Parameter value is not valid in this mode
when trying to write an illegal value to a
Occurs
parameter.
ALARM 92, Parameter value exceeds the min/max limits
Occurs when trying to set a value outside the range.
Parameter can only be changed when the motor is
stopped. Err. A wrong password was entered, occurs when
using a wrong password for changing a passwordprotected parameter.
VLT® Micro Drive FC 51 Programming Guide
66
68MG02C602 - VLT® is a registered Danfoss trademark
Index
VLT® Micro Drive FC 51 Programming Guide
Index
A
Abbreviations And Standards............................................................ 7
Active Set-up.................................................. 8, 44, 28, 11, 13, 50, 55
Alarm, Warning And Extended Status Word.............................. 65