2.1 The Graphical and Numerical Local Control Panels
2.1.1 The LCD-Display12
2.1.3 Display Mode14
2.1.4 Display Mode - Selection of Read-Outs14
2.1.5 Parameter Set-Up15
2.1.6 Quick Menu Key Functions15
2.1.8 Main Menu Mode18
2.1.9 Parameter Selection18
2.1.10 Changing Data19
2.1.11 Changing a Text Value19
2.1.12 Changing19
3
11
11
2.1.13 Infinitely Variable Change of Numeric Data Value19
2.1.14 Value, Step-by-Step19
2.1.15 Read-out and Programming of Indexed Parameters20
2.1.16 Local Control Keys21
2.1.17 Initialisation to Default Settings21
3 Parameter Descriptions
3.2 Parameters: 0-** Operation and Display
3.3 Parameters: 1-** Load and Motor
3.4 Parameters: 2-** Brakes
3.5 Parameters: 3-** Reference/Ramps
3.6 Parameters: 4-** Limits/Warnings
3.7 Parameters: 5-** Digital In/Out
3.8 Parameters: 6-** Analog In/Out
3.9 Parameters: 7-** Controllers
3.10 Parameters: 8-** Communications and Options
3.11 Parameters: 9-** Profibus
3.12 Parameters: 10-** DeviceNet CAN Fieldbus
23
24
34
52
57
67
72
91
100
106
112
112
3.13 Parameters: 12-** Ethernet
3.14 Parameters: 13-** Smart Logic Control
3.15 Parameters: 14-** Special Functions
3.16 Parameters: 15-** Drive Information
MG33MF02 - VLT® is a registered Danfoss trademark
112
112
125
133
1
Contents
VLT® AutomationDrive Programming Guide
3.17 Parameters: 16-** Data Read-outs
3.18 Parameters: 17-** Motor Feedb. Option
3.19 Parameters: 18-** Data Readouts 2
3.20 Parameters: 30-** Special Features
3.21 Parameters: 35-** Sensor Input Option
4 Parameter Lists
4.1.1 Conversion154
4.1.2 Active/Inactive Parameters in Different Drive Control Modes154
5 Troubleshooting
5.1.1 Warnings/Alarm Messages192
Index
138
145
147
148
151
153
192
204
2MG33MF02 - VLT® is a registered Danfoss trademark
Introduction
VLT® AutomationDrive Programming Guide
1 Introduction
Programming Guide
Software
This Programming Guide can be used for all FC 300 frequency
converters with software version 6.7x.
The software version number can be seen from 15-43 SoftwareVersion.
Table 1.1
version: 6.7x
1.1.1 Approvals
Table 1.2
1.1.2 Symbols
The following symbols are used in this manual.
WARNING
Indicates a potentially hazardous situation which, if not
avoided,
could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided,
may result in minor or moderate injury. It may
also be used to alert against unsafe practices.
CAUTION
Indicates
property-damage-only accidents.
NOTE
Indicates
with attention to avoid mistakes or operate equipment at
less than optimal performance.
1.1.3 Definitions
Frequency converter
I
VLT,
Maximum output current.
a situation that may result in equipment or
highlighted information that should be regarded
MAX
I
VLT
,N
Rated output current supplied by the frequency converter.
U
VLT, MAX
Maximum output voltage.
Input
Control command
and stop the connected motor by means of LCP and
Start
digital inputs.
Functions are divided into two groups.
Functions in group 1 have higher priority than functions in
group 2.
Group 1Reset, Coasting stop, Reset and Coasting stop,
Quick-stop,
Group 2Start, Pulse start, Reversing, Start reversing, Jog
and
Table 1.3
DC braking, Stop and the [OFF] key.
Freeze output
Motor
Motor Running
Torque
generated on output shaft and speed from zero
rpm to max. speed on motor.
f
JOG
Motor frequency when the jog function is activated (via
digital terminals).
f
M
Motor frequency.
f
MAX
Maximum motor frequency.
f
MIN
Minimum motor frequency.
f
M,N
Rated motor frequency (nameplate data).
I
M
Motor current (actual).
I
M,N
Rated motor current (nameplate data).
n
M,N
Rated motor speed (nameplate data).
n
s
Synchronous motor speed
2 ×
par
=
. 1 − 23 × 60
par
. 1 − 39
n
s
n
slip
s
Motor slip.
P
M,N
Rated motor power (nameplate data in kW or HP).
11
MG33MF02 - VLT® is a registered Danfoss trademark
3
175ZA078.10
Pull-out
rpm
Torque
Introduction
VLT® AutomationDrive Programming Guide
11
T
M,N
Rated torque (motor).
Pulse Reference
pulse frequency signal transmitted to the digital inputs
A
(terminal 29 or 33).
U
M
Instantaneous motor voltage.
U
M,N
Rated motor voltage (nameplate data).
Break-away torque
Ref
MAX
Determines the relationship between the reference input
at
100% full scale value (typically 10 V, 20 mA) and the
resulting reference. The maximum reference value set in
3-03 Maximum Reference.
Ref
MIN
Determines the relationship between the reference input
0% value (typically 0 V, 0 mA, 4 mA) and the resulting
at
reference. The minimum reference value set in
3-02 Minimum Reference.
Miscellaneous
Analog Inputs
analog inputs are used for controlling various
The
functions of the frequency converter.
There are two types of analog inputs:
Current input, 0-20 mA and 4-20 mA
Voltage input, -10 to +10 V DC.
Analog Outputs
analog outputs can supply a signal of 0-20 mA, 4-20
The
mA.
Automatic Motor Adaptation, AMA
algorithm determines the electrical parameters for
AMA
Illustration 1.1
the connected motor at standstill.
Brake Resistor
brake resistor is a module capable of absorbing the
η
VLT
The efficiency of the frequency converter is defined as the
between the power output and the power input.
ratio
The
brake power generated in regenerative braking. This
regenerative braking power increases the intermediate
circuit voltage and a brake chopper ensures that the
power is transmitted to the brake resistor.
Start-disable command
stop command belonging to the group 1 control
A
commands - see this group.
Stop command
See
Control commands.
References
Analog Reference
A
signal transmitted to the analog inputs 53 or 54, can be
voltage or current.
Binary Reference
A
signal transmitted to the serial communication port.
Preset Reference
A
defined preset reference to be set from -100% to +100%
of the reference range. Selection of eight preset references
via the digital terminals.
CT Characteristics
Constant
torque characteristics used for all applications
such as conveyor belts, displacement pumps and cranes.
Digital Inputs
digital inputs can be used for controlling various
The
functions of the frequency converter.
Digital Outputs
frequency converter features two Solid State outputs
The
that can supply a 24 V DC (max. 40 mA) signal.
DSP
Signal Processor.
Digital
ETR
Electronic
Thermal Relay is a thermal load calculation
based on present load and time. Its purpose is to estimate
the motor temperature.
Hiperface
Hiperface®
®
is a registered trademark by Stegmann.
4MG33MF02 - VLT® is a registered Danfoss trademark
Introduction
VLT® AutomationDrive Programming Guide
Initialising
initialising is carried out (14-22 Operation Mode), the
If
frequency converter returns to the default setting.
Intermittent Duty Cycle
An intermittent duty rating refers to a sequence of duty
cycles. Each cycle consists of an on-load and an off-load
period. The operation can be either periodic duty or nonperiodic duty.
LCP
The Local Control Panel makes up a complete interface for
control and programming of the frequency converter. The
control panel is detachable and can be installed up to 3 m
from the frequency converter, i.e. in a front panel with the
installation kit option.
lsb
Least significant bit.
msb
Most significant bit.
MCM
Short for Mille Circular Mil, an American measuring unit for
cable cross-section. 1 MCM = 0.5067mm2.
On-line/Off-line Parameters
Changes
after the data value is changed. Changes to off-line
parameters are not activated until you enter [OK] on the
LCP.
Process PID
The
temperature, etc. by adjusting the output frequency to
match the varying load.
PCD
Process
Power Cycle
Switch
power on again.
Pulse Input/Incremental Encoder
An
information on motor speed. The encoder is used in
applications where great accuracy in speed control is
required.
RCD
Residual
Set-up
You
between the four parameter Set-ups and edit one Set-up,
while another Set-up is active.
SFAVM
Switching
Vector Modulation (14-00
to on-line parameters are activated immediately
PID control maintains the desired speed, pressure,
Control Data
off the mains until display (LCP) is dark – then turn
external, digital pulse transmitter used for feeding back
Current Device.
can save parameter settings in four Set-ups. Change
pattern called
Stator Flux oriented Asynchronous
Switching Pattern).
Slip Compensation
frequency converter compensates for the motor slip
The
by giving the frequency a supplement that follows the
measured motor load keeping the motor speed almost
constant.
Smart Logic Control (SLC)
SLC is a sequence of user defined actions executed
The
when the associated user defined events are evaluated as
true by the Smart Logic Controller. (Parameter group 13-**
Smart Logic Control (SLC).
STW
Status Word
FC Standard Bus
Includes RS-485 bus with FC protocol or MC protocol. See
8-30 Protocol.
Thermistor
temperature-dependent resistor placed where the
A
temperature is to be monitored (frequency converter or
motor).
Trip
state entered in fault situations, e.g. if the frequency
A
converter is subject to an over-temperature or when the
frequency converter is protecting the motor, process or
mechanism. Restart is prevented until the cause of the
fault has disappeared and the trip state is cancelled by
activating reset or, in some cases, by being programmed
to reset automatically. Trip may not be used for personal
safety.
Trip Locked
state entered in fault situations when the frequency
A
converter is protecting itself and requiring physical
intervention, e.g. if the frequency converter is subject to a
short circuit on the output. A locked trip can only be
cancelled by cutting off mains, removing the cause of the
fault, and reconnecting the frequency converter. Restart is
prevented until the trip state is cancelled by activating
reset or, in some cases, by being programmed to reset
automatically. Trip may not be used for personal safety.
VT Characteristics
Variable
VVC
If
Voltage Vector Control (VVC
and the stability, both when the speed reference is
changed and in relation to the load torque.
60° AVM
Switching
Modulation (14-00
Power Factor
The
torque characteristics used for pumps and fans.
plus
compared with standard voltage/frequency ratio control,
pattern called 60°
Switching Pattern).
power factor is the relation between I1 and I
plus
) improves the dynamics
Asynchronous Vector
RMS
.
11
MG33MF02 - VLT® is a registered Danfoss trademark
5
Introduction
x U x I
cos
11
Power factor
=
3
x U x I
3
1
ϕ
RMS
The power factor for 3-phase control:
VLT® AutomationDrive Programming Guide
7.Please note that the frequency converter has
voltage sources than L1, L2 and L3, when
more
load sharing (linking of DC intermediate circuit)
or external 24 V DC are installed. Check that all
=
I1 x cos
I
RMS
ϕ1
=
I
RMS
I
1
since cos
ϕ1 = 1
The power factor indicates to which extent the frequency
converter imposes a load on the mains supply.
The lower the power factor, the higher the I
RMS
for the
same kW performance.
I
RMS
=
I
+
1
2
I
+
I
+ .. +
5
7
2
I
n
2
2
In addition, a high power factor indicates that the different
harmonic
currents are low.
The frequency converters' built-in DC coils produce a high
power factor, which minimizes the imposed load on the
mains supply.
Warning against unintended start
voltage sources have been disconnected and that
the necessary time has elapsed before
commencing repair work.
1.The motor can be brought to a stop by means of
digital commands, bus commands, references or
a local stop, while the frequency converter is
connected to mains. If personal safety considerations (e.g. risk of personal injury caused by
contact with moving machine parts following an
unintentional start) make it necessary to ensure
that no unintended start occurs, these stop
functions are not sufficient. In such cases the
mains supply must be disconnected or the Safe
WARNING
The voltage of the frequency converter is dangerous
whenever
motor, frequency converter or fieldbus may cause death,
serious personal injury or damage to the equipment.
Consequently, the instructions in this manual, as well as
national and local rules and safety regulations, must be
complied with.
Safety Regulations
connected to mains. Incorrect installation of the
1.
The mains supply to the frequency converter
must be disconnected whenever repair work is to
be carried out. Check that the mains supply has
been disconnected and that the necessary time
has elapsed before removing motor and mains
supply plugs.
2.[Off] does not disconnect the mains supply and
consequently it must not be used as a safety
switch.
3.The equipment must be properly earthed, the
user must be protected against supply voltage
and the motor must be protected against
overload in accordance with applicable national
NOTE
When using the Safe Stop function, always follow the
instructions in the section Safe Stop of the Design Guide.
Stop function must be activated.
2.The motor may start while setting the
parameters. If this means that personal safety
may be compromised (e.g. personal injury caused
by contact with moving machine parts), motor
starting must be prevented, for instance by use
of the Safe Stop function or secure disconnection
of the motor connection.
3.A motor that has been stopped with the mains
supply connected, may start if faults occur in the
electronics of the frequency converter, through
temporary overload or if a fault in the power
supply grid or motor connection is remedied. If
unintended start must be prevented for personal
safety reasons (e.g. risk of injury caused by
contact with moving machine parts), the normal
stop functions of the frequency converter are not
sufficient. In such cases the mains supply must be
disconnected or the Safe Stop function must be
activated.
and local regulations.
4.The earth leakage current exceeds 3.5 mA.
5.Protection against motor overload is not included
in the factory setting. If this function is desired,
set 1-90 Motor Thermal Protection to data value
ETR trip 1 [4] or data value ETR warning 1 [3].
6.Do not remove the plugs for the motor and
mains supply while the frequency converter is
4.Control signals from, or internally within, the
frequency
converter may in rare cases be
activated in error, be delayed or fail to occur
entirely. When used in situations where safety is
critical, e.g. when controlling the electromagnetic
brake function of a hoist application, these
control signals must not be relied on exclusively.
connected to mains. Check that the mains supply
has been disconnected and that the necessary
time has elapsed before removing motor and
mains plugs.
6MG33MF02 - VLT® is a registered Danfoss trademark
Introduction
VLT® AutomationDrive Programming Guide
WARNING
High Voltage
Touching
equipment has been disconnected from mains.
Also make sure that other voltage inputs have been
disconnected, such as external 24 V DC, load sharing
(linkage of DC intermediate circuit), as well as the motor
connection for kinetic back up.
Systems where frequency converters are installed must, if
necessary, be equipped with additional monitoring and
protective devices according to the valid safety regulations,
e.g law on mechanical tools, regulations for the prevention
of accidents etc. Modifications on the frequency converters
by means of the operating software are allowed.
NOTE
Hazardous
builder/ integrator who is responsible for taking necessary
preventive means into consideration. Additional
monitoring and protective devices may be included, always
according to valid national safety regulations, e.g. law on
mechanical tools, regulations for the prevention of
accidents.
the electrical parts may be fatal - even after the
situations shall be identified by the machine
11
NOTE
Lifts and Hoists:
Crane,
The controlling of external brakes must always have a
redundant system. The frequency converter can in no
circumstances be the primary safety circuit. Comply with
relevant standards, e.g.
Hoists and cranes: IEC 60204-32
Lifts: EN 81
Protection Mode
a hardware limit on motor current or dc-link voltage
Once
is exceeded the frequency converter will enter “Protection
mode”. “Protection mode” means a change of the PWM
modulation strategy and a low switching frequency to
minimize losses. This continues 10 s after the last fault and
increases the reliability and the robustness of the
frequency converter while re-establishing full control of the
motor.
In hoist applications “Protection mode” is not usable
because the frequency converter will usually not be able to
leave this mode again and therefore it will extend the time
before activating the brake – which is not recommendable.
The “Protection mode” can be disabled by setting
14-26 Trip Delay at Inverter Fault to zero which means that
the frequency converter will trip immediately if one of the
hardware limits is exceeded.
NOTE
is recommended to disable protection mode in hoisting
It
applications (14-26 Trip Delay at Inverter Fault = 0)
MG33MF02 - VLT® is a registered Danfoss trademark
7
3 Phase
power
input
DC bus
Switch Mode
Power Supply
Motor
Analog Output
Interface
relay1
* relay2
ON=Terminated
OFF=Open
Brake
resistor
130BC931.10
91 (L1)
92 (L2)
93 (L3)
PE
88 (-)
89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4-20 mA
12 (+24V OUT)
13 (+24V OUT)
37 (D IN)
18 (D IN)
20 (COM D IN)
10Vdc
15mA 130/200mA
+ -+-
(U) 96
(V) 97
(W) 98
(PE) 99
(COM A OUT) 39
(A OUT) 42
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
0V
5V
S801
0/4-20 mA
RS-485
RS-485
03
+10Vdc
0/-10Vdc -
+10Vdc
+10Vdc
0/4-20 mA
0/-10Vdc -
240Vac, 2A
24Vdc
02
01
05
04
06
240Vac, 2A
24V (NPN)
0V (PNP)
0V (PNP)
24V (NPN)
19 (D IN)
24V (NPN)
0V (PNP)
27
24V
0V
(D IN/OUT)
0V (PNP)
24V (NPN)
(D IN/OUT)
0V
24V
29
24V (NPN)
0V (PNP)
0V (PNP)
24V (NPN)
33 (D IN)
32 (D IN)
1 2
ON
S201
ON
21
S202
ON=0/4-20mA
OFF=0/-10Vdc +10Vdc
95
400Vac, 2A
P 5-00
21
ON
S801
(R+) 82
(R-) 81
*
*
: Chassis
: Earth
**
Introduction
VLT® AutomationDrive Programming Guide
11
1.1.4 Electrical Wiring - Control Cables
Illustration 1.2 Basic Wiring Schematic Drawing.
A=Analog, D=Digital
Terminal
* Terminal 37 is not included in FC 301 (except frame size A1). Relay 2 and terminal 29 have no function in FC 301.
** Do not connect cable screen.
Very long control cables and analog signals may in rare cases and depending on installation result in 50/60 Hz earth loops
37 is used for Safe Stop. For Safe Stop installation instructions, refer to the Design Guide.
due to noise from mains supply cables.
If this occurs, it may be necessary to break the screen or insert a 100 nF capacitor between screen and chassis.
The digital and analog inputs and outputs must be connected separately to the common inputs (terminal 20, 55, 39) of the
frequency converter to avoid ground currents from both groups to affect other groups. For example, switching on the
digital input may disturb the analog input signal.
8MG33MF02 - VLT® is a registered Danfoss trademark
12131819272932332037
+24 VDC
0 VDC
130BT106.10
PNP (Source)
Digital input wiring
NPN (Sink)
Digital input wiring
12131819272932332037
+24 VDC
0 VDC
130BT107.11
130BA681.10
12 13 1837
130BA155.12
3227192933 20
P 5-12 [0]
P 5-10 [8]
Start/Stop
+24V
Speed
Safe Stop
Start/Stop
[18]
Introduction
VLT® AutomationDrive Programming Guide
Input polarity of control terminals
Illustration 1.3
11
Illustration 1.5
1.1.5 Start/Stop
Illustration 1.4
NOTE
Control cables must be screened/armoured.
See section on earthing of screened/armoured control
in the Design Guide for the correct termination of
Reference
Terminal 53, Low Voltage = 0 V
Terminal 53, High Voltage = 10 V
Terminal 53, Low Ref./Feedback = 0 RPM
Terminal 53, High Ref./Feedback = 1500 RPM
Switch S201 = OFF (U)
Terminal 29 = 5-13 Terminal 29 Digital Input
Speed up [21]
Terminal 32 = 5-14 Terminal 32 Digital Input
Speed down [22]
NOTE
29 only in FC x02 (x=series type).
Terminal
18 = 5-10 Terminal 18 Digital Input Start
Illustration 1.9
10MG33MF02 - VLT® is a registered Danfoss trademark
Auto
on
Reset
Hand
on
O
Status
Quick
Menu
Main
Menu
Alarm
Log
Back
Cancel
Info
OK
Status
1(0)
1234rpm10,4A43,5Hz
Run OK
43,5Hz
On
Alarm
Warn.
130BA018.13
1
2
3
4
b
a
c
How to Programme
VLT® AutomationDrive Programming Guide
2 How to Programme
2.1 The Graphical and Numerical Local
Control Panels
The easiest programming of the frequency converter is
performed
to consult the frequency converter Design Guide, when
using the Numeric Local Control Panel (LCP 101).
The control panel is divided into four functional groups
All data is displayed in a graphical LCP display, which can
show up to five items of operating data while displaying
[Status].
by the Graphical LCP (LCP 102). It is necessary
1.Graphical display with Status lines.
2.Menu keys and indicator lights - changing
parameters and switching between display
functions.
3.Navigation keys and indicator lights (LEDs).
4.Operation keys and indicator lights (LEDs).
22
Display lines
a.Status line: Status messages displaying icons and
graphic.
b.Line 1-2: Operator data lines displaying data
defined or chosen by the user. By pressing
[Status], up to one extra line can be added.
c.Status line: Status messages displaying text.
Illustration 2.1
MG33MF02 - VLT® is a registered Danfoss trademark
11
Top section
Middle section
Bottom section
Status
43 RPM
1.4 Hz
Auto Remote Running
! Pwr.card temp (W29)
2.9%
5.44 A25.3kW
1(1)
130BP074.10
!
On
Warn.
Alarm
130BP044.10
130BP045.10
Status
Quick
Menu
Main
Menu
Alarm
Log
How to Programme
2.1.1 The LCD-Display
VLT® AutomationDrive Programming Guide
22
The LCD-display has back light and a total of 6 alphanumeric
rotation (arrow), the chosen Set-up as well as the
programming Set-up. The display is divided into 3 sections.
Top section shows up to 2 measurements in normal
operating status.
The top line in the Middle section shows up to 5
measurements with related unit, regardless of status
(except in the case of alarm/warning).
Bottom section always shows the state of the frequency
converter in Status mode.
lines. The display lines show the direction of
Illustration 2.3
Keys
LCP
The control keys are divided into functions. The keys
below the display and indicator lamps are used for
parameter Set-up, including choice of display indication
during normal operation.
Illustration 2.4
Illustration 2.2
[Status]
and/or the motor. Choose between 3 different readouts by
The Active Set-up (selected as the Active Set-up in
Active Set-up) is shown. When programming another
0-10
Set-up than the Active Set-up, the number of the
programmed Set-up appears to the right.
Display contrast adjustment
Press [Status] and [▲] for darker display
Press [Status] and [▼] for brighter display
Most parameter set-ups can be changed immediately via
the LCP, unless a password has been created via 0-60 MainMenu Password or via 0-65 Quick Menu Password.
Indicator lights (LEDs)
If certain threshold values are exceeded, the alarm and/or
warning LED lights up. A status and alarm text appear on
the LCP.
The ON LED is activated when the frequency converter
receives mains voltage or via a DC bus terminal or 24 V
external supply. At the same time, the back light is on.
Green LED/On: Control section is working.
•
•
•
12MG33MF02 - VLT® is a registered Danfoss trademark
Yellow LED/Warn.: Indicates a warning.
Flashing Red LED/Alarm: Indicates an alarm.
pressing the [Status] key: 5 line readouts, 4 line readouts
or Smart Logic Control.
Use [Status] for selecting the mode of display or for
changing back to Display mode from either the Quick
Menu mode, the Main Menu mode or Alarm mode. Also
use the [Status] key to toggle single or double read-out
mode.
[Quick Menu] allows quick access to different Quick Menus
such as
Use [Quick Menu] for programming the parameters
belonging to the Quick Menu. It is possible to switch
directly between Quick Menu mode and Main Menu mode.
[Main Menu] is used for programming all parameters.
It is possible to switch directly between Main Menu mode
and Quick Menu mode.
Parameter shortcut can be carried out by pressing down
the [Main Menu] key for 3 seconds. The parameter shortcut
allows direct access to any parameter.
indicates the status of the frequency converter
My Personal Menu
•
Quick Set-up
•
Changes Made
•
Loggings
•
B
a
c
k
C
a
n
c
e
l
I
n
f
o
130BP046.10
Hand
on
O
Auto
on
Reset
How to Programme
VLT® AutomationDrive Programming Guide
[Alarm Log]
displays an Alarm list of the five latest alarms
(numbered A1-A5). To obtain additional details about an
alarm, use the arrow keys to manoeuvre to the alarm
number and press [OK]. Information is displayed about the
condition of the frequency converter before it enters the
alarm mode.
[Back] reverts to the previous step or layer in the
navigation structure.
[Cancel] last change or command will be cancelled as long
as the display has not been changed.
[Info] supplies information about a command, parameter,
or function in any display window. [Info] provides detailed
information whenever help is needed.
Exit info mode by pressing either [Info], [Back], or [Cancel].
Illustration 2.5
[Hand On]
enables control of the frequency converter via
the LCP. [Hand On] also starts the motor, and it is now
possible to enter the motor speed data by means of the
arrow keys. The key can be selected as [1] Enable or [0]Disable via 0-40 [Hand on] Key on LCP
External stop signals activated by means of control signals
or a serial bus will override a “start” command via the LCP.
The following control signals will still be active when
[Hand On] is activated
[Hand on] - [Off] - [Auto On]
•
Reset
•
Coasting stop inverse
•
Reversing
•
Set-up select bit 0- Set-up select bit 1
•
Stop command from serial communication
•
Quick stop
•
DC brake
•
[Off] stops the connected motor. The key can be selected
as [1] Enable or [0] Disable via 0-41 [Off] Key on LCP. If no
external stop function is selected and the [Off] key is
inactive the motor can be stopped by disconnecting the
voltage.
22
Illustration 2.6
Illustration 2.7
Navigation Keys
The
four navigation keys are used to navigate between the
different choices available in [Quick Menu], [Main Menu]
and [Alarm Log]. Use the keys to move the cursor.
[OK] is used for choosing a parameter marked by the
cursor and for enabling the change of a parameter.
Local Control Key for local control are found at the bottom
of the LCP.
[Auto On] enables the frequency converter to be
controlled via the control terminals and/or serial communication. When a start signal is applied on the control
terminals and/or the bus, the frequency converter will
start. The key can be selected as [1] Enable or [0] Disable
via 0-42 [Auto on] Key on LCP.
NOTE
active HAND-OFF-AUTO signal via the digital inputs has
An
higher priority than the control keys [Hand On] – [Auto
On].
is used for resetting the frequency converter after
[Reset]
an alarm (trip). It can be selected as [1] Enable or [0]Disable via 0-43 [Reset] Key on LCP.
The parameter shortcut can be carried out by holding
down the [Main Menu] key for 3 seconds. The parameter
shortcut allows direct access to any parameter.
2.1.2 Quick Transfer of Parameter Settings
between
Converters
Multiple Frequency
Once the set-up of a frequency converter is complete, we
Illustration 2.8
recommend
that you store the data in the LCP or on a PC
via MCT 10 Set-up Software Tool.
MG33MF02 - VLT® is a registered Danfoss trademark
13
Auto
on
Reset
Hand
on
O
Status
Quick
Menu
Main
Menu
Alarm
Log
Back
Cancel
Info
OK
On
Alarm
Warn.
130BA027.10
How to Programme
VLT® AutomationDrive Programming Guide
2.1.3 Display Mode
22
Illustration 2.9
storage in LCP
Data
1.
Go to 0-50 LCP Copy
2.Press the [OK] key
3.Select “All to LCP”
4.Press the [OK] key
All parameter settings are now stored in the LCP indicated
by the progress bar. When 100% is reached, press [OK].
NOTE
the motor before performing this operation.
Stop
Connect the LCP to another frequency converter and copy
parameter settings to this frequency converter as well.
the
Data transfer from LCP to frequency converter
1.
Go to 0-50 LCP Copy
3.Select “All from LCP”
2.Press the [OK] key
4.Press the [OK] key
The parameter settings stored in the LCP are now
transferred to the frequency converter indicated by the
progress bar. When 100% is reached, press [OK].
NOTE
Stop
the motor before performing this operation.
In normal operation, up to 5 different operating variables
be indicated continuously in the middle section: 1.1,
can
1.2, and 1.3 as well as 2 and 3.
2.1.4 Display Mode - Selection of ReadOuts
It is possible to toggle between three status read-out
screens
by pressing the [Status] key.
Operating variables with different formatting are shown in
each status screen - see below.
Table 2.1 shows the measurements you can link to each of
the operating variables. When Options are mounted,
additional measurements are available. Define the links via
0-20 Display Line 1.1 Small, 0-21 Display Line 1.2 Small,
0-22 Display Line 1.3 Small, 0-23 Display Line 2 Large, and
0-24 Display Line 3 Large.
Each readout parameter selected in 0-20 Display Line 1.1
Small to 0-24 Display Line 3 Large has its own scale and
digits after a possible decimal point. By larger numeric
value of a parameter fewer digits are displayed after the
decimal point.
Ex.: Current readout 5.25A; 15.2A 105A.
Operating variableUnit
16-00 Control Wordhex
16-01 Reference [Unit][unit]
16-02 Reference [%]%
16-03 Status Wordhex
16-05 Main Actual Value [%]%
16-10 Power [kW][kW]
16-11 Power [hp][HP]
16-12 Motor Voltage[V]
16-13 Frequency[Hz]
16-14 Motor Current[A]
16-16 Torque [Nm]Nm
16-17 Speed [RPM][RPM]
16-18 Motor Thermal%
16-20 Motor Angle
16-30 DC Link VoltageV
16-32 Brake Energy /skW
16-33 Brake Energy /2 minkW
16-34 Heatsink Temp.C
16-35 Inverter Thermal%
16-36 Inv. Nom. CurrentA
16-37 Inv. Max. CurrentA
16-38 SL Controller State
16-39 Control Card Temp.C
16-40 Logging Buffer Full
16-50 External Reference
14MG33MF02 - VLT® is a registered Danfoss trademark
1.1
2
3
1.3
1.2
130BP041.10
799 RPM
Auto Remote Ramping
1 (1)
36.4 kw7.83 A
0.000
53.2 %
Status
1.1
1.2
2
1.3
130BP062.10
207RPM
Auto Remote Running
1 (1)
24.4 kW5.25A
6.9
Hz
Status
130BP063.10
778 RPM
Auto Remote Running
1 (1)
4.0 kW0.86 A
State: 0 o 0 (o)
When: Do: -
Status
How to Programme
Operating variableUnit
16-51 Pulse Reference
16-52 Feedback [Unit][Unit]
16-53 Digi Pot Reference
16-60 Digital Inputbin
16-61 Terminal 53 Switch SettingV
16-62 Analog Input 53
16-63 Terminal 54 Switch SettingV
16-64 Analog Input 54
16-65 Analog Output 42 [mA][mA]
16-66 Digital Output [bin][bin]
16-67 Pulse Input #29 [Hz][Hz]
16-68 Freq. Input #33 [Hz][Hz]
16-69 Pulse Output #27 [Hz][Hz]
16-70 Pulse Output #29 [Hz][Hz]
16-71 Relay Output [bin]
16-72 Counter A
16-73 Counter B
16-80 Fieldbus CTW 1hex
16-82 Fieldbus REF 1hex
16-84 Comm. Option STWhex
16-85 FC Port CTW 1hex
16-86 FC Port REF 1hex
16-90 Alarm Word
16-92 Warning Word
16-94 Ext. Status Word
VLT® AutomationDrive Programming Guide
Illustration 2.11
screen III
Status
This state displays the event and action of the Smart Logic
Control. For further information, see section Smart LogicControl.
Illustration 2.12
22
Table 2.1
Status
screen I
This read-out state is standard after start-up or initialization.
Use [INFO] to obtain information about the measurement
links to the displayed operating variables (1.1, 1.2, 1.3, 2
and 3).
See the operating variables shown in the screen below.
Illustration 2.10
Status screen II
the operating variables (1.1, 1.2, 1.3 and 2) shown in
See
the screen below.
In the example, Speed, Motor current, Motor power and
Frequency are selected as variables in the first and second.
MG33MF02 - VLT® is a registered Danfoss trademark
2.1.5 Parameter Set-Up
The frequency converter can be used for practically all
assignments,
which is why the number of parameters is
quite large. The frequency converter offers a choice
between two programming modes - a Main Menu and a
Quick Menu mode.
The former provides access to all parameters. The latter
takes the user through a few parameters making it
possible to start operating the frequency converter.
Regardless of the mode of programming, you can change
a parameter both in the Main Menu mode and in the
Quick Menu mode.
2.1.6 Quick Menu Key Functions
Pressing [Quick Menus] The list indicates the different
areas
contained in the Quick menu.
Select My Personal Menu to display the chosen personal
parameters. These parameters are selected in 0-25 MyPersonal Menu. Up to 50 different parameters can be
added in this menu.
15
130BC916.10
Q1 My Personal Menu
Q2 Quick Setup
Q4 Smart Setup
Q5 Changes Made
0RPM 0.00A 1(1)
Quick Menus
How to Programme
VLT® AutomationDrive Programming Guide
22
Illustration 2.13
Quick setup to go through a limited amount of
Select
parameters to get the motor running almost optimally. The
default setting for the other parameters considers the
desired control functions and the configuration of signal
inputs/outputs (control terminals).
The selection of parameter is effected by means of the
arrow keys. The parameters in the following table are
accessible.
ParameterSetting
0-01 Language
1-20 Motor Power [kW][kW]
1-22 Motor Voltage[V]
1-23 Motor Frequency[Hz]
1-24 Motor Current[A]
1-25 Motor Nominal Speed[rpm]
5-12 Terminal 27 Digital Input[0] No function*
1-29 Automatic Motor Adaptation (AMA) [1] Enable complete
3-02 Minimum Reference[rpm]
3-03 Maximum Reference[rpm]
3-41 Ramp 1 Ramp up Time[sec]
3-42 Ramp 1 Ramp Down Time[sec]
3-13 Reference Site
Table 2.2
*
If terminal 27 is set to “no function”, no connection to
+24 V on terminal 27 is necessary.
Select Changes made to get information about:
the last 10 changes. Use the [▲] [▼] navigation
•
keys to scroll between the last 10 changed
parameters.
the changes made since default setting.
•
Select Loggings to get information about the display line
read-outs. The information is shown as graphs.
Only display parameters selected in 0-20 Display Line 1.1Small and 0-24 Display Line 3 Large can be viewed. It is
possible to store up to 120 samples in the memory for
later reference.
16MG33MF02 - VLT® is a registered Danfoss trademark
AMA
Quick
Menu
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
How to Programme
2.1.7 Initial Commissioning
VLT® AutomationDrive Programming Guide
The easiest way of carrying out the initial commissioning is
using the [Quick Menu] key and follow the quick set-up
by
procedure using LCP 102 (read Table 2.3Table 2.4 from left
to right). The example applies to open loop applications.
Press
0-01 Language
1-20 Motor Power [kW]
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
22
Q2 Quick Menu
Set language
Set Motor nameplate power
Set Nameplate voltage
Set Nameplate frequency
Set Nameplate current
1-25 Motor Nominal Speed
5-12 Terminal 27 Digital Input
1-29 Automatic Motor Adaptation
(AMA)
3-02 Minimum Reference
3-03 Maximum Reference
3-41 Ramp 1 Ramp up Time
3-42 Ramp 1 Ramp Down Time
3-13 Reference Site
Set Nameplate speed in RPM
If terminal default is Coastinverse it is possible to change
this setting to No function. No
connection to terminal 27 is
then needed for running AMA
Set desired AMA function.
complete AMA is
Enable
recommended
Set the minimum speed of the
shaft
motor
Set the maximum speed of the
shaft
motor
Set the ramping up time with
reference
motor speed, n
to synchronous
s
Set the ramping down time
reference to synchronous
with
motor speed, n
s
Set the site from where the
reference
must work
Table 2.3
MG33MF02 - VLT® is a registered Danfoss trademark
17
130BP066.10
1107 RPM
0 -
**
Operation/Display
1 -
**
Load/Motor
2 -
**
Brakes
3 -
**
Reference / Ramps
3.84 A1 (1)
Main menu
130BP067.10
740RPM
0 -01 Language
[0] English
10.64A1 [1]
0-0
*
Basic Settings
How to Programme
VLT® AutomationDrive Programming Guide
Another easy way of commissioning the drive is by using
Smart Application Setup (SAS), which can also be
the
found under the Quick Menu. Follow the indications on
22
the successive screens for setting-up the applications
listed.
All parameters can be changed in the Main Menu.
However,
depending on the choice of configuration
(1-00 Configuration Mode), some parameters can be
"missing". E.g. open loop hides all the PID parameters, and
other enabled options make more parameter groups
visible.
[Info] can be used throughout the SAS to see help
information for various selections, settings, and messages.
2.1.9 Parameter Selection
The following three applications are included:
In the Main menu mode, the parameters are divided into
Mechanical Brake
•
Conveyor
•
Pump/Fan
•
The following four field-busses can be selected:
Profibus
•
Profinet
•
DeviceNet
•
EthernetIP
•
NOTE
start conditions will be ignored while in the wizard.
The
NOTE
Smart Setup runs automatically on the first power-up
The
of the frequency converter or after a reset to factory
settings. If no action is taken, the SAS screen will automatically disappear after 10 min.
2.1.8 Main Menu Mode
Start the Main Menu mode by pressing [Main Menu]. The
read-out
The middle and bottom sections on the display show a list
of parameter groups which can be chosen by toggling [▲]
and [▼] keys.
shown below appears on the display.
groups. Select a parameter group with the navigation keys.
The following parameter groups are accessible:
selecting a parameter group, choose a parameter by
means of the navigation keys.
The middle section on the display shows the parameter
number and name as well as the selected parameter value.
Illustration 2.14
Each parameter has a name and number which remain the
regardless of the programming mode. In the Main
same
Menu mode, the parameters are divided into groups. The
first digit of the parameter number (from the left) indicates
the parameter group number.
18MG33MF02 - VLT® is a registered Danfoss trademark
Illustration 2.15
130BP068.10
740RPM
0 -01 Language
[0] English
10.64 A1 [1]
0-0
*
Basic Settings
130BP069.10
1- 6*
113 RPM 1.78 A 1(1)
Load depen. setting
1 - 60 Low speed load
compensation
100%
130BP070.10
1 - 60 Low speed load
compensation
1 0%
Load depen. setting1- 6*
729RPM 6.21A 1(1)
6
130BP073.10
635 RPM
1 - 71 Start Delay
00.0s
0.44 A1 (1)
1- 7*
Start Adjustments
130BP072.10
957RPM
1-71 High starting torque time
0. s
11.58A1 (1)
1-7*Start Adjustments
4
How to Programme
2.1.10 Changing Data
VLT® AutomationDrive Programming Guide
The procedure for changing data is the same in the Quick
and the Main menu mode. Press [OK] to change the
menu
selected parameter.
The procedure for changing data depends on whether the
selected parameter represents a numerical data value or a
text value.
2.1.11 Changing a Text Value
If the selected parameter is a text value, change the text
value
with the [▲] [▼] keys.
Place the cursor on the value to save and press [OK].
Illustration 2.16
2.1.12 Changing
If the chosen parameter represents a numeric data value,
the chosen data value by means of the [◀] [▶]
change
navigation keys as well as the [▲] [▼] navigation keys. Press
[◀] [▶] keys to move the cursor horizontally.
Illustration 2.18
2.1.13 Infinitely Variable Change of
Numeric
If the chosen parameter represents a numeric data value,
select
a digit with [◀] [▶].
Illustration 2.19
Change the selected digit infinitely variably with [▲] [▼].
The chosen digit is indicated by the cursor. Place the
cursor on the digit to save and press [OK].
Data Value
22
Illustration 2.17
Press [▲]
[▼] keys to change the data value. [▲] increases
the data value, and [▼] decreases the data value. Place the
cursor on the value to save and press [OK].
MG33MF02 - VLT® is a registered Danfoss trademark
Illustration 2.20
2.1.14 Value, Step-by-Step
Certain parameters can be changed step by step or
infinitely
1-22 Motor Voltage and 1-23 Motor Frequency.
The parameters are changed both as a group of numeric
data values and as numeric data values infinitely varying.
varying. This applies to 1-20 Motor Power [kW],
19
130BA191.10
1
Auto
on
Reset
Hand
on
O
Menu
Status
Quick
Setup
Main
Menu
Back
2
3
4
OK
On
Alarm
Warn.
Setup
130BP077.10
22.8
rpm
Setup 1
How to Programme
VLT® AutomationDrive Programming Guide
2.1.15 Read-out and Programming of
Indexed
Parameters
22
Parameters are indexed when placed in a rolling stack.
15-30
Fault Log: Error Code to 15-32 Alarm Log: Time contain
a fault log which can be read out. Choose a parameter,
press [OK], and use [▲] [▼] to scroll through the value log.
Use 3-10 Preset Reference as another example:
Choose the parameter, press [OK], and use [▲] [▼] to scroll
through the indexed values. To change the parameter
value, select the indexed value and press [OK]. Change the
value by pressing [▲] [▼]. Press [OK] to accept the new
setting. Press [Cancel] to abort. Press [Back] to leave the
parameter.
The following instructions are valid for the Numerical LCP
(LCP 101).
The control panel is divided into four functional groups:
1.Numerical display.
2.Menu keys and indicator lights - changing
parameters and switching between display
functions.
3.Navigation keys and indicator lights (LEDs).
4.Operation keys and indicator lights (LEDs).
Display line: Status messages displaying icons and numeric
value.
Indicator lights (LEDs)
Green LED/On: Indicates if control section is on.
•
Yellow LED/Wrn.: Indicates a warning.
•
Flashing red LED/Alarm: Indicates an alarm.
•
LCP keys
[Menu] Select one of the following modes:
Status
•
Quick Setup
•
Main Menu
•
Illustration 2.21
Mode
Status
Displays the status of the frequency converter or the
motor.
If an alarm occurs the NLCP automatically switches to
status mode.
A number of alarms can be displayed.
NOTE
Parameter copy is not possible with LCP 101 Numerical
Local Control Panel.
Illustration 2.22
20MG33MF02 - VLT® is a registered Danfoss trademark
Setup 1
130BP078.10
A 17
130BP079.10
Menu
StatusQuick
Setup
Main
Menu
P 2-03
Setup 1
130BP046.10
Hand
on
O
Auto
on
Reset
How to Programme
Illustration 2.23
Main
Menu/Quick Setup is used for programming all
parameters or only the parameters in the Quick Menu (see
also description of the LCP 102 earlier in ).
The parameter values can be changed by pressing [▲] or
[▼] when the value is flashing.
Select Main Menu by pressing [Menu] a number of times.
Select the parameter group [xx-__] and press [OK]
Select the parameter [__-xx] and press [OK]
If the parameter is an array parameter select the array
number and press [OK]
Select the wanted data value and press [OK]
Parameters with functional choices display values such as
[1], [2], etc. For a description of the different choices, see
the individual description of the parameters in 3 Parameter
Descriptions
[Back] for stepping backwards
[▲] [▼] are used for manoeuvring between commands and
within parameters.
VLT® AutomationDrive Programming Guide
possible to enter the motor speed data by means of the
arrow
keys. The key can be selected as [1] Enable or [0]
Disable via 0-40 [Hand on] Key on LCP.
External stop signals activated by means of control signals
or a serial bus will override a 'start' command via the LCP.
The following control signals are still active when [Hand
On] is activated:
[Hand On] - [Off] - [Auto On]
•
Reset
•
Coasting stop inverse
•
Reversing
•
Set-up select lsb - Set-up select msb
•
Stop command from serial communication
•
Quick stop
•
DC brake
•
[Off] stops the connected motor. The key can be selected
as [1] Enable or [0] Disable via 0-41 [Off] Key on LCP.
If no external stop function is selected and the [Off] key is
inactive the motor can be stopped by disconnecting the
voltage.
[Auto On] enables the frequency converter to be
controlled via the control terminals and/or serial communication. When a start signal is applied on the control
terminals and/or the bus, the frequency converter will
start. The key can be selected as [1] Enable or [0] Disable
via 0-42 [Auto on] Key on LCP.
22
Illustration 2.24
2.1.16 Local Control Keys
Keys for local control are found at the bottom of the LCP.
Illustration 2.25
[Hand On] enables
the LCP. [Hand On] also starts the motor and it is now
control of the frequency converter via
NOTE
active HAND-OFF-AUTO signal via the digital inputs has
An
higher priority than the control keys [Hand On] [Auto On].
is used for resetting the frequency converter after
[Reset]
an alarm (trip). It can be selected as [1] Enable or [0]Disable via 0-43 [Reset] Key on LCP.
2.1.17 Initialisation to Default Settings
Initialise the frequency converter to default settings in two
ways.
Recommended
1.
2.Press [OK]
3.Select “Initialisation”
4.Press [OK]
5.Cut off the mains supply and wait until the
initialisation (via 14-22 Operation Mode)
Select 14-22 Operation Mode
display turns off.
MG33MF02 - VLT® is a registered Danfoss trademark
21
How to Programme
6.Reconnect the mains supply - the frequency
converter
22
14-22 Operation Mode initialises all except:
14-50 RFI Filter
8-30 Protocol
8-31 Address
8-32 FC Port Baud Rate
8-35 Minimum Response Delay
8-36 Max Response Delay
8-37 Max Inter-Char Delay
15-00 Operating Hours to 15-05 Over Volt's
15-20 Historic Log: Event to 15-22 Historic Log:
Time
15-30 Fault Log: Error Code to 15-32 Alarm Log:
Time
Manual initialisation
is now reset.
VLT® AutomationDrive Programming Guide
1.Disconnect from mains and wait until the display
turns off.
2.2aPress [Status] - [Main Menu] - [OK] at
the same time while power up for LCP
102, Graphical Display
2bPress [Menu] while power up for LCP
101, Numerical Display
3.Release the keys after 5 s.
4.The frequency converter is now programmed
according to default settings.
This procedure initialises all except:
15-00 Operating Hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
NOTE
A
manual initialisation also resets serial communication, RFI
filter settings (14-50 RFI Filter) and fault log settings.
22MG33MF02 - VLT® is a registered Danfoss trademark
Parameter Descriptions
3 Parameter Descriptions
VLT® AutomationDrive Programming Guide
16-** Readout parameters
3.1 Parameter Selection
Parameters for FC 300 are grouped into various parameter
for easy selection of the correct parameters for
groups
optimized operation of the frequency converter.
0-** Operation and Display parameters
Basic Settings, set-up handling
•
Display and Local Control Panel parameters for
•
choosing readouts, setting up selections and
copying functions
1-** Load and Motor parameters includes all load and
motor related parameters
2-** Brake parameters
DC brake
•
Dynamic brake (Resistor brake)
•
Mechanical brake
•
Over Voltage Control
•
3-** References and ramping parameters includes DigiPot
function
17-**
Encoder Option parameters
18-** Readout 2 parameters
30-** Special Features
32-** MCO Basic Settings parameters
33-** MCO Adv. Settings parameters
34-** MCO Data Readouts
35-** Sensor Input Option parameters
Too see if a parameter can be used in a specific control
mode,
use the table in 4.1.2 Active/Inactive Parameters in
Different Drive Control Modes.
33
4-** Limits Warnings; setting of limits and warning
parameters
5-** Digital inputs and outputs includes relay controls
6-** Analog inputs and outputs
7-** Controls; Setting parameters for speed and process
controls
8-** Communication and option parameters for setting of
FC RS485 and FC USB port parameters.
9-** Profibus parameters
10-** DeviceNet and CAN Fieldbus parameters
12-** Ethernet parameters
13-** Smart Logic Control parameters
14-** Special function parameters
15-** Drive information parameters
MG33MF02 - VLT® is a registered Danfoss trademark
23
Parameter Descriptions
VLT® AutomationDrive Programming Guide
3.2 Parameters: 0-** Operation and Display
Parameters related to the fundamental functions of the
frequency
ration of the LCP display.
33
3.2.1 0-0* Basic Settings
converter, function of the LCP keys and configu-
0-01 Language
Option:Function:
[51] Bahasa Indonesia Part of Language package 2
[52] HrvatskiPart of Language package 3
0-02 Motor Speed Unit
Option:Function:
0-01 Language
Option:Function:
Defines the language to be used in the
The frequency converter can be
display.
delivered with 4 different language
packages. English and German are
included in all packages. English cannot
be erased or manipulated.
[0] * EnglishPart of Language packages 1 - 4
The display showing depends on settings in
Motor Speed Unit and 0-03 Regional Settings. The
0-02
default setting of 0-02 Motor Speed Unit and
0-03 Regional Settings depends on which region of
the world the frequency converter is supplied to, but
can be re-programmed as required.
NOTE
Changing the Motor Speed Unit will reset certain
parameters to their initial value. It is
recommended to select the motor speed unit
[1]DeutschPart of Language packages 1 - 4
[2]FrancaisPart of Language package 1
[3]DanskPart of Language package 1
[4]SpanishPart of Language package 1
[5]ItalianoPart of Language package 1
[6]SvenskaPart of Language package 1
[0]RPM Selects display of motor speed variables and
[1] * HzSelects display of motor speed variables and
first, before modifying other parameters.
parameters
terms of motor speed (RPM).
parameters
terms of output frequency to the motor (Hz).
(i.e. references, feedbacks and limits) in
(i.e. references, feedbacks and limits) in
[7]NederlandsPart of Language package 1
[10] ChinesePart of Language package 2
[20] SuomiPart of Language package 1
[22] English USPart of Language package 4
[27] GreekPart of Language package 4
[28] Bras.portPart of Language package 4
[36] SlovenianPart of Language package 3
[39] KoreanPart of Language package 2
[40] JapanesePart of Language package 2
[41] TurkishPart of Language package 4
[42] Trad.ChinesePart of Language package 2
[43] BulgarianPart of Language package 3
[44] SrpskiPart of Language package 3
[45] RomanianPart of Language package 3
[46] MagyarPart of Language package 3
[47] CzechPart of Language package 3
[48] PolskiPart of Language package 4
[49] RussianPart of Language package 3
NOTE
This
parameter cannot be adjusted while the motor is
running.
0-03 Regional Settings
Option:Function:
[0] * Interna-
tional
[1]US
Activates 1-20
the motor power in kW and sets the default
value of 1-23 Motor Frequency to 50Hz.
Activates 1-20
the motor power in HP and sets the default
value of 1-23 Motor Frequency to 60Hz.
Motor Power [kW] for setting
Motor Power [kW] for setting
NOTE
This
parameter cannot be adjusted while the motor is
running.
0-04 Operating State at Power-up (Hand)
Option:Function:
Selects the operating mode upon
reconnection of the frequency converter to
mains voltage after power down in Hand
(local) operation mode.
[0]ResumeRestarts the frequency converter, maintaining
same and the same start/stop settings
the
[50] ThaiPart of Language package 2
24MG33MF02 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® AutomationDrive Programming Guide
0-04 Operating State at Power-up (Hand)
Option:Function:
(applied by [Hand On/Off]) as before the
converter was powered down.
local reference, after mains voltage
the frequency converter.
[1] * Forced stop,
ref=old
[2]Forced stop,
ref=0
frequency
Restarts the frequency converter with a
saved
reappears and after pressing [Hand On].
Resets the local reference to 0 upon
restarting
3.2.2 0-1* Set-up Operations
Define and control the individual parameter setups.
The
frequency converter has four parameter setups that
can be programmed independently of each other. This
makes the frequency converter very flexible and able to
solve advanced control functionality problems, often
saving the cost of external control equipment. For example
these can be used to program the frequency converter to
operate according to one control scheme in one setup
(e.g. motor 1 for horizontal movement) and another
control scheme in another setup (e.g. motor 2 for vertical
movement). Alternatively they can be used by an OEM
machine builder to identically program all their factory
fitted frequency converters for different machine types
within a range to have the same parameters and then
during production/commissioning simply select a specific
setup depending on which machine the frequency
converter is installed on.
The active setup (i.e. the setup in which the frequency
converter is currently operating) can be selected in
0-10 Active Set-up and is displayed in the LCP. Using Multi
set-up it is possible to switch between setups with the
frequency converter running or stopped, via digital input
or serial communication commands. If it is necessary to
change setups whilst running, ensure 0-12 This Set-upLinked to is programmed as required. Using 0-11 Edit Set-up
it is possible to edit parameters within any of the setups
whilst continuing the frequency converter operation in its
Active Setup which can be a different setup to that being
edited. Using 0-51 Set-up Copy it is possible to copy
parameter settings between the setups to enable quicker
commissioning if similar parameter settings are required in
different setups.
0-10 Active Set-up
Option:Function:
[1] * Set-up 1
[2]Set-up 2
[3]Set-up 3
[4]Set-up 4
[9]Multi Set-upRemote selection of set-ups using digital
Use 0-51
Set-up Copy to copy a set-up to one or all other
[1] Set-up 1
separate parameter set-ups within which all
parameters can be programmed.
inputs
This set-up uses the settings from 0-12 ThisSet-up Linked to. Stop the frequency
converter before making changes to openand closed loop functions
to [4] Set-up 4 are the four
and the serial communication port.
set-ups. Stop the frequency converter before switching
between set-ups where parameters marked ‘not
changeable during operation’ have different values. To
avoid conflicting settings of the same parameter within
two different set-ups, link the set-ups together using
0-12 This Set-up Linked to. Parameters which are ‘not
changeable during operation’ are marked FALSE in the
parameter lists in 4 Parameter Lists.
0-11 Edit Set-up
Option:Function:
Select the set-up to be edited (i.e.
programmed)
active set-up or one of the inactive set-ups.
[0]Factory setup Cannot be edited but it is useful as a data
source
known state.
[1] * Set-up 1
[2]Set-up 2
[3]Set-up 3
[4]Set-up 4
[9]Active Set-up Can also be edited during operation. Edit
[1] Set-up 1
freely during operation, independently of
the active set-up.
chosen set-up from a range of sources:
the
LCP, FC RS-485, FC USB or up to five fieldbus
sites.
during operation; either the
to return the other set-ups to a
to [4] Set-up 4 can be edited
33
0-10 Active Set-up
Option:Function:
Select the set-up to control the frequency
converter
[0]Factory setup Cannot be changed. It contains the Danfoss
data
when returning the other set-ups to a
known state.
functions.
set, and can be used as a data source
MG33MF02 - VLT® is a registered Danfoss trademark
25
130BA199.10
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
P 0-11
P 0-11
P 0-11
P 0-11
Set-up
Set-up
Set-up
Set-up
PLC Fieldbus
130BP075.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling 0-1*
[1]
Setup 1
130BP076.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[2]
Setup 2
Parameter Descriptions
VLT® AutomationDrive Programming Guide
0-12 This Set-up Linked to
Option:Function:
Set-up 2 are synchronised (or ‘linked’). Synchro-
can be performed in two ways:
nisation
1. Change the edit set-up to Set-up 2 [2] in
33
0-11 Edit Set-up and set 0-12 This Set-up Linked
to to Set-up 1 [1]. This will start the linking
(synchronising) process.
Illustration 3.2
OR
While still in Set-up 1, copy Set-up 1 to Set-
2.
up 2. Then set 0-12 This Set-up Linked to to Set-up 2 [2]. This will start the linking process.
Illustration 3.1
0-12 This Set-up Linked to
Option:Function:
26MG33MF02 - VLT® is a registered Danfoss trademark
To enable conflict-free changes from one set-up
another during operation, link set-ups
to
containing parameters which are not
changeable during operation. The link will
ensure synchronising of the ‘not changeable
during operation’ parameter values when
moving from one set-up to another during
operation. ‘Not changeable during operation’
parameters can be identified by the label FALSE
in the parameter lists in the section Parameter
Lists.
0-12 This Set-up Linked to is used by Multi set-
up in 0-10 Active Set-up. Multi set-up is used to
move from one set-up to another during
operation (i.e. while the motor is running).
Example:
Use Multi set-up to shift from Set-up 1 to Setup 2 whilst the motor is running. Programme in
Set-up 1 first, then ensure that Set-up 1 and
changeable during operation’ parameters are
now the same in Set-up 1 and Set-up 2. If there
are changes to a ‘not changeable during
operation’ parameter, e.g. 1-30 Stator Resistance(Rs), in Set-up 2, they will also be changed
automatically in Set-up 1. A switch between
Set-up 1 and Set-up 2 during operation is now
possible.
Parameter Descriptions
VLT® AutomationDrive Programming Guide
0-13 Readout: Linked Set-ups
Array [5]
Range:Function:
0 * [0 - 255 ] View a list of all the set-ups linked by means of
This Set-up Linked to. The parameter has one
0-12
index for each parameter set-up. The parameter
value displayed for each index represents which
set-ups are linked to that parameter set-up.
IndexLCP value
0{0}
1{1,2}
2{1,2}
3{3}
4{4}
Table 3.2 Example: Set-up 1 and Set-up 2 are
linked
0-14 Readout: Edit Set-ups / Channel
Range:Function:
0
N/A*
[-2147483648 2147483647
N/A]
View the setting of 0-11
each of the four different communication channels. When the number is
displayed in hex, as it is in the LCP, each
number represents one channel.
Numbers 1-4 represent a set-up number;
‘F’ means factory setting; and ‘A’ means
active set-up. The channels are, from
right to left: LCP, FC-bus, USB, HPFB1-5.
Example: The number AAAAAA21h
means that the FC bus selected Set-up 2
in 0-11 Edit Set-up, the LCP selected Setup 1 and all others used the active setup.
Edit Set-up for
0-15 Readout: actual setup
Range:Function:
0 * [0 - 255 ] Makes it possible to read out the active set-up,
when multi set-up is selected in 0-10 Active
also
Set-up.
3.2.3 0-2* LCP Display
Define the variables displayed in the Graphical Local
Control
Panel.
NOTE
Please
refer to 0-37 Display Text 1, 0-38 Display Text 2 and
0-39 Display Text 3 for information on how to write display
texts.
0-20 Display Line 1.1 Small
Option:Function:
Select a variable for display in
1, left position.
line
[0] *NoneNo display value selected.
[953]Profibus Warning
Word
[1005]Readout Transmit
Counter
Error
[1006]Readout Receive Error
Counter
[1007]Readout Bus Off
Counter
[1013]Warning Parameter
[1230]Warning Parameter
[1472]VLT Alarm Word
[1473]VLT Warning Word
[1474]VLT Ext. Status Word
[1501]Running Hours
[1502]kWh Counter
[1600]Control WordPresent control word
[1601]Reference [Unit]Total reference (sum of digital/
analog/preset/bus/freeze
catch up and slow-down) in
selected unit.
[1602]Reference %Total reference (sum of digital/
analog/preset/bus/freeze
catch up and slow-down) in
percent.
[1603]Status WordPresent status word.
[1605]Main Actual Value [%] Actual value as a percentage.
[1609]Custom Readout
[1610]Power [kW]Actual power consumed by the
in kW.
motor
[1611]Power [hp]Actual power consumed by the
in HP.
motor
[1612]Motor VoltageVoltage supplied to the motor.
[1613]FrequencyMotor frequency, i.e. the output
frequency
converter in Hz
[1614]Motor CurrentPhase current of the motor
measured
[1615]Frequency [%]Motor frequency, i.e. the output
frequency
converter in percent.
[1616]Torque [Nm]Actual motor torque in Nm
[1617] * Speed [RPM]Speed in RPM (revolutions per
minute)
speed in closed loop.
from the frequency
as effective value.
from the frequency
i.e. the motor shaft
ref./
ref./
33
MG33MF02 - VLT® is a registered Danfoss trademark
27
Parameter Descriptions
VLT® AutomationDrive Programming Guide
0-20 Display Line 1.1 Small
Option:Function:
[1618]Motor ThermalThermal load on the motor,
calculated
[1619]KTY sensor
33
[1620]Motor Angle
[1622]Torque [%]Present motor load as a
[1625]Torque [Nm] High
[1630]DC Link VoltageIntermediate circuit voltage in
[1632]Brake Energy /sPresent brake power transferred
[1633]Brake Energy /2 minBrake power transferred to an
[1634]Heatsink Temp.Present heat sink temperature
[1635]Inverter ThermalPercentage load of the inverters.
[1636]Inv. Nom. CurrentNominal current of the
[1637]Inv. Max. CurrentMaximum current of the
[1638]SL Controller StateState of the event executed by
[1639]Control Card Temp.Temperature of the control card.
[1650]External ReferenceSum of the external reference as
[1651]Pulse ReferenceFrequency in Hz connected to
[1652]Feedback [Unit]Reference value from
[1653]Digi Pot Reference
[1660]Digital InputSignal states form the 6 digital
temperature
percentage
torque.
the
to
Stated as an instantaneous
value.
external
mean power is calculated
continuously for the most
recent 120 s.
of
cut-out limit is 95 ±5 °C; cutting
back in occurs at 70 ±5 °C.
frequency
frequency
the
a
analog/pulse/bus.
the
33).
programmed
terminals
33). There are 16 bits in total,
but only six of them are used.
Input 18 corresponds to the
leftmost of the used bits. Signal
low = 0; Signal high = 1.
by the ETR function.
of the rated motor
frequency converter.
an external brake resistor.
brake resistor. The
the frequency converter. The
converter.
converter.
control.
percentage, i.e. the sum of
digital inputs (18, 19 or 32,
digital input(s).
(18, 19, 27, 29, 32 and
0-20 Display Line 1.1 Small
Option:Function:
[1661]Terminal 53 Switch
Setting
[1662]Analog Input 53Actual value at input 53 either
[1663]Terminal 54 Switch
Setting
[1664]Analog Input 54Actual value at input 54 either
[1665]Analog Output 42
[mA]
[1666]Digital Output [bin]Binary value of all digital
[1667]Freq. Input #29 [Hz]Actual value of the frequency
[1668]Freq. Input #33 [Hz]Actual value of the frequency
[1669]Pulse Output #27 [Hz] Actual value of impulses applied
[1670]Pulse Output #29 [Hz] Actual value of impulses applied
[1674]Prec. Stop CounterDisplay the actual counter value.
[1675]Analog In X30/11Actual value at input X30/11
[1676]Analog In X30/12Actual value at input X30/12
[1677]Analog Out X30/8
[mA]
[1678]Analog Out X45/1
[mA]
[1679]Analog Out X45/3
[mA]
[1680]Fieldbus CTW 1Control word (CTW) received
Setting of input terminal 54.
= 0; Voltage = 1.
Current
a reference or protection
as
value.
Setting of input terminal 54.
= 0; Voltage = 1.
Current
reference or protection value.
as
Actual value at output 42 in
Use 6-50 Terminal 42 Output
mA.
to select the value to be shown.
outputs.
at terminal 29 as an
applied
impulse input.
at terminal 33 as an
applied
impulse input.
terminal 27 in digital output
to
mode.
terminal 29 in digital output
to
mode.
Control)
Control)
as reference or protection
either
value.
as reference or protection
either
value.
Actual value at output X30/8 in
Use 6-60 Terminal X30/8
mA.
Output to select the value to be
shown.
the Bus Master.
from
28MG33MF02 - VLT® is a registered Danfoss trademark
Parameter Descriptions
VLT® AutomationDrive Programming Guide
0-20 Display Line 1.1 Small
Option:Function:
[1682]Fieldbus REF 1Main reference value sent with
word from the Bus
control
Master.
[1684]Comm. Option STWExtended fieldbus communi-
option status word.
cation
[1685]FC Port CTW 1Control word (CTW) received
the Bus Master.
from
[1686]FC Port REF 1Status word (STW) sent to the
Master.
Bus
[1690]Alarm WordOne or more alarms in a Hex
code.
[1691]Alarm Word 2One or more alarms in a Hex
code.
[1692]Warning WordOne or more warnings in a Hex
code.
[1693]Warning Word 2One or more warnings in a Hex
code.
[1694]Ext. Status WordOne or more status conditions
a Hex code.
in
[3401]PCD 1 Write to MCO
[3402]PCD 2 Write to MCO
[3403]PCD 3 Write to MCO
[3404]PCD 4 Write to MCO
[3405]PCD 5 Write to MCO
[3406]PCD 6 Write to MCO
[3407]PCD 7 Write to MCO
[3408]PCD 8 Write to MCO
[3409]PCD 9 Write to MCO
[3410]PCD 10 Write to MCO
[3421]PCD 1 Read from
MCO
[3422]PCD 2 Read from
MCO
[3423]PCD 3 Read from
MCO
[3424]PCD 4 Read from
MCO
[3425]PCD 5 Read from
MCO
[3426]PCD 6 Read from
MCO
[3427]PCD 7 Read from
MCO
[3428]PCD 8 Read from
MCO
[3429]PCD 9 Read from
MCO
[3430]PCD 10 Read from
MCO
[3440]Digital Inputs
0-20 Display Line 1.1 Small
Option:Function:
[3441]Digital Outputs
[3450]Actual Position
[3451]Commanded Position
[3452]Actual Master Position
[3453]Slave Index Position
[3454]Master Index Position
[3455]Curve Position
[3456]Track Error
[3457]Synchronizing Error
[3458]Actual Velocity
[3459]Actual Master Velocity
[3460]Synchronizing Status
[3461]Axis Status
[3462]Program Status
[3470]MCO Alarm Word 1
[3471]MCO Alarm Word 2
[9913]Idle time
[9914]Paramdb requests in