Installation guide
Max. 100 °C / 210 °F
Max. 130
Thermostatic expansion valve
Type TR 6
Refrigerants:
R22/R407C and R410A
067R9508
A
Max. working pressure:
PS / MWP = 42 bar / 610 psig
Flow direction:
B
Normal: A → B
Reverse: B → A
Qnom. A → B [kW / TR] = 100%
Q
B → A [kW / TR] = 80% Adjustable settingFixed setting
nom.
Max. test pressure:
47 bar / 680 psig
067R9508
A B
Min. 5% Ag
Danfoss
°C / 265 °F R22 / R407C: Max. 100 °C / 210 °F
R410A: Max. 75 °C / 167 °F
t-lived peak 150 °C / 300 °F
67-74.11
© Danfoss I DCS (sw) I 2015.12
DKRCC.PI.AN0.A5.02 / 520H8512 | 1
Factory setting
SS = 2 °C / 3.6 °F or according to customer specication
Danfoss
67-81.11
© Danfoss I DCS (sw) I 2015.12
= 19 mm /
3
/
in.
4
Torque = 10 Nm / 7 ft-lb
SH / 1 turn / 360 °
R22 / R407C: 1.0 °C / 1.8 °F
R410A: 0.8 °C / 1.1 °F
Refrigerant Number of turns
from SS to
tight spring
Number of turns
from SS to
loose spring
R22 / R407C +7.25 –4.25
R410A +9.5 –2
DKRCC.PI.AN0.A5.02 / 520H8512 | 2