Condensing pressure regulator, type KVR
Differential pressure valve, type NRD
Regulating system KVR and NRD is used to
maintain a constant and sufficiently high
condenser and receiver pressure in refrigeration
and air conditioning plant with air-cooled
condensers.
KVR can also be used together with receiver
pressure regulator, type KVD.
Minimum opening pressure differential for NRDStart opening: Δp = 1.4 bar
KVR 12 - KVR 22 is evaluated for R290, R454A, R454C,
R455A, R600, R600a, R1234ze(E), R1270 by ignition
source assessment in accordance with standard
EN13463-1.
R452B**, R454A*, R454B**, R454C*, R455A*, R507, R513A,
R515B, R516A, R600*, R600a*, R1233zd(E)**, R1234ze(E)*,
R1234yf**
*KVR 12 - KVR 22 and NRD only
**NRD only
5 – 17.5 bar
Factory setting = 10 bar
KVR: PS/MWP = 28 bar
NRD: PS/MWP = 49 bar
KVR: Pe = 31 bar
NRD: Pe = 81 bar
KVR: -45 – 130 °C,
NRD: -50 – 155 °C
KVR 12 – 22 = 6.2 bar
KVR 28 – 35 = 5 bar
For complete list of approved refrigerants,
visit http://store.danfoss.com/ and search for
individual code numbers, where refrigerants are
listed as part of technical data.
NRD is evaluated for R32, R1270, R290, R452B, R454A,
R454B, R454C R455A, R600, R600a, R1233zd(E),
R1234ze(E), R1234yf by ignition source assessment in
accordance with standard EN13463-1.
All Danfoss products fulfill the requirements in REACH.
One of the obligations in REACH is to inform customers about
presence of Candidate list substances if any, we hereby inform
you about one substance on the candidate list:
an O-ring used in this product contains Diisopentylphthalat
(CAS no: 605-50-5) in a concentration above 0.1% w/w.
AI251086497566en-000901 | 2
Data sheet | Condensing pressure regulator, type KVR and differential pressure valve, type NRD
Liquid capacity
Max. regulator capacity Qe 1)
Liquid capacity in [kW]
Condensing
Type
KVR 12
KVR 15
KVR 22
KVR 28
KVR 35
KVR 12
KVR 15
KVR 22
KVR 28
KVR 35
1
) The capacities are based on:
temperature t
– Evaporating temperature te= -10 °C
– For other evaporating temperatures see table below