Danfoss Electronics MCD 500 Features and Benefits

VLT® Soft Starter MCD 500
VLT® Soft Starter MCD 500 is a total motor starting solution. Current transformers measure motor current and provide feedback for controlled motor ramp proles.
AAC, Adaptive Acceleration Control, automatically employs the best starting and stopping prole for the application.
Adaptive Acceleration Control means that for each start and stop, the soft
Perfect
match for: – Pumps – Conveyors – Fans – Mixers – Compressors – Centrifuges – Mills – Saws, and many more
starter compares and adapts the process to the chosen prole tting to the application.
Three menu systems: Quick Menu, Application Setup and Main Menu provide optimum programming
approach. VLT® Soft Starter MCD 500 has a four line graphical display and a logic keypad making programming easy. Advanced setup is possible displaying operational status.
Power range:
21 – 1600 A, 10 – 1140 HP
(1600 HP inside Delta Connection)
Versions for 200 – 690 VAC
Feature Benet
AAC Adaptive Acceleration Control
Adjustable bus bars allow for both top and bottom entry (360–1600 A, 160–850 kW)
DC injection braking distributed evenly over three phases
Inside Delta (6-wire connection)
Log menus, 99 events and trip log provide information on events, trips and performance
Auto Reset – Less down-time Jog (slow-speed operation) – Application exibility
Second-order thermal model
Internal bypass contactors (21–215 A, 7.5–110 kW)
Auto-start/stop clock – Application exibility Compact size – amongst the smallest
in their class
4-line graphical display
Multiple programming setup (Standard Menu, Extended Menu, Quick Set)
Multiple languages – Serving the whole world
100%
90%
80%
70%
60%
50%
Speed
40%
30%
20%
10%
0
Three Adapt ive Acceleration Control (AAC) star t proles; early, constant and late acceleration
Time
– Automatically adapts to the chosen
starting and stopping prole
– Space saving, less cable cost
and easy retrotting
– Less installation cost and
less stress on the motor
– Smaller soft starter can be selected
for the application
– Eases analysis of the application
– Allows motors to be used to their full
potential without damage from overloading
– Saves space and wiring compared to
external bypass
– Very little heat dissipates when running.
Eliminates costly external fans, wiring or bypass contactors
– Saves space in cabinets and other application
setups
– Optimum programming approach and setup
for viewing operational status
– Simplies the programming, but still holding
to maximum exibility
700%
600%
500%
400%
300%
200%
100%
Current (% motor full load current)
10% 20% 30% 40% 50%
Rotor speed (% full speed)
Constant current / current ramp – here shown with
kicksta rt
60%70% 80%90% 100%
Fully featured Soft Starter for motors up to 850 kW
Total motor starting solution Advanced start, stop and
protection features
Adaptive Acceleration Control Inside Delta connection 4-line graphical display Multiple programming setup menus
Optional:
Modules for serial communication:
– DeviceNet – Probus – Modbus RTU – USB
Control Panel VLT® LCP 501 PC software:
– WinMaster
– WinStart
– VLT® MCT10
Control Panel VLT® LCP 501
A full function HMI interface –
everything you can do on the VLT® Soft Starter MCD 500 is possible via the LCP 501
Danfoss “FC” menu structure
and button interface concept
Multiple language selection
– incl. Russian and Chinese
Full graphics Real language in 4 lines Full parameter list, Quick Menu
and application setup
Adjustable multiple monitoring views A “copy-paste” function allows the user
to copy parameter settings in the LCP and load to other unit.
IP 65, NEMA 12 3 m cable and mounting kit included
Specications
Mains voltage (L1, L2, L3)
MCD5-xxxx-T5 200 VAC ~ 525 VAC (± 10%) MCD5-xxxx-T7 380 VAC ~ 690 VAC (± 10%) (in-line connection) MCD5-xxxx-T7 380 VAC ~ 600 VAC (± 10%) ´(inside delta conn ection)
Control voltage (terminals A4, A5, A6)
CV1 (A5, A6) 24 VAC/VDC (± 20%) CV2 (A5, A6) 110~120 VAC (+ 10% / - 15%) CV2 (A4, A6) 220~240 VAC (+ 10% / - 15%) Mains frequency 50/60 Hz (± 10%) Rated insulation voltage to earth 600 VAC Rated impulse withstand voltage 4 kV
Form designation
Short circuit capability
Coordination with semiconductor fuses Typ e 2 Coordination with HRC fuses Typ e 1 MCD500-0021B to 0215B Prospective current of 65 kA MCD500-0245C Prospective current of 85 kA MCD500-1200C to 1600C Prospective current of 100 kA
Electromagnetic capability (compliant with EU Directive 89/336/EEC)
EMC Emissions (Terminals 13 & 14)
EMC Immunity IEC 60947-4-2
Outputs
Relay Outputs
Programmable Outputs Relay A (13, 14) Normally open Relay B (21, 22, 24) Changeover Relay C (33, 34) Normally open Analogue Output (07, 08) 0 – 20 mA or 4 – 20 mA (selectable) Maximum load 600 Ω (12 VDC @ 20 mA) (accuracy ± 5%) 24 VDC Output (16, 08) Maximum load 200 mA (accuracy ± 10%)
Environmental
Protection MCD5-0021B ~ MCD5-0105B IP 20 & NEMA, UL Indoor Type 1 Protection MCD5-0131B ~ MCD5-1600C IP 00, UL Indoor Open Type Operating temperature -10° C to 60° C, above 40° C with derating Storage temperature - 25° C to + 60° C Operating Altitude 0 – 1000 m, above 1000 m with derating Humidity 5% to 95% Relative Humidity Pollution degree Pollution Degree 3
Heat Dissipation
During start 4.5 watts per ampere
Bypassed or continuous, semiconductor motor starter form 1
IEC 60947-4-2 Class B and Lloyds Marine No. 1 Specication
10A @ 250 VAC resistive, 5A @ 250 VAC AC15 pf 0.3
Dimensions
Current rating [A] Weight [kg] Height [mm] Width [mm] Depth [mm] Frame size
21, 37, 43 and 53 4.2
68 4.5
84, 89 and 105 4.9 213
131, 141, 195 and 215 14.9 438 275 250 G2
245 23.9 460 390 279 G3
360, 380 and 428 35
595, 619, 790 and 927 45
1200, 1410 and 1600 12 0 856 585 364 G5
295 150
689 430 302 G4
183
G1