Danfoss Electronics MCD 500 Operating Instructions

MAKING MODERN LIVING POSSIBLE
Operating Instructions
VLT® Soft Starter MCD 500
vlt-drives.danfoss.com
Contents Operating Instructions
Contents
1 Safety
1.1 Warnings
2 Introduction
3 Installation
3.1 Mechanical Installation
3.2 Dimensions and Weights
4 Electrical Installation
4.1 Control Wiring
4.1.1 Ways to Control the Soft Starter 13
4.1.2 Control Terminals 13
4.1.3 Remote Inputs 13
4.1.4 Serial Communication 14
4.1.5 Ground Terminal 14
4.1.6 Power Terminations 15
4.2 Power Input and Output Congurations
10
10
11
13
13
16
4.2.1 Internally Bypassed Models (MCD5-0021B to MCD5-0961B) 16
4.2.2 MCD5-0245C 17
4.2.3 MCD5-0360C to MCD5-1600C 17
4.3 Motor Connection
4.3.1 Testing the Installation 17
4.3.2 In-line Installation 18
4.3.2.1 Internally Bypassed 18
4.3.2.2 Non-bypassed 18
4.3.2.3 Externally Bypassed 18
4.3.3 Inside Delta Installation 19
4.3.3.1 Internally Bypassed 19
4.3.3.2 Non-bypassed 19
4.3.3.3 Externally Bypassed 20
4.4 Current Ratings
4.4.1 In-line Connection (Bypassed) 21
4.4.2 In-line Connection (Non-bypassed/Continuous) 22
4.4.3 Inside Delta Connection (Bypassed) 23
17
20
4.4.4 Inside Delta Connection (Non-bypassed/Continuous) 24
4.5 Minimum and Maximum Current Settings
4.6 Bypass Contactor
4.7 Main Contactor
4.8 Circuit Breaker
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 1
25
26
26
26
Contents
VLT® Soft Starter MCD 500
4.9 Power Factor Correction
4.10 Fuses
4.10.1 Power Supply Fuses 26
4.10.2 Bussmann Fuses 27
4.10.3 Ferraz Fuses 29
4.10.4 UL Fuse Selection and Short Circuit Ratings 31
4.11 Schematic Diagrams
5 Product Features
5.1 Motor Overload Protection
5.2 Adaptive Control
5.3 Starting Modes
5.3.1 Constant Current 36
5.3.2 Current Ramp 36
5.3.3 Adaptive Control 36
5.3.4 Kick Start 37
5.4 Stopping Modes
5.4.1 Coast to Stop 37
26
26
33
35
35
35
36
37
5.4.2 TVR Soft Stop 37
5.4.3 Adaptive Control 38
5.4.4 Pump Stopping 38
5.4.5 Brake 38
5.5 Jog Operation
5.6 Inside Delta Operation
5.7 Typical Start Currents
5.8 Installation with Main Contactor
5.9 Installation with Bypass Contactor
5.10 Emergency Run Operation
5.11 Auxiliary Trip Circuit
5.12 DC Brake with External Zero-speed Sensor
5.13 Soft Braking
5.14 Two-speed Motor
6 Operation
6.1 Control Methods
6.2 Operation and LCP
39
40
41
42
43
44
45
46
47
48
50
50
51
6.2.1 Operating Modes 51
6.3 Remote Mounted LCP
6.3.1 Synchronising the LCP and the Soft Starter 52
6.4 Welcome Screen
6.5 Local Control Keys
2 Danfoss A/S © 10/2015 All rights reserved. MG17K502
52
52
52
Contents Operating Instructions
6.6 Displays
6.6.1 Temperature Monitoring Screen (S1) 53
6.6.2 Programmable Screen (S2) 53
6.6.3 Average Current (S3) 53
6.6.4 Current Monitoring Screen (S4) 53
6.6.5 Frequency Monitoring Screen (S5) 53
6.6.6 Motor Power Screen (S6) 53
6.6.7 Last Start Information (S7) 53
6.6.8 Date and Time (S8) 53
6.6.9 SCR Conduction Bargraph 54
6.6.10 Performance Graphs 54
7 Programming
7.1 Access Control
7.2 Quick Menu
7.2.1 Quick Set-up 55
7.2.2 Application Set-up Examples 56
7.2.3 Loggings 57
52
55
55
55
7.3 Main Menu
7.3.1 Parameters 57
7.3.2 Parameter Shortcut 57
7.3.3 Parameter List 58
8 Parameter Descriptions
8.1 Primary Motor Settings
8.1.1 Brake 60
8.2 Protection
8.2.1 Current Imbalance 60
8.2.2 Undercurrent 61
8.2.3 Instantaneous Overcurrent 61
8.2.4 Frequency Trip 61
8.3 Inputs
8.4 Outputs
8.4.1 Relay A Delays 63
8.4.2 Relays B and C 63
8.4.3 Low Current Flag and High Current Flag 64
57
59
59
60
62
63
8.4.4 Motor Temperature Flag 64
8.4.5 Analog Output A 64
8.5 Start/Stop Timers
8.6 Auto-Reset
8.6.1 Auto-Reset Delay 65
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 3
64
65
Contents
VLT® Soft Starter MCD 500
8.7 Secondary Motor Set
8.8 Display
8.8.1 User Programmable Screen 67
8.8.2 Performance Graphs 68
8.9 Restricted Parameters
8.10 Protection Action
8.11 Factory Parameters
9 Tools
9.1 Set Date and Time
9.2 Load/Save Settings
9.3 Reset Thermal Model
9.4 Protection Simulation
9.5 Output Signal Simulation
9.6 Digital I/O State
9.7 Temp Sensors State
9.8 Alarm Log
9.8.1 Trip Log 72
65
67
68
69
69
70
70
70
70
71
71
71
72
72
9.8.2 Event Log 72
9.8.3 Counters 72
10 Troubleshooting
10.1 Trip Messages
10.2 General Faults
11 Specications
11.1 UL Compliant Installation
11.1.1 Models MCD5-0021B to MCD5-0105B 82
11.1.2 Models MCD5-0131B to MCD5-0215B 82
11.1.3 Models MCD5-0245B to MCD5-0396B 82
11.1.4 Models MCD5-0245C 82
11.1.5 Models MCD5-0360C to MCD5-1600C 82
11.1.6 Models MCD5-0469B to MCD5-0961B 82
11.1.7 Pressure Terminal/Connector Kits 82
11.2 Accessories
11.2.1 LCP Remote Mounting Kit 82
73
73
78
80
82
82
11.2.2 Communication Modules 82
11.2.3 PC Software 83
11.2.4 Finger Guard Kit 83
11.2.5 Surge Protection Kit (Lightning Protection) 83
12 Busbar Adjustment Procedure (MCD5-0360C to MCD5-1600C)
4 Danfoss A/S © 10/2015 All rights reserved. MG17K502
84
Contents Operating Instructions
13 Appendix
13.1 Symbols, Abbreviations, and Conventions
Index
86
86
87
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 5
Safety
VLT® Soft Starter MCD 500
11
1 Safety
1.1 Warnings
When reading this manual, pay special attention to the following symbols:
NOTICE
Useful hints for the reader.
CAUTION
Indicates a general warning.
WARNING
Indicates a high-voltage warning.
The examples and diagrams in this manual are included solely for illustrative purposes. The information contained in this manual is subject to change at any time and without prior notice. Responsibility or liability is under no circumstances accepted for direct, indirect, or consequential damages resulting from the use or application of this equipment.
NOTICE
Before changing any parameter settings, save the current parameter to a le using MCD PC Software or the Save User Set function.
WARNING
WARNING - ELECTRICAL SHOCK HAZARD
VLT® Soft Starters MCD 500 contain dangerous voltages when connected to mains voltage. Only a competent electrician should carry out the electrical installation. Improper installation of the motor or the soft starter can cause equipment failure, serious injury, or death. Follow the guidelines in this manual and local electrical safety codes. Models MCD5-0360C ~ MCD5-1600C: Treat the bus bar and heat sink as live whenever the unit has mains voltage connected (including when the soft starter is tripped or waiting for a command).
WARNING
Disconnect the soft starter from mains voltage before carrying out repair work. It is the responsibility of the person installing the soft starter to provide proper grounding and branch circuit protection according to local electrical safety codes. Do not connect power factor correction capacitors to the output of MCD 500 soft starters. If static power factor correction is employed, it must be connected to the supply side of the soft starter. MCD5-0021B ~ MCD5-961B: After transportation, mechanical shock, or rough handling there is a risk that the bypass contactor has latched into the On state. To prevent the motor from starting immediately, on rst commissioning, or operation after transportation, always ensure that the control supply is applied before the power. Applying control supply before power ensures that the contactor state is initialised.
WARNING
SAFETY OF PERSONNEL
The soft starter is not a safety device and does not provide electrical isolation or disconnection from the supply.
If isolation is required, the soft starter must be
installed with a main contactor.
The start and stop functions of the soft starter
must not be relied upon for personnel safety. Faults occurring in the mains supply, the motor connection, or the electronics of the soft starter, can cause unintended motor starts or stops.
To provide machine or personnel safety, control the isolation device through an external safety system.
In Auto On mode, the motor can be controlled remotely (via remote inputs) while the soft starter is connected to mains.
CAUTION
These stop functions are not sucient to avoid unintended start. If faults occur in the electronics of the soft starter, a motor that has been stopped may start. A temporary fault in the supply mains or a cease in the motor connection can also cause a stopped motor to start.
6 Danfoss A/S © 10/2015 All rights reserved. MG17K502
Safety Operating Instructions
CAUTION
Use the Auto start feature with caution. Read all the notes related to Auto start before operation.
Equipment containing electrical
components may not be disposed of
together with domestic waste.
It must be collected separately as
electrical and electronic waste
according to local and currently valid
legislation.
Table 1.1 Disposal Instructions
1 1
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 7
Introduction
2 Introduction
VLT® Soft Starter MCD 500
22
The VLT® Soft Starter MCD 500 is an advanced digital soft start solution for motors 11–850 kW. The soft starters provide a complete range of motor and system protection features, and are designed for reliable performance in the most demanding installation situations.
2.1.1 Feature List
Models for all connection requirements
21–1600 A (in-line connection).
In-line or inside delta connection.
Internally bypassed up to 961 A.
Mains voltage: 200–525 V AC or 380–690 V AC.
Control voltage: 24 V AC/V DC, 110–120 V AC, or
220–240 V AC.
User-friendly LCP
Loggings.
Real-time graphs.
SCR conduction bar graph.
Tools
Application set-ups.
Date and time stamped event log with 99 entries.
8 most recent trips.
Counters.
Protection simulation.
Output signal simulation.
Inputs and outputs
Local or remote control input options.
(3 x xed, 1 x programmable).
Relay outputs (3 x programmable).
Analog programmable output.
24 V DC 200 mA supply output.
Start and run modes
Adaptive control.
Constant current.
Current ramp.
Kick start.
Jog.
Emergency run operation.
Stop modes
Adaptive deceleration control.
Timed voltage ramp soft stop.
DC brake.
Soft brake.
Starter disable.
Other features
Auto start/stop timer.
Second order thermal model.
Battery back-up of clock and thermal model.
Optional DeviceNet, Modbus, Ethernet, or
PROFIBUS communication modules.
Comprehensive protection
Wiring/Connection/Supply
- Motor connection.
- Phase sequence.
- Power loss.
- Individual phase loss.
- Mains frequency.
Current
- Excess start time.
- Current imbalance.
- Undercurrent.
- Instantaneous overcurrent.
Thermal
- Motor thermistor.
- Motor overload.
- Bypass contactor overload.
- Heat sink temperature.
Communication
- Network comms.
- Starter comms.
External
- Input trip.
Starter
- Individually short-circuited SCR.
- Battery/clock.
8 Danfoss A/S © 10/2015 All rights reserved. MG17K502
MCD 5
- -
-
-
0021 = 21 A, AC53b 3-30:330 0037 = 37 A, AC53b 3-30:330 0043 = 43 A, AC53b 3-30:330 0053 = 53 A, AC53b 3-30:330
0068 = 68 A, AC53b 3-30:570 0084 = 84 A, AC53b 3-30:570
0089 = 89 A, AC53b 3-30:570 0105 = 105 A, AC53b 3-30:570 0131 = 131 A, AC53b 3-30:570 0141 = 141 A, AC53b 3-30:570 0195 = 195 A, AC53b 3-30:570 0215 = 215 A, AC53b 3-30:570 0245 = 245 A, AC53b 3-30:570 0331 = 331 A, AC53b 3-30:570 0396 = 396 A, AC53b 3-30:570 0469 = 469 A, AC53b 3-30:570 0525 = 525 A, AC53b 3-30:570 0632 = 632 A, AC53b 3-30:570 0744 = 744 A, AC53b 3-30:570 0826 = 826 A, AC53b 3-30:570
0961 = 961 A, AC53b 3-30:570
00 = IP00 20 = IP20
G1 = 0021 ~ 0105 A G2 = 0131 ~ 0215 A G3 = 0245 ~ 0396 A G4 = 0360 ~ 0961 A G5 = 1200 ~ 1600 A
0245 = 245 A, AC53a 3-30:50-6 0360 = 360 A, AC53a 3-30:50-6 0380 = 380 A, AC53a 3-30:50-6 0428 = 428 A, AC53a 3-30:50-6 0595 = 595 A, AC53a 3-30:50-6 0619 = 619 A, AC53a 3-30:50-6 0790 = 790 A, AC53a 3-30:50-6
0927 = 927 A,AC53a 3-30:50-6
1200 = 1200 A, AC53a 3-30:50-6 1410 = 1410 A, AC53a 3-30:50-6 1600 = 1600 A, AC53a 3-30:50-6
177HA382.11
Current rating
B = Bypassed
C = Non-bypassed
Mains voltage T5 = 200 - 525 VAC T7 = 380 - 690 VAC
Frame size
= Not selectable
Not used
IP rating
Control voltage
CV1 = 24 VAC/VDC
CV2 = 110-120 VAC or 220-240 VAC
Introduction Operating Instructions
2.1.2 Type Code
2 2
Illustration 2.1 Type Code Ordering Form
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 9
Installation
VLT® Soft Starter MCD 500
3 Installation
3.1 Mechanical Installation
33
1 MCD5-0021B to MCD5-0215B: Allow 100 mm (3.94 inches) between the soft starters.
MCD5-0245B to MCD5-0961B: Allow 200 mm (7.88 inches) between the soft starters.
MCD5-0245C: Allow 100 mm (3.94 inches) between the soft starters.
MCD5-0360C to MCD5-1600C: Allow 200 mm (7.88 inches) between the soft starters.
2 MCD5-0021B to MCD5-0215B: Allow 50 mm (1.97 inches) between the soft starter and solid surfaces.
MCD5-0245B to MCD5-0961B: Allow 200 mm (7.88 inches) between soft starters.
MCD5-0245C: Allow 100 mm (3.94 inches) between the soft starter and solid surfaces.
MCD5-0360C to MCD5-1600C: Allow 200 mm (7.88 inches) between the soft starter and solid surfaces.
3 It is possible to mount the soft starter on its side. Derate the soft starter rated current by 15%.
4 If mounted without communication modules, soft starters may be mounted side-by-side with no clearance.
Illustration 3.1 Clearances and Derating Values at Installation
10 Danfoss A/S © 10/2015 All rights reserved. MG17K502
177HA514.10
Installation Operating Instructions
3.2 Dimensions and Weights
3 3
Model A [mm] (in) B [mm] (in) C [mm] (in) D [mm] (in) E [mm] (in) Weight [kg] (lbs)
MCD5-0021B
MCD5-0037B
MCD5-0043B
MCD5-0053B
MCD5-0068B
MCD5-0084B
MCD5-0089B
MCD5-0105B
MCD5-0131B
MCD5-0141B
MCD5-0195B
MCD5-0215B
MCD5-0245B
MCD5-0331B
MCD5-0396B
MCD5-0469B
MCD5-0525B
MCD5-0632B
MCD5-0744B
MCD5-0826B
MCD5-0961B
MCD5-0245C
MCD5-0360C
MCD5-0380C
MCD5-0428C
MCD5-0595C
MCD5-0619C
MCD5-0790C
MCD5-0927C
295
(11.6)
438
(17.2)
440
(17.3)
640
(25.2)
460
(18.1)
689
(27.1)
278
(10.9)
380
(15.0)
392
(15.4)
600
(23.6)
400
(15.0)
522
(20.5)
150
(5.9)
275
(10.8)
424
(16.7)
433
(17.0)
390
(15.4)
430
(16.9)
124
(4.9)
248
(9.8)
376
(14.8)
320
(12.6)
320
(12.6)
320
(12.6)
183
(7.2)
213
(8.14)
250
(9.8)
296
(11.7)
295
(11.6)
279
(11.0)
300
(11.8)
4.2
(9.3)
4.5
(9.9)
4.9
(10.8)
14.9
(32.8)
26 (57.2)
30.2
(66.6)
49.5
(109.1)
60.0
(132.3)
23.9
(52.7)
35
(77.2)
45
(99.2)
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 11
Installation
Model A [mm] (in) B [mm] (in) C [mm] (in) D [mm] (in) E [mm] (in) Weight [kg] (lbs)
MCD5-1200C
MCD5-1410C
MCD5-1600C
856
(33.7)
VLT® Soft Starter MCD 500
727
(28.6)
585
(23.0)
500
(19.7)
364
(14.3)
120
(264.6)
33
Illustration 3.2 Dimensions and Weights
12 Danfoss A/S © 10/2015 All rights reserved. MG17K502
177HA504.10
Start/stop
Reset
Start
Stop
Reset
Start
Stop
Reset
15
16
17
18
25
18
15
16
17
18
25
18
15
16
17
18
25
18
2
3
1
Electrical Installation Operating Instructions
4 Electrical Installation
4.1 Control Wiring
4.1.1 Ways to Control the Soft Starter
Control the soft starter in 3 ways:
Pressing the keys on the LCP.
Via remote inputs.
Via a serial communication link.
The MCD 500 always responds to a local start or stop command (via the [Hand On] and [O] keys on the LCP). Pressing the [Auto On] key selects remote control (the soft starter accepts commands from the remote inputs). In remote mode, the Auto On LED is on. In local mode, the Hand On LED is on if the soft starter starts or runs. The O LED is on if the soft starter is stopped or stops.
4.1.2 Control Terminals
Control terminations use 2.5 mm2 plug-in terminal blocks. Dierent models require control voltage to dierent terminals:
NOTICE
SELV oers protection by way of extra low voltage. Protection against electric shock is ensured when the electrical supply itself is of the SELV type and the instal­lation follows local/national regulations on SELV supplies.
4 4
NOTICE
Galvanic (ensured) isolation is obtained by fullling requirements for higher isolation and by providing the relevant creepages/clearance distances. These requirements are described in the IEC 61140 standard. The components that make up the electrical isolation also comply with the requirements for higher isolation and the relevant test as described in IEC 61140.
4.1.3 Remote Inputs
The soft starter has 3 xed inputs for remote control. Control these inputs by contacts rated for low voltage, low current operation (gold ash or similar).
CV1 (24 V AC/V DC): A5, A6.
CV2 (110–120 V AC): A5, A6.
CV2 (220–240 V AC): A4, A6.
1 2-wire control
2 3-wire control
3 4-wire control
Illustration 4.2 2-, 3-, and 4-wire Control
Illustration 4.1 Wiring to Control Terminals
The reset input can be normally open or normally closed. To select the conguration, use parameter 3-8 Remote Reset Logic.
NOTICE
Do not short terminals 05 and 06 without using a thermistor.
All control terminals and relay terminals comply with SELV (Safety Extra Low Voltage). This protection does not apply to grounded delta leg above 400 V.
To maintain SELV, all connections made to the control terminals must be PELV (for example thermistor must be reinforced/double insulated from motor).
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 13
CAUTION
Do not apply voltage to the control input terminals. These terminals are active 24 V DC inputs and must be controlled with potential-free contacts. Segregate cables to the control inputs from mains voltage and motor cabling.
Electrical Installation
VLT® Soft Starter MCD 500
4.1.4 Serial Communication
Control via the serial communication network is always enabled in local control mode and can be enabled or disabled in remote control mode (see parameter 3-2 Comms in Remote). Control via the serial communication network requires an optional communication module.
44
4.1.5 Ground Terminal
Ground terminals are located at the back of the soft starter.
MCD5-0021B to MCD5-0105B have 1 terminal on
the input side (top).
MCD5-0131B to MCD5-0961B and MCD5-0245C to
MCD5-1600C have 2 terminals, 1 on the input side (top), and 1 on the output side (bottom).
14 Danfoss A/S © 10/2015 All rights reserved. MG17K502
177HA646.10
177HA647.10
177HA648.10
177HA649.10
5 mm
15 mm
28 mm
11 mm
(M10)
177HA643.10
6 mm
15 mm
28 mm
11 mm
(M10)
177HA644.10
13 mm
12 mm
32 mm
11 mm
(M10)
177HA645.10
Electrical Installation Operating Instructions
4.1.6 Power Terminations
NOTICE
For personnel safety, snap-o tabs protect the power terminals on models up to MCD5-0105B. When using large cables, it may be necessary to break o these tabs.
NOTICE
Some units use aluminium busbars. When connecting power terminations, clean the surface contact area thoroughly (using an emery or stainless steel brush), and use an appropriate jointing compound to prevent corrosion.
Use only copper stranded or solid conductors, rated for 75 °C or higher.
4 4
Cable size: 6–50 mm2 (AWG 10-1/0)
14 mm (0.55 inch)
Torx T20 x 150
Torque: 4 Nm (2.9 ft-lb)
Flat 7 mm x 150
MCD5-0021B to MCD5-0105B
38 Nm (28 ft-lb)
MCD5-0131B MCD5-0141B to MCD5-0215B MCD5-0245B
38 Nm (28 ft-lb) 38 Nm (28 ft-lb)
MCD5-0331B to MCD5-0396B MCD5-0469B to MCD5-0961B MCD5-0245C
MCD5-0360C to MCD5-0927C MCD5-1200C to MCD5-1600C
Table 4.1 Measurements and Torques for Power Terminations
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 15
20.0
1/L1, 3/L2, 5/L3
2/T1, 4/T2, 6/T3
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
1/L1 3/L2 5/L3
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
177HA650.10
Electrical Installation
VLT® Soft Starter MCD 500
4.2 Power Input and Output Congurations
4.2.1 Internally Bypassed Models (MCD5-0021B to MCD5-0961B)
Models MCD5-0021B to MCD5-0215B have power inputs at the top of the unit and outputs at the bottom of the unit.
Internally bypassed models MCD5-0245B to MCD5-0396B have output busbars at the bottom of the unit and input busbars at both the top and bottom. The AC supply can be connected top-in, bottom-out or bottom-in, bottom-out.
44
Internally bypassed models MCD5-0469B to MCD5-0961B have input and output busbars at the top and bottom of the unit. The AC supply can be connected:
Top-in/bottom-out.
Top-in/top-out.
Bottom-in/bottom-out.
Bottom-in/top-out.
Illustration 4.3 Internally Bypassed Models, MCD5-0021B to MCD5-0105B, MCD5-0131B to MCD5-0215B, MCD5-0245B to MCD5-0396B,
MCD5-0469B to MCD5-0961B
16 Danfoss A/S © 10/2015 All rights reserved. MG17K502
177HA651.10
1/L1 3/L2 5/L3
T1B T2B T3B
2/T1 4/T2 6/T3
(L1B L2B L3B)
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
1/L1 3/L2 5/L3
(L1B L2B L3B)
2/T1 4/T2 6/T3
(L1B L2B L3B)
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
1/L1 3/L2 5/L3
(L1B L2B L3B)
2/T1 4/T2 6/T3
177HA652.10
Electrical Installation Operating Instructions
4.2.2 MCD5-0245C
MCD5-0245C has dedicated bypass terminals at the bottom of the unit. The bypass terminals are:
T1B
T2B
T3B
Illustration 4.4 Bypass Terminals on MCD5-0245C
4.2.3 MCD5-0360C to MCD5-1600C
4 4
Illustration 4.5 Location of Bypass Terminals, MCD5-0360C to
MCD5-1600C
4.3 Motor Connection
MCD 500 soft starters can be connected to the motor in­line or inside delta (also called 3-wire and 6-wire connection). When connecting in inside delta, enter the motor full load current (FLC) for parameter 1-1 Motor Full Load Current. The MCD 500 automatically calculates inside delta current based on this data. Parameter 15-7 Motor Connection is set to Auto Detect as default and can be set to force the soft starter in inside delta or in-line.
MCD5-0360C to MCD5-1600C have dedicated bypass terminals on the input busbars. The bypass terminals are:
The busbars on non-bypassed models MCD5-0360C to MCD5-1600C can be adjusted for top or bottom input and output as required. See chapter 12 Busbar Adjustment Procedure (MCD5-0360C to MCD5-1600C) for step-by-step instructions. The soft starters are manufactured top-in/ bottom-out.
NOTICE
For models MCD5-0360C to MCD5-1600C to be UL­compliant, mount them top-in, bottom-out, or top-out, bottom-in. See chapter 11.1 UL Compliant Installation for more information.
L1B
L2B
L3B
4.3.1 Testing the Installation
The MCD 500 can be connected to a small motor for testing. During this test, the control input and relay output protection settings can be tested. This test mode is not suitable for testing soft starting or soft stopping performance.
The minimum FLC of the test motor is 2% of the minimum FLC of the soft starter (see chapter 4.5 Minimum and Maximum Current Settings).
NOTICE
When testing the soft starter with a small motor, set parameter 1-1 Motor FLC to the minimum allowable value. Models which are internally bypassed do not require an external bypass contactor.
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 17
177HA430.12
M
3
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
K1
K1 F1
177HA429.12
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
K1
K1 F1
M
3
177HA617.11
M
3
F1
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
K1
K1
T1B
T2B
T3B
K2
34
33
K2
Electrical Installation
VLT® Soft Starter MCD 500
4.3.2 In-line Installation
4.3.2.1 Internally Bypassed
4.3.2.3 Externally Bypassed
Non-bypassed models have dedicated bypass terminals, which allow the soft starter to continue providing protection and monitoring functions even when bypassed via an external contactor. Connect the bypass contactor to the bypass terminals and control it by a programmable output congured to Run (see parameters 4-1 to 4-9).
44
NOTICE
The bypass terminals on MCD5-0245C are:
T1B
T2B
T3B
The bypass terminals on MCD5-0360C to MCD5-1600C are:
L1B
L2B
K1 Main contactor (optional)
F1 Semiconductor fuses (optional)
L3B
If necessary, the fuses can be installed on the input side.
Illustration 4.6 In-line Installation, Internally Bypassed
4.3.2.2 Non-bypassed
K1 Main contactor
K2 Bypass contactor (external)
F1 Semiconductor fuses (optional)
K1 Main contactor (optional)
F1 Semiconductor fuses (optional)
Illustration 4.7 In-line Installation, Non-bypassed
18 Danfoss A/S © 10/2015 All rights reserved. MG17K502
Illustration 4.8 In-line Installation, Externally Bypassed,
MCD5-0245C
177HA431.12
M
3
F1
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
K1
K1
L1B
L2B
L3B
K2
34
33
K2
6/T
2/T
13
14
4/T
K1
U1(1) U2(4)
V1(2)
V2(5)
W1(3) W2(6)
5/L3
3/L2
1/L1
E
K1 F1
M
3
177HA501.11
177HA500.12
M
3
6/T
2/T
5/L
3/L
1/L
1
1
4/T
K1
K1 F
U1(1 U2(4
V1(2
V2(5
W1( W2(
L2
L1
L3
E
Electrical Installation Operating Instructions
4.3.3.1 Internally Bypassed
4 4
K1 Main contactor
K2 Bypass contactor (external)
F1 Semiconductor fuses (optional)
Illustration 4.9 In-line Installation, Externally Bypassed,
MCD5-0360Cto MCD5-1600C
4.3.3 Inside Delta Installation
CAUTION
When connecting the MCD 500 in inside delta congu- ration, always install a main contactor or shunt trip circuit breaker.
NOTICE
When connecting in inside delta, enter the motor full load current (FLC) for parameter 1-1 Motor FLC. The MCD 500 automatically calculates inside delta currents based on this data. Parameter 15-7 Motor Connection is set to Auto detect as default and can be set to force the soft starter in inside delta or in-line.
K1 Main contactor
F1 Semiconductor fuses (optional)
Illustration 4.10 Inside Delta Installation, Internally Bypassed
4.3.3.2 Non-bypassed
K1 Main contactor
F1 Semiconductor fuses (optional)
Illustration 4.11 Inside Delta Installation, Non-bypassed
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 19
177HA618.11
M
3
6/T
2/T
5/L3
3/L2
1/L1
13
14
4/T
E
K1
K1
U1(1) U2(4)
V1(2)
V2(5)
W1(3) W2(6)
T2B
T1B
T3B
K2
34
33
K2
F1
177HA502.12
M
3
6/T
2/T
5/L3
3/L2
1/L1
13
14
4/T
E
K1
K1 F1
U1(1) U2(4)
V1(2)
V2(5)
W1(3) W2(6)
L2B
L1B
L3B
K2
34
33
K2
Electrical Installation
VLT® Soft Starter MCD 500
4.3.3.3 Externally Bypassed
Non-bypassed models have dedicated bypass terminals, which allow the soft starter to continue providing protection and monitoring functions even when bypassed via an external bypass contactor. Connect the bypass contactor to the bypass terminals and control the contactor by a programmable output congured to Run (see parameters 4-1 to 4-9).
44
NOTICE
The bypass terminals on MCD5-0245C are:
T1B
T2B
T3B
The bypass terminals on MCD5-0360C to MCD5-1600C are:
L1B
L2B
L3B
If necessary, the fuses can be installed on the input side.
K1 Main contactor
K2 Bypass contactor (external)
F1 Semiconductor fuses (optional)
Illustration 4.13 Inside Delta Installation, Externally Bypassed,
MCD5-0360C to MCD5-1600C
K1 Main contactor
K2 Bypass contactor (external)
F1 Semiconductor fuses (optional)
Illustration 4.12 Inside Delta Installation, Externally Bypassed,
MCD5-0245C
Current Ratings
4.4
Contact the local supplier for ratings under operating conditions not covered by these ratings charts.
All ratings are calculated at an altitude of 1000 m and ambient temperature of 40 °C.
20 Danfoss A/S © 10/2015 All rights reserved. MG17K502
Electrical Installation Operating Instructions
4.4.1 In-line Connection (Bypassed)
NOTICE
Models MCD5-0021B to MCD5-0961B are internally bypassed. Models MCD5-0245C to MCD5-1600C require an external bypass contactor.
Type code Ampere rating
AC-53b
3-30:330
[A]
MCD5-0021B 21 17 15
MCD5-0037B 37 31 26
MCD5-0043B 43 37 30
MCD5-0053B 53 46 37
AC-53b
3-30:570
[A]
MCD5-0068B 68 55 47
MCD5-0084B 84 69 58
MCD5-0089B 89 74 61
MCD5-0105B 105 95 78
MCD5-0131B 131 106 90
MCD5-0141B 141 121 97
MCD5-0195B 195 160 134
MCD5-0215B 215 178 148
MCD5-0245B 245 194 169
MCD5-0245C 255 201 176
MCD5-0331B 331 266 229
MCD5-0360C 360 310 263
MCD5-0380C 380 359 299
MCD5-0396B 396 318 273
MCD5-0428C 430 368 309
MCD5-0469B 496 383 326
MCD5-0525B 525 425 364
MCD5-0595C 620 540 434
MCD5-0619C 650 561 455
MCD5-0632B 632 512 438
MCD5-0790C 790 714 579
MCD5-0744B 744 606 516
MCD5-0826B 826 684 571
MCD5-0927C 930 829 661
MCD5-0961B 961 796 664
MCD5-1200C 1200 1200 1071
MCD5-1410C 1410 1319 1114
MCD5-1600C 1600 1600 1353
AC-53b
4-20:340
[A]
AC-53b
4-20:580
[A]
AC-53b
4.5-30:330
[A]
AC-53b
4.5-30:570
[A]
4 4
Table 4.2 Internally Bypassed Models
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 21
Start Time (seconds)
Starts Per Hour
Electrical Installation
VLT® Soft Starter MCD 500
44
Illustration 4.14 AC-53 Rating for Bypassed Operation
All ratings are calculated at an altitude of 1000 m and ambient temperature of 40 °C.
4.4.2 In-line Connection (Non-bypassed/Continuous)
Type code Ampere ratings
AC-53a
3-30:50-6
MCD5-0245C 245 A 195 A 171 A
MCD5-0360C 360 A 303 A 259 A
MCD5-0380C 380 A 348 A 292 A
MCD5-0428C 428 A 355 A 300 A
MCD5-0595C 595 A 515 A 419 A
MCD5-0619C 619 A 532 A 437 A
MCD5-0790C 790 A 694 A 567 A
MCD5-0927C 927 A 800 A 644 A
MCD5-1200C 1200 A 1135 A 983 A
MCD5-1410C 1410 A 1187 A 1023 A
MCD5-1600C 1600 A 1433 A 1227 A
Table 4.3 Non-bypassed Models
AC-53a
4-20:50-6
AC-53a
4.5-30:50-6
Illustration 4.15 AC-53 Rating for Continuous Operation
All ratings are calculated at an altitude of 1000 m and ambient temperature of 40 °C.
Contact a local supplier for ratings under operating conditions not covered by these ratings charts.
22 Danfoss A/S © 10/2015 All rights reserved. MG17K502
Electrical Installation Operating Instructions
4.4.3 Inside Delta Connection (Bypassed)
NOTICE
Models MCD5-0021B to MCD5-0961B are internally bypassed. Models MCD5-0245C to MCD5-1600C require an external bypass contactor.
Type code Ampere ratings
AC-53b
3-30:330
[A]
MCD5-0021B 32 26 22
MCD5-0037B 56 47 39
MCD5-0043B 65 56 45
MCD5-0053B 80 69 55
AC-53b
3-30:570
[A]
MCD5-0068B 102 83 71
MCD5-0084B 126 104 87
MCD5-0089B 134 112 92
MCD5-0105B 158 143 117
MCD5-0131B 197 159 136
MCD5-0141B 212 181 146
MCD5-0195B 293 241 201
MCD5-0215B 323 268 223
MCD5-0245B 368 291 254
MCD5-0245C 383 302 264
MCD5-0331B 497 400 343
MCD5-0360C 540 465 395
MCD5-0380C 570 539 449
MCD5-0396B 594 478 410
MCD5-0428C 645 552 463
MCD5-0469B 704 575 490
MCD5-0525B 787 637 546
MCD5-0595C 930 810 651
MCD5-0619C 975 842 683
MCD5-0632B 948 768 658
MCD5-0790C 1185 1072 869
MCD5-0744B 1116 910 774
MCD5-0826B 1239 1026 857
MCD5-0927C 1395 1244 992
MCD5-0961B 1441 1194 997
MCD5-1200C 1800 1800 1607
MCD5-1410C 2115 1979 1671
MCD5-1600C 2400 2400 2030
AC-53b
4.20-:340
[A]
AC-53b
4-20:580
[A]
AC-53b
4.5-30:330
[A]
AC-53b
4.5-30:570
[A]
4 4
Table 4.4 Bypassed Models
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 23
Start Time (seconds)
Starts Per Hour
Electrical Installation
VLT® Soft Starter MCD 500
44
Illustration 4.16 AC-53 Rating for Bypassed Operation
All ratings are calculated at an altitude of 1000 m and ambient temperature of 40 °C.
4.4.4 Inside Delta Connection (Non-bypassed/Continuous)
Type code Ampere ratings
AC-53a
3-30:50-6
MCD5-0245C 368 A 293 A 257 A
MCD5-0360C 540 A 455 A 389 A
MCD5-0380C 570 A 522 A 438 A
MCD5-0428C 643 A 533 A 451 A
MCD5-0595C 893 A 773 A 629 A
MCD5-0619C 929 A 798 A 656 A
MCD5-0790C 1185 A 1042 A 851 A
MCD5-0927C 1391 A 1200 A 966 A
MCD5-1200C 1800 A 1702 A 1474 A
MCD5-1410C 2115 A 1780 A 1535 A
MCD5-1600C 2400 A 2149 A 1841 A
Table 4.5 Non-bypassed Models
AC-53a
4-20:50-6
AC-53a
4.5-30:50-6
Illustration 4.17 AC-53 Rating for Continuous Operation
All ratings are calculated at an altitude of 1000 m and ambient temperature of 40 °C.
Contact a local supplier for ratings under operating conditions not covered by these ratings charts.
24 Danfoss A/S © 10/2015 All rights reserved. MG17K502
Electrical Installation Operating Instructions
4.5 Minimum and Maximum Current Settings
The minimum and maximum full load current settings depend on the model:
In-line connection Inside delta connection
Model Minimum [A] Maximum [A] Minimum [A] Maximum [A]
MCD5-0021B 5 23 7 34
MCD5-0037B 9 43 13 64
MCD5-0043B 10 50 15 75
MCD5-0053B 11 53 16 79
MCD5-0068B 15 76 23 114
MCD5-0084B 19 97 29 145
MCD5-0089B 20 100 30 150
MCD5-0105B 21 105 32 157
MCD5-0131B 29 145 44 217
MCD5-0141B 34 170 51 255
MCD5-0195B 40 200 60 300
MCD5-0215B 44 220 66 330
MCD5-0331B 70 350 70 525
MCD5-0396B 85 425 85 638
MCD5-0469B 100 500 100 750
MCD5-0525B 116 580 116 870
MCD5-0632B 140 700 140 1050
MCD5-0744B 164 820 164 1230
MCD5-0825B 184 920 184 1380
MCD5-0961B 200 1000 200 1500
MCD5-0245C 51 255 77 382
MCD5-0360C 72 360 108 540
MCD5-0380C 76 380 114 570
MCD5-0428C 86 430 129 645
MCD5-0595C 124 620 186 930
MCD5-0619C 130 650 195 975
MCD5-0790C 158 790 237 1185
MCD5-0927C 186 930 279 1395
MCD5-1200C 240 1200 360 1800
MCD5-1410C 282 1410 423 2115
MCD5-1600C 320 1600 480 2400
4 4
Table 4.6 Minimum and Maximum Full Load Current
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 25
Electrical Installation
VLT® Soft Starter MCD 500
4.6 Bypass Contactor
Some MCD 500 soft starters are internally bypassed and do not require an external bypass contactor.
HRC fuses (such as Ferraz AJT fuses) can be used for Type 1 coordination according to the IEC 60947-4-2 standard.
CAUTION
Non-bypassed soft starters may be installed with an external bypass contactor. Select a contactor with an AC1 rating greater than or equal to the full load current rating of the connected motor.
44
4.7 Main Contactor
A main contactor must be installed if the MCD 500 is connected to the motor in inside delta format and is optional for in-line connection. Select a contactor with an AC3 rating greater than or equal to the full load current rating of the connected motor.
4.8 Circuit Breaker
A shunt trip circuit breaker may be used instead of a main contactor to isolate the motor circuit in the event of a soft starter trip. The shunt trip mechanism must be powered from the supply side of the circuit breaker or from a separate control supply.
Power Factor Correction
4.9
Adaptive control controls the speed prole of the motor within the programmed time limit. This control may result in a higher level of current than traditional control methods.
For applications using adaptive control to soft stop the motor with stop times greater than 30 s, select motor branch protection as follows:
Standard HRC mains fuses: Minimum 150% motor
full load current.
Motor rated mains fuses: Minimum rating
100/150% motor full load current.
Motor control circuit breaker minimum long time
setting: 150% motor full load current.
Motor control circuit breaker minimum short time
setting: 400% motor full load current for 30 s.
Fuse recommendations are calculated for 40 °C, up to 1000 m.
CAUTION
EQUIPMENT DAMAGE
Connect power factor correction capacitors to the input side of the soft starter. Connecting power factor correction capacitors to the output side damages the soft starter.
If power factor correction is used, use a dedicated contactor to switch in the capacitors.
Fuses
4.10
4.10.1 Power Supply Fuses
Semiconductor fuses can be used for Type 2 coordination (according to the IEC 60947-4-2 standard). They reduce the risk of damage to SCRs from transient overload currents.
NOTICE
Fuse selection is based on a 400% FLC start for 20 s with:
Standard published starts per hour.
Duty cycle.
40 °C ambient temperature.
Up to 1000 m altitude.
For installations operating outside these conditions, consult a local Danfoss supplier. Table 4.7 to Table 4.12 contain recommendations only. Always consult a local supplier to conrm the selection for a particular application.
26 Danfoss A/S © 10/2015 All rights reserved. MG17K502
Electrical Installation Operating Instructions
4.10.2 Bussmann Fuses
Model
MCD5-0021B 1150 170M1314 170M1314 170M1314
MCD5-0037B 8000 170M1316 170M1316 170M1316
MCD5-0043B 10500 170M1318 170M1318 170M1318
MCD5-0053B 15000 170M1318 170M1318 170M1318
MCD5-0068B 15000 170M1319 170M1319 170M1318
MCD5-0084B 512000 170M1321 170M1321 170M1319
MCD5-0089B 80000 170M1321 170M1321 170M1321
MCD5-0105B 125000 170M1321 170M1321 170M1321
MCD5-0131B 125000 170M1321 170M1321 170M1321
MCD5-0141B 320000 170M2621 170M2621 170M2621
MCD5-0195B 320000 170M2621 170M2621 170M2621
MCD5-0215B 320000 170M2621 170M2621 170M2621
MCD5-0245B 320000 170M2621 170M2621 170M2621
MCD5-0331B 202000 170M5011 170M5011
MCD5-0396B 320000 170M6011
MCD5-0469B 320000
MCD5-0525B 781000 170M6013 170M6013 170M6013
MCD5-0632B 781000 170M5015 170M5015
MCD5-0744B 1200000 170M5017 170M6017
MCD5-0826B 2530000 170M6017 170M6017
MCD5-0961B 2530000 170M6018
MCD5-0245C 320000 170M2621 170M2621 170M2621
MCD5-0360C 320000 170M6010 170M6010 170M6010
MCD5-0380C 320000 170M6011 170M6011
MCD5-0428C 320000 170M6011 170M6011
MCD5-0595C 1200000 170M6015 170M6015 170M6014
MCD5-0619C 1200000 170M6015 170M6015 170M6014
MCD5-0790C 2530000 170M6017 170M6017 170M6016
MCD5-0927C 4500000 170M6019 170M6019 170M6019
MCD5-1200C 4500000 170M6021
MCD5-1410C 6480000
MCD5-1600C 12500000
SCR I2t (A2s)
Supply voltage
(440 V AC)
170M6008
170M6019
1)
1)
Supply voltage
(575 V AC)
170M6013
1)
Supply voltage
(690 V AC)
4 4
Table 4.7 Square Body (170M)
1) Two fuses connected in parallel are required per phase.
MG17K502 Danfoss A/S © 10/2015 All rights reserved. 27
Loading...
+ 65 hidden pages