When reading this manual, pay special attention to the
following symbols:
NOTICE
Useful hints for the reader.
CAUTION
Indicates a general warning.
WARNING
Indicates a high-voltage warning.
The examples and diagrams in this manual are included
solely for illustrative purposes. The information contained
in this manual is subject to change at any time and
without prior notice. Responsibility or liability is under no
circumstances accepted for direct, indirect, or
consequential damages resulting from the use or
application of this equipment.
NOTICE
Before changing any parameter settings, save the current
parameter to a le using MCD PC Software or the SaveUser Set function.
WARNING
WARNING - ELECTRICAL SHOCK HAZARD
VLT® Soft Starters MCD 500 contain dangerous voltages
when connected to mains voltage. Only a competent
electrician should carry out the electrical installation.
Improper installation of the motor or the soft starter can
cause equipment failure, serious injury, or death. Follow
the guidelines in this manual and local electrical safety
codes.
Models MCD5-0360C ~ MCD5-1600C:
Treat the bus bar and heat sink as live whenever the unit
has mains voltage connected (including when the soft
starter is tripped or waiting for a command).
WARNING
Disconnect the soft starter from mains voltage before
carrying out repair work.
It is the responsibility of the person installing the soft
starter to provide proper grounding and branch circuit
protection according to local electrical safety codes.
Do not connect power factor correction capacitors to the
output of MCD 500 soft starters. If static power factor
correction is employed, it must be connected to the
supply side of the soft starter.
MCD5-0021B ~ MCD5-961B:
After transportation, mechanical shock, or rough
handling there is a risk that the bypass contactor has
latched into the On state. To prevent the motor from
starting immediately, on rst commissioning, or
operation after transportation, always ensure that the
control supply is applied before the power. Applying
control supply before power ensures that the contactor
state is initialised.
WARNING
SAFETY OF PERSONNEL
The soft starter is not a safety device and does not
provide electrical isolation or disconnection from the
supply.
If isolation is required, the soft starter must be
•
installed with a main contactor.
The start and stop functions of the soft starter
•
must not be relied upon for personnel safety.
Faults occurring in the mains supply, the motor
connection, or the electronics of the soft starter,
can cause unintended motor starts or stops.
To provide machine or personnel safety, control the
isolation device through an external safety system.
In Auto On mode, the motor can be controlled remotely
(via remote inputs) while the soft starter is connected to
mains.
CAUTION
These stop functions are not sucient to avoid
unintended start.
If faults occur in the electronics of the soft starter, a
motor that has been stopped may start. A temporary
fault in the supply mains or a cease in the motor
connection can also cause a stopped motor to start.
The VLT® Soft Starter MCD 500 is an advanced digital soft
start solution for motors 11–850 kW. The soft starters
provide a complete range of motor and system protection
features, and are designed for reliable performance in the
most demanding installation situations.
The MCD 500 always responds to a local start or stop
command (via the [Hand On] and [O] keys on the LCP).
Pressing the [Auto On] key selects remote control (the soft
starter accepts commands from the remote inputs). In
remote mode, the Auto On LED is on. In local mode, the
Hand On LED is on if the soft starter starts or runs. The O
LED is on if the soft starter is stopped or stops.
4.1.2 Control Terminals
Control terminations use 2.5 mm2 plug-in terminal blocks.
Dierent models require control voltage to dierent
terminals:
NOTICE
SELV oers protection by way of extra low voltage.
Protection against electric shock is ensured when the
electrical supply itself is of the SELV type and the installation follows local/national regulations on SELV supplies.
44
NOTICE
Galvanic (ensured) isolation is obtained by fullling
requirements for higher isolation and by providing the
relevant creepages/clearance distances. These
requirements are described in the IEC 61140 standard.
The components that make up the electrical isolation
also comply with the requirements for higher isolation
and the relevant test as described in IEC 61140.
4.1.3 Remote Inputs
The soft starter has 3 xed inputs for remote control.
Control these inputs by contacts rated for low voltage, low
current operation (gold ash or similar).
CV1 (24 V AC/V DC): A5, A6.
•
CV2 (110–120 V AC): A5, A6.
•
CV2 (220–240 V AC): A4, A6.
•
12-wire control
23-wire control
34-wire control
Illustration 4.2 2-, 3-, and 4-wire Control
Illustration 4.1 Wiring to Control Terminals
The reset input can be normally open or normally closed.
To select the conguration, use parameter 3-8 Remote ResetLogic.
NOTICE
Do not short terminals 05 and 06 without using a
thermistor.
All control terminals and relay terminals comply with SELV
(Safety Extra Low Voltage). This protection does not apply
to grounded delta leg above 400 V.
To maintain SELV, all connections made to the control
terminals must be PELV (for example thermistor must be
reinforced/double insulated from motor).
Do not apply voltage to the control input terminals.
These terminals are active 24 V DC inputs and must be
controlled with potential-free contacts.
Segregate cables to the control inputs from mains
voltage and motor cabling.
Electrical Installation
VLT® Soft Starter MCD 500
4.1.4 Serial Communication
Control via the serial communication network is always
enabled in local control mode and can be enabled or
disabled in remote control mode (see parameter 3-2Comms in Remote). Control via the serial communication
network requires an optional communication module.
44
4.1.5 Ground Terminal
Ground terminals are located at the back of the soft
starter.
MCD5-0021B to MCD5-0105B have 1 terminal on
•
the input side (top).
MCD5-0131B to MCD5-0961B and MCD5-0245C to
•
MCD5-1600C have 2 terminals, 1 on the input
side (top), and 1 on the output side (bottom).
For personnel safety, snap-o tabs protect the power terminals on models up to MCD5-0105B. When using large cables,
it may be necessary to break o these tabs.
NOTICE
Some units use aluminium busbars. When connecting power terminations, clean the surface contact area thoroughly
(using an emery or stainless steel brush), and use an appropriate jointing compound to prevent corrosion.
Use only copper stranded or solid conductors, rated for 75 °C or higher.
44
Cable size: 6–50 mm2 (AWG 10-1/0)
14 mm (0.55 inch)
Torx T20 x 150
Torque: 4 Nm (2.9 ft-lb)
Flat 7 mm x 150
MCD5-0021B to MCD5-0105B
38 Nm (28 ft-lb)
MCD5-0131BMCD5-0141B to MCD5-0215BMCD5-0245B
38 Nm (28 ft-lb)38 Nm (28 ft-lb)
MCD5-0331B to MCD5-0396BMCD5-0469B to MCD5-0961BMCD5-0245C
MCD5-0360C to MCD5-0927CMCD5-1200C to MCD5-1600C
Table 4.1 Measurements and Torques for Power Terminations
4.2.1 Internally Bypassed Models (MCD5-0021B to MCD5-0961B)
Models MCD5-0021B to MCD5-0215B have power inputs at the top of the unit and outputs at the bottom of the unit.
Internally bypassed models MCD5-0245B to MCD5-0396B have output busbars at the bottom of the unit and input busbars
at both the top and bottom. The AC supply can be connected top-in, bottom-out or bottom-in, bottom-out.
44
Internally bypassed models MCD5-0469B to MCD5-0961B have input and output busbars at the top and bottom of the unit.
The AC supply can be connected:
Top-in/bottom-out.
•
Top-in/top-out.
•
Bottom-in/bottom-out.
•
Bottom-in/top-out.
•
Illustration 4.3 Internally Bypassed Models, MCD5-0021B to MCD5-0105B, MCD5-0131B to MCD5-0215B, MCD5-0245B to MCD5-0396B,
MCD5-0245C has dedicated bypass terminals at the bottom
of the unit. The bypass terminals are:
T1B
•
T2B
•
T3B
•
Illustration 4.4 Bypass Terminals on MCD5-0245C
4.2.3 MCD5-0360C to MCD5-1600C
44
Illustration 4.5 Location of Bypass Terminals, MCD5-0360C to
MCD5-1600C
4.3 Motor Connection
MCD 500 soft starters can be connected to the motor inline or inside delta (also called 3-wire and 6-wire
connection). When connecting in inside delta, enter the
motor full load current (FLC) for parameter 1-1 Motor FullLoad Current. The MCD 500 automatically calculates inside
delta current based on this data. Parameter 15-7 MotorConnection is set to Auto Detect as default and can be set
to force the soft starter in inside delta or in-line.
MCD5-0360C to MCD5-1600C have dedicated bypass
terminals on the input busbars. The bypass terminals are:
•
•
•
The busbars on non-bypassed models MCD5-0360C to
MCD5-1600C can be adjusted for top or bottom input and
output as required. See chapter 12 Busbar AdjustmentProcedure (MCD5-0360C to MCD5-1600C) for step-by-step
instructions. The soft starters are manufactured top-in/
bottom-out.
NOTICE
For models MCD5-0360C to MCD5-1600C to be ULcompliant, mount them top-in, bottom-out, or top-out,bottom-in. See chapter 11.1 UL Compliant Installation for
more information.
L1B
L2B
L3B
4.3.1 Testing the Installation
The MCD 500 can be connected to a small motor for
testing. During this test, the control input and relay output
protection settings can be tested. This test mode is not
suitable for testing soft starting or soft stopping
performance.
The minimum FLC of the test motor is 2% of the minimum
FLC of the soft starter (see chapter 4.5 Minimum andMaximum Current Settings).
NOTICE
When testing the soft starter with a small motor, set
parameter 1-1 Motor FLC to the minimum allowable
value.
Models which are internally bypassed do not require an
external bypass contactor.
Non-bypassed models have dedicated bypass terminals,
which allow the soft starter to continue providing
protection and monitoring functions even when bypassed
via an external contactor. Connect the bypass contactor to
the bypass terminals and control it by a programmable
output congured to Run (see parameters 4-1 to 4-9).
44
NOTICE
The bypass terminals on MCD5-0245C are:
T1B
•
T2B
•
T3B
•
The bypass terminals on MCD5-0360C to MCD5-1600C
are:
L1B
•
L2B
K1Main contactor (optional)
F1Semiconductor fuses (optional)
•
L3B
•
If necessary, the fuses can be installed on the input side.
When connecting the MCD 500 in inside delta congu-ration, always install a main contactor or shunt trip
circuit breaker.
NOTICE
When connecting in inside delta, enter the motor full
load current (FLC) for parameter 1-1 Motor FLC. The MCD
500 automatically calculates inside delta currents based
on this data. Parameter 15-7 Motor Connection is set to
Auto detect as default and can be set to force the soft
starter in inside delta or in-line.
Non-bypassed models have dedicated bypass terminals,
which allow the soft starter to continue providing
protection and monitoring functions even when bypassed
via an external bypass contactor. Connect the bypass
contactor to the bypass terminals and control the
contactor by a programmable output congured to Run
(see parameters 4-1 to 4-9).
44
NOTICE
The bypass terminals on MCD5-0245C are:
T1B
•
T2B
•
T3B
•
The bypass terminals on MCD5-0360C to MCD5-1600C
are:
L1B
•
L2B
•
L3B
•
If necessary, the fuses can be installed on the input side.
Some MCD 500 soft starters are internally bypassed and do
not require an external bypass contactor.
HRC fuses (such as Ferraz AJT fuses) can be used for Type
1 coordination according to the IEC 60947-4-2 standard.
CAUTION
Non-bypassed soft starters may be installed with an
external bypass contactor. Select a contactor with an AC1
rating greater than or equal to the full load current rating
of the connected motor.
44
4.7 Main Contactor
A main contactor must be installed if the MCD 500 is
connected to the motor in inside delta format and is
optional for in-line connection. Select a contactor with an
AC3 rating greater than or equal to the full load current
rating of the connected motor.
4.8 Circuit Breaker
A shunt trip circuit breaker may be used instead of a main
contactor to isolate the motor circuit in the event of a soft
starter trip. The shunt trip mechanism must be powered
from the supply side of the circuit breaker or from a
separate control supply.
Power Factor Correction
4.9
Adaptive control controls the speed prole of the motor
within the programmed time limit. This control may
result in a higher level of current than traditional control
methods.
For applications using adaptive control to soft stop the
motor with stop times greater than 30 s, select motor
branch protection as follows:
Standard HRC mains fuses: Minimum 150% motor
•
full load current.
Motor rated mains fuses: Minimum rating
•
100/150% motor full load current.
Motor control circuit breaker minimum long time
•
setting: 150% motor full load current.
Motor control circuit breaker minimum short time
•
setting: 400% motor full load current for 30 s.
Fuse recommendations are calculated for 40 °C, up to 1000
m.
CAUTION
EQUIPMENT DAMAGE
Connect power factor correction capacitors to the input
side of the soft starter. Connecting power factor
correction capacitors to the output side damages the
soft starter.
If power factor correction is used, use a dedicated
contactor to switch in the capacitors.
Fuses
4.10
4.10.1 Power Supply Fuses
Semiconductor fuses can be used for Type 2 coordination
(according to the IEC 60947-4-2 standard). They reduce the
risk of damage to SCRs from transient overload currents.
NOTICE
Fuse selection is based on a 400% FLC start for 20 s
with:
Standard published starts per hour.
•
Duty cycle.
•
40 °C ambient temperature.
•
Up to 1000 m altitude.
•
For installations operating outside these conditions,
consult a local Danfoss supplier.
Table 4.7 to Table 4.12 contain recommendations only.
Always consult a local supplier to conrm the selection
for a particular application.