When reading this manual, pay special attention to the
following symbols:
NOTICE
Useful hints for the reader.
CAUTION
Indicates a general warning.
WARNING
Indicates a high-voltage warning.
The examples and diagrams in this manual are included
solely for illustrative purposes. The information contained
in this manual is subject to change at any time and
without prior notice. Responsibility or liability is under no
circumstances accepted for direct, indirect, or
consequential damages resulting from the use or
application of this equipment.
NOTICE
Before changing any parameter settings, save the current
parameter to a le using MCD PC Software or the SaveUser Set function.
WARNING
WARNING - ELECTRICAL SHOCK HAZARD
VLT® Soft Starters MCD 500 contain dangerous voltages
when connected to mains voltage. Only a competent
electrician should carry out the electrical installation.
Improper installation of the motor or the soft starter can
cause equipment failure, serious injury, or death. Follow
the guidelines in this manual and local electrical safety
codes.
Models MCD5-0360C ~ MCD5-1600C:
Treat the bus bar and heat sink as live whenever the unit
has mains voltage connected (including when the soft
starter is tripped or waiting for a command).
WARNING
Disconnect the soft starter from mains voltage before
carrying out repair work.
It is the responsibility of the person installing the soft
starter to provide proper grounding and branch circuit
protection according to local electrical safety codes.
Do not connect power factor correction capacitors to the
output of MCD 500 soft starters. If static power factor
correction is employed, it must be connected to the
supply side of the soft starter.
MCD5-0021B ~ MCD5-961B:
After transportation, mechanical shock, or rough
handling there is a risk that the bypass contactor has
latched into the On state. To prevent the motor from
starting immediately, on rst commissioning, or
operation after transportation, always ensure that the
control supply is applied before the power. Applying
control supply before power ensures that the contactor
state is initialised.
WARNING
SAFETY OF PERSONNEL
The soft starter is not a safety device and does not
provide electrical isolation or disconnection from the
supply.
If isolation is required, the soft starter must be
•
installed with a main contactor.
The start and stop functions of the soft starter
•
must not be relied upon for personnel safety.
Faults occurring in the mains supply, the motor
connection, or the electronics of the soft starter,
can cause unintended motor starts or stops.
To provide machine or personnel safety, control the
isolation device through an external safety system.
In Auto On mode, the motor can be controlled remotely
(via remote inputs) while the soft starter is connected to
mains.
CAUTION
These stop functions are not sucient to avoid
unintended start.
If faults occur in the electronics of the soft starter, a
motor that has been stopped may start. A temporary
fault in the supply mains or a cease in the motor
connection can also cause a stopped motor to start.
The VLT® Soft Starter MCD 500 is an advanced digital soft
start solution for motors 11–850 kW. The soft starters
provide a complete range of motor and system protection
features, and are designed for reliable performance in the
most demanding installation situations.
The MCD 500 always responds to a local start or stop
command (via the [Hand On] and [O] keys on the LCP).
Pressing the [Auto On] key selects remote control (the soft
starter accepts commands from the remote inputs). In
remote mode, the Auto On LED is on. In local mode, the
Hand On LED is on if the soft starter starts or runs. The O
LED is on if the soft starter is stopped or stops.
4.1.2 Control Terminals
Control terminations use 2.5 mm2 plug-in terminal blocks.
Dierent models require control voltage to dierent
terminals:
NOTICE
SELV oers protection by way of extra low voltage.
Protection against electric shock is ensured when the
electrical supply itself is of the SELV type and the installation follows local/national regulations on SELV supplies.
44
NOTICE
Galvanic (ensured) isolation is obtained by fullling
requirements for higher isolation and by providing the
relevant creepages/clearance distances. These
requirements are described in the IEC 61140 standard.
The components that make up the electrical isolation
also comply with the requirements for higher isolation
and the relevant test as described in IEC 61140.
4.1.3 Remote Inputs
The soft starter has 3 xed inputs for remote control.
Control these inputs by contacts rated for low voltage, low
current operation (gold ash or similar).
CV1 (24 V AC/V DC): A5, A6.
•
CV2 (110–120 V AC): A5, A6.
•
CV2 (220–240 V AC): A4, A6.
•
12-wire control
23-wire control
34-wire control
Illustration 4.2 2-, 3-, and 4-wire Control
Illustration 4.1 Wiring to Control Terminals
The reset input can be normally open or normally closed.
To select the conguration, use parameter 3-8 Remote ResetLogic.
NOTICE
Do not short terminals 05 and 06 without using a
thermistor.
All control terminals and relay terminals comply with SELV
(Safety Extra Low Voltage). This protection does not apply
to grounded delta leg above 400 V.
To maintain SELV, all connections made to the control
terminals must be PELV (for example thermistor must be
reinforced/double insulated from motor).
Do not apply voltage to the control input terminals.
These terminals are active 24 V DC inputs and must be
controlled with potential-free contacts.
Segregate cables to the control inputs from mains
voltage and motor cabling.
Electrical Installation
VLT® Soft Starter MCD 500
4.1.4 Serial Communication
Control via the serial communication network is always
enabled in local control mode and can be enabled or
disabled in remote control mode (see parameter 3-2Comms in Remote). Control via the serial communication
network requires an optional communication module.
44
4.1.5 Ground Terminal
Ground terminals are located at the back of the soft
starter.
MCD5-0021B to MCD5-0105B have 1 terminal on
•
the input side (top).
MCD5-0131B to MCD5-0961B and MCD5-0245C to
•
MCD5-1600C have 2 terminals, 1 on the input
side (top), and 1 on the output side (bottom).
For personnel safety, snap-o tabs protect the power terminals on models up to MCD5-0105B. When using large cables,
it may be necessary to break o these tabs.
NOTICE
Some units use aluminium busbars. When connecting power terminations, clean the surface contact area thoroughly
(using an emery or stainless steel brush), and use an appropriate jointing compound to prevent corrosion.
Use only copper stranded or solid conductors, rated for 75 °C or higher.
44
Cable size: 6–50 mm2 (AWG 10-1/0)
14 mm (0.55 inch)
Torx T20 x 150
Torque: 4 Nm (2.9 ft-lb)
Flat 7 mm x 150
MCD5-0021B to MCD5-0105B
38 Nm (28 ft-lb)
MCD5-0131BMCD5-0141B to MCD5-0215BMCD5-0245B
38 Nm (28 ft-lb)38 Nm (28 ft-lb)
MCD5-0331B to MCD5-0396BMCD5-0469B to MCD5-0961BMCD5-0245C
MCD5-0360C to MCD5-0927CMCD5-1200C to MCD5-1600C
Table 4.1 Measurements and Torques for Power Terminations
4.2.1 Internally Bypassed Models (MCD5-0021B to MCD5-0961B)
Models MCD5-0021B to MCD5-0215B have power inputs at the top of the unit and outputs at the bottom of the unit.
Internally bypassed models MCD5-0245B to MCD5-0396B have output busbars at the bottom of the unit and input busbars
at both the top and bottom. The AC supply can be connected top-in, bottom-out or bottom-in, bottom-out.
44
Internally bypassed models MCD5-0469B to MCD5-0961B have input and output busbars at the top and bottom of the unit.
The AC supply can be connected:
Top-in/bottom-out.
•
Top-in/top-out.
•
Bottom-in/bottom-out.
•
Bottom-in/top-out.
•
Illustration 4.3 Internally Bypassed Models, MCD5-0021B to MCD5-0105B, MCD5-0131B to MCD5-0215B, MCD5-0245B to MCD5-0396B,
MCD5-0245C has dedicated bypass terminals at the bottom
of the unit. The bypass terminals are:
T1B
•
T2B
•
T3B
•
Illustration 4.4 Bypass Terminals on MCD5-0245C
4.2.3 MCD5-0360C to MCD5-1600C
44
Illustration 4.5 Location of Bypass Terminals, MCD5-0360C to
MCD5-1600C
4.3 Motor Connection
MCD 500 soft starters can be connected to the motor inline or inside delta (also called 3-wire and 6-wire
connection). When connecting in inside delta, enter the
motor full load current (FLC) for parameter 1-1 Motor FullLoad Current. The MCD 500 automatically calculates inside
delta current based on this data. Parameter 15-7 MotorConnection is set to Auto Detect as default and can be set
to force the soft starter in inside delta or in-line.
MCD5-0360C to MCD5-1600C have dedicated bypass
terminals on the input busbars. The bypass terminals are:
•
•
•
The busbars on non-bypassed models MCD5-0360C to
MCD5-1600C can be adjusted for top or bottom input and
output as required. See chapter 12 Busbar AdjustmentProcedure (MCD5-0360C to MCD5-1600C) for step-by-step
instructions. The soft starters are manufactured top-in/
bottom-out.
NOTICE
For models MCD5-0360C to MCD5-1600C to be ULcompliant, mount them top-in, bottom-out, or top-out,bottom-in. See chapter 11.1 UL Compliant Installation for
more information.
L1B
L2B
L3B
4.3.1 Testing the Installation
The MCD 500 can be connected to a small motor for
testing. During this test, the control input and relay output
protection settings can be tested. This test mode is not
suitable for testing soft starting or soft stopping
performance.
The minimum FLC of the test motor is 2% of the minimum
FLC of the soft starter (see chapter 4.5 Minimum andMaximum Current Settings).
NOTICE
When testing the soft starter with a small motor, set
parameter 1-1 Motor FLC to the minimum allowable
value.
Models which are internally bypassed do not require an
external bypass contactor.
Non-bypassed models have dedicated bypass terminals,
which allow the soft starter to continue providing
protection and monitoring functions even when bypassed
via an external contactor. Connect the bypass contactor to
the bypass terminals and control it by a programmable
output congured to Run (see parameters 4-1 to 4-9).
44
NOTICE
The bypass terminals on MCD5-0245C are:
T1B
•
T2B
•
T3B
•
The bypass terminals on MCD5-0360C to MCD5-1600C
are:
L1B
•
L2B
K1Main contactor (optional)
F1Semiconductor fuses (optional)
•
L3B
•
If necessary, the fuses can be installed on the input side.
When connecting the MCD 500 in inside delta congu-ration, always install a main contactor or shunt trip
circuit breaker.
NOTICE
When connecting in inside delta, enter the motor full
load current (FLC) for parameter 1-1 Motor FLC. The MCD
500 automatically calculates inside delta currents based
on this data. Parameter 15-7 Motor Connection is set to
Auto detect as default and can be set to force the soft
starter in inside delta or in-line.
Non-bypassed models have dedicated bypass terminals,
which allow the soft starter to continue providing
protection and monitoring functions even when bypassed
via an external bypass contactor. Connect the bypass
contactor to the bypass terminals and control the
contactor by a programmable output congured to Run
(see parameters 4-1 to 4-9).
44
NOTICE
The bypass terminals on MCD5-0245C are:
T1B
•
T2B
•
T3B
•
The bypass terminals on MCD5-0360C to MCD5-1600C
are:
L1B
•
L2B
•
L3B
•
If necessary, the fuses can be installed on the input side.
Some MCD 500 soft starters are internally bypassed and do
not require an external bypass contactor.
HRC fuses (such as Ferraz AJT fuses) can be used for Type
1 coordination according to the IEC 60947-4-2 standard.
CAUTION
Non-bypassed soft starters may be installed with an
external bypass contactor. Select a contactor with an AC1
rating greater than or equal to the full load current rating
of the connected motor.
44
4.7 Main Contactor
A main contactor must be installed if the MCD 500 is
connected to the motor in inside delta format and is
optional for in-line connection. Select a contactor with an
AC3 rating greater than or equal to the full load current
rating of the connected motor.
4.8 Circuit Breaker
A shunt trip circuit breaker may be used instead of a main
contactor to isolate the motor circuit in the event of a soft
starter trip. The shunt trip mechanism must be powered
from the supply side of the circuit breaker or from a
separate control supply.
Power Factor Correction
4.9
Adaptive control controls the speed prole of the motor
within the programmed time limit. This control may
result in a higher level of current than traditional control
methods.
For applications using adaptive control to soft stop the
motor with stop times greater than 30 s, select motor
branch protection as follows:
Standard HRC mains fuses: Minimum 150% motor
•
full load current.
Motor rated mains fuses: Minimum rating
•
100/150% motor full load current.
Motor control circuit breaker minimum long time
•
setting: 150% motor full load current.
Motor control circuit breaker minimum short time
•
setting: 400% motor full load current for 30 s.
Fuse recommendations are calculated for 40 °C, up to 1000
m.
CAUTION
EQUIPMENT DAMAGE
Connect power factor correction capacitors to the input
side of the soft starter. Connecting power factor
correction capacitors to the output side damages the
soft starter.
If power factor correction is used, use a dedicated
contactor to switch in the capacitors.
Fuses
4.10
4.10.1 Power Supply Fuses
Semiconductor fuses can be used for Type 2 coordination
(according to the IEC 60947-4-2 standard). They reduce the
risk of damage to SCRs from transient overload currents.
NOTICE
Fuse selection is based on a 400% FLC start for 20 s
with:
Standard published starts per hour.
•
Duty cycle.
•
40 °C ambient temperature.
•
Up to 1000 m altitude.
•
For installations operating outside these conditions,
consult a local Danfoss supplier.
Table 4.7 to Table 4.12 contain recommendations only.
Always consult a local supplier to conrm the selection
for a particular application.
4.10.4 UL Fuse Selection and Short Circuit Ratings
2 short circuit current ratings (SCCR) are available for UL-compliant applications.
Standard fault currents (@600 V AC circuits)
The standard fault currents are determined referring to UL 508, section 1, table 51.2. This standard species the short circuit
current that the soft starter must withstand based on the horse power rating (or full load current (FLC) rating, or locked
rotor amps (LRA) depending on the model).
If using the standard fault current ratings, the fuse must be in accordance with the information in Table 4.12 (that is modeland manufacturer-specic).
High available fault currents (@480 V AC circuits)
It is possible to specify short circuit current ratings exceeding the minimum ratings set by the standard fault currents when
the soft starter is capable of withstanding the high available short circuit current in accordance with the UL 508 test.
If using the high available fault current ratings, select a suitable fuse based on amperage and fuse class (J or L as
applicable).
The thermal model used for motor overload in the soft
starter has 2 components:
Motor windings: The motor windings have a low
•
thermal capacity and aect the short-term
thermal behaviour of the motor. The motor
windings are where the current generates heat.
Motor body: The motor body has a large thermal
•
capacity and aects the long-term behaviour of
the motor. The thermal model includes considerations for the following:
-Motor current.
-Iron losses.
-Winding resistance losses.
-Motor body and winding thermal
capacities.
-Cooling during run and cooling at
standstill.
-The percentage of the rated capacity of
the motor. This sets the displayed value
for the winding model and is
by the motor FLC setting among others.
aected
ically whether the motor has sucient thermal
capacity remaining to complete another start
successfully.
The memory function of the model means that
•
the motor is fully protected in warm-start
situations. The model uses data from the realtime clock to account for elapsed cooling time,
even if control power has been removed.
The overload protection function provided by this model is
compliant with a NEMA 10 curve, but provides superior
protection at low levels of overload due to the separation
of the winding thermal model.
55
NOTICE
Set parameter 1-1 Motor FLC to the rated motor FLC. Do
not add the overload rating as the soft starter calculates
this rating.
The thermal overload protection used in the soft starter
has a number of advantages over the thermal relays.
The eect of fan cooling is accounted for when
•
the motor is running.
The actual full load current and locked rotor time
•
can be used to more accurately tune the model.
The thermal characteristics of the windings are
treated separately from the rest of the motor
(that is the model recognises that the windings
have low thermal mass and high thermal
resistance).
The winding portion of the thermal model
•
responds rapidly compared with the body
portion. Thus, the motor can be run closer to its
safe maximum operating temperature while still
being protected from thermal damage.
The percentage of motor thermal capacity used
•
during each start is stored in memory. The soft
starter can be congured to determine automat-
Illustration 5.1 Protection Degree Compared to Overload
1.
MSTC1)=5
2.
MSTC1)=10
3.
MSTC1)=20
1) MSTC is the motor start time constant. It is
locked rotor time (in parameter 1-2 Locked Rotor Time) when
the locked rotor current is 600% of FLC.
Adaptive Control
5.2
Adaptive control is motor control based on the
performance characteristics of the motor. With adaptive
control, select the starting or stopping prole that best
matches the load type. The soft starter automatically
controls the motor to match the prole. The MCD 500
oers 3 proles:
Adaptive control uses 2 algorithms, 1 to measure the
motor characteristics, and 1 to control the motor. The soft
starter uses the rst start to determine the motor characteristics at zero speed and at maximum speed. During each
subsequent start and stop, the soft starter dynamically
adjusts its control to ensure that the actual motor
performance matches the selected prole throughout the
start. If the actual speed is too low for the prole, the soft
55
starter increases power to the motor. If the speed is too
high, the soft starter decreases power.
5.3 Starting Modes
5.3.1 Constant Current
Current ramp starting can be useful for applications where:
The load can vary between starts (for example a
•
conveyor which may start loaded or unloaded).
Set parameter 1-5 Initial Current to a level that
starts the motor with a light load. Set parameter1-4 Current Limit to a level that starts the motor
with a heavy load.
The load breaks away easily, but starting time
•
must be extended (for example a centrifugal
pump where pipeline pressure must build up
slowly).
The electricity supply is limited (for example a
•
generator set), and a slower application of load
allows greater time for the supply to respond.
Constant current is the traditional form of soft starting. It
raises the current from zero to a specied level and keeps
the current stable at that level until the motor has
accelerated.
Constant current starting is ideal for applications where the
start current must be kept below a particular level.
1 Parameter 1-5 Initial current
2 Parameter 1-6 Start ramp time
3 Parameter 1-4 Current limit
4 Full voltage current
Illustration 5.3 Example of a 10 s Current Ramp Time
5.3.3 Adaptive Control
1 Parameter 1-5 Initial current
2 Parameter 1-4 Current limit
3 Full voltage current
Illustration 5.2 Example of Constant Current
In an adaptive control soft start, the soft starter adjusts the
current to start the motor within a specied time and
using a selected acceleration prole.
CAUTION
Adaptive control cannot start the motor faster than a
5.3.2 Current Ramp
Current ramp soft starting raises the current from a
specied starting level (1) to a maximum limit (3), over an
extended period (2).
direct on-line (DOL) start. If the time set in parameter 1-6
Start ramp time is shorter than the motor DOL start time,
starting current may reach DOL levels.
Every application has a particular starting prole based on
characteristics of the load and the motor. To suit the
requirements of dierent applications, adaptive control
oers 3 dierent starting proles. Selecting a prole that
0
10%
20%
30%
40%
50%
Time
60%
70%
80%
90%
100%
4
177HA507.10
Speed
1
2
3
700%
600%
500%
300%
100%
400%
200%
10% 20% 30% 40% 50%
Rotor speed (% full speed)
60% 70% 80% 90% 100%
177HA508.10
Current (% motor full load current)
1
5
4
6
3
2
Product FeaturesOperating Instructions
matches the inherent prole of the application can help
smooth out acceleration across the full start time. Selecting
a very dierent adaptive control-prole can neutralise the
inherent prole to some extent.
To use adaptive control to control starting performance:
1.Select Adaptive control in parameter 1-3 StartMode.
2.Set parameter 1-6 Start Ramp Time.
3.Select the desired
prole in parameter 1-13
Adaptive Start Prole.
4.Set parameter 1-4 Current Limit suciently high to
allow a successful start.
The rst adaptive control start is a constant current start.
This start type allows the soft starter to learn the characteristics of the connected motor. The soft starter uses this
motor data during subsequent adaptive control starts.
5.3.4 Kick Start
Kick start provides a short boost of extra torque at the
beginning of a start, and can be used with current ramp or
constant current starting.
Kick start can be useful to help start loads that require
high breakaway torque but then accelerate easily (for
example ywheel loads such as presses).
Illustration 5.5 Example of Rotor Speed when using Kick Start
Stopping Modes
5.4
5.4.1 Coast to Stop
Coast to stop lets the motor slow at its natural rate, with
NOTICE
Adaptive control controls the load according to the
no control from the soft starter. The time required to stop
depends on the type of load.
programmed prole. Start current varies according to the
selected acceleration prole and the programmed start
5.4.2 TVR Soft Stop
time.
The soft starter has to learn the characteristics of a new
motor:
If replacing a motor connected to a soft starter
•
programmed for adaptive control starting or
stopping.
If the soft starter has been tested on a dierent
•
Timed voltage ramp reduces the voltage to the motor
gradually over a dened time. The load may continue to
run after the stop ramp is complete.
Timed voltage ramp stopping can be useful for
applications where the stop time has to be extended, or to
avoid transients on generator-set supplies.
motor before actual installation.
If parameter 1-1 Motor Full Load Current or parameter1-12 Adaptive Control Gain is changed, the soft starter
automatically re-learns the motor characteristics.
The rst adaptive control stop is a normal soft stop. This
stop type allows the soft starter to learn the characteristics
of the connected motor. The soft starter uses this motor
data during subsequent adaptive control stops.
NOTICE
Adaptive control controls the load according to the
programmed prole. Stopping current varies according
to the selected deceleration prole and stop time.
The soft starter has to learn the characteristics of a new
motor:
If replacing a motor connected to soft starter
55
1 Parameter 1-11 Stop Time
Illustration 5.6 TVR Soft Stop
•
programmed for adaptive control starting or
stopping.
if the soft starter has been tested on a dierent
•
motor before actual installation.
If parameter 1-1 Motor Full Load Current or parameter1-12 Adaptive Control Gain is changed, the soft starter
automatically re-learns the motor characteristics.
5.4.3 Adaptive Control
To use adaptive control to control stopping performance:
5.4.4 Pump Stopping
The hydraulic characteristics of pump systems vary considerably. This variation means the ideal deceleration prole
1.Select Adaptive control from the Stop Mode menu.
2.Set parameter 1-11 Stop Time.
3.Select the required
prole in parameter 1-14
and stop time vary from application to application.
Table 5.1 provides guidelines on selecting between
adaptive control-proles. For identication of the best
prole for the application, test all 3 proles.
Late decelerationHigh-head systems, where even a small
Constant
deceleration
Early decelerationOpen pump systems, where uid must drain
Table 5.1 Selection of Adaptive Control Deceleration Proles
5.4.5 Brake
Brake reduces the time the motor requires to stop.
Application
decrease in motor/pump speed results in a
rapid transition between forward ow and
reverse ow.
Low to medium head, high-ow applications
where the uid has high momentum.
back through the pump without driving the
pump in reverse.
During braking, an increased noise level from the motor
may be audible. This noise is a normal part of motor
NOTICE
braking.
Adaptive control does not actively slow the motor down
and does not stop the motor faster than a coast to stop.
To shorten the stopping time of high-inertia loads, use a
brake function, see chapter 5.4.5 Brake.
If the brake torque is set too high, the motor stops
before the end of the brake time. The motor suers
unnecessary heating which could result in damage.
Careful conguration is required to ensure safe operation
of the soft starter and the motor.
A high brake torque setting can result in peak currents
up to motor DOL being drawn while the motor is
stopping. Ensure that protection fuses installed in the
motor branch circuit are selected appropriately.
CAUTION
RISK OF OVERHEATING
Brake operation causes the motor to heat faster than the
rate calculated by the motor thermal model. If using
brake functionality, install a motor thermistor or allow
sucient restart delay (parameter 2-11 Restart Delay).
When brake is selected, the soft starter uses DC injection
to slow the motor.
MCD 500 braking
Does not require the use of a DC brake contactor.
•
Controls all 3 phases so that the braking currents
•
and associated heating are evenly distributed
through the motor.
Braking has 2 stages:
1.Pre-brake: Provides an intermediate level of
braking to slow motor speed to a point where
full brake can be operated successfully (approximately 70% speed).
2.Full brake: Provides maximum braking torque but
is ineective at speeds greater than approximately 70%.
To congure the MCD 500 for brake operation:
1.Set parameter 1-11 Stop Time for the desired
stopping time duration (1). The stop time is the
total braking time and must be set suciently
longer than the brake time (parameter 1-16 BrakeTime) to allow the pre-braking stage to reduce
motor speed to approximately 70%. If the stop
time is too short, braking is not successful and
the motor coasts to stop.
2.Set parameter 1-16 Brake Time to approximately
one quarter of the programmed stop time. The
brake time sets the time for the full brake-stage
(2).
3.Adjust parameter 1-15 Brake Torque so that the
desired stopping performance is achieved. If set
too low, the motor does not stop completely and
coasts to stop by the end of the braking period.
1 Parameter 1-11 Stop Time
2 Parameter 1-16 Brake Time
3 Coast to stop time
Illustration 5.8 Brake Time
CAUTION
When using DC brake:
1.Connect the mains supply to the soft starter
(input terminals L1, L2, L3) in positive phase
sequence.
2.Set parameter 2-1 Phase Sequence to Positive
only.
NOTICE
For loads which may vary between braking cycles, install
a zero-speed sensor to ensure that the soft starter ends
DC braking when the motor stops. This installation
avoids unnecessary heating of the motor.
For more information on using the MCD 500 with an
external speed sensor (for example for applications with
variable load during the braking cycle), see chapter 5.12 DCBrake with External Zero-speed Sensor.
Jog Operation
5.5
Jog runs the motor at reduced speed, to allow alignment
of the load or to assist servicing. The motor can be jogged
in either forward or reverse direction.
The maximum available torque for jog forward is approximately 50–75% of motor full load torque (FLT) depending
on the motor. The torque when the motor is jogged in
reverse is approximately 25–50% of FLT. Parameter 15-8 Jog
Torque controls how much of the maximum available jog
torque the soft starter applies to the motor.
NOTICE
Setting parameter 15-8 Jog Torque above 50% may cause
increased shaft vibration.
CAUTION
Slow speed running is not intended for continuous
operation due to reduced motor cooling. Jog operation
causes the motor to heat faster than the rate calculated
by the motor thermal model. If using jog, install a motor
thermistor, or allow sucient restart delay (parameter2-11 Restart Delay).
5.6 Inside Delta Operation
Adaptive control, jog, and brake functions are not
55
1 Jog forward
2 Jog reverse
3 Normal operation
supported in inside delta (6-wire) operation. If these
functions are programmed when the soft starter is
connected inside delta, the behaviour is as in Table 5.2:
Adaptive
control
start
Adaptive
control
stop
JogThe soft starter issues a warning with the error
BrakeThe starter performs a coast to stop.
Table 5.2 Inside Delta Behaviour at Adaptive Control, Jog,
and Brake
The soft starter performs a constant current start.
If stop time is >0 s, the starter performs a TVR soft
stop. If stop time is set to 9 s, the starter performs a
coast to stop.
message Unsupported Option.
NOTICE
Illustration 5.9 Jog Operation
To activate jog operation, use a programmable input
(parameter 3-3 Input A Function).
When connected in inside delta, current imbalance is the
only phase loss protection that is active during run. Do
not disable parameter 2-2 Current Imbalance during
inside delta operation.
To stop a jog operation, perform either of the following:
Remove the jog command.
•
[O] on the LCP.
Press
•
Activate Starter disable using the LCP
•
programmable inputs.
If the jog command is still present, jog recommences at
the end of a restart delay. All other commands except the
ones listed are ignored during jog operation.
NOTICE
Inside delta operation is only possible with mains
voltage ≤600 V AC.
NOTICE
Soft start and soft stop are not available during jog
operation. Jog is only available for the primary motor.
To determine the typical start current for an application,
use this information.
NOTICE
These start current requirements are appropriate and
typical in most circumstances, However, the performance
and start torque requirements of motors and machines
do vary. For further assistance, contact the local Danfoss
supplier.
General and water
Agitator4.0 FLC
Centrifugal pump3.5 x FLC
Compressor (Screw, unloaded)3.0 x FLC
Compressor (Reciprocating, unloaded)4.0 x FLC
Conveyor4.0 x FLC
Fan (damped)3.5 x FLC
Fan (undamped)4.5 x FLC
Mixer4.5 x FLC
Positive displacement pump4.0 x FLC
Submersible pump3.0 x FLC
Table 5.3 Typical Start Currents for General and Water
Applications
Pulp and paper
Dryer4.5 x FLC
Re-pulper4.5 x FLC
Shredder4.5 x FLC
Table 5.6 Typical Start Currents for Pulp and Paper Applications
Petrochemical
Ball mill4.5 x FLC
Centrifuge4.0 x FLC
Extruder5.0 x FLC
Screw conveyor4.0 x FLC
Table 5.7 Typical Start Currents for Petrochemical Applications
Transport and machine tool
Ball mill4.5 x FLC
Grinder3.5 x FLC
Material conveyor4.0 x FLC
Palletiser4.5 x FLC
Press3.5 x FLC
Roller mill4.5 x FLC
Rotary table4.0 x FLC
Table 5.8 Typical Start Currents for Transport and Machine
Tool Applications
55
Metals and mining
Belt conveyor4.5 x FLC
Dust collector3.5 x FLC
Grinder3.0 x FLC
Hammer mill4.5 x FLC
Rock crusher4.0 x FLC
Roller conveyor3.5 x FLC
Roller mill4.5 x FLC
Tumbler4.0 x FLC
Wire draw-machine5.0 x FLC
Table 5.4 Typical Start Currents for Metals and Mining
Applications
Food processing
Bottle washer3.0 x FLC
Centrifuge4.0 x FLC
Dryer4.5 x FLC
Mill4.5 x FLC
Palletiser4.5 x FLC
Separator4.5 x FLC
Slicer3.0 x FLC
Lumber and wood products
Bandsaw4.5 x FLC
Chipper4.5 x FLC
Circular saw3.5 x FLC
Debarker3.5 x FLC
Edger3.5 x FLC
Hydraulic power pack3.5 x FLC
Planer3.5 x FLC
Sander4.0 x FLC
Table 5.9 Typical Start Currents for Lumber and Wood
Products Applications
Table 5.5 Typical Start Currents for Food Processing
The MCD 500 is installed with a main contactor (AC3 rated). Supply control voltage from the input side of the contactor.
The soft starter main contactor output controls the main contactor. The main contactor output is by default assigned to
output relay A (terminals 13, 14).
55
1Control voltage (model dependent)K1Main contactor
The MCD 500 is installed with a bypass contactor (AC1 rated). The soft starter run-output controls the bypass contactor. The
run output is by default assigned to output relay B (terminals 21, 22, 24).
55
1Control voltage (model dependent)K1Bypass contactor
224 V DC outputF1Semiconductor fuses (optional)
3Remote control inputs S1Start contact
4Motor thermistor input (PTC only) S2Stop contact
5Relay outputsS3Reset contact
63-phase supply 13, 14Relay output A
7Motor terminals21, 22, 24Relay output B
33, 34Relay output C
Illustration 5.11 Installation with Bypass Contactor
Parameter settings:
•
Parameter 4-4 Relay B Function
-Select Run - assigns the run output function to output relay B (default value).
In normal operation, the MCD 500 is controlled via a remote 2-wire signal (terminals 17, 18).
A 2-wire circuit connected to input A (terminals 11, 16) controls emergency run. Closing input A causes the soft starter to
run the motor and ignore all trip conditions.
55
1Control voltage (model dependent)S1Start/stop contact
224 V DC outputS2Reset contact
3Remote control inputs S3Emergency run-contact
4Motor thermistor input (PTC only) 13, 14Relay output A
5Relay outputs21, 22, 24Relay output B
63-phase supply 33, 34Relay output C
7Motor terminals
Illustration 5.12 Emergency Run Operation
Parameter settings:
•
•
Parameter 3-3 Input A Function.
-Select Emergency Run - assigns input A to emergency run-function.
Although Emergency run satises the functionality requirements of Fire mode, Danfoss does not recommend its use in
situations that require testing and/or compliance with specic standards as it is not certied.
5.11 Auxiliary Trip Circuit
In normal operation, the MCD 500 is controlled via a remote 2-wire signal (terminals 17, 18).
Input A (terminals 11, 16) is connected to an external trip circuit (such as a low-pressure alarm switch for a pumping
system). When the external circuit activates, the soft starter trips and stops the motor.
55
1Control voltage (model dependent)S1Start/stop contact
224 V DC outputS2Reset contact
3Remote control inputs S3Auxiliary trip contact
4Motor thermistor input (PTC only) 13, 14Relay output A
-Select Input Trip (N/O) assigns input A to auxiliary trip (N/O)-function.
Parameter 3-4 Input A Name.
•
-Select a name, for example Low Pressure - assigns a name to input A.
Parameter 3-8 Remote Reset Logic.
•
-Select as required, for example Normally Closed - the input behaves like a normally closed contact.
5.12 DC Brake with External Zero-speed
Sensor
For loads varying between braking cycles, there are
55
benets in using an external zero-speed sensor to interface
with the MCD 500 for brake shut-o. This control method
ensures that the MCD 500 braking always shuts o when
the motor has reached a standstill, thus avoiding
unnecessary motor heating.
Illustration 5.14 shows how to use a zero-speed sensor with
the MCD 500 to turn o the brake function at motor
standstill. The zero-speed sensor (-A2) is often referred to
as an under-speed detector. Its internal contact is open at
zero-speed and closed at any speed above zero-speed.
Once the motor has reached a standstill, terminals 11 and
16 open, and the soft starter is disabled. When the next
start command is given, that is next application of K10,
terminals 11 and 16 close, and the soft starter is enabled.
1 Control voltage15,16Start
Operate the MCD 500 in remote mode and set parameter3-3 Input A Function to Starter disable.
2 Motor terminals17,18Stop
3 3-phase supply25,18Reset
4 Starter disable
AO (ready)
(shown on soft
starter display)
5 Start signal (2, 3, or
BStart
4-wire)
6 Zero-speed detectC Run
7 Zero-speed sensorD Stop
EZero speed
Illustration 5.14 Turning O Brake Function at Standstill with
Zero-speed Sensor
For details on conguring DC Brake, see chapter 5.4.5 Brake.
CAUTION
When using DC brake, connect the mains supply to the
soft starter (input terminals L1, L2, L3) in positive phase
sequence. Then set parameter 2-1 Phase Sequence to
Positive only.
For high inertia loads, the MCD 500 can be congured for soft braking.
In this application, the MCD 500 is employed with forward run and braking contactors. When the soft starter receives a start
signal (pushbutton S1), it closes the forward run contactor (K1) and controls the motor according to the programmed
primary motor settings.
When the soft starter receives a stop signal (pushbutton S2), it opens the forward run contactor (K1) and closes the braking
contactor (K2) after a delay of approximately 2–3 s (KT1). K12 is also closed to activate the secondary motor settings, which
are user-programmed for the desired stopping performance characteristics.
When motor speed approaches zero, the external zero-speed sensor (A2) stops the soft starter and opens the braking
contactor (K2).
1Control voltage (model dependent)K10Run relay
2Remote control inputs K11Start relay
3Motor thermistor input (PTC only) K12Brake relay
4Relay outputsK13Zero-speed detector relay
53-phase supply K1Line contactor (Run)
6Motor terminalsK2Line contactor (Brake)
A2Zero-speed sensorK1TRun delay timer
S1Start contactK2TBrake delay timer
S2Stop contactK3TZero-speed detector delay timer
S3Reset contact
55
Illustration 5.15 Soft Braking Conguration
Parameter settings:
•
Parameter 3-3 Input A Function
-Select Motor Set Select - assigns input A for motor set selection.
-Set starting performance characteristics using the primary motor set (parameter group 1 Primary Motor
-Set braking performance characteristics using the secondary motor settings (parameter group 7 Secondary
Parameter 4-7 Relay C Function.
•
-Select Trip - assigns trip function to output relay C.
Motor Set).
VLT® Soft Starter MCD 500
NOTICE
If the soft starter trips on supply frequency (parameter 16-5 Frequency) when the braking contactor K2 opens, modify
the setting of parameters 2-8 to 2-10.
5.14 Two-speed Motor
55
The MCD 500 can be congured for control of dual speed Dahlander type motors, using a high-speed contactor (K1), lowspeed contactor (K2), and a star contactor (K3).
NOTICE
Pole amplitude modulated (PAM) motors alter the speed by eectively changing the stator frequency using external
winding conguration. Soft starters are not suitable for use with this type of 2-speed motor.
When the soft starter receives a high-speed start signal, it closes the high-speed contactor (K1) and star contactor (K3). Then
it controls the motor according to the primary motor settings (parameters 1-1 to 1-16).
When the soft starter receives a low-speed start signal, it closes the low-speed contactor (K2). This action closes input A and
the soft starter controls the motor according to the secondary motor settings (parameters 7-1 to 7-16).
NOTICE
If the soft starter trips on supply frequency (16-5 Frequency) when the high-speed start signal (7) is removed, modify the
setting of parameters 2-8 to 2-10.
Contactors K2 and K3 must be mechanically interlocked.
Parameter settings:
Parameter 3-3 Input A Function.
•
•
NOTICE
If the soft starter trips on supply frequency (parameter 16-5 Frequency) when the high-speed signal (7) is removed,
modify the settings of parameters 2-9 to 2-10.
-Select Motor Set Select - assigns input A for motor set selection.
-Set high-speed performance characteristics using parameters 1-1 to 2-9.
-Set low-speed performance characteristics using parameters 7-1 to 7-16.
Parameter 4-4 Relay B Function.
-Select Trip - assigns trip function to relay output B.
Control via the serial communication network is always disabled in Hand On mode. Enable/disable start/stop
•
commands via the serial network in Auto On mode by changing the setting of 3-2 Comms in Remote.
VLT® Soft Starter MCD 500
The MCD 500 can also be
In Hand On mode, the soft starter ignores any auto-start/stop setting. To congure auto-start/stop operation, set parameters5-1 to 5-4.
To switch between Hand On and Auto On modes, press the keys on the LCP.
[Hand On]: Start the motor and enter Hand On mode.
•
[O]: Stop the motor and enter Hand On mode.
•
[Auto On]: Set the soft starter to Auto On mode.
•
[Reset]: Reset a trip (Hand On mode only).
•
The MCD 500 can also be set to allow local control only or remote control only, using parameter 3-1 Local/Remote.
If parameter 3-1 Local/Remote is set to Remote Control Only, the [O] key is disabled. Stop the motor by remote control or via
the serial communication network.
Hand On modeAuto On mode
To soft start the motor.Press [Hand On] on the LCP.Activate the Start remote input.
To stop the motor.Press [O] on the LCP.Activate the Stop remote input.
To reset a trip on the soft starter.Press [Reset] on the LCP.Activate the Reset remote input.
Auto start/stop operation.Disabled.Enabled.
Table 6.1 Start, Stop, and Reset in Hand On Mode and Auto On Mode
congured to auto-start or auto-stop. Auto-start/stop operation is only available in Auto On mode.
To stop the motor with a coast to stop, regardless of the setting in parameter 1-10 Stop Mode, press [O] and [Reset] at the
same time. The soft starter removes power from the motor and opens the main contactor, and the motor coasts to stop.
NOTICE
Brake and jog functions operate only with in-line connected motors (see chapter 5.6 Inside Delta Operation).
To reset a trip on the soft starter, press [Reset] on
•
the LCP
To stop the motor with a coast to stop, regardless
•
of the setting of parameter 1-10 Stop mode, press
[O] and [Reset] at the same time. The soft
starter removes power from the motor and opens
the main contactor, and then the motor coasts to
stop.
In Auto On mode:
To soft start the motor, activate the Start remote
•
input.
To stop the motor, activate the Stop remote input.
•
To reset a trip on the soft starter, activate the
•
Reset remote input.
NOTICE
Brake and jog functions operate only with in-line
connected motors (see chapter 4.3.3 Inside Delta Instal-lation).
6.2.2 The LCP
14-line display for status and programming details.
2 Display control keys:
[Status]: Returns to the status displays
[Quick Menu]: Opens the Quick Menu
[Main Menu]: Opens the Main Menu
[Alarm Log]: Opens the Alarm Log
3 Menu navigation keys:
[Back]: Exits the menu or parameter, or cancel a
parameter change
[OK]: Enters a menu or parameter, or save a parameter
change
[▲]/[▼]:
Scroll to the next or previous menu or parameter.
•
Change the setting of the current parameter.
•
Scroll through the status screens.
•
4 Soft starter local control keys:
[Hand On]: Starts the motor and enter local control
mode.
[O]: Stops the motor (only active in Hand On mode).
A remote-mounted LCP can be installed with the MCD 500.
The control panel LCP 501 can be mounted up to 3 m
away from the soft starter, for control and monitoring.
The soft starter can be controlled and programmed from
either the remote LCP or the LCP on the soft starter. Both
displays show the same information.
The remote LCP also allows parameter settings to be
copied between soft starters.
6.3.1 Synchronising the LCP and the Soft
Starter
The DB9 cable can be connected/disconnected from the
LCP while the soft starter runs.
The
rst time an LCP is plugged into a soft starter, the soft
starter copies its parameter settings to the LCP.
New display detected
NOTICE
The LCP can be removed or replaced while the soft
starter runs. It is not necessary to remove mains or
control voltage.
6.4 Welcome Screen
When control power is applied, the soft starter displays the
welcome screen
ReadyS1
Welcome
1.05/2.0/1.13
MCD5-0053-T5-G1-CV2
Third display line: Software versions for remote LCP, control software,
model software.
Fourth display line: Product model number.
NOTICE
The LCP version is only displayed if a remote LCP 501 is
connected when control power is applied. If no remote
LCP is present, only the control software and model
software versions are displayed.
6.5 Local Control Keys
If the LCP has previously been used with an MCD 500,
select whether to copy the parameters from the LCP to the
soft starter, or from the soft starter to the LCP.
To select the required option:
1.
Press the [▲] and [▼] keys.
A dotted line surrounds the selected option.
2.Press [OK] to proceed with the Copy Parameters
selection.
2aDisplay to Starter.
2bStarter to Display.
Copy parameters
Display to starter
Starter to display
NOTICE
If the parameter software version in the LCP is dierent
from the software version of the soft starter, only Starter
to Display is available.
NOTICE
While the LCP synchronises, only the [▲], [▼], [OK], and
[O] keys are enabled.
If parameter 3-1 Local/Remote is set to LCL/RMT Anytime or
LCL/RMT When OFF, the [Hand On] and [Auto On] keys are
always active. If the soft starter is in Auto On mode,
pressing [Hand On] enters Hand On mode and starts the
motor.
If parameter 3-1 Local/Remote is set to Remote Control Only,
the [O] key is disabled. Stop the motor by remote control
or via the serial communication network.
Displays
6.6
The LCP displays a wide range of performance information
about the soft starter. Press [Status] to access the status
display screens, then press [▲] and [▼] to select the
information to display. To return to the status screens from
within a menu, press [Back] repeatedly, or press [Status].
Available status information:
The temperature screen shows the temperature of the
motor as a percentage of total thermal capacity. It also
shows which motor data set is in use.
The temperature monitoring screen is the default status
screen.
ReadyS1
MS1000.0A000.0kW
Primary Motor Set
M1 000%
6.6.2 Programmable Screen (S2)
The user-programmable screen of the soft starter can be
congured to show the most important information for the
particular application. Use parameters 8-2 to 8-5 to select
which information to display.
ReadyS2
MS1000.0A000.0kW
-.-- pf
00000 hrs
6.6.3 Average Current (S3)
The average current screen shows the average current of
all 3 phases.
ReadyS3
MS1000.0A000.0kW
0.0A
6.6.5 Frequency Monitoring Screen (S5)
The frequency screen shows the mains frequency as
measured by the soft starter.
ReadyS5
MS1000.0A000.0kW
00.0Hz
6.6.6 Motor Power Screen (S6)
The motor power screen shows motor power (kW, hp, and
kVA) and power factor.
ReadyS6
MS1000.0A000.0kW
000.0kW0000HP
0000kVA-. - - pf
6.6.7 Last Start Information (S7)
The last start information screen shows details of the most
recent successful start:
Start duration, (s).
•
Maximum start current drawn (as a percentage of
•
motor full load current).
Calculated rise in motor temperature.
•
ReadyS7
MS1000.0A000.0kW
Last start000 s
000% FLC
ΔTemp 0%
6.6.8 Date and Time (S8)
The date/time screen shows the current system date and
time (24-hour format). For details on setting the date and
time, see chapter 9.1 Set Date and Time.
6
6
6.6.4 Current Monitoring Screen (S4)
ReadyS8
The current screen shows real-time line current on each
phase.
The SCR conduction bargraph shows the level of
conduction on each phase.
Illustration 6.2 Bargraph
6
6.6.10 Performance Graphs
The MCD 500 can display real-time performance
information for:
Current.
•
Motor temperature.
•
Motor kW.
•
Motor kVA.
•
Motor power factor.
•
The newest information is displayed at the right-hand edge
of the screen. Older data is not stored. To allow past
performance to be analysed, the graph can also be paused.
To pause or unpause the graph, press and hold [OK] for
more than 0.5 s.
NOTICE
The soft starter does not collect data while the graph is
paused. When graphing resumes, a small gap is shown
between the old data and the new data.
It is possible to access the programming menus at any
time, including while the soft starter is running. All
changes take eect immediately.
7.1 Access Control
A 4-digit security access code protects critical parameters
(parameter group 15 Restricted Parameters and higher),
preventing unauthorised users from viewing or modifying
parameter settings.
If attempts are made to enter a restricted parameter group,
the LCP prompts for an access code. The access code is
requested once for the programming session, and authorisation continues until closing the menu.
To enter the access code:
1.Press [Back] and [OK] to select a digit.
2.
Press [▲] and [▼] to change the value.
3.When all 4 digits match the access code, press
[OK].
The LCP displays an acknowledgement message before
continuing.
Enter Access Code
####
OK
Access Allowed
SUPERVISOR
To change the access code, use parameter 15-1 Access Code.
NOTICE
The security access code also protects the protection
simulation and output simulation. The counters and
thermal model reset can be viewed without entering an
access code, but an access code must be entered to
reset.
The default access code is 0000.
To prevent users from altering parameter settings, lock the
menus. The adjustment lock can be set to allow Read &Write, Read Only, or No Access in 15-2 Adjustment Lock.
If a user attempts to change a parameter value or access
the Main Menu when the adjustment lock is active, an
error message is displayed:
Access Denied
Adj Lock is On
7.2 Quick Menu
[Quick Menu] provides access to the menus for setting up
the soft starter for simple applications.
7.2.1 Quick Set-up
Quick set-up provides access to commonly used
parameters, allowing to congure the soft starter as
required for the application. For details of individual
parameters, see chapter 8 Parameter Descriptions.
The application set-ups menu makes it easy to congure
77
the soft starter for common applications. The soft starter
selects the parameters relevant to the application and
suggests a typical setting. Each parameter can be adjusted
Fan damped
Motor Full Load Current
Start ModeConstant Current
Current Limit350%
Table 7.4 Suggested Values for Damped Fan Applications
Fan undamped
Motor Full Load Current
Start ModeAdaptive Control
Adaptive Start ProleConstant Acceleration
Start Ramp Time20 s
Excess Start Time 30 s
Locked Rotor Time20 s
Table 7.5 Suggested Values for Undamped Fan Applications
Compressor screw
Motor Full Load Current
to suit the exact requirements.
Start ModeConstant Current
On the display, the highlighted values are suggested
values. The values indicated by a ▶ are the loaded values.
Start Ramp Time5 s
Current Limit400%
Always set 1-1 Motor FLC to match the motor nameplate
full load current. The suggested value for motor FLC is the
minimum FLC of the soft starter.
Pump centrifugal
Motor Full Load Current
Start modeAdaptive control
Adaptive start proleEarly acceleration
Start ramp time10 s
Stop modeAdaptive control
Adaptive stop proleLate deceleration
Stop time 15 s
Table 7.2 Suggested Values for Centrifugal Pump Applications
Pump submersible
Motor Full Load Current
Start ModeAdaptive Control
Adaptive Start ProleEarly Acceleration
Start Ramp Time5 s
Stop ModeAdaptive Control
Adaptive Stop ProleLate Deceleration
Stop Time5 s
Table 7.3 Suggested Values for Submersible Pump Applications
Table 7.6 Suggested Values for Compressor Screw Applications
Compressor recip
Motor Full Load Current
Start ModeConstant Current
Start Ramp Time10 s
Current Limit450%
Table 7.7 Suggested Values for Compressor Recip Applications
Conveyor
Motor Full Load Current
Start ModeConstant Current
Start Ramp Time5 s
Current Limit400%
Stop ModeAdaptive Control
Adaptive Stop ProleConstant Deceleration
Stop Time10 s
Table 7.8 Suggested Values for Conveyor Applications
Crusher rotary
Motor Full Load Current
Start ModeConstant Current
Start Ramp Time10 s
Current Limit400%
Excess Start Time30 s
Locked Rotor Time20 s
Table 7.9 Suggested Values for Crusher Rotary Applications
Table 7.10 Suggested Values for Crusher Jaw Applications
7.2.3 Loggings
To view performance information in real-time graphs, enter
the Loggings menu.
Current (%FLC).
•
Motor Temp (%).
•
Motor kW (%).
•
Motor kVA (%).
•
Motor pf.
•
The newest information is displayed at the right-hand edge
of the screen. The graph can be paused to analyse data by
pressing and holding the [OK] key. To restart the graph,
press and hold [OK].
7.3.1 Parameters
Parameters allow viewing and changing all programmable
parameters that control how the soft starter operates.
To open Parameters, press [Main Menu] then select
Parameters.
Navigating through parameters
To scroll through parameter groups, press [▲] or
•
[▼].
To view the parameters in a group, press [OK].
•
To return to the previous level, press [Back].
•
To close Parameters, press the [Back].
•
Changing a parameter value
Scroll to the appropriate parameter and press
•
[OK] to enter edit mode.
To alter the parameter setting, press [▲] and [▼].
•
To save changes, press [OK]. The setting shown
•
on the display is saved and the LCP returns to the
parameter list.
To cancel changes, press [Back]. The LCP returns
•
to the parameter list without saving changes.
77
Main Menu
7.3
[Main Menu] provides access to menus for setting up the
soft starter for advanced applications and for monitoring
performance.
7.3.2 Parameter Shortcut
The MCD 500 also includes a parameter shortcut, which
gives direct access to a parameter within the Parameters
menu.
The parameters in Primary Motors Settingscongure the
soft starter to match the connected motor. These
parameters describe the operating characteristics of the
motor and allow the soft starter to model the motor
temperature.
NOTICE
Parameter 1-2 Locked Rotor Time determines the trip
current for motor overload protection. Its default setting
provides motor overload protection:
Class 10.
•
Trip current 105% of FLA, or equivalent.
•
1-1 Motor FLC
Option:Function:
Model
dependent
Matches the soft starter to the connected
motor full load current. Set to the full load
current (FLC) rating shown on the motor
nameplate.
NOTICE
The setting for this parameter sets the
basis for calculation of all current-based
protection settings.
1-2 Locked Rotor Time
Range:Function:
10 s* [0:01–2:00
(min:s)]
1-3 Start Mode
Option:Function:
Constant Current*
Adaptive Control
1-4 Current Limit
Range:Function:
350%* [100–
600%
FLC]
Sets the maximum length of the time the
motor can sustain locked rotor current from
cold before reaching its maximum
temperature. Set according to the motor
datasheet.
Selects the soft start mode. See
chapter 5.3 Starting Modes for more details.
Sets the current limit for constant current and
current ramp soft starting as a percentage of
motor full load current. See
chapter 5.3 Starting Modes for more details.
1-5 Initial Current
Range:Function:
350%* [100–
600%
FLC]
1-6 Start Ramp Time
Range:Function:
10 s* [1–180s]Sets the total start time for an adaptive control
1-7 Kick Start Level
Range:Function:
500%* [100%–
700% FLC]
Sets the initial start current level for current
ramp starting, as a percentage of motor full
load current. Set so that the motor begins to
accelerate immediately after a start is initiated.
If current ramp starting is not required, set the
initial current equal to the current limit. See
chapter 5.3 Starting Modes for more details.
start or the ramp time for current ramp starting
(from the initial current to the current limit). See
chapter 5.3 Starting Modes for more details.
Sets the level of the kick start current.
CAUTION
Kick start subjects the mechanical
equipment to increased torque
levels. Ensure the motor, load, and
couplings can handle the additional
torque before using this feature.
1-8 Kick Start Time
Range:Function:
0000
ms*
[0–
2000 ms]
Sets the kick start duration. A setting of 0
disables kick start. See chapter 5.3 Starting
Modes for more details.
CAUTION
Kick start subjects the mechanical
equipment to increased torque levels.
Ensure the motor, load and couplings
can handle the additional torque
before using this feature.
Brake uses DC injection to slow the motor actively. See
chapter 5.4 Stopping Modes for more details.
1-15 Brake Torque
1-11 Stop Time
Range:Function:
0s* [0:00–
88
4:00
(min:s)]
Sets the time for soft stopping the motor using
timed voltage ramp or adaptive control. If a main
contactor is installed, the contactor must remain
closed until the end of the stop time. To control
the main contactor, use a programmable output
congured to Run. Sets the total stopping time
when using brake. See chapter 5.4 Stopping
Modes for more details.
1-12 Adaptive Control Gain
Range:Function:
75%* [1–200%] Adjusts the performance of adaptive control.
This setting aects both starting and stopping
control.
NOTICE
Leave the gain setting at the default
level unless adaptive control
performance is not satisfactory. If the
motor accelerates or decelerates too
quickly at the end of a start or stop,
increase the gain setting by 5–10%. If
the motor speed uctuates during
starting or stopping, decrease the gain
setting slightly.
1-13 Adaptive Start Prole
Range:Function:
20%* [20–100%] Sets the amount of brake torque the soft
starter uses to slow the motor.
1-16 Brake Time
Range:Function:
1 s* [1–
Sets the duration for DC injection during a braking
30 s]
stop.
NOTICE
This parameter is used with parameter 1-11
Stop Time. See
chapter 8.1.1 Brakechapter 5.4 Stopping Modes
for details.
8.2 Protection
2-1 Phase Sequence
Option:Function:
Selects which phase sequences the soft starter
allows at a start. During its pre-start checks, the
soft starter examines the sequence of the
phases at its input terminals. If the actual
sequence does not match the selected option,
the soft starter trips.
Any sequence*
Positive only
Negative only
Option:Function:
Selects which prole the soft starter uses
for an adaptive control soft start. See
chapter 5.4 Stopping Modes for more
details.
Early Acceleration
Constant
Acceleration*
Late Acceleration
8.2.1 Current Imbalance
If the currents on the 3 phases vary from each other by
more than a specied amount, the soft starter can be
congured to trip. The imbalance is calculated as the
dierence between the highest and lowest currents on all
3 phases, as a percentage of the highest current.
Current imbalance detection is desensitised by 50% during
starting and soft stopping.
0 s* [0:00–4:00 (min:s)] Sets delay between the input
activating and soft starter tripping.
3-7 Input A Initial Delay
Range:Function:
0 s* [00:00–
30:00 (min:s)]
Sets a delay before an input trip can occur.
The initial delay is counted from the time a
start signal is received. The state of the input
is ignored until the initial delay has elapsed.
3-8 Remote Reset Logic
Option:Function:
Selects whether the remote reset input of
the soft starter (terminals 25, 18) is normally
open or normally closed.
Normally Closed*
Normally Open
8.4 Outputs
4-1 Relay A Function
Option:Function:
Selects the function of Relay A (normally
open).
ORelay A is not used
Main
Contactor*
RunThe relay closes when the starter changes to
TripThe relay closes when the starter trips.
WarningThe relay closes when the starter issues a
Low Current
Flag
High Current
Flag
Motor Temp
Flag
The relay closes when the soft starter receives
a start command, and remains closed as long
as the motor receives voltage.
run state.
warning.
The relay closes when the low current ag
activates (parameter 4-10 Low Current Flag).
The relay closes when the high current ag
activates (parameter 4-11 High Current Flag).
The relay closes when the motor temperature
ag activates (parameter 4-12 Motor
Temperature Flag).
8.4.1 Relay A Delays
The soft starter can be congured to wait before opening
or closing relay A.
4-2 Relay A On Delay
Range:Function:
0 s* [0:00–5:00 (min:s)]Sets the delay for closing relay A.
4-3 Relay A O Delay
Range:Function:
0 s* [0:00–5:00 (min:s)] Sets the delay for reopening relay A.
8.4.2 Relays B and C
Parameters 4-4 to 4-9congure the operation of relays B
and C in the same way as parameters 4-1 to 4-3congure
relay A. See chapter 8.4.2 4-2 Relay A On Delay and
chapter 8.4.2 4-3 Relay A O Delay for details.
Relay B is a change-over relay.
•
Relay C is normally open.
•
4-4 Relay B Function
Option:Function:
Selects the function of relay B (change-over).
ORelay B is not used
Main
Contactor
Run*
TripThe relay closes when the soft starter trips.
WarningThe relay closes when the soft starter issues a
Low Current
Flag
High Current
Flag
Motor Temp
Flag
4-5 Relay B On Delay
Range:Function:
0 s* [0:00–5:00 (min:s)]Sets the delay for closing relay B.
4-6 Relay B O Delay
Range:Function:
0 s* [0:00–5:00 (min:s)] Sets the delay for reopening relay B.
4-7 Relay C Function
Option:Function:
ORelay C is not used
Main
Contactor
RunThe relay closes when the soft starter changes
Trip*
WarningThe relay closes when the soft starter issues a
0 s* [0:00–5:00 (min:s)]Sets the delay for closing relay C.
4-9 Relay C O Delay
Range:Function:
0 s* [0:00–5:00 (min:s)] Sets the delay for reopening relay C.
8.4.3 Low Current Flag and High Current
Flag
The soft starter has low and high current ags to give early
warning of abnormal operation. The current ags can be
congured to indicate an abnormal current level during
88
operation, between the normal operating level and the
undercurrent or instantaneous overcurrent trip levels. The
ags can signal the situation to external equipment via 1
of the programmable outputs. The ags clear when the
current returns within the normal operating range by 10%
of the programmed ag value.
4-10 Low Current Flag
Range:Function:
50%* [1–100%
FLC]
Sets the level at which the low current
ag operates, as a percentage of motor
full load current.
4-11 High Current Flag
Range:Function:
100%* [50–600%
FLC]
Sets the level at which the high current
ag operates, as a percentage of motor
full load current.
The soft starter has an analog output, which can be
connected to associated equipment to monitor motor
performance.
4-13 Analog Output A
Option:Function:
Selects which information is reported via analog
output A.
Current (%
FLC)*
Motor
Temp (%)
Motor kW
(%)
Motor kVA
(%)
Motor pfMotor power factor, measured by the soft starter.
Current as a percentage of motor full load current.
Motor temperature as a percentage of the thermal
capacity of the motor.
Measured motor kilowatts, as a percentage of
maximum kW.
Measured motor kilovolt amperes, as a percentage
of maximum kVA.
Measure motor kW: √3 x average current
•
x mains reference voltage x measure
power factor.
Maximum motor kW: √3 x motor FLC x
•
mains reference voltage. Power factor is
assumed to be 1.
Measure motor kVA: √3 x average current
•
x main reference voltage.
Maximum motor kVA: √3 x motor FLC x
•
mains reference voltage.
4-14 Analog A Scale
Option:Function:
Selects the range of the output.
0–20 mA
4–20 mA*
4-15 Analog A Maximum Adjustment
Range:Function:
8.4.4 Motor Temperature Flag
The soft starter has a motor temperature ag to give early
warning of abnormal operation. The ag can indicate that
the motor is operating above its normal operating
temperature, but lower than the overload limit. The ag
can signal the situation to external equipment via 1 of the
programmable outputs.
4-12 Motor Temperature Flag
Range:Function:
80%* [0–160%] Sets the level at which the motor temperature
ag operates, as a percentage of the motor
thermal capacity.
100%* [0–600%] Calibrates the upper limit of the analog
output to match the signal measured on an
external current measuring device.
4-16 Analog A Minimum Adjustment
Range:Function:
0%* [0–600%] Calibrates the lower limit of the analog output
to match the signal measured on an external
current measuring device.
8.5 Start/Stop Timers
CAUTION
UNINTENDED START
The auto-start timer overrides any other form of control.
The motor may start without warning.
Selects whether the soft starter auto-starts after a
specied delay, or at a time of day.
The soft starter does not auto-start.
O*
Timer The soft starter does auto-start after a delay from the
next stop, as specied in parameter 5-2 Auto-start Time.
Clock The soft starter auto-starts at the time programmed in
parameter 5-2 Auto-start Time.
5-2 Auto-Start Time
Range:Function:
1 min* [00:01–24:00
(hrs:min)]
Sets the time for the soft starter to
auto-start, in 24-hour clock format.
5-3 Auto-Stop Type
Option: Function:
Selects whether the soft starter auto-stops after a
specied delay, or at a time of day.
The soft starter does not auto-stop.
O*
Time The soft starter auto-stops after a delay from the next
start, as specied in parameter 5-4 Auto-stop Time.
Clock The soft starter auto-stops at the time programmed in
parameter 5-4 Auto-stop Time.
5-4 Auto-Stop Time
Range:Function:
1 min* [00:01–
24:00
(hrs:min)]
Sets the time for the soft starter to auto-
stop, in 24-hour clock format.
WARNING
Do not use this function with remote
2-wire control. The soft starter still
accepts start and stop commands
from the remote inputs or serial
communication network. To disable
local or remote control, use
parameter 3-1 Local/Remote. If autostart is enabled and the user is in the
menu system, auto-start becomes
active if the menu times out (if no
LCP activity is detected for 5
minutes).
8.6 Auto-Reset
The soft starter can be programmed to reset certain trips
automatically, which can help minimise operating
downtime. Trips are divided into 3 categories for autoreset, depending on the risk to the soft starter:
Group
Current imbalance
Phase loss
A
Power loss
Frequency
Undercurrent
B
Instantaneous overcurrent
Input A trip
Motor overload
C
Motor thermistor
Heat overtemperature
Table 8.1 Trip Categories for Auto-reset
Other trips cannot be automatically reset.
This function is ideal for remote installations using 2-wire
control in Auto On mode. If the 2-wire start signal is
present after an auto-reset, the soft starter restarts.
6-1 Auto-Reset Action
Option:Function:
Selects which trips can be auto-reset.
Do not Auto-Reset*
Reset Group A
Reset Group A & B
Reset Group A, B & C
6-2 Maximum Resets
Range:Function:
1* [1–5] Sets how many times the soft starter auto-resets, if it
continues to trip. The reset counter increases by 1
each time the soft starter auto-resets, and decreases
by 1 after each successful start/stop cycle.
NOTICE
If the starter is manually reset, the reset counter returns
to 0.
8.6.1 Auto-Reset Delay
The soft starter can be congured to wait before autoresetting a trip. Separate delays can be set for trips in
Groups A and B, or in Group C.
6-3 Reset Delay Groups A & B
Range:Function:
5 s* [00:05–15:00 (min:s)] Sets the delay before setting Group
A and Group B trips.
6-4 Reset Delay Group C
Range:Function:
5 min* [5–60 (minutes)] Sets the delay before resetting Group
[Motor dependent] Sets the secondary motor full load
current.
7-2 Locked Rotor Time-2
Range:Function:
10 s* [0:01–2:00
(min:s)]
Sets the maximum length of the time the
motor can run at locked rotor current from
cold before reaching its maximum
temperature. Set according to the motor
datasheet.
If this information is not available, set the
value to <20 s.
7-3 Start Mode-2
Option:Function:
Selects the soft start mode.
Constant Current*
Adaptive Control
88
7-4 Current Limit-2
Range:Function:
350%* [100–600%
FLC]
Sets the current limit for constant current
and current ramp soft starting, as a
percentage of motor full load current.
7-5 Initial Current-2
Range:Function:
350%* [100–
600%
FLC]
Sets the initial start current level for current
ramp starting, as a percentage of motor full
load current. Set so that the motor begins to
accelerate immediately after a start is initiated.
If current ramp starting is not required, set the
initial current equal to the current limit.
7-6 Start Ramp Time-2
Range:Function:
10 s* [1–180 s] Sets the total start time for an adaptive control
start or the ramp time for current ramp
starting (from the initial current to the current
limit). ).
7-7 Kick Start Level-2
Range:Function:
500%* [100–700% FLC] Sets the level of the kick start current.
7-9 Excess Start Time-2
Range:Function:
programmed limit, the soft starter trips. Set for
a period slightly longer than required for a
normal healthy start. A setting of 0 disables
excess start time protection.
20 s* [0:00–
4:00
(min:s)]
Set as required.
7-10 Stop Mode-2
Option:Function:
Selects the stop mode.
Coast to Stop*
TVR Soft Stop
Adaptive Control
Brake
7-11 Stop Time-2
Range:Function:
0 s* [0:00–4:00 (min:s) ]Sets the stop time.
7-12 Adaptive Control Gain-2
Range:Function:
75%* [1–200%] Adjusts the performance of adaptive control.
The setting aects both starting and stopping
control
NOTICE
Leave the gain setting at the default
level unless adaptive control
performance is not satisfactory.
If the motor accelerates or decelerates
quickly at the end of a start or stop,
increase the gain by setting by 5–10%.
If the motor speed uctuates during
starting or stopping, decrease the gain
setting slightly.
7-13 Adaptive Start Prole-2
Option:Function:
Selects which prole the soft starter
uses for an adaptive control soft start.
Early Acceleration
Constant Acceleration*
Late Acceleration
7-8 Kick Start Time-2
Range:Function:
0000 ms* [0–2000 ms] Sets the kick start duration. A setting of
Starter StateThe operating state of the soft starter (starting,
Motor CurrentThe average current measured on 3 phases.
Motor pfThe motor power factor, measured by the soft
Mains
Frequency
Motor kWThe motor running power in kilowatts.
Motor hpThe motor running power in horse power.
Motor TempThe motor temperature, calculated by the
kWhThe number of kilowatt hours the motor has
88
Hours RunThe number of hours the motor has run via
Displays no data in the selected area, allowing
long messages to be shown without
overlapping.
running, stopping, or tripped). Only available
for Top L and Btm L.
starter.
The average frequency measured on 3 phases.
thermal model.
run via the soft starter.
the soft starter.
8-9 Mains Reference Voltage
Range:Function:
400 V* [100–
690 V]
Sets the nominal voltage for the monitoring
functions of the LCP. The nominal voltage is
used to calculate motor kilowatts and kilovolt
amperes (kVA), but does not aect the motor
control protection of the soft starter.
Enter the measured mains voltage.
8.9 Restricted Parameters
15-1 Access Code
Range:Function:
0000* [0000–
9999]
Sets the access code to enter the simulation
tools and counter resets or the restricted
section of the programming menu (parameter
group 15 Restricted Parameters and higher).
Press [Back] and [OK] to select which digit to
alter, and use [▲] and [▼] to change the value.
NOTICE
If the access code is lost, contact the
local Danfoss supplier for master access
code that allows to reprogramme a new
access code.
8.8.2 Performance Graphs
The loggings menu allows to view performance
information in real-time graphs.
The newest information is displayed at the right-hand edge
of the screen. The graph can be paused to analyse data by
pressing and holding [OK]. To restart the graph, press and
hold [OK].
8-6 Graph Timebase
Option:Function:
Sets the graph time scale. The graph progressively
replaces the old data with new data.
10 s*
30 s
1 min
5 minutes
10 minutes
30 minutes
1 hour
8-7 Graph Maximum Adjustment
Range:Function:
400%* [0–600%] Adjusts the upper limit of the performance
graph
15-2 Adjustment Lock
Option:Function:
Selects whether the LCP allows parameters to be
changed via the programming menu.
Read &
Write*
Read Only Prevents users altering parameter values in the
No Access Prevents users adjusting parameters in the
Allows users to alter parameter values in the
programming menu.
programming menu. Parameter values can still be
viewed.
programming menu unless an access code is
entered.
NOTICE
Changes to the adjustment lock setting take
eect only after the programming menu has
been closed.
8-8 Graph Minimum Adjustment
Range:Function:
0%* [0–600%] Adjusts the lower limit of the performance
Continued use of emergency run is not
recommended. Emergency run may compromise
the soft starter life as all protections and trips
are disabled.
Using the soft starter in Emergency run-mode
voids the product warranty.
Selects whether the soft starter permits emergency run
operation. In Emergency run, the soft starter starts (if
not already running) and continues to operate until
emergency run ends, ignoring stop commands and
trips.
Emergency run is controlled using a programmable
input.
When emergency run is activated in internally bypassed
models which are not running, the soft starter attempts
a normal start while ignoring all trips. If a normal start
is not possible, a DOL start via the internal bypass
contactors is attempted. For non-bypassed models, an
external emergency run bypass contactor may be used.
15-4 Current Calibration
Range:Function:
100%* [85%
-
115%]
15-5 Main Contactor Time
Range:Function:
400
ms*
15-6 Bypass Contactor Time
Range:Function:
150
ms*
Motor Current Calibration calibrates the soft
starter's current monitoring circuits to match an
external current metering device.
Use the following formula to determine the
necessary adjustment:
Calibration( % ) =
e . g . 102 % =
66A
65A
NOTICE
This adjustment aects all current-based
functions.
[100–
2000 ms]
[100–
2000 ms]
Sets the delay period between the soft
starter switching the main contactor output
(terminals 13, 14) and beginning the pre-
start checks (before start) or entering the not
ready state (after a stop). Set according to
the specications of the main contactor used.
Sets the soft starter to match the bypass
contactor closing/opening time. Set
according to the specications of the
bypass contactor used. If the time is too
short, the soft starter trips.
CurrentshownonMCD500display
Currentmeasuredbyexternaldevice
15-7 Motor Connection
Option:Function:
Selects the soft starter automatically detects the
format of the connection to the motor.
Auto-Detect*
In-line
Inside Delta
15-8 Jog Torque
Range:Function:
50%* [20–100%]
NOTICE
Setting this parameter above 50% may
cause increased shaft vibration.
Sets the torque level for jog operation. See
chapter 5.5 Jog Operation for more details.
8.10 Protection Action
16-1 to 16-13 Protection Action
Option:Function:
Selects the soft starter response to each
protection.
16-1 Motor Overload.
•
16-2 Current Imbalance.
•
16-3 Undercurrent.
•
16-4 Inst Overcurrent.
•
16-5 Frequency.
•
16-6 Heat sink Overtemp.
•
16-7 Excess Start Time.
•
16-8 Input A Trip.
•
16-9 Motor Thermistor.
•
16-10 Starter/Comms.
•
16-11 Network/Comms.
•
16-12 Battery/Clock.
•
16-13 Low Control Volts.
•
Trip Starter*
Warn and
Log
Log Only
8.11 Factory Parameters
These parameters are restricted for factory use and are not
available to the user.
The security access code also protects simulation tools
and counter resets. The default access code is 0000.
9.1 Set Date and Time
To set the date and time:
1.Open the Tools Menu.
2.Scroll to Set Date & Time.
3.Press [OK] to enter edit mode.
4.Press [OK] to select which part of the date or
time to edit.
Tools
Load Defaults
Load User Set 1
Save User Set 1
Table 9.1 Tools Menu
Load Defaults
No
Yes
Table 9.2 Load Defaults Menu
When the action has been completed, the screen briey
displays a conrmation message, then returns to the status
screens.
9.3 Reset Thermal Model
NOTICE
The security access code protects the reset thermal
model.
99
5.
Use [▲] and [▼] to change the value.
To save changes, press [OK] repeatedly. The soft starter
conrms the changes. To cancel changes, press [Back]
repeatedly.
Load/Save Settings
9.2
The MCD 500 includes options to:
The advanced thermal modelling software in the soft
starter constantly monitors the motor performance. This
monitoring allows the soft starter to calculate the motor
temperature and ability to start successfully at any time.
If necessary, reset the thermal model.
Load defaults: Load the soft starter parameters
•
with default values.
Load User Set 1: Reload previously saved
•
parameter settings from an internal le.
Save User Set 1: Save the current parameter
•
settings to an internal le.
In addition to the factory default values le, the soft starter
can store a user-dened parameter le. This le contains
default values until a user le is saved.
To load or save parameter settings:
1.Open the Tools Menu.
2.
Use [▼] to select the required function, then press
[OK].
3.At the conrmation prompt, select Yes to conrm
or No to cancel. Then press [OK] to load/save the
selection or exit the screen.
CAUTION
Resetting the motor thermal model may compromise
motor life and should only be done in the case of
emergency.
1.Open Tools.
2.Scroll to Reset Thermal Model and press [OK].
3.At the conrmation prompt, press [OK] to conrm
then enter the access code, or press [Back] to
cancel the action.
4.Select Reset or Do Not Reset, then press [OK].
When the thermal model has been reset, the soft
starter returns to the previous screen.
The security access code protects protection simulation.
To test the operation and control circuits of the soft starter
without connecting it to mains voltage, use the software
simulation functions.
To conrm that the soft starter responds correctly and
reports the situation on the display and across the
communication network, it is able to simulate each
dierent protection.
To use the protection simulation:
1.Open the Main Menu.
2.Scroll to Protection Sim and press [OK].
3.
To select the protection to simulate, press [▲] and
[▼].
4.To simulate the selected protection, press [OK].
5.The screen is displayed while [OK] is pressed. The
soft starter response depends on the protection
action setting (parameter group 16 ProtectionActions).
6.To return to the simulation list, press [Back].
7.
To select another simulation, press [▲] or [▼], or
press [Back] to return to the Main Menu.
9.5 Output Signal Simulation
NOTICE
The security access code protects the output signal
simulation.
The LCP allows simulation of output signalling to conrm
that the output relays are operating correctly.
NOTICE
To test operation of the ags (motor temperature and
low/high current), set an output relay to the appropriate
function and monitor the relay behaviour.
To use the output signal simulation:
1.Open the Main Menu.
2.Scroll to Output Signal Sim and press [OK], then
enter the access code.
3.
To select a simulation, press [▲] and [▼], then
press [OK].
4.
To turn the signal on and o, press [▲] and [▼].
To conrm correct operation, monitor the state of
the output.
5.To return to the simulation list, press [Back].
Prog Relay A
O
On
Table 9.6 Output Signal Simulation Menu
Digital I/O State
9.6
99
MS1000.0A0000.0kW
Tripped
Selected Protection
Table 9.5 Protection Simulation Menu
NOTICE
If the protection trips the soft starter, reset before
simulating another protection. If the protection action is
set to Warn or Log, no reset is required.
If the protection is set to Warn & Log, the warning
message can be viewed only while [OK] is pressed.
If the protection is set to Log only, nothing appears on
the screen but an entry appears in the log.
This screen shows the status of the Digital I/O in order.
The top line of the screen shows:
Start.
•
Stop.
•
Reset.
•
Programmable input.
•
The bottom line of the screen shows programmable
outputs A, B, and C.
Digital I/O State
Inputs: 0100
Outputs: 100
Table 9.7 Digital I/O Status Screen
Tools
VLT® Soft Starter MCD 500
9.7 Temp Sensors State
This screen shows the state of the motor thermistor.
The screen shot shows the thermistor state as O (open).
Temp Sensors State
Thermistor: O
S = shrt H=hot C=cld O=opn
Table 9.8 Motor Thermistor Status Screen
9.8 Alarm Log
The [Alarm Log] key opens the alarm logs, which contain:
Trip log.
•
Event log.
•
Counters which store information on the soft
•
starter operating history.
9.8.3 Counters
NOTICE
The security access code protects the counters function.
The performance counters store statistics on the soft
starter operation:
Hours run (lifetime and since counter last reset).
•
Number of starts (lifetime and since counter last
•
reset).
Motor kWh (lifetime and since counter last reset).
•
Number of times the thermal model has been
•
reset.
The resettable counters (hours run, starts, and motor kWh)
can only be reset if the correct access code is entered.
To view the counters:
9.8.1 Trip Log
1.Press [Alarm Log].
The trip log stores details of the 8 most recent trips,
99
including the date and time the trip happened. Trip 1 is
the most recent and trip 8 is the oldest stored trip.
To open the trip log
1.Press [Alarm Log].
2.Scroll to Trip Log and press [OK].
3.
To select a trip to view, press [▲] and [▼], then
press [OK] to display details.
To close the log and return to the main display, press
[Back].
2.Scroll to Counters and press [OK].
3.
To scroll through the counters, press [▲] and [▼].
Press [OK] to view details.
4.To reset a counter, press [OK] then enter the
access code. Select Reset, then press [OK] to
conrm.
To close the counter and return to the alarm logs, press
[Back].
9.8.2 Event Log
The event log stores time-stamped details of the 99 most
recent events (actions, warnings, and trips), including the
date and time of the event. Event 1 is the most recent and
event 99 is the oldest stored event.
To open the event log:
1.Press [Alarm Log].
2.Scroll to Event Log and press [OK].
3.
To select an event to view, press [▲] and [▼], then
press [OK] to display details.
To close the log and return to the main display, press
[Back].
When a protection condition is detected, the MCD 500
writes this condition to the event log, and may also trip, or
issue a warning. The soft starter response depends on the
protection action settings (parameter group 16 ProtectionActions).
Some protections responses cannot be adjusted. Usually,
external events (for example phase loss) or a fault within
the soft starter cause these trips. These trips do not have
associated parameters and cannot be set to Warn or Log.
If the soft starter trips:
1.Identify and clear the condition that triggered the
trip.
2.Reset the soft starter.
3.Restart the soft starter.
To reset the soft starter, press [Reset] or activate the Resetremote input.
If the soft starter has issued a warning, it resets itself once
the cause of the warning has been resolved.
10.1 Trip Messages
Table 10.1 lists the protection mechanisms in the soft starter and the probable cause of the trip. Some of these protection
mechanisms can be adjusted using parameter group 2 Protection and parameter group 16 Protection Action. Other settings
are built-in system protections and cannot be set or adjusted.
DisplayPossible cause/Suggested solution
Awaiting dataThe LCP does not receive data from the control PCB. Check the cable connection and the tting of
the display on the soft starter.
Battery/clockA verication error has occurred on the real-time clock, or the back-up battery voltage is low. If
the battery is low and the power is o, date/time settings are lost. Reprogramme the date and
time.
Related parameter:
Parameter 16-12 Battery Clock.
•
ControllerThis is a name selected for a programmable input. Refer to Input A trip.
Current imbalance Problems with the motor, the environment, or the installation can cause current imbalance, such
as:
An imbalance in the incoming mains voltage.
•
A problem with the motor windings.
•
A light load on the motor.
•
A phase loss on mains terminals L1, L2, or L3 during run mode.
•
An SCR that has failed open circuit. A failed SCR can only be denitely diagnosed by replacing the
SCR and checking the soft starter performance.
Related parameters:
Parameter 2-2 Current Imbalance.
•
Parameter 2-3 Current Imbalance Delay.
•
Parameter 16-2 Current Imbalance.
•
Current read err lxWhere X is 1, 2, or 3.
Internal fault (PCB fault). The output from the current transformer circuit is not close enough to
zero when the SCRs are turned o. Contact the local Danfoss supplier for advice.
Heat sink overtemp Check that cooling fans are operating. If mounted in an enclosure, check if ventilation is adequate.
Fans operate during start, run, and for 10 minutes after the soft starter exits the stop state.
NOTICE
Models MCD5-0021B ~ MCD4-0053B and MCD5-0141B do not have a cooling fan.
Models with fans operate the cooling fans from a start until 10 minutes after a stop.
Related parameters:
Parameter 16-6 Heat sink Overtemp.
•
High levelThis is a name selected for a programmable input. Refer to Input A trip.
High pressureThis is a name selected for a programmable input. Refer to Input A trip.
Input A trip The programmable input is set to a trip function and has activated. Resolve the trigger condition.
Related parameters:
Parameter 3-3 Input A Function.
•
Parameter 3-4 Input A Name.
•
Parameter 3-5 Input A Trip.
•
Parameter 3-6 Input A Trip Delay.
•
Parameter 3-7 Input A Initial Delay.
•
Parameter 16-8 Input A Trip.
•
Instantaneous overcurrent There has been a sharp rise in motor current, probably caused by a locked rotor condition (shear
pin) while running. Check for a jammed load.
Related parameters:
Parameter 2-6 Instantaneous Overcurrent.
•
Parameter 2-7 Instantaneous Overcurrent Delay.
•
Parameter 16-4 Inst Overcurrent.
•
Internal fault XThe soft starter has tripped on an internal fault. Contact the local Danfoss supplier with the fault
code (X).
Related parameters: None.
L1 phase loss
L2 phase loss
L3 phase loss
L1-T1 shorted
L2-T2 shorted
L3-T3 shorted
Low control voltsThe soft starter has detected a drop in the control voltage.
Low levelThis is a name selected for a programmable input. Refer to Input A trip.
Low pressureThis is a name selected for a programmable input. Refer to Input A trip.
During prestart, check that the soft starter has detected a phase loss as indicated.
In run state, the soft starter has detected that the current on the aected phase has dropped
below 3.3% of the programmed motor FLC for more than 1 s. This current drop indicates that
either the incoming phase or connection to the motor has been lost.
Check the supply and the input, and output connections at the soft starter, and at the motor end.
A failed SCR can also cause phase loss, particularly an SCR that has failed open circuit. A failed SCR
can only be denitely diagnosed by replacing the SCR and checking the soft starter performance.
Related parameters: None.
During prestart checks, the soft starter has detected a shorted SCR or a short within the bypass
contactor as indicated.
Related parameters: None.
Check the external control supply (terminals A4, A5, A6) and reset the soft starter.
•
If the external control supply is stable:
Check if the 24 V supply on the main control PCB is faulty; or
•
If the bypass driver PCB is faulty (internally bypassed models only).
If the start current is too low, the motor does not produce enough torque to
•
accelerate to full speed. The soft starter may trip on excess start time.
NOTICE
Make sure that the motor starting parameters are appropriate for the
application and that the intended motor starting prole is used. If
parameter 3-3 Input A Function is set to Motor Set Select, check that the
corresponding input is in the expected state.
Check if the load is jammed. Check the load for severe overloading or a locked
•
rotor situation.
Erratic motor operation.
Erratic and noisy motor operation.If the soft starter is connected to the motor using inside delta conguration, the soft
Soft stop ends too quickly.
Adaptive control, DC brake, and jog functions not
working.
A reset does not occur after an auto-reset, when
using a remote 2-wire control.
Remote start/stop command overrides Auto Start/
Stop settings when using remote 2-wire control.
After selecting adaptive control, the motor used an
ordinary start and/or the second start was dierent
to the rst.
Non-resettable THERMISTOR CCT trip, when there is
a link between thermistor input 05, 06 or when the
motor thermistor connected between 05, 06 is
permanently removed.
Parameter settings cannot be stored.
The LCP shows message Awaiting data.The LCP does not receive data from the control PCB. Check the cable connection.
The SCRs in the soft starter require at least 5 A of current to latch. If testing the
•
soft starter on a motor with full load current less than 5 A, the SCRs may not
latch correctly.
starter may not be correctly detecting the connection. Contact the local Danfoss
supplier for advice.
The soft stop settings may not be appropriate for the motor and load. Review the
•
settings of
-Parameter 1-10 Stop Mode.
-Parameter 1-11 Stop Time.
-Parameter 7-10 Stop Mode-2.
-Parameter 7-11 Stop Time-2.
If the motor is lightly loaded, soft stop has limited eect.
•
These features are only available with in-line installation. If the soft starter is
•
installed inside delta, these features do not operate.
Remove and reapply the remote 2-wire start signal for a restart.
•
Only use Auto Start/Stop in Auto On mode with 3-wire or 4-wire control.
•
The rst adaptive control start is current limit so that the soft starter can learn
•
from the motor characteristics. Subsequent starts use adaptive control.
The thermistor input is enabled once a link is tted and short-circuit protection
•
has activated.
Remove the link then load the default parameter set. This disables the thermistor
input and clears the trip.
Place a 1k2 Ω resistor across the thermistor input.
Turn thermistor protection to Log only (parameter 16-9 Motor Thermistor).
Make sure to save the new value by pressing [OK] after adjusting a parameter
•
setting. If pressing [BACK], the change is not saved.
Check that the adjustment lock (parameter 15-2 Adjustment Lock) is set to Read/
•
Write. If the adjustment lock is on, settings can be viewed, but not changed.
Knowing the security access code is necessary to change the adjustment lock
setting.
The EEPROM may be faulty on the main control PCB. A faulty EEPROM also trips
•
the soft starter, and the LCP displays the message Par. Out of Range. Contact the
Supply
Mains voltage (L1, L2, L3)
MCD5-xxxx-T5200–525 V AC (±10%)
MCD5-xxxx-T7380–690 V AC (±10%) (in-line connection)
MCD5-xxxx-T7380–600 V AC (±10%) (inside delta connection)
Control voltage (A4, A5, A6)
CV1 (A5, A6)24 V AC/V DC (±20%)
CV2 (A5, A6)110–120 V AC (+10%/-15%)
CV2 (A4, A6)220–240 V AC (+10%/-15%)
Current consumption (maximum)
CV12.8 A
CV2 (110–120 V AC)1 A
CV2 (220–240 V AC)500 mA
Mains frequency45–66 Hz
Rated insulation voltage to ground600 V AC
Rated impulse withstand voltage4 kV
Form designationBypassed or continuous, semiconductor motor starter form 1
Short circuit capability (IEC)
Coordination with semiconductor fuses Type 2
Coordination with HRC fuses Type 1
MCD5-0021B to MCD5-0215Bprospective current 65 kA
MCD5-0245B to MCD5-0961Bprospective current 85 kA
MCD5-0245C to MCD5-0927Bprospective current 85 kA
MCD5-1200C to MCD5-1600Cprospective current 100 kA
For UL short circuit current ratings, see Table 4.12.
1111
Electromagnetic capability (compliant with EU Directive 89/336/EEC)
EMC emissions IEC 60947-4-2 Class B and Lloyds Marine No 1 Specication
EMC immunityIEC 60947-4-2
Inputs
Input ratingActive 24 V DC, 8 mA approximately
Start (15, 16) Normally open
Stop (17, 18) Normally closed
Reset (25, 18)Normally closed
Programmable input (11, 16) Normally open
Motor thermistor (05, 06) Trip >3.6 kΩ, reset <1.6kΩ
Outputs
Relay outputs10 A @ 250 V AC resistive, 5A @ 250 V AC AC15 pf 0.3
Programmable outputs
Relay A (13, 14) Normally open
Relay B (21, 22, 24) Change-over
Relay C (33, 34) Normally open
Analog output (07, 08) 0–20 mA or 4–20 mA (selectable)
Maximum load600 Ω (12 V DC @ 20 mA)
Accuracy±5%
24 V DC output (16, 08) maximum load 200 mA
Accuracy±10%
Environmental
Protection
MCD5-0021B to MCD5-0105BIP20 & NEMA, UL Indoor Type 1
MCD5-0131B to MCD5-1600CIP00, UL Indoor Open Type
Operating temperature-10 °C to +60 °C, above 40 °C with derating
Storage temperature-25 °C to +60 °C
Operating altitude (using MCD PC software) 0–1000 m, above 1000 m with derating
Humidity5–95% relative humidity
Pollution degreePollution degree 3
VibrationIEC 60068-2-6
Heat Dissipation
During start4.5 W per ampere
During run
MCD5-0021B to MCD5-0053B≤39 W approximately
MCD5-0068B to MCD5-0105B≤51 W approximately
MCD5-0131B to MCD5-0215B≤120 W approximately
MCD5-0245B to MCD5-0469B≤140 W approximately
MCD5-0525B to MCD5-0961B≤357 W approximately
MCD5-0245C to MCD5-0927C4.5 W per ampere approximately
MCD5-1200C to MCD5-1600C4.5 W per ampere approximately
Certication
C✓IEC 60947-4-2
UL 508
UL/C-UL
MCD5-0021B to MCD5-0396B, MCD5-0245C to MCD5-1600C
MCD5-0469B to MCD5-0961B
MCD5-0021B to MCD5-105B
MCD5-0131B to MCD5-1600C
CEIEC 60947-4-2
CCCGB 14048-6
Marine
(MCD5-0021B to MCD5-0961B)Lloyds Marine No 1 Specication
RoHS Compliant with EU Directive 2002/95/EC
1) For UL certication extra requirements may apply, depending on the models. For details, see chapter 11.1 UL Compliant Installation.
This section details more requirements and conguration
settings for the VLT® Soft Starter MCD 500 to be ULcompliant. See also Table 4.12.
11.1.1 Models MCD5-0021B to
MCD5-0105B
There are no additional requirements for these models.
11.1.2 Models MCD5-0131B to
MCD5-0215B
Use with nger guard kit, ordering number
•
175G5662.
Use the recommended pressure terminal/
•
connector kit. See Table 11.1 for more
information.
11.1.3 Models MCD5-0245B to
MCD5-0396B
Use with nger guard kit, ordering number
•
175G5XXX.
Use the recommended pressure terminal/
•
connector kit. See Table 11.1 for more
information.
1111
11.1.4 Models MCD5-0245C
11.1.7 Pressure Terminal/Connector Kits
For models MCD50131B to MCD5-0396B and MCD5-0245C
to MCD5-1600C to be UL-compliant, use the recommended
pressure terminal/connector as detailed in Table 11.1.
ModelFLC (A)
MCD5-0131B1451 OPHD 95-16
MCD5-0141B1701 OPHD 120-16
MCD5-0195B2001 OPHD 150-16
MCD5-0215B2201 OPHD 185-16
MCD5-0245B2551 OPHD 240-20
MCD5-0331B3501OPHD 400-16
MCD5-0396B4252OPHD 185-16
MCD5-0245C2551OPHD 240-20
MCD5-0360C360
MCD5-0380C380
MCD5-0428C430
MCD5-0595C620
MCD5-0619C650
MCD5-0790C79042 x 600T-2
MCD5-0927C93032 x 600T-2
MCD5-1200C1200
MCD5-1410C1410
MCD5-1600C16005
Table 11.1 Pressure Terminal/Connector Kits
Number of
wires
21 x 600T-2
4 1 x 750T-4
Recommended
lugs ordering
numbers
1 x 750T-4 and
1 x 600T-3
Use the recommended pressure terminal/
•
connector kit. See Table 11.1 for more
information.
11.1.5 Models MCD5-0360C to
MCD5-1600C
Congure the busbars for line/load terminals at
•
opposite ends of the soft starter (that is Top in/
Bottom out, or Top out/Bottom in.
Use the recommended pressure terminal/
•
connector kit. See Table 11.1 for more
information.
11.1.6 Models MCD5-0469B to
MCD5-0961B
These models are UL recognised components. Separate
cable landing busbars may be required within the electrical
cabinet when terminating cables sized according to the
National Wiring Code (NEC) regulations.
Accessories
11.2
11.2.1 LCP Remote Mounting Kit
The MCD 500 LCP can be mounted up to 3 metres away
from the soft starter, allowing remote control and
monitoring. The remote LCP also allows parameter settings
to be copied between soft starters.
175G0096 Control Panel LCP 501
•
11.2.2 Communication Modules
MCD 500 soft starters support network communication via
easy-to-install communication modules. Each soft starter
can support 1 communication module at a time.
As standard, MCD 500 rated impulse withstand voltage is
limited to 4 kV. The surge protection kits protect the
system and make the soft starter immune to high-voltage
impulses.
6 kV
175G0100 SPD Surge protection kit for G1
•
175G0101 SPD Surge protection kit, G2-G5
•
12 kV
175G0102 SPD Surge protection kit for G1
•
175G0103 SPD Surge protection kit, G1-G5
•
11.2.4 Finger Guard Kit
Finger guards may be specied for personnel safety. Finger
guards t over the soft starter terminals to prevent
accidental contact with live terminals. Finger guards
provide IP20 protection when correctly installed.
MCD5-0131B to MCD5-0215B: 175G5662
•
MCD5-0245B to MCD5-0396B: 175G5730
•
MCD5-0469B to MCD5-0961B: 175G5731
•
MCD5-245C: 175G5663
•
MCD5-0360C to MCD5-0927C: 175G5664
•
MCD5-1200C to MCD5-1600C: 175G5665
•
NOTICE
To be UL-compliant, the models MCD5-0131B to
MCD5-0396B require nger guards.
Illustration 11.1 System with Surge Protection Kit
12 Busbar Adjustment Procedure (MCD5-0360C to MCD5-1600C)
The busbars on non-bypassed models MCD5-0360C to
MCD5-1600C can be adjusted for top or bottom input and
output as required.
NOTICE
Many electronic components are sensitive to static
electricity. Voltages so low that they cannot be felt, seen
or heard, can reduce the life, aect performance, or
completely destroy sensitive electronic components.
When performing service, use proper ESD equipment to
prevent possible damage from occurring.
All units are manufactured with input and output bus bars
at the bottom of the unit as standard. If necessary, the
input and/or output bus bars can be moved to the top of
the unit.
1.Remove all wiring and links from the soft starter
before dismantling the unit.
2.Remove the unit cover (4 screws).
3.Remove the LCP faceplate, then gently remove
the LCP (2 screws).
4.Remove the control card terminal plugs.
5.Gently fold the main plastic away from the soft
starter (12 screws).
6.Unplug the LCP loom from CON 1 (see Notice).
1212
7.Label each SCR ring loom with the number of
the corresponding terminal on the main control
PCB, then unplug the looms.
8.Unplug the thermistor, fan, and current
transformer wires from the main control PCB.
9.Remove the plastic tray from the soft starter (4
screws).
Illustration 12.1
10.Unscrew and remove the magnetic bypass plates
(models MCD5-0620C to MCD5-1600C ONLY).
11.Remove the current transformer assembly (3
screws).
12.Identify which bus bars to remove. Remove the
bolts holding these bus bars in place then slide
the bus bars out through the bottom of the
starter (4 bolts per bus bar).
NOTICE
Remove the main plastic slowly to avoid damaging the
LCP wiring loom which runs between the main plastic
and the backplane PCB.
13.Slide the bus bars in through the top of the
starter. For input bus bars, place the short curved
end outside the soft starter. For output bus bars,
place the unthreaded hole outside the soft
starter.
14.Replace the dome washers with the at face
towards the bus bar, then tighten the bolts
holding the bus bars in place to 20 Nm.
15.Place the current transformer assembly over the
input bus bars and screw the assembly to the
body of the starter (see Notice).
16.Run all wiring to the side of the soft starter and
secure with cable ties.
Illustration 12.3
NOTICE
If moving the input busbars, the current transformers
must also be recongured.
1.Label the current transformers L1, L2, and L3
(L1 is leftmost when working from the front of
the starter). Remove the cable ties and unscrew
the current transformers from the bracket.
2.Move the current transformer bracket to the top
of the starter. Position the current transformers
for the correct phases, then screw the current
transformers to the bracket. For models
MCD5-0360C to MCD5-0930, place the current
transformers on an angle. The left-hand legs of
each current transformer are on the top row of
holes and the right-hand legs are on the
bottom tabs.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to
products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property
of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
175R0549MG17K50210/2015
*MG17K502*
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.