Condensing pressure regulator, type KVR
Differential pressure valve, type NRD
Regulating system KVR and NRD is used to
maintain a constant and sufficiently high
condenser and receiver pressure in refrigeration
and air conditioning plant with air-cooled
condensers.
KVR can also be used together with receiver
pressure regulator, type KVD.
Minimum opening pressure differential for NRDStart opening: Δp = 1.4 bar
KVR 12 - KVR 22 is evaluated for R290, R454A, R454C,
R455A, R600, R600a, R1234ze(E), R1270 by ignition
source assessment in accordance with standard
EN13463-1.
R452B**, R454A*, R454B**, R454C*, R455A*, R507, R513A,
R515B, R516A, R600*, R600a*, R1233zd(E)**, R1234ze(E)*,
R1234yf**
*KVR 12 - KVR 22 and NRD only
**NRD only
5 – 17.5 bar
Factory setting = 10 bar
KVR: PS/MWP = 28 bar
NRD: PS/MWP = 49 bar
KVR: Pe = 31 bar
NRD: Pe = 81 bar
KVR: -45 – 130 °C,
NRD: -50 – 155 °C
KVR 12 – 22 = 6.2 bar
KVR 28 – 35 = 5 bar
For complete list of approved refrigerants,
visit http://store.danfoss.com/ and search for
individual code numbers, where refrigerants are
listed as part of technical data.
NRD is evaluated for R32, R1270, R290, R452B, R454A,
R454B, R454C R455A, R600, R600a, R1233zd(E),
R1234ze(E), R1234yf by ignition source assessment in
accordance with standard EN13463-1.
All Danfoss products fulfill the requirements in REACH.
One of the obligations in REACH is to inform customers about
presence of Candidate list substances if any, we hereby inform
you about one substance on the candidate list:
an O-ring used in this product contains Diisopentylphthalat
(CAS no: 605-50-5) in a concentration above 0.1% w/w.
AI251086497566en-000901 | 2
Data sheet | Condensing pressure regulator, type KVR and differential pressure valve, type NRD
Liquid capacity
Max. regulator capacity Qe 1)
Liquid capacity in [kW]
Condensing
Type
KVR 12
KVR 15
KVR 22
KVR 28
KVR 35
KVR 12
KVR 15
KVR 22
KVR 28
KVR 35
1
) The capacities are based on:
temperature t
– Evaporating temperature te= -10 °C
– For other evaporating temperatures see table below
Data sheet | Condensing pressure regulator, type KVR and differential pressure valve, type NRD
Sizing
Valve selection
For optimum performance, it is important to
select a KVR valve according to system conditions
and application.
Example
When selecting the appropiate valve it may
be necessary to convert the actual evaporator
capacity using a correction factors.
This is required when your system conditions are
different than the table conditions.
The selection is also dependant on the
acceptable pressure drop across the valve.
The following example illustrates how this is
done.
Application example
Liquid capacity application
The following data must be used when sizing a
KVR valve:
• Refrigerant: HCFC, HFC and HC: KVR 12 – KVR 22,
HCFC and non-flammable HFC: KVR 28 – KVR 35
Data sheet | Condensing pressure regulator, type KVR and differential pressure valve, type NRD
Valve selection
(continued)
Step 1
Determine the correction factor for evaporating
temperature te.
From the correction factors table an evaporating
temperature of -40 °C, R22 corresponds to a
factor of 1.09.
Correction factors
t
e
[°C]
R221.091.051.021.00.980.96
R134a1.141.091.041.00.960.93
R404A, R5071.181.111.051.00.950.92
R407C1.121.081.041.00.970.93
Plant capacity x correction factor = table capacity
-40-30-20-10010
Step 2
Corrected evaporator capacity is
Qe = 100 x 1.09 = 109.0 kW
Step 3
Now select the appropriate capacity table and
choose the line for a condensing temperature
tc= 30 °C.
Using the corrected evaporator capacity, select a
KVR 12, KVR 15, KVR 22 delivers 142.9 kW at
1.6 bar pressure drop across the valve.
Based on the required connection size of 5⁄8 in.
ODF, the KVR 15 is the proper selection for this
example.
valve that provides an equivalent or greater
capacity at an acceptable pressure drop.
Step 4
KVR 15, 5⁄8 in. solder connection:
code no. 034L0097 (see ordering list)
Data sheet | Condensing pressure regulator, type KVR and differential pressure valve, type NRD
Design / Function
1. Seal cap
2. Gasket
3. Setting screw
4. Main spring
5. Valve body
6. Equalizing bellows
7. Valve plate
8. Valve seat
9. Damping device
10. Pressure gauge connection
11. Cap
12. Gasket
13. Insert
14. Copper tube
15. Washer
16. Teflon disk
17. Piston
18. Spring
19. Valve body
20. Guide
21. Stop face
KVRNRD
1
= 8 mm
2
3
4
5
6
7
8
9
10
11
12
13
Condensing pressure regulator, type KVR opens
upon a rise in pressure on the inlet side, i.e. when
the pressure in the condenser reaches the set
value. KVR regulation is dependent only on the
inlet pressure. Pressure variations on the outlet
side of the regulator do not affect the degree of
opening, since type KVR has an equalizing
bellows (6). The effective area of this bellows
corresponds to that of the valve seat.
In addition, the regulator is equipped with an
effective damping device (9) to safe-guard
against pulsations which can normally occur in
refrigeration plant.
The damping device contributes to ensuring
a long working life for the regulator without
impairing regulation accuracy.
Differential valve type NRD begins to open when
the pressure drop in the valve is 1.4 bar.
Data sheet | Condensing pressure regulator, type KVR and differential pressure valve, type NRD
P-band and OffsetPrinciple diagram
Capacity
100%
100%
Rated capacity
Set point
513
513
Min. setting point
Offset
P-band
Adjustment range
16
16
Max. setting point
[bar]
Proportional band
The proportional band or P-band is defined as
the amount of pressure required to move the
valve plate from closed (set point) to fully open
position.
Example
If the valve is set to open at 10 bar and the
valve P-band is 6.2, the valve will give maximum
capacity when the inlet pressure reaches
16.2 bar.
Offset
The offset is defined as the amount of pressure
required to move the valve plate from closed
position (set point) to the necessary opening
degree for the actual load.
The offset is always a part of the P-band.
Example with R22
A working temperature of 36 °C ~ 13 bar is
required, and the temperature must not drop
below 27 °C ~ 10 bar (set point).
The offset will then be 3 bar.
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
vided that such alterations can be made without subsequential changes being necessaryeady agreed.