Crankcase pressure regulator Type KVL
Crankcase pressure regulator type KVL is fitted in the suction line ahead of the compressor.
KVL protects the compressor motor against overload during start-up after long standstill periods or after defrost periods (high pressure in evaporator).
Features • Accurate, adjustable pressure regulation
• Wide capacity and operating ranges
• Pulsation damping design
• Stainless steel bellows
• Compact angle design for easy installation in any position
• “Hermetic” brazed construction
• Available in a wide size range of flare and ODF solder types
• KVL 12 – KVL 22: may be used in the following EX range: Category 3 (Zone 2)
© Danfoss | DCS (az) | 2018.03
DKRCC.PD.HH0.D8.02 | 1
Data sheet | Crankcase pressure regulator, type KVL
Approvals
Technical data
UL LISTED, file SA7200 EAN
Refrigerants
Regulating range
Maximum working pressure PS/MWP = 18 bar
Maximum test pressure Pe = 19.8 bar
Medium temperature range -60 – 130 °C
Maximum P-band
Kv-value1) with maximum P-band
1
) The Kv value is the flow of water in [m3 / h] at a pressure drop across valve of 1 bar, ρ = 1000 kg / m3.
This product (KVL 12 – KVL 22) is evaluated for R290, R600, R600a, R1270 by ignition source assessment in accordance with standard EN13463-1.
R22, R1270*, R134a, R290*, R40 4A, R407A, R407C, R407F, R448A, R449A, R450A, R452A, R507A, R513A, R600*, R600a* * KVL 12 – KVL 22 only
0.2 – 6 bar
Factory setting = 2 bar
KVL 12 – 22: 2 bar
KVL 28 – 35: 1.5 bar
KVL 12 – 22: 3.2 m3 / h
KVL 28 – 35: 8.0 m3 / h
For complete list of approved refrigerants, visit www.products.danfoss.com and search for individual code numbers, where refrigerants are listed as part of technical data.
Ordering
Rated capacity 1)
Type
KVL 12
KVL 15 7.1 5.3 6.3 6.5
KVL 22 7.1 5.3 6.3 6.5
KVL 28
KVL 35 17.8 13.2 15.9 16.4 1 3⁄8 35 034L0052
1
) Rated capacity is the regulator capacity at: suction temperature ts = -10 °C condensing temperature tc = 25 °C pressure drop in regulator Δp = 0.2 bar To select the product for other conditions or refrigerants, use Danfoss Coolselector®2.
2
) KVL supplied without flare nuts. Separate flare nuts can be supplied: 1⁄2 in / 12 mm, code no. 011L1103 5⁄8 in / 16 mm, code no. 011L1167
R22 R134a
7.1 5.3 6.3 6.4
7.1 5.3 6.3 6.4 12 034L0048
17.8 13.2 15.9 16.4 1 1⁄8 034L0046
17.8 13.2 15.9 16.4 28 034L0051
[kW]
R404A/
R507
R407C [in] [mm] [in] [mm]
Flare
connection 2)
1
2 12 034L0041
5
8 16 034L0042
Code no.
Solder ODF
1
2 034L0043
5
8 16 034L0049
7
8 22 034L0045
Code no.
The connection dimensions chosen must not be too small, as gas velocities in excess of 40 m / s at the inlet of the regulator can result in flow noise.
REACH requirements
© Danfoss | DCS (az) | 2018.03
All Danfoss products fulfill the requirements in REACH. One of the obligations in REACH is to inform customers about presence of Candidate list substances if any, we hereby inform you about one substance on the candidate list: an O-ring used in this product contains Diisopentylphthalat (CAS no: 605-50-5) in a concentration above 0.1% w/w.
DKRCC.PD.HH0.D8.02 | 2
Data sheet | Crankcase pressure regulator, type KVL
Capacity
Max. regulator capacity Qe 1)
Pressure
drop in
Type
KVL 12 KVL 15 KVL 22
KVL 28 KVL 35
1
) The values in the capacity tables refer to the evaporator capacity and are based on liquid temperature tl = 25 °C
regulator
∆p
[bar] [bar] -35 -30 -25 -20 -15 -10 -5 0 5 10 15
0.1 1 1.9 1.2
0.1 2 3.0 3.3 3.1 2.1 0.2
0.1 3 3.0 3.3 3.7 4.1 4.0 2.2
0.1 4 3.0 3.3 3.7 4.1 4.6 5.0 3.9 0.1
0.1 5 3.0 3.3 3.7 4.1 4.6 5.0 5.5 5.2 1.0
0.1 6 3.0 3.3 3.7 4.1 4.6 5.0 5.5 6.0 6.2 1.3
0.2 1 2.6 1.7
0.2 2 4.2 4.7 4.4 3.0 0.2
0.2 3 4.2 4.7 5.3 5.9 5.6 3.1
0.2 4 4.2 4.7 5.3 5.9 6.5 7.1 5.5 0.1
0.2 5 4.2 4.7 5.3 5.9 6.5 7.1 7.8 7.3
0.2 6 4.2 4.7 5.3 5.9 6.5 7.1 7.8 8.5 8.7 1.9
0.3 1 3.2 2.0
0.3 2 5.2 5.8 5.4 3.7 0.3
0.3 3 5.2 5.8 6.5 7.2 6.9 3.8
0.3 4 5.2 5.8 6.5 7.2 8.0 8.8 6.7 0.2
0.3 5 5.2 5.8 6.5 7.2 8.0 8.8 9.6 9.0 1.7
0.3 6 5.2 5.8 6.5 7.2 8.0 8.8 9.6 10.5 10.7 2.3
0.1 1 4.1 2.6
0.1 2 7.4 7.9 7.0 4.6 0.4
0.1 3 7.4 8.3 9.3 10.3 8.9 4.7
0.1 4 7.4 8.3 9.3 10.3 11.4 12.3 8.5 0.2
0.1 5 7.4 8.3 9.3 10.3 11.4 12.6 13.8 11.6 2.2
0.1 6 7.4 8.3 9.3 10.3 11.4 12.6 13.8 15.1 13.9 2.8
0.2 1 5.8 3.6
0.2 2 10.6 11.2 9.8 6.5 0.5
0.2 3 10.6 11.8 13.2 14.7 12.5 6.6
0.2 4 10.6 11.8 13.2 14.7 16.2 17.5 12.0 0.3
0.2 5 10.6 11.8 13.2 14.7 16.2 17.8 19.6 16.4 3.1
0.2 6 10.6 11.8 13.2 14.7 16.2 17.8 19.6 21.4 19.6 4.0
0.3 1 7.0 4.4
0.3 2 13.0 13.8 12.1 8.0 0.6
0.3 3 13.0 14.6 16.3 18.0 15.4 8.1
0.3 4 13.0 14.6 16.3 18.0 19.9 21.5 14.7 0.3
0.3 5 13.0 14.6 16.3 18.0 19.9 21.9 24.1 20.0 3.7
0.3 6 13.0 14.6 16.3 18.0 19.9 21.9 24.1 26.3 24.1 4.9
Maximum
suction
pressure
PS
Capacity Qe in [kW] at suction temperature ts after the regulator [°C]
R22
© Danfoss | DCS (az) | 2018.03
Correction factors for liquid temperature t
tl [°C] 10 15 20 25 30 35 40 45 50
R22 0.90 0.93 0.96 1.0 1.05 1.10 1.13 1.18 1.24
Plant capacity × correction factor = the values in the table
l
DKRCC.PD.HH0.D8.02 | 3