KPU 60/70 - Thermostats
KPU 60/70 thermostats are designed to be technician-friendly by functioning as easy and direct replacements for most controls on the market and feature snap-action switches, highly visible contrast scales, ngertip tests, and are easily adjustable using a standard refrigeration wrench.
Easy adjustment of temperature setting with hand knob (all but models with manual reset). Dierential setting
Features
KPU 60/70
adjusted with standard refrigeration wrench. A set screw prevents settings from migrating.
Snap-action switch
“Fingertip” test for contact operation
Facts
Applications:
• Traditional refrigeration
• Air conditioning
• Heating systems
Easy to access contacts with 24 FLA rating
High visibility, high contrast scale
- Ambient temperature: −40 °F to +122 °F (175 °F for maximum 2 hours)
- Switch: Single pole changeover switch (SPDT)
- Enclosure: NEMA 1
- Cable entry: ⁄ inch cable entry for ½ inch male pipe thread connection (conduit boss) or similar screwed cable entry
22
Quick Select Guide
Technical data and ordering
KPU 60/70 Thermostats
Danfoss
Typ e
KPU 61
KPU 61
Bulb type
Straight
capillary tube
Remote
air coil
KPU 62 Room sensor
KPU 68 Room sensor
KPU 73 Remote bulb
KPU 71 Remote bulb
KPU 77 Remote bulb
1
Bulb must be installed in colder position than thermostat housing and capillary tube.
2
Temperature variations in excess of 70 °F between sensing bulb, housing, and capillary tube will inuence scale accuracy.
Range
(°F)
−20 to 60 SPDT/Auto 80 10 to 40 2.5 to 13 250
1
−20 to 60 SPDT/Auto 80 8 to 40 2.5 to 13 250
1
1
−20 to 60 SPDT/Auto Room sensor 10 to 40 2.5 to 13 250
1
25 to 95 SPDT/Auto Room sensor 8 to 45 3 to 13 250
2
−15 to 60 SPDT/Auto 80 6.5 to 32 5 to 50 175
2
25 to 70 SPDT/Auto 80 5.5 to 18 4 to 16 175 060L5218
2
60 to 140 SPDT/Auto 80 6 to 18 6.3 to 18 265
Contact/
Reset
Capillary
tube length
(in.)
temp. setting
Resistive load
Contact Load
Inductive load
Full load
Locked rotor
Pilot duty 12W/120V DC
Dierential
at lowest
24A/120V AC 24A/240V AC
24A/120V AC 24A/240V AC
144A/120V AC 144A/240V AC
at highest
temp. setting
Maximum
bulb
temperature (°F)
Competitor
part no.
Danfoss
Code No.
O10-1416 O10-1010
O16-111
060L5201
O10-1419
O10-1408 O10-1409 O10-1473
060L5203
O16-104
O10-1410
O10-1072 O10-1418
O16-594
060L5206
O60-101
O10-1802
O16-595 O10-301
060L5215
O16-165
O60-100 O60-120
060L5208
O60-200
A19AAF-12C
A19AAB-4C
060L5223
A19ABB-2C A19ABB-7C
Quick Select Guide