Danfoss Electronics KPU 19 Data Sheet

Data sheet
Thermostat KPU 19
KPU 19 thermostats are used for temperature regulation in refrigeration, freezing, air conditioning, ventilating and heating systems.
KPU 19 thermostats are tted with Single-Pole Double-Throw (SPDT) or Single-Pole Single-Throw (SPST) contact system.
The standard KPU 19 enclosure is rated NEMA ~ 1. NEMA ~ 1 is obtained when the thermostat is
mounted on a at surface with all unused holes covered.
Features
Approvals
© Danfoss | DCS (rm) | 2019.05 DKRCC.PD.CA0.H3.22 | 520H11473 | 1
• Long operational life time
• Stable settings
• Reliable and robust SPST and SPDT contact system
• Switching points can be set easily and accurately using the range scale plate and dierential adjusting knob.
UL 873, le E96053
• Terminals enable easy wiring
• KPU 19 easily replaces other manufacturers’ thermostats
Data sheet | Thermostat, KPU 19
H
H
Technical data
Ordering
Ambient temperature
Max. bulb temperature 140 °F
Functional range -30 – 80 °F
Differential 3.6 – 12.6 °F
Reset Automatic
Switch system SPST (close on temp. rise), SPDT
Resistive load
Contact load
Enclosure
Typ e Regulating
KPU 19 -30 – 80 3.6 – 12.6 3⁄8 x 4 ½ 120 auto. SPDT 06 0L2150
KPU 19 -30 – 80 3.6 – 12.6 3⁄8 x 4 ½ 80 auto.
KPU 19 -30 – 80 3.6 – 12.6
Inductive load
Pilot duty 125V A; 120 / 240V AC
range
[°F] ∆T [°F] [°F] [in]
Full load
Locked rotor
Dierential Bulb size Capillary
-31 – 140 °F for KPU with remote bulb
-31 – 140 °F for KPU with room sensor
0.5 ~ 16A / 120V AC
0.5 ~ 8A / 240V AC
0.5 ~ 16A / 120V AC
0.5 ~ 8A / 240V AC
96A / 120V AC 48A / 240V AC
NEMA ~1 (when mounted on a flat surface with all unused holes covered)
tube length
Air coil /
Room sensor
Reset Switch
system
SPST
(close on
temp. rise)
auto. SPDT 06 0L2152
Code no.
060L2151
Contact system
Enclosed accessories:
• Sensor clamp for bulb fastening.
• Blinding sticker to cover the hole after dial knob removal. Blinding sticker can be used only once.
• Hand knob for adjustment.
Switch type Switch action Applicaton
1. Terminals C – H close high and
C
SPDT
C
SPST (open low)
open low terminals C – L can be used as low temperature alarm.
L
oss
2. Terminals C – L open high and
Danfoss
60-1421.10
close low terminals C – H can be used as high temperature alarm.
Terminals C – H close high and open low
1. Low temperature cut-out
2. High temperature cut-out
1. Low temperature cut-out
2. Condenser fan cycling control
© Danfoss | DCS (rm) | 2019.052 | 520H11473 | DKRCC.PD.CA0.H3.22