Data sheet
Thermostat
KPU 19
KPU 19 thermostats are used for temperature
regulation in refrigeration, freezing, air
conditioning, ventilating and heating systems.
KPU 19 thermostats are tted with Single-Pole
Double-Throw (SPDT) or Single-Pole Single-Throw
(SPST) contact system.
The standard KPU 19 enclosure is rated
NEMA ~ 1.
NEMA ~ 1 is obtained when the thermostat is
mounted on a at surface with all unused holes
covered.
Features
Approvals
© Danfoss | DCS (rm) | 2019.05 DKRCC.PD.CA0.H3.22 | 520H11473 | 1
• Long operational life time
• Stable settings
• Reliable and robust SPST and SPDT contact
system
• Switching points can be set easily and accurately
using the range scale plate and dierential
adjusting knob.
UL 873, le E96053
• Terminals enable easy wiring
• KPU 19 easily replaces other manufacturers’
thermostats
Data sheet | Thermostat, KPU 19
Technical data
Ordering
Ambient temperature
Max. bulb temperature 140 °F
Functional range -30 – 80 °F
Differential 3.6 – 12.6 °F
Reset Automatic
Switch system SPST (close on temp. rise), SPDT
Resistive load
Contact load
Enclosure
Typ e Regulating
KPU 19 -30 – 80 3.6 – 12.6 3⁄8 x 4 ½ 120 auto. SPDT 06 0L2150
KPU 19 -30 – 80 3.6 – 12.6 3⁄8 x 4 ½ 80 auto.
KPU 19 -30 – 80 3.6 – 12.6 –
Inductive load
Pilot duty 125V A; 120 / 240V AC
range
[°F] ∆T [°F] [°F] [in]
Full load
Locked rotor
Dierential Bulb size Capillary
-31 – 140 °F for KPU with remote bulb
-31 – 140 °F for KPU with room sensor
0.5 ~ 16A / 120V AC
0.5 ~ 8A / 240V AC
0.5 ~ 16A / 120V AC
0.5 ~ 8A / 240V AC
96A / 120V AC
48A / 240V AC
NEMA ~1 (when mounted on a flat surface with all unused
holes covered)
tube length
Air coil /
Room sensor
Reset Switch
system
SPST
(close on
temp. rise)
auto. SPDT 06 0L2152
Code no.
060L2151
Contact system
Enclosed accessories:
• Sensor clamp for bulb fastening.
• Blinding sticker to cover the hole after dial knob
removal. Blinding sticker can be used only once.
• Hand knob for adjustment.
Switch type Switch action Applicaton
1. Terminals C – H close high and
C
SPDT
C
SPST (open low)
open low terminals C – L can be
used as low temperature alarm.
L
oss
2. Terminals C – L open high and
Danfoss
60-1421.10
close low terminals C – H can be
used as high temperature alarm.
Terminals C – H close high and
open low
1. Low temperature cut-out
2. High temperature cut-out
1. Low temperature cut-out
2. Condenser fan cycling control
© Danfoss | DCS (rm) | 2019.052 | 520H11473 | DKRCC.PD.CA0.H3.22