3.1.2 Local (Hand On) and Remote (Auto On) Control18
3.1.3 Control Structure Closed Loop19
3.1.4 Reference Handling20
3.2 General Aspects of EMC
3.2.1 Emission Requirements22
3.3 Galvanic Isolation (PELV)
3.4 Earth Leakage Current
3.5 Extreme Running Conditions
3.5.1 Motor Thermal Protection25
4 Selection
4.1 Options and Accessories
4.1.1 Local Control Panel (LCP)26
4.1.2 Remote Mounting Kit for LCP26
4.1.3 FC 51 LCP Mounting Instruction27
4.1.4 FC 51 Remote Mounting Kit Mounting Instruction27
4.1.5 IP21/TYPE 1 Enclosure Kit29
21
23
24
24
26
26
4.1.6 Type 1 (NEMA)29
4.1.7 De-Coupling29
4.1.8 FC 51 Type 1 Kit Mounting Instruction for M1, M2 and M330
4.1.9 FC 51 Type 1 Kit Mounting Instruction for M4 and M530
MG02K302 - Rev. 2013-12-031
Contents
VLT® Micro Drive FC 51 Design Guide
4.1.10 FC 51 IP21 Kit Mounting Instruction31
4.1.11 FC 51 De-coupling Plate Mounting Instruction for M1 and M232
4.1.12 FC 51 De-coupling Plate Mounting Instruction for M332
4.1.13 FC 51 De-coupling Plate Mounting Instruction for M4 and M533
4.1.14 FC 51 DIN Rail Kit Mounting Instruction34
4.1.15 Line Filter MCC 107 Installation Instructions34
4.1.16 Mounting35
4.1.17 Wiring35
4.1.18 Dimensions36
4.2 Special Conditions
4.2.1 Purpose of Derating37
4.2.2 Derating for Ambient Temperature37
4.2.3 Derating for Low Air Pressure38
4.2.4 Automatic Adaptations to Ensure Performance38
4.2.5 Derating for Running at Low Speed38
5 How to Order
5.1 Drive Configurator
5.2 FC Identification
5.3 Type Code
5.4 Ordering Numbers
5.5 Options
6 How to Install
6.1 Before Starting
6.2 Side-by-Side Installation
6.3 Before Commencing Repair Work
37
39
39
39
40
41
41
43
43
43
43
6.4 Mechanical Dimensions
6.5 Electrical Installation in General
6.6 Fuses
6.7 Mains Connection
6.8 Motor Connection
6.9 Use of EMC-Correct Cables
6.10 Earthing of Screened/Armoured Control Cables
6.11 Residual Current Device
6.12 Electrical Overview
6.12.1 Power Circuit - Overview51
6.13 Electrical Installation and Control Cables
6.14 Control Terminals
6.14.1 Access to Control Terminals52
6.14.2 Connecting to Control Terminals53
2MG02K302 - Rev. 2013-12-03
44
44
45
46
46
49
50
50
51
52
52
Contents
VLT® Micro Drive FC 51 Design Guide
6.15 Switches
6.16 Final Set-Up and Test
6.17 Parallel Connection of Motors
6.18 Motor Installation
6.19 Installation of Misc. Connections
6.20 Safety
6.20.1 High Voltage Test57
6.20.2 Safety Earth Connection57
7 Programming
7.1 How to Programme
7.1.1 Programming with MCT 10 Set-up Software58
7.1.2 Programming with the LCP 11 or LCP 1258
7.2 Status Menu
7.3 Quick Menu
7.4 Quick Menu Parameters
7.5 Main Menu
7.6 Quick Transfer of Parameter Settings between Multiple Frequency Converters
53
53
55
56
56
57
58
58
59
59
60
63
63
7.7 Read-out and Programming of Indexed Parameters
7.8 Initialise the Frequency Converter to Default Settings in two Ways
8 RS-485 Installation and Set-up
8.1 RS-485 Installation and Set-up
8.1.1 Overview65
8.1.2 Network Connection65
8.1.3 Frequency Converter Hardware Set-up65
8.1.4 EMC Precautions66
8.2 FC Protocol Overview
8.3 Network Configuration
8.4 FC Protocol Message Framing Structure
8.4.1 Content of a Character (byte)67
8.4.2 Telegram Structure67
8.4.3 Telegram Length (LGE)67
8.4.4 Frequency Converter Address (ADR)68
8.4.5 Data Control Byte (BCC)68
8.4.6 The Data Field68
63
64
65
65
66
67
67
8.4.7 The PKE Field69
8.4.8 Parameter Number (PNU)69
8.4.9 Index (IND)69
8.4.10 Parameter Value (PWE)69
8.4.11 Data Types Supported by the Frequency Converter70
MG02K302 - Rev. 2013-12-033
Contents
VLT® Micro Drive FC 51 Design Guide
8.4.12 Conversion70
8.5 Examples
8.6 Modbus RTU Overview
8.6.1 Assumptions71
8.6.2 What the User Should Already Know71
8.6.3 Modbus RTU Overview71
8.6.4 Frequency Converter with Modbus RTU72
8.7 Network Configuration
8.8 Modbus RTU Message Framing Structure
8.8.1 Frequency Converter with Modbus RTU72
8.8.2 Modbus RTU Message Structure72
8.8.3 Start/Stop Field73
8.8.4 Address Field73
8.8.6 Data Field73
8.8.7 CRC Check Field73
8.8.8 Coil Register Addressing73
8.8.9 How to Control the Frequency Converter75
8.8.10 Function Codes Supported by Modbus RTU75
70
71
72
72
8.8.11 Modbus Exception Codes76
8.9 How to Access Parameters
8.9.1 Parameter Handling76
8.9.2 Storage of Data76
8.9.3 IND (Index)76
8.9.4 Text Blocks76
8.9.6 Parameter Values76
8.10 Examples
8.10.1 Read Coil Status (01 hex)77
8.10.2 Force/Write Single Coil (05 hex)77
8.10.3 Force/Write Multiple Coils (0F hex)78
8.10.4 Read Holding Registers (03 hex)78
8.10.5 Preset Single Register (06 hex)78
8.10.6 Preset Multiple Registers (10 hex)79
8.11 FC Drive Control Profile
8.11.1 Control Word According to FC Profile (8-10 Protocol = FC profile)79
8.11.2 Status Word According to FC Profile (STW) (8-30 Protocol = FC profile)81
76
77
79
8.11.3 Bus Speed Reference Value82
9 Specifications
Index
4MG02K302 - Rev. 2013-12-03
83
89
Introduction
VLT® Micro Drive FC 51 Design Guide
1 Introduction
1.1 Available Literature
NOTICE
This design guide contains the basic information
necessary
converter.
Danfoss technical literature is available in print from local
Danfoss
BusinessAreas/DrivesSolutions/Documentations
1.2 Document and Software Version
This manual is regularly reviewed and updated. All
suggestions
the document version and the corresponding software
version.
EditionRemarksSoftware Version
MG02K3XXReplaces MG02K2XX3.1X
Table 1.1 Document and Software Version
for installing and running the frequency
Sales Offices or online at: www.danfoss.com/
VLT Micro Drive FC 51 Quick Guide, MG02B
•
VLT Micro Drive FC 51 Programming Guide, MG02C
•
FC 51 LCP Mounting Instruction, MI02A
•
FC 51 De-coupling Plate Mounting Instruction,
•
MI02B
FC 51 Remote Mounting Kit Mounting Instruction,
•
MI02C
FC 51 DIN Rail Kit Mounting Instruction, MI02D
•
FC 51 IP21 Kit Mounting Instruction, MI02E
•
FC 51 Nema1 Kit Mounting Instruction, MI02F
•
FC 51 Line Filter MCC 107 Installation Instruction,
•
MI02U
for improvement are welcome. Table 1.1 shows
1.3 Abbreviations
°C
AAmpere/AMP
ACAlternating current
AMTAutomatic Motor Tuning
AWGAmerican wire gauge
DCDirect current
EMCElectro Magnetic Compatibility
ETRElectronic Thermal Relay
FCFrequency Converter
f
M,N
gGram
HzHertz
I
INV
I
LIM
I
M,N
I
VLT,MAX
I
VLT,N
kHzKilohertz
LCPLocal Control Panel
mMeter
mAMilliampere
MCTMotion Control Tool
mHMillihenry Inductance
minMinute
msMillisecond
nFNanofarad
NmNewton Meters
n
s
P
M,N
PCBPrinted Circuit Board
PELVProtective Extra Low Voltage
RPMRevolutions Per Minute
RegenRegenerative terminals
sSecond
T
LIM
U
M,N
VVolts
Degrees Celsius
Nominal motor frequency
Rated Inverter Output Current
Current limit
Nominal motor current
The maximum output current
The rated output current supplied by the
frequency
Synchronous Motor Speed
Nominal motor power
Torque limit
Nominal motor voltage
converter
11
Table 1.2 Abbreviations
MG02K302 - Rev. 2013-12-035
175ZA078.10
Pull-out
rpm
Torque
Introduction
VLT® Micro Drive FC 51 Design Guide
11
1.4 Definitions
Break-away torque
1.4.1 Frequency Converter
I
VLT,MAX
maximum output current.
The
I
VLT,N
The rated output current supplied by the frequency
converter.
U
VLT, MAX
The maximum output voltage.
1.4.2 Input
Control command
connected motor can be started and stopped with LCP
The
and the digital inputs.
Functions are divided into 2 groups.
Functions in group 1 have higher priority than functions in
group 2.
Group 1Reset, Coasting stop, Reset and Coasting stop,
Quick-stop, DC braking, Stop and the [Off] key.
Group 2Start, Pulse start, Reversing, Start reversing, Jog
Freeze output
and
Table 1.3 Function Groups
Illustration 1.1 Break-away Torque
η
VLT
efficiency of the frequency converter is defined as the
The
ratio between the power output and the power input.
Start-disable command
A stop command belonging to the group 1 control
commands, see Table 1.3.
Stop command
See Control commands.
1.4.3 Motor
f
JOG
The
motor frequency when the jog function is activated
(via digital terminals).
f
M
The motor frequency.
f
MAX
The maximum motor frequency.
f
MIN
The minimum motor frequency.
f
M,N
The rated motor frequency (nameplate data).
I
M
The motor current.
I
M,N
The rated motor current (nameplate data).
n
M,N
The rated motor speed (nameplate data).
P
M,N
The rated motor power (nameplate data).
U
M
The instantaneous motor voltage.
U
M,N
The rated motor voltage (nameplate data).
1.4.4 References
Analog Reference
signal transmitted to the analog inputs 53 or 54, can be
A
voltage or current.
Bus Reference
A signal transmitted to the serial communication port (FC
port).
Preset Reference
A defined preset reference to be set from -100% to +100%
of the reference range. Selection of 8 preset references via
the digital terminals.
Ref
MAX
Determines the relationship between the reference input
at 100% full scale value (typically 10 V, 20 mA) and the
resulting reference. The maximum reference value set in
3-03 Maximum Reference.
Ref
MIN
Determines the relationship between the reference input
at 0% value (typically 0 V, 0 mA, 4 mA) and the resulting
reference. The minimum reference value set in
3-02 Minimum Reference
6MG02K302 - Rev. 2013-12-03
Introduction
VLT® Micro Drive FC 51 Design Guide
1.4.5 Miscellaneous
Analog Inputs
analog inputs are used for controlling various
The
functions of the frequency converter.
There are 2 types of analog inputs:
Current input, 0-20 mA and 4-20 mA
•
Voltage input, 0-10 V DC.
•
Analog Outputs
The analog outputs can supply a signal of 0-20 mA, 4-20
mA, or a digital signal.
Automatic Motor Tuning, AMT
AMT algorithm determines the electrical parameters for the
connected motor at standstill.
Brake Resistor
The brake resistor is a module capable of absorbing the
brake power generated in regenerative braking. This
regenerative braking power increases the intermediate
circuit voltage and a brake chopper ensures that the
power is transmitted to the brake resistor.
CT Characteristics
Constant torque characteristics used for all applications
such as conveyor belts, displacement pumps and cranes.
Digital Inputs
The digital inputs can be used for controlling various
functions of the frequency converter.
Relay Outputs
The frequency converter features two programmable Relay
Outputs.
ETR
Electronic Thermal Relay is a thermal load calculation
based on present load and time. Its purpose is to estimate
the motor temperature.
Initialising
If initialising is carried out (14-22 Operation Mode), the
programmable parameters of the frequency converter
return to their default settings.
Initialising 14-22 Operation Mode does not initialise
communication parameters.
Intermittent Duty Cycle
An intermittent duty rating refers to a sequence of duty
cycles. Each cycle consists of an on-load and an off-load
period. The operation can be either periodic duty or noneperiodic duty.
LCP
The Local Control Panel makes up a complete interface for
control and programming of the frequency converter. The
control panel is detachable and can be installed up to 3 m
from the frequency converter, that is, in a front panel with
the installation kit option.
lsb
Least significant bit.
MCM
for Mille Circular Mil, an American measuring unit for
Short
cable cross-section. 1 MCM ≡ 0.5067 mm2.
msb
Most significant bit.
On-line/Off-line Parameters
Changes to on-line parameters are activated immediately
after the data value is changed. Changes to off-line
parameters are not activated until pressing [OK].
PI Controller
The PI controller maintains the desired speed, pressure,
temperature, etc. by adjusting the output frequency to
match the varying load.
RCD
Residual Current Device.
Set-up
Save parameter settings in 2 set-ups. Change between the
2 parameter set-ups and edit one set-up, while another
set-up is active.
Slip Compensation
The frequency converter compensates for the motor slip
by giving the frequency a supplement that follows the
measured motor load keeping the motor speed almost
constant.
Smart Logic Control (SLC)
The SLC is a sequence of user-defined actions executed
when the associated user-defined events are evaluated as
true by the SLC.
Thermistor
A temperature-dependent resistor placed where the
temperature is to be monitored (frequency converter or
motor).
STW
Status Word.
FC Standard Bus
Includes RS 485 bus with FC protocol. See 8-30 Protocol.
Trip
A state entered in fault situations, e.g. if the frequency
converter is subject to an over-temperature or when the
frequency converter is protecting the motor, process or
mechanism. Restart is prevented until the cause of the
fault has disappeared and the trip state is canceled by
activating reset or, in some cases, by being programmed
to reset automatically. Trip may not be used for personal
safety.
11
MG02K302 - Rev. 2013-12-037
Introduction
VLT® Micro Drive FC 51 Design Guide
11
Trip Locked
state entered in fault situations when the frequency
A
converter is protecting itself and requiring physical
intervention, for example, if the frequency converter is
subject to a short circuit on the output. A locked trip can
only be canceled by cutting off mains, removing the cause
of the fault, and reconnecting the frequency converter.
Restart is prevented until the trip state is canceled by
activating reset or, in some cases, by being programmed
to reset automatically. Trip locked may not be used for
personal safety.
VT Characteristics
Variable torque characteristics used for pumps and fans.
plus
VVC
If compared with standard voltage/frequency ratio control,
Voltage Vector Control (VVC
plus
) improves the dynamics
and the stability, both when the speed reference is
changed and in relation to the load torque.
1.5 Power Factor
The power factor is the relation between I1
× U ×
I
3
1 ×
COS
Power factor
=
3 ×
ϕ
U
×
I
RMS
The power factor for 3-phase control:
and I
RMS
.
I
cos
ϕ1
×
1
=
I
1
=
since cos
I
I
RMS
RMS
ϕ1 =1
The power factor indicates to which extent the frequency
converter
The lower the power factor, the higher the I
imposes a load on the mains supply.
RMS
for the
same kW performance.
2
2
2
I
RMS
=
I
+
I
+
1
5
I
+ . . +
7
2
I
n
In addition, a high-power factor indicates that the different
harmonic
currents are low.
8MG02K302 - Rev. 2013-12-03
Safety and Conformity
VLT® Micro Drive FC 51 Design Guide
2 Safety and Conformity
2.1 Safety
The following symbols are used in this document:
WARNING
Indicates a potentially hazardous situation which could
in death or serious injury.
result
CAUTION
Indicates a potentially hazardous situation which could
in minor or moderate injury. It may also be used
result
to alert against unsafe practices.
NOTICE
Indicates important information, including situations that
may
result in damage to equipment or property.
WARNING
DISCHARGE TIME
The
frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. Failure to wait the specified
time after power has been removed before performing
service or repair work, could result in death or serious
injury.
1.Stop motor.
2.Disconnect AC mains, permanent magnet type
motors, and remote DC-link power supplies,
including battery back-ups, UPS, and DC-link
connections to other frequency converters.
3.Wait for the capacitors to discharge fully, before
performing any service or repair work. The
duration of waiting time is specified in
Table 2.1.
22
2.1.1 Safety Precautions
WARNING
HIGH VOLTAGE
Frequency
connected to AC mains input power. Failure to perform
installation, start-up, and maintenance by qualified
personnel could result in death or serious injury.
converters contain high voltage when
Installation, start-up, and maintenance must be
•
performed by qualified personnel only.
WARNING
UNINTENDED START
When
the frequency converter is connected to AC mains,
the motor may start at any time, causing risk of death,
serious injury, equipment, or property damage. The
motor can start by means of an external switch, a serial
bus command, an input reference signal from the LCP or
LOP, via remote operation using MCT 10 software, or
after a cleared fault condition.
Disconnect the frequency converter from mains
•
whenever personal safety considerations make
it necessary to avoid unintended motor start.
Press [Off/Reset] on the LCP, before
•
programming parameters.
The frequency converter, motor, and any driven
•
equipment must be in operational readiness
when the frequency converter is connected to
AC mains.
SizeMinimum waiting time (min)
M1, M2 and M34
M4 and M515
Table 2.1 Discharge Time
WARNING
LEAKAGE CURRENT HAZARD
Leakage
frequency converter properly could result in death or
serious injury.
currents exceed 3.5 mA. Failure to ground the
Ensure correct grounding of the equipment by
•
a certified electrical installer.
WARNING
EQUIPMENT HAZARD
Contact
can result in death or serious injury.
with rotating shafts and electrical equipment
Ensure that only trained and qualified
•
personnel perform installation, start up, and
maintenance.
Ensure that electrical work conforms to national
•
and local electrical codes.
Follow the procedures in this manual.
•
MG02K302 - Rev. 2013-12-039
Safety and Conformity
VLT® Micro Drive FC 51 Design Guide
CAUTION
WINDMILLING
22
Unintended
causes risk of personal injury and equipment damage.
•
rotation of permanent magnet motors
Ensure that permanent magnet motors are
blocked to prevent unintended rotation.
CAUTION
POTENTIAL HAZARD IN THE EVENT OF INTERNAL
FAILURE
of personal injury when the frequency converter is
Risk
not properly closed.
Before applying power, ensure all safety covers
•
are in place and securely fastened.
2.2 Disposal Instruction
Equipment containing electrical
components may not be disposed of
together with domestic waste.
It must be separately collected with
electrical and electronic waste according
to local and currently valid legislation.
2.3 Approvals
information on safety aspects relating to the frequency
converter.
declaration.
The low-voltage directive (73/23/EEC)
Frequency converters must be CE labeled in accordance
with the low-voltage directive of January 1, 1997. The
directive applies to all electrical equipment and appliances
used in the 50-1000 V AC and the 75-1500 V DC voltage
ranges. Danfoss CE-labels in accordance with the directive
and issues a declaration of conformity upon request.
The EMC directive (89/336/EEC)
EMC is short for electromagnetic compatibility. The
presence of electromagnetic compatibility means that the
mutual interference between different components/
appliances does not affect the way the appliances work.
The EMC directive came into effect January 1, 1996.
Danfoss CE-labels in accordance with the directive and
issues a declaration of conformity upon request. To carry
out EMC-correct installation, see the instructions in this
Design Guide. In addition, Danfoss specifies which
standards our products comply with. Danfoss offers the
filters presented in the specifications and provide other
types of assistance to ensure the optimum EMC result.
The frequency converter is most often used by professionals of the trade as a complex component forming part
of a larger appliance, system or installation. Not that the
responsibility for the final EMC properties of the appliance,
system or installation rests with the installer.
Danfoss do this by means of a manufacturer's
Table 2.2 Approvals
The
frequency converter complies with UL508C thermal
memory retention requirements. For more information
refer to chapter 3.5.1 Motor Thermal Protection.
2.4 CE Labeling
2.4.1 CE Conformity and Labeling
What is CE Conformity and Labeling?
The
purpose of CE labeling is to avoid technical trade
obstacles within EFTA and the EU. The EU has introduced
the CE label as a simple way of showing whether a
product complies with the relevant EU directives. The CE
label says nothing about the specifications or quality of
the product. Frequency converters are regulated by 3 EU
directives:
The machinery directive (98/37/EEC)
All machines with critical moving parts are covered by the
machinery directive of January 1, 1995. Since a frequency
converter is largely electrical, it does not fall under the
machinery directive. However, if a frequency converter is
supplied for use in a machine, Danfoss provides
2.4.2 What is Covered
The EU "Guidelines on the Application of Council Directive89/336/EEC" outline three typical situations of using a
frequency converter. See chapter 2.4.3 Danfoss FrequencyConverter and CE Labeling for EMC coverage and CE
labeling.
1.The frequency converter is sold directly to the
end-consumer. The frequency converter is for
example sold to a DIY market. The end-consumer
is a layman. He installs the frequency converter
himself for use with a hobby machine, a kitchen
appliance, etc. For such applications, the
frequency converter must be CE labeled in
accordance with the EMC directive.
2.The frequency converter is sold for installation in
a plant. The plant is built up by professionals of
the trade. It could be a production plant or a
heating/ventilation plant designed and installed
by professionals of the trade. Neither the
frequency converter nor the finished plant has to
be CE labeled under the EMC directive. However,
the unit must comply with the basic EMC
requirements of the directive. This is ensured by
10MG02K302 - Rev. 2013-12-03
Safety and Conformity
VLT® Micro Drive FC 51 Design Guide
using components, appliances, and systems that
CE labeled under the EMC directive.
are
3.The frequency converter is sold as part of a
complete system. The system is being marketed
as complete and could for example, be an airconditioning system. The complete system must
be CE labeled in accordance with the EMC
directive. The manufacturer can ensure CE
labeling under the EMC directive either by using
CE labeled components or by testing the EMC of
the system. If only CE labeled components are
chosen, the entire system does not have to be
tested.
2.4.3 Danfoss Frequency Converter and CE
Labeling
CE labeling is a positive feature when used for its original
purpose,
However, CE labeling may cover many different specifications. Check what a given CE label specifically covers.
The covered specifications can be very different and a CE
label may therefore give the installer a false feeling of
security when using a frequency converter as a component
in a system or an appliance.
Danfoss CE labels the frequency converters in accordance
with the low-voltage directive. This means that if the
frequency converter is installed correctly, Danfoss
guarantees compliance with the low-voltage directive.
Danfoss issues a declaration of conformity that confirms
our CE labeling in accordance with the low-voltage
directive.
The CE label also applies to the EMC directive provided
that the instructions for EMC-correct installation and
filtering are followed. On this basis, a declaration of
conformity in accordance with the EMC directive is issued.
The Design Guide offers detailed instructions for installation to ensure EMC-correct installation. Furthermore,
Danfoss specifies which our different products comply
with.
that is, to facilitate trade within the EU and EFTA.
2.4.4 Compliance with EMC Directive
89/336/EEC
As mentioned, the frequency converter is mostly used by
professionals
forming part of a larger appliance, system, or installation.
Not that the responsibility for the final EMC properties of
the appliance, system or installation rests with the installer.
As an aid to the installer, Danfoss has prepared EMC installation guidelines for the Power Drive system. The standards
and test levels stated for Power Drive systems are
complied with, if the EMC-correct instructions for installation are followed.
The frequency converter has been designed to meet the
IEC/EN 60068-2-3 standard, EN 50178 9.4.2.2 at 50 °C.
of the trade as a complex component
2.5 Aggressive Environments
A frequency converter contains many mechanical and
electronic
to environmental effects.
components. All are to some extent vulnerable
CAUTION
The frequency converter should not be installed in
environments
capable of affecting and damaging the electronic
components. Failure to take the necessary protective
measures increases the risk of stoppages, thus reducing
the life of the frequency converter.
Liquids can be carried through the air and condense in the
frequency
components and metal parts. Steam, oil, and salt water
may cause corrosion of components and metal parts. In
such environments, use equipment with enclosure rating
IP54. As an extra protection, coated printed circuit boards
can be ordered as an option. (Standard on some power
sizes.)
Airborne particles such as dust may cause mechanical,
electrical, or thermal failure in the frequency converter. A
typical indicator of excessive levels of airborne particles is
dust particles around the frequency converter fan. In dusty
environments, use equipment with enclosure rating IP54 or
a cabinet for IP20/TYPE 1 equipment.
with airborne liquids, particles, or gases
converter and may cause corrosion of
22
Danfoss provides other types of assistance that can help to
obtain the best EMC result.
MG02K302 - Rev. 2013-12-0311
In environments with high temperatures and humidity,
corrosive gases such as sulphur, nitrogen, and chlorine
compounds causes chemical processes on the frequency
converter components.
Such chemical reactions rapidly affects and damages the
electronic components. In such environments, mount the
equipment in a cabinet with fresh air ventilation, keeping
aggressive gases away from the frequency converter.
SYSTEM CURVE
FAN CURVE
PRESSURE%
130BA780.10
A
B
C
0
20
40
60
80
100
120
20406080100 120 140 160 180
VOLUME%
120
100
80
60
40
20
0
20406080 100120 140 160 180
120
100
80
60
40
20
020406080100 120 140 160 180
Voume %
Voume %
INPUT POWER %PRESSURE %
SYSTEM CURVE
FAN CURVE
A
B
C
130BA781.10
ENERGY
CONSUMED
Safety and Conformity
VLT® Micro Drive FC 51 Design Guide
An extra protection in such areas is a coating of the
circuit boards, which can be ordered as an option.
printed
2.7.2 The Clear Advantage - Energy Savings
The clear advantage of using a frequency converter for
22
NOTICE
Mounting frequency converters in aggressive
environments
increases the risk of stoppages and consid-
erably reduces the life of the frequency converter.
controlling
electricity savings.
When comparing with alternative control systems and
technologies, a frequency converter is the optimum energy
control system for controlling fan and pump systems.
the speed of fans or pumps lies in the
Before installing the frequency converter, check the
ambient
air for liquids, particles, and gases. This is done by
observing existing installations in this environment. Typical
indicators of harmful airborne liquids are water or oil on
metal parts, or corrosion of metal parts.
Excessive dust particle levels are often found on installation cabinets and existing electrical installations. One
indicator of aggressive airborne gases is blackening of
copper rails and cable ends on existing installations.
2.6 Vibration and Shock
The frequency converter has been tested according to the
procedure
based on the shown standards, Table 2.3
Vibration and shock
Illustration 2.1 Fan Curves (A, B, and C) for Reduced Fan
Volumes
The frequency converter complies with requirements that
exist for units mounted on the walls and floors of
production premises, as well as in panels bolted to walls or
floors.
IEC/EN 60068-2-6Vibration (sinusoidal) - 1970
IEC/EN 60068-2-64Vibration, broad-band random
Table 2.3 Standards
2.7 Advantages
2.7.1 Why use a Frequency Converter for
Controlling
A frequency converter takes advantage of the fact that
centrifugal
tionality for such fans and pumps. For further information
see chapter 2.7.3 Example of Energy Savings.
fans and pumps follow the laws of propor-
Fans and Pumps?
12MG02K302 - Rev. 2013-12-03
Illustration 2.2 When using a frequency converter to reduce
capacity to 60% - more than 50% energy savings may be
fan
obtained in typical applications.
n
100%
50%
25%
12,5%
50%100%
80%
80%
175HA208.10
Power ~n
3
Pressure ~n
2
Flow ~n
130BA782.10
Discharge
damper
Less energy savings
IGV
Costlier installation
Maximum energy savings
130BA779.11
060060060
0
20
40
60
80
100
Discharge Damper Solution
IGV Solution
VLT Solution
Energy consumed
Energy consumed
Energy consumed
Input power %
Volume %
Safety and Conformity
VLT® Micro Drive FC 51 Design Guide
2.7.3 Example of Energy Savings
As shown in Illustration
changing the RPM. By reducing the speed only 20% from
the rated speed, the flow is also reduced by 20%. This is
because the flow is directly proportional to the RPM. The
consumption of electricity, however, is reduced by 50%.
If the system in question only needs to be able to supply a
flow that corresponds to 100% a few days in a year, while
the average is below 80% of the rated flow for the
remainder of the year, the amount of energy saved is even
more than 50%.
Illustration 2.3 describes the dependence of flow, pressure
and power consumption on RPM.
2.3, the flow is controlled by
Illustration 2.5
shows typical energy savings obtainable
with 3 well-known solutions when fan volume is reduced
to i.e. 60%.
As the graph shows, more than 50% energy savings can be
achieved in typical applications.
22
Illustration 2.3 Laws of Proportionally
Q
n
1
1
:
:
=
Q
n
2
2
:
H
H
P
1
=
P
2
2
n
1
1
=
n
2
2
3
n
1
n
2
Flow
Pressure
Power
Q=FlowP=Power
Q1=Rated
flowP1=Rated power
Q2=Reduced flowP2=Reduced power
H=Pressuren=Speed regulation
H1=Rated
H2=Reduced
pressuren1=Rated speed
pressuren2=Reduced speed
Table 2.4 The Laws of Proportionality
2.7.4 Comparison of Energy Savings
The Danfoss frequency converter solution offers major
savings
compared with traditional energy saving solutions.
This is because the frequency converter is able to control
fan speed according to thermal load on the system and
the fact that the frequency converter has a built-in facility
that enables the frequency converter to function as a
Building Management System, BMS.
Illustration 2.4 The 3 Common Energy Saving Systems
Illustration 2.5 Energy Savings
Discharge dampers reduce power consumption. Inlet Guide
offer a 40% reduction, but are expensive to install.
Vans
The Danfoss frequency converter solution reduces energy
consumption with more than 50% and is easy to install.
MG02K302 - Rev. 2013-12-0313
175HA209.11
60
50
40
30
20
10
H
s
0100200300400
(mwg)
B
C
A
750rpm
1050rpm
1350rpm
1650rpm
0
10
20
30
(kW)
40
50
60
200100300
(
m3 /h
)
(
m3 /h
)
400
750rpm
1050rpm
1350rpm
1650rpm
P
shaft
C
1
B
1
A
1
Safety and Conformity
VLT® Micro Drive FC 51 Design Guide
2.7.5 Example with Varying Flow over 1
Year
22
This example is calculated based on pump characteristics
obtained
from a pump datasheet.
The result obtained shows energy savings in excess of 50%
at the given flow distribution over a year. The pay back
period depends on the price per kWh and price of
frequency converter. In this example it is less than a year
when compared with valves and constant speed.
If a frequency converter is used for controlling the flow or
pressure
of a system, improved control is obtained.
A frequency converter can vary the speed of the fan or
pump, obtaining variable control of flow and pressure.
Furthermore, a frequency converter can quickly adapt the
speed of the fan or pump to new flow or pressure
conditions in the system.
Simple control of process (Flow, Level or Pressure) utilising
the built-in PI control.
2.7.7 Star/Delta Starter or Soft-starter not
Required
When larger motors are started, it is necessary in many
countries
In more traditional systems, a star/delta starter or softstarter is widely used. Such motor starters are not required
if a frequency converter is used.
As illustrated in Illustration 2.8, a frequency converter does
not consume more than rated current.
to use equipment that limits the start-up current.
2.7.8 Using a Frequency Converter Saves
Money
Example chapter
that a lot of equipment is not required when a frequency
converter is used. It is possible to calculate the cost of
installing the 2 different systems. In the example, the 2
systems can be established at roughly the same price.
2.7.9 Without a Frequency Converter shows
22
1
2Star/delta starter
3Soft-starter
4Start directly on mains
Illustration 2.8 Current
VLT®
Micro Drive
MG02K302 - Rev. 2013-12-0315
M
-+
M
M
x6x6
x6
175HA205.12
Valve
position
Starter
Fuses
LV
supply
P.F.C
Flow
3-Port
valve
Bypass
Return
Control
Supply
air
V.A.V
outlets
Duct
P.F.C
Mains
Fuses
Starter
Bypass
supply
LV
Return
valve
3-Port
Flow
Control
Valve
position
Starter
Power
Factor
Correction
Mains
IGV
Mechanical
linkage
and vanes
Fan
Motor
or
actuator
Main
B.M.S
Local
D.D.C.
control
Sensors
PT
Pressure
control
signal
0/10V
Temperature
control
signal
0/10V
Control
Mains
Cooling sectionHeating section
Fan sectionInlet guide vane
PumpPump
Safety and Conformity
VLT® Micro Drive FC 51 Design Guide
2.7.9 Without a Frequency Converter
22
D.D.C.Direct Digital Control
E.M.S.Energy Management system
V.A.V.Variable Air Volume
Sensor PPressure
Sensor TTemperature
Table 2.6 Abbreviations used in Illustration 2.9
Illustration 2.9 Traditional Fan System
16MG02K302 - Rev. 2013-12-03
175HA206.11
Pump
Flow
Return
Supply
air
V.A.V
outlets
Duct
Mains
Pump
Return
Flow
Mains
Fan
Main
B.M.S
Local
D.D.C.
control
Sensors
Mains
Cooling sectionHeating section
Fan section
Pressure
control
0-10V
or
0/4-20mA
Control
temperature
0-10V
or
0/4-20mA
Control
temperature
0-10V
or
0/4-20mA
VLT
M
-+
VLT
M
M
PT
VLT
x3x3
x3
Safety and Conformity
2.7.10 With a Frequency Converter
D.D.C.Direct Digital Control
E.M.S.Energy Management system
V.A.V.Variable Air Volume
Sensor P Pressure
Sensor T Temperature
VLT® Micro Drive FC 51 Design Guide
22
Table 2.7 Abbreviations used in Illustration
2.10
Illustration 2.10 Fan System Controlled by Frequency
Converters
MG02K302 - Rev. 2013-12-0317
130BB892.10
100%
0%
-100%
100%
Local
reference
scaled to
Hz
Auto mode
Hand mode
LCP Hand on,
off and auto
on keys
Local
Remote
Reference
Ramp
P 4-10
Motor speed
direction
To motor
control
Reference
handling
Remote
reference
P 4-14
Motor speed
high limit [Hz]
P 4-12
Motor speed
low limit [Hz]
P 3-4* Ramp 1
P 3-5* Ramp 2
Hand
On
Off
Reset
Auto
On
130BB893.10
Product Overview
3 Product Overview
3.1 Control Structures
VLT® Micro Drive FC 51 Design Guide
33
Select open loop or closed loop in 1-00
Configuration Mode.
3.1.1 Control Structure Open Loop
Illustration 3.1 Open Loop Structure
In the configuration shown in Illustration 3.1, 1-00 Configuration Mode is set to [0] Open loop. The resulting reference
from the reference handling system or the local reference
is received and fed through the ramp limitation and speed
limitation before being sent to the motor control. The
output from the motor control is then limited by the
maximum frequency limit.
After pressing the [Auto On] key, the frequency converter
into auto mode and follows (as default) the remote
goes
reference. In this mode, it is possible to control the
frequency converter via the digital inputs and RS-485. See
more about starting, stopping, changing ramps and
parameter set-ups etc. in parameter group 5-1* DigitalInputs or parameter group 8-5* Serial Communication.
3.1.2 Local (Hand On) and Remote (Auto
Control
On)
The frequency converter can be operated manually via the
local
control panel (LCP) or remotely via analog/digital
inputs or serial bus. If allowed in 0-40 [Hand on] Key on
LCP, 0-44 [Off/Reset] Key on LCP, and 0-42 [Auto on] Key on
LCP, it is possible to start and stop the frequency converter
by LCP pressing the [Hand On] and [Off/Reset] keys. Alarms
can be reset via the [Off/Reset] key. After pressing the
[Hand On] key, the frequency converter goes into hand
mode and follows (as default) the local reference set by
using the LCP potentiometer (LCP 12) or [▲]/[▼] (LCP 11).
The potentiometer can be disabled by parameter 6-80 LCPPotmeter Enable. If the potentiometer is disabled, use the
navigation keys for adjusting reference.
18MG02K302 - Rev. 2013-12-03
Illustration 3.2 LCP Control Keys
Local reference forces the configuration mode to open
independent on the setting of 1-00 Configuration
loop,
Mode.
Local reference is restored at power-down.
7-30 PI
Normal/Inverse
Control
PI
Reference
Feedback
Scale to
speed
P 4-10
Motor speed
direction
To motor
control
130BB894.11
S
100%
0%
-100%
100%
*[-1]
_
+
Product Overview
VLT® Micro Drive FC 51 Design Guide
3.1.3 Control Structure Closed Loop
The internal controller allows the frequency converter to become an integral part of the controlled system. The frequency
converter
value and determines the error, if any, between these 2 signals. It then adjusts the speed of the motor to correct this error.
receives a feedback signal from a sensor in the system. It then compares this feedback to a set-point reference
For example, consider a pump application where the speed of a pump is to be controlled so that the static pressure in a
pipe is constant. The desired static pressure value is supplied to the frequency converter as the set-point reference. A static
pressure sensor measures the actual static pressure in the pipe and supplies this to the frequency converter as a feedback
signal. If the feedback signal is greater than the set-point reference, the frequency converter slows down to reduce the
pressure. In a similar way, if the pipe pressure is lower than the set-point reference, the frequency converter automatically
speed up to increase the pressure provided by the pump.
Illustration 3.3 Control Structure Closed Loop
While the default values for the frequency converter’s closed loop controller often provides satisfactory performance, the
control
of the system can often be optimised by adjusting some of the closed loop controller’s parameters.
Up to 8 preset references can be programmed in the frequency converter. The active preset reference can be selected using
External references (analog inputs and serial communication bus references)
•
The preset relative reference
•
Feedback controlled setpoint
•
digital inputs or the serial communications bus. The reference can also be supplied externally, most commonly from an
analog input. This external source is selected by one of the 3 Reference Source parameters (3-15 Reference 1 Source,
3-16 Reference 2 Source and 3-17 Reference 3 Source). All reference resources and the bus reference are added to produce the
total external reference. The external reference, the preset reference or the sum of the 2 can be selected to be the active
reference. Finally, this reference can by be scaled using 3-14 Preset Relative Reference.
20MG02K302 - Rev. 2013-12-03
1
2
z
z
z
L1
L2
L3
PE
U
V
W
C
S
I
2
I
1
I
3
I
4
C
S
C
S
C
S
C
S
I
4
C
S
z
PE
3
4
5
6
175ZA062.12
Product Overview
VLT® Micro Drive FC 51 Design Guide
The scaled reference is calculated as follows:
Reference
= X + X ×
100
Y
Where X is the external reference, the preset reference or the sum of these and Y is 3-14 Preset Relative Reference in [%].
If Y, 3-14 Preset Relative Reference, is set to 0%, the reference is not affected by the scaling.
3.2 General Aspects of EMC
Electrical interference is usually conducted at frequencies in the range 150 kHz to 30 MHz. Airborne interference from the
frequency
As shown in Illustration 3.5, capacitance in the motor cable coupled with a high dU/dt from the motor voltage generate
leakage currents.
The use of a screened motor cable increases the leakage current (see Illustration 3.5) because screened cables have higher
capacitance to ground than unscreened cables. If the leakage current is not filtered, it causes greater interference on the
mains in the radio frequency range below approximately 5 MHz. Since the leakage current (I1) is carried back to the unit
through the screen (I3), there is in principle only a small electro-magnetic field (I4) from the screened motor cable according
to Illustration 3.5.
The screen reduces the radiated interference, but increases the low-frequency interference on the mains. Connect the motor
cable screen to the frequency converter enclosure as well as on the motor enclosure. This is best done by using integrated
screen clamps so as to avoid twisted screen ends (pigtails). Pigtails increase the screen impedance at higher frequencies,
which reduces the screen effect and increases the leakage current (I4).
If a screened cable is used for relay, control cable, signal interface and brake, mount the screen on the enclosure at both
ends. In some situations, however, it is necessary to break the screen to avoid current loops.
converter system in the range 30 MHz to 1 GHz is generated from the inverter, motor cable, and the motor.
33
1Ground wire4Frequency converter
2Screen5Screened motor cable
3AC mains supply6Motor
Illustration 3.5 Situation that Generates Leakage Currents
If the screen is to be placed on a mounting plate for the frequency converter, the mounting plate must be made of metal,
convey the screen currents back to the unit. Moreover, ensure good electrical contact from the mounting plate through
to
the mounting screws to the frequency converter chassis.
When unscreened cables are used, some emission requirements are not complied with, although most immunity
requirements are observed.
MG02K302 - Rev. 2013-12-0321
Product Overview
VLT® Micro Drive FC 51 Design Guide
To reduce the interference level from the entire system (unit+installation), make motor and brake cables as short as
possible.
Avoid placing cables with a sensitive signal level alongside motor and brake cables. Radio interference higher than
50 MHz (airborne) is especially generated by the control electronics.
3.2.1 Emission Requirements
33
The EMC product standard for frequency converters
defines
4 categories (C1, C2, C3 and C4) with specified
requirements for emission and immunity. Table 3.1 states
the definition of the 4 categories and the equivalent classification from EN 55011.
Equivalent
Category Definition
emission
in EN
class
55011
C1Frequency converters installed in
first environment (home and
the
office) with a supply voltage less
than 1000 V.
C2Frequency converters installed in
first environment (home and
the
office) with a supply voltage less
than 1000 V, which are neither
plug-in nor movable and are
intended to be installed and
commissioned by a professional.
C3Frequency converters installed in
second environment
the
(industrial) with a supply voltage
lower than 1000 V.
C4Frequency converters installed in
second environment with a
the
supply voltage equal to or above
1000 V or rated current equal to or
above 400 A or intended for use in
complex systems.
Class B
Class A Group 1
Class A Group 2
No limit line.
An EMC plan
should be
made.
When the generic (conducted) emission standards are
used,
the frequency converters are required to comply
with the limits in Table 3.2.
Environment
First
environment
and
(home
office)
Second
environment
(industrial
environment)
Table 3.2 Correlation between Generic Emission Standards and
55011
EN
Generic emission
standard
EN/IEC 61000-6-3 Emission
standard for residential,
commercial and light
industrial environments.
EN/IEC 61000-6-4 Emission
standard
environments.
for industrial
Equivalent
emission
class
in EN 55011
Class B
Class A Group 1
Table 3.1 Correlation between IEC 61800-3 and EN 55011
22MG02K302 - Rev. 2013-12-03
Product Overview
VLT® Micro Drive FC 51 Design Guide
3.2.2 EMC Test Results (Emission)
Drive typeConducted emission. Maximum shielded cable length [m]Radiated emission
Housing, trades and
light
industries
Without
external
filter
With
external
filter
Without
external
filter
Industrial environment
With
external
filter
Without
external
filter
≤2.2 kW.
Single
230 V
phase,
≤7.5 kW. Up
500 V AC,
to
3 phase
11 kW to 22
Up to
kW.
500 V AC, 3
phase
Table 3.3 EMC Test Result
EN 55011 Class A2EN 55011 Class A1EN 55011 Class BEN 55011 Class A2EN 55011 Class A1
Without
external
filter
25-1550515Yes-NoYes
25-1550-15Yes-NoYes
25-1550-15Yes-NoYes
Industrial environment
With
external
filter
Without
external
filter
With
external
filter
With
external
filter
33
3.2.3 Harmonics Emission Requirements
Equipment connected to the public supply network
WARNING
Cannot comply, only with power option
OptionsDefinition
1IEC/EN 61000-3-2 Class A for 3-phase balanced
equipment
kW total power).
2IEC/EN 61000-3-12 Equipment 16 A-75 A and profes-
sional
current.
Table 3.4 Harmonics Emission Requirements
3.2.4 Immunity Requirements
The immunity requirements for frequency converters
depend
on the environment where they are installed. The
requirements for the industrial environment are higher
than the requirements for the home and office
environment. All Danfoss frequency converters comply
with the requirements for the industrial environment and
consequently comply also with the lower requirements for
home and office environment with a large safety margin.
(for professional equipment only up to 1
equipment as from 1 kW up to 16 A phase
3.3 Galvanic Isolation (PELV)
3.3.1 PELV - Protective Extra Low Voltage
PELV offers protection by way of extra low voltage.
Protection
electrical supply is of the PELV type and the installation is
made as described in local/national regulations on PELV
supplies.
All control terminals and relay terminals 01-03/04-06
comply with PELV (Protective Extra Low Voltage) (Does not
apply to grounded Delta leg above 440 V).
Galvanic (ensured) isolation is obtained by fulfilling
requirements for higher isolation and by providing the
relevant creapage/clearance distances. These requirements
are described in the EN 61800-5-1 standard.
The components that make up the electrical isolation, as
described, also comply with the requirements for higher
isolation and the relevant test as described in EN
61800-5-1.
The PELV galvanic isolation can be shown in Illustration 3.7.
against electric shock is ensured when the
To maintain PELV all connections made to the control
terminals must be PELV, e.g. thermistor must be
reinforced/double insulated.
MG02K302 - Rev. 2013-12-0323
SMPS
130BB896.10
1
2
3
a
M
130BB901.10
1324
5
a
M
Product Overview
VLT® Micro Drive FC 51 Design Guide
0.25-22 kW
3.4 Earth Leakage Current
WARNING
DISCHARGE TIME
Touching
33
the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been
disconnected, such as load sharing (linkage of DC
intermediate circuit), as well as the motor connection for
kinetic back-up.
Before touching any electrical parts, wait at least the
amount of time indicated in Table 2.1.
Shorter time is allowed only if indicated on the
1 Power supply (SMPS)
2 Optocouplers, communication between AOC and BOC
3 Custom relays
a Control card terminals
nameplate for the specific unit.
NOTICE
Leakage Current
Illustration 3.6 Galvanic Isolation
The
exceeds 3.5 mA. To ensure that the ground cable has a
good mechanical connection to the ground connection,
30-90 kW
the cable cross section must be at least 10 mm2 Cu or 16
mm2 Al or 2 rated earth wires terminated separately.
Residual Current Device protection RCD
This product can cause a DC current in the protective
conductor. Where a residual current device (RCD) is used
for protection in case of direct or indirect contact, only
an RCD of Type B is allowed on the supply side of this
product. Otherwise, another protective measure shall be
applied, such as separation from the environment by
double or reinforced insulation, or isolation from the
supply system by a transformer. See also Application
Note Protection against Electrical Hazards, MN90G.
Protective earthing of the frequency converter and the
1 Power supply (SMPS) incl. signal isolation of UDC, indicating
the
intermediate current voltage
2 Gate drive that runs the IGBTs (trigger transformers/opto-
couplers)
3 Current transducers
4 Internal soft-charge, RFI and temperature measurement
circuits
5 Custom relays
a Control card terminals
use of RCDs must always follow national and local
regulations.
3.5 Extreme Running Conditions
Short circuit (motor phase – phase)
Current
the DC-link, protects the frequency converter against short
circuts. A short circuit between 2 output phases causes an
overcurrent in the inverter. The inverter is turned off
Illustration 3.7 Galvanic Isolation
individually when the short circuit current exceeds the
permitted value (Alarm 16 Trip Lock).
For information about protecting the frequency converter
The functional galvanic isolation (see Illustration
the RS-485 standard bus interface.
3.6) is for
against a short circuit at the load sharing and brake
outputs, see the design guidelines.
Switching on the output
Switching on the output between the motor and the
CAUTION
Installation at high altitude:
At
altitudes above 2,000 m, contact Danfoss regarding
PELV.
frequency converter is fully permitted. The frequency
converter is not damaged in any way by switching on the
output. However, fault messages may appear.
the electrical parts could be fatal - even after
earth leakage current from the frequency converter
measurement in each of the 3 motor phases or in
24MG02K302 - Rev. 2013-12-03
1.21.01.4
30
10
20
100
60
40
50
1.81.62.0
2000
500
200
400
300
1000
600
t [s]
175ZA052.12
f
OUT
= 2 x f
M,N
f
OUT
= 0.2 x f
M,N
f
OUT
= 1 x f
M,N
(par. 1-23)
IMN(par. 1-24)
I
M
Product Overview
VLT® Micro Drive FC 51 Design Guide
Motor-generated over-voltage
voltage in the intermediate circuit is increased when
The
the motor acts as a generator. This occurs in following
cases:
The load drives the motor (at constant output
•
frequency from the frequency converter), that is
the load generates energy.
During deceleration ("ramp-down") if the moment
•
of inertia is high, the friction is low and the rampdown time is too short for the energy to be
dissipated as a loss in the frequency converter,
the motor and the installation.
Incorrect slip compensation setting (1-62 Slip
•
Compensation) may cause higher DC link voltage.
The control unit may attempt to correct the ramp if
possible (2-17 Over-voltage Control.)
The inverter turns off to protect the transistors and the
intermediate circuit capacitors when a certain voltage level
is reached.
Mains drop-out
During a mains drop-out, the frequency converter keeps
running until the intermediate circuit voltage drops below
the minimum stop level, which is typically 15% below the
frequency converter's lowest rated supply voltage. The
mains voltage before the drop-out and the motor load
determines how long it takes for the frequency converter
to coast.
3.5.1 Motor Thermal Protection
Motor thermal protection can be provided in 2 ways.
Illustration 3.8 ETR Characteristics
The
X-axis shows the ratio between I
motor
and I
motor
nominal. The Y- axis shows the time in seconds before the
ETR cut of and trips the frequency converter. The curves
show the characteristic nominal speed, at twice the
nominal speed and at 0,2 x the nominal speed.
At lower speed, the ETR cuts off at lower heat due to less
cooling of the motor. In that way, the motor is protected
from being over heated even at low speed. The ETR
feature is calculating the motor temperature based on
actual current and speed. The calculated temperature is
visible as a read out parameter in 16-18 Motor Thermal in
the product specific Programming Guide.
A special version of the ETR is also available for EX-e
motors in ATEX areas. This function makes it possible to
enter a specific curve to protect the Ex-e motor. The
Programming Guide takes the user through the set-up.
33
method uses a motor thermistor, via one of the
One
following
Thermistor input on a standard AI
•
Sensor input MCB 114
•
PTC Thermistor input MCB 112
•
The frequency converter monitors motor temperature as
the speed and load vary to detect overheating conditions.
The other method calculates motor temperature by
measuring current, frequency, and operating time. The
converter displays the thermal load on the motor in
percentage and can issue a warning at a programmable
overload setpoint. Programmable options at the overload
allow the frequency converter to stop the motor, reduce
output, or ignore the condition. Even at low speeds, the
frequency converter meets I2t Class 20 electronic motor
overload standards.
This method is called Electronic Thermal Relay (ETR).
MG02K302 - Rev. 2013-12-0325
Selection
4 Selection
4.1 Options and Accessories
VLT® Micro Drive FC 51 Design Guide
4.1.1 Local Control Panel (LCP)
®
For detailed information on programming, see VLT
44
Drive FC 51Programming Guide.
Micro
NOTICE
The frequency converter can also be programmed from a
PC
via RS-485 com-port by installing the MCT 10 Set-up
Software.
This software can either be ordered using code number
130B1000 or downloaded from the DanfossWeb site:
navigation structure.
[▲] [▼]: For maneuvering between parameter groups,
parameters and within parameters.
[OK]: For selecting a parameter and for accepting changes
to parameter settings.
Operation Keys:
A yellow light above the operation keys indicates the
active key.
[Hand On]: Starts the motor and enables control of the
frequency converter via the LCP.
[Off/Reset]: Stops the motor (off). If in alarm mode the
alarm is reset.
[Auto On]: The frequency converter is controlled either via
control terminals or serial communication.
[Potentiometer] (LCP 12): The potentiometer works in 2
ways depending on the mode in which the frequency
converter is running.
In Auto Mode the potentiometer acts as an extra
programmable analog input.
In Hand on Mode the potentiometer controls local
reference.
Illustration 4.1 Description of LCP Keys and Display
Press [Menu] to select one of the following menus:
Status:
For
readouts only.
Quick Menu:
For access to Quick Menus 1 and 2.
Main Menu:
For access to all parameters.
4.1.2 Remote Mounting Kit for LCP
The LCP can be moved to the front of a cabinet by using
remote built-in kit. The enclosure is IP55.
the
EnclosureIP55 front
Max. cable length between LCP and unit:3 m
Communication std:RS-485
Ordering no.132B0102
Table 4.1 Technical Data
26MG02K302 - Rev. 2013-12-03
130BA526.10
62.3±0.2
82.8±0.2
4xR 1.5±0.5
1
130BA568.10
1
2
3
130BA527.10
Selection
VLT® Micro Drive FC 51 Design Guide
4.1.3 FC 51 LCP Mounting Instruction
Step 1
the bottom of the LCP in the frequency converter.
Place
Illustration 4.2 Place the LCP in the Frequency Converter
Step 2
the top of the LCP into the frequency converter.
Push
4.1.4 FC 51 Remote Mounting Kit Mounting
Instruction
Step 1
Fit
gasket on LCP in the frequency converter.
Illustration 4.4 Fit Gasket on LCP
Step 2
LCP on panel - see dimensions of hole on drawing.
Place
44
Illustration 4.3 Push the Top of the LCP into Place
Illustration 4.5 Dimensions of Hole
Illustration 4.6 Panel, Gasket and LCP
MG02K302 - Rev. 2013-12-0327
Loading...
+ 65 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.