Copyright, Limitation of Liability and Revision Rights5
Symbols6
Abbreviations7
Definitions7
2 Introduction to VLT Automation VT Drive
CE labelling17
Vibration and shock19
Control Structures24
General aspects of EMC34
Immunity Requirements38
Galvanic isolation (PELV)39
PELV - Protective Extra Low Voltage39
Earth leakage current40
Control with Brake Function41
Control with Brake Function42
Mechanical Brake Control42
Extreme Running Conditions42
Safe Stop Operation (Optional)47
5
15
3 VLT Automation VT Drive Selection
General Specifications49
Efficiency65
Special Conditions72
Options and Accessories77
General Description89
High Power Options95
Installation of Duct Cooling Kit in Rittal Enclosures95
Outside Installation/ NEMA 3R Kit for Rittal Enclosures98
Installation on Pedestal99
Input Plate Option102
Installation of Mains Shield for Frequency Converters103
Frame size F Panel Options104
4 How to Order
Ordering Form107
Type Code String108
49
107
MG.20.X1.22 - VLTp is a registered Danfoss trademark
1
ContentsAutomation VT Drive FC322 Design Guide
Ordering Numbers111
5 How to Install
Mechanical Installation125
Pre-installation131
Planning the Installation Site131
Receiving the Frequency Converter
Transportation and Unpacking131
Lifting132
Cooling and Airflow136
Electrical Installation140
Connections - Frame sizes D, E and F156
Power Connections156
Disconnectors, Circuit Breakers and Contactors170
Final Set-Up and Test171
Safe Stop Installation173
Safe Stop Commissioning Test174
Additional Connections176
Installation of Misc. Connections179
Safety181
EMC-correct Installation182
Residual Current Device186
125
131
6 Application Examples
Potentiometer Reference188
Automatic Motor Adaptation (AMA)188
SLC Application Example189
System Status and Operation192
Cascade Controller Wiring Diagram
Fixed Variable Speed Pump Wiring Diagram194
Lead Pump Alternation Wiring Diagram194
7 RS-485 Installation and Set-up
RS-485 Installation and Set-up197
FC Protocol Overview199
Network Configuration201
FC Protocol Message Framing Structure201
Examples209
Modbus RTU Overview210
187
193
197
2
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Automation VT Drive FC322 Design GuideContents
VLT Automation VT Drive with Modbus RTU210
Modbus RTU Message Framing Structure211
How to Access Parameters216
Examples217
Danfoss FC Control Profile222
8 Troubleshooting
231
MG.20.X1.22 - VLTp is a registered Danfoss trademark
3
1
1 How to Read this Design GuideAutomation VT Drive FC322 Design Guide
4
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Automation VT Drive FC322 Design Guide1 How to Read this Design Guide
1 How to Read this Design Guide
1
1.1.1 Copyright, Limitation of Liability and Revision Rights
This publication contains information proprietary to Danfoss. By accepting and using this manual the user agrees that the information contained herein
will be used solely for operating equipment from Danfoss or equipment from other vendors provided that such equipment is intended for communication
with Danfoss equipment over a serial communication link. This publication is protected under the Copyright laws of Denmark and most other countries.
Danfoss does not warrant that a software program produced according to the guidelines provided in this manual will function properly in every physical,
hardware or software environment.
Although Danfoss has tested and reviewed the documentation within this manual, Danfoss makes no warranty or representation, neither expressed nor
implied, with respect to this documentation, including its quality, performance, or fitness for a particular purpose.
In no event shall Danfoss be liable for direct, indirect, special, incidental, or consequential damages arising out of the use, or the inability to use information
contained in this manual, even if advised of the possibility of such damages. In particular, Danfoss is not responsible for any costs, including but not
limited to those incurred as a result of lost profits or revenue, loss or damage of equipment, loss of computer programs, loss of data, the costs to substitute
these, or any claims by third parties.
Danfoss reserves the right to revise this publication at any time and to make changes to its contents without prior notice or any obligation to notify former
MG.20.X1.22 - VLTp is a registered Danfoss trademark
5
1
1 How to Read this Design GuideAutomation VT Drive FC322 Design Guide
1.1.3 Symbols
Symbols used in this guide.
NB!
Indicates something to be noted by the reader.
Indicates a general warning.
Indicates a high-voltage warning.
Indicates default setting
6
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Automation VT Drive FC322 Design Guide1 How to Read this Design Guide
1.1.4 Abbreviations
Alternating currentAC
American wire gaugeAWG
Ampere/AMPA
Automatic Motor AdaptationAMA
Current limitI
Degrees Celsius°C
Direct currentDC
Drive DependentD-TYPE
Electro Magnetic CompatibilityEMC
Electronic Thermal RelayETR
DriveFC
Gramg
HertzHz
KilohertzkHz
Local Control PanelLCP
Meterm
Millihenry InductancemH
MilliamperemA
Millisecondms
Minutemin
Motion Control ToolMCT
NanofaradnF
Newton MetersNm
Nominal motor currentI
Nominal motor frequencyf
Nominal motor powerP
Nominal motor voltageU
Parameterpar.
Protective Extra Low VoltagePELV
Printed Circuit BoardPCB
Rated Inverter Output CurrentI
Revolutions Per MinuteRPM
Regenerative terminalsRegen
Seconds
Synchronous Motor Speedn
Torque limitT
VoltsV
I
VLT,MAX
I
VLT,N
LIM
M,N
M,N
M,N
M,N
INV
s
LIM
The maximum output current
The rated output current supplied by the frequency converter
1
1.1.5 Definitions
Drive:
I
VLT,MAX
The maximum output current.
I
VLT,N
The rated output current supplied by the frequency converter.
U
VLT, MAX
The maximum output voltage.
MG.20.X1.22 - VLTp is a registered Danfoss trademark
7
1
1 How to Read this Design GuideAutomation VT Drive FC322 Design Guide
Input:
Control command
You can start and stop the connected motor by means of
LCP and the digital inputs.
Functions are divided into two groups.
Functions in group 1 have higher priority than functions in
group 2.
Motor:
f
JOG
The motor frequency when the jog function is activated (via digital terminals).
f
M
The motor frequency.
f
MAX
The maximum motor frequency.
f
MIN
The minimum motor frequency.
f
M,N
The rated motor frequency (nameplate data).
I
M
The motor current.
I
M,N
The rated motor current (nameplate data).
n
M,N
The rated motor speed (nameplate data).
P
M,N
The rated motor power (nameplate data).
T
M,N
The rated torque (motor).
U
M
The instantaneous motor voltage.
U
M,N
The rated motor voltage (nameplate data).
Group 1Reset, Coasting stop, Reset and Coasting stop, Quick-
stop, DC braking, Stop and the "Off" key.
Group 2Start, Pulse start, Reversing, Start reversing, Jog and
Freeze output
8
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Automation VT Drive FC322 Design Guide1 How to Read this Design Guide
VLT
The efficiency of the frequency converter is defined as the ratio between the power output and the power input.
Start-disable command
A stop command belonging to the group 1 control commands - see this group.
Stop command
See Control commands.
References:
Analog Reference
A signal transmitted to the analog inputs 53 or 54, can be voltage or current.
Bus Reference
A signal transmitted to the serial communication port (FC port).
Preset Reference
A defined preset reference to be set from -100% to +100% of the reference range. Selection of eight preset references via the digital terminals.
Pulse Reference
A pulse frequency signal transmitted to the digital inputs (terminal 29 or 33).
Ref
MAX
Determines the relationship between the reference input at 100% full scale value (typically 10 V, 20mA) and the resulting reference. The maximum
reference value set in par. 3-03.
1
Ref
MIN
Determines the relationship between the reference input at 0% value (typically 0V, 0mA, 4mA) and the resulting reference. The minimum reference value
set in par. 3-02.
Miscellaneous:
Analog Inputs
The analog inputs are used for controlling various functions of the frequency converter.
There are two types of analog inputs:
Current input, 0-20 mA and 4-20 mA
Voltage input, 0-10 V DC.
Analog Outputs
The analog outputs can supply a signal of 0-20 mA, 4-20 mA, or a digital signal.
Automatic Motor Adaptation, AMA
AMA algorithm determines the electrical parameters for the connected motor at standstill.
Brake Resistor
The brake resistor is a module capable of absorbing the brake power generated in regenerative braking. This regenerative braking power increases the
intermediate circuit voltage and a brake chopper ensures that the power is transmitted to the brake resistor.
CT Characteristics
Constant torque characteristics used for positive displacement pumps and blowers.
MG.20.X1.22 - VLTp is a registered Danfoss trademark
9
1
1 How to Read this Design GuideAutomation VT Drive FC322 Design Guide
Digital Inputs
The digital inputs can be used for controlling various functions of the frequency converter.
10
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Automation VT Drive FC322 Design Guide1 How to Read this Design Guide
Digital Outputs
The drive features two Solid State outputs that can supply a 24 V DC (max. 40 mA) signal.
DSP
Digital Signal Processor.
Relay Outputs:
The frequency converter drive features two programmable Relay Outputs.
ETR
Electronic Thermal Relay is a thermal load calculation based on present load and time. Its purpose is to estimate the motor temperature.
GLCP:
Graphical Local Control Panel (LCP102)
Initialising
If initialising is carried out (par. 14-22), the programmable parameters of the frequency converter return to their default set tings.
Intermittent Duty Cycle
An intermittent duty rating refers to a sequence of duty cycles. Each cycle consists of an on-load and an off-load period. The operation can be either
periodic duty or none-periodic duty.
LCP
The Local Control Panel (LCP) makes up a complete interface for control and programming of the frequency converter. The control panel is detachable
and can be installed up to 3 metres from the frequency converter, i.e. in a front panel by means of the installation kit option.
The Local Control Panel is available in two versions:
-Numerical LCP101 (NLCP)
-Graphical LCP102 (GLCP)
lsb
Least significant bit.
1
MCM
Short for Mille Circular Mil, an American measuring unit for cable cross-section. 1 MCM ิ 0.5067 mm
msb
Most significant bit.
NLCP
Numerical Local Control Panel LCP101
On-line/Off-line Parameters
Changes to on-line parameters are activated immediately after the data value is changed. Changes to off-line parameters are not activated until you enter
[OK] on the LCP.
PID Controller
The PID controller maintains the desired speed, pressure, temperature, etc. by adjusting the output frequency to match the varying load.
RCD
Residual Current Device.
MG.20.X1.22 - VLTp is a registered Danfoss trademark
2
.
11
1
1 How to Read this Design GuideAutomation VT Drive FC322 Design Guide
Set-up
You can save parameter settings in four Set-ups. Change between the four parameter Set-ups and edit one Set-up, while another Set-up is active.
12
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Automation VT Drive FC322 Design Guide1 How to Read this Design Guide
SFAVM
Switching pattern called
S tator F lux oriented A synchronous V ector M odulation (par. 14-00).
Slip Compensation
The frequency converter compensates for the motor slip by giving the frequency a supplement that follows the measured motor load keeping the motor
speed almost constant..
Smart Logic Control (SLC)
The SLC is a sequence of user defined actions executed when the associated user defined events are evaluated as true by the SLC.
Thermistor:
A temperature-dependent resistor placed where the temperature is to be monitored (frequency converter or motor).
Trip
A state entered in fault situations, e.g. if the frequency converter is subject to an over-temperature or when the frequency converter is protecting the
motor, process or mechanism. Restart is prevented until the cause of the fault has disappeared and the trip state is cancelled by activating reset or, in
some cases, by being programmed to reset automatically. Trip may not be used for personal safety.
Trip Locked
A state entered in fault situations when the frequency converter is protecting itself and requiring physical intervention, e.g. if the frequency converter is
subject to a short circuit on the output. A locked trip can only be cancelled by cutting off mains, removing the cause of the fault, and reconnecting the
frequency converter. Restart is prevented until the trip state is cancelled by activating reset or, in some cases, by being programmed to reset automatically.
Trip locked may not be used for personal safety.
VT Characteristics
Variable torque characteristics used for pumps and fans.
plus
VVC
If compared with standard voltage/frequency ratio control, Voltage Vector Control (VVC
reference is changed and in relation to the load torque.
plus
) improves the dynamics and the stability, both when the speed
1
60° AVM
Switching pattern called 60°
A synchronous V ector M odulation (par. 14-00).
1.1.6 Power Factor
The power factor is the relation between I1 and I
The power factor for 3-phase control:
The power factor indicates to which extent the frequency converter im-
poses a load on the mains supply.
The lower the power factor, the higher the I
formance.
In addition, a high power factor indicates that the different harmonic currents are low.
The frequency converters' built-in DC coils produce a high power factor, which minimizes the imposed load on the mains supply.
.
RMS
for the same kW per-
RMS
MG.20.X1.22 - VLTp is a registered Danfoss trademark
The voltage of the frequency converter is dangerous whenever connected to mains. Incorrect installation of the motor, frequency
converter or fieldbus may cause damage to the equipment, serious personal injury or death. Consequently, the instructions in this
manual, as well as national and local rules and safety regulations, must be complied with.
Safety Regulations
1. The frequency converter must be disconnected from mains if repair work is to be carried out. Check that the mains supply has been disconnected and
that the necessary time has passed before removing motor and mains plugs.
2. The [STOP/RESET] key on the control panel of the frequency converter does not disconnect the equipment from mains and is thu s not to be used as
a safety switch.
3. Correct protective earthing of the equipment must be established, the user must be protected against supply voltage, and the motor must be protected
against overload in accordance with applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is set by par. 1-90
value) or data value [ETR warning]. Note: The function is initialised at 1.16 x rated motor current and rated motor frequency. For the North American
market: The ETR functions provide class 20 motor overload protection in accordance with NEC.
6. Do not remove the plugs for the motor and mains supply while the frequency converter is connected to mains. Check that the mains supply has been
disconnected and that the necessary time has passed before removing motor and mains plugs.
7. Please note that the frequency converter has more voltage inputs than L1, L2 and L3, when load sharing (linking of DC intermediate circuit) and external
24 V DC have been installed. Check that all voltage inputs have been disconnected and that the necessary time has passed before commencing repair
work.
Installation at High Altitudes
Motor Thermal Protection
. If this function is desired, set par. 1-90 to data value [ETR trip] (default
2
By altitudes above 2 km, please contact Danfoss regarding PELV.
Warning against Unintended Start
1. The motor can be brought to a stop by means of digital commands, bus commands, references or a local stop, while the frequency converter is
connected to mains. If personal safety considerations make it necessary to ensure that no unintended start occurs, these stop functions are not sufficient.
2. While parameters are being changed, the motor may start. Consequently, the stop key [STOP/RESET] must always be activated; following which data
can be modified. 3. A motor that has been stopped may start if faults occur in the electronics of the frequency converter, or if a temporary overload or
a fault in the supply mains or the motor connection ceases.
Warning:
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load sharing (linkage of DC intermediate circuit), as well as
The purpose of CE labelling is to avoid technical trade obstacles within EFTA and the EU. The EU has introduced the CE label as a simple way of showing
whether a product complies with the relevant EU directives. The CE label says nothing about the specifications or quality of the product. Frequency
converters are regulated by three EU directives:
The machinery directive (98/37/EEC)
All machines with critical moving parts are covered by the machinery directive of January 1, 1995. Since a frequency converter is largely electrical, it does
not fall under the machinery directive. However, if a frequency converter is supplied for use in a machine, we provide information on safety aspects
relating to the frequency converter. We do this by means of a manufacturer's declaration.
The low-voltage directive (73/23/EEC)
Frequency converters must be CE labelled in accordance with the low-voltage directive of January 1, 1997. The directive applies to all electrical equipment
and appliances used in the 50 - 1000 V AC and the 75 - 1500 V DC voltage ranges. Danfoss CE-labels in accordance with the directive and issues a
declaration of conformity upon request.
The EMC directive (89/336/EEC)
EMC is short for electromagnetic compatibility. The presence of electromagnetic compatibility means that the mutual interference between different
components/appliances does not affect the way the appliances work.
The EMC directive came into effect January 1, 1996. Danfoss CE-labels in accordance with the directive and issues a declaration of conformity upon
request. To carry out EMC-correct installation, see the instructions in this Design Guide. In addition, we specify which standards our products comply
with. We offer the filters presented in the specifications and provide other types of assistance to ensure the optimum EMC result.
The frequency converter is most often used by professionals of the trade as a complex component forming part of a larger appliance, system or installation.
It must be noted that the responsibility for the final EMC properties of the appliance, system or installation rests with the installer.
2.3.2 What Is Covered
2
The EU "
Guidelines on the Application of Council Directive 89/336/EEC
coverage and CE labelling.
1.The frequency converter is sold directly to the end-consumer. The frequency converter is for example sold to a DIY market. The end-consumer
is a layman. He installs the frequency converter himself for use with a hobby machine, a kitchen appliance, etc. For such applications, the
frequency converter must be CE labelled in accordance with the EMC directive.
2.The frequency converter is sold for installation in a plant. The plant is built up by professionals of the trade. It could be a production plant or a
heating/ventilation plant designed and installed by professionals of the trade. Neither the frequency converter nor the finished plant has to be
CE labelled under the EMC directive. However, the unit must comply with the basic EMC requirements of the directive. This is ensured by using
components, appliances, and systems that are CE labelled under the EMC directive.
3.The frequency converter is sold as part of a complete system. The system is being marketed as complete and could e.g. be an air-conditioning
system. The complete system must be CE labelled in accordance with the EMC directive. The manufacturer can ensure CE labelling under the
EMC directive either by using CE labelled components or by testing the EMC of the system. If he chooses to use only CE labelled components,
he does not have to test the entire system.
" outline three typical situations of using a frequency converter. See below for EMC
MG.20.X1.22 - VLTp is a registered Danfoss trademark
2.3.3 Danfoss Frequency Converter and CE Labelling
CE labelling is a positive feature when used for its original purpose, i.e. to facilitate trade within the EU and EFTA.
However, CE labelling may cover many different specifications. Thus, you have to check what a given CE label specifically covers.
The covered specifications can be very different and a CE label may therefore give the installer a false feeling of security when using a frequency converter
as a component in a system or an appliance.
Danfoss CE labels the frequency converters in accordance with the low-voltage directive. This means that if the frequency converter is installed correctly,
we guarantee compliance with the low-voltage directive. Danfoss issues a declaration of conformity that confirms our CE labelling in accordance with the
low-voltage directive.
The CE label also applies to the EMC directive provided that the instructions for EMC-correct installation and filtering are followed. On this basis, a
declaration of conformity in accordance with the EMC directive is issued.
The Design Guide offers detailed instructions for installation to ensure EMC-correct installation. Furthermore, Danfoss specifies which our different prod-
ucts comply with.
Danfoss gladly provides other types of assistance that can help you obtain the best EMC result.
2.3.4 Compliance with EMC Directive 89/336/EEC
As mentioned, the frequency converter is mostly used by professionals of the trade as a complex component forming part of a larger appliance, system,
or installation. It must be noted that the responsibility for the final EMC properties of the appliance, system or installation rests with the installer. As an
aid to the installer, Danfoss has prepared EMC installation guidelines for the Power Drive system. The standards and test levels stated for Power Drive
systems are complied with, provided that the EMC-correct instructions for installation are followed, see the section
The frequency converter has been designed to meet the IEC/EN 60068-2-3 standard, EN 50178 pkt. 9.4.2.2 at 50°C.
A frequency converter contains a large number of mechanical and electronic components. All are to some extent vulnerable to environmental effects.
The frequency converter should not be installed in environments with airborne liquids, particles, or gases capable of affecting and
damaging the electronic components. Failure to take the necessary protective measures increases the risk of stoppages, thus reducing
the life of the frequency converter.
Liquids can be carried through the air and condense in the frequency converter and may cause corrosion of components and metal parts. Steam, oil, and
salt water may cause corrosion of components and metal parts. In such environments, use equipment with enclosure rating IP 54/55. As an extra
protection, coated printed circuit boards can be ordered as an option.
Particles such as dust may cause mechanical, electrical, or thermal failure in the frequency converter. A typical indicator of excessive levels of
Airborne
airborne particles is dust particles around the frequency converter fan. In very dusty environments, use equipment with enclosure rating IP 54/55 or a
cabinet for IP 00/IP 20/TYPE 1 equipment.
In environments with high temperatures and humidity,
on the frequency converter components.
corrosive gases such as sulphur, nitrogen, and chlorine compounds will cause chemical processes
EMC Immunity
.
18
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Such chemical reactions will rapidly affect and damage the electronic components. In such environments, mount the equipment in a cabinet with fresh
air ventilation, keeping aggressive gases away from the frequency converter.
An extra protection in such areas is a coating of the printed circuit boards, which can be ordered as an option.
NB!
Mounting frequency converters in aggressive environments increases the risk of stoppages and considerably reduces the life of the
converter.
Before installing the frequency converter, check the ambient air for liquids, particles, and gases. This is done by observing existing installations in this
environment. Typical indicators of harmful airborne liquids are water or oil on metal parts, or corrosion of metal parts.
Excessive dust particle levels are often found on installation cabinets and existing electrical installations. One indicator of aggressive airborne gases is
blackening of copper rails and cable ends on existing installations.
NB!
D and E enclosures have a stainless steel back-channel option to provide additional protection in aggressive environments. Proper ventilation is still
required for the internal components of the drive. Contact Danfoss for additional information.
2
2.4 Vibration and shock
The frequency converter has been tested according to the procedure based on the shown standards:
The frequency converter complies with requirements that exist for units mounted on the walls and floors of production premises, as well as in panels
bolted to walls or floors.
IEC/EN 60068-2-6:Vibration (sinusoidal) - 1970
IEC/EN 60068-2-64:Vibration, broad-band random
2.5 Advantages
2.7.1 Why use a Frequency Converter for Controlling Fans and Pumps?
A frequency converter takes advantage of the fact that centrifugal fans and pumps follow the laws of proportionality for such fans and pumps. For further
information see the text
The Laws of Proportionality
2.7.2 The Clear Advantage - Energy Savings
The very clear advantage of using a frequency converter for controlling the speed of fans or pumps lies in the electricity savings.
When comparing with alternative control systems and technologies, a frequency converter is the optimum energy control system for controlling fan and
pump systems.
.
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Illustration 2.1: The graph is showing fan curves (A, B and
C) for reduced fan volumes.
Illustration 2.2: When using a frequency converter to reduce
fan capacity to 60% - more than 50% energy savings may
be obtained in typical applications.
2.7.3 Example of Energy Savings
As can be seen from the figure (the laws of proportional ity), the flow is controlled by changing t he RPM. By reducing the speed only 20% from the rated
speed, the flow is also reduced by 20%. This is because the flow is directly proportional to the RPM. The consumption of electricity, however, is reduced
by 50%.
If the system in question only needs to be able to supply a flow that corresponds to 100% a few days in a year, while the average is below 80% of the
rated flow for the remainder of the year, the amount of energy saved is even more than 50%.
The laws of proportionality
The figure below describes the dependence of flow, pressure and power consumption on RPM.
Q = FlowP = Power
Q1 = Rated flowP1 = Rated power
Q
= Reduced flowP2 = Reduced power
2
H = Pressuren = Speed regulation
H1 = Rated pressuren1 = Rated speed
H
= Reduced pressuren2 = Reduced speed
2
20
MG.20.X1.22 - VLTp is a registered Danfoss trademark
2.7.7 Star/delta Starter or Soft-starter not required
When larger motors are started, it is necessary in many countries to use equipment that limits the start-up current. In more tr aditional systems, a star/
delta starter or soft-starter is widely used. Such motor starters are not required if a frequency converter is used.
2
As illustrated in the figure below, a frequency converter does not consume more than rated current.
1 = VLT Automation VT Drive
2 = Star/delta starter
3 = Soft-starter
4 = Start directly on mains
MG.20.X1.22 - VLTp is a registered Danfoss trademark
The frequency converter is a high performance unit for demanding applications. It can handle various kinds of motor control principles such as U/f special
motor mode and VVC plus and can handle normal squirrel cage asynchronous motors.
Short circuit behavior on this FC depends on the 3 current transducers in the motor phases.
par. 1-00 Configuration Mode
In
is to be used
it can be selected if open or closed lo op
2.8.2 Control Structure Open Loop
Illustration 2.4: Open Loop structure.
In the configuration shown in the illustration above,
handling system or the local reference is received and fed through the ramp limitation and speed limitation before being sent to the motor control.
The output from the motor control is then limited by the maximum frequency limit.
par. 1-00 Configuration Mode
is set to Open loop [0]. The resulting reference from the reference
24
MG.20.X1.22 - VLTp is a registered Danfoss trademark
The closed loop controller allows the drive to become an integral part of the controlled system. The drive receives a feedback signal from a sensor in the
system. It then compares this feedback to a set-point reference value and determines the error, if any, between these two signals. It then adjusts the
speed of the motor to correct this error.
2
For example, consider a pump application where the speed of a pump is to be controlled so that the static pressure in a pipe is constant. The desired
static pressure value is supplied to the drive as the set-point reference. A static pressure sensor measures the actual static pressure in the pipe and
supplies this to the drive as a feedback signal. If the feedback signal is greater than the set-point reference, the drive will slow down to reduce the
pressure. In a similar way, if the pipe pressure is lower than the set-point reference, the drive will automatically speed up to increase the pressure provided
by the pump.
NB!
While the default values for the drive’s Closed Loop controller will often provide satisfactory performance, the control of the system
can often be optimized by adjusting some of the Closed Loop controller’s parameters. It is also possible to autotune the PI constants.
The figure is a block diagram of the drive’s Closed Loop controller. The details of the Reference Handling block and Feedback Handling block are described
in their respective sections below.
26
MG.20.X1.22 - VLTp is a registered Danfoss trademark
A block diagram of how the drive processes the feedback signal is shown below.
2
Feedback handling can be configured to work with applications requiring advanced control, such as multiple setpoints and multiple feedbacks. Three
types of control are common.
Single Zone, Single Setpoint
Single Zone Single Setpoint is a basic configuration. Setpoint 1 is added to any other reference (if any, see Reference Handling) and the feedback signal
is selected using par. 20-20.
Multi Zone, Single Setpoint
Multi Zone Single Setpoint uses two or three feedback sensors but only one setpoint. The feedbacks can be added, subtracted (only feedback 1 and 2)
or averaged. In addition, the maximum or minimum value may be used. Setpoint 1 is used exclusively in this configuration.
Multi Setpoint Min
If
attempts to keep all zones at or below their respective setpoints, while
setpoints.
Example:
A two zone two setpoint application Zone 1 setpoint is 15 bar and the feedback is 5.5 bar. Zone 2 setpoint is 4.4 bar and the feedback is 4.6 bar. If
Setpoint Max
setpoint, resulting in a negative difference). If
has the larger difference (feedback is lower than setpoint, resulting in a positive difference).
[13] is selected, the setpoint/feedback pair with the largest difference controls the speed of the drive.
Multi Setpoint Min
[14] is selected, Zone 1’s setpoint and feedback are sent to the PID controller, since this has the smaller difference (feedbac k i s higher th an
Multi Setpoint Min
[13] is selected, Zone 2’s setpoint and feedback is sent to the PID controller, since this
[13] attempts to keep all zones at or above their respective
Multi Setpoint Maximum
[14]
Multi
MG.20.X1.22 - VLTp is a registered Danfoss trademark
In some applications it may be useful to convert the feedback signal. One example of this is using a pressure signal to provide flow feedback. Since the
square root of pressure is proportional to flow, the square root of the pressure signal yields a value proportional to the flow. This is shown below.
2.8.7 Reference Handling
Details for Open Loop and Closed Loop operation.
A block diagram of how the drive produces the Remote Reference is shown below:.
28
MG.20.X1.22 - VLTp is a registered Danfoss trademark
•External references (analog inputs, pulse frequency inputs, digital potentiometer inputs and serial communication bus references).
•The Preset relative reference.
•Feedback controlled setpoint.
Up to 8 preset references can be programmed in the drive. The active preset reference can be selected using digital inputs or the serial communications
bus. The reference can also be supplied externally, most commonly from an analog input. This external source is selected by one of the 3 Reference
Source parameters (par. 3-15
This is also commonly called a Speed Up/Speed Down Control or a Floating Point Control. To set it up, one digital input is programmed to increase the
reference while another digital input is programmed to decrease the reference. A third digital input can be used to reset the Digipot reference. All reference
resources and the bus reference are added to produce the total External Reference. The External Reference, the Preset Reference or the sum of the two
can be selected to be the active reference. Finally, this reference can by be scaled using par. 3-14
The scaled reference is calculated as follows:
Reference
Where X is the external reference, the preset reference or the sum of these and Y is par. 3-14
= X + X ×
NB!
If Y, par. 3-14
Reference 1 Source
Y
(
)
100
Preset Relative Reference
, par. 3-16
Reference 2 Source
is set to 0%, the reference will not be affected by the scaling
and par. 3-17
Reference 3 Source
Preset Relative Reference
Preset Relative Reference
). Digipot is a digital potentiometer.
.
in [%].
30
MG.20.X1.22 - VLTp is a registered Danfoss trademark
The following is an example of a Closed Loop Control for a booster pump application:
2
In a water distribution system, the pressure is to be maintained at a constant value. The desired pressure (setpoint) is set between 0 and 10 Bar using
a 0-10 volt potentiometer or can be set by a parameter. The pressure sensor has a range of 0 to 10 Bar and uses a two-wire transmitter to provide a
4-20 mA signal. The output frequency range of the drive is 10 to 50 Hz.
1. Start/Stop via switch connected between terminals 12 (+24 V) and 18.
2. Pressure reference via a potentiometer (0-10 Bar, 0-10 V) connected
to terminals 50 (+10 V), 53 (input) and 55 (common).
3. Pressure feedback via transmitter (0-10 Bar, 4-20 mA) connected to
terminal 54. Switch S202 behind the Local Control Panel set to ON
(current input).
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Electrical interference is usually conducted at frequences in the range 150 kHz to 30 MHz. Airborne interference from the drive system in the range 30
MHz to 1 GHz is generated from the inverter, motor cable, and the motor.
As shown in the illustration below, capacitive currents in the motor cable coupled with a high dV/dt from the motor voltage generate leakage currents.
The use of a screened motor cable increases the leakage current (see illustration below) because screened cables have higher capacitance to earth than
unscreened cables. If the leakage current is not filtered, it will cause greater interference on the mains in the radio frequency range below approx. 5
MHz. Since the leakage current (I
from the screened motor cable according to the below figure.
The screen reduces the radiated interference but increases the low-frequency interference on the mains. The motor cable screen must be connected to
the frequency converter enclosure as well as on the motor enclosure. This is best done by using integrated screen clamps so as to avoid twisted screen
ends (pigtails). These increase the screen impedance at higher frequencies, which reduces the screen effect and increases the leakage current (I
If a screened cable is used for Fieldbus, relay, control cable, signal interface and brake, the screen must be mounted on the enclosure at both ends. In
some situations, however, it will be necessary to break the screen to avoid current loops.
) is carried back to the unit through the screen (I 3), there will in principle only be a small electro-magnetic field (I4)
1
).
4
If the screen is to be placed on a mounting plate for the frequency converter, the mounting plate must be made of metal, because the screen currents
have to be conveyed back to the unit. Moreover, ensure good electrical contact from the mounting plate through the mounting screws to the frequency
converter chassis.
NB!
When unscreened cables are used, some emission requirements are not complied with, although the immunity requirements are ob-
served.
In order to reduce the interference level from the entire system (unit + installation), make motor and brake cables as short as possible. Avoid placing
cables with a sensitive signal level alongside motor and brake cables. Radio interference higher than 50 MHz (airborne) is especially generated by the
control electronics.
34
MG.20.X1.22 - VLTp is a registered Danfoss trademark
plants with a high percentage of rectifier load, maintain harmonic cur-
rents at a low level to avoid overload of the transformer and high tem-
perature in the cables.
2
NB!
Some of the harmonic currents might disturb communication equipment connected to the same transformer or cause resonance in
connection with power-factor correction batteries.
NB!
To ensure low harmonic currents, the frequency converter is equipped with intermediate circuit coils as standard. This normally reduces
the input current I
The voltage distortion on the mains supply voltage depends on the size of the harmonic currents multiplied by the mains impedance for the frequency
in question. The total voltage distortion THD is calculated on the basis of the individual voltage harmonics using this formula:
RMS
by 40%.
THD
%=
2
5
+
2
U
+ ... +
7
U
2
U
N
(UN% of U)
2.9.5 Harmonics Emission Requirements
Equipment connected to the public supply network:
Options: Definition:
1IEC/EN 61000-3-2 Class A for 3-phase balanced equip-
ment (for professional equipment only up to 1 kW total
power).
2IEC/EN 61000-3-12 Equipment 16A-75A and professio-
nal equipment as from 1 kW up to 16A phase current.
2.9.6 Harmonics Test Results (Emission)
Power sizes up to PK75 in T2 and T4 complies with IEC/EN 61000-3-2 Class A. Power sizes from P1K1 and up to P18K in T2 and up to P90K in T4 complies
with IEC/EN 61000-3-12. Power sizes P110 - P450 in T4 also complies with IEC/EN 61000-3-12 even though not required because currents are above 75
A.
Table 4, R
S
SC
at the interface point between the user’s supply and the public system.
It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the
equipment is connected only to a supply with a short-circuit power S
Other power sizes can be connected to the public supply network by consultation with the distribution network operator.
>= 120, THD <= 48% and PWHD >=46% provided that the short-circuit power of the supply Ssc is greater than or equal to:
sce
= 3 ×
R
×
U
×
I
SCE
mains
= 3 × 120 × 400 ×
equ
I
equ
greater than or equal to specified above.
sc
MG.20.X1.22 - VLTp is a registered Danfoss trademark
PELV offers protection by way of extra low voltage. Protection against electric shock is ensured when the electrical supply is of the PELV type and the
installation is made as described in local/national regulations on PELV supplies.
All control terminals and relay terminals 01-03/04-06 comply with PELV (Protective Extra Low Voltage) (Does not apply to grounded Delta leg above 400
V).
Galvanic (ensured) isolation is obtained by fulfilling requirements for higher isolation and by providing the relevant creapage/clearance distances. These
requirements are described in the EN 61800-5-1 standard.
The components that make up the electrical isolation, as described below, also comply with the requirements for higher isolation and the relevant test
as described in EN 61800-5-1.
The PELV galvanic isolation can be shown in six locations (see illustration):
In order to maintain PELV all connections made to the control terminals must be PELV, e.g. thermistor must be reinforced/double insulated.
1.Power supply (SMPS) incl. signal isolation of U
intermediate current voltage.
2.Gate drive that runs the IGBTs (trigger transformers/opto-cou-
plers).
3.Current transducers.
4.Opto-coupler, brake module.
5.Internal inrush, RFI, and temperature measurement circuits.
6.Custom relays.
, indicating the
DC
Illustration 2.5: Galvanic isolation
2
The functional galvanic isolation (a and b on drawing) is for the 24 V back-up option and for the RS 485 standard bus interface.
Installation at high altitude:
380 - 500 V, enclosure A, B and C: At altitudes above 2 km, please contact Danfoss regarding PELV.
380 - 500 V, enclosure D, E and F: At altitudes above 3 km, please contact Danfoss regarding PELV.
525 - 690 V: At altitudes above 2 km, please contact Danfoss regarding PELV.
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Touching the electrical ts may be fatal - even after the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected, such a s load sharing (linkage of DC intermediate circuit), as well as
the motor connection for kinetic back-up.
Before touching any electrical parts, wait at least the amount of time indicated in the
Shorter time is allowed only if indicated on the nameplate for the specific unit.
Leakage Current
The earth leakage current from the frequency converter exceeds 3.5 mA. To ensure that the earth cable has a good mechanical
connection to the earth connection (terminal 95), the cable cross section must be at least 10 mm
seately.
Residual Current Device
This product can cause a d.c. current in the protective conductor. Where a residual current device (RCD) is used for protection in case
of di rect o r i ndir ect co nt act , on ly an RC D of Ty pe B is a llowe d o n the supply s ide o f this pr oduc t. Oth er wise , anot he r pro tecti ve measure
shall be applied, such as separation from the environment by double or reinforced insulation, or isolation from the supply system by a
transformer. See also RCD Application Note MN.90.GX.02.
Protective earthing of the frequency converter and the use of RCD's must always follow national and local regulations.
Safety Precautions
2
or 2 rated earth wires terminated
section.
40
MG.20.X1.22 - VLTp is a registered Danfoss trademark
In certain applications, for instance centrifuges, it is desirable to bring the motor to a stop more rapidly than can be achieved through controlling via
ramp down or by free-wheeling. In such applications, dynamic braking with a braking resistor may be utilized. Using a braking resistor ensures that the
energy is absorbed in the resistor and not in the frequency converter.
If the amount of kinetic energy transferred to the resistor in each braking period is not known, the average power can be calculated on the basis of the
cycle time and braking time also called intermitted duty cycle. The resistor intermittent duty cycle is an indication of the duty cycle at which the resistor
is active. The below figure shows a typical braking cycle.
The intermittent duty cycle for the resistor is calculated as follows:
Duty Cycle = tb/T
T = cycle time in seconds
is the braking time in seconds (as part of the total cycle time)
t
b
2
Danfoss offers brake resistors with duty cycle of 5%, 10% and 40% suitable for use with the Automation VT Drive FC322 series. If a 10% duty cycle
resistor is applied, this is able of absorbing braking power upto 10% of the cycle time with the remaining 90% being used to dissipate heat from the
resistor.
For further selection advice, please contact Danfoss.
NB!
If a short circuit in the brake transistor occurs, power dissipation in the brake resistor is only prevented by using a mains switch or
contactor to disconnect the mains for the frequency converter. (The contactor can be controlled by the frequency converter).
MG.20.X1.22 - VLTp is a registered Danfoss trademark
The brake is protected against short-circuiting of the brake resistor, and the brake transistor is monitored to ensure that short-circuiting of the transistor
is detected. A relay/digital output can be used for protecting the brake resistor against overloading in connection with a fault in the frequency converter.
In addition, the brake makes it possible to read out the momentary power and the mean power for the latest 120 seconds. The brake can also monitor
the power energizing and make sure it does not exceed a limit selected in par. 2-12
the function to carry out when the power transmitted to the brake resistor exceeds the limit set in par. 2-12
NB!
Monitoring the brake power is not a safety function; a thermal switch is required for that purpose. The brake resistor circuit is not earth
leakage protected.
Brake Power Limit (kW)
. In par. 2-13
Brake Power Limit (kW)
Brake Power Monitoring
, select
.
Over voltage control (OVC)
active for all units. The function ensures that a trip can be avoided if the DC link voltage increases. This is done by increasing the output frequency to
limit the voltage from the DC link. It is a very useful function, e.g. if the ramp-down time is too short since tripping of the frequency converter is avoided.
In this situation the ramp-down time is extended.
(exclusive brake resistor) can be selected as an alternative brake function in par. 2-17
Over-voltage Control
. This function is
2.12 Mechanical Brake Control
2.14.1 Brake Resistor Cabling
EMC (twisted cables/shielding)
To reduce the electrical noise from the wires between the brake resistor and the frequency converter, the wires must be twisted.
For enhanced EMC performance a metal screen can be used.
2.13 Extreme Running Conditions
Short Circuit (Motor Phase – Phase)
The frequency converter is protected against short circuits by means of current measurement in each of the three motor phases or in the DC link. A short
circuit between two output phases will cause an overcurrent in the inverter. The inverter will be turned off individually when the short circuit current
exceeds the permitted value (Alarm 16 Trip Lock.
To protect the drive against a short circuit at the load sharing and brake outputs please see the design guidelines.
Switching on the Output
Switching on the output between the motor and the frequency converter is fully permitted. You cannot damage the frequency converter in any way by
switching on the output. However, fault messages may appear.
Motor-generated Overvoltage
The voltage in the intermediate circuit is increased when the motor acts as a generator.
This occurs in following cases:
1.The load drives the motor, ie. the load generates energy.
2.During deceleration ("ramp-down") if the moment of inertia is high, the friction is low and the ramp-down time is too short for the energy to be
dissipated as a loss in the frequency converter, the motor and the installation.
3.In-correct slip compensation setting may cause higher DC link voltage.
The control unit may attempt to correct the ramp if possible (par. 2-17
The inverter turns off to protect the transistors and the intermediate circuit capacitors when a certain voltage level is reach ed.
See par. 2-10 and par. 2-17 to select the method used for controlling the intermediate circuit voltage level.
Over-voltage Control
.
High Temperature
High ambient temperature may overheat the frequency converter.
42
MG.20.X1.22 - VLTp is a registered Danfoss trademark
During a mains drop-out, the frequency converter keeps running until the intermediate circuit voltage drops below the minimum stop level, which is
typically 15% below the frequency converter's lowest rated supply voltage.
The mains voltage before the drop-out and the motor load determines how long it takes for the inverter to coast.
plus
Static Overload in VVC
When the frequency converter is overloaded (the torque limit in par. 4-16/4-17 is reached), the controls reduces the output frequency to reduce the load.
If the overload is excessive, a current may occur that makes the frequency converter cut out after approx. 5-10 s.
Operation within the torque limit is limited in time (0-60 s) in par. 14-25.
2.15.1 Motor Thermal Protection
This is the way Danfoss is protecting the motor from being overheated. It is an electronic feature that simulates a bimetal relay based on internal
measurements. The characteristic is shown in the following figure:
mode
2
Illustration 2.6: The X-axis is showing the ratio between I
cuts off and trips the drive. The curves are showing the characteristic nominal speed at twice the nominal speed and at 0,2x the nominal
speed.
It is clear that at lower speed the ETR cuts of at lower heat due to less cooling of the motor. In that way the motor are protected from being over heated
even at low speed. The ETR feature is calculating the motor temperature based on actual current and speed. The calculated temperature is visible as a
read out parameter in par. 16-18
The thermistor cut-out value is > 3 k.
Integrate a thermistor (PTC sensor) in the motor for winding protection.
Motor protection can be implemented using a range of techniques: PTC
sensor in motor windings; mechanical thermal switch (Klixon type); or
Electronic Thermal Relay (ETR).
Motor Thermal
in the frequency converter.
motor
and I
nominal. The Y- axis is showing the time in seconds before the ETR
motor
MG.20.X1.22 - VLTp is a registered Danfoss trademark
The FC322 can perform the Safety Function “Uncontrolled Stopping by removal of power” (as defined by draft IEC 61800-5-2) or Stop Category 0 (as
defined in EN 60204-1).
It is designed and approved suitable for the requirements of Safety Category 3 in EN 954-1. This functionality is called Safe Stop.
Prior to integration and use of FC322 Safe Stop in an installation, a thorough risk analysis on the installation must be carried out in order to determine
whether the FC322 Safe Stop functionality and safety category are appropriate and sufficient.
The Safe Stop function is activated by removing the voltage at Terminal 37 of the Safe Inverter. By connecting the Safe Inverter to external safety devices
providing a safe relay, an installation for a safe Stop Category 1 can be obtained. The Safe Stop function of FC322 can be used for asynchronous and
synchronous motors.
Safe Stop activation (i.e. removal of 24 V DC voltage supply to terminal 37) does not provide electrical safety.
NB!
The Safe Stop function of FC322 can be used for asynchronous and synchronous motors. It may happen that two faults occur in the
frequency converter's power semiconductor. When using synchronous motors this may cause a residual rotation. The rotation can be
calculated to Angle=360/(Number of Poles). The application using synchronous motors must take this into consideration and ensure
that this is not a safety critical issue. This situation is not relevant for asynchronous motors.
2
NB!
In order to use the Safe Stop functionality in conformance with the requirements of EN-954-1 Category 3, a number of conditions must
be fulfilled by the installation of Safe Stop. Please see section
NB!
The frequency converter does not provide a safety-related protection against unintended or malicious voltage supply to terminal 37
and subsequent reset. Provide this protection via the interrupt device, at the application level, or organisational level.
For more information - see section
Safe Stop Installation
Safe Stop Installation
.
for further information.
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Weight enclosure IP 54 [kg]96104125136151263272313129912991299129915411541
Normal overload 110% for 1 minute
Frequency converter
56
IP 21 / Nema 1D1D1D2D2D2E1E1E1F1/F3F1/F3F1/F3F1/F3F2/F4F2/F4
Typical Shaft Output [HP] at 460V150200250300350450550600650750900100012001350
Typical Shaft Output [kW] at 400V
IP 00D3D3D4D4D4E2E2E2F1/F3F1/F3F1/F3F1/F3F2/F4F2/F4
IP 54 / Nema 12D1D1D2D2D2E1E1E1F1/F3F1/F3F1/F3F1/F3F2/F4F2/F4
Output current
For type of fuse see section
Max. input current
1)
American Wire Gauge3) Measured using 5 m screened motor cables at rated load and rated frequency4) The typical power loss is at normal load conditions and expected to be within +/- 15% (tolerance relates to variety in voltage and cable conditions).
2)
Values are based on a typical motor efficiency (eff2/eff3 border line). Lower efficiency motors will also add to the power loss in the frequency converter and vice versa.
If the switching frequency is raised from nominal the power losses may rise significantly.
for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/- 5%).
LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 Watts to the losses. (Though typically only 4 Watts extra for a fully loaded control card or options
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Typical Shaft Output [HP] at 575 V506075100125150200250300350400450500600650750950 1050 1150 1350
Typical Shaft Output [kW]
For type of fuse see section
IP 21 / Nema 1D1D1D1D1D1D1D1D2D2D2D2E1E1E1E1
IP 00D3D3D3D3D3D3D3D4D4D4D4E2E2E2E2-----
IP 54 / Nema 12D1D1D1D1D1D1D1D2D2D2D2E1E1E1E1
Output current
Max. input current
1)
2)
American Wire Gauge3) Measured using 5 m screened motor cables at rated load and rated frequency4) The typical power loss is at normal load conditions and expected to be within +/- 15% (tolerance relates to variety in voltage and cable conditions). Values are based on a typical motor efficiency (eff2/eff3 border
line). Lower efficiency motors will also add to the power loss in the frequency converter and vice versa.
MG.20.X1.22 - VLTp is a registered Danfoss trademark
If the switching frequency is raised from nominal the power losses may rise significantly. LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 [W]
to the losses. (Though typically only 4 [W] extra for a fully loaded control card, or options for slot A or slot B, each).
Adding the F-enclosure option cabinet (resulting in the F3 and F4 enclosure sizes) adds 295 kg to the estimated weight.
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/- 5%).
The RS-485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the supply voltage (PELV).
3
MG.20.X1.22 - VLTp is a registered Danfoss trademark
The load on the frequency converter has little effect on its efficiency. In general, the efficiency is the same at the rated motor frequency f
motor supplies 100% of the rated shaft torque or only 75%, i.e. in case of part loads.
This also means that the efficiency of the frequency converter does not change even if other U/f characteristics are chosen.
However, the U/f characteristics influence the efficiency of the motor.
The efficiency declines a little when the switching frequency is set to a value of above 5 kHz. The efficiency will also be slightly reduced if the mains
voltage is 480 V, or if the motor cable is longer than 30 m.
Efficiency of the motor ()
The efficiency of a motor connected to the frequency converter depends on magnetising level. In general, the efficiency is just as good as with mains
operation. The efficiency of the motor depends on the type of motor.
In the range of 75-100% of the rated torque, the efficiency of the motor is practically constant, both when it is controlled by the frequency converter
and when it runs directly on mains.
In small motors, the influence from the U/f characteristic on efficiency is marginal. However, in motors from 11 kW and up, the advantages are significant.
In general, the switching frequency does not affect the efficiency of small motors. Motors from 11 kW and up have their efficiency improved (1-2%). This
is because the sine shape of the motor current is almost perfect at high switching frequency.
Efficiency of the system (
To calculate the system efficiency, the efficiency of VLT Automation VT Drive (
) =
SYSTEM
VLT
x
MOTOR
MOTOR
SYSTEM
VLT
)
, even if the
M,N
) is multiplied by the efficiency of the motor (
VLT
MOTOR
):
3
Calculate the efficiency of the system at different loads based on the graph above.
MG.20.X1.22 - VLTp is a registered Danfoss trademark
When a motor is connected to a frequency converter, it is necessary to check that the cooling of the motor is adequate.
The level of heating depends on the load on the motor, as well as the operating speed and time.
Constant torque applications (CT mode)
A problem may occur at low RPM values in constant torque applications. In a constant torque application s a motor may over-heat at low speeds due to
less cooling air from the motor integral fan.
Therefore, if the motor is to be run continuously at an RPM value lower than half of the rated value, the motor must be supplied with additional air-cooling
(or a motor designed for this type of operation may be used).
An alternative is to reduce the load level of the motor by choosing a larger motor. However, the design of the frequency converter puts a limit to the
motor size.
Variable (Quadratic) torque applications (VT)
In VT applications such as centrifugal pumps and fans, where the torque is proportional to the square of the speed and the power is proportional to the
cube of the speed, there is no need for additional cooling or de-rating of the motor.
In the graphs shown below, the typical VT curve is below the maximum torque with de-rating and maximum torque with forced cooling at all speeds.
76
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Maximum Load for a Standard Motor at 40 °C driven by a frequency converter type VLT FCxxx
3
Legend: Typical torque at VT load ವವವMax torque with forced cooling ಥಥಥಥಥMax torque
Note 1) Over-syncronous speed operation will result in the available motor torque decreasing inversely proportional with the increase in speed. This
must be considered during the design phase to avoid over-loading of the motor.
3.5.5 Derating for Installing Long Motor Cables or Cables with Larger Cross-Section
NB!
Applicable for drives up to 90 kW only.
The maximum cable length for this frequency converter is 300 m unscreened and 150 m screened cable.
The frequency converter has been designed to work using a motor cable with a rated cross-section. If a cable with a larger cross-section is used, reduce
the output current by 5% for every step the cross-section is increased.
(Increased cable cross-section leads to increased capacity to earth, and thus an increased earth leakage current).
3.5.6 Automatic Adaptations to Ensure Performance
The frequency converter constantly checks for critical levels of internal temperature, load current, high voltage on the intermediate circuit and low motor
speeds. As a response to a critical level, the frequency converter can adjust the switching frequency and / or change the switching pattern in order to
ensure the performance of the frequency converter. The capability to automatically reduce the output current extends the acceptable operating conditions
even further.
3.6 Options and Accessories
Danfoss offers a wide range of options and accessories for the frequency converters.
3.6.1 Mounting of Option Modules in Slot B
The power to the frequency converter must be disconnected.
For A2 and A3 enclosures:
•Remove the LCP (Local Control Panel), the terminal cover, and the LCP frame from the frequency converter.
•Fit the MCB10x option card into slot B.
MG.20.X1.22 - VLTp is a registered Danfoss trademark
MCB 101 is used for extension of the number of digital and analog inputs
and outputs of the VLT Automation VT Drive.
Contents: MCB 101 must be fitted into slot B in the VLT Auto-
mation VT Drive.
•MCB 101 option module
•Extended LCP frame
•Terminal cover
Galvanic Isolation in the MCB 101
Digital/analog inputs are galvanically isolated from other inputs/outputs on the MCB 101 and in the control card of the drive. Digital/analog outputs in
the MCB 101 are galvanically isolated from other inputs/outputs on the MCB 101, but not from these on the control card of the drive.
If the digital inputs 7, 8 or 9 are to be switched by use of the internal 24 V power supply (terminal 9) the connection between terminal 1 and 5 which is
illustrated in the drawing has to be established.
Illustration 3.20: Principle Diagram
80
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Do not combine low voltage parts and PELV systems.
3.6.8 24 V Back-Up Option MCB 107 (Option D)
3
External 24 V DC Supply
An external 24 V DC supply can be installed for low-voltage supply to the control card and any option card installed. This enables full operation of the
LCP (including the parameter setting) and field busses without mains supplied to the power section.
External 24 V DC supply specification:
Input voltage range24 V DC ±15 % (max. 37 V in 10 s)
Max. input current2.2 A
Average input current for the frequency converter0.9 A
Max cable length75 m
Input capacitance load< 10 uF
Power-up delay< 0.6 s
The inputs are protected.
Terminal numbers:
Terminal 35: - external 24 V DC supply.
Terminal 36: + external 24 V DC supply.
Follow these steps:
1.Remove the LCP or Blind Cover
2.Remove the Terminal Cover
3.Remove the Cable De-coupling Plate and the plastic cover un-
derneath
4.Insert the 24 V DC Backup External Supply Option in the Option
Slot
5.Mount the Cable De-coupling Plate
6.Attach the Terminal Cover and the LCP or Blind Cover.
When MCB 107, 24 V backup option is supplying the control circuit, the
internal 24 V supply is automatically disconnected.
Illustration 3.21: Connection to 24 V backup supplier (A2-
A3).
84
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Please note the values available within the different standard groups of resistors:
E12: Closest standard value is 470വ, creating an input of 449.9വ and 8.997V.
E24: Closest standard value is 510വ, creating an input of 486.4വ and 9.728V.
E48: Closest standard value is 511വ, creating an input of 487.3വ and 9.746V.
E96: Closest standard value is 523വ, creating an input of 498.2വ and 9.964V.
Analog inputs - terminal X42/1-6
Parameter group for read out: 18-3*. See also
Programming Guide.
3
Parameter groups for set-up: 26-0*, 26-1*, 26-2* and 26-3*. See also
3 x Analog inputsOperating rangeResolutionAccuracySamplingMax loadImpedance
Used as
temperature
sensor input
Used as
voltage input
When used for voltage, analog inputs are scalable by parameters for each input.
When used for temperature sensor, analog inputs scaling is preset to necessary signal level for specified temperature span.
When analog inputs are used for temperature sensors, it is possible to read out feedback value in both rC and rF.
When operating with temperature sensors, maximum cable length to connect sensors is 80 m non-screened / non-twisted wires.
Analog outputs - terminal X42/7-12
Parameter group for read out and write: 18-3*. See also
Parameter groups for set-up: 26-4*, 26-5* and 26-6*. See also
3 x Analog outputsOutput signal levelResolutionLinearityMax load
Volt0-10 VDC11 bits1% of full scale1 mA
-50 to +150 °C11 bits-50 °C
0 - 10 VDC10 bits
Programming Guide
Programming Guide.
±1 Kelvin
+150 °C
±2 Kelvin
0.2% of full
scale at cal.
temperature
Programming Guide
3 Hz--
2.4 Hz
+/- 20 V
continuously
Approximately
5 k
Analog outputs are scalable by parameters for each output.
The function assigned is selectable via a parameter and have same options as for analog outputs on control card.
For a more detailed description of parameters, please refer to the
Real-time clock (RTC) with back-up
The data format of RTC includes year, month, date, hour, minutes and weekday.
Accuracy of clock is better than s 20 ppm at 25 rC.
The built-in lithium back-up battery lasts on average for minimum 0 years, when frequency converter is operating at 40 rC ambient temperature. If battery
pack back-up fails, analog I/O option must be exchanged.
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Cascade control is a common control system used to control parallel pumps or fans in an energy efficient way.
The Cascade Controller option provides the capability to control multiple pumps configured in parallel in a way that makes them appear as a single larger
pump.
3
When using Cascade Controllers, the individual pumps are automatically turned on (staged) and turned off (de-staged) as needed in order to satisfy the
required system output for flow or pressure. The speed of pumps connected to VLT Automation VT Drive is also controlled to provide a continuous range
of system output.
Illustration 3.24: Cascade control of multiple pumps
The Cascade Controllers are optional hardware and software components that can be added to the VLT Automation VT Drive. It consists of an option
board containing 3 relays that is installed in the B option location on the Drive. Once options are installed the parameters needed to support the Cascade
Controller functions will be available through the control panel in the 27-** parameter group. The Extended Cascade Controller offers more functionality
than the Basic Cascade Controller. It can be used to extend the Basic Cascade with 3 relays and even to 8 relays with the Advanced Cascade Control card
installed.
While the Cascade controller is designed for pumping applications and this document describes the cascade controller for this application, it is also possible
to use the Cascade Controllers for any application requiring multiple motors configured in parallel.
88
MG.20.X1.22 - VLTp is a registered Danfoss trademark
The Cascade Controller software runs from a single VLT Automation VT Drive with the Cascade Controller option card installed. This frequency converter
is referred to as the Master Drive. It controls a set of pumps each controlled by a frequency converter or connected directly to mains through a contactor
or through a soft starter.
Each additional frequency converter in the system is referred to as a Follower Drive. These frequency converters do not need the Cascade Controller
option card installed. They are operated in open loop mode and receive their speed reference from the Master Drive. The pumps connected to these
frequency converters are referred to as Variable Speed Pumps.
Each additional pump connected to mains through a contactor or through a soft starter is referred to as a Fixed Speed Pump.
Each pump, variable speed or fixed speed, is controlled by a relay in the Master Drive. The frequency converter with the Cascade Controller option card
installed has five relays available for controlling pumps. Two (2) relays are standard in the FC and additional 3 relays are found on the option card MCO
101 or 8 relays and 7 digital inputs on option card MCO 102.
The Cascade Controller is capable of controlling a mix of variable speed and fixed speed pumps. Possible configurations are described in more detail in
the next section. For simplicity of description within this manual, Pressure and Flow will be used to describe the variable output of the set of pumps
controlled by the cascade controller.
3.6.12 Extended Cascade Control MCO 101
3
The MCO 101 option includes 3 pieces of change-over contacts and can be fitted into option slot B.
Electrical Data:
Max terminal load (AC)240 V AC 2A
Max terminal load (DC)24 V DC 1 A
Min terminal load (DC)5 V 10 mA
Max switching rate at rated load/min load6 min-1/20 sec
Illustration 3.25: Mounting of B-options
-1
MG.20.X1.22 - VLTp is a registered Danfoss trademark
In applications where the motor is used as a brake, energy is generated in the motor and send back into the frequency converter. If the energy can not
be transported back to the motor it will increase the voltage in the converter DC-line. In applications with frequent braking and/or high inertia loads this
increase may lead to an over voltage trip in the converter and finally a shut down. Brake resistors are used to dissipate the excess energy resulting from
the regenerative braking. The resistor is selected in respect to its ohmic value, its power dissipation rate and its physical size. Danfoss offers a wide variety
of different resistors that are specially designed to our frequency converters. See the section
resistors. Code numbers can be found in the section
How to order
.
Control with brake function
for the dimensioning of brake
3
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Harmonic current distortion is caused by the 6-pulse diode rectifier of the variable speed drive. The harmonic currents are affecting the installed serial
equipment identical to reactive currents. Consequently harmonic current distortion can result in overheating of the supply transformer, cables etc. De-
pending on the impedance of the power grid, harmonic current distortion can lead to voltage distortion also affecting other equipment powered by the
same transformer. Voltage distortion is increasing losses, causes premature aging and worst of all erratic operation. The majority of harmonics are reduced
by the built-in DC coil but if additional reduction is needed, Danfoss offers two types of passive filters.
The Danfoss AHF 005 and AHF 010 are advanced harmonic filters, not to be compared with traditional harmonic trap filters. The Danfoss harmonic filters
have been specially designed to match the Danfoss frequency converters.
AHF 010 is reducing the harmonic currents to less than 10% and the AHF 005 is reducing harmonic currents to less than 5% at 2% background distortion
and 2% imbalance.
3.6.17 Output Filters
The high speed switching of the frequency converter produces some secondary effects, which influence the motor and the enclosed environment. These
side effects are addressed by two different filter types, -the du/dt and the Sine-wave filter.
du/dt filters
Motor insulation stresses are often caused by the combination of rapid voltage and current increase. The rapid energy changes can also be reflected back
to the DC-line in the inverter and cause shut down. The du/dt filter is designed to reduce the voltage rise time/the rapid energy change in the motor and
by that intervention avoid premature aging and flashover in the motor insulation. du/dt filters have a positive influence on the radiation of magnetic noise
in the cable that connects the drive to the motor. The voltage wave form is still pulse shaped but the du/dt ratio is reduced in comparison with the
installation without filter.
Sine-wave filters
Sine-wave filters are designed to let only low frequencies pass. High frequencies are consequently shunted away which results in a sinusoidal phase to
phase voltage waveform and sinusoidal current waveforms.
With the sinusoidal waveforms the use of special frequency converter motors with reinforced insulation is no longer needed. The acoustic noise from the
motor is also damped as a consequence of the wave condition.
Besides the features of the du/dt filter, the sine-wave filter also reduces insulation stress and bearing currents in the motor thus leading to prolonged
motor lifetime and longer periods between services. Sine-wave filters enable use of longer motor cables in applications where the motor is installed far
from the drive. The length is unfortunately limited because the filter does not reduce leakage currents in the cables.
94
MG.20.X1.22 - VLTp is a registered Danfoss trademark
3.7.1 Installation of Duct Cooling Kit in Rittal Enclosures
This section deals with the installation of IP00 / chassis enclosed frequency converters with duct work cooling kits in Rittal enclosures. In addition to the
enclosure a 200 mm base/plinth is required.
3
Illustration 3.28: Installation of IP00 in Rittal TS8 enclosure.
The minimum enclosure dimension is:
•D3 and D4 frame: Depth 500 mm and width 600 mm.
•E2 frame: Depth 600 mm and width 800 mm.
MG.20.X1.22 - VLTp is a registered Danfoss trademark
The maximum depth and width are as required by the installation. When using multiple frequency converters in one enclosure it is recommended that
each drive is mounted on its own back panel and supported along the mid-section of the panel. These duct work kits do not support the “in frame”
mounting of the panel (see Rittal TS8 catalogue for details). The duct work cooling kits listed in the table below are suitable for use only with IP 00 /
Chassis frequency converters in Rittal TS8 IP 20 and UL and NEMA 1 and IP 54 and UL and NEMA 12 enclosures.
For the E2 frames it is important to mount the plate at the absolute rear of the Rittal enclosure due to the weight of the frequency
converter.
NB!
A door-fan(s) is required on the Rittal cabinet to remove the loses not contained in the back-channel of the drive. The minimum door-
fan(s) airflow required at the drive maximum ambient for the D3 and D4 is 391 m^3/h (230 cfm). The minimum door-fan(s) airflow
required at the drive maximum ambient for the E2 is 782 m^3/h (460 cfm). If the ambient is below maximum or if additional compo-
nents, heat loses, are added within the enclosure a calculation must be made to ensure the proper airflow is provided to cool the inside
of the Rittal enclosure.
Ordering Information
Rittal TS-8 EnclosureFrame D3 Kit Part No.Frame D4Kit Part No.Frame E2 Part No.
1800 mm176F1824176F1823Not possible
2000 mm176F1826176F1825176F1850
2200 mm176F0299
Kit Contents
•Ductwork components
•Mounting hardware
•Gasket material
•Delivered with D3 and D4 frame kits:
•175R5639 - Mounting templates and top/bottom cut out for Rittal enclosure.
•Delivered with E2 frame kits:
•175R1036 - Mounting templates and top/bottom cut out for Rittal enclosure.
All fasteners are either:
•10 mm, M5 Nuts torque to 2.3 Nm (20 in-lbs)
•T25 Torx screws torque to 2.3 Nm (20 in-lbs)
NB!
Please see the
External ducts
If additional duct work is added externally to the Rittal cabinet the pressure drop in the ducting must be calculated. Use the charts below to derate the
frequency converter according to the pressure drop.
Duct Kit Instruction Manual, 175R5640,
for further information
96
MG.20.X1.22 - VLTp is a registered Danfoss trademark
3.7.2 Outside Installation/ NEMA 3R Kit for Rittal Enclosures
This section is for the installation of NEMA 3R kits available for the frequency converter frames D3, D4 and E2. These kits are designed and tested to be
used with IP00/ Chassis versions of these frames in Rittal TS8 NEMA 3R or NEMA 4 enclosures. The NEMA-3R enclosure is an outdoor enclosure that
provides a degree of protection against rain and ice. The NEMA-4 enclosure is an outdoor enclosure that provides a greater degree of protection against
weather and hosed water.
The minimum enclosure depth is 500 mm (600 mm for E2 frame) and the kit is designed for a 600 mm (800 mm for E2 frame) wide enclosure. Other
enclosure widths are possible, however additional Rittal hardware is required. The maximum depth and width are as required by the installation.
NB!
The current rating of drives in D3 and D4 frames are de-rated by 3%, when adding the NEMA 3R kit. Drives in E2 frames require no
derating
NB!
A door-fan(s) is required on the Rittal cabinet to remove the loses not contained in the back-channel of the drive. The minimum door-
fan(s) airflow required at the drive maximum ambient for the D3 and D4 is 391 m^3/h (230 cfm). The minimum door-fan(s) airflow
required at the drive maximum ambient for the E2 is 782 m^3/h (460 cfm). If the ambient is below maximum or if additional compo-
nents, heat loses, are added within the enclosure a calculation must be made to ensure the proper airflow is provided to cool the inside
of the Rittal enclosure.
98
MG.20.X1.22 - VLTp is a registered Danfoss trademark
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.