Adjustable frequency drives contain high voltage when
connected to AC line power. Installation, startup, and
maintenance should be performed by qualified personnel
only. Failure to perform installation, startup, and
maintenance by qualified personnel could result in death
or serious injury.
High Voltage
Adjustable frequency drives are connected to hazardous
AC line voltage. Extreme care should be taken to protect
against shock. Only trained personnel familiar with
electronic equipment should install, start, or maintain this
equipment.
WARNING
UNINTENDED START!
When the adjustable frequency drive is connected to AC
line power, the motor may start at any time. The
adjustable frequency drive, motor, and any driven
equipment must be in operational readiness. Failure to be
in operational readiness when the adjustable frequency
drive is connected to AC line power could result in death,
serious injury, equipment, or property damage.
Unintended Start
When the adjustable frequency drive is connected to AC
line power, the motor may be started with an external
switch, a serial bus command, an input reference signal, or
a cleared fault condition. Use appropriate caution to guard
against an unintended start.
Voltage [V]Minimum waiting time [minutes]
415
200–2400-34-0.5 hp7.5-50 hp
380–4800.34-10 hp15-100 hp
525–6001.0-10 hp15-100 hp
525–69015-100 hp
High voltage may be present even when the warning LED
indicator lights are off.
Discharge Time
Symbols
The following symbols are used in this manual.
WARNING
Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may
also be used to alert against unsafe practices.
CAUTION
Indicates a situation that may result in equipment or
property damage-only accidents.
NOTE!
Indicates highlighted information that should be observed
in order to avoid mistakes or operate equipment at less
than optimal performance.
WARNING
DISCHARGE TIME!
Adjustable frequency drives contain DC link capacitors that
can remain charged even when the adjustable frequency
drive is not powered. To avoid electrical hazards,
disconnect AC line power, any permanent magnet type
motors, and any remote DC link power supplies, including
battery backups, UPS and DC link connections to other
adjustable frequency drives. Wait for the capacitors to fully
discharge before performing any service or repair work.
The wait time required is listed in the Discharge Time table.
Failure to wait for the specified period of time after power
has been removed to do service or repair could result in
death or serious injury.
MG33AM22 - VLT® is a registered Danfoss trademark
Approvals
Table 1.2
Safety
VLT® AutomationDrive Instruction
Manual
NOTE!
Imposed limitations on the output frequency
(due to export control regulations):
From software version 6.72, the output frequency of the
adjustable frequency drive is limited to 590 Hz. Software
versions 6x.xx also limit the maximum output frequency to
590 Hz, but these versions cannot be flashed, i.e., neither
downgraded nor upgraded.
MG33AM22 - VLT® is a registered Danfoss trademark
Contents
Contents
VLT® AutomationDrive Instruction
Manual
1 Introduction
1.1 Purpose of the Manual
1.2 Additional Resources
1.3 Product Overview
1.4 Internal Controller Functions
1.5 Frame Sizes and Power Ratings
2 Installation
2.1 Installation Site Checklist
2.2 Adjustable Frequency Drive and Motor Pre-installation Checklist
2.3 Mechanical Installation
2.3.1 Cooling3-1
2.3.2 Lifting3-2
2.3.3 Mounting3-2
2.3.4 Tightening Torques3-2
2.4 Electrical Installation
2.4.1 Requirements3-5
2.4.2 Grounding Requirements3-5
2-1
2-2
2-3
2-3
2-3
2-5
3-1
3-1
3-1
3-1
3-3
2.4.2.1 Leakage Current (>3.5 mA)3-6
2.4.2.2 Grounding Using Shielded Cable3-6
2.4.3 Motor Connection3-6
2.4.4 AC Line Input Connection3-7
2.4.5 Control Wiring3-7
2.4.5.1 Access3-7
2.4.5.2 Control Terminal Types3-8
2.4.5.3 Wiring to Control Terminals3-9
2.4.5.4 Using Shielded Control Cables3-10
2.4.5.5 Control Terminal Functions3-10
2.4.5.6 Jumper Terminals 12 and 273-10
2.4.5.7 Terminal 53 and 54 Switches3-11
2.4.5.8 Mechanical Brake Control3-11
2.4.6 Serial Communication3-12
2.5 Safe Stop
2.5.1 Terminal 37 Safe Stop Function3-13
2.5.2 Safe Stop Commissioning Test3-16
3-12
3 Start-up and Functional Testing
3.1 Pre-start
MG33AM22 - VLT® is a registered Danfoss trademark
4-1
4-1
Contents
VLT® AutomationDrive Instruction
Manual
3.1.1 Safety Inspection4-1
3.2 Applying Power
3.3 Basic Operational Programming
3.4 Asynchronous Motor Set-up
3.5 PM Motor Set-up in VVC
plus
3.6 Automatic Motor Adaptation
3.7 Check Motor Rotation
3.8 Check Encoder Rotation
3.9 Local Control Test
3.10 System Start-up
4 User Interface
4.1 Local Control Panel
4.1.1 LCP Layout5-1
4.1.2 Setting LCP Display Values5-2
4.1.3 Display Menu Keys5-2
4.1.4 Navigation Keys5-3
4.1.5 Operation Keys5-3
4.2 Backup and Copying Parameter Settings
4-3
4-3
4-4
4-5
4-5
4-6
4-6
4-7
4-7
5-1
5-1
5-3
4.2.1 Uploading Data to the LCP5-4
4.2.2 Downloading Data from the LCP5-4
4.3 Restoring Default Settings
4.3.1 Recommended Initialization5-4
4.3.2 Manual Initialization5-4
5 About Adjustable Frequency Drive Programming
5.1 Introduction
5.2 Programming Example
5.3 Control Terminal Programming Examples
5.4 International/North American Default Parameter Settings
5.5 Parameter Menu Structure
5.5.1 Main menu structure6-5
5.6 Remote Programming with MCT 10 Set-up Software
6 Application Examples
6.1 Introduction
6.2 Application Examples
5-4
6-1
6-1
6-1
6-2
6-3
6-4
6-9
7-1
7-1
7-1
7 Status Messages
7.1 Status Display
8-1
8-1
MG33AM22 - VLT® is a registered Danfoss trademark
Contents
VLT® AutomationDrive Instruction
Manual
7.2 Status Message Definitions Table
8 Warnings and Alarms
8.1 System Monitoring
8.2 Warning and Alarm Types
8.3 Warning and Alarm Displays
8.4 Warning and Alarm Definitions
9 Basic Troubleshooting
9.1 Start Up and Operation
10 Specifications
10.1 Power-dependent Specifications
10.2 General Technical Data
10.3 Fuse Specifications
10.3.2 Recommendations11-19
10.3.3 CE Compliance11-19
10.4 Connection Tightening Torques
8-1
9-1
9-1
9-1
9-1
9-2
10-1
10-1
11-1
11-1
11-14
11-19
11-28
12 Index
12-1
MG33AM22 - VLT® is a registered Danfoss trademark
Contents
VLT® AutomationDrive Instruction
Manual
MG33AM22 - VLT® is a registered Danfoss trademark
1
2
3
4
5
6
7
8
9
10
11
12
13
14
8
15
16
17
18
130BB492.10
Introduction
VLT® AutomationDrive Instruction
Manual
1 Introduction
11
Figure 1.1 Exploded View A1-A3, IP20
LCP10 Motor output terminals 96 (U), 97 (V), 98 (W)
1
2RS-485 serial bus connector (+68, -69)11 Relay 1 (01, 02, 03)
3Analog I/O connector12 Relay 2 (04, 05, 06)
4LCP input plug13 Brake (-81, +82) and load sharing (-88, +89) terminals
5Analog switches (A53), (A54)14 Line power input terminals 91 (L1), 92 (L2), 93 (L3)
6Cable strain relief/PE ground15 USB connector
7Decoupling plate16 Serial bus terminal switch
8Grounding clamp (PE)17 Digital I/O and 24 V power supply
9Shielded cable grounding clamp and strain relief18 Control cable cover plate
Table 1.1 Legend to Figure 1.1
MG33AM22 - VLT® is a registered Danfoss trademark1-1
1
2
3
4
5
6
7
8
9
10
11
12
13
16
17
18
19
14
15
FAN MOUNTING
QDF-30
DC-
DC+
Remove jumper to activate Safe Stop
Max. 24 Volt !
12
13
18
19 27 29 32
33
20
61
68
39
42
50
53 54
0605 04
0302 01
130BB493.10
Introduction
VLT® AutomationDrive Instruction
Manual
11
Figure 1.2 Exploded View B and C Sizes, IP55/66
LCP11 Relay 2 (04, 05, 06)
1
2Cover12 Lifting ring
3RS-485 serial bus connector13 Mounting slot
4Digital I/O and 24 V power supply14 Grounding clamp (PE)
5Analog I/O connector15 Cable strain relief/PE ground
6Cable strain relief/PE ground16 Brake terminal (-81, +82)
7USB connector17 Load sharing terminal (DC bus) (-88, +89)
8Serial bus terminal switch18 Motor output terminals 96 (U), 97 (V), 98 (W)
9Analog switches (A53), (A54)19 Line power input terminals 91 (L1), 92 (L2), 93 (L3)
10Relay 1 (01, 02, 03)
Table 1.2 Legend to Figure 1.2
programming, and functional testing. The remaining
1.1
Purpose of the Manual
This manual is intended to provide detailed information for
the installation and startup of the adjustable frequency
chapters provide supplementary details. These details
include user interface, detailed programming, application
examples, startup troubleshooting, and specifications.
drive. provides requirements for mechanical and electrical
installation, including input, motor, control and serial
communications wiring and control terminal functions.
provides detailed procedures for startup, basic operational
1-2MG33AM22 - VLT® is a registered Danfoss trademark
Introduction
VLT® AutomationDrive Instruction
Manual
1.2 Additional Resources
Other resources are available to understand advanced
adjustable frequency drive functions and programming.
®
The VLT
•
detail on working with parameters and many
application examples.
The VLT® Design Guide is intended to provide
•
detailed capabilities and functionality to design
motor control systems.
Supplementary publications and manuals are
•
available from Danfoss.
See http://www.danfoss.com/BusinessAreas/Drives-
Solutions/Documentations/Technical
+Documentation.htm for listings.
Optional equipment is available that may change
•
some of the procedures described. Reference the
instructions supplied with those options for
specific requirements. Contact the local Danfoss
supplier or visit the Danfoss website: http://
www.danfoss.com/BusinessAreas/DrivesSolutions/
Documentations/Technical+Documentation.htm, for
downloads or additional information.
Programming Guide provides greater
1.4
Internal Controller Functions
Figure 1.3 is a block diagram of the adjustable frequency
drive's internal components. See Table 1.3 for their
functions.
Figure 1.3 Adjustable Frequency Drive Block Diagram
11
1.3
Product Overview
An adjustable frequency drive is an electronic motor
controller that converts AC line power input into a variable
AC waveform output. The frequency and voltage of the
output are regulated to control the motor speed or torque.
The adjustable frequency drive can vary the speed of the
motor in response to system feedback, such as position
sensors on a conveyor belt. The adjustable frequency drive
can also regulate the motor by responding to remote
commands from external controllers.
In addition, the adjustable frequency drive monitors the
system and motor status, issues warnings or alarms for
fault conditions, starts and stops the motor, optimizes
energy efficiency, and offers many more control,
monitoring, and efficiency functions. Operation and
monitoring functions are available as status indications to
an outside control system or serial communication
network.
MG33AM22 - VLT® is a registered Danfoss trademark1-3
Introduction
AreaTitleFunctions
11
1Mains input
2Rectifier
3DC bus
4DC reactors
5Capacitor bank
6Inverter
7Output to motor
8Control circuitry
Three-phase AC line power
•
supply to the adjustable
frequency drive
The rectifier bridge converts
•
the AC input to DC current to
supply inverter power
Intermediate DC bus circuit
•
handles the DC current
Filter the intermediate DC
•
circuit voltage
Prove line transient protection
•
Reduce RMS current
•
Raise the power factor
•
reflected back to the line
Reduce harmonics on the AC
•
input
Stores the DC power
•
Provides ride-through
•
protection for short power
losses
Converts the DC into a
•
controlled PWM AC waveform
for a controlled variable
output to the motor
Regulated three-phase output
•
power to the motor
Input power, internal
•
processing, output, and motor
current are monitored to
provide efficient operation
and control
User interface and external
•
commands are monitored and
performed
Status output and control can
•
be provided
VLT® AutomationDrive Instruction
Manual
Table 1.3 Legend to Figure 1.3
1-4MG33AM22 - VLT® is a registered Danfoss trademark
MG33AM22 - VLT® is a registered Danfoss trademark1-5
Introduction
VLT® AutomationDrive Instruction
Manual
11
1-6MG33AM22 - VLT® is a registered Danfoss trademark
Installation
2 Installation
2.1 Installation Site Checklist
The adjustable frequency drive relies on the
•
ambient air for cooling. Observe the limitations
on ambient air temperature for optimal operation
Ensure that the installation location has sufficient
•
support strength to mount the adjustable
frequency drive
Keep the manual, drawings, and diagrams
•
accessible for detailed installation and operation
instructions. It is important that the manual is
available for equipment operators.
Locate equipment as near to the motor as
•
possible. Keep motor cables as short as possible.
Check the motor characteristics for actual
tolerances. Do not exceed
1,000 ft [300 m] for unshielded motor
•
leads
500 ft [150 m] for shielded cable.
•
Ensure that the ingress protection rating of the
•
adjustable frequency drive is suitable for the
installation environment. IP55 (NEMA 12) or IP66
(NEMA 4) enclosures may be necessary.
VLT® AutomationDrive Instruction
Manual
2.2
Adjustable Frequency Drive and Motor
Pre-installation Checklist
Compare the model number of unit on the
•
nameplate to what was ordered to verify the
proper equipment
Ensure each of the following are rated for the
•
same voltage:
Ensure that the adjustable frequency drive output
•
current rating is equal to or greater than motor
full load current for peak motor performance.
2.3
Mechanical Installation
Line power
Adjustable frequency drive
Motor
Motor size and adjustable frequency
drive power must match for proper
overload protection
If adjustable frequency drive rating is
less than motor, full motor output
cannot be achieved
2
2
CAUTION
Ingress protection
IP54, IP55 and IP66 ratings can only be guaranteed if the
unit is properly closed.
Ensure that all cable connectors and unused
•
holes for connectors are properly sealed.
Ensure that the unit cover is properly closed
•
CAUTION
Device damage through contamination
Do not leave the adjustable frequency drive uncovered.
For “spark-free” installations according to European
Agreement concerning International Carriage of Dangerous
Goods by Inland Waterways (ADN_2011 ###), refer to VLT
AutomationDrive FC 300 Design Guide.
2.3.1 Cooling
To provide cooling airflow, mount the unit to a
•
solid flat surface or to the optional backplate (see
2.3.3 Mounting)
Top and bottom clearance for air cooling must be
•
provided. Generally, 100–225 mm (4–10 in) is
required. See Figure 2.1 for clearance
requirements
Improper mounting can result in overheating and
•
reduced performance
Derating for temperatures starting between 104
•
°F [40 °C] and 122 °F [50 °C] and elevation 3,300
®
ft [1,000 m] above sea level must be considered.
See the equipment Design Guide for detailed
information.
MG33AM22 - VLT® is a registered Danfoss trademark2-1
a
b
130BA419.10
130BA219.10
A
130BA228.10
A
2
Installation
Figure 2.1 Top and Bottom Cooling Clearance
VLT® AutomationDrive Instruction
Manual
Improper mounting can result in overheating and
•
reduced performance
Use the slotted mounting holes on the unit for
•
wall mounting, when provided.
Figure 2.2 Proper Mounting with Backplate
Item A is a backplate properly installed for required airflow
to cool the unit.
Enclosure
a/b (inch
[mm])
Table 2.1 Minimum Airflow Clearance Requirements
Lifting
2.3.2
Check the weight of the unit to determine a safe
•
lifting method
Ensure that the lifting device is suitable for the
•
task
If necessary, plan for a hoist, crane, or forklift with
•
the appropriate rating to move the unit
For lifting, use hoist rings on the unit, where
•
provided
Mounting
2.3.3
Mount the unit vertically
•
The adjustable frequency drive allows side by
•
side installation
Ensure that the strength of the mounting location
•
will support the unit weight
Mount the unit onto a solid flat surface or onto
•
the optional backplate to provide cooling airflow
(see Figure 2.2 and Figure 2.3)
A1-A5B1-B4C1, C3C2, C4
3.94 [100]7.87 [200] 7.87 [200] 8.86 [225]
Figure 2.3 Proper Mounting with Railings
NOTE!
Backplate is needed when mounted on railings.
2.3.4 Tightening Torques
See 10.4 Connection Tightening Torques for proper
tightening specifications.
2-2MG33AM22 - VLT® is a registered Danfoss trademark
3 Phase
power
input
DC bus
Switch Mode
Power Supply
Motor
Analog Output
Interface
relay1
* relay2
ON=Terminated
OFF=Open
Brake
resistor
130BC931.10
91 (L1)
92 (L2)
93 (L3)
PE
88 (-)
89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4-20 mA
12 (+24V OUT)
13 (+24V OUT)
37 (D IN)
18 (D IN)
20 (COM D IN)
10Vdc
15mA 130/200mA
+ -+-
(U) 96
(V) 97
(W) 98
(PE) 99
(COM A OUT) 39
(A OUT) 42
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
0V
5V
S801
0/4-20 mA
RS-485
RS-485
03
+10Vdc
0/-10Vdc -
+10Vdc
+10Vdc
0/4-20 mA
0/-10Vdc -
240Vac, 2A
24Vdc
02
01
05
04
06
240Vac, 2A
24V (NPN)
0V (PNP)
0V (PNP)
24V (NPN)
19 (D IN)
24V (NPN)
0V (PNP)
27
24V
0V
(D IN/OUT)
0V (PNP)
24V (NPN)
(D IN/OUT)
0V
24V
29
24V (NPN)
0V (PNP)
0V (PNP)
24V (NPN)
33 (D IN)
32 (D IN)
1 2
ON
S201
ON
21
S202
ON=0/4-20mA
OFF=0/-10Vdc +10Vdc
95
400Vac, 2A
P 5-00
21
ON
S801
(R+) 82
(R-) 81
*
*
: Chassis
: Earth
**
Installation
VLT® AutomationDrive Instruction
Manual
2.4 Electrical Installation
This section contains detailed instructions for wiring the
adjustable frequency drive. The following tasks are
described.
Wiring the motor to the adjustable frequency drive output terminals
•
Wiring the AC line power to the adjustable frequency drive input terminals
•
Connecting control and serial communication wiring
•
After power has been applied, checking input and motor power; programming control terminals for their intended
•
functions
2
2
Figure 2.4 Basic Wiring Schematic Drawing
A=Analog, D=DigitalTerminal 37 is used for Safe Stop. For Safe Stop installation
MG33AM22 - VLT® is a registered Danfoss trademark2-3
instructions, refer to the Design Guide.
1
2
3
4
5
6
7
8
PE
U
V
W
9
L1
L2
L3
PE
130BB607.10
10
Installation
VLT® AutomationDrive Instruction
Manual
2
* Terminal 37 is not included in FC 301 (except frame size
A1). Relay 2 and terminal 29 have no function in FC 301.
** Do not connect cable screen.
Figure 2.5 Typical Electrical Connection
1
2Adjustable frequency drive7Motor, 3-phase and PE
PLC6Min. 200 mm (7.9 in) between control cables, motor and line
power
3Output contactor (Generally not recommended)8Line power, 3-phase and reinforced PE
4Grounding rail (PE)9Control wiring
5Cable insulation (stripped)10
Equalizing min. 16 mm2 (0.025 in2)
Table 2.2 Legend to Figure 2.5
2-4MG33AM22 - VLT® is a registered Danfoss trademark
L1
L1L2L2L3L3
GND
919293
Fuses
130BB460.10
Installation
VLT® AutomationDrive Instruction
Manual
2.4.1 Requirements
WARNING
EQUIPMENT HAZARD!
Rotating shafts and electrical equipment can be hazardous.
All electrical work must conform to national and local
electrical codes. It is strongly recommended that installation, start-up, and maintenance be performed only by
trained and qualified personnel. Failure to follow these
guidelines could result in death or serious injury.
Input fusing is required to provide this
protection, see Figure 2.6. If not factory supplied,
fuses must be provided by the installer as part of
installation. See maximum fuse ratings in
10.3 Fuse Specifications.
2
2
CAUTION
WIRING ISOLATION!
Run input power, motor wiring and control wiring in three
separate metallic conduits or use separated shielded cable
for high frequency noise isolation. Failure to isolate power,
motor and control wiring could result in less than
optimum adjustable frequency drive and associated
equipment performance.
For your safety, comply with the following requirements.
Electronic controls equipment is connected to
•
hazardous AC line voltage. Extreme care should
be taken to protect against electrical hazards
when applying power to the unit.
Run motor cables from multiple adjustable
•
frequency drives separately. Induced voltage from
output motor cables run together can charge
equipment capacitors even with the equipment
turned off and locked out.
Overload and Equipment Protection
An electronically activated function within the
•
adjustable frequency drive provides overload
protection for the motor. The overload calculates
the level of increase to activate timing for the trip
(controller output stop) function. The higher the
current draw, the quicker the trip response. The
overload provides Class 20 motor protection. See
8 Warnings and Alarms for details on the trip
function.
Because the motor wiring carries high frequency
•
current, it is important that wiring for line power,
motor power, and control is run separately. Use
metallic conduit or separated shielded wire.
Failure to isolate power, motor, and control
wiring could result in less than optimum
equipment performance.
All adjustable frequency drives must be provided
•
with short-circuit and overcurrent protection.
Figure 2.6 Adjustable Frequency Drive Fuses
Wire Type and Ratings
All wiring must comply with local and national
•
regulations regarding cross-section and ambient
temperature requirements.
Danfoss recommends that all power connections
•
be made with a minimum 167 °F [75 °C] rated
copper wire.
See 10.1 Power-dependent Specifications for
•
recommended wire sizes.
Grounding Requirements
2.4.2
WARNING
GROUNDING HAZARD!
For operator safety, it is important to ground the
adjustable frequency drive properly in accordance with
national and local electrical codes, as well as instructions
contained within these instructions. Ground currents are
higher than 3.5 mA. Failure to ground the adjustable
frequency drive properly could result in death or serious
injury.
NOTE!
It is the responsibility of the user or certified electrical
installer to ensure correct grounding of the equipment in
accordance with national and local electrical codes and
standards.
MG33AM22 - VLT® is a registered Danfoss trademark2-5
130BA266.10
+DC
BR-
B
MAINS
L1 L2 L3
91 92 93
RELAY 1 RELAY 2
99
- LC -
UVW
MOTOR
Installation
VLT® AutomationDrive Instruction
Manual
2
Follow all local and national electrical codes to
•
ground electrical equipment properly.
Proper protective grounding for equipment with
•
ground currents higher than 3.5 mA must be
established, see Leakage Current (>3,5 mA)
A dedicated ground wire is required for input
•
power, motor power and control wiring
Use the clamps provided with the equipment for
•
proper ground connections
Do not ground one adjustable frequency drive to
•
another in a “daisy chain” fashion
Keep the ground wire connections as short as
•
possible
Use of high strand wire to reduce electrical noise
•
is recommended
Follow the motor manufacturer wiring
•
requirements
2.4.2.1
Follow national and local codes regarding protective
grounding of equipment with a leakage current > 3.5 mA.
Adjustable frequency drive technology implies high
frequency switching at high power. This will generate a
leakage current in the ground connection. A fault current
in the adjustable frequency drive at the output power
terminals might contain a DC component which can
charge the filter capacitors and cause a transient ground
current. The ground leakage current depends on various
system configurations including RFI filtering, shielded
motor cables, and adjustable frequency drive power.
EN/IEC61800-5-1 (Power Drive System Product Standard)
requires special care if the leakage current exceeds 3.5 mA.
Grounding must be reinforced in one of the following
ways:
See EN 60364-5-54 § 543.7 for further information.
Using RCDs
Where residual current devices (RCDs), also known as
ground leakage circuit breakers (GLCBs), are used, comply
with the following:
Leakage Current (>3.5 mA)
Ground wire of at least 0.0155 in2 [10 mm2]
•
Two separate ground wires both complying with
•
the dimensioning rules
Use RCDs of type B only which are capable of
detecting AC and DC currents
Use RCDs with an inrush delay to prevent faults
due to transient ground currents
Dimension RCDs according to the system configuration and environmental considerations
2.4.2.2
Grounding clamps are provided for motor wiring (see
Figure 2.7).
Figure 2.7 Grounding with Shielded Cable
2.4.3
Grounding Using Shielded Cable
Motor Connection
WARNING
INDUCED VOLTAGE!
Run output motor cables from multiple adjustable
frequency drives separately. Induced voltage from output
motor cables run together can charge equipment
capacitors even with the equipment turned off and locked
out. Failure to run output motor cables separately could
result in death or serious injury.
For maximum wire sizes, see 10.1 Power-
•
dependent Specifications
Comply with local and national electrical codes
•
for cable sizes.
Motor wiring knockouts or access panels are
•
provided at the base of IP21 and higher
(NEMA1/12) units
Do not install power factor correction capacitors
•
between the adjustable frequency drive and the
motor
Do not wire a starting or pole-changing device
•
between the adjustable frequency drive and the
motor.
Connect the 3-phase motor wiring to terminals
•
96 (U), 97 (V), and 98 (W).
2-6MG33AM22 - VLT® is a registered Danfoss trademark
95
130BB920.10
+DC
BR-
B
M A I N S
L1 L2 L3
91 92 93
RELAY 1 RELAY 2
99
- LC -
U V W
MOTOR
99
130BT248.10
Installation
VLT® AutomationDrive Instruction
Manual
Ground the cable in accordance with grounding
•
instructions provided.
Torque terminals in accordance with the
•
information provided in
Follow the motor manufacturer wiring
•
requirements
Figure 2.8 represents line power input, motor, and
grounding for basic adjustable frequency drives. Actual
configurations vary with unit types and optional
equipment.
reference power lines. When supplied from an
isolated line power source (IT line power or
floating delta) or TT/TN-S line power with a
grounded leg (grounded delta), set 14-50 RFI 1 to
[0] Off. When off, the internal RFI filter capacitors
between the chassis and the intermediate circuit
are isolated to avoid damage to the intermediate
circuit and to reduce ground capacity currents in
accordance with IEC 61800-3.
2.4.5 Control Wiring
Isolate control wiring from high power
•
components in the adjustable frequency drive.
If the adjustable frequency drive is connected to
•
a thermistor, for PELV isolation, optional
thermistor control wiring must be reinforced/
double insulated. A 24 V DC supply voltage is
recommended.
2.4.5.1
Access
Remove access cover plate with a screw driver.
•
See Figure 2.9.
Or remove front cover by loosening attaching
•
screws. See Figure 2.10.
2
2
Figure 2.8 Example of Motor, Line Power and Ground Wiring
AC Line Input Connection
2.4.4
Size wiring based upon the input current of the
•
adjustable frequency drive. For maximum wire
sizes, see 10.1 Power-dependent Specifications.
Comply with local and national electrical codes
•
for cable sizes.
Connect 3-phase AC input power wiring to
•
terminals L1, L2, and L3 (see Figure 2.8).
Depending on the configuration of the
•
equipment, input power will be connected to the
line input power or the input disconnect.
Ground the cable in accordance with grounding
•
instructions provided in 2.4.2 Grounding
Requirements
All adjustable frequency drives may be used with
•
an isolated input source as well as with ground
Figure 2.9 Control Wiring Access for A2, A3, B3, B4, C3 and C4
Enclosures
MG33AM22 - VLT® is a registered Danfoss trademark2-7
130BT334.10
2
3
4
1
130BB921.11
12 13 18 19 27 29 32 33 20 37
39 42 50 53 54 55
61 68 69
130BB931.10
1
23
Installation
2
Figure 2.10 Control Wiring Access for A4, A5, B1, B2, C1 and C2
Enclosures
See Table 2.3 before tightening the covers.
FrameIP20IP21IP55IP66
A3/A4/A5--22
B1/B2-*2.22.2
C1/C2/C3/C4-*2.22.2
* No screws to tighten
- Does not exist
Table 2.3 Tightening Torques for Covers (Nm)
2.4.5.2
Figure 2.11 and shows the removable adjustable frequency
drive connectors. Terminal functions and default settings
are summarized in Table 2.5.
Figure 2.11 Control Terminal Locations
2-8MG33AM22 - VLT® is a registered Danfoss trademark
Control Terminal Types
VLT® AutomationDrive Instruction
Manual
Figure 2.12 Terminal Numbers
Connector 1 provides four programmable digital
•
inputs terminals, two additional digital terminals
programmable as either input or output, a 24 V
DC terminal supply voltage, and a common for
optional customer supplied 24 V DC voltage. FC
302 and FC 301 (optional in A1 enclosure) also
provide a digital input for STO (Safe Torque Off)
function.
Connector 2 terminals (+)68 and (-)69 are for an
•
RS-485 serial communications connection
Connector 3 provides two analog inputs, one
•
analog output, 10 V DC supply voltage, and
commons for the inputs and output
Connector 4 is a USB port available for use with
•
the MCT 10 Set-up Software
Also provided are two Form C relay outputs that
•
are in various locations depending upon the
adjustable frequency drive configuration and size
Some options available for ordering with the unit
•
may provide additional terminals. See the manual
provided with the equipment option.
See 10.2 General Technical Data for terminal ratings details.
Terminal Parameter
12, 13-+24 V DC24 V DC supply
185-10[8] Start
195-11[10] Reversing
325-14[0] No
335-15[0] No
Terminal description
Default
settingDescription
Digital inputs/outputs
operation
operation
voltage. Maximum
output current is 200
mA total (130 mA for
FC 301) for all 24 V
loads. Usable for
digital inputs and
external transducers.
Digital inputs.
2
1
10 mm
130BA310.10
12 13
18
19
27
29
32
33
Installation
VLT® AutomationDrive Instruction
Manual
Terminal description
Default
Terminal Parameter
275-12[2] Coast
295-13[14] JOG
20-Common for digital
37-Safe Torque
39-
426-50[0] No
50-+10 V DC10 V DC analog
536-1*ReferenceAnalog input.
546-2*Feedback
55-
settingDescription
inverse
Off (STO)
Analog inputs/outputs
operation
Selectable for either
digital input or
output. Default setting
is input.
inputs and 0 V
potential for 24 V
supply.
Safe input. Used for
STO.
Common for analog
output
Programmable analog
output. The analog
signal is 0–20 mA or
4–20 mA at a
maximum of 500 Ω
supply voltage. 15 mA
maximum commonly
used for potentiometer or thermistor.
Selectable for voltage
or current. Switches
A53 and A54 select
mA or V.
Common for analog
input
Terminal description
Default
Terminal Parameter
01, 02, 035-40 [0]
04, 05, 065-40 [1][0] No
Table 2.5 Terminal Description Serial Communication
settingDescription
[0] No
operation
operation
Form C relay output.
Usable for AC or DC
voltage and resistive
or inductive loads.
2.4.5.3 Wiring to Control Terminals
Control terminal connectors can be unplugged from the
adjustable frequency drive for ease of installation, as
shown in Figure 2.11.
1.Open the contact by inserting a small screwdriver
into the slot above or below the contact, as
shown in Figure 2.13.
2.Insert the bared control wire into the contact.
3.Remove the screwdriver to fasten the control wire
into the contact.
4.Ensure the contact is firmly established and not
loose. Loose control wiring can be the source of
equipment faults or less than optimal operation.
See 10.1 Power-dependent Specifications for control terminal
wiring sizes.
See 6 Application Examples for typical control wiring
connections.
2
2
Table 2.4 Terminal Description Digital Inputs/Outputs, Analog Inputs/Outputs
Terminal description
Default
Terminal Parameter
61-
68 (+)8-3*RS-485 Interface. A
69 (-)8-3*
settingDescription
Serial communication
Relays
Integrated RC filter for
cable screen. ONLY for
connecting the shield
when experiencing
EMC problems.
control card switch is
provided for
termination resistance.
Figure 2.13 Connecting Control Wiring
MG33AM22 - VLT® is a registered Danfoss trademark2-9
1
2
PE
FC
PE
PLC
130BB922.12
PEPE
<10 mm
100nF
FC
PE
PE
PLC
<10 mm
130BB609.12
PE
FC
PE
FC
130BB923.12
PEPE
69
68
61
69
68
61
1
2
<10 mm
PE
FC
PE
FC
130BB924.12
PEPE
69
69
68
68
1
2
<10 mm
2
Installation
VLT® AutomationDrive Instruction
Manual
2.4.5.4 Using Shielded Control Cables
Correct shielding
The preferred method in most cases is to secure control
and serial communication cables with shielding clamps
provided at both ends to ensure best possible high
frequency cable contact.
If the ground potential between the adjustable frequency
drive and the PLC is different, electrical noise may occur
that will disturb the entire system. Solve this problem by
fitting an equalizing cable next to the control cable.
Minimum cable cross-section: 0.025 in2 [16 mm2].
Figure 2.14 Correct Shielding
1
Min. 0.025 in2 [16 mm2]
2Equalizing cable
Table 2.7 Legend to Figure 2.16
Alternatively, the connection to terminal 61 can be
omitted:
Figure 2.17 Twisted-pair Cables without Terminal 61
1
Min. 0.025 in2 [16 mm2]
2Equalizing cable
Table 2.8 Legend to Figure 2.17
1
Min. 0.025 in2 [16 mm2]
2Equalizing cable
Table 2.6 Legend to Figure 2.14
50/60 Hz ground loops
With very long control cables, ground loops may occur. To
eliminate ground loops, connect one end of the shield-toground with a 100 nF capacitor (keeping leads short).
Figure 2.15 50/60 Hz Ground Loops
Avoid EMC noise on serial communication
This terminal is grounded via an internal RC link. Use
twisted-pair cables to reduce interference between
conductors. The recommended method is shown below:
Figure 2.16 Twisted-pair Cables
2.4.5.5
Control Terminal Functions
Adjustable frequency drive functions are commanded by
receiving control input signals.
Each terminal must be programmed for the
•
function it will be supporting in the parameters
associated with that terminal. See Table 2.5 for
terminals and associated parameters.
It is important to confirm that the control
•
terminal is programmed for the correct function.
See 4 User Interface for details on accessing
parameters and 5 About Adjustable FrequencyDrive Programming for details on programming.
The default terminal programming is intended to
•
initiate adjustable frequency drive functioning in
a typical operational mode.
2.4.5.6
Jumper Terminals 12 and 27
A jumper wire may be required between terminal 12 (or
13) and terminal 27 for the adjustable frequency drive to
operate when using factory default programming values.
Digital input terminal 27 is designed to receive an
•
24 V DC external interlock command. In many
applications, the user wires an external interlock
device to terminal 27
When no interlock device is used, wire a jumper
•
between control terminal 12 (recommended) or
13 to terminal 27. This provides an internal 24 V
signal on terminal 27.
2-10MG33AM22 - VLT® is a registered Danfoss trademark
130BT310.10
1
2
N O
V LT
BUS TER.
OFF-ON
A53 A54
U- I U- I
Installation
•
•
•
No signal present prevents the unit from
operating.
When the status line at the bottom of the LCP
reads AUTO REMOTE COAST, this indicates that
the unit is ready to operate but is missing an
input signal on terminal 27.
When factory installed optional equipment is
wired to terminal 27, do not remove that wiring
VLT® AutomationDrive Instruction
Manual
2.4.5.7 Terminal 53 and 54 Switches
Analog input terminals 53 and 54 can select
•
either voltage (-10 to 10 V) or current (0/4–20
mA) input signals
Remove power to the adjustable frequency drive
•
before changing switch positions.
Set switches A53 and A54 to select the signal
•
type. U selects voltage, I selects current.
The switches are accessible when the LCP has
•
been removed (see Figure 2.18).
2
2
NOTE!
Some option cards available for the unit may cover these
switches and must be removed to change switch settings.
Always remove power to the unit before removing option
cards.
Terminal 53 default is for a speed reference signal
•
in open-loop set in 16-61 Terminal 53 Switch
Setting
Terminal 54 default is for a feedback signal in
•
closed-loop set in 16-63 Terminal 54 Switch Setting
Figure 2.18 Location of Terminals 53 and 54 Switches and Bus
Termination Switch
2.4.5.8
In hoisting/lowering applications, it is necessary to be able
to control an electro-mechanical brake:
Mechanical Brake Control
Control the brake using any relay output or
•
digital output (terminal 27 or 29).
Keep the output closed (voltage-free) as long as
•
the adjustable frequency drive is unable to
‘support’ the motor, such as when the load is too
heavy, for example.
Select [32]Mechanical brake control in parameter
•
group 5-4* for applications with an electromechanical brake.
The brake is released when the motor current
•
exceeds the preset value in 2-20 Release BrakeCurrent.
The brake is engaged when the output frequency
•
is less than the frequency set in 2-21 Activate
Brake Speed [RPM] or 2-22 Activate Brake Speed
[Hz], and only if the adjustable frequency drive
carries out a stop command.
MG33AM22 - VLT® is a registered Danfoss trademark2-11
L1L2L3
UVW
0201
A1
A2
130BA902.10
Drive
Output
relay
Command Circuit
220Vac
Mechanical
Brake
Shaft
Motor
Frewheeling
diode
Brake
380Vac
Output
Contactor
Input
Power Circuit
61
68
69
+
130BB489.10
RS-485
2
Installation
VLT® AutomationDrive Instruction
Manual
If the adjustable frequency drive is in alarm mode or in an
overvoltage situation, the mechanical brake immediately
cuts in.
In the vertical movement, the key point is that the load
must be held, stopped, controlled (raised, lowered) in a
perfectly safe mode during the entire operation. Because
the adjustable frequency drive is not a safety device, the
crane/lift designer (OEM) must decide on the type and
number of safety devices (e.g. speed switch, emergency
brakes, etc.) to be used, in order to be able to stop the
load in case of emergency or malfunction of the system,
according to relevant national crane/lift regulations.
Figure 2.20 Serial Communication Wiring Diagram
For basic serial communication set-up, select the following
1.
Protocol type in 8-30 Protocol.
2.Adjustable frequency drive address in
8-31 Address.
3.
Baud rate in 8-32 Baud Rate.
Two communication protocols are internal to the
•
adjustable frequency drive. Follow the motor
manufacturer wiring requirements.
Danfoss FC
Modbus RTU
Functions can be programmed remotely using
•
the protocol software and RS-485 connection or
Figure 2.19 Connecting the Mechanical Brake to the Adjustable
Frequency Drive
in parameter group 8-** Communications and
Options.
Selecting a specific communication protocol
•
changes various default parameter settings to
Serial Communication
2.4.6
match that protocol’s specifications along with
making additional protocol-specific parameters
Connect RS-485 serial communication wiring to terminals
(+)68 and (-)69.
available
Option cards which can be installed in the
•
adjustable frequency drive are available to
A shielded serial communication cable is
•
recommended
See 2.4.2 Grounding Requirements for proper
•
provide additional communication protocols. See
the option-card documentation for installation
and instruction manual
grounding
2-12MG33AM22 - VLT® is a registered Danfoss trademark
2.5
Safe Stop
The adjustable frequency drive can perform the safety
function Safe Torque Off (STO, as defined by EN IEC
61800-5-21) and Stop Category 0 (as defined in EN
60204-12).
Danfoss has named this functionality Safe Stop. Before
integration and use of Safe Stop in an installation, perform
a thorough risk analysis to determine whether the Safe
Installation
VLT® AutomationDrive Instruction
Manual
Stop functionality and safety levels are appropriate and
sufficient. Safe Stop is designed and approved suitable for
the requirements of:
-Safety Category 3 according to EN ISO 13849-1
-Performance Level "d" according to EN ISO
13849-1:2008
-SIL 2 Capability according to IEC 61508 and EN
61800-5-2
-SILCL 2 according to EN 62061
1)
Refer to EN IEC 61800-5-2 for details of Safe torque off
(STO) function.
2)
Refer to EN IEC 60204-1 for details of stop category 0
and 1.
Activation and Termination of Safe Stop
The Safe Stop (STO) function is activated by removing the
voltage at Terminal 37 of the Safe Inverter. By connecting
the Safe Inverter to external safety devices providing a safe
delay, an installation for a safe Stop Category 1 can be
obtained. The Safe Stop function can be used for
asynchronous, synchronous, and permanent magnet
motors.
WARNING
After installation of Safe Stop (STO), a commissioning test
as specified in 2.5.2 Safe Stop Commissioning Test must be
performed. A passed commissioning test is mandatory
after first installation and after each change to the safety
installation.
Safe Stop Technical Data
The following values are associated to the different types
of safety levels:
Reaction time for T37
-Maximum reaction time: 10 ms
Reaction time = delay between de-energizing the STO
input and switching off the adjustable frequency drive
output bridge.
Data for EN ISO 13849-1
-Performance Level "d"
-MTTFd (Mean Time To Dangerous Failure): 14,000
years
-DC (Diagnostic Coverage): 90%
-Category 3
-Lifetime 20 years
Data for EN IEC 62061, EN IEC 61508, EN IEC 61800-5-2
-SIL 2 Capability, SILCL 2
-PFH (Probability of Dangerous failure per
Hour)=1e-10FIT=7e-19/h-9/h>90%
No maintenance of the STO functionality is needed.
Security measures have to be taken by the user, e.g.,
installation in a closed cabinet that is only accessible for
skilled personnel.
SISTEMA Data
Functional safety data is available via a data library for use
with the SISTEMA calculation tool from the IFA (Institute
for Occupational Safety and Health of the German Social
Accident Insurance) and data for manual calculation. The
library is complete and continually extended.
Terminal 37 Safe Stop Function
2.5.1
The adjustable frequency drive is available with safe stop
functionality via control terminal 37. Safe stop disables the
control voltage of the power semiconductors of the
adjustable frequency drive output stage. This in turn
prevents generating the voltage required to rotate the
motor. When the Safe Stop (T37) is activated, the
adjustable frequency drive issues an alarm, trips the unit,
and coasts the motor to a stop. Manual restart is required.
The safe stop function can be used as an emergency stop
for the adjustable frequency drive. In normal operating
mode when safe stop is not required, use the regular stop
function instead. When automatic restart is used, ensure
the requirements of ISO 12100-2 paragraph 5.3.2.5 are
fulfilled.
Liability Conditions
It is the responsibility of the user to ensure that qualified
personnel installs and operates the safe stop function:
Read and understand the safety regulations
•
concerning health and safety/accident prevention
Understand the generic and safety guidelines
•
given in this description and the extended
description in the relevant Design Guide
Have a good knowledge of the generic and safety
•
standards applicable to the specific application
2
2
MG33AM22 - VLT® is a registered Danfoss trademark2-13
Installation
VLT® AutomationDrive Instruction
Manual
2
User is defined as: integrator, operator, service technician,
maintenance technician.
Standards
Use of safe stop on terminal 37 requires that the user
satisfies all provisions for safety including relevant laws,
regulations and guidelines. The optional safe stop function
complies with the following standards.
IEC 60204-1: 2005 category 0 – uncontrolled stop
•
IEC 61508: 1998 SIL2
•
IEC 61800-5-2: 2007 – safe torque off (STO)
•
function
IEC 62061: 2005 SIL CL2
•
ISO 13849-1: 2006 Category 3 PL d
•
ISO 14118: 2000 (EN 1037) – prevention of
•
unexpected start-up
The information and instructions of the instruction manual
are not sufficient for a proper and safe use of the safe stop
functionality. The related information and instructions of
the relevant Design Guide must be followed.
Protective Measures
Qualified and skilled personnel are required for
•
installation and commissioning of safety
engineering systems
The unit must be installed in an IP54 cabinet or
•
in an equivalent environment. In special
applications, a higher IP degree is required
The cable between terminal 37 and the external
•
safety device must be short circuit protected
according to ISO 13849-2 table D.4
When external forces influence the motor axis (for
•
example, suspended loads), additional measures
are required (for example, a safety holding brake)
to eliminate potential hazards
Safe Stop Installation and Set-up
It is not recommended to stop the adjustable
•
frequency drive by using the Safe Torque Off
function. If a running adjustable frequency drive
is stopped by using the function, the unit trips
and stops by coasting. If unacceptable or
dangerous, use another stopping mode to stop
the adjustable frequency drive and machinery,
before using this function. Depending on the
application, a mechanical brake can be required.
For synchronous and permanent magnet motor
•
adjustable frequency drives, in a multiple IGBT
power semiconductor failure: In spite of the
activation of the Safe Torque Off function, the
system can produce an alignment torque which
maximally rotates the motor shaft by 180/p
degrees. p denotes the pole pair number.
This function is suitable for performing
•
mechanical work on the system or affected area
of a machine only. It does not provide electrical
safety. Do not use this function as a control for
starting and/or stopping the adjustable frequency
drive.
Follow these steps to perform a safe installation of the
adjustable frequency drive:
1.Remove the jumper wire between control
terminals 37 and 12 or 13. Cutting or breaking
the jumper is not sufficient to avoid shortcircuiting. (See jumper on Figure 2.21.)
2.Connect an external Safety monitoring relay via a
NO safety function to terminal 37 (safe stop) and
either terminal 12 or 13 (24 V DC). Follow the
instructions for the safety device. The Safety
monitoring relay must comply with Category
3 /PL “d” (ISO 13849-1) or SIL 2 (EN 62061).
WARNING
SAFE STOP FUNCTION!
The safe stop function does NOT isolate AC line voltage to
the adjustable frequency drive or auxiliary circuits. Perform
work on electrical parts of the adjustable frequency drive
or the motor only after isolating the AC line voltage supply
and waiting the length of time specified in Table 1.1.
Failure to isolate the AC line voltage supply from the unit
and waiting the time specified could result in death or
serious injury.
2-14MG33AM22 - VLT® is a registered Danfoss trademark
12/13
37
130BA874.10
130BC971.10
12
2
4
1
5
3
37
Installation
Figure 2.21 Jumper between Terminal 12/13 (24 V) and 37
VLT® AutomationDrive Instruction
Manual
WARNING
Safe Stop activation (that is removal of 24 V DC voltage
supply to terminal 37) does not provide electrical safety.
The Safe Stop function itself is therefore not sufficient to
implement the Emergency-Off function as defined by EN
60204-1. Emergency-Off requires measures of electrical
isolation, for example, by switching off line power via an
additional contactor.
1.Activate the Safe Stop function by removing the
24 V DC voltage supply to the terminal 37.
2.After activation of Safe Stop (that is, after the
response time), the adjustable frequency drive
coasts (stops creating a rotational field in the
motor). The response time is typically less than 10
ms.
The adjustable frequency drive is guaranteed not to restart
creation of a rotational field by an internal fault (in
accordance with Cat. 3 PL d acc. EN ISO 13849-1 and SIL 2
acc. EN 62061). After activation of Safe Stop, the display
shows the text ”Safe Stop activated”. The associated help
text says, "Safe Stop has been activated”. This means that
the Safe Stop has been activated, or that normal operation
has not been resumed yet after Safe Stop activation.
2
2
Figure 2.22 Installation to Achieve a Stopping Category 0 (EN
60204-1) with Cat. 3 /PL “d” (ISO 13849-1) or SIL 2 (EN 62061).
1Adjustable frequency drive
2[Reset] key
3Safety relay (cat. 3, PL d or SIL2
4Emergency stop button
5Short-circuit protected cable (if not inside installation IP54
cabinet)
Table 2.9 Legend to Figure 2.22
Safe Stop Commissioning Test
After installation and before first operation, perform a
commissioning test of the installation using safe stop. Also,
perform the test after each modification of the installation.
NOTE!
The requirements of Cat. 3 /PL “d” (ISO 13849-1) are only
fulfilled while 24 V DC supply to terminal 37 is kept
removed or low by a safety device which itself fulfills Cat.
3 PL “d” (ISO 13849-1). If external forces act on the motor,
it must not operate without additional measures for fall
protection. External forces can arise for example, in the
event of vertical axis (suspended loads) where an
unwanted movement, for example caused by gravity, could
cause a hazard. Fall protection measures can be additional
mechanical brakes.
By default the Safe Stop function is set to an Unintended
Restart Prevention behavior. Therefore, to resume
operation after activation of Safe Stop,
1.reapply 24 V DC voltage to terminal 37 (text Safe
Stop activated is still displayed)
2.create a reset signal (via bus, digital I/O, or
[Reset] key.
The Safe Stop function can be set to an Automatic Restart
behavior. Set the value of 5-19 Terminal 37 Safe Stop from
default value [1] to value [3].
Automatic Restart means that Safe Stop is terminated, and
normal operation is resumed, as soon as the 24 V DC are
applied to Terminal 37. No Reset signal is required.
MG33AM22 - VLT® is a registered Danfoss trademark2-15
Installation
VLT® AutomationDrive Instruction
Manual
2
WARNING
Automatic Restart Behavior is permitted in one of the two
situations:
1.Unintended restart prevention is implemented by
other parts of the safe stop installation.
2.A presence in the hazard zone can be physically
excluded when safe stop is not activated. In
particular, paragraph 5.3.2.5 of ISO 12100-2 2003
must be observed
2.5.2 Safe Stop Commissioning Test
After installation and before first operation, perform a
commissioning test of an installation or application, using
Safe Stop.
Perform the test again after each modification of the
installation or application involving the Safe Stop.
NOTE!
A passed commissioning test is mandatory after first installation and after each change to the safety installation.
The commissioning test (select one of cases 1 or 2 as
applicable):
Case 1: Restart prevention for Safe Stop is required (that is
Safe Stop only where 5-19 Terminal 37 Safe Stop is set to
default value [1], or combined Safe Stop and MCB 112
where 5-19 Terminal 37 Safe Stop is set to [6] PTC 1 & RelayA or [9] PTC 1 & Relay W/A):
1.1 Remove the 24 V DC voltage supply to
terminal 37 using the interrupt device while the
adjustable frequency drive drives the motor (that
is line power supply is not interrupted). The test
step is passed when
the motor reacts with a coast, and
•
the mechanical brake is activated (if
•
connected)
the alarm “Safe Stop [A68]” is displayed
•
in the LCP, if mounted
1.2 Send Reset signal (via bus, digital I/O, or
[Reset] key). The test step is passed if the motor
remains in the safe stop state, and the
mechanical brake (if connected) remains
activated.
1.3 Reapply 24 V DC to terminal 37. The test step
is passed if the motor remains in the coasted
state, and the mechanical brake (if connected)
remains activated.
1.4 Send Reset signal (via bus, digital I/O, or
[Reset] key). The test step is passed when the
motor becomes operational again.
The commissioning test is passed if all four test steps 1.1,
1.2, 1.3 and 1.4 are passed.
Case 2: Automatic Restart of Safe Stop is wanted and
allowed (that is, Safe Stop only where 5-19 Terminal 37Safe Stop is set to [3], or combined Safe Stop and MCB
112 where 5-19 Terminal 37 Safe Stop is set to [7] PTC 1 &Relay W or [8] PTC 1 & Relay A/W):
2.1 Remove the 24 V DC voltage supply to
terminal 37 by the interrupt device while the
adjustable frequency drive drives the motor (that
is line power supply is not interrupted). The test
step is passed when
the motor reacts with a coast, and
•
the mechanical brake is activated (if
•
connected)
the alarm “Safe Stop [A68]” is displayed
•
in the LCP, if mounted
2.2 Reapply 24 V DC to terminal 37.
The test step is passed if the motor becomes operational
again. The commissioning test is passed if both test steps
2.1 and 2.2 are passed.
NOTE!
See warning on the restart behavior in 2.5.1 Terminal 37
Safe Stop Function
WARNING
The Safe Stop function can be used for asynchronous,
synchronous and permanent magnet motors. Two faults
can occur in the power semiconductor of the adjustable
frequency drive. When using synchronous or permanent
magnet motors a residual rotation can result from the
faults. The rotation can be calculated to Angle = 360/
(Number of Poles). The application using synchronous or
permanent magnet motors must take this residual rotation
into consideration and ensure that it does not pose a
safety risk. This situation is not relevant for asynchronous
motors.
2-16MG33AM22 - VLT® is a registered Danfoss trademark
Loading...
+ 78 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.