Danfoss Electronics ERC 112 Installation Guide

DKRCE.PI.RL0.A2.02
520H10340
23
14
Installation Guide
ERC 112
Bottle Cooler Controller
Technical specification
Power Supply 100 – 240 V AC Switch mode power supply. Average 0.7 W
Input
Output
Probes
Connectors
Programming Programming with Danfoss KoolProg, KoolKey and KoolDock
Assembly
5 inputs: 4 analogue (digital), 1 digital; user specific assignment
• Air / Evaporator / Condenser • Door sensor: all types, user specific
• Light sensor: Danfoss ECO light sensor
"DO1" (Compressor relay)
"DO4"
"DO5" FLA 2 / LRA 12, TV-1 8 A resistive, 2(2) A "DO6" FLA 2 / LRA 12, TV-1 8 A resistive, 2(2) A
• Danfoss NTC sensors and Danfoss ECO accessories
• Danfoss PT1000 ohm / 0°C
• Modular connector system for OEM customers, with optional output screw terminal adapter
• Input connector type: Rast2 5 Edge connectors
• output connector type: RAST 5 standard
3 types for all controls: front mounting; brackets; fully integrated solution (requires OEM specific design of mounting hole)
UL60730 EN60730 120 V AC: 16 A resistive / FLA 16/LRA 72
240 V AC: 10 A resistive / FLA 10 / LRA 60 8 A resistive, FLA 2 / LRA 12, TV-1
• Motion sensor
16(16) A
8 A resistive, 2(2) A
Max 10 A total "DO4-6"
Display LED display, 3 digit, decimal point and multi functionality icons; °C / °F scale Keypad 4 buttons (integrated IP65 design), 2 left, 2 right; user programmable Operating Conditions Storage Conditions Range of Measurement
Protection
Environmental Pollution degree II, non-condensing Resistance to heat & fire EMC category Category I Operating Cycles Compressor relay: more than 175.000 at full load (16 A (16 A))
Approvals
0 °C – 55 °C, 93% rH
-40 °C – 85 °C, 93% rH
-40 °C – 85 °C
Front: IP65 Rear: water and dust protection corresponds to IP31, accessibility of connectors limit rear part rating to IP00
Category D (UL94-V0)
• R290 / R600a end-use applications employing in accordance to EN / IEC 60335-2-24, annex CC and EN / IEC 60335-2-89, annex BB
• Glow wire according to EN / IEC 60335-1 / IEC / EN 60730
• UL60730
• NSF
• CQC
• EAC
• Ukraine
• These approvals are only valid when using the accessories approved
Dimensions
36.5 mm
28 mm
78.25 mm
78.25 mm
71 mm
28.5 mm
Front mounting
(Lock with frame)
82.25 mm
71 mm
30 mm
Rear mounting
(Lock with clips)
Functional description of used sensors
Control temperature sensor
The control sensor must always be connected and is used for controlling the cut-in and cut-out of the compressor according to the set-point. The sensor is also used for the displayed temperature. Most common placement is in the return air to the evaporator.
Evaporator sensor
The evaporator sensor is only used for de-icing of the evaporator and has no control purpose. Place the sensor where the ice melts last. Please be aware of that sharp fins can damage the cable.
Condenser temperature sensor
The condenser sensor is used to protect the compressor against high pressure when the condenser is blocked or the condenser fan fails. Place the sensor at the liquid side of the condenser. Use a metal bracket or metal tape to ensure good thermal conductivity. Be sure that the cable does not pass hot spots at the compressor or condenser that exceeds 80 °C.
ERC front and button functionality
Configurable functionality
Button
1 press OK 1 pess and hold 2 press BACK 2 pess and hold 3 press UP 3 pess and hold 4 press DOWN 4 pess and hold
Configurable functionality
Button
1 press 1 pess and hold 2 press 2 pess and hold 3 press 3 pess and hold 4 press 4 pess and hold
Basic
function
Toggle
ECO
operating
Toggle
pull-
down
Not
Increase
display
intensity
ON/OFF
Decrease
intensity
Increase setpoint
display
Decrease
setpoint
Toggle °C or °F
Enter
holiday
Toggle
defrost
Toggle
winter/
summer
Toggle
light
Info
menu
Wiring diagram
ERC 112D
100 – 240 V AC ± 10% 50/60 Hz 0T55
Outputs
1
2 3 4 5 6 1
DO1
LNDO2 DO3 DO4
Inputs
Configuration of outputs
Relay
outputs
DO1 (o1C) DO2 (o2C) DO3 (o3C) DO4 (o4C)
Compress. Defrost Fan Light Alarm
Configuration of inputsConfiguration of inputs
Input/ sensor
Cabinet
sensor
S1 S2 S3 S4
di
Evapor.
sensor
Conden.
sensor
ERC 112C
100 – 240 V AC ± 10% 50/60 Hz 0T55
Outputs
2 3 4 5
DO1
LNDO2 DO3
Inputs
S1 S2 S3 S4 di
Door
sensor
Light
sensor
Movem.
sensor
Heating
application
Comm.
Menu structure Operation Changing the setpoint:
Press and hold 5 sec to access the menu
1. Parameter group
Lower left button
1. Parameter name Lower left button
Two kinds of left buttons - see pictures 1. and 3.
Current temperature
1.
Flashing temperature setpoint
2.
3.
Activating manual defrost
Scroll through menu group
Scroll through parameters
Press briefly to start or stop defrost
1.
2.
SC
3.
SC
^ ^
^ ^
The display shows the current temperature
Press: UP/DOWN to adjust setup
After 30 seconds, the display automatically reverts to showing the current temperature
Defrost symbol is shown in defrost mode
Defrost symbol will disappear after the defrost is finished. (The dEF text during the defrost is displayed or not based on the cabinet manufacturer settings)
Example of changing a parameter Turning ON/OFF the ECO function
To select: press the lower
left button (OK)
To confirm: press the lower
To accept: press the lower left
press the upper left button (BACK)
To return to parameter group:
press upper left button (BACK)
left button (OK)
button (OK) and return to
parameter name
To exit without accept:
1.
2.
Scroll through parameters group
3.
4.
Scroll through group "dEF" parameters
5.
6.
7.
8.
Press and hold 5 sec to access the menu
Press: UP / DOWN to scroll through the menu
Press: UP / DOWN to find the desired parameter
Press: UP / DOWN to enter the desired value
Press briefly to enter
ECO mode
Password protection
Press and hold 5 sec to access the menu
Acknowledging alarm
1.
2.
1.
2.
The alarm code flashing alternately with the temperature and the alarm symbol is displayed
After the acknowledge the temperature is displayed and the alarm symbol remains shown
ECO
The green ECO symbol is list when in ECO mode
Password protection on three levels: LEVEL 1: shop (daily use by shop personnel) LEVEL 2: ser (service technician) LEVEL 3: OEM (OEM programming
Press any button to acknowlege
© Danfoss | ADAP-KOOL | 2018.05
DKRCE.PI.RL0.A3.02 / 520H10340
press upper left button (BACK)
To return to menu:
9.
After 30 seconds of inactivity, the display automatically reverts to showing the current temperature
Parameter table
Menu Parameter name
Thermostat tHE Main menu for thermostatic settings
Set point SEt Set point value 2.0 -100.0 200.0 °C Set point adjustment ratio SPr Actual value of setpoint. Adjustment = diF * SPr 0.5 0.0 1.0 Differential diF Thermostat differential for serving 2.0 0.0 20.0 K High Set point HSE High limitation of thermostat setpoint in position warm 50.0 -100.0 200.0 °C Low Set point LSE Low limitation of thermostat setpoint in position cold -35.0 -100.0 200.0 °C
Initial cut in iCi
Seasonal offset temperature SP2
Seasonal differential dF2
Fan FAn Main menu for fan settings
Fan control method FCt
Fan On Delay Fod Delay for fan start after compressor cutin 0 0 240 Sec Fan Stop delay FSd Delay for fan stop after compressor cutout 0 0 240 Sec Fan On Cycle FoC On time for fan during compressor off period 0 0 960 Sec Fan Stop Cycle FSC Stop time for fan during compressor off period 0 0 960 Sec Fan Minimum Stop time FSt Minimum Stop time for fan protection 10 0 960 Sec
Δt for fan to cut in FdC
Fan delay on door open Fdt
Fan limit temperature FLt
Fan limit Delta temperature Fd F
Light Lig Main menu for Light settings
Cabinet Light Control Source CLC
Pull Down Pud Main menu for pull-down settings
Light off delay Lod Delay to turn off the cabinet light after door close. 0=No delay 0 0 300 Sec
Pull-down Initiate Temperature Pit
Pull-down Cycling PCy
Pull-down defrost Interval Pdi
Pull-down duration Pdd Max time for pull-down mode from initiated till terminated 24 0 48 hour
Pull-down limit temp PLt
Pull-down reduction temp Δt Prt
Defrost dEF Main menu for Defrost settings
Defrost type dFt
Adaptive defrost Add
Def terminate temp dtt Defrost stop temperature 6.0 0.0 25.0 °C
Def reset temp drt
Def Min Interval dii Minimum Interval between defrost starts 6 1 96 hour Def Max Interval dAi Maximum Inter val between defrost starts 7 1 96 hour Def Min Time dit Minimum defrost time 5 0 240 min Def Max time dAt Maximum defrost time 30 0 480 min Drip off time dot Dr ip off delay time 0 0 60 min Fan delay after Defrost Fdd D elay for fan start after defrost 0 0 600 sec
Fan start Temp Ftd
Defrost Fan on dFA Fan cutin during defrost no no yES
Defrost on compressor time dCt
Defrost by compressor running time
Defrost start evaporator temperature
Defrost Δt ddt
Initial Defrost Interval idi First time defrost after power-up 3 0 96 hour
Initial Defrost Duration idd
Compressor CoP Main menu for Compressor timer settings
Voltage protection uPt
Minimum Cutin voltage uLi Compressor must not be cut in if power supply goes lower than 0 0 270 Vac Minimum cut-out voltage uLo Compressor must be cut out if power supply goes lower than 0 0 270 Va c
Maximum voltage uHi
Sensor Error Type EHd
Error run time Er t Run time for compressor in case of control probe error 0 0 60 min Error stop time ESt Stop time for compressor in case of control probe error 1 0 60 min Min Stop time CSt Minimum OFF time for compressor 2 0 30 min Min run time Crt Minimum ON time for compressor 0 0 30 min Max Off time Cot Maximum OFF time for compressor 0 0 480 min Compressor door open delay Cd d Door open delay to stop compressor. 0 = Disable 0 0 15 min System resume after door open Srt Fan and Compressor resume after cut out by door open. 0=Disable 0 0 60 min Power On Delay Pod Delay time from power on until the outputs are activated 300 0 300 Sec
Power-on temperature Pot
Condenser Protection
Condenser Alarm Limit CAL
Condenser Block Limit CbL
Condenser OK limit CoL
Condenser Low Temp. Limit CLL
Menu
Description Def Min Max Unit
code
Comp relay action when Tair is between Cut-in and Cut-out at power-up yES: Cut in the compressor no: Cut out the compressor
Offset value for set point and alarms when the seasonal offset button is activated.
Temperature differential during seasonal offset mode. This diffe­rential not applicable during ECO mode.
FAo: Fan always on SEt: Fan follow compressor by manually settings Aut: Automatical Fan control
Delta T for fan to cut in which the temperature offset comparing with thermostat cut in temperature
0: Fan stop immediately when door open 1~998: delay for fan stop after door open 999: fan keep running all the time during door opening
This parameter defines the maximum evaporator temperature at which the Fan must switch OFF.
This is the evaporator delta temperature for the fan to switch ON after it is switched off due to FLt setting.
on: Always ON (Button is default to control light for all these options) oFF: Always OFF dor: Door sensor only
Temperature measured by control-sensor that will trigger the pull-down mode
The duration of the thermostatic operation at pull-down mode The periode will start first time the controller reaches the PCt
Defrost interval during pull-down Over-rules the defrost interval in normal mode
The calculated cutout temp for pulldown mustn't lower than this limit to prevent freezing of product
This progressive temp value is used for calculating cutin temp and cutout temp for Pull-down mode: Pulldown-Cutin = NormalCutin - Δt * Hours Pulldown-Cutout = NormalCutout - Δt * Hours
no: Defrost function is disabled nAt: Natural defrost. time defrost EL: Electrical heater Hgd: Hot gas defrost
no: Defrost controlled by time yES: Automatic defrost control activated
Defrost timer reset temperature 0-199: normal evaluation between evaporator/air temp and drt 200: disable drt function
Fan start temperature after defrost. it's based on evaporator temperature. This only applies if an evaporator temperature sensor is fitted
no: Elapsed time yES: Accumulated compressor run time
Continuous compressor running can cause defrost
doC
0: Deactived
dEt Defrost star t trigger for adaptive defrost -50.0 -50.0 0.0 °C
Defrost Δt compare with evporator temperature of first cut out after defrost to trigger defrost start
Determine defrost or not while startup by relay1 counter 0: Disable idi function 1-998: Normal evaluation between idd and relay 1 counter 999: idi is always enabled
no: No voltage protection yES: Voltage protection activated based on voltage related settings
Maximum supply voltage for the compressor to postpone startup or stop at
no: No sensor error handling SEt: In case of control sensor error, follow error run/stop time
If Air temperature at power up is higher than this, power on delay is overruled
Con Blocked condenser protection.
Alarm limit for condenser temperature Available only if condensor sensor is attached / assigned
Stop limit. If this temperature is exceeded, compressor must be stopped Available only if condensor sensor is attached/assigned
OK limit. Compressor is allowed to start again if the condenser temperature is lower than this temperature Available only if condensor sensor is attached / assigned
Low limit. Compressor is not allowed to start if the condenser temperature is lower than this temperature Available only if condensor sensor is attached / assigned
no no yES
0 -25 25 K
2 0 20 K
FAo FAo Aut
0.0 -10.0 10.0 K
0 0 999 Sec
50 0 50 °C
2 1 10 K
on on dor
50.0 -40.0 50.0 °C
30 0 360 min
15 0 48 hour
0.0 -55.0 55.0 °C
0.1 0.0 10.0 K
no no Hgd
no no yES
5.0 0.0 200.0 °C
25.0 -25.0 25.0 °C
no no yES
0 0 24 hour
5.0 0.0 30.0 K
100 0 999 cycle
no no yES
270 0 270 Vac
no no SEt
-100 -100 200 °C
80 0 200 °C
85 0 200 °C
60 0 200 °C
-5 -100 20 °C
Current
Menu Parameter name
setting
Display diS Display settings
Display intensity auto control diC
Display Intensity din
Display Unit CFu C=Celsius. F=Fahrenheit -C -C -F
Temp sensor to display trS
Display Resolution rES
Display Range Limit rLt
Display Delay ddL
Display Offset doF Correction for bad sensor placement. Value at 0 °C 0.0 -10.0 10.0 K
Lock-time After defrost dLt
Show Economy/Night Mode SEC
Show Pull Down SSC
Show Holiday SHo
Show Defrost SdF
Show compressor symbol SCS
Show Fan symbol SFS
Show Defrost symbol SdS
Show ECO symbol SES
Minimum Display value Ld
Maximum display value Hd
Alarm ALA Main menu for alarm settings
Signalling threshold value St Temperature limit for Maximum display visualization 200 -100.0 200-0 °C
High Temp Alarm HAt High alarm limit 15.0 -100.0 200.0 °C Low Temp Alarm LAt Low alarm limit -50.0 -100.0 200.0 °C High Alarm delay H td Alarm delay time for high-temperature alarm 30 0 240 min Low Alarm delay Ltd Alarm delay time for low-temperature alarm 0 0 240 min
Pulldown delay Pdd
Door Open delay dod Alarm delay on open door Alarm. 0=Disable 2 0 60 min
Voltage alarm uAL
Leakage alarm LEA Leakage detection for compressor protection. 0=Disable 0 0 96 hour
Alarm Buzzer Duration Abd
Auto Clearance of Alarm ACA
Auto­Heater Control
ECO strategy
Automatic heater mode enable
Energy mode delay End Delay between heater and compressor operation 60 0 360 min Auto Heat set point AHS Heater Set point: the set point of auto heating 2.0 -100.0 200.0 °C Auto heat differential AHd Thermostat differential for auto heatting 2.0 0.0 20.0 K
ECO on / off ECo
Door Actions EdA Times of door action to trigger exiting ECO 1 1 10 Pir Actions EPA Times of PIR action to trigger exiting ECO 1 1 10
Action counter time ECt
Door delay Edd Door delay after door close to trigger entering ECO 180 0 180 min Pir delay EPd PIR delay to trigger entering ECO 120 0 180 min
Shop Light Day S Ld
Shop Light Night SLn
Time to pull down tto
Light Source delay on ECO LSd
EWU active on / off
Shop close hour CLH
Early wake up time offset ErL
Holiday Length HoL
ECO manag. ECA Main menu for ECO management
ECO Temperature Offset Eto
Holiday Temperature Offset Hto
ECO Differential diE Thermostat differential for ECO 2.0 0.0 10.0 K ECO Fan on cycle Fo E On time for fan during compressor off period in ECO mode 0 0 960 Sec ECO Fan stop cycle FSE Off time for fan during compressor off period in ECO mode 0 0 960 S ec
ECO Cabinet light control ELC
Eco Light delay ELd Delay from shop light is turned on or off till mode shift is allowed 5 0 10 min
Menu
Description Def Min Max Unit
code
no: Display intensity use fixed value yES: Display intensity controlled automaticlly by ambient light
Normal Intensity of display when no ambient light sensor is attached Minimum intensity when ambient light sensor is attached
SCo: Temperature control EuA: Evaporator temperture Con: Condenser temperature (Condenser cleaning) AuS: Only for showing on display
0.1: Decimal with 0.1 degree resolution
0.5: Decimal with 0.5 degree resolution 1: Integers
no: Disabled. display is allowed to go outside of ’ThSP - diF*SPr ~ ThSP + diF* (1 - SPr)’ yES: Enabled. display is not allowed to go outside of ’ThSP - diF*SPr ~ ThSP + diF*(1 - SPr)'
Time-constant for averaging of temperature at display Temp value reaches 100 % when 5 * ddL expires
In order not to show a rising temperature during defrosting, the displayed temperature is locked at the temperature shown at the start of the defrost cycle for the number of minutes set in this parameter. 0=No lock
no: "ECo" and "ngt" will not be showed for Economy / Night Mode yES: "ECo" or "ngt" will be displayed through whole Economy / Night Mode
no: "SC" will not be showed for Pull down state yES: "SC" will be displayed through whole Pull down state
no: Display will show temperature or ECO mode during holiday mode yES: Display will show "HoL" during holiday mode
no: Display will show temperature during defrost yES: Display will show dEF during defrost
no: Compressor symbol will not show on display yES: Show compressor symbol on display
no: Fan symbol will not show on display yES: Show fan symbol on display
no: Defrost symbol will not show on display yES: Show defrost symbol on display
no: ECO symbol will not show on display yES: Show ECO symbol on display
Temperature displayed by the controller, if the probe value is less than minimum display value.
Temperature displayed by the controller if the probe value is between Maximum display and Signaling threshold value and the trend of the probe is increasing
Alarm delay time during & after defrost and after power up (Only for high-temp. alarm)
no: No voltage alarm yES: Voltage alarm activated
0: Buzzer is off [0. 999]: Buzzer will continue for the time set by the parameter in minutes in which process the sound format is such as IIIIIIII______________________IIIIIIIIII_____ 999: Buzzer continues for ever with IIIIIIIII______________________IIIIIIIIII__________ and so on
no: Disable this function; alarm status will not disappear automatically without acknowledge by user even if the alarm recovers yES: Enable this function; alarm status can change from active to inactive automatically on condition that the alarm recovers (Errors are always auto-clearance enabled)
Main menu for Street cooler settings
AHC
(Street-Cooler : Coolers placed in the street with frost protection )
yES: Heater will be active if air-temperature is too low
AuH
no: Normal operation
ECS Main menu for ECO strategy
Eco active or not If no all other settings are not active
Door action or PIR action within action counter time can trigger exiting ECO
Shop light level during opening hours When above this level ECO mode is canceled Disabled if no light sensor connected/assigned
Shop light level during closing hours When below this level ECO mode is enabled Disabled if no light sensor connected/assigned
Time which ERC stay in ECO and holiday mode to decide to enter Pull down or Serving mode
Time delay for light source to change from serving mode source to ECO mode source
Euu Enable or disable early wake up yES no yES
Shop is assumed to be closed when staying in ECO mode longer than shop close hour
Time of exiting ECO mode for next day: Time of first activity to exit ECO mode - the Early wake-up time 0: Early wake up function disabled
In case that no activity has been registered for a number of days specified by the Holiday, the Early-wake-up is deactivated and the cooler must stay in Holiday mode until activity is detected
If this offset is below zero, it means that Night mode will be activated instead of ECO mode
Increase or decrease of temperature with respect to normal mode during Holiday mode
on: Always ON (Button is default to control light for all these options) oFF: Always OFF dor: Door sensor only
no no yES
10 2 10
SCo SCo AuS
0.1 0.1 1
no no yES
0 0 10 min
15 0 60 min
no no yES
no no yES
no no yES
yES no yES
yES no yES
yES no yES
yES no yES
yES no yES
-100 -100.0 200.0 °C
200 -100.0 200.0 °C
240 0 960 min
no no yES
0 0 999 min
yES no yES
no no yES
yES no yES
30 0 180 min
5 0 80
3 0 80
0 0 168 hour
0 0 180 min
6 0 24 hour
120 0 240 min
72 0 999 hour
4.0 -25.0 25.0 K
6.0 -25.0 25.0 K
on on dor
Current
Menu Parameter name
setting
Assign. ASi Assignment of inputs and outputs
MODBUS Safety uSA
Temp Adj. for S1 t1A Adjust value for sensor1 before being used by application 0.0 -20.0 20.0 K Temp Adj. for S2 t2A Adjust value for sensor2 before being used by application 0.0 -20.0 20.0 K Temp Adj. for S3 t3A Adjust value for sensor3 before being used by application 0.0 -20.0 20.0 K Temp Adj. for S4 t4A Adjust value for sensor4 before being used by application 0.0 -20.0 20.0 K
S1/S2/S3 Config
S4 Config S4C
S1/S2/S3 Application
S4 Application S4A
DI Config diC
DO1 Config o1C
DO2 Config o2C
DO3 Config o3C Same as DO2 Config FAn 0 Lig DO4 Config o4C Same as DO2 Config Lig 0 Lig
Button 1 Short Config
Button 1 Long Config
Button 4 Short Config b4C Config of key 4 short. Lower right. As key 1 short tn noP C FA
Button 4 Long Config b4L
Button 5 Short Config b5C
Button 5 Long Config b5L
Pass-word level1 PS1
Pass-word level2 PS2
Pass-word level3 PS3
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed. All trademarks in this material are property of the property of the respective companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Menu
Description Def Min Max Unit
code
no: MODBUS auto detection is enabled yES: MODBUS communication is deactivaed
Sensor type used for sensor input 1/2/3
S1C
Stn: Standard NTC 5k @ 25 °C (EKS211) in Celsius
S2C
Htn: High temperature NTC 100k @ 25 °C in Celsius
S3C
Ldr: Light sensor(LDR). Luminens dig: Digital input. On / Off
Stn: Standard NTC 5k @ 25 °C (EKS211). in Celsius Htn: High temperature NTC 100k @ 25 °C. in Celsius Pt1: PT1000 sensor 1000K @ 0 °C. in Celsius Ldr: Light sensor(LDR). Luminens dig: Digital input. On / Off
Select the function to be controlled via the Sensor 1 / 2 / 3 nC: Not connected SCo: Temperature control EuA: Evaporator temperture
S1A
Con: Condenser temperature (Condenser cleaning)
S2A
AuS: Only for showing temperature on display
S3A
Ldr: Light sensor(LDR). Luminens ECo: External input to control ECO mode doC: Door contact. Contact closed when door closed doo: Door contact. Contact open when door closed
Select the function to be controlled via the Sensor 4 input nC: Not connected SCo: Temperature control EuA: Evaporator temperture Con: Condenser temperature (Condenser cleaning) AuS: Only for showing temperature on display Ldr: Light sensor (LDR). Luminens ECo: External input to control ECO mode doC: Door contact. Contact closed when door closed doo: Door contact. Contact open when door closed bt5: Button5
Select the function to be controlled via the digital I/O non: Not used. (If communication is available depending on MODBUS safety) doC: Door contact. Contact closed when door closed doo: Door contact. Contact open when door closed ECo: External input to control ECO mode Pir: Movement sensor (Passive infrared)
CoP: Compressor (With ZeroCrossing) PiC: Pilot compressor (No ZeroCrossing) HEt: Inverse output. Heating application (With ZeroCrossing) PiH: Pilot Heat relay (No ZeroCrossing)
no: Not used dEF: Electric defrost heater / Valve for hot gas ALA: Alarm output FAn: Fan control Lig: Light control
Config of key 1 short. Lower left noP: Not operating tP: Increase Setpoint tn: Decrease setpoint
b1C
ECo: Toggle Eco mode
b2C
Lig: Toggle light
b3C
dEF: Toggle defrost SuP: Toggle Super-Cool /Pull-down diP: Increase display intensity din: Decrease display intensity CFA: Toggle Celsius and Fahrenheit
Config of key 1 long. lower left noP: Not operating tP: Increase Setpoint tn: Decrease setpoint ECo: Toggle Eco mode Lig: Toggle light
b1L
dEF: Toggle defrost
b2L
SuP: Toggle Super-Cool /Pull-down
b3L
diP: Increase display intensity din: Decrease display intensity CFA: Toggle Celsius and Fahrenheit PoF: ERC power ON/OFF HoL: Enter holiday mode inF: Enter Info menu “tEc”: Toggle Winter & Summer Eco mode
Config of key 4 long. Lower right noP: Not operating tP: Increase Setpoint tn: Decrease setpoint tn: Decrease setpoint ECo: Toggle Eco mode Lig: Toggle light dEF: Toggle defrost SuP: Toggle Super-Cool /Pull-down diP: Increase display intensity din: Decrease display intensity CFA: Toggle Celsius and Fahrenheit PoF: ERC power ON/OFF HoL: Enter holiday mode “tEc”: Toggle Winter & Summer Eco mode
Config of key 5 short. Lower right noP: Not operating ECo: Toggle Eco mode SuP: Toggle Super-Cool / Pull-down Lig: Toggle light dEF:Toggle defrost
Config of key 5 long. Lower right noP: Not operating ECo: Toggle Eco mode SuP: Toggle Super-Cool / Pull-down Lig: Toggle light dEF: Toggle defrost PoF: ERC power ON / OFF HoL: Enter holiday mode
Shop owner Most common parameters for instance real time clock. day / night mode etc. 0: Disabled
Service technician all parameters with read permission and possibility to change a number of parameters like defrost, fan etc. 0: Disabled
OEM Customer All parameters read and write permission. But with some restriction to for instance reset statictical information 0: Disabled
no no yES
Stn Stn dig
Stn Stn dig
SCo nC doo
nC nC bt5
non non Pir
CoP CoP Pi H
dEF 0 Lig
noP noP CFA
PoF noP InF
Lig noP HoL
noP noP dEF
noP noP HoL
0 0 999
0 0 999
0 0 999
Current
setting