Danfoss Electronics AK-CC 550A Installation Guide

Instructions
AK-CC 550A
Identification
Principle
Dimensions
084B8030
S2:
Insulate sensor Fühler isolieren Capteur isolés Isolér føleren Sensores aislados
AKV info !!
230 V a.c. spole 230 V a.c. coil 230 V a.c. Spule 230 V c.a. Bobine 230 V c.a. Bobina 230 V c.a. Bobine
AK-CC 550A
Additional information: English Manual
Weitere Information: Deutsches Manual
Renseignements supplémentarires: Manuel en français
Yderligere information: Dansk Manual
Información adicional: Manual español
Informazioni aggiuntive! Manuale in italiano
Ytterligare information: Svenska Handbok
Aanvullende informatie: Dutch Handleiding
RS8FS...
RI8NP702 2018-09
The controller is provided with signs from the factory indicating application 1. If you employ another use, signs are provided so that you can mount the relevant one.
Werkseitig wird der Regler mit Schildern geliefert, die Anwendung 1 angeben. Wenn Sie eine andere Anwendung verwenden, so montieren Sie bitte das entsprechende der mitgelieferten Schilder.
Les régulateurs sortis d’usine sont livrés avec une étiquette indiquant l’utilisation 1. Si vous optez pour une autre utilisation, des plaques sont jointes pour vous permettre de monter la plaque adéquate.
Fra fabrikken er regulatoren leveret med skilte, der angiver anvendelse 1. Hvis du benytter en anden anvendelse, er der medleveret skilte, så du kan montere det aktuelle.
1
1 - 8
2
3
4
2 Instructions RI8NP702 © Danfoss 2018-09 AK-CC 550A
5
6
7
9
8
9
10
10
AK-CC 550A Instructions RI8NP702 © Danfoss 2018-09 3
Data communication Datenkommunikation Transmission de données Datakommunikation
Important All connections to the data communication MODBUS and RS 485 must comply
with the requirements for data communication cables. See literature: RC8AC.
Wichtig Alle Anschlüsse an die Datenkommunikation MODBUS und RS 485 müssen die
Anforderungen erfüllen, die an Datenkommunikationskabel gestellt werden. Siehe Literatur: RC8AC
Important Tout raccordement au système de données MODBUS et à RS 485 doit satisfaire
à la norme applicable pour les câbles de transmission de données. Voir documentation : RC8AC
Vigtigt Alle tilslutninger til datakommunikationen MODBUS og RS 485, skal overholde
de krav, der stilles til datakommunikationskabler. Se litteratur: RC8AC
System manager / Gateway
Display EKA 163 / 164
L < 15 m
L > 15 m
AK-SM.... AKA 245 version 6.20+ /
AK-SM...
OEM
! Address: o03 > 0
4 Instructions RI8NP702 © Danfoss 2018-09 AK-CC 550A
Connections
English
Overview of outputs and applications.
See also electrical diagrams earlier in the instruction
DI1
Digital input signal. The defined function is active when the input is short-circuited/ opened. The function is defined in o02.
DI2
Digital input signal. The defined function is active when the input is short-circuited/ opened. The function is defined in o37.
Pressure transmitter
AKS 32R
Connect to terminal 30, 31 and 32. (Used cable 060G1034: Black=30, Blue=31, Brown=32) The signal from one pressure transmitter can be received by up to 10 controllers. But only if there are no significant pressure decreases between the evaporators to be controlled.
S2, S6
Pt 1000 ohm sensor
S6 / S5B / S3B, product sensor or defrost sensor B or air sensor B.
The application determines which.
S3, S4, S5
Pt 1000 ohm sensor or PTC 1000 ohm sensor. All have to be of the same type.
S3, air sensor, placed in the warm air before the evaporator S4, air sensor, placed in the cold air after the evaporator
(the need for either S3 or S4 can be deselected in the configuration)
S5, defrost sensor, placed on the evaporator
Application DO1 DO2 DO3 DO4 DO5 DO6 DI1 DI2 DI3 AI1 AI2 AI3 AI4 AI5 AI6
1
2
3
4
5
6
7
8
9
10
• •
• •
• •
• •
• •
suction
Blinds
heat
hotgas
2 1
• •
• •
• •
• •
• •
EKA Display
If there is be external reading/operation of the controller, display type EKA 163B or EKA 164B can be connected.
RS485 (terminal 51, 52, 53)
For data communication, but only if a data communication module is inserted in the controller. The module can be a LON RS485, DANBUSS or a MODBUS. Terminal 51 = screen Terminal 52 = A (A+) Terminal 53 = B (B-) (For LON RS485 and gateway type AKA 245 the gateway must be version 6.20 or higher.)
RJ45
For data communication, but only if a TCP/IP module is inserted in the controller. (OEM)
MODBUS
For data communication. Terminal 56 = screen Terminal 57 = A+ Terminal 58 = B­(Alternatively the terminals can be connected to an external display type EKA 163A or 164A, but then they cannot be used for data communication. Any data communication must then be carried out by one of the other methods.)
Supply voltage
230 V a.c., 50/60 Hz
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S5B
P0 S2 S3 S4 S5 S3B
AK-CC 550A Instructions RI8NP702 © Danfoss 2018-09 5
DO1
Connection of expansion valve type AKV or AKVA. The coil must be a 230 V a.c. coil.
DO2
Alarm
There is a connection between terminal 7 and 8 in alarm situations and when the controller is without power.
Rail heat and heating element in drip tray
There is connection between terminal 7 and 9 when heating takes place.
Night blind
There is connection between terminal 7 and 9 when the night blind is up.
Suction line valve
There is connection between terminal 7 and 9 when the suction line must be open.
DO6
Light relay
There is connection between terminal 17 and 18 when the light must be on.
Rail heat, Compressor 2
There is connection between terminal 17 and 19 when the function must be active.
DI3
Digital input signal. The signal must have a voltage of 0 / 230 V AC. The function is defined in o84.
Data communication
If data communication is used, it is important that the installation of the data communication cable is performed correctly. See separate literature No. RC8AC…
DO3
Refrigeration, Rail heat, Heat function, Defrost 2
There is connection between terminal 10 and 11 when the function must be active.
Heating element in drip tray
There is connection between terminal 10 and 11 when heating takes place.
DO4
Defrost
There is connection between terminal 12 and 14 when defrosting takes place.
Hot gas / drain valve
There is connection between terminal 13 and 14 during normal operation. There is connection between terminal 12 and 14 when the hot gas valves must open.
DO5
Fan
There is connection between terminal 15 and 16 when the fan is on.
Coordinated defrost via cable connections
Electric noise
Cables for sensors, DI inputs and data communication must be kept separate from other electric cables:
- Use separate cable trays
- Keep a distance between cables of at least 10 cm
- Long cables at the DI input should be avoided
Installation considerations
Accidental damage, poor installation, or site conditions, can give rise to malfunctions of the control system, and ultimately lead to a plant breakdown. Every possible safeguard is incorporated into our products to prevent this. However, a wrong installation, for example, could still present problems. Electronic controls are no substitute for normal, good engineering practice. Danfoss will not be responsible for any goods, or plant compo­nents, damaged as a result of the above defects. It is the installer's responsibility to check the installation thoroughly, and to fit the necessary safety devices. Special reference is made to the necessity of signals to the controller when the compressor is stopped and to the need of liquid receivers before the compressors. Your local Danfoss agent will be pleased to assist with further advice, etc.
Max. 10
The following controllers can be connected up in this way: EKC 204A, AK-CC 210, AK-CC 250, AK-CC 450, AK-CC 550_,
Refrigeration is resumed when all controllers have “released” the signal for defrost.
Coordinated defrost via data communication
The setting of controllers to coordinate their defrosting takes place in the gateway/system manager.
Refrigeration is resumed when all controllers have “released” the signal for defrost.
6 Instructions RI8NP702 © Danfoss 2018-09 AK-CC 550A
Operation
Display
The values will be shown with three digits, and with a setting you can determine whether the temperature is to be shown in °C or in °F.
Light-emitting diodes (LED) on front panel
The LED’s on the front panel will light up when the relevant relay is activated.
= Refrigeration = Defrost = Fan running
The light-emitting diodes will flash when there is an alarm. In this situation you can download the error code to the display and cancel/sign for the alarm by giving the top button a brief push.
The buttons
When you want to change a setting, the upper and the lower buttons will give you a higher or lower value depending on the button you are pushing. But before you change the value, you must have access to the menu. You obtain this by pushing the upper button for a couple of seconds - you will then enter the col­umn with parameter codes. Find the parameter code you want to change and push the middle buttons until value for the parameter is shown. When you have changed the value, save the new value by once more pushing the middle button.
Examples
Set menu
1. Push the upper button until a parameter r01 is shown
2. Push the upper or the lower button and find that parameter you want to change
3. Push the middle button until the parameter value is shown
4. Push the upper or the lower button and select the new value
5. Push the middle button again to freeze the value.
Cutout alarm relay / receipt alarm/see alarm code
• A short press of the upper button
If there are several alarm codes they are found in a rolling stack. Push the uppermost or lowermost button to scan the rolling stack.
Set temperature
1. Push the middle button until the temperature value is shown
2. Push the upper or the lower button and select the new value
3. Push the middle button again to conclude the setting.
Reading the temperature at defrost sensor (Or product sensor, if selected in o92.)
• A short press of the lower button
Get a good start
With the following procedure you can start regulation very quick­ly:
1 Open parameter r12 and stop the regulation (in a new and not
previously set unit, r12 will already be set to 0 which means stopped regulation.)
2 Select electrical connection based on the drawings on page 2
and 3
3 Open parameter o61 and set the electric connection number in
it
4 Now select one of the preset settings from the table
Auxiliary schedule for settings (quick-setup)
Preset settings (o62) 1 2 3 4 5 6
Temperature (SP)
Max. temp. setting (r02)
Min. temp. setting (r03)
Sensor signal for thermo­stat. S4% (r15) Alarm limit high (A13)
Alarm limit low (A14)
Sensor signal for alarm funct.S4% (A36) Interval between defrost (d03) Defrost sensor: 0=time, 1=S5, 2=S4 (d10) DI1 config. (o02)
Sensor signal for display view S4% (017)
Note: For applications 9 and 10 the sensor weighting for the S3/S4 sensors is not used for the
thermostat, alarm thermostat and display readings as the sensor uses are predefined.
Case Room
Defrost stop on Defrost stop on
time S5 time S5
2°C -2°C -28°C 4°C 0°C -22°C
6°C 4°C -22°C 8°C 5°C -20°C
0°C -4°C -30°C 0°C -2°C -24°C
100% 0%
8°C 6°C -15°C 10°C 8°C -15°C
-5°C -5°C -30°C 0°C 0°C -30°C
0% 100% 0%
6 h 6h 12h 8h 8h 6h
0 1 1 0 1 1
Case cleaning (=10) Door function (=2)
0%
5 Open parameter o62 and set the number for the array of preset-
tings. The few selected settings will now be transferred to the menu.
6 Select refrigerant via parameter o30
7 Open parameter r12 and start the regulation
8 Go through the survey of factory settings. The values in the grey
cells are changed according to your choice of settings. Make any necessary changes in the respective parameters.
9 For network. Set the address in o03
10 Send address to system unit:
• MODBUS: Activate scan function in system unit
• If another data communication card is used in the controller:
- LON RS485: Activate the function o04
Manuel start or stop of a defrost
• Push the lower button for four seconds.
(However, not at Application 6)
AK-CC 550A Instructions RI8NP702 © Danfoss 2018-09 7
Menu survey
Parameter EL-diagram page 2 or 3
Function Code 1 2 3 4 5 6 7 8 9 10
Normal operation
Temperature (setpoint) - - - 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 2
Thermostat
Differential r01 1 1 1 1 1 1 1 1 1 1 0.1 K 20 K 2
Max. limitation of setpoint setting Min. limitation of setpoint setting Adjustment of temperature indication
Temperature unit (°C/°F) Correction of the signal from S4
Correction of the signal from S3
Manual service, stop regulation, start regulation (-1, 0, 1) Displacement of reference during night operation Define thermostat function 1=ON/OFF, 2=Modulating Definition and weighting, if applicable, of thermostat sen-
sors - S4% (100%=S4, 0%=S3) Time between melt periods Duration of melt periods Temperature setting for thermostat band 2 . As differential
r02 1 1 1 1 1 1 1 1 1 1 -49°C 50°C 50 r03 1 1 1 1 1 1 1 1 1 1 -50°C 49°C -50 r04 1 1 1 1 1 1 1 1 1 1 -10 10 0
r05 1 1 1 1 1 1 1 1 1 1 0/°C 1/F 0/°C r09 1 1 1 1 1 1 1 1 1 1 -10 K 10 K 0
r10 1 1 1 1 1 1 1 1 1 1 -10 K 10 K 0 r12 1 1 1 1 1 1 1 1 1 1 -1 1 0
r13 1 1 1 1 1 1 1 1 1 1 -50 K 50 K 0 r14 1 1 1 1 1 1 1 1 1 1 1 2 1
r15 1 1 1 1 1 1 1 1 0 % 100 % 100
r16 1 1 1 1 1 1 1 1 1 1 0 hrs 10 hrs 1 r17 1 1 1 1 1 1 1 1 1 1 0 min. 30 min. 5 r21 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 2
use r01
Correction of the signal from S6 r59 1 1 1 1 1 1 1 1 -10 K 10 K 0 Definition and weighting, if applicable, of thermostat sen­sors when night cover is on. (100%=S4, 0%=S3)
Heat function
r61 1 1 1 1 1 1 1 1 0 % 100 % 100
r62 1 0 K 50 K 2
Neutral zone between refrigeration and heat function Time delay at switch between refrigeration and heat
r63 1 0 min. 240 min. 0
function
Alarms
Delay for temperature alarm
Delay for door alarm
Delay for temperature alarm after defrost
High alarm limit for thermostat 1
Low alarm limit for thermostat 1
High alarm limit for thermostat 2
Low alarm limit for thermostat 2
High alarm limit for sensor S6 at thermostat 1
Low alarm limit for sensor S6 at thermostat 1
High alarm limit for sensor S6 at thermostat 2
Low alarm limit for sensor S6 at thermostat 2
S6 alarm time delay With setting = 240 the S6 alarm will be omitted Alarm time delay or signal on the DI1 input
Alarm time delay or signal on the DI2 input
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)
A03 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 30 A04 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 60 A12 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 90 A13 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 8 A14 1 1 1 1 1 1 1 1 1 1 -50°C 50°C -30 A20 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 8 A21 1 1 1 1 1 1 1 1 1 1 -50°C 50°C -30 A22 1 1 1 1 1 1 1 1 -50°C 50°C 8 A23 1 1 1 1 1 1 1 1 -50°C 50°C -30 A24 1 1 1 1 1 1 1 1 -50°C 50°C 8 A25 1 1 1 1 1 1 1 1 -50°C 50°C -30 A26 1 1 1 1 1 1 1 1 0 min. 240 min. 240
A27 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 30 A28 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 30 A36 1 1 1 1 1 1 1 1 0 % 100 % 100
Delay for S6 (product sensor alarm) after defrost A52 1 1 1 1 1 1 1 1 0 min. 240 min. 90
Compressor
Min. ON-time c01 1 1 1 1 0 min. 30 min. 0 Min. OFF-time c02 1 1 1 1 0 min. 30 min. 0
Time delay for cutin of comp.2
c05 1 0 sec 999 sec 5
Defrost
Defrost method: 0=off, 1= EL, 2= gAs d01 1 1 1 1 1 1 1 1 1 1 0/off 2/gAs 1/EL Defrost stop temperature
Interval between defrost starts
Max. defrost duration
Displacement of time on cutin of defrost at start-up
Drip off time
Delay for fan start after defrost
Fan start temperature
Fan cutin during defrost
d02 1 1 1 1 1 1 1 1 1 1 0°C 50°C 6 d03 1 1 1 1 1 1 1 1 1 1 0 hrs/Off 240 hrs 8 d04 1 1 1 1 1 1 1 1 1 1 0 min. 360 min. 45 d05 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 0 d06 1 1 1 1 1 1 1 1 1 1 0 min. 60 min. 0 d07 1 1 1 1 1 1 1 1 1 1 0 min. 60 min. 0 d08 1 1 1 1 1 1 1 1 1 1 -50 °C 0 °C -5
d09 1 1 1 1 1 1 1 1 1 1 0 3 1 0: Stopped 1: Running 2: Running during pump down and defrost 3: Running but stops at the temperature set in d41
Defrost sensor: 0 =Stop on time, 1=S5, 2=S4, 3=Sx
d10 1 1 1 1 1 1 1 1 1 1 0 3 0 (Application 1-8 and 10: both S5 and S6. Application 9: S5 and S5B)
Pump down delay
d16 1 1 1 1 1 1 1 1 1 1 0 min. 60 min. 0 Drain delay (used at hot gas defrost only) d17 1 0 min. 60 min. 0
Max. aggregate refrigeration time between two defrosts
Heat in drip tray. Time from defrosting stops to heating
d18 1 1 1 1 1 1 1 1 1 1 0 hrs 48 hrs 0/OFF
d20 1 0 min. 240 min. 30 in the drip tray is switched off
Min.-value Max.-value
Factory
setting
SW = 2.0x
Actual
setting
8 Instructions RI8NP702 © Danfoss 2018-09 AK-CC 550A
Continued Code 1 2 3 4 5 6 7 8 9 10 Min. Max. Fac. Actual
Adaptive defrost:
d21 1 1 1 1 1 1 1 1 1 1 0 4 0 0=not active, 1=monitoring only, 2=skip allowed day, 3=skip allowed both day and night, 4=own assessment + all schedules
Time delay before opening of hot gas valve d23 1 0 min 60 min 0 Rail heat during defrost
0=off. 1=on. 2=Pulsating Max. duration of -d- in display d40 1 1 1 1 1 1 1 1 1 1 5 min. 240 min. 30 min.
Temperature limit for fan stop during defrost when d09 is set to 3
Injection control function
Max. value of superheat reference
Min. value of superheat reference
d27 1 1 1 1 1 1 1 0 2 2
d41 1 1 1 1 1 1 1 1 1 1 -20°C 20°C 0
n09 1 1 1 1 1 1 1 1 1 1 2°C 20°C 12
n10 1 1 1 1 1 1 1 1 1 1 2°C 20°C 3 MOP temperature. Off if MOP temp. = 15.0 °C n11 1 1 1 1 1 1 1 1 1 1 -50°C 15°C 15 Period time of AKV pulsation
Only for trained personnel
Max. limitation for the superheat reference when regulating with adaptiv liquid control Min. limitation for the superheat reference when regulating with adaptiv liquid control
n13 1 1 1 1 1 1 1 1 1 1 3 sec 6 sec 6
P86 1 1 1 1 1 1 1 1 1 1 1°C 20°C 3
P87 1 1 1 1 1 1 1 1 1 1 0°C 20°C 1
Fan
Fan stop temperature (S5)
Pulse operation on fans: 0=No pulse operation, 1=At
F04 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 50
F05 1 1 1 1 1 1 1 1 1 1 0 2 0 thermostat cuts out only, 2= Only at thermostat cut outs during night operation
Period time for fan pulsation (on-time + off-time) F06 1 1 1 1 1 1 1 1 1 1 1 min. 30 min. 5 On-time in % of period time F07 1 1 1 1 1 1 1 1 1 1 0 % 100 % 100
Real time clock
Six start times for defrost. Setting of hours. 0=OFF
Six start times for defrost. Setting of minutes. 0=OFF
Clock - Setting of hours
Clock - Setting of minute
Clock - Setting of date
Clock - Setting of month
Clock - Setting of year
Miscellaneous
Delay of output signals after power failure
Input signal on DI1. Function: 0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-signal). 5=ext.main switch. 6=night operation 7=thermostat band changeover (activate r21). 8=alarm function when closed. 9=alarm function when open. 10=Appliance cleaning (pulse signal). 11=forced cooling at hot gas defrost, 12=night cover. 15=case shut down.
t01 -
1 1 1 1 1 1 1 1 1 1 0 hrs 23 hrs 0
t06
t11 -
1 1 1 1 1 1 1 1 1 1 0 min. 59 min. 0
t16
t07 1 1 1 1 1 1 1 1 1 1 0 hrs 23 hrs 0
t08 1 1 1 1 1 1 1 1 1 1 0 min. 59 min. 0
t45 1 1 1 1 1 1 1 1 1 1 1 day 31 day 1
t46 1 1 1 1 1 1 1 1 1 1 1 mon. 12 mon. 1
t47 1 1 1 1 1 1 1 1 1 1 0 year 99 year 0
o01 1 1 1 1 1 1 1 1 1 1 0 sec 600 sec 5
o02 1 1 1 1 1 1 1 1 1 1 0 21 0
20=Refrigerant alarm. 21= adaptiv liquid control at short circuited
Network address
On/Off switch (Service Pin message) IMPORTANT! o61 must be set prior to o04
o03 1 1 1 1 1 1 1 1 1 1 0 240 0
o04 1 1 1 1 1 1 1 1 1 1 0/Off 1/On 0/Off
(used at LON 485 and DANBUSS only)
Access code 1 (all settings) Used sensor type : 0=Pt1000, 1=Ptc1000, o06 1 1 1 1 1 1 1 1 1 1 0/Pt 1/Ptc 0/Pt
Readout of software version o08 1 1 1 1 1 1 1 1 1 1
Max hold time after coordinated defrost
Select signal for display view. S4% (100%=S4, 0%=S3)
Pressure transmitter working range – min. value
Pressure transmitter working range – max. value Refrigerant setting:
o05 1 1 1 1 1 1 1 1 1 1 0 100 0
o16 1 1 1 1 1 1 1 1 1 1 0 min. 360 min. 20
o17 1 1 1 1 1 1 1 1 0 % 100 % 100
o20 1 1 1 1 1 1 1 1 1 1 -1 bar 5 bar -1
o21 1 1 1 1 1 1 1 1 1 1 6 bar 200 bar 12
o30 1 1 1 1 1 1 1 1 1 1 0 42 0 1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13. 7=R13b1. 8=R23. 9=R500. 10=R503. 11=R114. 12=R142b. 13=User defined. 14=R32. 15=R227. 16=R401A. 17=R507. 18=R402A. 19=R404A. 20=R407C. 21=R407A. 22=R407B. 23=R410A. 24=R170. 25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270. 30=R417A. 31=R422A. 32=R413A. 33=R422D. 34=R427A. 35=R438A.
36=R513A. 37=R407F. 38=R1234ze. 39=R1234yf. 40=R448A. 41=R449A. 42=R452A
AK-CC 550A Instructions RI8NP702 © Danfoss 2018-09 9
Continued Code 1 2 3 4 5 6 7 8 9 10 Min. Max. Fac. Actual
Input signal on DI2. Function: (0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-signal). 5=ext. main switch 6=night operation 7=thermostat band changeover (activate r21). 8=alarm function when closed. 9=alarm function when open. 10=Appliance cleaning (pulse signal). 11=forced cooling at hot gas defrost.). 12=night cover, 13=coordinated defrost).
o37 1 1 1 1 1 1 1 1 1 1 0 21 0
15=case shut down. 20=Refrigerant alarm. 21= adaptiv
liquid control at short circuited Configuration of light function: 1=Light follows day /night
o38 1 1 1 1 1 1 1 1 1 4 1 operation, 2=Light control via data communication via ‘o39’, 3=Light control with a DI-input, 4=As "2", but light switch on and night cover will open if the network cut out for more than 15 minutes.
Activation of light relay (only if o38=2) On=light o39 1 1 1 1 1 1 1 1 0/Off 1/On 0/Off Rail heat On time during day operations
Rail heat On time during night operations
Rail heat period time (On time + Off time)
Appliance cleaning. 0=no Appliance cleaning. 1=Fans only. 2=All output Off.
Selection of EL diagram. See overview page 2 and 3
Download a set of predetermined settings. See overview page 7.
Access code 2 (partial access)
Replace the controllers factory settings with the present settings
Input signal on DI3. Function: (high voltage input) (0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-signal). 5=ext. main switch 6=night operation,
o41 1 1 1 1 1 1 1 0 % 100 % 100
o42 1 1 1 1 1 1 1 0 % 100 % 100
o43 1 1 1 1 1 1 1 6 min. 60 min. 10
*** o46 1 1 1 1 1 1 1 1 1 1 0 2 0
* o61 1 1 1 1 1 1 1 1 1 1 1 10 1 * o62 1 1 1 1 1 1 1 1 1 1 0 6 0
*** o64 1 1 1 1 1 1 1 1 1 1 0 100 0
o67 1 1 1 1 1 1 1 1 1 1 0/Off 1/On 0/Off
o84 1 1 1 1 1 1 1 1 1 1 0 21 0
7=thermostat band changeover (activate r21). 8=Not used. 9=Not used. 10=Appliance cleaning (pulse signal).
11=forced cooling at hot gas defrost, 12=night cover.
13=Not used. 14=Refrigeration stopped (forced closing)). 15=case shut down. 21= adaptiv liquid control at short circuited Rail heat control
o85 1 1 1 1 1 1 1 0 2 0 0=not used, 1=pulse control with timer function (o41 and o42), 2=pulse control with dew point function
Dew point value where the rail heat is minimum o86 1 1 1 1 1 1 1 -10°C 50°C 8 Dew point value where the rail heat is 100% on o87 1 1 1 1 1 1 1 -9°C 50°C 17 Lowest permitted rail heat effect in % o88 1 1 1 1 1 1 1 0 % 100 % 30 Time delay from "open door” refrigeration is started o89 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 30
Fan operation at stopped cooling (forced closing): 0= Stopped (defrost allowed) 1= Running (defrost allowed) 2= Stopped (defrost not allowed) 3= Running (defrost not allowed)
1=defrost stop temperature, 2=S6 temperature,
o90 1 1 1 1 1 1 1 1 1 1
o92 1 1 1 1 1 1 1 1 1 1 1 4 1
0 3 1
3=S5_B temperature (application 9), 4=S3B (application
10)
Display of temperature
o97 1 1 1 1 1 1 1 1 1 1 1 2 1
1= u56 Air temperature 2= u36 product temperature
Light and night blinds defined
o98 1 1 1 1 1 1 1 1 1 1 0 1 0
0: Light is switch off and night blind is open when the main switch is off 1: Light and night blind is independent of main switch
Configuration of alarm relay
P41 1 1 1 1 1 0 127 111
The alarm relay will be activated upon an alarm signal from the following groups: 1 - High temperature alarms 2 - Low temperature alarms 4 - Sensor error 8 - Digital input enabled for alarm 16 - Defrosting alarms 32 - Miscellaneous 64 - Injection alarms The groups that are to activate the alarm relay must be set by using a numerical value which is the sum of the groups that must be activated. (E.g.: a value of 5 will activate all high temperature alarms and all sensor error and 0 will cancel the relay function).
10 Instructions RI8NP702 © Danfoss 2018-09 AK-CC 550A
Continued Code 1 2 3 4 5 6 7 8 9 10 Min. Max. Fac. Actual
Service
Temperature measured with S5 sensor
Status on DI1 input. on/1=closed
u09 1 1 1 1 1 1 1 1 1 1 u10 1 1 1 1 1 1 1 1 1 1
Actual defrost time (minutes) u11 1 1 1 1 1 1 1 1 1 1
Temperature measured with S3 sensor
Status on night operation (on or off) 1=on
Temperature measured with S4 sensor
u12 1 1 1 1 1 1 1 1 1 1 u13 1 1 1 1 1 1 1 1 1 1
u16 1 1 1 1 1 1 1 1 1 1 Thermostat temperature u17 1 1 1 1 1 1 1 1 Run time of thermostat (cooling time) in minutes u18 1 1 1 1 1 1 1 1 1 1 Temperature of evaporator outlet temp. u20 1 1 1 1 1 1 1 1 1 1 Superheat across evaporator u21 1 1 1 1 1 1 1 1 1 1 Reference of superheat control u22 1 1 1 1 1 1 1 1 1 1 Opening degree of AKV valve ** u23 1 1 1 1 1 1 1 1 1 1 Evaporating pressure Po (relative) u25 1 1 1 1 1 1 1 1 1 1 Evaporator temperature To (Calculated) u26 1 1 1 1 1 1 1 1 1 1
Temperature measured with S6 sensor
u36 1 1 1 1 1 1 1 1 (product temperature)
Status on DI2 output. on/1=closed
Air temperature . Weighted S3 and S4
Measured temperature for alarm thermostat
Status on relay for cooling
Status on relay for fan
Status on relay for defrost
Status on relay for railheat
Status on relay for alarm
Status on relay for light
Status on relay for valve in suction line
Status on relay for compressor 2
Temperature measured with S5B sensor
Temperature measured with S3B sensor
Status on relay for hot gas- / drain valve ** u80 1 Status on relay for heating element in drip tray Status on relay for night blinds ** u82 1 Status on relay for defrost B ** u83 1 Status on relay for heat function
u37 1 1 1 1 1 1 1 1 1 1
u56 1 1 1 1 1 1 1 1 1 1
u57 1 1 1 1 1 1 1 1
** u58 1 1 1 1 ** u59 1 1 1 1 1 1 1 1 1 1 ** u60 1 1 1 1 1 1 1 1 1 ** u61 1 1 1 1 1 1 1 ** u62 1 1 1 1 1 ** u63 1 1 1 1 1 1 1 1 ** u64 1 ** u67 1
u75 1
u76 1
** u81 1
** u84 1 Readout of the actual rail heat effect u85 1 1 1 1 1 1 1 1: Thermostat 1 operating, 2: Thermostat 2 operating u86 1 1 1 1 1 1 1 1 1 1 Status on high voltage input DI3 u87 1 1 1 1 1 1 1 1 1 1 Readout of thermostats actual cut in value u90 1 1 1 1 1 1 1 1 1 1 Readout of thermostats actual cut out value u91 1 1 1 1 1 1 1 1 1 1 Readout of status on the adaptive defrost
U01 1 1 1 1 1 1 1 1 1 1 0: Off. Function is not activated and are zero set 1: Sensor error or S3/S4 are reversed. 2: Tuning is in progress 3: Normal 4: Light build-up of ice 5: Medium build-up of ice 6: Heavy build-up of ice
Number of defrosts carried out since the initial power
U10 1 1 1 1 1 1 1 1 1 1
up or since the resetting of the function Number of defrosts skipped since the initial power up
U11 1 1 1 1 1 1 1 1 1 1
or since the resetting of the function
*) Can only be set when regulation is stopped (r12=0) **) Can be controlled manually, but only when r12=-1 ***) With access code 2 the access to these menus will be limited
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you reconnect the supply voltage
Factory settings are indicated for standard units. Other code numbers have customized settings.
AK-CC 550A Instructions RI8NP702 © Danfoss 2018-09 11
Fault message
In an error situation the LED’s on the front will flash and the alarm relay will be activated. If you push the top button in this situation you can see the alarm report in the display. There are two kinds of error reports - it can either be an alarm occurring dur­ing the daily operation, or there may be a defect in the installation. A-alarms will not become visible until the set time delay has expired. E-alarms, on the other hand, will become visible the moment the error occurs. (An A alarm will not be visible as long as there is an active E alarm). Here are the messages that may appear:
Code / Alarm text via data communication
A1/--- High t.alarm High temperature alarm
A2/--- Low t. alarm Low temperature alarm
A4/--- Door alarm Door alarm
A5/--- Max hold time The ”o16” function is activated during
A10/--- Inject prob. Control problem
A11/--- No Rfg. sel. No refrigerant selected
A13/--- High temp S6Temperature alarm. High S6
A14/--- Low temp S6 Temperature alarm. Low S6
A15/--- DI1 alarm DI1 alarm
A16/--- DI2 alarm DI2 alarm
A45/--- Standby mode
A59/--- Case clean Case cleaning. Signal from DI input
AA2/ ---Refrig Leak A refrigerant leak detection signal is
AA3/--- CO2 alarm A refrigerant leak detection signal is
--- AD fault Error in the adaptive defrost function
--- AD Iced Evaporator is iced up. Reduction of
--- AD not defr. Defrost of evaporator is not
--- AD flashgas. Flash gas is formed at the valve
E1/--- Ctrl. error Faults in the controller
E6/--- RTC error Check clock
E20/--- Pe error Error on pressure transmitter Pe
E24/--- S2 error Error on S2 sensor 4
E25/--- S3 error Error on S3 sensor 4
E26/--- S4 error Error on S4 sensor 4
E27/--- S5 error Error on S5 sensor 4
E28/--- S6 error Error on S6 sensor 4
E34/ --- S3 error B Error on S3B sensor
E37/--- S5 error B Error on S5B sensor
---/--- Max Def.Time Defrost stopped based on time in-
Description
a coordinated defrost
Standby position (stopped refrigera­tion via r12 or DI input)
received
received and the selected refrigerant is CO2
air flow
satisfactory
stead of, as wanted, on temperature
Alarm relay groups (P41)
1
2
8
16
64
64
1
2
8
8
-
-
8
8
16
16
16
16
32
32
64
4
4
16
Operating status (Measurement)
The controller goes through some regulating situa­tions where it is just waiting for the next point of the regulation. To make these “why is nothing happening” situations visible, you can see an operating status on the display. Push briefly (1s) the upper button. If there is a status code, it will be shown on the display. The indi­vidual status codes have the following meanings:
Normal regulation S0 0
Waiting for end of the coordinated defrost S1 1
When the compressor is operating it must run for at least x minutes.
When the compressor is stopped, it must remain stopped for at least x minutes.
The evaporator drips off and waits for the time to run out S4 4
Refrigeration stopped by main switch. Either with r12 or a DI-input
Refrigeration stopped by thermostat S11 11
Defrost sequence. Defrost in progress S14 14
Defrost sequence. Fan delay — water attaches to the evaporator
Refrigeration stopped due to open ON input or stopped regulation
Door is open. DI input is open S17 17
Melt function in progress. Refrigeration is interrupted S18 18
Modulating thermostat control S19 19
Emergency cooling due to sensor error S20 20
Regulation problem in the injections function S21 21
Start-up phase 2. Evaporator being charged S22 22
Adaptive control S23 23
Start-up phase 1. Signal reliability from sensors is controlled
Manual control of outputs S25 25
No refrigerant selected S26 26
Case cleaning S29 29
Forced cooling S30 30
Delay on outputs during start-up S32 32
Heat function r36 is active S33 33
Case shutdown S45 45
Operation with adaptiv liquid control S48 48
Other displays:
The defrost temperature cannot be displayed. There is stop based on time
Defrost in progress / First cooling after defrost -d-
Password required. Set password PS
Regulation is stopped via main switch OFF
S2 2
S3 3
S10 10
S15 15
S16 16
S24 24
non
Ctrl. state: (Shown in all menu displays)
*) Emergency cooling will take effect when there is lack of signal from a defined S3
or S4 sensor or signal from the pressure transmitter is outside signal range. The regulation will continue with a registered average cutin frequency. There are two registered values – one for day operation and one for night operation.
Data communication
The importance of individual alarms can be defined with a setting. The setting must be carried out in the group "Alarm destinations"
Settings from System manager
Settings from AKM (AKM destination)
Log Alarm relay Send via
Non High Low-High
Network High 1 X X X X Middle 2 X X X Low 3 X X X Log only X Disabled
12 Instructions RI8NP702 © Danfoss 2018-09 AK-CC 550A
ADAP-KOOL®
Loading...