Danfoss Electronics AK-CC 210 Installation Guide

INSTRUCTIONS
AK-CC 210 (115 V)
084R8007
t
= 0 - +55°C, 32 - +131°F
amb
115 V a.c., 50/60 Hz
2.5 VA
10 V < U < 256 V
084R8007
CE (250 V a.c.) UL *** (240 V a.c.)
DO1. Refrigeration * 10 (6) A
DO2. Defrost * 10 (6) A
DO3. Fan or refrigeration 2 *
DO4. Alarm, light, rail heat or hotgas defrost *
* DO1 and DO2 are 16 A relays. DO3 and DO4 are 8 A relays. Max. load must be keept. ** Gold plating ensures make function with small contact loads *** UL-approval based on 30000 couplings
6 (3) A
4 (1) A Min. 100 mA**
10 A Resistive 5FLA, 30LRA
10 A Resistive 5FLA, 30LRA
6 A Resistive 3FLA, 18LRA 131 VA Pilot duty 4 A Resistive 131 VA Pilot duty
Coordinated defrost
Data communication
Type: Pt 1000 (1000 Ω /0°C ) /
Ptc 1000 (1000 Ω /25°C ) / NTC-M2020 (5000 Ω / 25°C)
LON RS485
MOD-bus
RI8MC65M 08-2011
o61 — Electrical connections
1 2
*)
*)
3 4
5 6
*)
*) *)
*)
7 8
9 10
*)
*)*)
*)
! ! !
2 Instructions RI8MC65M © Danfoss 8/2011 AK-CC 210
*) DI1, DI2: AU: Guld, Gold, Or, Oro l = max. 15 m
Setting:
1 Open parameter r12 and stop the regulation
2 Select electric connection based on the draw-
ings on page 2
3 Open parameter o61 and set the electric con-
nection number in it
4 Now select one of the preset settings from the
table on the right-hand side
5 Open parameter o62 and set the number for
the array of presettings
6 Open parameter r12 and start the regulation
7 Go through the survey of factory settings.
Make any necessary changes in the respective parameters.
8 For network. Set the address in o03 and then
transmit it to the gateway/system unit with setting o04.
English (°C)
Auxiliary table for settings (quick-setup)
Preset settings (o62) 1 2 3 4 5 6
Temperature (SP) Max. temp. setting (r02) Min. temp. setting (r03) Sensor signal for thermostat. S4% (r15) Alarm limit high (A13) Alarm limit low (A14) Sensor signal for alarm funct.S4% (A36) Interval between defrost (d03) Defrost sensor: 0=time, 1=S5, 2=S4 (d10) DI1 config. (o02) Sensor signal for display view S4% (017)
Defrost stop on
time
4°C 2°C -24°C 6°C 3°C -22°C 6°C 4°C -22°C 8°C 5°C -20°C 2°C 0°C -26°C 4°C 1°C -24°C
10°C 8°C -15°C 10°C 8°C -15°C
-5°C -5°C -30°C 0°C 0°C -30°C
6 h 6h 12h 8h 8h 12h
Case Room
Defrost stop
on S5
100% 0%
100% 0%
0 1 1 0 1 1
Case cleaning =10 Door function =3
100% 0%
Array 1-6: The settings in the grey fields will be changed
Defrost stop on
time
Defrost stop
on S5
Function Codes 1 2 3 4 5 6 7 8 9 10 Normal operation
Temperature (set point) --- -50.0°C 50.0°C 2.0°C
Thermostat
Differential *** r01 0.0 K 20.0K 2.0 K Max. limitation of setpoint setting *** r02 -49.0°C 50°C 50.0°C Min. limitation of setpoint setting *** r03 -50.0°C 49.0°C -50.0°C Adjustment of temperature indication r04 -20.0 K 20.0 K 0.0 K Temperature unit (°C/°F) r05 °C °F °C Correction of the signal from S4 r09 -10.0 K +10.0 K 0.0 K Correction of the signal from S3 r10 -10.0 K +10.0 K 0.0 K Manual service, stop regulation, start regulation (-1, 0, 1) r12 -1 1 0 Displacement of reference during night operation r13 -10.0 K 10.0 K 0.0 K Definition and weighting, if applicable, of thermostat sensors
- S4% (100%=S4, 0%=S3) The heating function is started a number of degrees below the thermostats cutout temperature Activation of reference displacement r40 r39 OFF ON OFF Value of reference displacement (activate via r39 or DI) r40 -50.0 K 50.0 K 0.0 K
Alarm
Delay for temperature alarm A03 0 min 240 min 30 min Delay for door alarm *** A04 0 min 240 min 60 min Delay for temperature alarm after defrost A12 0 min 240 min 90 min High alarm limit *** A13 -50.0°C 50.0°C 8.0°C Low alarm limit *** A14 -50.0°C 50.0°C -30.0°C Alarm delay DI1 A27 0 min 240 min 30 min Alarm delay DI2 A28 0 min 240 min 30 min Signal for alarm thermostat. S4% (100%=S4, 0%=S3) A36 0% 100% 100%
Compressor
Min. ON-time c01 0 min 30 min 0 min Min. OFF-time c02 0 min 30 min 0 min Time delay for cutin of comp.2 c05 0 sec 999 sec 0 sec Compressor relay 1 must cutin and out inversely (NC-function)
Defrost
Defrost method (none/EL/GAS/BRINE) d01 no bri EL Defrost stop temperature d02 0.0°C 25.0°C 6.0°C Interval between defrost starts d03 0 hours Max. defrost duration d04 0 min 180 min 45 min Displacement of time on cutin of defrost at start-up d05 0 min 240 min 0 min Drip off time d06 0 min 60 min 0 min Delay for fan start after defrost d07 0 min 60 min 0 min Fan start temperature d08 -15.0°C 0.0°C -5.0°C Fan cutin during defrost 0: Stopped 1: Running 2: Running during pump down and defrost Defrost sensor (0=time, 1=S5, 2=S4) d10 0 2 0 Pump down delay d16 0 min 60 min 0 min Drain delay d17 0 min 60 min 0 min Max. aggregate refrigeration time between two defrosts d18 0 hours 48 hours 0 hours Defrost on demand - S5 temperature’s permitted variation dur­ing frost build-up. On central plant choose 20 K (=off) Delay of hot gas injection d23 0 min 60 min 0 min
Fan
Fan stop at cutout compressor F01 no yes no Delay of fan stop F02 0 min 30 min 0 min Fan stop temperature (S5) F04 -50.0°C 50.0°C 50.0°C
Parameters EL-diagram number (page 2)
r15 0% 100% 100%
r36 -15.0 K -3.0 K -15.0 K
c30 0
d09 0 2 1
d19 0.0 K 20.0 k 20.0 K
Min.­value
OFF
Max.­value
1
ON
240 hours
Factory
setting
0
OFF
8 hours
Actual
setting
AK-CC 210 Instructions RI8MC65M © Danfoss 8/2011 3
Loading...
+ 5 hidden pages