* DO1 and DO2 are 16 A relays. DO3 and DO4 are 8 A relays. Max. load must be keept.
** Gold plating ensures make function with small contact loads
*** UL-approval based on 30000 couplings
6 (3) A
4 (1) A
Min. 100 mA**
10 A Resistive
5FLA, 30LRA
10 A Resistive
5FLA, 30LRA
6 A Resistive
3FLA, 18LRA
131 VA Pilot duty
4 A Resistive
131 VA Pilot duty
*) DI1, DI2: AU: Guld, Gold, Or, Oro l = max. 15 m
Setting:
1 Open parameter r12 and stop the regulation
2 Select electric connection based on the draw-
ings on page 2
3 Open parameter o61 and set the electric con-
nection number in it
4 Now select one of the preset settings from the
table on the right-hand side
5 Open parameter o62 and set the number for
the array of presettings
6 Open parameter r12 and start the regulation
7 Go through the survey of factory settings.
Make any necessary changes in the respective
parameters.
8 For network. Set the address in o03 and then
transmit it to the gateway/system unit with
setting o04.
English (°C)
Auxiliary table for settings
(quick-setup)
Preset settings (o62)123456
Temperature (SP)
Max. temp. setting (r02)
Min. temp. setting (r03)
Sensor signal for thermostat. S4% (r15)
Alarm limit high (A13)
Alarm limit low (A14)
Sensor signal for alarm funct.S4% (A36)
Interval between defrost (d03)
Defrost sensor: 0=time, 1=S5, 2=S4 (d10)
DI1 config. (o02)
Sensor signal for display view S4% (017)
Array 1-6: The settings in the grey fields will be changed
Defrost
stop on
time
Defrost stop
on S5
Function Codes 123456789 10
Normal operation
Temperature (set point)----50.0°C50.0°C2.0°C
Thermostat
Differential***r010.0 K20.0K2.0 K
Max. limitation of setpoint setting***r02-49.0°C50°C50.0°C
Min. limitation of setpoint setting***r03-50.0°C49.0°C-50.0°C
Adjustment of temperature indicationr04-20.0 K20.0 K0.0 K
Temperature unit (°C/°F)r05°C°F°C
Correction of the signal from S4r09-10.0 K +10.0 K0.0 K
Correction of the signal from S3r10-10.0 K +10.0 K0.0 K
Manual service, stop regulation, start regulation (-1, 0, 1)r12-110
Displacement of reference during night operationr13-10.0 K10.0 K0.0 K
Definition and weighting, if applicable, of thermostat sensors
- S4% (100%=S4, 0%=S3)
The heating function is started a number of degrees below the
thermostats cutout temperature
Activation of reference displacement r40r39OFFONOFF
Value of reference displacement (activate via r39 or DI)r40-50.0 K50.0 K0.0 K
Alarm
Delay for temperature alarmA030 min240 min 30 min
Delay for door alarm***A040 min240 min 60 min
Delay for temperature alarm after defrostA120 min240 min 90 min
High alarm limit***A13-50.0°C50.0°C8.0°C
Low alarm limit***A14-50.0°C50.0°C-30.0°C
Alarm delay DI1A270 min240 min 30 min
Alarm delay DI2A280 min240 min 30 min
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)A360%100%100%
Compressor
Min. ON-timec010 min30 min0 min
Min. OFF-timec020 min30 min0 min
Time delay for cutin of comp.2c050 sec999 sec0 sec
Compressor relay 1 must cutin and out inversely
(NC-function)
Defrost
Defrost method (none/EL/GAS/BRINE)d01nobriEL
Defrost stop temperatured020.0°C25.0°C6.0°C
Interval between defrost startsd030 hours
Max. defrost durationd040 min180 min 45 min
Displacement of time on cutin of defrost at start-upd050 min240 min0 min
Drip off timed060 min60 min0 min
Delay for fan start after defrostd070 min60 min0 min
Fan start temperatured08-15.0°C0.0°C-5.0°C
Fan cutin during defrost
0: Stopped
1: Running
2: Running during pump down and defrost
Defrost sensor (0=time, 1=S5, 2=S4)d10020
Pump down delayd160 min60 min0 min
Drain delayd170 min60 min0 min
Max. aggregate refrigeration time between two defrostsd180 hours 48 hours 0 hours
Defrost on demand - S5 temperature’s permitted variation during frost build-up. On central plant choose 20 K (=off)
Delay of hot gas injectiond230 min60 min0 min
Fan
Fan stop at cutout compressorF01noyesno
Delay of fan stopF020 min30 min0 min
Fan stop temperature (S5)F04-50.0°C50.0°C50.0°C
Actual temperature measurement for the HACCP functionh01
Last registered peak temperatureh10
Selection of function and sensor for the HACCP function. 0 = no
HACCP function. 1 = S4 used (maybe also S3). 2 = S5 used
Alarm limit for the HACCP functionh12-50.0°C50.0°C8.0°C
Time delay for the HACCP alarmh130 min. 240 min. 30 min.
Select signal for the HACCP function. S4% (100% = S4, 0% = S3)h140%100%100%
Real time clock
Six start times for defrost.
Setting of hours.
0=OFF
Six start times for defrost.
Setting of minutes.
0=OFF
Clock - Setting of hours***t070 hours 23 hours 0 hours
Clock - Setting of minute***t080 min59 min0 min
Clock - Setting of date***t451311
Clock - Setting of month***t461121
Clock - Setting of year***t470990
Miscellaneous
Delay of output signals after start-upo010 s600 s5 s
Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when
open. 3=door alarm when open. 4=defrost start (pulse-pressure). 5=ext.main switch. 6=night operation 7=change reference (activate r40). 8=alarm function when closed. 9=alarm
function when open. 10=case cleaning (pulse pressure).
11=forced cooling at hot gas defrost.
Network address (0=off)o0302400
On/Off switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04
Access code 1 (all settings)o0501000
Used sensor type (Pt /PTC/NTC)o06PtntcPt
Display step = 0.5 (normal 0.1 at Pt sensor)o15noyesno
Max hold time after coordinated defrosto160 min60 min20
Select signal for display view. S4% (100%=S4, 0%=S3)o170%100%100%
Input signal on DI2. Function:
(0=not used. 1=status on DI2. 2=door function with alarm when
open. 3=door alarm when open. 4=defrost start (pulse-pressure). 5=ext. main switch 6=night operation 7=change reference (activate r40). 8=alarm function when closed. 9=alarm
function when open. 10=case cleaning (pulse pressure).
11=forced cooling at hot gas defrost.). 12=coordinated defrost)
Configuration of light function (relay 4)
1=ON during day operation. 2=ON / OFF via data communication. 3=ON follows the DI-function, when DI is selected to door
function or to door alarm
Activation of light relay (only if o38=2)o39OFFONOFF
Rail heat On time during day operationso410%100%100
Rail heat On time during night operationso420%100%100
Rail heat period time (On time + Off time)o436 min60 min10 min
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output
Off.
Selection of EL diagram. See overview page 2*o611101
Download a set of predetermined settings. See overview
previous page.
Access code 2 (partly access)***o6401000
Save the controllers present settings to the programming key.
Select your own number.
Load a set of settings from the programming key (previously
saved via o65 function)
Replace the controllers factory settings with the present settings
Service
Status codes are shown on page 5S0-S33
Temperature measured with S5 sensor***u09
Status on DI1 input. on/1=closedu10
Temperature measured with S3 sensor***u12
Status on night operation (on or off) 1=closed***u13
Temperature measured with S4 sensor***u16
Thermostat temperatureu17
Read the present regulation referenceu28
Status on DI2 output. on/1=closedu37
Temperature shown on displayu56
Measured temperature for alarm thermostatu57
Status on relay for cooling**u58
Status on relay for fan**u59
Status on relay for defrost**u60
Status on relay for railheat**u61
Status on relay for alarm**u62
Status on relay for light**u63
Status on relay for valve in suction line**u64
Status on relay for compressor 2**u67
***o46020
*o62060
123456789 10
h11020
t01-t060 hours 23 hours 0 hours
t11-t160 min59 min0 min
o021110
o04OFFONOFF
o370120
o38131
o650250
o660250
o67OFFOnOFF
*) Can only be set when regulation is stopped (r12=0)
**) Can be controlled manually, but only when r12=-1
***) With access code 2 the access to these menus will be limited
Factory settings are indicated for standard units. Other code numbers have customized settings.
E 1Fault in controllerA 1High temperature alarmS0Regulating
E 6Change battery + check clockA 2Low temperature alarmS 1Waiting for end of the coordinated defrost
E 25S3 sensor errorA 4Door alarmS 2ON-time Compressor
E 26S4 sensor errorA 5Max. Hold timeS 3OFF-time Compressor
E 27S5 sensor errorA 15DI 1 alarmS 4Drip-off time
A 16DI 2 alarmS 10Refrigeration stopped by main switch
A 45Standby modeS 11Refrigeration stopped by thermostat
A 59Case cleaningS 14Defrost sequence. Defrosting
A 60HACCP alarmS 15Defrost sequence. Fan delay
S 17Door open (open DI input)
S 20Emergency cooling
S 25Manual control of outputs
S 29Case cleaning
S 30Forced cooling
S 32Delay of output at start-up
S33Heat function r36 is active
nonThe defrost temperature cannot be dis-
Make any necessary changes in the respective
parameters.
8 For network. Set the address in o03 and then
Auxiliary table for settings
(quick-setup)
Preset settings (o62)123456
Temperature (SP)
Max. temp. setting (r02)
Min. temp. setting (r03)
Sensor signal for thermostat. S4% (r15)
Alarm limit high (A13)
Alarm limit low (A14)
Sensor signal for alarm funct.S4% (A36)
Interval between defrost (d03)
Defrost sensor: 0=time, 1=S5, 2=S4 (d10)
DI1 config. (o02)
Sensor signal for display view S4% (017)
transmit it to the gateway/system unit with
setting o04.
Function Codes 123456789 10
Normal operation
Temperature (set point)----58.0°F122.0°F36.0°F
Thermostat
Differential***r010°F36.0°F36.0°F
Max. limitation of setpoint setting***r02-56.0°F122°F122°F
Min. limitation of setpoint setting***r03-58.0°F120°F-58.0°F
Adjustment of temperature indicationr04-4.0°F68.0°F32.0°F
Temperature unit (°C/°F)r05°C°F°F
Correction of the signal from S4r09-18.0°F +18.0°F0.0°F
Correction of the signal from S3r10-18.0°F +18.0°F0.0°F
Manual service, stop regulation, start regulation (-1, 0, 1)r12-110
Displacement of reference during night operationr13-18.0°F +18.0°F0.0°F
Definition and weighting, if applicable, of thermostat sensors
- S4% (100%=S4, 0%=S3)
The heating function is started a number of degrees below the
thermostats cutout temperature
Activation of reference displacement r40r39OFFONOFF
Value of reference displacement (activate via r39 or DI)r40-90.0°F90.0°F0.0°F
Alarm
Delay for temperature alarmA030 min240 min 30 min
Delay for door alarm***A040 min240 min 60 min
Delay for temperature alarm after defrostA120 min240 min 90 min
High alarm limit***A13-58.0°F122.0°F46.0°F
Low alarm limit***A14-58.0°F122.0°F -22.0°F
Alarm delay DI1A270 min240 min 30 min
Alarm delay DI2A280 min240 min 30 min
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)A360%100%100%
Compressor
Min. ON-timec010 min30 min0 min
Min. OFF-timec020 min30 min0 min
Time delay for cutin of comp.2c050 sec999 sec0 sec
Compressor relay 1 must cutin and out inversely
(NC-function)
Defrost
Defrost method (none/EL/GAS/BRINE)d01nobriEL
Defrost stop temperatured0232.0°F77.0°F43.0°F
Interval between defrost startsd030 hours
Max. defrost durationd040 min180 min 45 min
Displacement of time on cutin of defrost at start-upd050 min240 min0 min
Drip off timed060 min60 min0 min
Delay for fan start after defrostd070 min60 min0 min
Fan start temperatured085.0°F32.0°F23.0°F
Fan cutin during defrost
0: Stopped
1: Running
2: Running during pump down and defrost
Defrost sensor (0=time, 1=S5, 2=S4)d10020
Pump down delayd160 min60 min0 min
Drain delayd170 min60 min0 min
Max. aggregate refrigeration time between two defrostsd180 hours 48 hours 0 hours
Defrost on demand - S5 temperature’s permitted variation during frost build-up. On central plant choose 20 K (=off)
Delay of hot gas injectiond230 min60 min0 min
Fan
Fan stop at cutout compressorF01noyesno
Delay of fan stopF020 min30 min0 min
Fan stop temperature (S5)F04-58.0°F122.0°F 122.0°F
ParametersEL-diagram number (page 2)
r150%100%100%
r36-27.0°F-5.0°F-22.0°F
c300
d09021
d190°F36.0°F36.0° F
CaseRoom
Defrost stop
on S5
100%0%
100%0%
011011
Case cleaning =10Door function =3
100%0%
Array 1-6: The settings in the grey fields will be changed
Actual temperature measurement for the HACCP functionh01
Last registered peak temperatureh10
Selection of function and sensor for the HACCP function. 0 = no
HACCP function. 1 = S4 used (maybe also S3). 2 = S5 used
Alarm limit for the HACCP functionh12-58.0°F 122.0°F46.0°F
Time delay for the HACCP alarmh130 min. 240 min. 30 min.
Select signal for the HACCP function. S4% (100% = S4, 0% = S3)h140%100%100%
Real time clock
Six start times for defrost.
Setting of hours.
0=OFF
Six start times for defrost.
Setting of minutes.
0=OFF
Clock - Setting of hours***t070 hours 23 hours 0 hours
Clock - Setting of minute***t080 min59 min0 min
Clock - Setting of date***t451311
Clock - Setting of month***t461121
Clock - Setting of year***t470990
Miscellaneous
Delay of output signals after start-upo010 s600 s5 s
Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when
open. 3=door alarm when open. 4=defrost start (pulse-pressure). 5=ext.main switch. 6=night operation 7=change reference (activate r40). 8=alarm function when closed. 9=alarm
function when open. 10=case cleaning (pulse pressure).
11=forced cooling at hot gas defrost.
Network address (0=off)o0302400
On/Off switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04
Access code 1 (all settings)o0501000
Used sensor type (Pt /PTC/NTC)o06PtntcPt
Display step = 0.5 (normal 0.1 at Pt sensor)o15noyesno
Max hold time after coordinated defrosto160 min60 min20
Select signal for display view. S4% (100%=S4, 0%=S3)o170%100%100%
Input signal on DI2. Function:
(0=not used. 1=status on DI2. 2=door function with alarm when
open. 3=door alarm when open. 4=defrost start (pulse-pressure). 5=ext. main switch 6=night operation 7=change reference (activate r40). 8=alarm function when closed. 9=alarm
function when open. 10=case cleaning (pulse pressure).
11=forced cooling at hot gas defrost.). 12=coordinated defrost)
Configuration of light function (relay 4)
1=ON during night operation. 2=ON / OFF via data communication. 3=ON follows the DI-function, when DI is selected to door
function or to door alarm
Activation of light relay (only if o38=2)o39OFFONOFF
Rail heat On time during day operationso410%100%100
Rail heat On time during night operationso420%100%100
Rail heat period time (On time + Off time)o436 min60 min10 min
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output
Off.
Selection of EL diagram. See overview page 2*o611101
Download a set of predetermined settings. See overview
previous page.
Access code 2 (partly access)***o6401000
Save the controllers present settings to the programming key.
Select your own number.
Load a set of settings from the programming key (previously
saved via o65 function)
Replace the controllers factory settings with the present settings
Service
Status codes are shown on page 8S0-S33
Temperature measured with S5 sensor***u09
Status on DI1 input. on/1=closedu10
Temperature measured with S3 sensor***u12
Status on night operation (on or off) 1=closed***u13
Temperature measured with S4 sensor***u16
Thermostat temperatureu17
Read the present regulation referenceu28
Status on DI2 output. on/1=closedu37
Temperature shown on displayu56
Measured temperature for alarm thermostatu57
Status on relay for cooling**u58
Status on relay for fan**u59
Status on relay for defrost**u60
Status on relay for railheat**u61
Status on relay for alarm**u62
Status on relay for light**u63
Status on relay for valve in suction line**u64
Status on relay for compressor 2**u67
*) Can only be set when regulation is stopped (r12=0)
**) Can be controlled manually, but only when r12=-1
***) With access code 2 the access to these menus will be limited
Factory settings are indicated for standard units. Other code numbers have customized settings.
E 1Fault in controllerA 1High temperature alarmS0Regulating
E 6Change battery + check clockA 2Low temperature alarmS 1Waiting for end of the coordinated defrost
E 25S3 sensor errorA 4Door alarmS 2ON-time Compressor
E 26S4 sensor errorA 5Max. Hold timeS 3OFF-time Compressor
E 27S5 sensor errorA 15DI 1 alarmS 4Drip-off time
A 16DI 2 alarmS 10Refrigeration stopped by main switch
A 45Standby modeS 11Refrigeration stopped by thermostat
A 59Case cleaningS 14Defrost sequence. Defrosting
A 60HACCP alarmS 15Defrost sequence. Fan delay
S 17Door open (open DI input)
S 20Emergency cooling
S 25Manual control of outputs
S 29Case cleaning
S 30Forced cooling
S 32Delay of output at start-up